Attachment_A_-_Drawings.pdf
PDF 10 MB Posted
- Attached to
- EROS Construction Services Federal contract opportunity
- Solicitation number
- 140G0123R0007
About this file
This document announces a federal solicitation for construction services. The U.S. Geological Survey is seeking proposals for EROS Construction Services between $1,000,000 to $5,000,000 through a total small business set-aside request for proposal. Interested small businesses registered in the System for Award Management that can meet the requirement are invited to electronically submit proposals by April 7, 2023. A pre-proposal site visit will be held on March 23, 2023 at the USGS in Sioux Falls, South Dakota, with questions due by March 28, 2023. The solicitation contains a statement of work, instructions, wage determination, clauses and attachments, and can be viewed at https://www.sam.gov using solicitation number 140G0123R0007.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| EROS_Cooling_Towers_Questions_and_Answers_0002.pdf | ||
| Sol_140G0123R0007_Amd_0002.pdf | ||
| Sol_140G0123R0007_Amd_0001.pdf | ||
| Attachment_F_-_Certification_for_Payment_(construction).pdf | ||
| Attachment_C_-_Release_of_Claims.doc | DOC document | |
| Attachment_B_-_Specifications.pdf | ||
| RFP_140G0123R0007_Sections_B-M_Final_Open_Market.pdf | ||
| Attachment_K_-_Past_Performance_Information.docx | DOCX document | |
| Attachment_G_-_DOL_Wage_Determination.pdf | ||
| Attachment_E_-_Payrolls_(WH-347).pdf | ||
| Attachment_L_-_Site_Visit_Security_Document.docx | DOCX document | |
| Attachment_J_-_Bid_Bond_SF_24.pdf | ||
| Attachment_I_-_Payment_Bond_SF_25A.pdf | ||
| Attachment_H_-_Performance_Bond_SF_25.pdf | ||
| Attachment_D_-_Nondisclosure_Agreement.doc | DOC document | |
| Sol_140G0123R0007.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Y#.#
X
X X
X
X
Y#.#
X
Y#.#
Z
Z
LEVEL
#'-##" AFF
J1
123A
X X
Room name
A100
A.F.F.
X
1'-0"
TRUE
Partition Type
Door Tag
Window Tag
Keyed Note
Ceiling Tag X = Material
Floor Transition Tag X = Material
Control Point
Revision Tag
Centerline Mark
Existing Construction shown Halftone
Demolished Items shown Dashed
New Construction shown Solid
Elevation Mark X = Elevation Number Y#.# = Sheet Number
North Arrow & True North Indicator
Section Mark X = Elevation Number Y#.# = Sheet Number
Detail Mark X = Elevation Number Y#.# = Sheet Number
Room Tag XXX = Room Number
Detail / Plan Callout X = Elevation Number Y#.# = Sheet Number
Elevation Datum
New Column Line
Existing Column Line
### X
Y#.#
SIM
123A
02.03
Refer to Partition Type Sheet
Sioux Falls
USGS Earth Resources
Observation and
Science Center29
USGS Earth Resources
Observation and Science Center
252nd Street th
A v e n u e
47914 252nd Street Sioux Falls, SD 57198
Approx. Area of Work
N
P ro je ct
Project No.
1 Memorial Dr, Suite 1800 St. Louis, MO 63102
Main: 314.621.4343 Fax: 314.621.0261 fox@fox-arch.com www.fox-arch.com
S he et T itl e
Issued for Construction
Sheet No.
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments of service or other documents not exhibiting this seal shall not be considered prepared by this architect. This architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawings and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Not To ScaleIndex To Drawings Location Plan
SENSATIVE BUT UNCLASSIFIED (SBU)
PROPERTY OF THE
UNITED STATES GOVERNMENT.
COPYING, DISSEMINATION, OR
DISTRIBUTION OF THIS DOCUMENT
TO UNAUTHORIZED RECIPIENTS IS
PROHIBITED
Do not remove this notice Properly destroy or return documents when no longer needed.
South Dakota Certificate of Authority No.: 0002868189
C
U se rs \z fo pp e\ D oc um en ts
\1
6.
U
S G
S S
D E
R O
S
P ha se
F lu id C oo le rs zf op pe fo x-ar ch
.c om
.r vt
6/12/2020 12:14:03 PM
C ov er S he et
CS0.01
P ha se I:
E R
O S
F lu id C oo le rs D es ig n S er vi ce s
1936.00
B
ID
D O
C U
M
EN
TS
06/12/2020
2n d
S tr ee t
S io ux F al ls
, S D
MEP Engineer SSC Engineering Contact: Ethan Schmitt
Structural Engineer SSC Engineering Contact: Michael Vande Velde
Project No: 1936.00
Project Issue Date: 06/12/2020
47914 252nd Street Sioux Falls, SD 57198
Phase I: 1996 Cooling Towers
BID DOCUMENTS
Architect Fox Architects Contact: Zach Foppe
Owner US Geological Survey Contact: Jesse Boyer
Owner
US Geological Survey
47914 252nd Street
Soiux Falls, SD 57198
605-594-2644
Contact: Jesse Boyer jboyer@usgs.gov
Architect
Fox Architects
1 Memorial Dr STE. 1800
St. Louis, MO 63102
314-621-4343
Contact: Zach Foppe zfoppe@fox-arch.com
SSC Engineering
18207 Edison Ave.
St Louis, MO 63005
636-530-7770
Contact: Ethan Schmitt eschmitt@sscengineering.com
MEP Engineer Structural Engineer
SSC Engineering
18207 Edison Ave.
St. Louis, MO 63005
636-530-7770
Contact: Michael Vande Velde mvandevelde@sscengineering.com
PORT PORTABLE
PREFAB PREFABRICATED
PREFIN PREFINISHED
PROP PROPERTY
PT PAINT
PTN PARTITION
PTWD PRESSURE TREATED WOOD
QTR QUARTER
QTY QUANTITY
R RADIUS
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RDR READER
RECES RECESSED
RECT RECTANG(LE)(ULAR)
REF REFER(ENCE)
REFL REFLECTED
REFR REFRIGERATOR
REINF REINFORCED(D)(ING)(MENT)
REQD REQUIRED
REV REVISION
RFG ROOFING
RL ROOF LEADER
RLG RAILING
RM ROOM
RO ROUGH OPENING
RTU ROOF TOP UNIT
SC SOLID CORE
SCHED SCHEDULE
SCR SCRIBE
SECUR SECURITY
SF SQUARE FEET
SG SINGLE
SHTHG SHEATHING
SIM SIMILAR
SK SINK
SLNT SEALANT
SM SHEET METAL
SPEC SPECIFICATIONS
SQ SQUARE
SSM SOLID SURFACE MATERIAL
SST STAINLESS STEEL
STD STANDARD
STL STEEL
STRUCT STRUCTURAL
SURF SURFACE
SUSP SUSPENDED
SYS SYSTEM(S)
T TREAD
T&G TOUNGUE AND GROOVE
TD TRENCH DRAIN
TEL TELECOM
TGL TEMPERED GLASS
THK THICK
TLT TOILET
TOC TOP OF CONCRETE
TOJ TOP OF JOIST
TOS TOP OF STEEL
TOW TOP OF WALL
TRTD TREATED
TYP TYPICAL
UNFIN UNDERLAYMENT
