Attachment_A_-_Amerex_Circuit_Monitor_&_Control_Panel_Manual.pdf
PDF 3 MB Posted
- Solicitation number
- 24-8299
- Issued by
- Collier County, Florida
About this file
This document is an Installation, Operation, and Instruction Manual for Amerex Corporation's Vehicle Fire Suppression System Circuit Monitor and Control Panel, specifically for model numbers 17308, 17309, 17310, and 17311. The manual comprehensively details the technical specifications, installation procedures, maintenance requirements, and troubleshooting guidelines for electronic fire suppression system panels designed for mobile equipment such as earth moving equipment, forestry vehicles, agricultural machinery, transit vehicles, and other mobile equipment. The manual covers critical components including heat detectors, linear actuators, pressure switches, manual actuation switches, and backup battery systems, with specific instructions for installation, circuit connections, testing, and maintenance.
The document outlines a three-year warranty for Vehicle Fire Suppression System components, with one-year warranties for small vehicle systems, batteries, and specialized sensors. The panels operate on 12-24 VDC systems, feature backup battery capabilities providing 24-hour protection during power loss, and include multiple diagnostic and safety features such as LED status indicators, audible alarms, and self-testing mechanisms. The system is designed with redundant safety circuits, including detection zones, actuation circuits, and pressure monitoring, enabling comprehensive fire detection and suppression capabilities across various vehicle types and hazardous environments. The manual emphasizes the importance of proper installation, periodic maintenance, and adherence to manufacturer guidelines to ensure optimal system performance and reliability.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Part No. 19680 Rev. G October 2014
Vehicle Fire Suppression System Copyright © 2012 Amerex Corp
AMEREX CORPORATION
7595 GADSDEN HIGHWAY – TRUSSVILLE, AL 35173
www.amerex-fire.com
Phone: 205.655.3271
Fax: 205.655.3279
Circuit Monitor Control Panel
Installation, Operation, and Instruction Manual
P/N 19680 – October 2014
Revision - G http://www.amerex-fire.com
Table of Contents:
Chapter 1: General Information
1.1 Introduction
1.2 What Can Be Protected
1.3 Agency Approval Standards
Chapter 2: Component Description
2.1 Operator Panels
2.1.1 Circuit Monitor Back Lead Connection
2.1.2 Circuit Monitor Bottom Lead Connection
2.1.3 Control Panel Back Lead Connection
2.1.4 Control Panel Bottom Lead Connection
2.2 Detection Devices
2.2.1 Spot Heat Detectors (SHD)
2.2.2 Linear Heat Detectors (LHD)
2.3 Cables
2.3.1 Connection Cables
2.3.2 Power Cable
2.3.3 Hazard Wire Lead Assembly
2.3.4 Linear Actuator Lead Assembly
2.3.5 Pressure Switch Cable
2.4 Pressure Switch
2.4.1 Agent Cylinder Pressure Switch
2.4.2 100 PSI Pressure Switch
2.5 Linear Actuator
2.6 Manual Actuation Switch
2.7 Replacement End Of Line Module (EOL)
2.8 Replacement Battery
2.9 Two Way Linear Actuator Splitter
2.10 Four Way Linear Actuator Splitter
2.11 Parts List And Service Tools
Chapter 3: Hazard Analysis
3.1 Introduction
3.2 Hazard Analysis
3.2.1 Identify The Ignition Source(s)
3.2.2 Identify The Fuel Source(s)
3.2.3 Consulting Vehicle Owner And/Or Original Equipment Manufacturer
3.2.4 Potential Workplace Hazards For The Equipment
3.2.5 Considerations To Be Evaluated
3.2.6 Selecting The Appropriate Agent
3.2.7 Selecting The Appropriate Method Of Detection
3.2.8 Selecting Methods Of Actuation
Chapter 4: System Installation and Design
4.1 Steps To System Design
4.2 Electronic Panel Installation
4.2.1 Back Connection Mounting Option
4.2.2 Bottom Connection Mounting Option
4.3 Detection Components Installations
4.3.1 Linear Heat Detector (LHD)
4.3.2 Spot Heat Detector (SHD)
4.3.3 Manual Actuation Button
4.3.4 100 PSI Pressure Switch
4.4 Detection Circuits
4.5 Actuation Circuits (Release Zone)
4.6 Input/Output Devices
4.6.1 Vehicle Power Input
4.6.2 Agent Cylinder Pressure Switch Input
4.6.3 Output Fire Signal Connections
4.7 Initial Commissioning
4.7.1 Circuit Monitor Operation
4.7.2 Control Panel Operation
4.7.3 Circuit Monitor And Control Panel Function Testing
4.7.4 Heat Detection Sensor Testing
Chapter 5: Inspection & Maintenance
5.1 Daily Inspection
5.2 Monthly Inspection
5.3 Semi-Annual Maintenance
5.4 (6) Six Year Maintenance
5.5 (12) Twelve Year Maintenance
5.6 Circuit Monitor And Control Panel Battery Replacement
Chapter 6: System Alarms & Troubleshooting
6.1 Power Circuit Diagnostics
6.2 Detection Circuit Diagnostics
6.3 Actuator Circuit Diagnostics
6.4 Backup Battery Diagnostics
6.5 Pressure Switch Circuit Diagnostics
Chapter 7: Warranty Statement
Chapter 1: General Information This document must be used in conjunction with the following standards:
1.All applicable NFPA standards.
2.All other standards or laws deemed applicable to an installation by local authorities having jurisdiction.
This manual is to used to describe optional electronics used in conjunction with an Amerex fire suppression system.
AMEREX ELECTRONIC PANELS ARE TO BE USED ONLY WITH AMEREX SYSTEM
COMPONENTS AND CABLES. THE USE OF UNAPPROVED COMPONENTS WILL VOID
AMEREX WARRANTY ON ALL SYSTEM COMPONENTS AND THE FACTORY MUTUAL
LISTING. IT IS THE RESPONSIBILITY OF INDIVIDUALS WHO INSTALL, OPERATE,
INSPECT, RECHARGE AND /OR MAINTAIN THESE SYSTEMS TO READ THIS ENTIRE
MANUAL.
Updated Installation, Operation, and Maintenance Manuals and Technical Bulletins will be available online at www.amerex-fire.com. It is important that these updates and additions be added to this manual according to the instructions that will accompany them.
