Attachment A 23100 - Glenwood 90PCT SET.pdf
PDF 7 MB Posted
- Solicitation number
- 56076
- Issued by
- Danville City, Virginia
About this file
The provided document is an Attachment A for a Request for Proposal (RFP) issued by the Danville Public School System (Virginia) for the complete turnkey installation of a new HVAC system at the Glenwood school. The scope of work includes furnishing and installing all equipment, ductwork, piping, and accessories as specified in the 90% progress set of mechanical drawings. The bidder will be responsible for providing the labor, materials, and equipment necessary for a complete and functional HVAC system. This RFP has a response deadline, but no specific award date is provided. The contract term is not explicitly stated.
The RFP does not provide details on pricing terms, set asides, incumbents, funding requirements/sources, or dollar amounts. However, it does require the successful contractor to coordinate with the building owner's asbestos abatement contractor prior to construction, as the building will remain occupied during the project. The contractor must also provide shop drawings, product data, and samples for approval, and ensure all work is performed in compliance with applicable codes and standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFP 2324-518 - Glenwood HVAC RFP Final.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL GENERAL NOTES
AD
D
M
22x12
NOTE: ALL DUCT DIMENSIONS SHOWN ON DRAWINGS ARE IN INCHES AND
INDICATE INSIDE FREE AREA UNLESS NOTED OTHERWISE.
MANUAL VOLUME DAMPER (MVD)
MOTOR OPERATED DAMPER (MOD) W/ACCESS DOOR
FIRE DAMPER WITH ACCESS DOOR
ACCESS DEVICE - SEE SPECIFICATIONS
SUPPLY DUCT TURNING UP
RETURN DUCT TURNING DOWN
FLEXIBLE CONNECTION
SUPPLY DIFFUSER
RETURN GRILLE OR REGISTER
EXHAUST GRILLE OR REGISTER
PLAN KEY NOTES
REVISION NOTES
RECTANGULAR DUCT
AC CONDENSATE DISCHARGE LINE
DIRECTION OF FLOW
DUCTWORK SYMBOLS MISCELLANEOUS ABBREVIATIONS AND SYMBOLS
AIR DEVICE SYMBOLS
EQUIPMENT TAGS
DUCTWORK LEGEND
AHU-X
EQUIPMENT TYPE
S-1
6"Ø AIR DEVICE TAG
CFM
DEVICE
TYPE
NECK SIZE
LINEAR DIFFUSER
C
W
CARBON DIOXIDE CO2 SENSOR
WALL SWITCH
T THERMOSTAT
AD ACCESS DOOR
AHU AIR HANDLING UNIT
APD AIRSIDE PRESSURE DROP
BAS BUILDING AUTOMATION SYSTEM
BHP BRAKE HORSEPOWER
BLDG BUILDING
CFM CUBIC FEET PER MINUTE
CO CLEAN-OUT
CU CONDENSING UNIT
D AC CONDENSATE DRAIN
DB DRY BULB
DDC DIRECT DIGITAL CONTROL
DN DOWN
DX DIRECT EXPANSION
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
ELEC ELECTRICAL
ESP EXTERNAL STATIC PRESSURE
ABBREVIATIONS
EX, (E) EXISTING
FD FIRE DAMPER
FLA FULL LOAD AMPERES
FT FOOT, FEET
HR HEATING HOT WATER RETURN
HS HEATING HOT WATER SUPPLY
LAT LEAVING AIR TEMPERATURE
MBH THOUSAND BTUH
MCA MINIMUM CIRCUIT AMPACITY
MECH MECHANICAL
MOP MAX. OVERCURRENT PROTECTION
N/A NOT APPLICABLE
NTS NOT TO SCALE
OA OUTSIDE AIR
PD PRESSURE DROP
PSI POUNDS PER SQUARE INCH
QTY QUANTITY
RA RETURN AIR
RS / RL REFRIGERANT SUCTION / LIQUID LINE SET
RTU ROOFTOP UNIT
SA SUPPLY AIR
SD SMOKE DETECTOR
SP STATIC PRESSURE
TEMP TEMPERATURE
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UC UNDERCUT
UH UNIT HEATER
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
VTR VENT THROUGH ROOF
W/ WITH
W/O WITHOUT
WB WET BULB
WMS WIRE MESH SCREEN
DUCT MOUNTED GRILLE OR REGISTER
RETURN DUCT TURNING UP
SUPPLY DUCT TURNING DOWN
UNIT NO.
GENERAL:
1. LU + S ENGINEERS HAS NOT PERFORMED ANY ASBESTOS INSPECTION AND IS NOT AWARE OF, NOR WILL BE RESPONSIBLE FOR ANY ASBESTOS RELATED ITEMS. ASBESTOS RELATED ITEMS WILL BE HANDLED UNDER A SEPARATE CONTRACT WITH THE BUILDING OWNER. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNERS ASBESTOS ABATEMENT CONTRACTOR FOR TESTING AND REMOVAL PRIOR TO ANY ACTUAL
CONSTRUCTION.
2. THE BUILDING IS TO REMAIN OCCUPIED DURING THE ENTIRE CONSTRUCTION PERIOD. THE CONTRACTOR SHALL VERIFY IN ADVANCE WITH THE OWNERS REPRESENTATIVE FOR ACCESS TO AREAS OF CONSTRUCTION. ANY AND ALL SYSTEM SHUTDOWNS WILL REQUIRE SCHEDULING WITH THE OWNERS REPRESENTATIVE. THE CONTRACTOR IS ADVISED THAT SOME AREAS OF CONSTRUCTION WILL BE PERFORMED AFTER NORMAL WORKING
HOURS.
3. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS BEFORE COMMENCING WORK AND SHALL NOTIFY THE ENGINEER IF A CONDITION EXISTS
WHICH PREVENTS THE CONTRACTOR FROM ACCOMPLISHING THE INTENT OF THE DOCUMENTS.
4. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT FOR THE COMPLETION OF ALL MECHANICAL WORK SHOWN ON THE DRAWINGS AND/OR SPECIFIED. THIS WILL INCLUDE ANY INCIDENTAL ACCESSORIES NECESSARY TO MAKE THE WORK COMPLETE IN ALL RESPECTS AND
READY FOR OPERATION.
5. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, PRODUCT DATA AND SAMPLES TO THE ENGINEER FOR APPROVAL. WRITTEN SUBMITTALS SHALL BE FORWARDED IN SIX (6) COPIES AND CLEARLY MARKED TO INDICATE SPECIFIC ITEM, PERFORMANCE OR CAPACITIES, SIZE, COLOR AND LOCATION OF USE. ALL SUBMITTALS SHALL BE CHECKED, DATED, PRESENTED AND LABELED IN A CLEAR AND THOROUGH MANNER. SUBMITTALS SHALL INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING: AIR HANDLING UNITS, CONDENSING UNITS, EXHAUST FANS, ELECTRIC DUCT HEATERS, UNIT HEATERS, DUCT ACCESSORIES, AIR DEVICES AND ALL PIPING AND ACCESSORIES. ALL ITEMS LISTED ON DRAWINGS AND/OR IN SPECIFICATIONS ARE NOT INTENDED TO PRECLUDE THE USE OF OTHER PRODUCTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MODIFICATIONS, REROUTING, RELOCATION AND VARIATIONS AT NO EXTRA COST TO THE OWNER WHEN AND IF SUBSTITUTED ITEMS ARE APPROVED FOR USE. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE STATE AND LOCAL CODES, THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), THE ENVIRONMENTAL
PROTECTION AGENCY (EPA) AND THE LOCAL AUTHORITIES HAVING JURISDICTION.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL COORDINATION OF TRADES WITH STRUCTURAL, PLUMBING, MECHANICAL, ELECTRICAL AND SPRINKLER SYSTEMS AND PROVIDING NECESSARY OFFSETS, TRANSITIONS, PIPE REROUTING, MATERIALS AND LABOR TO ARRANGE EQUIPMENT, DUCTWORK AND PIPING AS REQUIRED FOR A PROPER AND ACCESSIBLE INSTALLATION. CLOSE COORDINATION WILL BE REQUIRED FOR ALL SERVICES
ABOVE CEILING.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL LOW VOLTAGE WIRING AND CONDUITS SERVING ANY AUTOMATIC TEMPERATURE CONTROLS RELATED ITEMS. THIS INCLUDES BUT IS NOT LIMITED TO THERMOSTATS, TIMECLOCKS, MOTOR OPERATED DAMPER ACTUATORS, SMOKE DETECTORS, DUCT PRESSURE SENSORS, STATIC PRESSURE CONTROLLERS, END SWITCHES, FAN INTERLOCKS, CONTACTORS AND ALL ACCESSORIES FOR A FULLY
FUNCTIONING AUTOMATIC TEMPERATURE CONTROLS SYSTEM.
8. INFORMATION ON EXISTING SERVICES WAS TAKEN FROM LIMITED FIELD SURVEY.
9. ALL PENETRATIONS SHALL BE SLEEVED. PENETRATIONS IN RATED ENCLOSURES SHALL BE SEALED WITH APPROVED FIRE RESISTIVE MATERIALS.
PENETRATIONS IN EXTERIOR ENCLOSURES SHALL BE SEALED WEATHERTIGHT. PENETRATIONS IN FINISHED AREAS SHALL HAVE ESCUTCHEON PLATES
OR FINISHED FLANGES.
10. ALL ITEMS, EQUIPMENT AND ACCESSORIES INSTALLED IN PLENUMS SHALL BE PLENUM RATED.
DEMOLITION:
1. THE CONTRACTOR SHALL CLOSELY COORDINATE LIMITS OF DEMOLITION WITH NEW WORK FOR THIS AREA.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING SCRAP MATERIALS AND DEBRIS ASSOCIATED WITH THIS WORK FROM THE SITE. ASCERTAIN
AS TO WHAT MATERIAL OR EQUIPMENT IS TO REMAIN IN POSSESSION OF THE OWNER.
3. ALL EQUIPMENT, DUCTWORK, PIPING, WIRING, ETC. DESIGNATED FOR REMOVAL SHALL INCLUDE ALL HANGERS, SUPPORTS AND APPURTENANCES. ANY SERVICE NOT TOTALLY REMOVED OR REUSED SHALL BE CAPPED, SEALED, OR OTHERWISE TERMINATED IN AN ACCEPTABLE MANNER.
4. WHEN EQUIPMENT CONTAINING REFRIGERANT IS DESIGNATED TO BE REMOVED, EXISTING REFRIGERANT IN THE SYSTEM SHALL BE RECLAIMED AND
DISPOSED ACCORDING TO FEDERAL AND STATE GUIDELINES AND REGULATIONS.
DUCTWORK:
1. PROVIDE FINAL CONNECTION TO ALL EQUIPMENT FURNISHED BY OWNER AND/OR OTHERS.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR BALANCING OF SYSTEM AS REQUIRED TO OBTAIN INDICATED AIRFLOW AT EACH AIR DEVICE AND/OR PIECE OF EQUIPMENT ACCORDING TO SMACNA STANDARDS (NEBB OR AABC STANDARDS ARE ALSO ACCEPTABLE).
3. THE ROUTING OF ALL DUCTWORK AS SHOWN ON THE DRAWINGS IS DIAGRAMMATIC ONLY, INTENDING TO SHOW GENERAL RUNS AND LOCATIONS OF EQUIPMENT, DUCTWORK AND SPECIALTIES. CONTRACTOR WILL BE RESPONSIBLE FOR THE EXACT LOCATION AND COORDINATION OF ALL ITEMS.
4. ALL DUCTWORK SHOWN ON PLANS OR INDICATED BY NOTES SHALL BE CONCEALED ABOVE CEILING OR IN WALLS UNLESS NOTED OTHERWISE.