UNO UNLESS NOTED OTHERWISE
UR URINAL
UTIL UTILITY
VAR VARI(ES)(ATION)
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VTR VENT THROUGH ROOF
W WIDTH
W/ WITH
W/O WITHOUT
WB WOOD BASE
WBL WOOD BLOCKING
WC WATER CLOSET
WD WOOD
WDW WINDOW
WO WHERE OCCURS
WP WATERPROOFING
WT WEIGHT
YD YARD
FURN FURNITURE
FWC FABRIC WALL COVERING
FXD FIXED
FXTR FIXTURE
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GFRC GLASS FIBER REINFORCED
CONCRETE
GL GLASS
GR GRAD(E)(ING)
GSB GYPSUM SHEATHING
BOARD
GT GROUT
GWB GYPSUM WALL BOARD
GYP GYPSUM
HB HOSE BIBB
HD HEAD
HDW HARDWARE
HDWD HARDWOOD
HM HOLLOW METAL
HO HOLD OPEN
HOR HORIZONTAL
HT HEIGHT
HVAC HEATING, VENTILATIING,
AND AIR CONDITIONING
ID INSIDE DIAMETER
IF INSIDE FACE
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
INV INVERT
JAN JANITOR
JT JOINT
KB KNEE BRACE
KIT KITCHEN
LAB LABORATORY
LAV LAVATORY
LB POUND
LF LINEAR FEET
LP LOW POINT
LT LIGHT
LVR LOUVER
MATL MATERIAL
MAX MAXIMUM
MD METAL DECK
MDF MEDIUM DENSITY
FIBERBOARD
MECH MECHANICAL
MED MEDIUM
MEMB MEMBRANE
MEZZ MEZZANINE
MFD MANUFACTURED
MFR MANUFACTURER
MGT MANAGEMENT
MIN MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MLWK MILLWORK
MO MASONRY OPENING
MTD MOUNTED
MTL METAL
MW MICROWAVE
NA NOT APPLICABLE
NIC NOT IN CONTRCT
NO NUMBER
NOM NOMINAL
NOMINAL
NS NARROW STILE
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OF OUTSIDE FACE
OHD OVERHEAD DOOR
OPNG OPENING(S)
OPP OPPOSITE
OPT OPTIONAL
ORD OVERFLOW ROOF DRAIN
OVFL OVERVLOW
PBD PARITICLE BOARD
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
PNL PANEL
& AND
ADJ ADJUSTABLE
ADJC ADJACENT
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
APC ACOUSTICAL PANEL
CEILING
APPL APPLIANCE
ARCH ARCHITECT(URAL)
ASSY ASSEMBLY
AUTO AUTOMATIC
AVG AVERAGE
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BOD BOTTOM OF DECK
BR BRICK
BTWN BETWEEN
BU BUILT UP
CAB CABINET
CEM CEMENT(ITIOUS)
CER CERAMIC
CIP CAST-IN-PLACE
CL CENTERLINE
CLG CEILING
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
COILG COILING
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONSTR CONSTRUCTION
CONT CONTINUOUS(ATION)
CONTR CONTRACT(OR)
CPT CARPET
CSJ CONSTRUCTION JOINT
CSWK CASEWORK
CT CERAMIC TILE
D DEEP, DEPTH
DEMO DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DIV DIVISION, DIVIDE
DN DOWN
DR DOOR
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
EA EACH
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
ENGR ENGINEER(ED)
ENTR ENTRANCE
EPB ELECTRICAL PANEL BOARD
EQ EQUAL
EQUIP EQUIPMENT
ETC ETCETERA
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXT EXTERIOR
FAB FABRIC
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER AND
CABINET
FHC FIRE HOSE AND CABINET
FIN FINISH
FLR FLOOR(ING)
FP FIRE PROTECTION, FIRE
PROOFING
FR FIRE RAT(ING)(ED)
FRMG FRAMING
FRP FIBERGLASS REINFORCED
PANEL
FTG FOOTING
FTWD FIRE TREATED WOOD
Abbreviations List Symbol Legend
SENSATIVE BUT UNCLASSIFIED (SBU)
PROPERTY OF THE
UNITED STATES GOVERNMENT
COPYING, DISSEMINATION, OR
DISTRIBUTION OF THIS DOCUMENT
TO UNAUTHORIZED RECIPIENTS IS PROHIBITED
Do not remove this notice Properly destroy or return documents when no longer needed.
No. Name
CS0.01 Cover Sheet
S0.1 Structural General Notes
S0.2 Structural General Notes & Typical Details
S1.1 Structural Floor Framing Plan
A1.21 Architectural Floor Plans
E0.1 Electrical General Notes and Symbols
E1.1 Cooler Penthouse Electrical Renovation Plan
E1.2 Chiller Room Electrical Renovation Plan
M0.1 Mechanical General Notes and Symbols
M0.2 Mechanical Schedules, Notes, Details
M1.1A Mechanical Penthouse Plan
M1.1B Mechanical Penthouse Plan
M1.1C Mechanical Penthouse Plan
M1.2 Chiller Room Piping Diagram
M1.3 Computer Room Piping Plan
M1.4 Chilled Water Piping Diagram
Cover
Structural
Architectural
Electrical
Mechanical
REVISIONS
No. Description Date jboyer Polygon jboyer Text Box
FOR INFORMATION ONLY:
THE PROJECT SCOPE IS TO REPLACE THREE COOLING TOWERS WITH FOUR NEW TOWERS. THE DRAWINGS ARE INCLUDED TO SHOW LOCATIONS OF TOWERS AND EXISTING PIPING. IGNORE REQUIREMENTS OUTSIDE OF THE STATEMENT OF WORK (PIPING REPLACEMENT, CHILLER ADDITION,) AS THIS WORK WILL BE COMPLETED AT A LATER DATE.
CLOUDED AREAS INDICATE PRIMARY AREAS OF WORK.
jboyer Polygon jboyer Text Box
FOR INFORMATION ONLY:
THE PROJECT SCOPE IS TO REPLACE THREE COOLING TOWERS WITH FOUR NEW TOWERS. THE DRAWINGS ARE INCLUDED TO SHOW LOCATIONS OF TOWERS AND EXISTING PIPING. IGNORE REQUIREMENTS OUTSIDE OF THE STATEMENT OF WORK (PIPING REPLACEMENT, CHILLER ADDITION,) AS THIS WORK WILL BE COMPLETED AT A LATER DATE.
CLOUDED AREAS INDICATE PRIMARY AREAS OF WORK.
jboyer Polygon jboyer Text Box
FOR INFORMATION ONLY:
THE PROJECT SCOPE IS TO REPLACE THREE COOLING TOWERS WITH FOUR NEW TOWERS. THE DRAWINGS ARE INCLUDED TO SHOW LOCATIONS OF TOWERS AND EXISTING PIPING. IGNORE REQUIREMENTS OUTSIDE OF THE STATEMENT OF WORK (PIPING REPLACEMENT, CHILLER ADDITION,) AS THIS WORK WILL BE COMPLETED AT A LATER DATE.
CLOUDED AREAS INDICATE PRIMARY AREAS OF WORK.
Text Box
FOR INFORMATION ONLY:
THE PROJECT SCOPE IS TO REPLACE THREE COOLING TOWERS WITH FOUR NEW TOWERS. THE DRAWINGS ARE INCLUDED TO SHOW LOCATIONS OF TOWERS AND EXISTING PIPING. IGNORE REQUIREMENTS OUTSIDE OF THE STATEMENT OF WORK (PIPING REPLACEMENT, CHILLER ADDITION,) AS THIS WORK WILL BE COMPLETED AT A LATER DATE.
CLOUDED AREAS INDICATE PRIMARY AREAS OF WORK.
GENERAL NOTES
DESIGN CRITERIA:
1. CODES AND STANDARDS:
2018 IBC
2. DESIGN GRAVITY LOADS:
DEAD LOADS:
FLOOR:
DEAD LOAD: 115 PSF
ROOF:
DEAD LOAD: 30 PSF
LIVE LOADS:
FLOOR:
LIVE LOAD: 100 PSF
ROOF:
MINIMUM LIVE LOAD: 28 P.S.F. PLUS ALLOWANCE FOR DRIFTED SNOW
GROUND SNOW LOAD: Pg = 40 P.S.F.
SNOW EXPOSURE FACTOR: Ce = 0.9
SNOW LOAD IMPORTANCE FACTOR: 1.0
SNOW THERMAL FACTOR: Ct = 1.0
3. WIND LOAD:
BASIC WIND SPEED: 115 M.P.H.