The applications and use of the Amerex Circuit Monitor and Control Panel Systems are limited to the applications and uses described in this manual. Technical data contained herein is based on controlled laboratory testing deemed appropriate by Factory Mutual Research Corp. and other listing agencies, and is intended for informational purposes only. The data presented is accurate for the testing performed, but is published with no guarantee relative to a given hazard where factors are different from those encountered during actual tests. Amerex disclaims any liability for any use of the data and information contained herein by any and all other parties. Please direct questions concerning information in this manual to:
AMEREX CORPORATION
Vehicle Systems Group
P.O. Box 81 Trussville, AL 35173-0081
Phone: (205) 655-3271
Fax: (205) 655-3279
Email: sales@amerex-fire.com http://www.amerex-fire.com
1.1 Introduction
The Circuit Monitor (P/N 17308 and 17309) and Control Panel (P/N 17310 and 17311) are designed specifically for mobile equipment vehicle applications. The panels provide electrical supervision for an integrated fire detection and suppression system.
The Circuit Monitor (P/N 17308 and 17309) provides electrical supervision of the power, detection and releasing circuits. The Circuit Monitor features visual LED system status indicators and an audible alarm that can be silenced. The system provides a test mode to verify LED and alarm function. The monitor is supplied with a self-recharging back- up battery to provide protection to the vehicle in the event of temporary power loss for up to 24 hours. The monitor is available with connectors on the bottom (P/N 17308) or back (P/N 17309).
The Control Panel (P/N 17310 and 17311) provides the same features as the Circuit Monitor but also includes a time adjustable relay circuit. The test mode for the Control Panel verifies LED, alarm function and relay function. The relay may be used for several applications including but not limited to vehicle shutdown, auxiliary alarm, or fuel pump shutoff. The relay circuit includes both closed and open contacts which transfer at the end of the time delay period. This contact transfer delay is programmable from 0-15 seconds. The panel is available with connectors on the bottom (P/N 17310) or back (P/N 17311).
Benefits of the System:
Simplified System Status and Troubleshooting Via Discreet LEDs
Simple programming features allow for design flexibility
Multiple Detection Inputs, Spot Heat Detectors (SHD), Linear Heat Detectors (LHD)
Allows for overheat early warning
24-hr rechargeable backup battery for protection during extended shut down
Trouble Ring back
Relay Output for Alarm Condition (Control Panel)
System Rest/Relay Override (Control Panel)
Diagnostic LED Self Test Function
12-24 VDC Operation
1.2 What Can Be Protected
A complete hazard analysis must be performed for each piece of equipment being protected to determine the machine components that would require overheat or fire protection.
Protection may include but is not limited to:
Earth Moving Equipment - Dozers, Haul Trucks, Cranes, Excavators, Drill Trucks, Conveyers, Draglines
Forestry / Land Clearing - Skidders, Feller Bunchers, Chippers, Grinders
Landfill / Refuse - Garbage Trucks, Compactors, Track Dozers
Agricultural Equipment - Tractors, Harvesters, Combines, Spreaders
Transit - Rail, Bus
Mobile Equipment - Pumps, Generators, Compressors, Cranes
1.3 Agency Approval Standards
Factory Mutual Corporation
UL 1254 Environmental Test Standards
Society of Automotive Engineers
SAE J1211 Recommended Environmental Practices for Electronic Equipment Design
SAE J1113 Electromagnetic Susceptibility Measurement Procedures for Vehicle
Components
CE Type Approval
ECE/324R10 6.5 & 6.6 Interference caused by ESA's - Broadband and Narrowband limits
ECE/324R10 6.7.2.1d Immunity to EM radiation of the ESA - Free Field
ECE/324R10 6.9 Emission of Conducted Disturbances
Approval No. 10R-047734
Approval Tests Conducted:
Radiated narrow band electromagnetic emissions
Radiated broad band electromagnetic emissions
INPUT POWER
CIRCUIT
ACTUATION CIRCUIT
(RELEASE ZONE)
LINEAR
ACTUATOR
Figure 2
DETECTION CIRCUITS
Chapter 2: Component Description This chapter describes the various components available for use with the Amerex Circuit Monitor and Control Panel Systems. These include electronics panels, detection sensors, cables and other components that comprise a complete system. A simple schematic is given below, which shows a basic Control Panel system layout and available circuits (See Figure 2). All available components, including additional components not shown in this schematic as well as those used for Circuit Monitor, are detailed in the following sections. For fire suppression systems and components, reference the appropriate Amerex Fire Suppression Installation, Operation and Maintenance Manual. Item numbers shown in brackets in the following section titles ([ITEM X]) correspond to the item numbers from the Parts List (See Section 2.11).
AGENT CYLINDER
C L
A S
S B
PRESSURE SWITCH
CIRCUIT
AUXILIARY OUTPUTS
C L
A S
Control Panel Features
1 System OK LED 5 Service System LED
2 Fire LED 6 Push to Test Button
3 Relay Engaged LED 7 Alarm Silence Button
4 Relay Reset Button 8 Alarm Silenced LED
5 4
Circuit Monitor Features
1 System OK LED
2 Fire LED
3 Service System LED
4 Push to Test Button
5 Alarm Silence Button
6 Alarm Silenced LED
Figure 2.1a
P/N 17309/17308
Figure 2.1b
P/N 17311/17310
Table 2.1a Table 2.1b
2.1 Operator Panels
Two choices of operator panels are available for this series of Amerex electronics.
Circuit Monitor - (P/N 17308 Bottom Lead Exit and P/N 17309 Back Lead Exit)
Control Panel - (P/N 17310 Bottom Lead Exit and P/N 17311 Back Lead Exit)
The Circuit Monitor details are shown in Table 2.1a and Figure 2.1a. The Control Panel is of the same design with an added agent cylinder pressure monitoring circuit, and fire relay output signal. Control Panel Details are shown in Table 2.1b and Figure 2.1b.
System Features
Electrical Specifications
Operating Voltage 12-VDC 24-VDC
Current Requirements
Normal Condition 18 mA 47 mA
Fault Condition 10-18 mA 47-52 mA
Alarm Condition 66 mA 78 mA
Mechanical Specifications Weight 19 oz (590 g)
Temperature Specifications Operating Temperature Range -40° F to 150° F (-40° C to 66° C)
Back-up Battery Specifications Operation Time 24 Hours of Fire Suppression Capability
Battery Composition Nickel Metal Hydride (NiMH)
Detection Circuit Specifications Heat Detection Class B
End Of Line Module (EOL) 2.2k Ohms
Alarm Specifications
Alarm Type Output Continuous Signal
Sound Level 85 dB @ 36” @ 12-VDC
Frequency Resonant Frequency: 2800 Hz continuous
2.1.1 Circuit Monitor Back Lead Connection (P/N 17309) [Item 1]
The Circuit Monitor panel allows for surface mount applications and wires routed from the back. All dimensions are in inches [mm].
2.1.2 Circuit Monitor Bottom Lead Connection (P/N 17308) [Item 1]
The Circuit Monitor panel allows for surface mount applications and wires routed from the bottom. All dimensions are in inches [mm].
