Attachment B - Basis of Design - Rental units.pdf

PDF 3 MB Posted

Attached to
Project Number: 516-22-601, Architect-Engineer (AE) - Install Alternate Connections - Steam and Chiller
Solicitation number
36C24823R0158
Issued by

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Bay Pines VA Chiller Plant #1 Rental Contingency

902 North Himes Avenue

Tampa, Florida, 33609

813-877-8251

800-966-8251 Toll Free

813-877-8252 Service Dispatch

800-966-8252 Toll Free Service Dispatch

813-877-8257 Fax www.tampabaytrane.com

Leon Cobarris Supervisory Engineering Technician Bay Pines VA 10000 Bay Pines Blvd.

Bay Pines, FL 33744

12/10/2021

Re: Rental Contingency Plan

Dear Mr. Cobarris

This letter is provided to assist Bay Pines VA with a HVAC rental contingency plan in the event the primary water cooled chillers in Plant #1 fail or both emergency air cooled chiller #6 & #7 fail.

Chiller Plant #1 Water Cooled Chillers

Chiller Plant #1 currently has 4 Trane centrifugal water cooled chillers. In the event of failure of all 4 centrifugal chillers a rental water cooled chiller(s) option could be implemented and tied into the chiller plant. Trane offers rental water cooled chillers ranging in tonnage from 225 – 1000 tons.

Depending on tonnage requirements at the time multiple water cooled chillers could be provided.

Rental water cooled chillers will need to be connected to the chiller plants supply and return chilled water piping as well as supply and return condenser water piping. The selection of the rental water cooled chiller will determine the power requirements. In the event Bay Pines VA does not have efficient house power to operate the rental chillers a rental diesel generator could be provided to power the rental units. All materials and labor to provide, install and operate the chillers can be provided.

Chiller Plant #1 Emergency Air Cooled Chiller #6 & #7

Chiller Plant #1 currently has two backup 200 ton air cooled chillers designated chiller #6 & #7 that provide backup to the operating rooms in the event the water cooled chillers in Plant #1 fail. In the event backup chiller #6 & #7 fail a rental air cooled chiller option could be implemented and tied into the chiller plant. Trane installed rental taps into the supply and return chilled water lines in chiller plant #1 in the event the backup air cooled chillers failed. Trane offers rental air cooled chillers up to 500 tons. The rental air cooled chiller would connect to the existing rental taps in chiller plant #1. The selection of the rental air cooled chiller will determine the power requirements. In the event Bay Pines VA does not have efficiency house power to operate the rental air cooled chiller a rental diesel generator could be provided to power the rental unit. All materials and labor to provide, install and operate the chiller can be provided.

Response Time

Trane rental services offers 24/7/365 local emergency service, engineering expertise and an expansive fleet of rental chillers, air conditioners, cooling towers, air handlers, portable heaters, power generators and ancillary products. We operate with the strength of a national company and the responsiveness of a dependable local shop.

Bay Pines VA Chiller Plant #1 Rental Contingency - 2 -

Rental Chiller / Generator Setup

Below is a general location where the rental equipment would be placed. Rental chillers are provided with a 48’ flatbed trailer. Chilled water hoses will be connected between the rental chiller(s) and chiller plant #1.

Thank you for allowing Trane to provide you with our recommendation. Bay Pines VA has been a valued customer for many years and we look forward to continuing our business relationship. Should you need any additional information, pricing or rental services please do not hesitate to call.

Respectfully Submitted, Derek Carter Senior Account Executive

Trane 902 North Himes Avenue Tampa, FL 33609 Work: 813-877-8251 Ext: 1238 Cell: 813-309-8604 Derek.carter@trane.com mailto:Derek.carter@trane.com

Leaving Chilled Water Temperature

Entering Condenser Water Temperature

85°F

44°F 1118

Contact Trane Rental Services for Low Temperature Applications 2Assuming a 10°F temperature change across both evaporator and condenser.

Minimum Standard Maximum

Evaporator Flow 520 gpm 2400 gpm 3815 gpm

Pressure Drop - 16.4 ft. H2O -

Condenser Flow 1407 gpm 3173 gpm 5160 gpm

Pressure Drop - 16.9 ft. H2O -

Maximum water side pressure is 300 psi (2.31 ft H2O = 1 psi)

Length 20 ft 10 in

Width 8 ft 6 in

Height 9 ft 9 in

Shipping Weight 38,900 lb

Operating Weight 46,855 lb

Lifting Device: Crane

Entering Condenser Water Temperature

85°F

44°F 1000

Contact Trane Rental Services for Low Temperature Applications 2Assuming a 10°F temperature change across both evaporator and condenser.

Minimum Standard Maximum

Evaporator Flow 520 gpm 2389 gpm 3815 gpm

Pressure Drop - 16.2 ft H2O -

Condenser Flow 1407 gpm 2826 gpm 5160 gpm

Pressure Drop - 12.2 ft H2O -

Maximum water side pressure is 300 psi (2.31 ft H2O = 1 psi)

Length 20 ft 7 in

Width 9 ft 11 in

Height 10 ft 4 in

Shipping Weight 39,000 lb

Operating Weight 46,955 lb

Lifting Device: Crane **Considered an oversized load. Permits required to ship.**

Entering Condenser Water Temperature

85°F

44°F 1000

Contact Trane Rental Services for Low Temperature Applications 2Assuming a 10°F temperature change across both evaporator and condenser.

Minimum Standard Maximum

Evaporator Flow 559 gpm 2390 gpm 4094 gpm

Pressure Drop - 14.75 ft H2O -

Condenser Flow 1404 gpm 2810 gpm 5147 gpm

Pressure Drop - 12.08 ft H2O -

Maximum water side pressure is 300 psi (2.31 ft H2O = 1 psi)

Length 21 ft 3 in

Width 9 ft 8 in

Height 11 ft 0 in

Shipping Weight 39,000 lb

Operating Weight 46,655 lb

**Considered an oversized load. Permits required to ship.**

Entering Condenser Water Temperature

85°F

44°F 1000

Contact Trane Rental Services for Low Temperature Applications 2Assuming a 10°F temperature change across both evaporator and condenser.

Minimum Standard Maximum

Evaporator Flow 555 gpm 2389 gpm 4067 gpm

Pressure Drop - 16.12 ft H2O -

Condenser Flow 1359 gpm 2816 gpm 4982 gpm

Pressure Drop - 12.63 ft H2O -

Maximum water side pressure is 300 psi (2.31 ft H2O = 1 psi)

Length 21 ft 1 in

Width 10 ft 3 in

Height 9 ft 11 in

Shipping Weight 38,000 lb

Operating Weight 45,721 lb

Entering Condenser Water Temperature

85°F

44°F 1000

Contact Trane Rental Services for Low Temperature Applications 2Assuming a 10°F temperature change across both evaporator and condenser.

Minimum Standard Maximum

Evaporator Flow 555 gpm 2400 gpm 4068 gpm

Pressure Drop - 15.58 ft H2O -

Condenser Flow 1359 gpm 3000 gpm 4983 gpm

Pressure Drop - 34.79 ft H2O -

Maximum water side pressure is 300 psi (2.31 ft H2O = 1 psi)

Length 20 ft 5 in

Width 9 ft 11 in

Height 10 ft 2 in

Shipping Weight 38,000 lb

Operating Weight 45,721 lb

Entering Condenser Water Temperature

95°F

44°F 1000

Contact Trane Rental Services for Low Temperature Applications 2Assuming a 10°F temperature change across both evaporator and condenser.

Minimum Standard Maximum

Evaporator Flow 609 gpm 2400 gpm 4440 gpm

Pressure Drop

(ft. H2O)

.86 18.7 65.57

Condenser Flow 1351 gpm 3000 gpm 4954 gpm

Pressure Drop

(ft. H2O)

4.81 20.15 49.68

Maximum water side pressure is 300 psi (2.31 ft H2O = 1 psi)

Length 22 ft 6 in

Width 9 ft 8 in

Height 10 ft 2 in

Shipping Weight 39,930 lbs

Operating Weight 47,263 lbs

Bay Pines VA Chiller Plant 1 Rental Contingency Plan
500 Ton AC Chiller spec sheet
1000 Ton WC Chiller spec sheet

File details come from the government source that posted it. Updated .