WIND LOAD IMPORTANCE FACTOR: I = 1.0
WIND LOAD IMPORTANCE FACTOR FOR WALLS
WIND EXPOSURE: C
BUILDING CATEGORY: ENCLOSED
WIND EXPOSURES:
COMPONENTS AND CLADDING WIND PRESSURES(PSF):
ZONE 1: +10, -13.3
ZONE 2: +10, -23.2
ZONE 3: +10, -34.3
ZONE 4: +14.5, -15.8
ZONE 5: +14.5, -19.5
INTERNAL PRESSURE COEFFICIENT: + 0.18
4. SEISMIC LOAD:
SPECTRAL ACCELERATIONS: Ss = 0.089
SPECTRAL ACCELERATIONS: S1 = 0.034
DESIGN SPECTRAL RESPONSE ACCELERATION: Sds = 0.095 DESIGN SPECTRAL RESPONSE ACCELERATION: Sd1 = 0.055
OCCUPANCY CATEGORY: II
SEISMIC DESIGN CATEGORY: A
SITE CLASS: D
SITE COEFFICIENTS: Fa = 1.6 Fv =2.4 IMPORTANCE FACTOR: Ie = 1.0
5. COMPONENT IMPORTANCE FACTOR:
Ip = 1.5
6. BASIC STRUCTURAL SYSTEMS:
A.) FRAME SYSTEM.
7. SEISMIC - RESISTING SYSTEM:
ORDINARY STEEL CONCENTRICALLY BRACED FRAME
R = 5 Cd = 4 1/2
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE PROCEDURE
ADDITIONAL ADDL.
ALUMINUM ALUM.
ANCHOR BOLT A.B.
AND &
ANGLE L
ARCHITECTURAL ARCH.
AT @
BASEMENT BSMT.
BASE PLATE B. P.
BEAM BM.
BEARING BRG.
BETWEEN BTW.
BLOCK BLK.
BOARD BD
BOTTOM BOT.
BOTTOM FACE B/FACE
BOTTOM OF METAL DECK BOD
BOTTOM OF FOOTING BOF
BOTTOM OF WALL BOW
BRICK BRK.
BRICK SHELF B/S
BRIDGING BRDG.
BUILDING BLDG.
CANTILEVER CANTL.
CAST IN PLACE C.I.P.
CEILING CLG.
CEMENT CEM.
CENTER LINE CL.
CENTER TO CENTER C/C
CENTERED CTR'D.
CLEAR CL. or CLR.
COLUMN COL.
CONCRETE CONC
CONNECTION CONN.
CONSTRUCTION CONST.
CONSTRUCTION JOINT C.J.
CONTINUOUS CONT.
CONTRACTOR CONTR.
COORDINATION COORD
DEAD LOAD D.L.
DECK DK.
DIAGONAL DIAG.
DIAMETER DIA.
DIMENSION DIM.
DOWELS DWLS.
DOWN DN.
DRAWINGS DWGS.
EACH EA.
EACH FACE E.F.
EACH WAY E.W.
ELECTRICAL ELECT.
ELEVATION EL.
ELEVATOR ELEV.
EMBEDDED EMBE'D.
EQUAL EQ
EQUIPMENT EQUIP.
EXISTING EXIST.
EXPANSION EXP
EXPANSION JOINT E.J.
EXTERIOR EXT.
FAR FACE F.F.
FINISH FIN.
FINISH FLOOR FIN. FLR.
FLOOR FL.
FOOTING FTG.
FOUNDATION FND.
FRAMING FRMG.
GALVANIZED GALV.
GAUGE GA.
GENERAL CONTRACTOR G.C.
GIRDER GIR.
GRADE GR.
GYPSUM GYP.
HEIGHT HT.
HIGH POINT H.P.
HORIZONTAL HORIZ.
INSIDE FACE I.F.
INTERIOR INT.
JOINT JT.or JNT.
JOIST JST.
STRUCTURAL ABBREVIATIONS:
KIP = 1000 lbs. K
KNOCKOUT KO
POUND lb.
LIGHT WEIGHT LT. WT.
LIVE LOAD L.L.
LONG LG.
LONGITUDINAL LONG.
LONG LEG HORIZONTAL L.L.H.
LONG LEG VERTICAL L.L.V.
LONG WAY L.W.
LOW POINT L.P.
MANUFACTURER MFG.
MARK MK.
MASONRY MAS.
MASONRY OPENING M.O.
MATERIAL MAT'L
MAXIMUM MAX.
MECHANICAL MECH
METAL MTL.
MINIMUM MIN.
MISCELLANEOUS MISC.
MOMENT CONNECTION M.C.
NEAR FACE N.F.
NOMINAL NOM.
NOT IN CONTRACT N.I.C.
NOT TO SCALE N.T.S.
ON CENTER O.C.
OPENING OPNG .
OPPOSITE HAND OPP.H.
OUTSIDE FACE O.F.
PANEL PNL.
PENTHOUSE P.H.
PLATE PL.
PLUMBING PLBG
PRECAST CONCRETE P.C.
PRE-ENGINEERED
METAL BUILDING PEMB
POCKET PCK'T.
POST TENSION P.T.
RADIUS RAD.
RECTANGULAR RECT.
REFERENCE REF.
REFER TO RE:
REINFORCING REINF.
REQUIRED REQ'D
REVISION REV.
ROOF RF.
ROOM RM
SCHEDULE SCHD.
SECTION SECT.
SHORT WAY S.W.
SIMILAR SIM.
SLAB SL.
SLAB ON GRADE S.O.G.
SPACE, SPACING, SPACES SPA.
SPECIFICATIONS SPECS
SQUARE SQ.
STANDARD STD.
STEEL STL.
STRUCTURE OR STRUCTURAL STRUC
SUPPORT SUPPT.
SYMMETRICAL SYMM.
THICKNESS THK.
TOP FACE T.FACE
TOP OF BRICK LEDGE T/BL
TOP OF FOOTING TOF
TOP OF CONCRETE TOC
TOP OF PIER TOP
TOP OF JOIST T/JST
TOP OF SLAB TSL
TOP OF STRUCTURAL STEEL TOS
TOP OF WALL TOW
TRUSS BEARING T/BRG.
TYPICAL TYP.
UNLESS NOTED OTHERWISE U.N.O.
VERTICAL VERT
VERIFY IN FIELD VIF
WIND BRACE W.B.
WELDED WIRE FABRIC W.W.F.
WITH W/
Bearing Walls
(ANSI31)
CMU
Walls
(ANSI37)
Concrete (Concrete)
Earth (Earth)
Equipment Pad (Earth)
Gravel (Rock)
Grout (Grout)
Overframe
Shear Wall (Shearwall)
Slab Recessed (Slab Recessed)
SLab Recessed (Zig Zag)
Steel (Steel)
Exist (Exist)
Hatch Patterns & Scale
Catwalk
(ANSI38)
Insulation (Rigid Insulation)
STRUCTURAL STEEL cont:
8. SPLICING OF STEEL MEMBERS, UNLESS SHOWN ON THE DRAWINGS, IS PROHIBITED
WITHOUT WRITTEN APPROVAL OF THE ARCHITECT.
9. NO CHANGE IN SIZE OR POSITION OF THE STRUCTURAL ELEMENTS SHALL BE MADE OF
HOLES, SLOTS, CUTS, ETC., AND ARE NOT PERMITTED THROUGH ANY MEMBER UNLESS
THEY ARE DETAILED ON THE APPROVED SHOP DRAWINGS.
10. NO FINAL BOLTING OR WELDING SHALL BE MADE UNTIL AS MUCH OF THE STRUCTURE
HAS BEEN PROPERLY ALIGNED AND WILL THEREBY BE STIFFENED.
11. UNLESS NOTED OTHERWISE, BEAMS SHALL BEAR 8" MINIMUM ON CONCRETE OR
MASONRY. ANCHOR BEAMS TO MASONRY WITH A GOVERNMENT-TYPE ANCHOR.