5. SUPPLY DUCTWORK SHALL BE LOW PRESSURE GALVANIZED SHEET METAL WITH FLEXIBLE DUCT BRANCHES.
6. RETURN AIR AND EXHAUST AIR DUCTWORK SHALL BE LOW PRESSURE GALVANIZED SHEET METAL.
7. ALL DUCTWORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION (SMACNA): DUCT CONSTRUCTION STANDARDS, LATEST EDITION; SIZED PER EQUAL FRICTION METHOD BASED ON 0.07" (LOW PRESSURE) FRICTION LOSS PER 100 FT OF DUCT. ANY DEVIATIONS FROM THE FITTING TYPES AS SHOWN ON THE PLANS SHALL BE APPROVED BY THE ENGINEER PRIOR TO ANY
FABRICATION OR INSTALLATION.
8. DUCTWORK PRESSURE CLASSIFICATIONS: ALL LOW PRESSURE DUCTWORK SHALL BE CONSTRUCTED AT MIN. +/- 2.0 IN WG. IF DUCTWORK'S FORESEEN STATIC PRESSURE IS HIGHER THAN +/- 2.0 IN WG (FOR LOW PRESSURE), THE NEXT AVAILABLE PRESSURE CLASS THAT IS GREATER THAN THE
FORESEEN STATIC PRESSURE SHALL BE USED.
9. DUCTWORK SEALING: ALL DUCTWORK SHALL BE SEALED ACCORDING TO SMACNA 'STANDARD DUCT SEALING REQUIREMENTS TABLE'. ALL INDOOR DUCTWORK SHALL BE SEALED AT MINIMUM 'B' LEVEL; ALL OUTDOOR DUCTWORK OR DUCTWORK LOCATED IN UNCONDITIONED SPACE SHALL BE SEALED
AT 'A' LEVEL.
10. ALL DUCT DIMENSIONS ARE IN INCHES AND ARE INSIDE CLEAR.
11. ALL DUCTWORK INCLUDING THE DUCT, DUCT FITTINGS, PLENUMS, AIR DEVICES, ETC. SCHEDULED TO BE WRAPPED (DW) SHALL BE INSULATED WITH FLEXIBLE FIBERGLASS INCLUDING FLAME RETARDANT LAMINATED KRAFT REINFORCED ALUMINUM FOIL VAPOR BARRIER. MINIMUM DENSITY SHALL BE
0.75 LB/CU FT. ALL INSULATION JOINTS SHALL BE TAPED. DUCTWRAP TAPE SHALL BE HIGH TENSILE ALUMINUM FOIL COATED ON ONE SIDE WITH A HIGH
PERFORMANCE ACRYLIC ADHESIVE.
12. PROVIDE FLEXIBLE CONNECTION AT DUCTWORK CONNECTIONS TO ALL MECHANICAL EQUIPMENT SUBJECT TO VIBRATION.
13. ALL SUB-MAIN AND BRANCH DUCTS CONNECTION TO TRUNK DUCTS, SHALL HAVE BOOT FITTINGS WITH 45 DEG. FLARE (SQUARE TO ROUND CONNECTIONS SHALL ALSO HAVE 45 DEG. FLARE). PROVIDE AND INSTALL ALL REQUIRED DAMPERS AT BRANCH DUCTS TO ALLOW SYSTEMS TO BE BALANCED PER DRAWINGS. ALL DAMPERS SHALL BE INSTALLED AS CLOSE AS POSSIBLE TO THE BRANCH TAP, IN ORDER TO REDUCE NOISE AT
DIFFUSERS/GRILLES.
14. ALL BRANCH DUCT RUNOUTS TO DIFFUSERS SHALL BE FULL CONNECTION SIZE OF DIFFUSER, UNLESS NOTED OTHERWISE.
15. INSULATED FLEXIBLE DUCT SHALL BE CUT TO EXACT LENGTH REQUIRED (MAXIMUM 5'-0" LONG). MAINTAIN MINIMUM 1.5 RADIUS RATIO WHERE BENDING OR OFFSETTING IS NECESSARY. MAXIMUM BEND SHALL BE NO MORE THAN 90 DEGREES. NO MORE THAN ONE CHANGE OF DIRECTION WILL BE ALLOWED IN EACH FLEXIBLE DUCT SECTION. COILING OR UNNECESSARY OFFSETS OF DUCTWORK SHALL NOT BE PERMITTED.
16. ALL DUCT PENETRATIONS ON SMOKE PARTITION SHALL BE SEALED AIR-TIGHT.
EQUIPMENT:
1. PROVIDE SMOKE DETECTORS FOR ALL MECHANICAL EQUIPMENT PER APPLICABLE CODE AND NFPA. ALL SMOKE DETECTORS SHALL BE INTERLOCKED
WITH THE CENTRAL ALARM SYSTEM IF SUCH A SYSTEM EXISTS.
2. PROVIDE SPRING TYPE VIBRATION ISOLATORS FOR ALL EQUIPMENT SUPPORTED FROM OR BEARING ON ANY PART OF THE BUILDING STRUCTURE.
3. INSTALL REFRIGERANT PIPING, VALVES AND ALL ACCESSORIES REQUIRED TO ENSURE A COMPLETE, SAFE AND OPERATING SYSTEM. THE DESIGN, SIZING, PITCHING AND LAYOUT OF THE REFRIGERANT PIPING SYSTEMS SHALL BE MADE BY OR APPROVED BY THE REFRIGERANT EQUIPMENT MANUFACTURER. REFRIGERANT PIPING (ALL SIZES) SHALL BE TYPE M SOFT DRAWN COPPER WITH WROUGHT COPPER BRAZED FITTINGS. THE REFRIGERANT SUCTION AND LIQUID PIPING SHALL BE INSULATED. INSULATION SHALL BE FLEXIBLE, ELASTOMERIC, CLOSED CELL, TUBULAR MOLDED TO ACCOMMODATE PIPING, WATER RESISTANT, OZONE RESISTANT, MINIMUM DENSITY 6 LB/CF, MAXIMUM THERMAL CONDUCTIVITY PER 1" THICKNESS OF
0.27 AT 75 DEGREES F. ALL JOINTS TRANSVERSE AND LONGITUDINAL, SHALL BE SEALED.
CONTROLS:
1. PROVIDE WALL-MOUNTED CARBON DIOXIDE SENSORS WITH READING DISPLAY AS INDICATED ON PLANS. CARBON DIOXIDE SENSORS SHALL BE DUAL WAVELENGTH WITH AUTOMATIC BASELINE ADJUSTMENT. ITS ACCURACY SHALL BE +/- 75 PPM OR 5% OF THE READING, WHICHEVER IS LESS. IT SHALL BE
PROVIDED BY ONE OF THE FOLLOWING MANUFACTURERS,
- AIRTEST - MODEL TR9294
- GREYSTONE ENERGY SYSTEM, INC. - MODEL: CD2RMC SERIES
- HONEYWELL INC. - MODEL: C7232A1016
- VERIS INDUSTRIES - MODEL: CWE SC
CARBON DIOXIDE SENSORS SHALL BE CALIBRATED BASED ON MANUFACTURER AND ASHRAE RECOMMENDATIONS. IT SHALL BE CALIBRATED AT LEAST
ONCE EVERY 12 MONTHS.
PIPING:
1. EQUIPMENT DRAIN PIPING: ALL SIZES, TYPE DWV COPPER; WROUGHT COPPER DRAINAGE PATTERN FITTINGS; 95-5 SOLDER
2. ALL PIPING TO BE SUPPORTED ON MAXIMUM 5'-0" CENTERS.
3. CLEAN, STERILIZE AND TEST ALL PIPING INSTALLED UNDER THIS CONTRACT IN ACCORDANCE WITH APPLICABLE STATE AND LOCAL CODES AND LOCAL
AUTHORITIES HAVING JURISDICTION.
4. ALL PIPING INCLUDING FITTINGS SCHEDULED TO BE INSULATED SHALL USE FLEXIBLE ELASTOMERIC INSULATION OR RIGID FIBERGLASS INSULATION.
5. THE ROUTING OF ALL PIPING AS SHOWN ON THE DRAWINGS ARE DIAGRAMMATIC ONLY, INTENDING TO SHOW GENERAL RUNS AND LOCATIONS OF PIPING, FIXTURES, AND SPECIALTIES. CONTRACTOR WILL BE RESPONSIBLE FOR THE EXACT LOCATION AND COORDINATION OF ALL ITEMS.
6. ALL PIPING SHOWN ON PLANS OR INDICATED BY NOTES SHALL BE CONCEALED ABOVE CEILING OR IN WALLS UNLESS NOTED OTHERWISE.
12"Ø ROUND DUCT
EQUIPMENT SERVICE CLEARANCE
(E) 22x12 EXISTING DUCTWORK
0-
M
.d w g
Sheet
Scale
Project NO.
Date
PROJECT NAME AND ADDRESS
SEAL
CLIENT
Revision/IssueNo. Date
SHEET TITLE
G
LE
N W
O O
D E
LE
M
EN
TA
R Y
SC
H
O O
L C
O N
VE
R
SI
O
N
H
AL
IF
AX
R
O
AD
D
AN
VI
LL
E, V
A
23100
11/08/2023
AS NOTED
Lu+S
4924 DOMINION BLVD, STE A
GLEN ALLEN, VA 23060
p: 804.925.2600 f: 804.925.2170 www.LSEngineers.net
90% PROGRESS SET
NOT FOR
CONSTRUCTION
11/08/23
NOTES AND LEGENDS
M0.1
Sheet List Table Sheet Number Sheet Title
M0.1 NOTES AND LEGENDS
M0.2 SCHEDULES
M0.3 SCHEDULES
M0.4 SCHEDULE AND DETAILS
M0.5 DETAILS AND REFRIGERANT SYSTEM DIAGRAMS
M2.1 FIRST FLOOR PLAN - MECHANICAL DUCTWORK
M2.2 BASEMENT AND SECOND FLOOR PLANS - MECHANICAL
DUCTWORK
M3.1 FIRST FLOOR PLAN - MECHANICAL PIPING
M3.2 BASEMENT AND SECOND FLOOR PLANS - MECHANICAL
PIPING
AutoCAD SHX Text
ENGINEERS
FAN SCHEDULE
UNIT LOCATION AND TYPE CFM TOTAL S.P. FAN
MOTOR DATA SELECTION BASED ON
REMARKS
NUMBER AREAS SERVED IN. W.G. RPM
HP V PH Hz MANUFACTURER MODEL NO.
EF-A TOILET CEILING 50 0.3 808 22 WATT 115 1 60 GREENHECK SP-A50-VG 1, 2
EF-B JANITOR / ELECTRICAL CLOSET CEILING 90 0.3 887 24 WATT 115 1 60 GREENHECK SP-A90-VG 1, 3
EF-C MEN'S / WOMEN'S INLINE 200 0.3 1300 1/6 115 1 60 GREENHECK SQ-080-VG 1, 2
EF-1 BASEMENT ELECTRICAL ROOM INLINE 550 0.5 1725 1/4 115 1 60 GREENHECK SQ-095-VG 1, 3
1. PROVIDE ECM FAN MOTOR
2. INTERLOCK WITH LIGHT SWITCH
3. CONTROLLED BY WALL SWITCH
PACKAGED ROOFTOP UNIT WITH GAS-FIRED BURNER SCHEDULE
EVAPORATOR FAN DATA DX COOLING DATA MODULATING HOT GAS REHEAT DATA GAS BURNER DATA ELECTRICAL DATA SELECTION BASED ON
UNIT LOCATION AND TOTAL
CFM
OA
CFM
EXT.S.P.
IN W.G.
FAN
RPM
MOTOR DATA EAT °F LAT °F
SENS.
