This is a Scope of Work document prepared by the South Carolina Department of Mental Health for HVAC maintenance and repair services across four Santee-Wateree Mental Health Center locations: Sumter County Mental Health Facility (801 North Pike West, Sumter, SC 29153), Kershaw County Mental Health Facility (2611 Liberty Hill Road, Camden, SC), Sumter ROI (1175 N. Guinyard Drive, Sumter, SC 29150), and Clarendon County Mental Health Facility (215 Commerce Street, Manning, SC 29102). The contract encompasses comprehensive maintenance and repair of all HVAC equipment at these facilities on a one-price, all-inclusive basis covering parts and labor. Services include a minimum of four quarterly inspections (conducted every 90 calendar days plus or minus five days) with required documentation on provided inspection sheets, preventive maintenance, emergency repairs, filter changes (Merv 8 or higher as specified), coil cleaning, refrigerant leak detection and repair, control system calibration, and seasonal startup and shutdown procedures. The contractor must respond to service calls placed before 9:00 AM with same-day onsite service by 3:00 PM and calls placed after 9:00 AM with same-day or next-day service by 3:00 PM or 8:00 AM respectively. All technicians must have a minimum of five years' experience and be capable of completing repairs during service calls. The equipment inventory includes VRF indoor and outdoor units, ductless split systems, outdoor heat pumps, dedicated outside air units, indoor air handling units, fans, and zone dampers across multiple manufacturers including Daikin, Trane, AMANA, and Greenheck.
The contract excludes lightning damage, acts of God, and vandalism unless covered by insurance claims, which the contractor must assist in filing. The contractor receives a 30-day deficiency inspection period at contract inception to identify equipment issues requiring correction, with the Department of Mental Health retaining approval authority over recommended repairs and pricing. The contractor must possess factory certification on Daikin VRF equipment and I-touch manager controls and maintain knowledge of half-capacity operations and BACNET integration capabilities. Additional HVAC equipment installed during the contract term will be added at the same unit pricing ($/ton) as originally quoted. An Energy Management System (EMS) is installed at the facilities, with CMI, Inc. as the vendor at Kershaw and Harris Integrated Solutions at Sumter Mental Health, and the contractor must be fully knowledgeable with ALC EMS systems or subcontract certified services. All correspondence, billings, letters, and quarterly reports must be submitted via email in PDF format to designated facility representatives, with quarterly inspection sheets due within seven calendar days of inspection completion.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 5400025052.doc | DOC document | |
| Notice of Cancellation.docx | DOCX document | |
| Amendment 1.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HVAC MAINTENANCE AND REPAIR SCOPE
OF WORK
FOR
SANTEE-WATEREE MENTAL HEALTH CENTERS
SOUTH CAROLINA DEPARTMENT OF MENTAL HEALTH
Physical Plant Services
7901 Farrow Road, Building 4, PPSE
Columbia, South Carolina 29203
PREPARED BY:
Mechanical Engineering Consulting Associates, Inc.
2330 Main Street
Columbia, South Carolina 29201
REVISED BY:
SC Department of Mental Health
March 7, 2023
Santee-Wateree Mental Health Center
HVAC Maintenance & Repair SOW
HVAC MAINTENANCE AND REPAIR SCOPE OF WORK
SANTEE-WATEREE MENTAL HEALTH CENTER (Four Locations)
1.0 General
A. Local facility / contact
Name: Sumter County Mental Health Facility (Main)
Address: 801 North Pike West Sumter, SC 29153
Phone: 803-840-0462 Contact: Mark Bellamy
Name: Kershaw County Mental Health Facility
Address: 2611 Liberty Hill Road Camden, SC
Phone: 803-840-0462 Contact: Mark Bellamy
Name: Sumter (ROI)
Address: 1175 N. Guinyard Drive, Sumter SC 29150
Phone: 803-840-0462
Contact: Mark Bellamy
Name: Clarendon County Mental Health Facility
Address: 215 Commerce Street Manning, SC 29102
Phone: 803-840-0462
Contact: Mark Bellamy
B. Equipment in scope under this contract includes moving and non-moving parts for split system heat pumps, fans, split system ductless heat pumps, intake/relief units zone dampers, time-clocks, controls, control systems, indoor and outdoor VRF systems, dedicated outside air units, piping, filters, ductwork and other components listed in requirements.