Figure 2.1.1
Figure 2.1.2
Back View
2.1.4 Control Panel Bottom Lead Connection (P/N 17310) [Item 1]
The Control Panel allows for surface mount applications and wires routed from the bottom. All dimension are in inches [mm].
2.1.3 Control Panel Back Lead Connection (P/N 17311) [Item 1]
The Control Panel allows for surface mount applications and wires routed from the back. All dimensions are in inches [mm].
Figure 2.1.3
Figure 2.1.4
Back View
2.2 Detection Devices
Amerex offers a variety of heat detectors for detecting fires and overheat conditions. A hazard analysis must be performed to identify the proper selection of heat detection methods.
2.2.1 Spot Heat Detectors (SHD) (P/N 14087, 14088, 16615) [Item 2]
A Spot Heat Detector is a normally open, self resetting contact closure device. The device is configured with four wires to allow supervision of series connected circuitry.
The internal contacts of the device will close upon reaching designed temperature set point parameters. Two versions of the device are available. One style of the device is supplied with a 280°F set point rating (P/N 14087) and 350ºF (P/N14088). Both have the mounting configuration shown in figures 2.2.1a and 2.2.1b. Another style of the device is supplied with a 450°F set point rating (P/N 16615) and has the mounting configuration shown in figure 2.2.1c.
P/N Set Point Set Point Color Identification
Mounting Style Figure
14087 280ºF (137ºC) Yellow Bracket 2.2.1a
14088 350ºF (176ºC) Red Bracket 2.2.1b
16615 450ºF (232ºC) Blue Bulkhead 2.2.1c
Table 2.2.1
Figure 2.2.1a
GREEN COLOR CODED
Figure 2.2.1b
Figure 2.2.1c
YELLOW SET POINT ID
RED SET POINT ID
BLUE SET POINT ID
LENGTH (SEE PARTS LIST)
Figure 2.2.2a
Figure 2.2.2b
P/N 20083
P/N 20075
LENGTH (SEE PARTS LIST)
2.2.2 Linear Heat Detector (LHD) with Protective Spring (P/N 20083); without Protective
Spring (P/N 20075) [ITEM 4]
A Linear Heat Detector (LHD) is a normally open device that closes when subjected to heat. The device is comprised of two internal coiled spring loaded conductors that make contact in the event of an overheat condition. A basic LHD (P/N 20075) is a available (See Figure 2.2.2a). A more robust LHD with a protective stainless steel spring along its length (P/N 20083) is also available and can be used to help prevent potential damage to the LHD (See Figure 2.2.2b). Both LHDs are green in color and have a temperature set point of 356°F (180ºC). LHDs must be replaced once they detect an overheat condition. Various lengths of both LHDs are available and shown in the Parts List (See Section 2.11).
2.3.2 Power Cable (P/N Varies) [Item 5]
The Power Cable is used to supply power to the Amerex Circuit Monitor and Control Panel by connecting the units to a power source. The cable is terminated with a sealed connector and ring terminals with a 10 Amp fuse located on the red (+) wire. Color coding (red) can be found on the terminated connector. Various lengths of this cable are available and shown in the Parts List (See Section 2.11).
Figure 2.3.2
LENGTH (SEE PARTS LIST)
RED COLOR CODED
10 AMP FUSE 3/8 I.D. RING TERMINAL
Figure 2.3.1
Pressure Switch and Relay Connection Cable (Used with the Control Panel P/N 17311/17310)
Power and Actuation Connection Cable (Used with the Control Panel and Circuit Monitor)
Detection Connection Cable (Used with the Control Panel and Circuit Monitor)
2.3 Cables
Amerex offers pre-assembled cables. Most of the Amerex cables are terminated with connectors. Amerex cables are color coded to allow for easy troubleshooting and installation.
2.3.1 Connection Cables (P/N 14841) [ITEM 4]
The Amerex Circuit Monitor and Control Panels come complete with the required connection cables and two EOL. Replacement connection cables can be ordered as part of a lager kit (P/N 14841) containing one set of connection cables shown in Figure
2.3.1 along with 4 additional cables not used with the Circuit Monitor or Control Panel (not pictured).
1 Heat Detection
2 Power Cable
3 Actuation
4 Pressure Switch
5 Relay Connections
Green color coded
Figure 2.3.3b
Yellow color coded
Figure 2.3.4a
2.3.4 Linear Actuator Lead Assembly (P/N Varies) [Item 7]
The Linear Actuator Connector Lead Assembly must be used to connect the Linear Actuator to the Circuit Monitor or Control Panel. The Actuator Connector Lead is a two-conductor wire equipped with yellow color-coded Amerex connectors. These connectors mate with the associated connector at the Control Panel and the Linear Actuator. The Linear Actuator Lead Assemblies available in various lengths, see parts list Section 2.11 for available lengths and associated part numbers.
Linear Actuator Lead Assembly Shielded (P/N Varies) [Item 7]
An additional line of heavy-duty actuator lead wire assemblies is available for the Amerex Fire Suppression Systems. The heavy-duty lead assemblies come with a solid abrasion resistant outer sleeve installed over the standard red hazard area wire and sealed to the modular pluggable connectors at each end. The Shielded Linear Actuator Lead Assemblies are available in various lengths, see parts list Section 2.11 for available lengths and associated part numbers.
Yellow color coded
Figure 2.2.4b
Hazard Wire Lead Assembly Shielded (P/N Varies) [Item 6]
An additional line of heavy-duty hazard wire Class B Detection Circuit assemblies are now available for Amerex Systems. The heavy duty Class B Detection Cable assemblies are supplied with an abrasion resistant outer sleeve installed over the standard hazard wire and sealed over the modular pluggable connectors at each end.
The Shielded Hazard Wire Lead Assemblies are available in various lengths, see parts list Section 2.11 for available lengths and associated part numbers.
Green color coded
2.3.3 Hazard Wire Lead Assembly (P/N Varies) [Item 6]
The Hazard Wire Class B detection circuit cable is identified by the single green color coded tie wrap shown at each end of the cable. The Class B cable is used to connect to either a Linear Heat Detector, Spot Heat Detector or Manual Actuation Button with controls of the associated electronics package. The cable is available in various lengths and is equipped with suitable green color coded pluggable connectors on each end.
The Hazard Wire Lead Assemblies are available in various lengths, see parts list Section 2.11 for available lengths and associated part numbers.
Figure 2.3.3a
2.3.5 Pressure Switch Cable (P/N 21539) [ITEM 8]
The Pressure Switch Cable is used to connect the Circuit Monitor and Control Panel to a Pressure Switch located on an Agent Cylinder Valve. Additional cables can also be used to connect link multiple Agent Cylinders to the same pressure switch circuit. Each is terminated with sealed connectors and color coding (blue) can be found on each connector. Various lengths of this cable are available and shown in the Parts List (See Section 2.11).