MBH
TOTAL
MBH
EAT °F DB
/ WB
EVAP
COIL LAT
°F DB /
WB
AMBIENT
°FDB
CAPACITY
MBH
LEAVING
UNIT °FDB
LEAVING
UNIT DEW
POINT °F
TEMP
RISE °F
REHEAT COIL
LAT °F DB / WB
GAS TYPE
EAT
°F
LAT
°F
INLET
PRESS. IN.
W.C.
HEATING
INPUT MBH /
OUTPUT
MBH
MCA MCOP V PH Hz MANUFACTURER MODEL NO. EER WEIGHT REMARKS
NUMBER AREAS SERVED
HP RPM V PH Hz DB WB DB WB N P
LB
RTU-1 OUTDOOR, CONFERENCE ROOM 116 6,650 1,200 1 1,332 3 1,750 208 3 60 81.1 65.6 56.2 54.9 175.59 209.02 73 / 64 53.16 / 52.71 70 174.54 78.38 52.41 24.04 77.19 / 61.95 Y - 65 100.6 7-14 320 / 259.2 93 110 208 3 60 TRANE YSJ210A3S0M 10.8 2,500 1, 2, 3, 4, 5
1. INSTALL SMOKE DETECTOR
2. ECONOMIZER CYCLE
3. PROVIDE FACTORY DISCONNECT, VFD DRIVE AND MERV 13 FILTERS
4. SIDE SUPPLY AIR AND RETURN AIR CONNECTIONS
5. OUTSIDE AIR DAMPER CONTROLLED BY SPACE CO2 SENSOR
ELECTRIC UNIT HEATER SCHEDULE
FAN DATA BASIS OF DESIGN
UNIT LOCATION AND TYPE
MOTOR DATA
LOAD
OPER.
WEIGHT
NUMBER AREAS SERVED
CFM WATTS V PH HZ V PH KW BTUH MANUFACTURER MODEL LBS
REMARKS
UH-1 BASEMENT ELECTRICAL ROOM HORIZONTAL 400 FRACTION 208 1 60 208 3 5 17,065 MARKEL F2F5105N 35 1
UH-2 BASEMENT ELECTRICAL ROOM HORIZONTAL 400 FRACTION 208 1 60 208 3 5 17,065 MARKEL F2F5105N 35 1
WH-1 FIRST FLOOR STAIR S03 WALL MOUNTED FULL RECESSED 245 FRACTION 208 1 60 208 1 3 10,240 MARKEL F3453T1D 65 2
1. PROVIDE MOUNTING BRACKETS, DISCONNECT SWITCH, WALL MOUNTED THERMOSTAT, FAN GUARD, 24 VOLT CONTROL TRANSFORMER AND CONTACTOR.
2. PROVIDE WALL BOX, DISCONNECT SWITCH, WALL MOUNTED KEY-COVER THERMOSTAT, 24 VOLT CONTROL TRANSFORMER AND CONTACTOR.
VARIABLE REFRIGERANT FLOW - HEAT RECOVERY BRANCH CIRCUIT BOX SCHEDULE
ELECTRICAL DATA SELECTION BASED ON
UNIT LOCATION AND TYPE REFRIGERANT NO. OF PORTS CONNECTED CLG CAP BTUH CONNECTED HEAT MCA MOCP V PH Hz MANUFACTURER MODEL NO. WEIGHT REMARKS
NUMBER AREAS SERVED TOTAL (SENSIBLE) CAPACITY BTUH LBS
MBC-1 1ST FLOOR, ODU-1 MAIN R410A 12 235,739 (176,731) 284,249 1.2 20 208 1 60 MITSUBISHI TCMBM1012JA11N4 160 1
MBC-2 1ST FLOOR, ODU-2 MAIN R410A 12 94,874 (76,762) 113,783 1.2 20 208 1 60 MITSUBISHI TCMBM1012JA11N4 160 1
MBC-3 1ST FLOOR, ODU-3 SINGLE R410A 6 119,726 (87,401) 143,944 0.6 20 208 1 60 MITSUBISHI TCMBG0106SJ11N4 80 1
MBC-4 1ST FLOOR, ODU-4 MAIN R410A 12 194,903 (144,269) 233,916 1.2 20 208 1 60 MITSUBISHI TCMBM1012JA11N4 160 1
MBC-5 2ND FLOOR, ODU-5 MAIN R410A 12 218,105 (157,522) 263,300 1.2 20 208 1 60 MITSUBISHI TCMBM1012JA11N4 160 1
1. PROVIDE CONDENSATE PUMP WITH RESEVOIR AND SENSOR
VARIABLE REFRIGERANT FLOW (HEAT PUMP) - DOAS INDOOR UNIT SCHEDULE
FAN DATA
DX COIL COOLING DATA DX COIL HEATING DATA UNIT ELECTRICAL DATA SELECTION BASED ON
UNIT OUTDOOR UNIT AREA SERVED
AIR SIDE DATA COOLING LOAD AIR SIDE DATA
HEATING
NUMBER
FAN
MOTOR DATA EAT °F LAT °F
SENS. TOTAL EAT °F LAT °F
LOAD V PH Hz MCA MOCP MANUFACTURER MODEL NO. WEIGHT REMARKS
CFM RPM
V PH Hz DB WB DB WB
BTUH BTUH DB DB BTUH LBS
OAU-1 ODU-OA1 1ST FLOOR OUTSIDE AIR 900 HIGH 208 1 60 95 76 57.9 56.6 37,370 63,940 16 62 49,020 208 1 60 4.8 15 MITSUBISHI TPEFYP072OA140A 215 1, 2, 3, 4
OAU-2 ODU-OA1 1ST FLOOR OUTSIDE IAR 600 HIGH 208 1 60 95 76 57.9 56.6 24,913 42,631 16 62 32,706 208 1 60 3.3 15 MITSUBISHI TPEFYP048OA140A 130 1, 2, 3
OAU-3 ODU-OA2 1ST FLOOR OUTSIDE IAR 800 MEDIUM 208 1 60 95 76 55.7 54.5 35,413 61,953 16 68 48,879 208 1 60 4.8 15 MITSUBISHI TPEFYP072OA140A 215 1, 2, 3, 4
OAU-4 ODU-OA2 1ST FLOOR OUTSIDE IAR 600 HIGH 208 1 60 95 76 57.9 56.6 24,913 42,631 16 62 32,706 208 1 60 3.3 15 MITSUBISHI TPEFYP048OA140A 130 1, 2, 3
OAU-5 ODU-OA3 2ND FLOOR OUTSIDE AIR 800 MEDIUM 208 1 60 95 76 55.7 54.5 35,413 61,953 16 68 48,879 208 1 60 4.8 15 MITSUBISHI TPEFYP072OA140A 215 1, 2, 3
1. PROVIDE INTEGRATED CONDENSATE PUMP, AND RESERVOIR SENSOR, INSTALL AS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
2. PROVIDE DRAIN PAN LEVEL SENSOR MODEL DPLS2
3. 100% OUTSIDE AIR UNIT
4. OUTSIDE AIR DAMPER CONTROLLED BY SPACE CO2 SENSOR(S)
VARIABLE REFRIGERANT FLOW (HEAT PUMP) AIR-COOLED OUTDOOR UNIT SCHEDULE
PROPELLER FAN DATA COMPRESSOR DATA NOMINAL CAPACITY ELECTRICAL DATA
SYSTEM
BASIS OF DESIGN
UNIT LOCATION NO CFM NO.
TYPE
COOLING HEATING MCA MOCP V PH Hz REFRIGERANT
CONNECTED
MANUFACTURER MODEL WEIGHT
REMARKS
NUMBER AREA SERVED MBH MBH TYPE CAPACITY (% OF NOM) LBS
ODU-OA1 GROUND, OAU-1, OAU-2 2 7,750 1 INVERTER
SCROLL 120 135 40 60 208 3 60 R410A 100.0 MITSUBISHI TUHYE1203AN40A 760 1, 2, 3
ODU-OA2 GROUND, OAU-3, OAU-4 2 7,750 1 INVERTER
SCROLL 120 135 40 60 208 3 60 R410A 100.0 MITSUBISHI TUHYE1203AN40A 760 1, 2, 3
ODU-OA3 GROUND, OAU-5 1 6,000 1 INVERTER
SCROLL 72 80 23 35 208 3 60 R410A 100.0 MITSUBISHI TUHYE0723AN40A 615 1, 2, 3
1. NOMINAL COOLING CAPACITIES ARE BASED ON INDOOR COIL ENTERING AIR TEMPERATURE OF 80°FDB/67°FWB, OUTDOOR 95°FDB
2. NOMINAL HEATING CAPACITIES ARE BASED ON INDOOR COIL ENTERING AIR TEMPERATURE OF 70°FDB, OUTDOOR 47°FDB
3. PROVIDE 24" METAL EQUIPMENT STAND
VARIABLE REFRIGERANT FLOW (HEAT RECOVERY) AIR-COOLED OUTDOOR UNIT SCHEDULE
PROPELLER FAN DATA COMPRESSOR DATA NOMINAL CAPACITY ELECTRICAL DATA
SYSTEM
BASIS OF DESIGN
UNIT LOCATION NO CFM NO.
TYPE
COOLING HEATING MCA MOCP V PH Hz REFRIGERANT
CONNECTED
MANUFACTURER MODEL WEIGHT BC CONTROLLER
REMARKS
NUMBER MBH MBH TYPE CAPACITY (% OF NOM) LBS NUMBER
ODU-1 GROUND 2 14,100 1 INVERTER
SCROLL 216 243 73 125 208 3 60 R410A 117.6 MITSUBISHI TURYE2163AN40A 1,065 MBC-1 1, 2, 3
ODU-2 GROUND 2 7,400 1 INVERTER
SCROLL 96 108 31 45 208 3 60 R410A 106.3 MITSUBISHI TURYE0963AN40A 735 MBC-2 1, 2, 3
ODU-3 GROUND 2 8,300 1 INVERTER
SCROLL 120 135 41 60 208 3 60 R410A 107.5 MITSUBISHI TURYE1203AN40A 750 MBC-3 1, 2, 3
ODU-4 GROUND 2 14,850 1 INVERTER
SCROLL 168 188 57 90 208 3 60 R410A 125.0 MITSUBISHI TURYE1683AN40A 935 MBC-4 1, 2, 3
ODU-5 GROUND 2 13,050 1 INVERTER
SCROLL 192 215 66 110 208 3 60 R410A 122.4 MITSUBISHI TURYE1923AN40A 1,065 MBC-5 1, 2, 3
1. NOMINAL COOLING CAPACITIES ARE BASED ON INDOOR COIL ENTERING AIR TEMPERATURE OF 80°FDB/67°FWB, OUTDOOR 95°FDB
2. NOMINAL HEATING CAPACITIES ARE BASED ON INDOOR COIL ENTERING AIR TEMPERATURE OF 70°FDB, OUTDOOR 47°FDB
3. PROVIDE 24" METAL EQUIPMENT STAND
AIR BALANCING SUMMARY
AIR HANDLING SUPPLY AIR RETURN AIR
OUTSIDE AIR CFM RELIEF AIR CFM
GENERAL EXH PRESSURIZATION REMARKS
UNIT NO. CFM CFM
NORMAL ECONOMIZER NORMAL ECONOMIZER
CFM CFM
RTU-1 6,650 5,450 1,200 6,650 - 5,450 - + 1,200
OAU-1 900 - 900 - - - 390 + 510
OAU-2 600 - 600 - - - 550 + 50
OAU-3 800 - 800 - - - - + 800
OAU-4 600 - 600 - - - 300 + 300
OAU-5 800 - 800 - - - 590 + 210
0-
M
.d w g
Sheet
Scale
Project NO.