C. Correspondence between the mental health facility and maintenance contractor shall be coordinated through designated facility representative(s) – designated person or persons from the facility will be determined at the start of contract. Designated person(s) may change during the contractual time, if so the Maintenance contractor will be notified a minimum of two weeks in advanced of the change.
D. Service / maintenance calls are included in the scope of work (SOW).
E. The building’s EMS / controls to be included in the SOW. The HVAC Maintenance
Contractor shall be responsible for EMS calls and repairs under SOW. EMS / controls shall be inspected once a year at minimum and an inspection report shall be sent to
SCDMH designated facility representative(s).
1.1 SCOPE OF WORK (SOW) INTENT
A. The maintenance and repair agreement to cover all aspects of HVAC normal and preventive maintenance as a one price covers all agreement to include parts and labor on moving and non-moving parts with the following exceptions:
1. Lighting Damage: While the contractor will be reimbursed for lightning damage claims, the contractor shall accomplish the following at no charge to the owner.
a. Provide immediate information to the owner’s representative that equipment has been damaged before repairs are begun.
b. Provide photographic evidence that the lightning damage has occurred.
c. Assist the owner in filing insurance claims.
2. Acts of God.
3. Vandalism.
1.2 FORMAT
A. This is a multi-page document. The following items will be attached to the SOW:
1. A listing of the equipment
2. Each piece of HVAC equipment will be listed to include the following as available.
Equipment Capacity
Manufacturer’s Name
Model Number
Voltage
B. Equipment inspection sheet. This sheet will be completed at each quarterly inspection visit and must be submitted to the designated facility representative within 10 calendar days of inspection. The required inspection sheet is attached.
C. Additional items to be covered at the request of the Owner (see FF. of section 1.3).
1. Cover all items requested by the owner not indicated in this document.
2. Reference FF. of section 1.3 for additional installed equipment.
1.3 REQUIREMENTS OF THE STANDARD MAINTENANCE & REPAIR SOW
A. The maintenance and repair contractor will provide a minimum of four (4) inspections annually which are to be documented (see attached inspection sheet). The inspection must be completed every 90 calendar days (+ or – five days). Timing for equipment or system shutdowns as necessary for proper inspections to be coordinated with the facility prior to inspections. Attached inspection sheets must be used for each of the four (4) inspections required each year and should be completed for each piece of equipment. Inspection sheets must be sent to the designated facility representative each quarter as documentation services covered in SOW are completed. The inspection sheets shall be sent to the designated facility representative within seven (7) calendar days of the actual inspection. Alternate inspection sheet templates to be approved by the engineer via the designated facility representative prior to substitution.
B. Furnish all labor and supplies necessary to make repairs, adjustments, routine and preventive maintenance to keep the equipment operating efficiently year-round.
C. Furnish coverage on non-moving parts that included but not limited to starters, controls, control systems, oil and refrigerant piping. All ductwork either fiberglass or sheet metal is covered. Exterior painting of non-moving parts is excluded from this contract.
D. Conduct an evaporator coil and condenser coil cleaning on an annual basis. The contractor will visually inspect each coil on the quarterly visit and clean more often if needed.
E. Provide coverage for motor starters and/or variable speed drives.
F. Provide seasonal startup/shutdown/change over inspection of all air type and water type air conditioning equipment including economizer controls.
G. Supply new compressor oil, oil filters, refrigerant filters and dryers after any compressor failure or change.
H. Check for refrigerant leaks, repair leaks, and replace any refrigerant lost to ensure optimum performance of the HVAC equipment.
I. Provide coverage for miscellaneous replacement of controls components for all HVAC equipment.
J. Check superheat on expansion valve and calibrate as required.
K. Check refrigerant circuit for expansion valve operations.
L. Lubricate all moving parts.
M. Clean all drain pans and drains as needed with a minimum of once per year.
N. Check operating pressures with gauges and record on quarterly inspection report. At the time the pressure readings are taken, note the supply air temperature, return air temperature and the outdoor air temperature. List outdoor temperature under remarks.
O. Calibrate and adjust operating and safety controls.
P. Check all belts and adjust or replace as needed.
Q. Check all equipment for unusual noise and vibration and repair or replace the causes of the noise condition as needed.