LENGTH (SEE PARTS LIST)
BLUE COLOR CODED
2.4 Pressure Switch
2.4.1 Agent Cylinder Pressure Switch (P/N 17609) [Item 9]
The Agent Cylinder Pressure Switch is supplied with and connected directly to the Agent Cylinder Valve. This switch is designed to monitor Agent Cylinder pressure. The switch is closed in a pressurized Agent Cylinder and opens when Agent Cylinder pressure drops below 270 psi indicating a discharged or leaking Agent Cylinder.
Reference the appropriate Amerex Fire Suppression Installation, Operation and Maintenance Manual for selection of Agent Cylinders with Pressure Switches.
2.4.2 100 PSI Pressure Switch (P/N 22574) [Item 10]
The 100 PSI Pressure Switch is designed to be used in the Pneumatic Actuation Network of a vehicle system. The Switch (P/N 22574) is normally in the open position and closes when subjected to nitrogen pressure in excess of 100 PSI. The Switch is threaded with a 1/4” NPT male port. The Switch must be installed in a tee in the Pneumatic Actuation Network just before the first Pneumatic (P/N 10147), or Electric / Pneumatic (P/N 17068) Control Head. The Switch can be utilized to send a signal such as “system discharge” back to the associated electronics panel, or to an external relay for sounding an auxiliary alarm or illuminating a light in the event of system discharge.
Figure 2.3.5
Figure 2.4.1
Figure 2.4.2
SUPPLIED WITH AN
O-RING
2.5 Linear Actuator (P/N 22579) [Item 11]
The Linear Actuator is a device when electrically activated extends a metal shaft which mechanically opens the Agent Cylinder Valve when used in a control head or opens a Nitrogen Cylinder when used in an Electric Nitrogen Actuator. The Linear Actuator connects to the Actuation circuit on the Circuit Monitor or Control Panel wiring harness. Once activated, a Linear Actuator cannot be reused and must be replaced. Service life of the Linear Actuator is 6 years after which it must be replaced. Total life of the Linear Actuator is 10 years after which it must be replaced whether it has been placed in service or not. Each Linear Actuator is supplied with a Mylar style label for identifying date of manufacture. An O- RING (P/N 17137) is provided with each Linear Actuator and must be used. Reference the appropriate Amerex Fire Suppression Installation, Operation and Maintenance Manual for Linear Actuator installation instructions.
2.6 Manual Actuation Switch (P/N 14053) [Item 12]
The Manual Actuation Switch (P/N 14053) is used in the “Class B” detection circuit. The switch is in the normally open position. The switch has a red “FIRE” button that can be pressed to complete the circuit of the “Class B” circuit for activating the fire suppression system.
Figure 2.5
Figure 2.6
TAMPER SEAL
(P/N 01387)
GREEN COLOR CODED
2.7 Replacement End Of Line Module (P/N 14010) [Item 13]
The End Of Line Module completes the two class B detection circuits. Two are furnished with each Circuit Monitor or Control Panel.
2.8 Replacement Battery (P/N 18156) [Item 14]
The Circuit Monitor and Control Panels contain a Nickel Metal Hydride back up battery to maintain vehicle protection in the event of loss of the main vehicle power source for up to 24 hours. The battery is DOT compliant for shipping purposes.
Figure 2.7
Figure 2.8
GREEN COLOR CODED
2.9 Two Way Linear Actuator Splitter (P/N 17091) [Item 15]
The Two Way Linear Actuator Splitter connects to the actuation circuit of the Amerex Circuit Monitor and the Control Panel to allow for two linear actuators. In the event of a alarm condition, both linear actuators will be activated.
2.10 Four Way Linear Actuator Splitter (P/N 14128) [Item 16]
The Four Way Linear Actuator Splitter connects to the actuation circuit of the Amerex Circuit Monitor and the Control Panel to allow for up to four linear actuators. In the event of a alarm condition, all linear actuators will be activated.
Figure 2.10
Figure 2.9
2.11 Parts List and Service Tools
Parts List
Item Number
Part Number
Description Qty. per System
17309 Circuit Monitor back conn.
17308 Circuit Monitor bottom conn.
17311 Control Panel back conn.
17310 Control Panel bottom conn.
14087 Spot Heat Detector 280º F
Optional 14088 Spot Heat Detector 350º F
16615 Bulkhead Heat Detector 450º F
20075-03 Linear Heat Detector 3 Ft.
100 Ft. Total
Max.
20075-06 Linear Heat Detector 6 Ft.
20075-10 Linear Heat Detector 10 Ft.
20075-16 Linear Heat Detector 16 Ft.
20075-20 Linear Heat Detector 20 Ft.
20075-25 Linear Heat Detector 25 Ft.
20075-30 Linear Heat Detector 30 Ft.
20075-40 Linear Heat Detector 40 Ft.
20075-50 Linear Heat Detector 50 Ft.
20083-03 Linear Heat Detector w/Sprg. 3 Ft.
20083-06 Linear Heat Detector w/Sprg. 6 Ft.
20083-10 Linear Heat Detector w/Sprg. 10 Ft.
20083-16 Linear Heat Detector w/Sprg. 16 Ft.
20083-20 Linear Heat Detector w/Sprg. 20 Ft.
20083-25 Linear Heat Detector w/Sprg. 25 Ft.
20083-30 Linear Heat Detector w/Sprg. 30 Ft.
20083-40 Linear Heat Detector w/Sprg. 40 Ft.
20083-50 Linear Heat Detector w/Sprg. 50 Ft.
4 14841 Connection Cable Replacement Kit Replacement
14016 Power Connection Lead 10 Ft.
14799 Power Connection Lead 15 Ft.
14017 Power Connection Lead 25 Ft.
14018 Power Connection Lead 40 Ft.
14019 Power Connection Lead 50 Ft.
14915 Power Connection Lead 60 Ft.
15150 Power Connection Lead 75 Ft.
14800 Power Lead Extension 10 Ft.
Optional 16527 Power Lead Extension 20 Ft.