Date
PROJECT NAME AND ADDRESS
SEAL
CLIENT
Revision/IssueNo. Date
SHEET TITLE
G
LE
N W
O O
D E
LE
M
EN
TA
R Y
SC
H
O O
L C
O N
VE
R
SI
O
N
H
AL
IF
AX
R
O
AD
D
AN
VI
LL
E, V
A
23100
11/08/2023
AS NOTED
Lu+S
4924 DOMINION BLVD, STE A
GLEN ALLEN, VA 23060
p: 804.925.2600 f: 804.925.2170 www.LSEngineers.net
90% PROGRESS SET
NOT FOR
CONSTRUCTION
11/08/23
SCHEDULES
M0.2
ELECTRIC DUCT HEATING COIL SCHEDULE
COIL DATA SELECTION BASED ON
UNIT LOCATION AND DUCT SIZE TYPE DESIGN EAT °F LAT °F V PH Hz KW CAPACITY MANUFACTURER MODEL NO.
REMARKS
NUMBER AREAS SERVED WxH (INCH) CFM DB DB BTU/H
DH-1 OAU-1 OUTSIDE AIR 16x12 SLIP-IN OPEN COIL 900 10 63 208 3 60 15 51,225 INDEECO QUA 1, 2, 3, 4
DH-2 OAU-2 OUTSIDE AIR 18x8 SLIP-IN OPEN COIL 600 10 63 208 3 60 10 34,150 INDEECO QUA 1, 2, 3, 4
DH-3 OAU-3 OUTSIDE AIR 22x8 SLIP-IN OPEN COIL 800 10 69 208 3 60 15 51,225 INDEECO QUA 1, 2, 3, 4
DH-4 OAU-4 OUTSIDE AIR 18x8 SLIP-IN OPEN COIL 600 10 63 208 3 60 10 34,150 INDEECO QUA 1, 2, 3, 4
DH-5 OAU-5 OUTSIDE AIR 22x8 SLIP-IN OPEN COIL 800 10 69 208 3 60 15 51,225 INDEECO QUA 1, 2, 3, 4
1. PROVIDE A BUILT-IN DIFFERENTIAL PRESSURE AIRFLOW SWITCH
2. PROVIDE A BUILT-IN SNAP ACTING DOOR INTERLOCKING DISCONNECT SWITCH WITH MARKED "ON" AND "OFF" POSITIONS
3. PROVIDE SCR POWER CONTROLLER
4. INSTALL HEATER PER MANUFACTURER'S INSTALLATION INSTRUCTIONS
MECHANICAL DUCTWORK AND PIPE INSULATION SCHEDULE
AL - ALUMINUM; ALG - ALUMAGUARD; PVC - POLYVINYL CHLORIDE
INSULATION FIELD
ITEMS SYSTEM LOCATION MATERIALTHICK APPLIED REMARKS
-NESS JACKET
DUCTWORK: LN - LINER; DW - DUCTWRAP; DB - DUCTBOARD
UNCONDITIONED OUTSIDE AIR DUCT & PLENUM ALL INDOOR DW 2" -
SUPPLY AIR DUCT ALL INDOOR DW 2" -
SUPPLY AIR DUCT ALL OUTDOOR DW 2" ALG PROVIDE ADDITIONAL 2" DB
RETURN AIR DUCT ALL INDOOR DW 2" -
RETURN AIR DUCT ALL OUTDOOR DW 2" ALG PROVIDE ADDITIONAL 2" DB
TRANSFER AIR DUCT ALL INDOOR LN 1" -
PIPES: PPI - PREFORMED PIPE INSULATION; BKT - BLANKET INSULATION
AC CONDENSATE ALL INDOOR PPI 1" -
AC CONDENSATE (NOT THROUGH RECLAIM SYSTEM) ALL OUTDOOR - - -
ALL REFRIGERANT LINE ALL INDOOR/OUTDOOR PPI 1" -
NOTES:
1. REFER TO PROJECT SPECIFICATION AND/OR SPECIFICATION NOTES ON DRAWINGS FOR PRODUCT MATERIAL INFORMATION, AND INSTALLATION REQUIREMENTS.
2. WHEN INSULATION IS REQUIRED (INTERNAL AND/OR EXTERNAL) ON SYSTEM PIPES OR DUCTWORK, ALL PIPE/DUCT ACCESSORIES SHALL BE PROVIDED WITH CONTINUOUS INSULATION.
3. ALL EXPOSED PIPING INSULATION SHALL BE PROTECTED WITH PVC JACKET.
AIR DISTRIBUTION DEVICE SCHEDULE
UNIT LOCATION SERVICE SHAPE MATERIAL NECK FINISH COLOR
SELECTION BASED ON
REMARKS/
NUMBER SIZE
MANUFACTURER MODEL NO.
ACCESSORIES
S-1 CEILING SUPPLY SQUARE 24x24 ALUMINUM ROUND WHITE TITUS OMNI-AA 1, 2
S-2 CEILING SUPPLY SQUARE 12x12 STEEL ROUND WHITE TITUS OMNI 1
S-3 SIDE WALL SUPPLY RECTANGLE ALUMINUM SEE DWG WHITE TITUS 300FL 3
S-4 CEILING SUPPLY SQUARE 24x24 ALUMINUM ROUND WHITE TITUS TDC-AA 4, 5
R-1 CEILING RETURN SQUARE 24x24 ALUMINUM SEE DWG WHITE TITUS PAR-AA 3
R-2 SIDE WALL RETURN RECTANGLE ALUMINUM SEE DWG WHITE TITUS 350FL 3
E-1 CEILING EXHAUST RECTANGLE ALUMINUM SEE DWG WHITE TITUS 50F 3
E-2 CEILING EXHAUST SQUARE 24x24 ALUMINUM SEE DWG WHITE TITUS PAR-AA 3
T-1 CEILING TRANSFER SQUARE 24x24 ALUMINUM SEE DWG WHITE TITUS PAR-AA
1. PROVIDE NECK MOUNTED SLIDING BLADE DAMPER
2. PROVIDE FACTORY INSTALLED INSULATION BLANKET TO PREVENT CONDENSATION
3. PROVIDE OPPOSED BLADE DAMPER
4. 18"x18" DIMENSION A SIZE, 4-WAY AIRFLOW PATTERN, 24x24 MODULE DIFFUSER
5. PROVIDE AG-95 DAMPER TO ALLOW VOLUME ADJUSTMENT FROM THE FACE OF THE DIFFUSER.
VARIABLE REFRIGERANT FLOW (HEAT RECOVERY) - INDOOR UNIT SCHEDULE
FAN DATA
DX COIL COOLING DATA DX COIL HEATING DATA UNIT ELECTRICAL DATA SELECTION BASED ON
UNIT TYPE ROOM NUMBER BRANCH CIRCUIT
AIR SIDE DATA COOLING LOAD AIR SIDE DATA
HEATING
NUMBER BOX NUMBER
EAT °F LAT °F
SENS. TOTAL EAT °F LAT °F
LOAD V PH Hz MCA MOCP MANUFACTURER MODEL NO. WEIGHT REMARKS
CFM / OA
V PH Hz DB WB DB WB
BTUH BTUH DB DB BTUH LBS
IDU-1-01 CEILING CONCEALED DUCTED 101, 102, 106 MBC-1 670 / 80 208 1 60 75 62.5 52 51 16,465 22,275 70 107 26,806 208 1 60 2.11 15 MITSUBISHI TPEFYP024MH142A 125 1, 2, 3, 4
IDU-1-02 CEILING CONCEALED DUCTED 103, 104, 107 MBC-1 670 / 80 208 1 60 75 62.5 52 51 16,465 22,275 70 107 26,806 208 1 60 2.11 15 MITSUBISHI TPEFYP024MH142A 125 1, 2, 3, 4
IDU-1-03 CEILING CASSETTE ONE-WAY 105, 108 MBC-1 305 208 1 60 75 62.5 59 58 5,030 5,568 70 90 6,652 208 1 60 0.25 15 MITSUBISHI TPMFYP006BM140F 40 1, 2, 3
IDU-1-04 CEILING CONCEALED DUCTED 144, 145, 148 MBC-1 670 / 80 208 1 60 75 62.5 52 51 16,465 22,275 70 107 26,806 208 1 60 2.11 15 MITSUBISHI TPEFYP024MH142A 125 1, 2, 3, 4
IDU-1-05 CEILING CONCEALED DUCTED 146, 147, 149 MBC-1 670 / 80 208 1 60 75 62.5 52 51 16,465 22,275 70 107 26,806 208 1 60 2.11 15 MITSUBISHI TPEFYP024MH142A 125 1, 2, 3, 4
IDU-1-06A CEILING CASSETTE FOUR-WAY 109 MBC-1 335 208 1 60 75 62.5 52 51 8,040 11,137 70 107 13,403 208 1 60 0.29 15 MITSUBISHI TPLFYP012FM140A 40 1, 2, 3
IDU-1-06B CEILING CASSETTE FOUR-WAY 109 MBC-1 335 208 1 60 75 62.5 52 51 8,040 11,137 70 107 13,403 208 1 60 0.29 15 MITSUBISHI TPLFYP012FM140A 40 1, 2, 3
IDU-1-07A CEILING CASSETTE FOUR-WAY 110 MBC-1 810 208 1 60 75 62.5 55 54 16,765 22,275 70 100 26,806 208 1 60 0.54 15 MITSUBISHI TPLFYP024EM140B 70 1, 2, 3
IDU-1-07B CEILING CASSETTE FOUR-WAY 110 MBC-1 810 208 1 60 75 62.5 55 54 16,765 22,275 70 100 26,806 208 1 60 0.54 15 MITSUBISHI TPLFYP024EM140B 70 1, 2, 3
IDU-1-08 CEILING CASSETTE FOUR-WAY 150 MBC-1 280 208 1 60 75 62.5 60 59 4,335 4,640 70 88 5,560 208 1 60 0.24 15 MITSUBISHI TPLFYP005FM140A 40 1, 2, 3
IDU-1-09A CEILING CASSETTE FOUR-WAY 151 MBC-1 810 208 1 60 75 62.5 51 50 21,025 27,845 70 108 33,756 208 1 60 0.57 15 MITSUBISHI TPLFYP030EM140B 70 1, 2, 3
IDU-1-09B CEILING CASSETTE FOUR-WAY 151 MBC-1 810 208 1 60 75 62.5 51 50 21,025 27,845 70 108 33,756 208 1 60 0.57 15 MITSUBISHI TPLFYP030EM140B 70 1, 2, 3
IDU-1-10 WALL MOUNTED 117 MBC-1 350 208 1 60 75 62.5 49 48 9,855 13,920 70 114 16,878 208 1 60 0.24 15 MITSUBISHI TPKFYP015LM140A 40 1, 2, 3
IDU-1-11A CEILING CASSETTE FOUR-WAY 129 MBC-2 280 208 1 60 75 62.5 60 59 4,340 4,650 70 88 5,560 208 1 60 0.24 15 MITSUBISHI TPLFYP005FM140A 40 1, 2, 3
IDU-1-11B CEILING CASSETTE FOUR-WAY 133 MBC-2 280 208 1 60 75 62.5 60 59 4,340 4,650 70 88 5,560 208 1 60 0.24 15 MITSUBISHI TPLFYP005FM140A 40 1, 2, 3
IDU-1-11C CEILING CASSETTE FOUR-WAY 136 MBC-2 280 208 1 60 75 62.5 60 59 4,340 4,650 70 88 5,560 208 1 60 0.24 15 MITSUBISHI TPLFYP005FM140A 40 1, 2, 3
IDU-1-11D CEILING CASSETTE FOUR-WAY 136 MBC-2 280 208 1 60 75 62.5 60 59 4,340 4,650 70 88 5,560 208 1 60 0.24 15 MITSUBISHI TPLFYP005FM140A 40 1, 2, 3
IDU-1-11E CEILING CASSETTE FOUR-WAY 136 MBC-2 280 208 1 60 75 62.5 60 59 4,340 4,650 70 88 5,560 208 1 60 0.24 15 MITSUBISHI TPLFYP005FM140A 40 1, 2, 3