R. Check electrical connections for tightness.
S. Provide filter changes quarterly or more frequently if needed. Merv 8 filters by Farr/Camfil or equal are required unless higher efficiency rated filters are required such as noted on plans for Sumter Mental Health facility. Contractor to field verify sizes and thickness of filters in each facility.
T. Exhaust fan grilles and internal blower / cabinet to be cleaned annually.
U. Keep the Owner informed of upgrades and improvements to prolong equipment life and reduce the cost of operation during the life of the contract.
V. Prior to the heating season, test and adjust combustion efficiency in gas fired equipment to optimum performance.
W. The maintenance and repair contractor will not release, nor cause to be released, accidentally or otherwise, any chlorofluorocarbons (refrigerant) into the air. All refrigerants must be reclaimed and recycled according to the latest state and federal governmental requirements and guidelines as published by the American Society of
Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
X. Lightning damage, acts of God, and vandalism are not covered under this agreement. The contractor will be responsible for any repairs needed due to these causes as an extra to the contract. The contractor will assist the Owner in filing insurance claims and will notify the
Owner prior to repairs to allow for documentation to the insurance company. Lack of notice prior to repairs may void the ability of the contractor to be paid for collectible repairs.
Y. All calls placed from Department of Mental Health to the HVAC Maintenance and
Repair Contractor shall be deemed a priority call. All service / maintenance repair calls placed before 9:00 AM will have same day onsite service. All service / maintenance repair calls placed after 9:00 AM will have same or next day onsite service. Service / maintenance calls are included in the SOW. Lack of response by the contractor may be considered cause to cancel the contract.
1. For call placed before 9:00 AM: the HVAC Maintenance and Repair Contractor must be onsite to provide service no later than 3:00 PM same day.
2. For call placed after 9:00 AM: the HVAC Maintenance and Repair Contractor must be onsite to provide service no later than 3:00 PM same day or onsite the next day starting at 8:00 AM.
3. The HVAC Maintenance and Repair Contractor must send certified technician(s) with a minimal of five years’ experience.
4. The HVAC Maintenance and Repair Contractor’s technician(s) must be capable of correcting issues during the service call. If issues are not able to be corrected same day as services, then the technician(s) will need to be able to communicate with the designated facility representative and provide reason why issue(s) are not completed with anticipated date of correction(s).
Z. The contractor is responsible for the hauling and lawful disposal of all used parts, oil, refrigerant, etc.
AA. The maintenance contractor will be required at the beginning of each contract year and prior to the first quarterly inspection to contact the designated facility representative to conduct one or more joint inspections of the HVAC system maintenance.
BB. All correspondence between the mental health facility and the maintenance contract including billings, letters, and quarterly reports to be emailed in PDF to the designated facility representative.
CC. The contractor selected to do the work will be allowed thirty (30) days in which to review the condition of the existing equipment in all locations. The contract is in place while the contractor is conducting the 30-day deficiency inspection The contractor will be expected to generate a list of any items which need to be corrected. Along with the list of items, the contractor is expected to send the cost estimated to remedy the problem. The Department of Mental Health has several options:
1. If DMH does not agree with any of the items presented, they may veto its implementation.
2. If DMH does not agree with the pricing, there are several options.
a. They may elect to correct the items with in-house personnel.
b. They may authorize the contractor to proceed with corrections at the price quoted.
c. They may take bids from other contractors in hopes of getting a price lower than the quoted amount and getting repairs done by other.
DD. When parts are no longer available, all repair requests must be directed in advance of equipment order or work performed to the designated facility representative. Labor continues to be covered under the terms of this contract.
EE: Questions arising from this SOW should be referred to the designated facility representative. Attachments to this SOW include.
1. A listing of the equipment to be covered under this SOW.
2. HVAC drawings in PDF are included where they are available.
3. Equipment inspection sheet.
4. Attached filter checklist must be posted and updated on site.
FF. Should additional HVAC equipment be added to a facility, the additional equipment will be added to this contract in the same unit pricing ($ / ton) as the equipment originally covered under the original terms of this contract.
GG. An ALC EMS system is installed. The contractor is to be fully knowledgeable with the system and with factory trained technicians or sub-contract such services to the local ALC vendor.