14801 Power Lead Extension 40 Ft.
15779 Replacement 10 AMP fuse Replacement
Parts List Parts List Parts List Parts List
Item Number
Part Number
Description Qty. per System
13981 Hazard Wire Lead Asy. 3 Ft.
Optional
13982 Hazard Wire Lead Asy. 6 Ft.
13983 Hazard Wire Lead Asy. 10 Ft.
13984 Hazard Wire Lead Asy. 15 Ft.
13985 Hazard Wire Lead Asy. 20 Ft.
13986 Hazard Wire Lead Asy. 30 Ft.
13987 Hazard Wire Lead Asy. 40 Ft.
13988 Hazard Wire Lead Asy. 50 Ft.
17063 Hazard Wire Lead Asy. 60 Ft.
16457 Heavy Duty Hazard Lead 3 Ft.
16458 Heavy Duty Hazard Lead 6 Ft.
16459 Heavy Duty Hazard Lead 10 Ft.
16460 Heavy Duty Hazard Lead 15 Ft.
16461 Heavy Duty Hazard Lead 20 Ft.
14723 Linear Actuator Lead Asy. 3 Ft.
Optional
14724 Linear Actuator Lead Asy. 6 Ft.
14123 Linear Actuator Lead Asy. 10 Ft.
14124 Linear Actuator Lead Asy. 20 Ft.
14125 Linear Actuator Lead Asy. 30 Ft.
14126 Linear Actuator Lead Asy. 40 Ft.
14127 Linear Actuator Lead Asy. 50 Ft.
16470 Heavy Duty Actuator Lead 3 Ft.
16471 Heavy Duty Actuator Lead 6 Ft.
16472 Heavy Duty Actuator Lead 10 Ft.
16473 Heavy Duty Actuator Lead 20 Ft.
21539-10 Pressure Switch Cable, 10 Foot Length
Optional
21539-20 Pressure Switch Cable, 20 Foot Length
21539-30 Pressure Switch Cable, 30 Foot Length
21539-40 Pressure Switch Cable, 40 Foot Length
21539-50 Pressure Switch Cable, 50 Foot Length
21539-55 Pressure Switch Cable, 55 Foot Length
Parts List Parts List Parts List Parts List
Item Number
Part Number
Description Qty. per System
9 17609 Agent Cylinder Pressure Switch Reference
22574 100 PSI Pressure Switch w/ Plug
Reference 22573 100 PSI Pressure Switch w.o./Plug
11 22579 Linear Actuator 1 minimum
12 14053 Manual Actuation Switch 1 minimum
13 14010 End Of Line Module Replacement
14 18156 Backup Battery Replacement
15 17091 Two Way Linear Act. Splitter Optional
16 14128 Four Way Linear Act. Splitter Optional
Service Tools
21447 Alarm Module 1 For Each
Linear Act.
Chapter 3: Hazard Analysis
3.1 Introduction
Before any component of the Amerex fire suppression system is installed, including electronics, the hazards to be protected must be identified. These hazards determine where and type of detection that is required along with the type of and quantity of fire suppression agent necessary for protection. When performing a hazard analysis, some helpful tools that can be useful are:
Flashlights – for those hard to see places.
Cameras and note pads – for helping with documenting the construction of the vehicle fire suppression system and creating a bill of materials. Installers must document and retain all system designs.
Temperature measuring devices – Thermocouples work well in helping to identify vehicle operating temperatures. Knowing the vehicle operating temperature details is crucial in selecting appropriate hardware when doing a hazard analysis and system layout.
Access to all Amerex Installation, Operation, & Maintenance Literature – System may require hardware not located in this manual.
NOTE: On all installations, consult the vehicle manufacturer and property owner before making any modifications to equipment.
3.2 Fire Hazard Analysis
A hazard analysis is used as the first step in a process used to assess risk of fire. The result of a hazard analysis is the identification of fire risks. The National Fire Protection Association (NFPA) offers a series of standards with guidelines for a particular product or system being installed. When conducting a hazard analysis, all applicable standards must be observed.
Examples of such standards include, but are limited to: NFPA 17, 17A, 52, 120, and 122.
Below are some additional considerations to be evaluated when doing a hazard analysis.
3.2.1 Identify the Ignition Source(s)
The potential for hot surfaces such as exhaust manifolds, muffler compartments, hydraulic pumps, and turbochargers can be ignition sources. Other hot surface ignition sources can be friction buildup from bearings, brakes, and gears. Electrical shorts from vehicle electronics and batteries can also be ignition sources.
3.2.2 Identify the Fuel Source(s)
Fuels can be found in many different forms including, but not limited to:
Class A Material: wood, paper, coal dust, rags, hoses, tires, combustible refuse buildup.
Class B Material: Flammable and combustible liquids such as gasoline, diesel fuel, cleaning fluids, hydraulic fluids, brake fluids, transmission fluids.
Class C Material: Class C items describe sources of electrical current that can energize an area where a fire is present.
3.2.3 Consulting Vehicle Owner and/or Original Equipment Manufacturer
Previous experience with machinery may indicate where special hazards exist.
Knowing the history about a particular model of vehicle/machine may help with decisions in protection.
3.2.4 Potential Workplace Hazards for the Equipment
Refuse vehicles frequently work in landfills. Some landfills carry substantial class A fuel sources. Machines working in steel refineries can be exposed to external ignition sources. These types of external hazards will have to be considered when determining the right protection required for the particular machine.
3.2.5 Considerations to be Evaluated
Is the hazard in an open area or closed compartment? In an open area, each hazard must be treated as a local application with careful considerations for selecting appropriate detection. Open area hazards can present challenges with heat transfer to the detector if the detector is not properly located for identifying the overheat condition.
Are there many obstructions? Obstructions can limit the exposure of heat to the heat detector. It may be necessary to use additional quantity of heat detection to compensate for obstructions.
How much air flows through the hazard? Airflow can adversely affect of nozzles and dispersion of Dry Chemical Agents. It may be necessary to use additional Nozzles to compensate for air flow.
What are the dimensions of the hazard? Determining hazard dimensions allows for Agent Cylinder size(s) and Nozzle quantities to be calculated.
What is the potential for the hazard to spread to other areas of the vehicle/machine?
Additional protection may be required for those areas as well.
Does the vehicle/machine have additional hand portable extinguishers? Hand portable fire extinguishers are necessary to be used as a backup to an automatic fire suppression system. Appropriate type and rating of hand portable fire extinguishers must be considered.
3.2.6 Selecting the Appropriate Agent
After identifying ignition and fuel sources (see Sections 3.2.1 and 3.2.2), the appropriate fire suppression agent must be selected.
ABC Dry Chemical - Works well on all Class A, B, and C fires. See the latest version of the Dry Chemical System Manual (P/N 13980) located on the Amerex website at www.amerex-fire.com.
Purple K Dry Chemical - Works well on Class B fires. See the latest version of the Dry Chemical System Manual (P/N 13980) located on the Amerex website at www.amerex-fire.com.
ICE Liquid Agent - Works well on Class A and B fires and is good for cooling hot surfaces (turbochargers, exhaust manifolds), but must not be used on electrically energized equipment (batteries, alternators, starters). See the latest version of the ICE System Manual (P/N 22012) located on the Amerex website at www.amerex-fire.com.
3.2.7 Selecting the Appropriate Method of Detection
After identifying vehicle hazard areas, it is necessary to select the appropriate form of detection for those areas. See the applicable electronics manual located on the Amerex website at www.amerex-fire.com.