12. FABRICATE ALL BEAMS WITH THE MILL CAMBER UP.
13. EXPANSION BOLTS:
UNLESS NOTED OTHERWISE, EXPANSION BOLTS SHALL HAVE THE FOLLOWING
MINIMUM ULTIMATE LOAD CAPACITIES WHEN DRILLED INTO CONCRETE WITH A
MINIMUM DESIGN STRENGTH OF 4000 P.S.I. ULTIMATE LOAD CAPACITIES SHALL
PROVIDE FOR A MINIMUM FACTOR OF SAFETY = 4.
DIAMETER SHEAR TENSION EFFECTIVE EMBEDMENT
1/2" 3570 LBS. 4040 LBS 3 1/4"
3/4" 7635 LBS 5075 LBS 3 3/4"
SEE SPECIFICATIONS
14. SHEAR STUDS: CONFORM TO A.W.S. D1.1-98, SHOP WELD EXCEPT WHERE APPLIED
THROUGH METAL DECK.
15. TESTING OF EXPANSION BOLTS AND EPOXY ANCHORS.
A. EXPANSION BOLTS: THE CONTRACTOR SHALL TEST 25% OF ALL EXPANSION
BOLTS ACCORDING TO THE MANUFACTURER'S REQUIRED TORQUES.
B. EPOXY ANCHORS: THE CONTRACTOR SHALL TEST 25% OF ALL EPOXY ANCHORS
WITH PULL TEST EQUAL TO 150% TIMES THE ALLOWABLE BOLT TENSILE
CAPACITIES.
C. NOTE: THE EPOXY ANCHORS ARE TO BE STORED IN A COOL LOCATION
ACCORDING TO THE MANUFACTURES SPECIFICATIONS.
16. SEE MISC. NOTES FOR EPOXY / ADHESIVE ANCHORS.
17. MATERIALS AND JOINTS FOR MOMENT CONNECTIONS AND CONNECTIONS FOR
VERTICALLY BRACED ELEMENTS SHALL CONFORM TO THE FOLLOWING:
A. MATERIALS SHALL CONFORM TO SEISMIC PROVISIONS, SECTION 6 AND
SUPPLEMENT NO. 1.
B. STEEL PLATES AND SHAPES SHALL HAVE A MINIMUM CHARPY V-NOTCH
TOUGHNESS CONFORMING TO SEISMIC PROVISIONS SECTION 6.3, AND
SUPPLEMENT NO. 1.
C. BOLTED AND WELDED JOINTS TO CONFORM TO SEISMIC PROVISION SECTIONS
7, AND SUPPLEMENT NO. 1.
STRUCTURAL STEEL:
1. STEEL SHALL CONFORM TO THE FOLLOWING GRADES:
ALL WF (U.N.O.): A992 GRADE 50 (FY=50)
ALL ANGLE, BASE PLATES, CONN. PLATES (U.N.O.): A36 (FY=36)
STRUCTURAL PIPE: A53 (FY=35)
STRUCTURAL TUBE: A500 GRADE B (FY=46)
HEADED STUDS AWS D1.1, TYPE B
THREADED ROD A36
ANCHOR ROD F1554,GR36 OR 55 PER DETAILS
BOLTS A325 / F1852
ELECTRODES MATCHING STRENGTH, 70KS: MIN.
2. ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED IN
ACCORDANCE WITH THE (A.I.S.C. 303-2010) CODE OF STANDARD PRACTICE, EXCEPT AS
MODIFIED IN THESE NOTES AND THE PROJECT SPECIFICATIONS.
3. CONNECTIONS MAY BE BOLTED OR WELDED. THE FABRICATOR IS RESPONSIBLE FOR
THE DESIGN, OF CONNECTIONS NOT DESIGNED ON THE DRAWINGS. GENERALLY,
CONNECTIONS SHOWN ON THE STRUCTURAL DRAWINGS ARE SCHEMATIC AND ARE
ONLY INTENDED TO SHOW THE RELATIONSHIP OF MEMBERS CONNECTED. ANY
CONNECTION THAT IS NOT SHOWN OR IS NOT COMPLETELY DETAILED ON THE
STRUCTURAL DRAWINGS SHALL BE DESIGNED BY AN ENGINEER, REGISTERED IN
DESIGNED BY AN ENGINEER, REGISTERED IN THE STATE OF (insert project state), RETAINED BY THE FABRICATOR. COMPLETELY DETAILED MEANS THE FOLLOWING
INFORMATION IS SHOWN ON THE DETAIL:
A. ALL PLATE DIMENSIONS AND GRADES.
B. ALL WELD SIZES, LENGTHS, PITCHES, AND RETURNS.
C. ALL HOLE SIZES AND SPACINGS.
D. NUMBER AND TYPES OF BOLTS: WHERE BOLTS ARE SHOWN BUT NO NUMBER
IS GIVEN, THE CONNECTION HAS NOT BEEN COMPLETELY DETAILED.
E. WHERE PARTIAL INFORMATION IS GIVEN, IT SHALL BE THE MINIMUM
REQUIREMENT FOR THE CONNECTION.
DESIGN CALCULATIONS FOR TYPICAL BEAM CONNECTIONS AND ALL PRIMARY BRACING
AND HANGER CONNECTIONS SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW AND
APPROVAL PRIOR TO FABRICATION.
4. CONNECTION DESIGN FORCES:
A. BEAMS, GREATER OF:
1. 55% OF TOTAL ALLOWABLE UNIFORM LOAD CAPACITY FROM A.I.S.C 13TH
EDITION TABLES FOR ALLOWABLE LOADS ON BEAMS, Wc/L
2. REACTIONS SHOWN ON DRAWINGS ARE ALLOWABLE LOADS.
3. 10 KIPS.
B. MOMENT CONNECTIONS INDICATED ON THE DRAWINGS THUS:
DESIGN FOR MOMENT SHOWN OR, IF NOT SHOWN, DEVELOP MOMENT
CAPACITY OF MEMBER WITH fb = 0.66FY.
C. MAINTAIN TENSION CAPACITY OF COLUMNS, DIAGONALS AND MEMBERS
SUBJECT TO TENSION AT BOLT HOLES, NOTCHES, OR COPES.
D. CONNECTION FORCE NOTATION:
P = AXIAL FORCE IN KIPS: (+) TENSION, (-) COMPRESSION
V OR [ ] = SHEAR IN KIPS
M = MOMENT IN FOOT KIPS
T = TORSION IN FOOT KIPs
1. LOADS SHOWN INCLUDE COMPENSATION FOR CODE PERMITTED
STRESS INCREASES AND LOAD REDUCTIONS FOR CONNECTION DESIGN.
5. THE MINIMUM PLATE THICKNESS SHALL BE 3/8.
6. BOLTED CONNECTIONS:
A. MINIMUM BOLT DIAMETER = 3/4"
B. SLIP CRITICAL CONNECTIONS OF A325SC OR A490SC BOLTS SHALL BE USED
FOR ALL BOLTED CONNECTIONS OF BRACING MEMBERS, MOMENT
CONNECTIONS, CANTILEVERS, AND AS SHOWN ON THE DRAWINGS. OVERSIZED
AND LONG-SLOTTED HOLES ARE ALLOWED FOR FRICTION CONNECTIONS.
C. ALL OTHER BOLTED CONNECTIONS SHALL BE BEARING TYPE USING A325N OR
A490N BOLTS. OVERSIZED HOLES AND LONG-SLOTTED HOLES ARE NOT
ALLOWED UNLESS SHOWN ON THE DRAWINGS.
D. A307 BOLTS MAY BE USED WHERE INDICATED ON THE DRAWINGS.
E. PROTRUDING BOLT HEADS, SHAFTS OR NUTS SHALL NOT EXTEND INTO NOR
PROHIBIT THE APPLICATION OF ARCHITECTURAL FINISHES AND THEY SHALL
NOT EXTEND INTO NOR PROHIBIT THE PLACEMENT OF STEEL DECKING TO THE
CORRECT LINE AND ELEVATION.
F. THE FABRICATOR IS RESPONSIBLE FOR VERIFYING THE TENSION CAPACITY OF
AXIALLY LOADED MEMBERS AFTER A SECTION IS REDUCED FOR BOLT HEADS.
MEMBER SIZE MAY BE INCREASED OR CONNECTION PLATES ADDED AS
REQUIRED.