HH. For reference, EMS systems are utilized at Kershaw and Sumter Mental Health. CMI, Inc is the vendor @ Kershaw; Harris Integrated Solutions is the vendor @ Sumter Mental
Health.
II. Related to VRF systems:
A. Service contractor must have technician’s factory certified to perform the service and troubleshooting of Daikin VRV equipment and controls.
B. Service contractor and onsite technicians must be factory certified on the service/operation of the Daikin I-touch manager, including BACNET integration where applies.
C. The VRV equipment has multiple outdoor units and can run at half capacity and/or take air handlers off the controls network. Service contractor must possess the knowledge of how to complete these tasks to prevent owner from having an entire system shutdown.
S.C DEPARTMENT OF MENTAL HEALTH
SUGGESTED SAMPLE HVAC UNIT REPORT
Date:
Facility: Address _____________________________________________
Manufacturer Unit Model ___________________________ Tag
Age (yrs)
Discharge press Suction press _ Suction temp
Liquid temp Superheat Subcooling
Evap. temp in Evap. temp out _ Outdoor duct temp
Ambient Temp
Evap. fan FLA Condenser fan FLA
Compressor RLA LRA
Unit voltage
Yes / No Yes / No
Properly charged: Dampers operation OK:
Suction drier installed: Insulation OK:
Condenser coil clean: Defrost cycle checked:
Are fins bent: Heat strips OK:
Evaporator coil clean: Reversing Valve OK:
Any duct leaks: Thermostat/controls OK:
Yes / No
Electrical components & safety controls confirmed:
Electrical connections properly installed/secured:
Confirm condensate overflow switch operation:
Condensate drain and pan properly installed and draining:
continued
S.C DEPARTMENT OF MENTAL HEALTH
SAMPLE HVAC UNIT REPORT
Yes / No
Check evaporator fan condition, motor operation and bearings:
Check condenser fan condition, motor operation and bearings:
Relubrication of severely dirty bearings necessary:
Crackcase heater installed and operating:
Air filters installed and clean:
Is unit operating properly:
Unit panels properly installed and secured:
Electrical panel and boxes properly installed and secured:
VRF related items including but not limited to EEV’s solenoids, 4-way valves, controls updates:
Desiccant wheel(s) clean:
O&M manual checklist reviewed / completed:
The following corrective action is required:
Additional comments:
Technician’s name _________________________________________________
Customer’s signature:
Phone:
S.A.#
FILTER CHANGE LOG
HVAC UNIT NO.
Date Existing filter (clean / dirty) Signature of technician Date changed
Note: Filter Change Log is required on all HVAC Units at all locations.
Sumter Mental Health Equipment Summary
VRF Indoor Ducted Unit
Symbol Model Number MFG Type Voltage Nom. Tonnage
DAH-A05 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A06 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A07 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A08 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A09 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A18 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-A19 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A26 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A27 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A28 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A29 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A30 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A32 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C01 FXMQ18 Daiken Ducted Concealed 208-1-60 1.5
DAH-C02 FXMQ12 Daiken Ducted Concealed 208-1-60 1
DAH-C03 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C04 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C05 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C06 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C07 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C08 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C09 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-C10 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C11 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C12 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C13 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C14 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C15 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C16 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C17 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-C18 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-C19 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-C20 FXMQ18 Daiken Ducted Concealed 208-1-60 1.5