Spot Heat Detectors (SHD) - Localized area devices that react to “set point” temperatures of 280ºF (138ºC), 350ºF (177ºC) or 450ºF (232ºC).
Linear Heat Detectors (LHD) - Broad area “linear wire” devices of various lengths, that have large surface area for heat detection with a “set point” of 356ºF (180ºC).
3.2.8 Selecting Methods of Actuation
If automatic actuation of any Agent Cylinders in the Amerex Fire Suppression System is selected, a manual means of actuation is also required. At least one manual means of actuation must be located within reach of the vehicle operator during normal vehicle operation. Additional manual means of actuation should be located conveniently in accessible areas along paths of egress. Such manual actuation devices include:
Manual Actuation Button (P/N 14053) - An electronic button located in the drivers area or other locations accessible in the event of a fire.
Manual or Manual/Electric Actuator (P/N 10210 or 23600) - Pneumatic actuation device located in the drivers area or other locations accessible in the event of a fire.
Reference the appropriate Amerex Fire Suppression Installation, Operation and Maintenance Manual.
Chapter 4: System Design, Operation & Installation This Chapter describes design and installation of the Amerex Circuit Monitor and Control Panel system. For mechanical components such as nozzles, agent cylinders and pneumatic actuation devices see Installation, Operation and Maintenance manual 13980.
4.1 Steps to System Design
The appropriate quantity and selection of agent cylinders, nozzles and heat detection devices should be made along with an idea of how the electronic programming should be set up after a hazard analysis has been completed.
The electronic panels must be properly located and installed (See Section 4.2).
The appropriate heat detection devices and manual means of system activation must be located and installed. (See Section 4.3)
Appropriate lengths and selection of wiring harnesses must be made to accommodate the particular style of heat detection device. Appropriate wiring paths must be made from the heat detection device to the electronic panels. (See Section 4.4).
Appropriate lengths and selection of wiring harnesses must be made to accommodate the release zone circuit(s). Appropriate wiring paths must be made from the release zone(s) to the electronic panels. (See Section 4.5).
Any auxiliary input/output devices shall be selected and located/installed. Wiring for such devices must be installed. Proper termination of the wiring harness must be performed (See Section 4.6).
The vehicle power input wiring must be installed. (See Section 4.6).
Once all wiring connections are made, Control Panel testing and programming must be performed (See Section 4.7).
4.2 Electronic Panel Installation
All electronic panels must be mounted in convenient locations permitting periodic maintenance and inspection along with minimal wiring and cable lengths. Proper routing of all wiring and cables to each system component is required and should be considered when choosing an appropriate location. Any obstacles, moving parts, hazard areas, or bulkheads that may inhibit complete connection of all system components or cause damage to components must be avoided. The Circuit Monitor and the Control Panel must be mounted in a location where the audio and visual indicators on the face of the panel may be seen and heard from the operator’s seat. The panel should be mounted in a dry location safe from any potential weather, moisture, and excessive vibration. Consider the most convenient routing path of the mating cables to determine whether a back or bottom connection panel is best.
#10 (5 MM) FASTENERS (QTY 4)
MOUNTING SURFACE
4.2.1 Back Connection Mounting Option (P/N 17309/17311)
Both Panels (P/N 17309/17311) mount in the same fashion as shown in Figure 4.2.1a.
Using the dimensions shown in Figures 2.1.1 and 2.1.3, cut a rectangular slot to accept the back connection ports of the panel. Match drill four holes for mounting screws.
Assemble the panel to the mounting surface using the appropriate hardware (See Figure 4.2.1a).
Figure 4.2.1a
4.2.2 Bottom Connection Mounting Option (P/N 17308/17310)
Both Panels (P/N 17308/17310) mount in the same fashion as shown in Figure 4.2.2.
Match drill four holes for mounting screws using dimension shown in Figures 2.1.2 and
2.1.4. Assemble the panel to the mounting surface using the appropriate hardware (See Figure 4.2.1b).
MOUNTING SURFACE
#10 (5 MM) FASTENERS (QTY 4)
Figure 4.2.2
INSTALLED
INSTALLED
P-CLAMP (P/N 18720) FOR LHD P/N 20075
P-CLAMP (P/N 21806) FOR LHD P/N 20083
2 1/2” MIN.
BEND RADIUS
EOL (P/N 14010)
LHD
(P/N 20075, SHOWN)
CLASS B
DETECTION LEAD
MOUNTING SURFACE
(HAZARD SIDE) Figure 4.3.1a
4.3 Detection Components Installations
Amerex offers several styles of heat detection devices that can be utilized in the Vehicle Fire Suppression System. Among those devices are linear heat detectors and spot heat detectors.
4.3.1 Linear Heat Detector (LHD)
The Linear Heat Detector is a preset 356ºF (180ºC) heat sensing device capable of sensing an overheat condition at any point along its routed path. All LHDs must be installed in accordance with the following instructions:
The LHD must be installed in a hazard area where the potential for fire or overheat conditions exist.
The LHD must be installed in areas where potential damage resulting from normal vehicle operation will not occur. The LHD cannot be chafed, cut, bent or crushed.
The LHD with protective spring (P/N 20083) should be used when extra protection of the LHD is needed.
The LHD wire must not be installed within any hazard area that exceeds 256°F during normal operating conditions. Physical contact with any high heat surfaces exceeding 256°F is not permitted.
Selection of the LHD length should be such that it adequately covers the hazard area but is not excessively long, reducing the potential of damage. The LHD must not interfere with routine vehicle maintenance.
The LHD must be installed in the Class B detection circuit. Multiple LHDs can be connected in series or used in the same circuit, but combined length of all LHDs used in a single circuit must not exceed 100 feet (30.4m).
The cable should be mounted high in the hazard compartment where higher temperatures are prevalent in overheat conditions.
The LHD must not be installed taught without strain relief. The LHD must not be crimped, pinched or bent beyond it’s minimum bend radius of 2 1/2”.
Each LHD must be installed using padded p-clamps (See Figure 4.3.1a) or the p-clamps can be substituted with cable ties and rubber sleeves (See Figure 4.3.1b). If p-clamps are used, LHDs without the stainless steel spring wire (P/N 20075) will use a 3/16” padded p-clamp (P/N 18720), while LHDs with the protective stainless steel spring wire (P/N 20083) will use a 3/8” padded p-clamp (P/N 21806). The LHD must be secured a minimum of every 18 inches.
Use of cable ties and rubber sleeve material is permitted only when using Amerex kits (P/N 23005 or P/N 23006). If using LHDs without the protective spring (P/N 20075), the 3/16” LHD Clamp Kit (P/N 23005) must be used, while LHDs with the protective spring (P/N 20083) will require the 3/8” LHD Clamp Kit (P/N 23006). The LHD must be secured to supporting structure by cinching cable tie over hose, LHD, and structure as shown. The LHD must be secured a minimum of every 18 inches.