IDU-1-12 CEILING CASSETTE FOUR-WAY 130 MBC-2 280 208 1 60 75 62.5 60 59 4,340 4,650 70 88 5,560 208 1 60 0.24 15 MITSUBISHI TPLFYP005FM140A 40 1, 2, 3
IDU-1-13 CEILING CASSETTE FOUR-WAY 131 MBC-2 315 208 1 60 75 62.5 56 55 6,175 7,440 70 96 8,935 208 1 60 0.28 15 MITSUBISHI TPLFYP008FM140A 40 1, 2, 3
IDU-1-14A CEILING CASSETTE FOUR-WAY 132 MBC-2 315 208 1 60 75 62.5 56 55 6,175 7,440 70 96 8,935 208 1 60 0.28 15 MITSUBISHI TPLFYP008FM140A 40 1, 2, 3
IDU-1-14B CEILING CASSETTE FOUR-WAY 132 MBC-2 315 208 1 60 75 62.5 56 55 6,175 7,440 70 96 8,935 208 1 60 0.28 15 MITSUBISHI TPLFYP008FM140A 40 1, 2, 3
IDU-1-15A CEILING CASSETTE FOUR-WAY 134 MBC-2 335 208 1 60 75 62.5 52 51 8,050 11,160 70 107 13,403 208 1 60 0.29 15 MITSUBISHI TPLFYP012FM140A 40 1, 2, 3
IDU-1-15B CEILING CASSETTE FOUR-WAY 134 MBC-2 335 208 1 60 75 62.5 52 51 8,050 11,160 70 107 13,403 208 1 60 0.29 15 MITSUBISHI TPLFYP012FM140A 40 1, 2, 3
IDU-1-16A CEILING CASSETTE FOUR-WAY 135 MBC-2 335 208 1 60 75 62.5 52 51 8,050 11,160 70 107 13,403 208 1 60 0.29 15 MITSUBISHI TPLFYP012FM140A 40 1, 2, 3
IDU-1-16B CEILING CASSETTE FOUR-WAY 135 MBC-2 335 208 1 60 75 62.5 52 51 8,050 11,160 70 107 13,403 208 1 60 0.29 15 MITSUBISHI TPLFYP012FM140A 40 1, 2, 3
IDU-1-17A CEILING CASSETTE FOUR-WAY 118 MBC-3 460 208 1 60 75 62.5 51 50 11,855 16,705 70 110 19,855 208 1 60 0.5 15 MITSUBISHI TPLFYP018FM140A 40 1, 2, 3
IDU-1-17B CEILING CASSETTE FOUR-WAY 118 MBC-3 390 208 1 60 75 62.5 51 50 9,850 13,920 70 110 16,876 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
IDU-1-18A CEILING CASSETTE FOUR-WAY 119 MBC-3 335 208 1 60 75 62.5 52 51 8,040 11,137 70 107 13,403 208 1 60 0.29 15 MITSUBISHI TPLFYP012FM140A 40 1, 2, 3
IDU-1-18B CEILING CASSETTE FOUR-WAY 119 MBC-3 335 208 1 60 75 62.5 52 51 8,040 11,137 70 107 13,403 208 1 60 0.29 15 MITSUBISHI TPLFYP012FM140A 40 1, 2, 3
IDU-1-18C CEILING CASSETTE FOUR-WAY 119 MBC-3 335 208 1 60 75 62.5 52 51 8,040 11,137 70 107 13,403 208 1 60 0.29 15 MITSUBISHI TPLFYP012FM140A 40 1, 2, 3
IDU-1-18D CEILING CASSETTE FOUR-WAY 119 MBC-3 335 208 1 60 75 62.5 52 51 8,040 11,137 70 107 13,403 208 1 60 0.29 15 MITSUBISHI TPLFYP012FM140A 40 1, 2, 3
IDU-1-19A CEILING CASSETTE FOUR-WAY 120 MBC-3 810 208 1 60 75 62.5 56 55 16,765 22,275 70 100 26,803 208 1 60 0.54 15 MITSUBISHI TPLFYP024EM140B 70 1, 2, 3
IDU-1-19B CEILING CASSETTE FOUR-WAY 120 MBC-3 810 208 1 60 75 62.5 56 55 16,765 22,275 70 100 26,803 208 1 60 0.54 15 MITSUBISHI TPLFYP024EM140B 70 1, 2, 3
IDU-1-20 CEILING CASSETTE FOUR-WAY 123 MBC-4 335 208 1 60 75 62.5 53 52 8,040 11,137 70 107 13,403 208 1 60 0.29 15 MITSUBISHI TPLFYP012FM140A 40 1, 2, 3
IDU-1-20A WALL MOUNTED 122 MBC-4 150 208 1 60 75 62.5 57 56 2,885 3,715 70 98 4,467 208 1 60 0.24 15 MITSUBISHI TPKFYP004LM140A 30 1, 2, 3
IDU-1-21 CEILING CASSETTE FOUR-WAY 124 MBC-4 315 208 1 60 75 62.5 57 56 6,165 7,425 70 96 8,935 208 1 60 0.28 15 MITSUBISHI TPLFYP008FM140A 40 1, 2, 3
IDU-1-22 CEILING CASSETTE FOUR-WAY 125 MBC-4 390 208 1 60 75 62.5 51 50 9,850 13,920 70 110 16,878 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
IDU-1-23 CEILING CASSETTE FOUR-WAY 128 MBC-4 280 208 1 60 75 62.5 60 59 4,335 4,640 70 88 5,560 208 1 60 0.24 15 MITSUBISHI TPLFYP005FM140A 40 1, 2, 3
IDU-1-24 CEILING CASSETTE FOUR-WAY 137 MBC-4 315 208 1 60 75 62.5 57 56 6,165 7,425 70 96 8,935 208 1 60 0.28 15 MITSUBISHI TPLFYP008FM140A 40 1, 2, 3
IDU-1-25 CEILING CASSETTE FOUR-WAY 138 MBC-4 810 208 1 60 75 62.5 56 55 16,765 22,275 70 100 26,807 208 1 60 0.54 15 MITSUBISHI TPLFYP024EM140B 70 1, 2, 3
IDU-1-26A CEILING CASSETTE FOUR-WAY 139 MBC-4 390 208 1 60 75 62.5 52 51 9,850 13,920 70 110 16,878 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
IDU-1-26B CEILING CASSETTE FOUR-WAY 139 MBC-4 390 208 1 60 75 62.5 52 51 9,850 13,920 70 110 16,878 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
IDU-1-27 CEILING CASSETTE FOUR-WAY 140 MBC-4 810 208 1 60 75 62.5 56 55 16,765 22,275 70 100 26,807 208 1 60 0.54 15 MITSUBISHI TPLFYP024EM140B 70 1, 2, 3
IDU-1-28 CEILING CASSETTE FOUR-WAY 141 MBC-4 315 208 1 60 75 62.5 57 56 6,165 7,425 70 96 8,935 208 1 60 0.28 15 MITSUBISHI TPLFYP008FM140A 40 1, 2, 3
IDU-1-29A CEILING CASSETTE FOUR-WAY 142 MBC-4 460 208 1 60 75 62.5 51 50 11,855 16,705 70 110 19,857 208 1 60 0.5 15 MITSUBISHI TPLFYP018FM140A 40 1, 2, 3
IDU-1-29B CEILING CASSETTE FOUR-WAY 142 MBC-4 460 208 1 60 75 62.5 51 50 11,855 16,705 70 110 19,857 208 1 60 0.5 15 MITSUBISHI TPLFYP018FM140A 40 1, 2, 3
IDU-1-30A CEILING CASSETTE FOUR-WAY 143 MBC-4 460 208 1 60 75 62.5 51 50 11,855 16,705 70 110 19,857 208 1 60 0.5 15 MITSUBISHI TPLFYP018FM140A 40 1, 2, 3
IDU-1-30B CEILING CASSETTE FOUR-WAY 143 MBC-4 460 208 1 60 75 62.5 51 50 11,855 16,705 70 110 19,857 208 1 60 0.5 15 MITSUBISHI TPLFYP018FM140A 40 1, 2, 3
1. PROVIDE WALL MOUNTED WIRED THERMOSTAT
2. PROVIDE INTEGRATED CONDENSATE PUMP, AND RESERVOIR SENSOR, INSTALL AS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
3. PROVIDE DRAIN PAN LEVEL SENSOR MODEL DPLS2
4. 80 CFM OUTSIDE AIR FLOW PROVIDED BY OUTSIDE AIR UNIT OAU-1
0-
M
.d w g
Sheet
Scale
Project NO.
Date
PROJECT NAME AND ADDRESS
SEAL
CLIENT
Revision/IssueNo. Date
SHEET TITLE
G
LE
N W
O O
D E
LE
M
EN
TA
R Y
SC
H
O O
L C
O N
VE
R
SI
O
N
H
AL
IF
AX
R
O
AD
D
AN
VI
LL
E, V
A
23100
11/08/2023
AS NOTED
Lu+S
4924 DOMINION BLVD, STE A
GLEN ALLEN, VA 23060
p: 804.925.2600 f: 804.925.2170 www.LSEngineers.net
90% PROGRESS SET
NOT FOR
CONSTRUCTION
11/08/23
SCHEDULES
M0.3
TEE
(AS REQUIRED BY UNIT)
THREADED PLUG FOR
SCREENED
RELIEF VENT
CLEAN-OUT AND
ADAPTOR
90° ELL
ADAPTOR
"A" = SUPPLY FAN TOTAL STATIC PRESSURE (IN INCHES) + 1" MIN.
"B" = 1/2 x "A" (IN INCHES)
MIN. 2xPIPE DIA. AIR GAP
COOLING COIL
WINTERIZATION DRAIN
CONDENSATE DRAIN SAME
SIZE AS UNIT DRAIN BUT
NOT LESS THAN 1"
A B
REMARKS:
1. SIZE DRAIN PIPE TO ACCOMMODATE PEAK COIL CONDENSATE FLOW, BUT DRAIN
PIPE SIZE SHALL BE NO LESS THAN 1".
2. DRAIN PANS AND CURBS MUST BE HIGH ENOUGH TO OVERCOME NEGATIVE SYSTEM
PRESSURE.
DRAIN
COOLING COIL CONDENSATE DRAIN DETAIL
SCALE: NONE NOTE: APPLIED TO DRAW-THROUGH COIL
METAL WIRE TIE
DOWN (TYPICAL)
AT STEEL JOISTS
AT WOOD TRUSS
L4x4x1/4WOOD MEMBERS
ROD WITH DOUBLE NUTS AS
AT 2'-0" O.C.
DRILL FOR 8d NAIL
HANGER ROD
ATTACHMENT (TYPICAL)
DRILL ANGLE TO MATCH HANGER
REQUIRED BY EQUIPMENT
L4x4x1/4
HANGER ROD
BAR JOIST AT 1'-0" O.C.
ROD WITH DOUBLE NUTS AS
REQUIRED BY EQUIPMENT
DRILL ANGLE TO MATCH HANGER
TYPICAL EQUIPMENT SUPPORT DETAIL
SCALE: NONE
STAINLESS STEEL
CLAMP PART OF
COMPONENT "A"
OUTDOOR
CONDENSING UNIT
UV CABLES
TIES PART OF
COMPONENT "B"
WALL-MOUNTED REFRIGERANT PIPING OUTLET
(COMPONENT A)
· BASED ON AIREX MANUFACTURING INC.
TYPE AIREX TITAN OUTLET
· EXTERIOR WALL SEAL PENETRATION
OUTLET WITH ELASTOMERIC LINE SET
COMPRESSION SLEEVE
INSULATION PROTECTIVE PVC COVER
(COMPONENT B)
· BASED ON AIREX MANUFACTURING INC.