G. SHOP DRAWINGS SHALL INDICATE THE TYPE OF BOLT USED IN EACH
CONNECTION AND THE ALLOWABLE VALUES USED FOR THE VARIOUS BOLT
TYPES.
7. WELDED CONNECTIONS:
A. WELDS ARE CONTINUOUS UNLESS NOTED OTHERWISE.
B. ALL FILLET WELDS: A.I.S.C. MINIMUM BUT NOT LESS THAN 1/8" UNLESS NOTED OTHERWISE.
C. ALL WELDING SHALL BE IN ACCORDANCE WITH THE "STRUCTURAL WELDING CODE"
(A.W.S. D1.1-10) PUBLISHED BY THE AMERICAN WELDING SOCIETY. ELECTRODES
FOR WELDING SHALL COMPLY WITH THE REQUIREMENTS OF TABLE 3.1 OF
(A.W.S. D1.1-10).
D. ALL GROOVE WELDS SHALL BE COMPLETE PENETRATION UNLESS NOTED
OTHERWISE.
EXISTING CONDITIONS:
1. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS, SUCH AS
DIMENSIONS, ELEVATIONS, CONFIGURATION, AND DETAILS OF EXISTING STRUCTURES
AND CONDITIONS WHERE THEY AFFECT NEW CONSTRUCTION. NOTIFY ENGINEER
IMMEDIATELY IF ANY DEVIATIONS FROM ANTICIPATED CONDITIONS ARE DISCOVERED.
2. COORDINATION W/ COMPLETE SET OF CONTRACT DOCUMENTS: THE CONTRACT
DOCUMENTS ARE ONE COMPLETE, COMPREHENSIVE AND INCLUSIVE DOCUMENT
CONSISTING OF THE AGGREGATE COLLECTION OF DRAWINGS AND SPECIFICATIONS
FOR ALL OF THE DISCIPLINES' DIVISIONS (E.G. SITE, CIVIL, ARCHITECTURAL,
STRUCTURAL, MECHANICAL, PLUMBING, ELECTRICAL, ETC.). NO SINGLE DISCIPLINE
DIVISION IS AUTONOMOUS NOR DOES IT STAND-ALONE FROM ANY OR ALL OTHER
DISCIPLINE DIVISIONS.
3. VERIFY ALL DIMENSIONS, ELEVATIONS, DEPRESSIONS, INSERTS, EMBEDDED ITEMS.
EQUIPMENT PADS AND SUPPORTS, OPENINGS, DETAILS, AND CONDITIONS BY CROSS-
REFERENCING TO ARCHITECTURAL AND ALL OTHER DISCIPLINE SECTION DRAWINGS,
PARTICULARLY CIVIL, MECHANICAL, AND ELECTRICAL SECTIONS.
4. SEE ARCHITECTURAL AND ALL OTHER DISCIPLINE SECTION DRAWINGS FOR
DIMENSIONS NOT SHOWN ON STRUCTURAL DRAWINGS..
5. STRUCTURAL DRAWINGS DO NOT SHOW ALL REQUIRED OPENINGS THROUGH
STRUCTURAL MEMBERS.
6. VERIFY SIZE AND LOCATION OF ALL OPENINGS WITH ARCHITECTURAL AND ALL OTHER
DISCIPLINE SECTION DRAWINGS.
7. NOTES REGARDING USE OF DRAWINGS:
DRAWING SCALES ARE NOTED FOR REFERENCE ONLY. NOT ALL ITEMS ARE DRAWN
TO SCALE, AND DRAWINGS SHOULD NOT BE SCALED TO OBTAIN DIMENSIONS OR
ELEVATIONS NOT INDICATED.
8. DENOTES MOMENT CONNECTION AT COLUMN OR BEAM. SEE S0.x FOR TYPICAL
MOMENT. CONNECTION DETAILS. SEE GENERAL NOTES SHEET FOR SPECIAL
REQUIREMENTS AT MOMENT CONNECTIONS WHICH ARE PART OF THE BUILDING
LATERAL FORCE RESISTING SYSTEM.
9. DUE TO MULTIPLE ADDITIONS TO THE EXISTING BUILDING, A WIDE VARIETY OF
EXTERIOR WALLS EXIST. THE "TYPICAL SQUEEZE LINTEL DETAIL" ON SHEET S-4 CAN
BE UTILIZED TO REINFORCE MOST EXISTING WALLS AT PENETRATIONS. THERE MAY
BE CASES WHERE THE SQUEEZE LINTEL DETAIL DOESN'T APPLY. THE CONTRACTOR
HAS THE OPTION TO SUBMIT HIS / HER OWN DETAIL TO THE STRUCTURAL ENGINEER
FOR REVIEW AND APPROVAL, OR PROVIDE THE STRUCTURAL ENGINEER ALL
PERTINENT INFORMATION AND STRUCTURAL ENGINEER WILL PROVIDE A DETAIL.
SHORING OF EXISTING:
SHORING OF EXISTING ROOF STRUCTURAL MEMBERS FOR INSTALLATION OF NEW
COLUMNS AND BEAMS IS REQUIRED ON THIS PROJECT. CONTRACTOR SHALL OBTAIN A
LICENSED PROFESSIONAL ENGINEER TO DESIGN AND SUBMIT SHORING PLANS,
CALCULATIONS, AND DETAILS OF SHORING FOR EXISTING ROOF MEMBERS FOR ALL
REWORK IDENTIFIED ON STRUCTURAL PLANS AS WELL ARCHITECTURAL DEMOLITION
PLANS. ALL DISCREPANCIES MUST BE BROUGHT TO THE ENGINEER OF RECORDS
ATTENTION AND RESOLVED PRIOR TO WORK COMMENCING IN THE FIELD. REACTIONS
FOR SHORING SHALL INCLUDE ALL CONSTRUCTION LOADS, AS WELL AS CURRENT IN-
PLACE LIVE AND DEAD LOADS. ARCHITECT/ENGINEER CAN NOT BE HELD LIABLE FOR
SHORING AND INSTALLATION METHODS NOR PROVIDE MEANS AND METHODS FOR
INSTALLATION OF NEW WORK AND DEMOLITION OF EXISTING WORK.
EXISTING REWORK NOTES:
MISCELLANEOUS:
1. STRUCTURAL DRAWINGS ARE INTENDED TO BE USED WITH ARCHITECTURAL,
PLUMBING, ELECTRICAL, FP AND MECHANICAL DRAWINGS. CONTRACTOR IS
RESPONSIBLE FOR COORDINATING SUCH REQUIREMENTS INTO THEIR SHOP
DRAWINGS AND WORK.
2. NO OPENING SHALL BE MADE IN ANY STRUCTURAL MEMBER WITHOUT THE WRITTEN
APPROVAL OF THE ARCHITECT.
3. NO CHANGE IN SIZE OR DIMENSION OF STRUCTURAL MEMBERS SHALL BE MADE
WITHOUT THE WRITTEN APPROVAL OF THE ARCHITECT.
4. OPENINGS 1'-4" AND LESS ON A SIDE ARE GENERALLY NOT SHOWN ON THE STRUCTURAL
DRAWINGS. REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS FOR SUCH
OPENINGS.
5. THE CONTRACTOR IS RESPONSIBLE FOR LIMITING THE AMOUNT OF CONSTRUCTION
LOAD IMPOSED UPON STRUCTURAL FRAMING. CONSTRUCTION LOADS SHALL NOT
EXCEED THE DESIGN CAPACITY OF THE FRAMING AT THE TIME THE LOADS ARE
IMPOSED.
6. THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION. THE
CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL TEMPORARY BRACING AND/OR
SUPPORT THAT MAY BE REQUIRED AS THE RESULT OF THE CONTRACTOR'S
CONSTRUCTION METHODS AND/OR SEQUENCES.
7. UNLESS OTHERWISE NOTED, FIRE PROOFING METHODS AND MATERIALS FOR
STRUCTURAL MEMBERS ARE NOT SHOWN ON STRUCTURAL DRAWINGS. REFER TO
ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR FIRE RATING REQUIREMENTS,
FIRE PROOFING METHODS AND MATERIALS.
8. DO NOT SCALE THESE DRAWINGS, USE DIMENSIONS.
9. CONTRACTOR'S CONSTRUCTION AND/OR ERECTION SEQUENCES SHALL RECOGNIZE
AND CONSIDER THE EFFECTS OF THERMAL MOVEMENTS OF STRUCTURAL ELEMENTS
DURING THE CONSTRUCTION PERIOD. EXPANSION JOINTS SHOWN ON THE DRAWINGS
HAVE BEEN DESIGNED TO ACCOMMODATE ANTICIPATED THERMAL MOVEMENT AFTER
THE BUILDING IS COMPLETE.
10. THE CONTRACTOR SHALL INFORM THE ARCHITECT IN WRITING OF ANY DEVIATION FROM
THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL NOT BE RELIEVED OF THE
RESPONSIBILITY FOR SUCH DEVIATION BY THE ARCHITECT'S APPROVAL OF SHOP
DRAWINGS, PRODUCT DATA, ETC., UNLESS HE HAS SPECIFICALLY INFORMED THE
ARCHITECT OF SUCH DEVIATION AT THE TIME OF SUBMISSION, AND THE ARCHITECT
HAS GIVEN WRITTEN APPROVAL TO THE SPECIFIC DEVIATION.
11. ALL THINGS WHICH, IN THE OPINION OF THE CONTRACTOR, APPEAR TO BE
DEFICIENCIES, OMISSIONS, CONTRADICTIONS, OR AMBIGUITIES, IN THE PLANS AND
SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT. PLANS
AND/OR SPECIFICATIONS WILL BE CORRECTED, OR WRITTEN INTERPRETATION OF THE
ALLEGED DEFICIENCY, OMISSION, CONTRADICTION OR AMBIGUITY WILL BE MADE BY
THE ARCHITECT BEFORE THE EFFECTED WORK PROCEEDS.
MISCELLANEOUS cont:
12. CHECK ALL DIMENSIONS AGAINST REQUIREMENTS OF OTHER CONTRACT
DOCUMENTS. FIELD VERIFY DIMENSIONS RELATING TO EXISTING CONDITIONS PRIOR
TO ORDERING MATERIALS AND FABRICATION.
13. WHERE DIMENSIONS OR WEIGHTS OF EQUIPMENT OR SYSTEMS ARE VARIABLE FROM
MANUFACTURER TO MANUFACTURER, VERIFY DIMENSIONS AND WEIGHTS SHOWN ON
DRAWINGS WITH SELECTED MANUFACTURER PRIOR TO ORDERING MATERIALS.
NOTIFY STRUCTURAL ENGINEER OF DISCREPANCIES. DO NOT PLACE EQUIPMENT
WHEN SHIPPING OR OPERATING WEIGHT EXCEEDS WEIGHT INDICATED ON
STRUCTURAL DRAWINGS.
14. NO MODIFICATION, ALTERATION OR REPAIR SHALL BE MADE WITHOUT PRIOR REVIEW
BY STRUCTURAL ENGINEER. SUBMIT DETAILS AND CALCULATIONS PREPARED BY A
PROFESSIONAL ENGINEER REGISTERED IN STATE WHERE PROJECT IS LOCATED AND
EMPLOYED BY CONTRACTORS.
15. VERIFY ELEVATOR PIT DIMENSIONS, LOCATIONS, LOADINGS AND DETAILS WITH
SUPPLIERS PRIOR TO THE FABRICATION AND/OR INSTALLATION OF ANY MATERIAL.
16. ELEVATOR HOIST BEAM, GUIDRAIL SUPPORTS, SILL DETAILS ARE SHOWN FOR BIDDING
PURPOSE ONLY AND MAY BE SUBJECT TO CHANGE FOR COORDINATION W/FINIAL
EQUIPMENT SELECTION.
17. ELEVATOR EQUIPMENT INSTALLATION PLATFORMS ARE THE RESPONSIBILITY OF THE
CONTRACTOR. SSC IS AVAILABLE TO PROVIDE DESIGN AS ADDITIONAL SERVICE.
18. EPOXY / ADHESIVE ANCHORS SHALL BE INSTALLED WITHIN THE TEMPERATURE
REQUIREMENTS PROVIDED BY THE EPOXY / ADHESIVE MANUFACTURER. THE
GENERAL CONTRACTOR SHALL NOTIFY THE ARCHITECT / ENGINEER IF
TEMPERATURES ARE NOT WITHIN THE PROPER RANGE.
SPECIAL INSPECTION:
1. PERIODIC INSPECTION OF STEEL FABRICATOR'S SHOP FOR QUALITY CONTROL AND
FABRICATION PROCESSES THAT COMPLY WITH AISC CODE OF STANDARD PRACTICE.
2. PERIODIC INSPECTION OF BOLTED AND WELDED STEEL CONNECTIONS IN THE FIELD PER
TABLE 1704.3 OF THE 2015 INTERNATIONAL BUILDING CODE
3. PERIODIC INSPECTION OF CONCRETE MATERIALS, REINFORCING AND PLACEMENT SHALL BE
INSPECTED PER TABLE 1704.4 OF THE 2015 INTERNATIONAL BUILDING CODE.
4. PERIODIC INSPECTION OF MASONRY MATERIALS, REINFORCING & PLACEMENT SHALL BE
INSPECTED PER TABLE 1704.5.3 OF THE 2015 INTERNATIONAL BUILDING CODE.
5. INSPECTION OF SITE SOILS, FILL PLACEMENT, AND BEARING CAPACITIES BY A LICENSED
GEOTECHNICAL ENGINEER AS FOLLOWS:
A. OBSERVATION OF PROOF ROLLING FOR THE SITE PRIOR TO FILL PLACEMENT.
COMPACTION TESTING OF STRUCTURAL FILL PLACEMENT. LIFTS SHALL NOT EXCEED 8"
B. COMPACT STRUCTURAL FILL TO 95% DRY DENSITY AS MEASURED BY THE STANDARD
PROCTOR METHOD, ASTM D-698
C. PROVIDE BEARING TESTS AT EACH FOOTING LOCATION TO CONFIRM BEARING
CAPACITY.
6. SPECIAL INSPECTION IS NOT A SUBSTITUTE FOR INSPECTION BY A CITY/COUNTY INSPECTOR.
7. SPECIAL INSPECTED WORK WHICH IS INSTALLED OR COVERED WITHOUT APPROVAL OF
LOCAL AND SPECIAL INSPECTORS IS SUBJECT TO REMOVAL OR EXPOSURE.
8. SPECIAL INSPECTORS MUST BE CERTIFIED BY THE CITY/COUNTY TO PERFORM THE TYPES OF
INSPECTIONS SPECIFIED.
9. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INFORM THE SPECIAL INSPECTOR OR
INSPECTION AGENCY AT LEAST ONE WORKING DAY PRIOR TO PERFORMING ANY WORK THAT
REQUIRES SPECIAL INSPECTION. ANY WORK PERFORMED WITHOUT REQUIRED SPECIAL
INSPECTION IS SUBJECT TO REMOVAL.
10. SUBMIT WRITTEN REPORTS WITHIN TWO DAYS OF TESTING TO ENGINEER OF RECORD.
NO. DESCRIPTION OF TYPE OF INSPECTION REQUIRED
DESIGN
STRENGTH
SPECIAL INSPECTION:
TABLE NOTES:
A. THE CONSTRUCTION INSPECTIONS LISTED ARE IN ADDITION TO THE CALLED INSPECTIONS REQUIRED BY IBC, AS AMENDED. SPECIAL INSPECTION IS NOT A SUBSTITUTE FOR INSPECTION BY A CITY / COUNTY INSPECTOR. SPECIALLY INSPECTED WORK WHICH IS INSTALLED OR COVERED WITHOUT THE APPROVAL OF THE CITY / COUNTY INSPECTOR I SUBJECT TO REMOVAL OR EXPOSURE.