4.3.2 Spot Heat Detector (SHD)
The Spot Heat Detector (SHD) is a preset heat sensing device designed to detect heat in localized areas of the hazard compartment. Three SHDs are available with preset temperature set points and mounting styles. All Spot Heat Detectors (SHD) must be installed in accordance with the following instructions:
The SHD must be installed in a hazard area where the potential for fire or overheat conditions exist. Normal ambient operating temperature should be approximately 100ºF below the set point temperature of the SHD used in that hazard area. The wiring portion of the SHD must not exceed 300ºF for extended periods of time.
The SHD can be mounted in any orientation as long as the metallic sensor tip is subjected to the hazard area that is to be protected. Locate the SHD where mud, oil or foreign debris do not interfere with the sensor tip. Locations subject to environmental extremes should also be avoided.
The SHD and its wiring must be installed in a location allowing access for testing and maintenance.
The SHD sensor is vibration resistant. However, do not install the sensor and wiring in locations with different vibration characteristics. For example, the sensor should not be mounted on an engine and the wiring fixed to the chassis unless proper cable routing and support are provided.
Secure the SHD sensor wiring using a padded p-clamp located on or within 4” of each connector (See Figure 4.3.2a).
The bracket style SHDs (P/N 14087/14088) must be mounted using their standard bracket and the appropriate hardware (See Figure 4.3.2a). The bulkhead style SHD (P/N 16615) must be mounted in a bulkhead configuration (See Figure 4.3.2b) by drilling a single 25/32”-7/8” hole through the bulkhead (3/16” MAX thickness) and inserting the SHD. Secure by threading the 1 1/8” jam nut to the threaded portion of the SHD using a medium grade thread locking compound. Tighten to a maximum of 10 inch-lbs.
LHD (P/N 20075)
3/16” RUBBER SLEEVE
MOUNTING STRUCTURE
CABLE TIE
Figure 4.3.1b
3/16” LHD CLAMP KIT
(P/N 23005)
LHD (P/N 20083)
3/8” RUBBER SLEEVE
MOUNTING STRUCTURE
CABLE TIE
3/8” LHD CLAMP KIT
(P/N 23006)
SHD (P/N 16615)(JAM
NUT REMOVED)
1/4 (6 MM) FASTENERS
(QTY 2)
MOUNTING SURFACE
(HAZARD SIDE)
4.3.3 Manual Actuation Button Installation (P/N 14053)
A fire suppression system is required to have at least one manual means of system actuation or release of the fire extinguishing agent. This manual release must be located within an operator’s reach or along a path of egress. Amerex offers two methods of manual actuation. The first is a manual means of pneumatic actuation using nitrogen cartridges within a pneumatic actuation network. Reference the appropriate Amerex Fire Suppression Installation, Operation and Maintenance Manual (P/N 13980) for installation instructions. The second option is a Manual Actuation Button as part of the Fire Suppression System. This button is a normally open switch that closes when the red “FIRE” button is pressed. The button is installed in the Class B detection circuit and can be flush mounted by drilling a single 1 1/2”-1 5/8” hole through a surface (7/16” MAX thickness) and inserting the Button (See Figure 4.3.3a). Attach using appropriate hardware. The button can also be surface mounted (See Figure 4.3.3b) using appropriate hardware. Use the dimensions shown in Figure 2.6.
SHD (P/N 14087/14088)
MOUNTING SURFACE
(HAZARD SIDE)
Figure 4.3.2a
Figure 4.3.2b
SENSOR TIP JAM NUT
P-CLAMP
1/4-20 FASTENERS
(QTY 4)
MOUNTING SURFACE
BUTTON (P/N 14053)
1/4-20 FASTENERS
(QTY 4)
MOUNTING SURFACE
Figure 4.3.3a Figure 4.3.3b
P-CLAMP SHD (P/N 14087/14088)
4.3.4 100 PSI Pressure Switch (P/N 22574/22573)
The 100 PSI Pressure Switch is a normally open used to indicate that a system actuation has occurred by means of manual actuation via the pneumatic actuation network. Reference the appropriate Amerex Fire Suppression Installation, Operation and Maintenance Manual for 100 PSI Pressure Switch and pneumatic actuation network installation instructions. The switch is connected to the Class B detection circuit of the system.
4.4 Detection Circuits
Detection: The Circuit Monitor and Control Panel can operate up to two detection zones and one releasing zone. The choices for detection are spot heat detectors, line-ar heat detectors, remote manual actuation buttons. The 100 PSI Switch can also be connected in the detection circuit to signal the panel of a pneumatic manual actuation, but does not act as a heat detection device. These Class B devices can be used in any combination by connecting in series. An End of Line Module (EOL) is always re-quired at the end of the Class B circuit. All detection cables and components are color coded green.
H
D
L
D
P
S I
S W
IT
C
C
A S
S B
D E
V
IC
E S
O
P T
IO
N
A L
M A
N U
A
R
E L
E A
E
U T
T O
N
CLASS B DET. HAZARD CABLE
(SEE PARTS LIST) (OPTIONAL)
LABELED DETECTION
ZONE 1 / ZONE 2
CIRCUIT MONITOR OR
CONTROL PANEL
(CONTROL PANEL SHOWN)
EOL (P/N 14010)
DETECTION LEAD
(SUPPLIED WITH CIRCUIT
MONITOR AND CONTROL
PANEL)
GREEN COLOR
CODED FOR
DETECTION CIRCUIT
SEE APPROPRIATE VEHICLE SYSTEMS MANUAL P/
N 13980 FOR CONNECTING LINEAR ACTUATORS TO
CONTROL HEADS AND OR OTHER DEVICES IN THE
SYSTEM AT WWW.AMEREX-FIRE.COM WEBSITE.
Figure 4.5
POWER CONNECTION
LEAD, SEE PARTS LIST
FOR PART NUMBERS AND
ASSOCIATED LENGTHS
(OPTIONAL POWER LEAD
EXTENTION AVIALABLE)
LINEAR ACTUATOR
(P/N 22579)
4.5 Actuation Circuits (Release Zones)
Actuation circuits (release zones) connect to a Linear Actuator (P/N 22579) for actuation of the Amerex Fire Suppression System. The release zone will activate up to 4 Linear Actuators (22579) with the use of the optional 2 or 4 way splitter. An example schematic is shown below, which includes cables and Linear Actuators. All actuation cables and components are color coded yellow. Reference the appropriate Amerex Fire Suppression Installation, Operation and Maintenance Manual for Linear Actuator installation instructions.