DAH-A10 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-A11 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A12 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A13 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A14 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A15 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-A16 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A17 FXMQ18 Daiken Ducted Concealed 208-1-60 1.5
DAH-A22 FXMQ12 Daiken Ducted Concealed 208-1-60 1
DAH-A31 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A36 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A37 FXMQ18 Daiken Ducted Concealed 208-1-60 1.5
DAH-A38 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B01 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-B02 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B03 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B04 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B05 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B06 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-B07 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-B08 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B09 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B10 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B11 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B12 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-B13 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B14 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-B15 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B16 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B17 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B18 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-B19 FXMQ12 Daiken Ducted Concealed 208-1-60 1
DAH-B20 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B21 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-B22 FXMQ18 Daiken Ducted Concealed 208-1-60 1.5
DAH-B23 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-A01 FMXQ30 Daiken Ducted Concealed 208-1-60 2.5
DAH-A02 FMXQ24 Daiken Ducted Concealed 208-1-60 2
DAH-A03 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A04 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A20 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A21 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A23 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A24 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A25 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A33 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A34 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-A35 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D01 FXMQ18 Daiken Ducted Concealed 208-1-60 1.5
DAH-D02 FXMQ12 Daiken Ducted Concealed 208-1-60 1
DAH-D03 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D04 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D05 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D06 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D07 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D08 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D09 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-D10 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D11 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D12 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D13 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D14 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D15 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D16 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D17 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D18 FXMQ07 Daiken Ducted Concealed 208-1-60 0.625
DAH-D19 FXMQ09 Daiken Ducted Concealed 208-1-60 0.8
DAH-D20 FXMQ18 Daiken Ducted Concealed 208-1-60 1.5
VRF Outdoor Unit
Symbol Model Number MFG Type Voltage Nom. Tonnage
CU-1A REYQ96 Daiken VRF Condensing Unit 480-3-60 8
CU-1B REYQ120 Daiken VRF Condensing Unit 480-3-60 10
CU-2A REYQ120 Daiken VRF Condensing Unit 480-3-60 10
CU-2B REYQ144 Daiken VRF Condensing Unit 480-3-60 12
CU-3A REYQ96 Daiken VRF Condensing Unit 480-3-60 8
CU-3B REYQ144 Daiken VRF Condensing Unit 480-3-60 12
Ductless Split Indoor AC Unit
Symbol Model Number MFG Type Voltage Nom. Tonnage
DAH-04 FTK24NMVJU Daiken Wall Mounted 208-1-60 2
Ductless Split Outdoor AC
Symbol Model Number MFG Type Voltage Nom. Tonnage
CU-4 RK24NMVJU Daiken DX Condensing Unit 208-1-60 2
Thru-Wall Heat Pump
Symbol Model Number MFG Type Voltage Nom. Tonnage
TWHP-1 PTH123G AMANA PTAC 208-1-60 1
Dedicated Outside Air Unit (grade mounted packaged with natural gas heat)
Symbol Model Number MFG Type Voltage Nom. Tonnage Airflow (cfm) Gas Input
OAU-1 DPS012AHMG4DW-4 Daiken DOAU 480-3-60 13 2130 200 MBH
OAU-2 DPS012AHMG4DW-4 Daiken DOAU 480-3-60 13 2145 200 MBH
Fan
Symbol Model Number MFG Control Voltage Airflow (cfm) SP (in)
CCF-1 SP-A190 Greenheck Light Switch 120-1-60 180 0.25
CCF-2 SP-A110 Greenheck Wall Switch 120-1-60 95 0.25
CCF-3 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-4 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-5 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-6 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-7 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-8 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-9 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-10 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-11 SP-A110 Greenheck Wall Switch 120-1-60 95 0.25
CCF-12 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-13 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-14 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-15 SP-A190 Greenheck Light Switch 120-1-60 180 0.25
CCF-16 SP-A110 Greenheck Wall Switch 120-1-60 95 0.25
CCF-17 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-18 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-19 SP-A110 Greenheck Wall Switch 120-1-60 95 0.25
CCF-20 SP-A190 Greenheck Light Switch 120-1-60 180 0.25
CCF-21 SP-A190 Greenheck Light Switch 120-1-60 180 0.25
CCF-22 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-23 SP-A110 Greenheck Light Switch 120-1-60 220 0.25
CCF-24 SP-A110 Greenheck Light Switch 120-1-60 220 0.25
CCF-25 SP-A110 Greenheck Wall Switch 120-1-60 95 0.25
CCF-26 SP-A110 Greenheck Light Switch 120-1-60 95 0.25
CCF-27 SP-A110 Greenheck Wall Switch 120-1-60 95 0.25
CCF-28 SP-A110 Greenheck Wall Switch 120-1-60 95 0.25
CCF-1 SP-A190 Greenheck Light Switch 120-1-60 180 0.25
CCF-2 SP-A190 Greenheck Light Switch 120-1-60 180 0.25
CCF-3 SP-A110 Greenheck Wall Switch 120-1-60 95 0.25
CCF-1 SP-224 Greenheck EMS 120-1-60 225 0.25
Outdoor Heat Pump
Symbol Model Number MFG Type Voltage Nom. Tonnage
CU - 1 DZ18VCO48 Daiken DX Condensing Unit 200/230-1-60 4
CU - 2 DZ18VCO48 Daiken DX Condensing Unit 200/230-1-60 4
Indoor Air Handling Unit (with supplemental electric heat)
Symbol Model Number MFG Type Voltage Nom. Tonnage
AH - 1 DV61PE Daiken Air Handler per unit label 5
AH - 2 DV61PE Daiken Air Handler per unit label 5
Kershaw Equipment Summary
Outdoor Heat Pump (CU-16 located in records building)
Symbol Model Number MFG Type Voltage Nom. Tonnage
CU - 1 2TWA2020A3000AB Trane DX Condensing Unit 200/230-3-60 5
CU - 2 2TWA2030A3000AB Trane DX Condensing Unit 200/230-3-60 2.5
CU - 3 2TWR2024A1000AB Trane DX Condensing Unit 200/230-1-60 2
CU - 4 2TWA2030A3000AB Trane DX Condensing Unit 200/230-3-60 2.5
CU - 5 2TWA2048A3000AB Trane DX Condensing Unit 200/230-3-60 4
CU - 6 2TWA2030A3000AB Trane DX Condensing Unit 200/230-3-60 2.5
CU - 7 2TWA2036A3000AB Trane DX Condensing Unit 200/230-3-60 3
CU - 8 2TWA2030A3000AB Trane DX Condensing Unit 200/230-3-60 2.5
CU - 9 2TWA2042A3000AA Trane DX Condensing Unit 200/230-3-60 3.5
CU - 10 2TWA2042A3000AB Trane DX Condensing Unit 200/230-3-60 3.5
CU - 11 2TWA2030A3000AB Trane DX Condensing Unit 200/230-3-60 2.5
CU - 12 2TWR2024A1000AB Trane DX Condensing Unit 200/230-1-60 2
CU - 13 4TWA4048A3000AB Trane DX Condensing Unit 200/230-3-60 4
CU - 14 2TWA2060A3000AB Trane DX Condensing Unit 200/230-3-60 5
CU - 15 2TWR2024A1000AB Trane DX Condensing Unit 200/230-1-60 2
CU - 16 E1RA036S06D York DX Condensing Unit 200/230-1-60 2
Indoor Air Handling Unit (SHP-16 located in records building)
Symbol Model Number MFG Type Voltage Nom. Tonnage
SHP - 1 TWE065E13FB2 Trane Air Handler per unit label 5
SHP - 2 TWE031E13FB1 Trane Air Handler per unit label 2.5
SHP - 3 TWE031E13FB1 Trane Air Handler per unit label 2
SHP - 4 TWE031E13FB1 Trane Air Handler per unit label 2.5
SHP - 5 TWE065E13FB2 Trane Air Handler per unit label 4
SHP - 6 TWE031E13FB1 Trane Air Handler per unit label 2.5
SHP - 7 TWE037E13FB1 Trane Air Handler per unit label 3
SHP - 8 TWE031E13FB1 Trane Air Handler per unit label 2.5
SHP - 9 TWE040E13FB2 Trane Air Handler per unit label 3.5
SHP - 10 TWE040E13FB2 Trane Air Handler per unit label 3.5
SHP - 11 TWE031E13FB1 Trane Air Handler per unit label 2.5
SHP - 12 TWE031E13FB1 Trane Air Handler per unit label 2
SHP - 13 TEM4AOC48S412SBA Trane Air Handler per unit label 4
SHP - 14 TWE065E13FB1 Trane Air Handler per unit label 5
SHP - 15 TWE031E13FB1 Trane Air Handler per unit label 2
SHP - 16 F2RP036H06G York Air Handler per unit label 3
Fan
Symbol Model Number MFG Control Voltage Airflow (cfm) SP (in)
ILF-1 CSP-255 Greenheck EMS 120-1-60 600 0.25
CCF-1 SP-218 Greenheck Light Switch 120-1-60 165 0.25
CCF-2 SP-224 Greenheck Variable Spd Switch 120-1-60 225 0.25
CCF-3 SP-216 Greenheck Light Switch 120-1-60 105 0.25
CCF-4 SP-216 Greenheck Light Switch 120-1-60 105 0.25
CCF-5 SP-216 Greenheck Light Switch 120-1-60 105 0.25
CCF-6 SP-216 Greenheck Light Switch 120-1-60 105 0.25
CCF-7 SP-216 Greenheck Light Switch 120-1-60 105 0.25
CCF-8 SP-224 Greenheck EMS 120-1-60 225 0.25
CCF-9 SP-224 Greenheck EMS 120-1-60 225 0.25
RHF-1 CUBE 101-3 Greenheck Hood Switch 120-1-60 1030 1
Zone Damper
Symbol Model Number MFG Max Airflow (cfm) Voltage Valve Size PD (in)
ZD-8 BRT-400 Nailor 350 24v 8 <0.05
ZD-10 BRT-400 Nailor 545 24v 10 <0.05
ZD-12 BRT-400 Nailor 785 24v 12 <0.05
ZD-14 BRT-400 Nailor 1070 24v 14 <0.05
BP-10 BRT-400 Nailor 980 24v 10 <0.05
BP-12 BRT-400 Nailor 1415 24v 12 <0.05
Gravity Vent
Symbol Model Number MFG Max Airflow Velocity (fpm) Type PD (in)
RV-1 GRS-8 Greenheck 165 375 Relief 0.05
RV-2 GRS-12 Greenheck 435 530 Relief 0.05
RV-3 GRS-8 Greenheck 210 477 Relief 0.05
RV-4 GRS-8 Greenheck 105 238 Relief 0.05
RV-5 GRS-12 Greenheck 450 548 Relief 0.05
Clarendon Equipment Summary
Outdoor Heat Pump
Symbol Model Number MFG Type Voltage Nom. Tonnage
4-ton E1FB048S06A York DX Condensing Unit 200/230-1-60 4
7.5-ton E3FB090A25A York DX Condensing Unit 200/230-3-60 7.5
10-ton DZ11TA1203AA Daiken DX Condensing Unit 200/230-3-60 10
Indoor Air Handling Unit with Electric Heater
Symbol Model Number MFG Type Voltage Nom. Tonnage
4-ton N5AHD16A06 York Air Handler per unit label 4
7.5-ton F3EH090A33A York Air Handler per unit label 7.5
10-ton DAT12043AA Daiken Air Handler per unit label 10
Fan
Symbol Model Number MFG Control Voltage Airflow (cfm) SP (in)
EF-1 CSP-125A Greenheck Time Clock 120-1-60 200 0.25
EF-2 SP-108 Greenheck Time Clock 120-1-60 101 0.25
EF-3 SP-108 Greenheck Time Clock 120-1-60 101 0.25
SP-1 BSQ-120 Greenheck T'Stat 120-1-60 1600 0.5
Zone Damper
Symbol Model Number MFG Max Airflow (cfm) Voltage Valve Size PD (in)
ZD-1 lSAOMC12 York 600 per label 12 <0.05
Sumter ROI Equipment Summary
Outdoor Heat Pump
Symbol Model Number MFG Type Voltage Nom. Tonnage
OSHP-1 WCH3602GKR1 Grand Aire DX Condensing Unit 200/230-1-60 5
OSHP-2 WCH3602GKR2 Grand Aire DX Condensing Unit 200/230-1-60 5
OSHP-3 2TWB3060A1000CA Trane DX Condensing Unit 200/230-1-60 5
OSHP-4 PH13NR060-K Payne DX Condensing Unit 200/230-1-60 5
Indoor Air Handling Unit with Electric Heater
Symbol Model Number MFG Type Voltage Nom. Tonnage
10-ton TWE120B300BB Trane Air Handler per unit label 10
10-ton TWE120B300BB Trane Air Handler per unit label 10
Fan
Symbol Model Number MFG Control Voltage Airflow (cfm) SP (in)
EF-1 CSP-125A Greenheck Time Clock 120-1-60 200 0.25
EF-2 SP-108 Greenheck Time Clock 120-1-60 101 0.25
EF-3 SP-108 Greenheck Time Clock 120-1-60 101 0.25
SP-1 BSQ-120 Greenheck T'Stat 120-1-60 1600 0.5