B. CONTINUOUS INSPECTION IS ALWAYS REQUIRED DURING THE PERFORMANCE OF THE WORK UNLESS OTHERWISE SPECIFIED.
C. THE SPECIAL INSPECTORS MUST BE CERTIFIED BY THE CITY / COUNTY TO PERFORM THE TYPES OF INSPECTION SPECIFIED.
D. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INFORM THE SPECIAL INSPECTOR OR INSPECTION AGENCY AT LEAST ONE WORKING DAY PRIOR TO PERFORMING ANY WORK THAT REQUIRES SPECIAL INSPECTION. A WORK PERFORMED WITHOUT REQUIRED SPECIAL INSPECTION IS SUBJECT TO
REMOVAL.
E. SUBMIT WRITTEN REPORTS WITHIN TWO DAYS OF TESTING TO ENGINEER OF RECORD. ALL REPORTS MUST IDENTIFY DISCREPANCIES. IT IS THE RESPONSIBILTY OF THE SPECIAL INSPECTOR TO FURNISH REPORTS AND SHOW ALL DISCREPANCIES HAVE BEEN CERTIFICATED OF OCCUPANCIES.
FAILURE OF SPECIAL INSPECTOR TO FOLLOW IBC CHAPTER 17 REQUIREMENTS IS A VIOLATION OF THE CODE FOR WHICH BUILDING HAD BEEN
DESIGNED.
THE FOLLOWING ELEMENTS OF CONSTRUCTION SHALL REQUIRE SPECIAL INSPECTION
PER IBC 2015 SECTION 1705. CONTRACTOR TO FURNISH INSPECTION UNLESS
INSTRUCTED OTHERWISE BY THE CONSTRUCTION CONTRACT.
1 ALL CAST-IN-PLACE CONCRETE SHOWN ON STRUCTURAL DRAWINGS
FOOTING / FOUNDATIONS
SLAB ON GRADE
SLAB ON METAL DECK
XXXX PSI
XXXX PSI
XXXX PSI
2 ALL BOLTS INSTALLED CONCRETE, INCLUDING EXPANSION
AND EPOXY ANCHORS, UNLESS SPECIFICALLY NOTED OTHERWISE
IN DETAILS.
3 PLACEMENT OF REINFORCING STEEL IN CONCRETE IDENTIFIED ABOVE FY=XX KSI
4 ALL PRECAST CONCRETE WALL PANELS XXXX PSI
5B ALL STRUCTURAL FIELD WELDING, (INCLUDING REINFORCING
STEEL) AND SHOP WELDS PERFORMED AT ANY LOCATION
OTHER THAN THE SHOP OF AN APPROVED FABRICATOR
STRUCTURAL STEEL
REINFORCING STEEL
SHEET STEEL FOR COLD FORMED METAL FRAMING
E-70X X
E-90X X
E-60X X
THE SPECIAL INSPECTOR NEED NOT BE CONTINUOUSLY PRESENT
QUALIFICATIONS OF WELDING PROCEDURES, AND WELDERS ARE
DURING WELDING OF THE FOLLOWING ITEMS PROVIDED THE MATERIALS,
VERIFIED PRIOR TO THE START OF WORK; PERIODOC INSPECTIONS ARE
MADE OF WORK IN PROGRESS, AND A VISUAL INSPECTION OF ALL
WELDS IS MADE PRIOR TO COMPLETION OR PRIOR TO SHIPMENT OF
SHOP WELDING
1. SINGLE-PASS FILLET WELDS NOT EXCEDDING 5/16 INCH SIZE.
2. WELDED SHEET STEEL FOR COLD FORMED STEEL FRAMING.
MEMBERS SUCH AS STUDS AND JOISTS.
5C ALL STRUCTURAL HIGH STRENGTH BOLTS A-325
A-490
6 MASONRY CONSTRUCTION
MORTAR CUBES ASTM C-109 AND C-270 TYPE M OR S
GROUT CUBES ASTM C-109 AND C-476 XXXX PSI
13 SOIL COMPACTION: PER GEOTECHNICAL REPORT
13A SOIL ENGINEER TO VERIFY SOIL CONDITIONS ARE SUBSTANTIALLY IN
CONFORMANCE WITH THE SOIL INVESTIGATION REPORT. MIN. BEARING
PRESSURE
XXXX PSF
SPECIAL INSPECTION cont:
MICHAEL VALERE VANDE VELDE
Professional Engineer
PE: 2004017260
EXP:12/31/20
The Seal and Signature apply only to the Document to which they are Affixed, and Expressly Disclaim any Responsibility for all other Plans, Specifications, Estimates, Reports, or other Documents or Instruments relating to or intended to be used for any part or parts of the Architectural or Engineering Project.
Copyright © 2020 by SSC Engineering, Inc.
S S
C J
O B
S
C
J O
B
A
P ro je ct
Project No.
1 Memorial Dr, Suite 1800 St. Louis, MO 63102
Main: 314.621.4343 Fax: 314.621.0261 fox@fox-arch.com www.fox-arch.com
S he et T itl e
Issued for Construction
Sheet No.
Professional Seal:
Missouri Certificate of Authority SSC Engineering Inc - #001244
BCDEFG
ABCDEFG
SENSITIVE BUT UNCLASSIFIED (SBU)
PROPERTY OF THE
UNITED STATES GOVERNMENT.
COPYING, DISSEMINATION, OR
DISTRIBUTION OF THIS DOCUMENT
TO UNAUTHORIZED RECIPIENTS IS
PROHIBITED
Do not remove this notice
Properly destroy or return documents when no longer needed.
US Geological Survey Jesse Boyer
Owner
Architect
Fox Architects Bob Dunn
MEP Engineer
SSC Engineering Ethan Schmitt
Structural Engineer
SSC Engineering Michael Vande Velde
Civil Engineer
Fire Protection
06.12.2020
C
U se rs \jh of fm an n.
EN
G
IN
EE
R
IN
G \D oc um en ts
\2
_U S
G S
-E R
O S
C O
N D
EN
S
ER
_S
TR
U
C _R
_j ho ff m an nU C
JP
Q
.r vt
6/12/2020 10:40:30 AM
S
TR
U C
TU
R
A L
G
EN
ER
A
L N
O
TE
S
S0.1
P ha se I:
E R
O S
F lu id C oo le rs D es ig n S er vi ce s
1936.00
0%
O
TB
06/12/2020
2n d
S tr ee t
S io ux F al ls
, S D
STRUCTURAL SHEET INDEX
SHEET NUMBERS SHEET NAME
S0.1 STRUCTURAL GENERAL NOTES
S0.2 STRUCTURAL GENERAL NOTES & TYPICAL DETAILS
S1.1 STRUCTURAL FLOOR FRAMING PLAN
CONTROL
JOINT
CONTROL
JOINT
CONTROL
JOINT
CONTROL
JOINT
TYPICAL SLAB CONTROL
AND CONSTRUCTION JOINT DETAIL
TYPICAL CONSTRUCTION JOINT
DETAIL FOR SLAB
SEE PLAN
S E
E P
L A
N
SEE ARCH. DWGS. FOR
JOINT PATTERN
3/4" DIA. SMOOTH BAR x 18" LG.
SPACED 12"O.C. GREASE ONE
END TO PREVENT BOND
S E
E P
L A
N
TYPICAL CONTROL JOINT
DETAIL FOR SLAB
D
S E
E P
L A
N
JOINT MAY BE SAWN OR
FORMED WITH PLASTIC STIP
D /4
NOTES:
1. CONSTRUCTION AND/OR CONTROL. JOINTS ARE
INTERCHANGEABLE AT THE CONTRACTORS OPTION. SEE
PLANS FOR JOINT LOCATIONS.
2. SAW CUTTING OF JOINTS SHALL BE DONE AS THE CONCRETE
SETS SUFFICIENTLY TO PERMIT CUTTING WITHOUT CHIPPING,
SPALLING OR TEARING, BUT NOT MORE THAN 24 HOURS AFTER
PLACING.
3. ACI RECOMMENDATION: PLACE SLABS IN LONG RECTANGULAR
STRIPS IN ALTERNATE PANELS. WIDTH OF STRIPS TO BE
12'-0" TO15'-0".
Q2
PLATE THICKNESS T1
DETAIL
A
SCALE:3/4"=1'-0"
Q2 L1 Q1
DETAIL
B
SCALE:3/4"=1'-0"
DETAIL
C
SCALE:3/4"=1'-0"
N
R O
W
N
R O
W
PLATE THICKNESS T2
(2)-L4x4xT3
(2)-L4x4xT3
BOLT TO
COL.
Q1 L1
EQ.
3"
/2
E
Q U
A L
/2
T Y
P
Q5 L5
Q4 L5
BOLTS TYPICAL 7/8" DIA. A325-N 4 1/2 GAGE
NOTE: SEE BRACE CONNECTION SCHEDULE
Q5 L5
PLATE THICKNESS T2
COL.
PER PLAN
5/16 11
5/16 7
Q1 L1
BOTTOM OF BEAM
OR JOIST
ADD'L L2x2x1/4 TO
BOT. CHORD PANEL
POINT AND WELD TO
TOP CHORD.
DECK
PER PLAN
SOLID HARDWOOD
CONT. BLOCKING
ROOF CURB
HANGER ROD
NUT AND WASHER
TOP AND BOTTOM
DBL. L3x3x1/4 TO
SUPPERT SUSPENDED
HOODS AND EQUIPMENT
6" LONG HARDWOOD
BLOCKING UNDER
R.T.U. CURB
L4x4x5/16 CONT.
UNDER ROOF CURB
COPE @ JOIST
L4x4
NOTE:
WHEN L4x4 CURB
SUPPORT DOES NOT
FALL @ A TOP CHORD
PANEL POINT USE THIS
DETAIL
R.T.U.
X
Y
Z
X
Z
ANGLE TO STEEL JOIST, TRUSS OR BEAM
ANGLE TO ANGLE SECTION AT ANGLE
PLAN VIEW
NOTES:
1. PROVIDE TYPICAL FRAME BELOW PERIMETER
OF BASE AT ALL ROOF MOUNTED EQUIPMENT.
1/8
ANGLE
OPENING
16 GAGE CLOSURE PLATE X
DECK DEPTH AT ALL OPENING
EDGES
3/16
ANGLE
1/8 2-12
M A
X
STEE
L
DECK
3/16
STEEL
BEAM
1/8 2-12
2. STEEL DECK SHALL BE CONNECTED TO ROOF FRAME
PER TYPICAL DETAIL AND GENERAL STRUCTURAL NOTES.
OPEN
STEEL DECK
AT JOIST OR TRUSS AT WIDE FLANGE BEAM
1/4" ± - TYPICAL
ANGLE - COPE VERTICAL
LEG AS SHOWN
3/16
ANGLE TO
ANGLE - TYP
ANGLE - TYP
ANGLE TO
PLATE
TO ANGLE
- TYP
EXTEND HORIZONTAL LEG 2"
MINIMUM PAST CENTERLINE OF
SUPPORTING MEMBER - TYPICAL
STEEL
DECK
STEEL
JOIST OR
TRUSS
8"-0" MAX
CENTER LINE OF
STEEL JOIST,
TRUSS OR BEAM
L6x4x3/8 (LLV)-TYPICAL
SEE MECH DWG FOR SIZE & HEIGHT
PAD FOR MECHANICAL EQUIPMENT
1" CHAMFER TYP.
BOTH SIDES
BEAM PER PLAN
ROUGHENED SURFACE
18"
6"
#3 @ 16" O.C.
TSL =
PER PLAN
#3 @ 16" O.C. E.W.
NOTE:
DECK @ PERIMETER OF BUILDING TO BE
WELDED TO JOISTS OR ANGLES U.N.O.
1 1/2" x 22ga.
INTERMEDIATE
RIB PAINTED
METAL DECK
3'-0" COVER
CL. OF
SUPPORT
HILTI #10 DRILL
SCREWS
IN SIDELAPS
@ 8" O.C.
(*NOTE TO ENGINEER:
VERIFY IF HILTI SLC 01
OR SLC 02 SCREWS
SHOULD BE USED)
TYPICAL DECK
EDGE SUPPORT
W/5/8" DIA. WELDS
@ 6"O.C.
TYPICAL DECK
DIAPHRAGM ANGLE
W/5/8" DIA @
6"O.C.
36/7-5/8" DIA WELD PATTERN
@ ALL SUPPORTS
MICHAEL VALERE VANDE VELDE
Professional Engineer
PE: 2004017260
EXP:12/31/20
The Seal and Signature apply only to the Document to which they are Affixed, and Expressly Disclaim any Responsibility for all other Plans, Specifications, Estimates, Reports, or other Documents or Instruments relating to or intended to be used for any part or parts of the Architectural or Engineering Project.
Copyright © 2020 by SSC Engineering, Inc.
S S
C J
O B
C
J O
B
A
P ro je ct
Project No.
1 Memorial Dr, Suite 1800 St. Louis, MO 63102
Main: 314.621.4343 Fax: 314.621.0261 fox@fox-arch.com www.fox-arch.com
S he et T itl e
Issued for Construction
Sheet No.
Professional Seal:
Missouri Certificate of Authority SSC Engineering Inc - #001244
BCDEFG
ABCDEFG
SENSITIVE BUT UNCLASSIFIED (SBU)
PROPERTY OF THE
UNITED STATES GOVERNMENT.
COPYING, DISSEMINATION, OR
DISTRIBUTION OF THIS DOCUMENT
TO UNAUTHORIZED RECIPIENTS IS
PROHIBITED
Do not remove this notice
Properly destroy or return documents when no longer needed.
US Geological Survey Jesse Boyer
Owner
Architect
Fox Architects Bob Dunn
MEP Engineer
SSC Engineering Ethan Schmitt
Structural Engineer
SSC Engineering Michael Vande Velde
Civil Engineer
Fire Protection
06.12.2020
C
U se rs \jh of fm an n.
EN
G
IN
EE
R
IN
G \D oc um en ts
\2
_U S
G S
-E R
O S
C O
N D
EN
S
ER
_S
TR
U
C _R
_j ho ff m an nU C
JP
Q
.r vt
6/12/2020 10:05:59 AM
S
TR
U C
TU
R
A L
G
EN
ER
A
L N
O
TE
S
TY
P
IC
A
L D
ET
A
IL
S
S0.2
P ha se I:
E R
O S
F lu id C oo le rs D es ig n S er vi ce s
1936.00
0%
O
TB
06/12/2020
2n d
S tr ee t
S io ux F al ls
, S D
NOT TO SCALE
TYPICAL SLAB ON GRADE DETAILS
NOT TO SCALE
TYPICAL GUSSET PLATE DETAILS
NOT TO SCALE
TYPICAL DETAIL @ ROOF TOP UNITS
NOT TO SCALE
STL.31-D_TYPICAL FRAMING AT LARGE OPENING
IN STEEL ROOF DECK OR BELOW ROOF
MOUNTED EQUIMENT
NOT TO SCALE
TYPICAL SECTION THROUGH HOUSEKEEPING
PAD @ BEAM
NOT TO SCALE
TYPICAL DECK WELDING (U.N.O.)
| CS0.01 |
| Sheets |
| A1.21 - Architectural Floor Plans |
| CS0.01 - Cover Sheet |
| E0.1 |
| E1.1 |
| M0.1 |
| M0.2 |
| M1.1A |
| M1.1B |
| M1.1C |
| M1.4 |
| S0.1 |
| Sheets |
| S0.1 - STRUCTURAL GENERAL NOTES |
| S0.2 |
| Sheets |
| S0.1 - STRUCTURAL GENERAL NOTES |
| S0.2 - STRUCTURAL GENERAL NOTES & TYPICAL DETAILS |
| S1.1 - STRUCTURAL FLOOR FRAMING PLAN |
| S4.1 - STRUCTURAL FRAMING SECTIONS |
File details come from the government source that posted it. Updated .