OPTIONAL TWO WAY LINEAR
ACTUATOR SPLITTER (P/N 17091)
OPTIONAL FOUR WAY
LINEAR ACTUATOR
SPLITTER (P/N 14128)
TO LINEAR
ACTUATORS
P/N 22579
TO LINEAR
ACTUATORS
P/N 22579
LINEAR ACUATOR
LEAD (SEE PARTS
LIST)
RED COLOR CODED
FOR POWER CIRCUIT
YELLOW COLOR
CODED FOR
ACTUATION CIRCUIT
CIRCUIT MONITOR OR
CONTROL PANEL
(CONTROL PANEL SHOWN)
4.6 Input/Output Devices
4.6.1 Vehicle Power Input
The Power Connection Lead, see Figure 4.4b, is used to bring power from the vehicle battery (12 or 24vdc) to the panel. It is supplied with a fuse holder and a 10 Amp fuse to protect the panel and associated circuits. The power lead is connected to the red color coded connector of the panel leads.
WARNING: USE OF THE AMEREX SUPPLIED POWER LEAD IS CRITICAL TO
PROPER FUNCTIONING AND PROTECTION OF ALL SYSTEMS ELECTRICAL
COMPONENTS. USE OF POWER SUPPPLY LEADS OTHER THAN THE TYPE
AND RATING SPECIFIED IN THIS AND ALL OTHER ASSOCIATED MANUALS
WILL VOID FACTORY MUTUAL APPROVALS AND VOID THE AMEREX
WARRANTY.
WARNING: AT NO TIME SHOULD THE BACK-UP BATTERY BE USED AS THE
MAIN POWER SOURCE. THE SYSTEM MUST BE CONNECTED DIRECTLY TO
THE VEHICLE BATTERY AS A MAIN POWER SOURCE.
4.6.2 Agent Cylinder Pressure Switch Input
The Control Panels (P/N 17310 and 17311) include two connection leads for the wiring of a pressure switch (or switches in the case of multiple agent cylinders). Pressure inside the agent cylinder holds electrical contacts normally closed. Loss of agent cylinder pressure will result in a “Service System” LED flash seven times at the control panel and the audible alarm will pulse, on systems so equipped. The Agent Cylinder Pressure Switch Leads are two blue color coded single conductor leads terminated with single conductor male and female plugs. These plugs are connected as supplied. To connect the agent cylinder pressure switch leads, unplug these leads from each other and attaché the two male and female leads from the pressure switches. If no pressure switch is used, the pressure switch leads from the panel must be plugged together to get the green System OK LED.
TO PRESSURE SWITCH RELAY CIRCUIT
Figure 4.6.2
BLUE COLOR CODED
FOR PRESSURE
SWITCH CIRCUIT
CONTROL PANEL
4.6.3 Output Fire Signal Connections
The Control Panels (P/N 17310 and 17311) include a connection lead for engine shutdown equipment or auxiliary safety equipment such as air dampers, warning horns or lights, See Figure 4.6.2. The relay circuit provides a normally open and normally closed contact to allow wiring for “energized to run” or “energized to stop” configurations. It is the responsibility of the installer to gain sufficient understanding of vehicle operation to determine:
If the device or equipment is “energized to run” or “energized to stop” (Power supplied to terminate normal operations). The relay is rated for maximum of 5 Amps and can be used with either 12 VDC or 24 VDC systems. If the relay is connected to a vehicle multiplex system or shutdown device the device program allows a delay or logic algorithm for mechanical bounce of 30 milliseconds.
WARNING: THE RELAY CONTACTS ARE RATED FOR A MAXIMUM OF 5 AMPS.
THIS VALUE MUST NOT BE EXCEEDED.
Any device that is wired to the relay contacts must draw its own current from an independent power lead fused with a 5 Amp type AGC fast blow fuse. In addition, the internal relay “common” contact is also protected with an internal self- resetting circuit breaker.
The color code for the relay wiring is as follows:
Common – Red
Normally Closed – Black
Normally Open – White
Use Amerex Hazard Wire or other insulated wire of AWG 18 or equivalent for connection purposes.
Two examples of relay usage are shown IN Figure 4.6.3a and 4.6.3b. They are for reference only. Before connecting the relay it is advisable to consult the vehicle manufacturer for proper engine shutdown methods. Not all vehicle electrical systems are the same, and improper shutdown procedures can damage certain vehicle components.
Example 1:
Normally open energize to stop. 12 volt external
Siren.
Red
Black (Not Used)
To vehicle negative ground
White (Normally Open)
(Common)
Figure 4.6.3a
Example 2:
Normally closed energize to run. 12 volt vehicle ignition.
White (Not Used)
Black
Red
To vehicle negative ground
Existing wiring to fuel pump, ignition coil, etc.
(Normally Closed) (Common)
Figure 4.6.3b
Table 4.6.3
Relay Delay Programming The delay for fire relay can be programmed on the Control Panel (the default delay is 0 seconds). The delays can be set from 0 to 15 seconds in 5 second intervals. To program delay use the following procedure:
1.) Press and Hold the “Relay Reset” and “Alarm Silence” buttons for 20 seconds.
2.) The panel will chirp once and the “System OK” LED will flash.
3.) Press the “Relay Reset” button “x” times for the relay delay.
4.) After 10 seconds has lapsed, the panel will chirp twice and the “System OK” LED will stop flashing.
Fire Relay Delay Values
After programming sequence is completed, verify correct value by pressing and holding the “Push to Test” button.
Setting Delay to Factory Default Value To return the fire activation relay to factory default value enter programming mode as described in “Relay Delay Programming (above), press and hold the “Push to Test” button (located under the Amerex logo) for five seconds. The alarm will sound and the “Relay” and “Silence” LED’s will flash once to acknowledge that the delay has been reset to factory default value of zero seconds (no delay).
Number of Times Button is Pressed Seconds of Delay
1 0
2 5
3 10
4 15
Trouble Source Number of Flashes
Main Power Trouble 1
Heat Zone 1 Trouble 2
Heat Zone 2 Trouble 3
Actuator Trouble 4
Backup Battery Trouble 5
Pressure Switch 7
Table 4.7.1b
4.7 Initial Commissioning
4.7.1 Circuit Monitor Operation (P/N 17308 and 17309)
The Circuit Monitor panel communicates the system status through LED codes as follows:
System OK When the panel is plugged in to an operational configuration the system will illuminate the green “System OK” LED.
System Alarm When either the heat detection circuit has detected fire or the Manual Actuation Switch has been depressed. The following sequence will occur:
“System OK” LED will turn off.
The audible alarm will sound continuously.
The “FIRE” LED will illuminate.
The system will discharge.
The “Service System” LED will illuminate.
The “Service System” LED will flash four times to indicate Actuator Trouble.
When the “FIRE” LED first comes on it will flash a number of times to indicate which zone is in alarm.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .