Attachment A Transformer list.xlsx
XLSX spreadsheet 21 KB Posted
- Solicitation number
- 1333ND25QNB190419
About this file
The file is an Excel spreadsheet (Attachment A Transformer List) detailing 122 transformers across multiple buildings and locations at the National Institute of Standards and Technology (NIST) Gaithersburg Campus. The comprehensive list includes detailed specifications for each transformer, such as building location, equipment ID, manufacturer, serial number, KVA rating, fluid type (predominantly SIL, FR3, and Biotemp), fluid capacity, and service requirements for oil quality, PCB analyses, and dissolved gas analysis (DGA). Transformer capacities range from 225 to 7500 KVA, with most units between 500 and 2000 KVA, and are located in various rooms, yards, and buildings including 101, 202, 205, 220, 245, 302, and others.
The associated federal contract opportunity (Solicitation 1333ND25QNB190419) is for Sitewide Transformer Inspection & Oil Analysis Services at the Gaithersburg Campus, prepared as a commercial services contract using FAR Part 12 and 13 procedures. NIST intends to award a single Firm-Fixed Price contract covering management, supervision, labor, materials, equipment, and supplies for transformer maintenance. The contract will include recurring services and a line item for additional services, with the contractor responsible for efficient, effective, and economical operation, scheduled and unscheduled maintenance, and minor repairs of the listed equipment systems.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
ATTACHMENT A
TRANSFORMER LIST AND SERVICES
| Building | Room | Equipment ID | Feeder | Manuf | Serial # | KVA | Fluid Type | Capacity (Gal) | Date Code | Transformer Service Requirement | ||
| Oil Quality | PCB Analyses | Dissolve Gas (DGA) |
| 101 A-W | A-23 | FA-2 | NA09313-002 | 1000 | SIL | 316 | 1 | 0 | 1 | ||||
| 101 A-W | A-23 | FB-2 | NA09313-001 | 1000 | SIL | 316 | 1 | 0 | 1 | ||||
| 101 A-W | A-23 | FD-2 | NA09313-003 | 1000 | SIL | 316 | 1 | 0 | 1 | ||||
| 101 C-W | C-08 | FA-2 | NA14359-002 | 750 | SIL | 241 | 1 | 0 | 1 | ||||
| 101 C-W | C-08 | FB-2 | NA14359-001 | 750 | SIL | 241 | 1 | 0 | 1 | ||||
| 101 C-W | C-08 | FD-2 | NA14359-003 | 750 | SIL | 241 | 1 | 0 | 1 | ||||
| 202 | A-142 | FA-1 | 120191 | 500 | Retrofilled w/ SIL | 288 | 1 | 1 | 1 | ||||
| 202 | A-142 | FB-1 | 120190 | 500 | Retrofilled w/ SIL | 288 | 1 | 1 | 1 | ` | |||
| 202 | A-142 | FC-1 | 120192 | 500 | Retrofilled w/ SIL | 288 | 1 | 1 | 1 | ||||
| 205 | FB-1 | 12JC577500001 | 750 | SIL | 1 | 0 | 1 | ||||||
| 205 | FC-1 | 12JC577510001 | 750 | SIL | 1 | 0 | 1 | ||||||
| 205 | 202 NT-2 | FB-1 | PFC0241 | 300 | SIL | ` | 1 | 0 | 1 | ||||
| 205 | 202 NT-1 | FC-1 | PFC0242 | 300 | SIL | 1 | 0 | 1 | |||||
| 205 | Yard | 202 NT-4 | FB-1 | PB07587-001 | 1500 | SIL | 1 | 0 | 1 | ||||
| 205 | Yard | 202 NT-3 | FC-1 | PB07586-001 | 1500 | SIL | 1 | 0 | 1 | ||||
| 206 | 101 | FA-1 | 4176720 | 300 | Retrofilled w/ SIL | 200 | 1 | 1 | 1 | ||||
| 206 | 101 | FB-1 | 4176719 | 300 | Retrofilled w/ SIL | 200 | 1 | 1 | 1 | ||||
| 206 | 101 | FC-1 | 4176721 | 300 | Retrofilled w/ SIL | 200 | 1 | 1 | 1 | ||||
| 220 | 500 | FA-2 | 3637847 | 1000 | Retrofilled w/ SIL | 275 | 1 | 1 | 1 | ||||
| 220 | 500 | FB-2 | 3637855 | 1000 | Retrofilled w/ SIL | 275 | 1 | 1 | 1 | ||||
| 220 | 500 | FD-2 | 3637849 | 1000 | Retrofilled w/ SIL | 275 | 1 | 1 | 1 | ||||
| 221 | 500 | FB-3 | CH | NA13954-003 | 1000 | SIL | 275 | 1 | 0 | 1 | |||
| 221 | 500 | FC-3 | CH | NA13954-002 | 1000 | SIL | 275 | 1 | 0 | 1 | |||
| 221 | 500 | FD-3 | CH | NA13954-001 | 1000 | SIL | 275 | 1 | 0 | 1 | |||
| 221 C-W | C-09 | FB-3 | 3639922 | 300 | Retrofilled w/ SIL | 200 | 1 | 1 | 1 | ||||
| 221 C-W | C-09 | FC-3 | 3639923 | 300 | Retrofilled w/ SIL | 200 | 1 | 1 | 1 | ||||
| 221 C-W | C-09 | FD-3 | 3639924 | 300 | Retrofilled w/ SIL | 200 | 1 | 1 | 1 | ||||
| 222 | 500 | FA-2 | 3637845 | 750 | Retrofilled w/ SIL | 248 | 1 | 1 | 1 | ||||
| 222 | 500 | FB-2 | 3637844 | 750 | Retrofilled w/ SIL | 248 | 1 | 1 | 1 | ||||
| 222 | 500 | FD-2 | 3637843 | 750 | Retrofilled w/ SIL | 248 | 1 | 1 | 1 | ||||
| 223 | 500 | 223 NTB | FB-3 | CH | AN00227-004 | 1000 | FRJ | 275 | 1 | 0 | 1 | ||
| 223 | 500 | 223 NTC | FC-3 | CH | AN00227-006 | 1000 | FRJ | 275 | 1 | 0 | 1 | ||
| 223 | 500 | 223 NTD | FD-3 | CH | AN00227-005 | 1000 | FRJ | 275 | 1 | 0 | 1 | ||
| 224 | 500 | FB-3 | 3637840 | 750 | Retrofilled w/ SIL | 248 | 1 | 1 | 1 | ||||
| 224 | 500 | FC-3 | 3637841 | 750 | Retrofilled w/ SIL | 248 | 1 | 1 | 1 | ||||
| 224 | 500 | FD-3 | 3637842 | 750 | Retrofilled w/ SIL | 248 | 1 | 1 | 1 | ||||
| 225 | 500 | FA-2 | NA12499-002 | 1000 | SIL | 275 | 1 | 0 | 1 | ||||
| 225 | 500 | FB-2 | NA12499-003 | 1000 | SIL | 275 | 1 | 0 | 1 | ||||
| 225 | 500 | FD-2 | NA12499-001 | 1000 | SIL | 275 | 1 | 0 | 1 | ||||
| 226 | 500 | FB-3 | NA16077-001 | 1500 | SIL | 447 | 1 | 0 | 1 | ||||
| 226 | 500 | FC-3 | NA16077-002 | 1500 | SIL | 447 | 1 | 0 | 1 | ||||
| 226 | 500 | FD-3 | NA16077-003 | 1500 | SIL | 447 | 1 | 0 | 1 | ||||
| 227 | FD-2 | ABB | NAB2199-0003 | 2000 | SIL | 1 | 0 | 1 | |||||
| 227 | FB-2 | ABB | NAB2199-0002 | 2000 | SIL | 1 | 0 | 1 | |||||
| 227 | FA-2 | ABB | NAB2199-0001 | 2000 | SIL | 1 | 0 | 1 | |||||
| 230 | B-02 | FB-3 | CH | NA13326-003 | 750 | SIL | 277 | 1 | 0 | 1 | |||
| 230 | B-02 | FC-3 | CH | NA13326-001 | 750 | SIL | 277 | 1 | 0 | 1 | |||
| 230 | B-02 | FD-3 | CH | NA13326-002 | 750 | SIL | 277 | 1 | 0 | 1 | |||
| 230 | B-02 | FA-2 | CH | SB13327-001 | 2000 | SIL | 597 | 1 | 0 | 1 | |||
| 231 | B-32 | FD-3 | CH | NA12499-004 | 1000 | SIL | 355 | 1 | 0 | 1 | |||
| 231 | B-32 | FC-3 | CH | NA12499-005 | 1000 | SIL | 355 | 1 | 0 | 1 | |||
| 231 | B-32 | FB-3 | CH | NA12999-006 | 1000 | SIL | 355 | 1 | 0 | 1 | |||
| 233 | HV room | FB-3 | CH | NA34152-002 | 500 | Biotemp | 1 | 0 | 1 | ||||
| 233 | HV room | FC-3 | CH | NA34152-003 | 500 | Biotemp | 1 | 0 | 1 | ||||
| 233 | HV room | FD-3 | CH | NA34152-001 | 500 | Biotemp | 1 | 0 | 1 | ||||
| 233 | Parking lot | FB-3 | 4183161 | 225 | Retrofilled w/ SIL | 147 | 1 | 1 | 1 | ||||
| 233 | Parking lot | FC-3 | 4183160 | 225 | Retrofilled w/ SIL | 147 | 1 | 1 | 1 | ||||
| 233 | Parking lot | FD-3 | 4183162 | 225 | Retrofilled w/ SIL | 147 | 1 | 1 | 1 | ||||
| 235 | B-100 | FA-1 | NA10194-001 | 2000 | SIL | 421 | 1 | 0 | 1 | ||||
| 235 | B-100 | FB-1 | NAI0l94-002 | 2000 | SIL | 421 | 1 | 0 | 1 | ||||
| 235 | FC-1 | NA10194-003 | 2000 | SIL | 284 | 1 | 0 | 1 | |||||
| 235 | Yard | FA-1 | NA34350-001 | 1500 | Biotemp | 1 | 0 | 1 | |||||
| 235 | Yard | FB-1 | NA34350-002 | 1500 | Biotemp | 1 | 0 | 1 | |||||
| 235 | Yard | FC-1 | NA34350-003 | 1500 | Biotemp | 1 | 0 | 1 | |||||
| 245 | T6 | Eaton | AN00182-001 | 1500 | FR3 | 1 | 0 | 1 | |||||
| 245 | Eaton | AN00183-002 | 500 | FR3 | 1 | 0 | 1 | ||||||
| 245 | Eaton | AN00182-003 | 1500 | FR3 | 1 | 0 | 1 | ||||||
| 245 | Eaton | AN00182-002 | 1500 | FR3 | 1 | 0 | 1 | ||||||
| 245 | Eaton | AN00183-001 | 500 | FR3 | 1 | 0 | 1 | ||||||
| 245 | Eaton | AN00183-003 | 500 | FR3 | 1 | 0 | 1 | ||||||
| 245 B-W | B-30 | FA-2 | 7018106 | 1000 | Retrofilled | 316 | 1 | 1 | 1 | ||||
| 245 B-W | B-30 | FB-2 | 7018107 | 1000 | Retrofilled | 316 | 1 | 1 | 1 | ||||
| 245 B-W | B-30 | FD-2 | 7018108 | 1000 | Retrofilled | 316 | 1 | 1 | 1 | ||||
| 245 B-W | B-30 | FA-2 | 7018088 | 500 | Retrofilled | 240 | 1 | 1 | 1 | ||||
| 245-B-W | B-30 | FB-2 | 7018087 | 500 | Retrofilled | 240 | 1 | 1 | 1 | ||||
| 245 B- W | B-30 | FD-2 | 7018086 | 500 | Retrofilled | 240 | 1 | 1 | 1 | ||||
| 245 | NT B7 | WestH | 63K10667 | 500 | FR3? | 1 | 0 | 1 | |||||
| 245 | Eaton | AN00205-003 | 1000 | FR3 | 1 | 0 | 1 | ||||||
| 245 | Eaton | AN00205-001 | 1000 | FR3 | 1 | 0 | 1 | ||||||
| 245 | Eaton | AN00205-002 | 1000 | FR3 | 1 | 0 | 1 | ||||||
| 245 | Eaton | AN00206-003 | 1000 | FR3 | 1 | 0 | 1 | ||||||
| 245 | Eaton | AN00206-001 | 1000 | FR3 | 1 | 0 | 1 | ||||||
| 245 | Eaton | AN00206-002 | 1000 | FR3 | 1 | 0 | 1 | ||||||
| 301 | A-141 | FB-2 | 7018120 | 750 | Retrofilled | 241 | 1 | 1 | 1 | ||||
| 301 | A-141 | FC-3 | 7018119 | 750 | Retrofilled | 241 | 1 | 1 | 1 | ||||
| 301 | A-141 | FD-3 | 7018118 | 750 | Retrofilled | 241 | 1 | 1 | 1 | ||||
| 302 | Yard | 302 Co-Gen | FC-9 | 447500A083-C582A | 7500 | FR3 | 1 | 0 | 1 | ||||
| 302 | 302-VSP | 302-NT-11 | West | PBA3778-0101 | 2500 | SIL | 1 | 0 | 1 | ||||
| 302 | 302-VSP | 302-NT-XX | West | PBA3778-0102 | 2500 | SIL | 1 | 0 | 1 | ||||
| 302 | Yard | FC-1 | CH | NA12388-002 | 1500 | SIL | 1 | 0 | 1 | ||||
| 302 | Yard | FB-1 | CH | NA12388-003 | 1500 | SIL | 1 | 0 | 1 | ||||
| 302 | Yard | FA-1 | CH | NA12388-001 | 1500 | SIL | 1 | 0 | 1 | ||||
| 302 | Yard | FD-7 | ABB | SEB3846-003T | 3000 | SIL | 1 | 0 | 1 | ||||
| 302 | FB-5 | ABB | SEB3846-002T | 3000 | SIL | 1 | 0 | 1 | |||||
| 302 | FA-4 | ABB | SEB3846-004T | 3000 | SIL | 1 | 0 | 1 | |||||
| 302 | FA-8 | WEST | SBA7344-0101 | 2500 | SIL | 1 | 0 | 1 | |||||
| 302 | FC-6 | ABB | SEB3846-001T | 3000 | SIL | 1 | 0 | 1 | |||||
| 302 | FC-5 | WEST | SBA7344-0102 | 2500 | SIL | 1 | 0 | 1 | |||||
| 304 | B-16 | FB-2 | 7018116 | 750 | Retrofilled w/ SIL | 241 | 1 | 1 | 1 | ||||
| 304 | B-16 | FC-3 | 7018117 | 750 | Retrofilled w/ SIL | 241 | 1 | 1 | 1 | ||||
| 304 | B-16 | FD-3 | 7018115 | 750 | Retrofilled w/ SIL | 241 | 1 | 1 | 1 | ||||
| 305 | AUL | FA-6 | ABB | NAB4334-001T | 1500 | Retrofilled w/ SIL | 418 | 1 | 1 | 1 | |||
| 305 | AUL | FB-6 | ABB | NAB4334-002T | 1500 | Retrofilled w/ SIL | 418 | 1 | 1 | 1 | |||
| 305 | AUL | FD-6 | ABB | NAB4334-003T | 1500 | Retrofilled w/ SIL | 418 | 1 | 1 | 1 | |||
| 316 | FD-8 | CH | 0959001651 | 2500? | FR3 | 1 | 0 | 1 | |||||
| 316 | FD-6 | CH | NIST-316-FD6 | 2000 | FR3 | 1 | 0 | 1 | |||||
| 316 | FB6 | CH | 10JC505540002 | 2000 | FR3 | 1 | 0 | 1 | |||||
| AML B215 | NT-FA7 | FA-7 | NA09329-001 | 2000 | SIL | 1 | 0 | 1 | |||||
| AML B215 | NT-FB7 | FB-7 | NA09329-002 | 2000 | SIL | 1 | 0 | 1 | |||||
| AML B215 | NT-FC7 | FC-7 | NA09329-003 | 2000 | SIL | 1 | 0 | 1 | |||||
| AML B215 | NT-FA7-2 | FA-7 | NA09329-004 | 2000 | SIL | 1 | 0 | 1 | |||||
| AML B215 | NT-FB7-2 | FB-7 | NA09329-005 | 2000 | SIL | 1 | 0 | 1 | |||||
| AML B215 | NT-FC7-2 | FC-7 | NA09329-006 | 2000 | SIL | 1 | 0 | 1 | |||||
| AML B215 | NT-FA7-3 | FA-7 | NA09329-008 | 2000 | SIL | 1 | 0 | 1 | |||||
| AML B215 | NT-FB7-3 | FB-7 | NA09329-009 | 2000 | SIL | 1 | 0 | 1 | |||||
| AML B215 | NT-FC7-3 | FC-7 | NA09329-007 | 2000 | SIL | 1 | 0 | 1 | |||||
| AML B215 | NT-FA7-4 | FA-7 | NA09330-001 | 2000 | SIL | 1 | 0 | 1 | |||||
| AML B215 | NT-FB7-4 | FB-7 | NA09330-002 | 2000 | SIL | 1 | 0 | 1 | |||||
| AML B215 | NT-FC7-4 | FC-7 | NA09330-003 | 2000 | SIL | 1 | 0 | 1 | |||||
| AML B215 | NT-FA7-5 | FA-7 | NA09330-004 | 2000 | SIL | 1 | 0 | 1 | |||||
| AML B215 | NT-FB7-5 | FB-7 | NA09330-005 | 2000 | SIL | 1 | 0 | 1 | |||||
| AML B215 | NT-FC7-5 | FC-7 | NA09330-006 | 2000 | SIL | 1 | 0 | 1 | |||||
| Total | 122 | 36 | 122 |
| Transformer Oil Analyses | No. of Oil Samples |
| Oil Quality | 122 |
| PCB | 36 |
| DGA | 122 |