TYPE AIREX E-FLEX GUARD
EQUIPMENT PAD
INSULATED
REFRIGERANT
PIPING
ALL MATERIAL WALL
ANCHOR SCREWS PART
OF COMPONENT "A"
WALL SURFACE GASKET SEAL
PART OF COMPONENT "A"
EXTERIOR WALL
PIPE SLEEVE SEAL
WEATHER TIGHT
GRADE LEVEL
REFRIGERANT PIPING EXTERIOR PENETRATION WALL BOX DETAIL
SCALE: NONE NOTE: INSTALL AS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS
PRIMARY CONDENSATE DRAIN
CEILING
ALL-THREAD ROD (TYP.)STRUCTURE ABOVE
IDU
W/ ISOLATORS
RETURN
AIR
SUPPLY
AIR
FLOAT SWITCH TO CUT OFF
SUPPLY AIR FAN UPON DETECTION
OF WATER; 24V POWERED FROM
AHU UNIT; MONITORED BY BAS
(BUILDING AUTOMATION SYSTEM);
AUXILIARY DRAIN PAN
NOTE:
1. AUXILIARY DRAIN PAN SHALL BE SIZED AT MIN. 2" BEYOND FOOTPRINT OF THE AHU UNIT ON ALL
SIZES AND IT SHALL BE AT MIN. 1.5" DEEP.
2. FLOAT SWITCH SHALL BE LOCATED AT THE LOWEST POINT OF THE AUXILIARY DRAIN PAN.
ABOVE CEILING AIR HANDLING UNIT DETAIL
SCALE: NONE NOTE: COORDINATE WITH FLOOR PLANS
TO STEEL FABRICATION
HEIGHT & LENGTH OF FRAMES PRIOR
MECHANICAL CONTRACTOR SHALL VERIFY
PRIMER & 2 COATS OF BLACK FINISH PAINT.
10'-0" MAX. W/ ONE COAT OF RUST INHIBITIVE
3x3x1/4" A36 SHOP WELDED FRAME - SPACE @
WEATHER PROOFING
.024" ALUMINUM JACKET
(2) 1/2"Ø CAST-IN-PLACE ANCHORS
2" RIGID INSULATION
DUCT, TYPICAL
4" HOUSEKEEPING PAD
HOLD DOWN TYP.
WELD PL 1/4"x3 1/2"x7"
TO FRAME
GRADE
BENEATH JACKET
1x2 MIN. CROWN
1/2"Ø ALL THREAD
3x3x1/4"
NOTE
M
IN
. 1 8"
INTENTIONALLY ROUGHEN SLAB AND
APPLY BONDING COMPOUND AT PAD
EX. FLOOR SLAB
EQUIPMENT
4" CHAMFER (TYP.)4"
M
IN
LOCATION OF EQUIP.
DWGS. FOR SIZE AND
SEE MECH. AND ELECT.
4"
TYP.
EXTERIOR WALL
WALL SLEEVE
CAULK
ALUMINUM COUNTER-FLASHING
AROUND DUCT
INSULATION WITH
ALUMINUM JACKET
SPRAYED-IN-PLACE
FOAM INSULATION
IN ANNULAR SPACE
FINISHED SPACES ONLY
ESCUTCHEON IN
INSULATION
THIS DETAIL FOR ABOVE-GRADE WALL PENETRATIONS ONLY.
NOTE:
ROUND OR
RECTANGLE
DUCTWORK
OUTDOOR DUCTWORK SUPPORT DETAIL
SCALE: NONE
HOUSEKEEPING PAD ON EXISTING SLAB DETAIL
SCALE: NONE
ABOVE GRADE DUCT PENETRATION DETAIL
SCALE: NONE
VARIABLE REFRIGERANT FLOW (HEAT RECOVERY) - INDOOR UNIT SCHEDULE
FAN DATA
DX COIL COOLING DATA DX COIL HEATING DATA UNIT ELECTRICAL DATA SELECTION BASED ON
UNIT TYPE ROOM NUMBER BRANCH CIRCUIT
AIR SIDE DATA COOLING LOAD AIR SIDE DATA
HEATING
NUMBER BOX NUMBER
EAT °F LAT °F
SENS. TOTAL EAT °F LAT °F
LOAD V PH Hz MCA MOCP MANUFACTURER MODEL NO. WEIGHT REMARKS
CFM / OA
V PH Hz DB WB DB WB
BTUH BTUH DB DB BTUH LBS
IDU-2-01 CEILING CASSETTE FOUR-WAY 207 MBC-5 280 208 1 60 75 62.5 60 59 4,335 4,640 70 88 5,560 208 1 60 0.24 15 MITSUBISHI TPLFYP005FM140A 40 1, 2, 3
IDU-2-02 CEILING CASSETTE FOUR-WAY 208 MBC-5 460 208 1 60 75 62.5 51 50 11,855 16,705 70 110 19,856 208 1 60 0.5 15 MITSUBISHI TPLFYP018FM140A 40 1, 2, 3
IDU-2-03 CEILING CASSETTE FOUR-WAY 209 MBC-5 460 208 1 60 75 62.5 51 50 11,855 16,705 70 110 19,856 208 1 60 0.5 15 MITSUBISHI TPLFYP018FM140A 40 1, 2, 3
IDU-2-04A CEILING CASSETTE FOUR-WAY 201 MBC-5 390 208 1 60 75 62.5 51 50 9,850 13,920 70 110 16,878 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
IDU-2-04B CEILING CASSETTE FOUR-WAY 201 MBC-5 390 208 1 60 75 62.5 51 50 9,850 13,920 70 110 16,878 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
IDU-2-05 CEILING CASSETTE FOUR-WAY 204 MBC-5 810 208 1 60 75 62.5 56 55 16,765 22,275 70 100 26,806 208 1 60 0.54 15 MITSUBISHI TPLFYP024EM140B 70 1, 2, 3
IDU-2-06 CEILING CASSETTE FOUR-WAY 206 MBC-5 390 208 1 60 75 62.5 51 50 9,850 13,920 70 110 16,878 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
IDU-2-07A CEILING CASSETTE FOUR-WAY 212 MBC-5 390 208 1 60 75 62.5 51 50 9,850 13,920 70 110 16,878 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
IDU-2-07B CEILING CASSETTE FOUR-WAY 212 MBC-5 390 208 1 60 75 62.5 51 50 9,850 13,920 70 110 16,878 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
IDU-2-08A CEILING CASSETTE FOUR-WAY 213 MBC-5 390 208 1 60 75 62.5 51 50 9,850 13,920 70 110 16,878 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
IDU-2-08B CEILING CASSETTE FOUR-WAY 213 MBC-5 390 208 1 60 75 62.5 51 50 9,850 13,920 70 110 16,878 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
IDU-2-09A CEILING CASSETTE FOUR-WAY 214 MBC-5 390 208 1 60 75 62.5 51 50 9,850 13,920 70 110 16,878 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
IDU-2-09B CEILING CASSETTE FOUR-WAY 214 MBC-5 390 208 1 60 75 62.5 51 50 9,850 13,920 70 110 16,878 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
IDU-2-10 CEILING CASSETTE FOUR-WAY 210 MBC-5 280 208 1 60 75 62.5 60 59 4,335 4,640 70 88 5,560 208 1 60 0.24 15 MITSUBISHI TPLFYP005FM140A 40 1, 2, 3
IDU-2-11A CEILING CASSETTE FOUR-WAY 211 MBC-5 390 208 1 60 75 62.5 51 50 9,850 13,920 70 110 16,878 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
IDU-2-11B CEILING CASSETTE FOUR-WAY 211 MBC-5 390 208 1 60 75 62.5 51 50 9,850 13,920 70 110 16,878 208 1 60 0.35 15 MITSUBISHI TPLFYP015FM140A 40 1, 2, 3
1. PROVIDE WALL MOUNTED WIRED THERMOSTAT
2. PROVIDE INTEGRATED CONDENSATE PUMP, AND RESERVOIR SENSOR, INSTALL AS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
3. PROVIDE DRAIN PAN LEVEL SENSOR MODEL DPLS2
TRANSFER AIR GRILLE WITH SOUND ATTENUATION DETAIL
SCALE: NONE
CEILING
FULL HEIGHT PARTITION
TRANSFER AIR GRILLE
SEE MECH PLANS FOR
SIZE AND LOCATION
1" LINER
FULL SIZE 90 DEGREE
ELBOW WITHOUT
TURNING VANE
TRANSFER AIR GRILLE
SEE MECH PLANS FOR
SIZE AND LOCATION
0-
M
.d w g
Sheet
Scale
Project NO.
Date
PROJECT NAME AND ADDRESS
SEAL
CLIENT
Revision/IssueNo. Date
SHEET TITLE
G
LE
N W
O O
D E
LE
M
EN
TA
R Y
SC
H
O O
L C
O N
VE
R
SI
O
N
H
AL
IF
AX
R
O
AD
D
AN
VI
LL
E, V
A
23100
11/08/2023
AS NOTED
Lu+S
4924 DOMINION BLVD, STE A
GLEN ALLEN, VA 23060
p: 804.925.2600 f: 804.925.2170 www.LSEngineers.net
90% PROGRESS SET
NOT FOR
CONSTRUCTION
11/08/23
SCHEDULE AND DETAILS
M0.4
BRANCH TAKE-OFFS
DAMPER QUADRANT
D
DAMPER QUADRANT
D
X Y
SPLIT DAMPER
X LESS THAN 12"
C CFM
A CFMB CFM
x Y=XA CFM
C CFM Y=X
X=12" OR MORE
C CFM
A CFM
C CFM
B CFM A CFM
x
WHERE POSSIBLE
FULL RADIUS
PREFERRED OFFSET
DD
DD
DD
DD
IF D=12" OR MORE
D LESS THAN 12"
USE VANED ELBOW
X OR Y LESS THAN 12"
R2=X+Y R1=(X+Y)/2
R2
R1 Y
X
DR=D
R
D
X OR Y LESS THAN 12"
R2=Y+Z R1=(Y+Z)/2
R2=X+W R1=(X+W)/2
R2
WR1
SPLIT DAMPER
Z R1 R2
YX
SPLIT DAMPER
YX
YX
20°MAX.
OFFSETS90° RADIUS ELBOWS90° TEES
X OR Y=12" OR MORE
SPLIT DAMPER
X Y
AIR DEVICE TAKE-OFFS
D
MIN.
1/2 D D
D
CEILING
AIR DEVICE
AIR CONNECTION VIA
FLEX. DUCT
D
HARD ELBOW
FLEX. DUCT TRUNK DUCT
NOTES:
1. ALL DUCT FITTING/ACCESSORIES SHALL
CONFORM TO SMACNA STANDARDS.
2. FLEX DUCT SHALL NOT EXCEED 5 FEET.
USE WHEN COIL OR
DIFFUSER IS 36" OR
LESS FROM BRANCH
TAKE-OFF
VERTICAL DROP
TO AIR DEVICE
FROM TRUNK DUCT
CEILING
AIR DEVICE
ROUND DUCT TAKE-OFF
FROM RECTANGULAR MAIN
(RETURN AIR)
ROUND DUCT TAKE-OFF
FROM RECTANGULAR MAIN
(SUPPLY AIR)
DAMPER QUADRANT SPLIT DAMPER
DAMPER QUADRANT
30°MAX.
A CFM B CFM
30°MAX.
A CFM+B CFM
B CFM
A CFM
A CFM+B CFM
30°MAX.
20°MAX.
D1
D2
STRAIGHT WYE TEE
(D1=D2 OR MORE)
BEND WYE TEE
3. ANY BENDS ON FLEX. DUCT SHALL BE
MADE WITH NO LESS THAN ONE DUCT
DIAMETER CENTERLINE RADIUS. FLEX DUCT
SHALL NOT BE COMPRESSED.
CONVERGING WYE TEE,
RECTANGULAR
LOW PRESSURE DUCTWORK STANDARD
SCALE: NONE NOTE: ALL DUCTWORK FABRICATION SHALL
MEET SMACNA STANDARD (LATEST EDITION)
ODU-1
MBC-1
IDU-1-01
IDU-1-02
IDU-1-03
IDU-1-04
IDU-1-05
IDU-1-06A
IDU-1-06B
IDU-1-07A
IDU-1-07B
IDU-1-08
IDU-1-09A
IDU-1-09B
IDU-1-10
ODU-2
MBC-2
IDU-1-11A
IDU-1-11B
IDU-1-11C
IDU-1-11D
IDU-1-11E
IDU-1-12
IDU-1-13
IDU-1-14A
IDU-1-14B
IDU-1-15A
IDU-1-15B
IDU-1-16A
IDU-1-16B
ODU-3
IDU-1-17A
IDU-1-17B
IDU-1-18A
IDU-1-18B
IDU-1-18C
IDU-1-18D
IDU-1-19A
IDU-1-19B
MBC-3
ODU-4
MBC-4
IDU-1-20
IDU-1-20A
IDU-1-21
IDU-1-22
IDU-1-23
IDU-1-24
IDU-1-25
IDU-1-26A
IDU-1-126B
IDU-1-29A
IDU-1-29B
IDU-1-30A
IDU-1-30B
IDU-1-27
IDU-1-28
ODU-5
MBC-5
IDU-2-01
IDU-2-02
IDU-2-03
IDU-2-04A
IDU-2-04B
IDU-2-05
IDU-206
IDU-2-07A
IDU-2-07B
IDU-2-08A
IDU-2-08B
IDU-2-09A
IDU-2-09B
IDU-2-10
IDU-2-11A
IDU-2-11B
ODU-OA1
OAU-1
OAU-2
ODU-OA2
OAU-3
OAU-4
ODU-OA3
OAU-5
PIPE DIAMETER, LIQUID / GAS
PIPE LENGTHLEGEND:
BRANCH JOINT, PROVIDED BY MANUFACTURERSYMBOL:
REFRIGERANT SYSTEM DIAGRAMS
SCALE: NONE NOTE: CONTRACTOR TO FIELD VERIFY
EXACT PIPE LENGTH AND TO CONFIRM
PIPE SIZES WITH MANUFACTURER
ODU-1 / MBC-1 REFRIGERANT PIPING ODU-2 / MBC-2 REFRIGERANT PIPING
ODU-3 / MBC-3 REFRIGERANT PIPING
ODU-4 / MBC-4 REFRIGERANT PIPING ODU-5 / MBC-5 REFRIGERANT PIPING
ODU-OA1 REFRIGERANT PIPING
ODU-OA2 REFRIGERANT PIPING
ODU-OA3 REFRIGERANT PIPING
7/8 / 1-1/8
105 FT
3/8 / 5/8
85 FT
3/8 / 5/8
65 FT
1/4 / 1/2
45 FT
3/8 / 5/8
15 FT
3/8 / 5/8
42 FT
1/4 / 1/2
60 FT
1/4 / 1/2
20 FT
3/8 / 5/8
3 FT
3/8 / 5/8
75 FT
3/8 / 3/4
30 FT
3/8 / 5/8
22 FT
1/4 / 1/2
15 FT
3/8 / 5/8
3 FT
3/8 / 5/8
22 FT
1/4 / 1/2
50 FT
3/4 / 7/8
75 FT
85 FT
15 FT
1/4 / 1/2
85 FT
20 FT
95 FT
1/4 / 1/2
75 FT
1/4 / 1/2
65 FT
1/4 / 1/2
5 FT
3/8 / 5/8
26 FT
22 FT
3 FT
3/8 / 5/8
45 FT
20 FT
3 FT
3/8 / 5/8
110 FT
20 FT
1/4 / 1/2
1/4 / 1/2
1/4 / 1/2
1/4 / 1/2
1/4 / 1/2
1/4 / 1/2
1/4 / 1/2
1/4 / 1/2
1/4 / 1/2
3/4 / 1-1/8
125 FT
1/4 / 1/2
5 FT
3/8 / 5/8
50 FT
3/8 / 5/8
3 FT
3/8 / 5/8
20 FT
1/4 / 1/2
3 FT
3/8 / 5/8
28 FT
1/4 / 1/2
3 FT
3/8 / 5/8
20 FT
3/8 / 5/8
40 FT
1/4 / 1/2
22 FT
1/4 / 1/2
18 FT
1/4 / 1/2
18 FT
7/8 / 1-1/8
45 FT
1/4 / 1/2
118 FT
1/4 / 1/2
2 FT
3/8 / 5/8
15 FT
1/4 / 1/2
100 FT
1/4 / 1/2
95 FT
1/4 / 1/2
80 FT
1/4 / 1/2
68 FT
1/4 / 1/2
50 FT
3/8 / 5/8
35 FT
1/4 / 1/2
15 FT
3/8 / 5/8
45 FT
1/4 / 1/2
62 FT
1/4 / 1/2
2 FT
1/4 / 1/2
20 FT
3/8 / 5/8
80 FT
3/8 / 5/8
140 FT
1/4 / 1/2
2 FT
1/4 / 1/2
20 FT
7/8 / 1-1/8
60 FT
1/4 / 1/2
45 FT
1/4 / 1/2
20 FT
1/4 / 1/2
45 FT
1/4 / 1/2
5 FT
3/8 / 5/8
78 FT
1/4 / 1/2
22 FT
3/8 / 5/8
72 FT
1/4 / 1/2
58 FT
1/4 / 1/2
5 FT
3/8 / 5/8
25 FT
1/4 / 1/2
15 FT
1/4 / 1/2
5 FT
3/8 / 5/8
23 FT
1/4 / 1/2
15 FT
1/4 / 1/2
5 FT
3/8 / 5/8
56 FT
1/4 / 1/2
15 FT
1/4 / 1/2
66 FT
1/4 / 1/2
40 FT
1/4 / 1/2
50 FT
3/8 / 3/4
20 FT
3/8 / 1-1/8
60 FT
3/8 / 5/8
20 FT
3/8 / 3/4
20 FT
3/8 / 1-1/8
60 FT
3/8 / 5/8
20 FT
3/8 / 7/8
60 FT
0-
M
.d w g
Sheet
Scale
Project NO.
Date
PROJECT NAME AND ADDRESS
SEAL
CLIENT
Revision/IssueNo. Date
SHEET TITLE
G
LE
N W
O O
D E
LE
M
EN
TA
R Y
SC
H
O O
L C
O N
VE
R
SI
O
N
H
AL
IF
AX
R
O
AD
D
AN
VI
LL
E, V
A
23100
11/08/2023
AS NOTED
Lu+S
4924 DOMINION BLVD, STE A
GLEN ALLEN, VA 23060
p: 804.925.2600 f: 804.925.2170 www.LSEngineers.net
90% PROGRESS SET
NOT FOR
CONSTRUCTION
11/08/23
DETAILS AND REFRIGERANT
SYSTEM DIAGRAMS
M0.5
DN
DN DN
DN
DN
UP UP
1 SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - MECHANICAL DUCTWORK
2 SCALE: 1/8" = 1'-0"
PARTIAL FIRST FLOOR PLAN - MECH DUCTWORK
CONFERENCE
CORRIDOR
STORAGE
CONFERENCE
WAITING ROOM
TOILET
OFFICE
LOBBY
OFFICE
VAULT
JANITOR
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
IT STORAGE
IT STORAGE
CORRIDOR
IT STORAGE
IT STORAGE
OFFICE 133
WOMEN'S
OFFICE
OFFICE129
MEN'S
S02
STAIR
S03
STAIR
S01
STAIR
IT STORAGE
IT STORAGE
RE
FE
R
TO
M 2.
- 2
, P
AR
TI
AL
F
IR
ST
F
LO
OR
P
LA
N
FO
R
CO
NT
IN
UO
US
RE
FE
R
TO
M 2.
- 1
, F
IR
ST
F
LO
OR
P
LA
N
FO
R
CO
NT
IN
UO
US
CONFERENCE
CORRIDOR
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
CORRIDOR
CORRIDOR
OFFICE 113
STAGE
JANITOR
CORRIDOR
STORAGE
STORAGE
DRESSING
ROOM
DRESSING
ROOM
OFFICE
OFFICE
OFFICE
OFFICE
CORRIDOR
CORRIDOR
CORRIDOR
CONFERENCE
OAU-1
OAU-3
OAU-4
1 GREENHECK WALL LOUVERED DISCHARGE MODEL WL-10x3, EXHAUST 50 CFM.
GREENHECK WALL LOUVERED DISCHARGE MODEL WL-10x3, EXHAUST 75 CFM.
GREENHECK BVE-808 BRICK VENT, EXHAUST 50 CFM.
OUTSIDE AIR FROM OAU-1, BALANCE AT 80 CFM.
REPLACE EXISTING SIDEWALL GRILLE WITH NEW RETURN AIR GRILLE 36"x24" R-2, BALANCE
RETURN AIR FLOW AT 2,725 CFM.
PLAN KEY NOTES:
EF-A
6" Ø
1 1
6" Ø
6" Ø
EF-B
6" Ø
6"Ø
EF-A
6"Ø
EF-A
6" Ø
EF-A
x6
8x
EF-C
x6
8x
EF-C
6" Ø
1 11
EF-A
6"Ø
6"Ø
6"Ø
1 11
6"Ø
6" Ø
6" Ø
EF-A
6"Ø
EF-A
6"Ø x1
OA INTAKE LOUVER
1.8 SF FREE AREA
900 CFM
12" INTAKE PLENUM
FULL SIZE OF LOUVER
DH-1
x8 x8
DH-4
x8
OAU-2
OA INTAKE LOUVER
1.2 SF FREE AREA
600 CFM
12" INTAKE PLENUM
FULL SIZE OF LOUVER
DH-2
OA INTAKE LOUVER
1.2 SF FREE AREA
600 CFM
12" INTAKE PLENUM
FULL SIZE OF LOUVER
DH-3
OA INTAKE LOUVER
1.6 SF FREE AREA
800 CFM
12" INTAKE PLENUM
FULL SIZE OF LOUVER
x8
RTU-1
24x34 (TOP)
ODU-1 ODU-2 ODU-3 ODU-4 ODU-5
ODU-OA1 ODU-OA2
EXISTING OUTDOOR
EQUIPMENT /
HOUSEKEEPING PAD
IDU-1-01
MBC-1
MBC-2MBC-3 MBC-4
IDU-1-03
IDU-1-06A IDU-1-06B
IDU-1-07A IDU-1-07B IDU-1-09A IDU-1-09B
IDU-1-08
IDU-1-10
IDU-1-11A IDU-1-11B
IDU-1-12 IDU-1-13
IDU-1-14A IDU-1-14B IDU-1-15A IDU-1-15B
IDU-1-16A IDU-1-16B
IDU-1-17B
IDU-1-17A
IDU-1-18A
IDU-1-18C
IDU-1-18B
IDU-1-19A IDU-1-19B
IDU-1-20
IDU-1-20A
IDU-1-21
IDU-1-22
IDU-1-23
IDU-1-24
IDU-1-25 IDU-1-26A IDU-1-26B IDU-1-27
IDU-1-28
IDU-1-29A IDU-1-29B
IDU-1-30A
x8 x8
IDU-1-30B
IDU-1-11C IDU-1-11D IDU-1-11E
A. ALL EXISTING MECHANICAL EQUIPMENT / DUCTWORK SHALL
BE DEMOLISHED AND REMOVED.
GENERAL NOTES:
W
WALL
SWITCH
x1
8"Ø
T
S-1
8"Ø
16x10
10x1014x10
6x
R-1
12x12
TYP 2
x1
8"Ø
S-1
8"Ø
S-1
8"ØS-1
8"Ø
S-1
6"Ø
EF-A
IDU-1-02
x1
8"Ø
T
S-1
8"Ø
16x10
10x1014x10
R-1
12x12
TYP 2
x1
8"Ø
S-1
8"Ø
S-1
8"Ø
S-1
8"Ø
EF-A EF-A
EF-A
EF-A
EF-A
EF-A
EF-A
IDU-1-04
x1
8"Ø
T
S-1
8"Ø
16x10
10x1014x10
R-1
12x12
TYP 2
x1
8"Ø
S-1
8"Ø
S-1
8"ØS-1
8"Ø
IDU-1-05
x1
8"Ø
T
S-1
8"Ø
16x10
10x1014x10
R-1
12x12
TYP 2
x1
8"Ø
S-1
8"Ø
S-1
8"Ø
S-1
8"Ø
ODU-OA3
12" EXHAUST AIR PLENUM
FULL SIZE OF LOUVER
EXHAUST AIR LOUVER
0.5 SF FREE AREA
300 CFM
EXHAUST AIR
LOUVER 0.5 SF
FREE AREA
200 CFM
12" EXHAUST AIR
PLENUM FULL SIZE
OF LOUVER
E-1
8x6
TYP 2
E-1
8x6
TYP 2
x1
8" Ø
14x1016x10
"Ø
10"Ø
"Ø
16x10 16x10
S-1
6"Ø
16x10 16x10
S-1
6"Ø S-1
6"Ø
12x8 10x8
6"Ø
8" Ø
8x8 16x8 12x8
6x
14x8
8" Ø
10x8 8x8
8" Ø
6"Ø
S-1
6"Ø
S-1
8"Ø
S-2
6"Ø
S-2
6"Ø
S-1
6"Ø
S-1
8"ØS-1
8"Ø
S-3
6x6
S-1
8"Ø
S-1
10"Ø
S-1
10"Ø
S-1
10"Ø
TTO IDU-1-17A
& IDU-1-17B
T
TO IDU-1-18A
THROUGH
IDU-1-18D
C
C TO ODU-3
OA DAMPER
TO
IDU-1-02
TO
IDU-1-01
T
TO
IDU-1-03
TO
IDU-1-04
TO
IDU-1-05
T
TO
IDU-1-06A T
TO
IDU-1-06B
T
TO IDU-1-07A
& IDU-1-7B
C
TO IDU-1-09A
& IDU-1-9B
T
TO
IDU-1-08
T
TO
IDU-1-10
T
TO OAU-1
OA DAMPER
WH-1
T
8"Ø
16x8
8"Ø
16x8
16x8
8" Ø
14x8
6" Ø
12x8
8" Ø
8x8
6" Ø
8x6
8x
6"Ø
16x8
8" Ø
14x8
6" Ø
6" Ø
12x8
6" Ø
10x8
6" Ø
8x88x88x8
6" Ø
6" Ø
6" Ø
8x6
6" Ø
6x6
6"Ø
6" Ø
S-1
8"Ø
S-1
8"Ø
S-1
8"Ø
S-1
6"Ø
S-2
6"Ø S-1
8"Ø S-1
6"ØS-1
6"Ø
S-2
6"Ø
S-2
6"Ø
S-1
6"Ø
S-1
6"Ø
S-1
6"Ø
S-2
6"Ø S-1
6"Ø S-1
6"Ø S-1
6"Ø S-1
6"Ø S-1
6"Ø S-1
8"Ø
S-1
6"Ø
6x
6x
6x
T
TO IDU-1-11A
T
TO IDU-1-11B
T TO
IDU-1-11C
T TO IDU-1-11D T TO IDU-1-11E
T
TO IDU-1-12
T
TO
IDU-1-13 T
TO IDU-1-14A
& IDU-1-14B T
TO IDU-1-15A
& IDU-1-15B
T
TO IDU-1-06A
& IDU-1-16B
T
TO IDU-1-30A
& IDU-1-30B
T
TO IDU-1-20
T
TO
IDU-1-20A T
TO
IDU-1-21
T TO
IDU-1-22
T TO
IDU-1-23
T
TO
IDU-1-24
T
TO
IDU-1-25
T
TO IDU-1-26A
& IDU-1-26B
T
TO
IDU-1-27
T
TO
IDU-1-28
T
TO IDU-1-29A
& IDU-1-29B
6" HOUSEKEEPING
PAD
INSTALL OUTDOOR
UNITS ON 24" METAL
EQUIPMENT STANDS
INSTALL OUTDOOR UNITS ON
24" METAL EQUIPMENT STANDS
6" HOUSEKEEPING PAD
24x34 x1
24x30
6" Ø x1
6"Ø
8"Ø x2 x1
12"Ø x1
12"Ø
"Ø
12"Ø
24x20
12"Ø x1 x1 x1 x1
12"Ø
12"Ø x1 x1
8"Ø
8X6
6" Ø
"Ø
"Ø
T
IDU-1-18D
TO IDU-1-19A
& IDU-1-19B
C TO RTU-1
C T
C
TO RTU-1TO RTU-1
24x30 (BOTTOM)
6" HOUSEKEEPING
PAD
24x18
24x18
24x18
24x30
24x18 DOWN TO
SIDEWALL RETURN
AIR GRILLE
R-2
36x24 R-2
36x24
3 SCALE: NONE
SITE PHOTO -
CONFERENCE ROOM 116
5 5
OA INTAKE
1,200 CFM MIN /
6,650 CFM MAX
S-2
8"Ø S-2
8"Ø
S-2
6"Ø S-2
6"Ø
S-4
12"ØS-4
12"Ø
S-4
12"ØS-4
12"Ø
S-4
12"Ø
TYP 11
S-2
6"ØS-2
6"Ø
T-1-12x12
TYP 2
14x12
T-1-12x12
TYP 2
14x12
0-
M
.d w g
Sheet
Scale
Project NO.
Date
PROJECT NAME AND ADDRESS
SEAL
CLIENT
Revision/IssueNo. Date
SHEET TITLE
G
LE
N W
O O
D E
LE
M
EN
TA
R Y
SC
H
O O
L C
O N
VE
R
SI
O
N
H
AL
IF
AX
R
O
AD
D
AN
VI
LL
E, V
A
23100
11/08/2023
AS NOTED
Lu+S
4924 DOMINION BLVD, STE A
GLEN ALLEN, VA 23060
p: 804.925.2600 f: 804.925.2170 www.LSEngineers.net
90% PROGRESS SET
NOT FOR
CONSTRUCTION
11/08/23
FIRST FLOOR PLAN -
MECHANICAL DUCTWORK
M2.1
UP
1 SCALE: 1/8" = 1'-0"
SECOND FLOOR PLAN - MECHANICAL DUCTWORK
2 SCALE: 1/8" = 1'-0"
BASEMENT FLOOR PLAN - MECHANICAL DUCTWORK
B01
ELECTRICAL
B02
CRAWL SPACE
S01
STAIR
S02
STAIR
S03
STAIR
WOMEN'S
OFFICE
OFFICE
MEN'S
CORRIDOR
OFFICE
ELECTRICAL
CORRIDOR
OFFICE
LOUNGE
OFFICE
OFFICE
OFFICE
JANITOR
OAU-5
x6
8x
EF-C
x6
8x
EF-C
6" Ø
6" Ø
EF-A
EF-A
DH-5
OA INTAKE LOUVER
1.6 SF FREE AREA
800 CFM22x8 22x8
12" INTAKE PLENUM
FULL SIZE OF LOUVERMBC-5
IDU-2-04B IDU-2-05
IDU-2-06
IDU-2-07A IDU-2-07B IDU-2-08A IDU-2-08B IDU-2-09A IDU-2-09B
IDU-2-02 IDU-2-03
IDU-2-10IDU-2-01
IDU-2-11A IDU-2-11B
EF-B
PLAN KEY NOTES:
GREENHECK WALL LOUVERED DISCHARGE MODEL WL-10x3, EXHAUST 75 CFM.
6"Ø
W
UH-1
UH-2
EF-1
x1 x8
12x10 x1
10x12 EXHAUST, 45°
ELBOW DOWN WITH
WMS DISCHARGE
OPENING, 550 CFM
M
OA INTAKE LOUVER
1.0 SF FREE AREA
550 CFM
12" OA INTAKE PLENUM
WITH MOTORIZED DAMPER,
FULL SIZE OF LOUVER
W T
EF-1 WALL
SWITCH
TO UH-1 &
UH-2
WALL
SWITCH
A. ALL EXISTING MECHANICAL EQUIPMENT / DUCTWORK SHALL
BE DEMOLISHED AND REMOVED.
GENERAL NOTES:
EXHAUST AIR
LOUVER 0.5 SF
FREE AREA
300 CFM
12" EXHAUST AIR
PLENUM FULL SIZE
OF LOUVER
EXHAUST AIR
LOUVER 0.5 SF
FREE AREA
200 CFM
12" EXHAUST AIR
PLENUM FULL SIZE
OF LOUVER
E-1
8x6
TYP 2
E-1
8x6
TYP 2
E-2
10x10
E-2
10x10
18x816x812x8 8x8
8x
8x6 6"Ø
6" Ø
6" Ø
6" Ø
6" Ø
6" Ø
6" Ø
6" Ø
6" Ø
6" Ø
10x8
8x6
6"ØS-1
6"Ø
IDU-2-04A
S-2
6"Ø
S-1
6"Ø S-1
6"Ø S-1
6"Ø
S-1
6"Ø S-1
6"Ø S-1
6"Ø S-2
6"Ø
S-1
6"Ø S-1
6"Ø
S-1
6"ØS-2
6"Ø
T
T T T
T T
T T T
T
T TTO
IDU-2-11A
TO
IDU-2-11B
TO IDU-2-04A
& IDU-2-04B
TO IDU-2-07A
& IDU-2-07B
TO
IDU-2-02
TO
IDU-2-01
TO
IDU-2-03
TO
IDU-2-05
TO
IDU-2-06
TO IDU-2-08A
& IDU-2-08B
TO IDU-2-09A
& IDU-2-09B
TO
IDU-2-10
0-
M
.d w g
Sheet
Scale
Project NO.
Date
PROJECT NAME AND ADDRESS
SEAL
CLIENT
Revision/IssueNo. Date
SHEET TITLE
G
LE
N W
O O
D E
LE
M
EN
TA
R Y
SC
H
O O
L C
O N
VE
R
SI
O
N
H
AL
IF
AX
R
O
AD
D
AN
VI
LL
E, V
A
23100
11/08/2023
AS NOTED
Lu+S
4924 DOMINION BLVD, STE A
GLEN ALLEN, VA 23060
p: 804.925.2600 f: 804.925.2170 www.LSEngineers.net
90% PROGRESS SET
NOT FOR
CONSTRUCTION
11/08/23
BASEMENT AND SECOND FLOOR
PLANS - MECHANICAL DUCTWORK
M2.2
DN
DN
UP UP
1 SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - MECHANICAL PIPING
2 SCALE: 1/8" = 1'-0"
PARTIAL FIRST FLOOR PLAN - MECH PIPING
CONFERENCE
CORRIDOR
STORAGE
CONFERENCE
WAITING ROOM
TOILET
OFFICE
LOBBY
OFFICE
VAULT
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
IT STORAGE
IT STORAGE
CORRIDOR
IT STORAGE
IT STORAGE
OFFICE 133
WOMEN'S
OFFICE
OFFICE129
MEN'S
S02
STAIR
S03
STAIR
S01
STAIR
IT STORAGE
IT STORAGE
RE
FE
R
TO
M 2.
- 2
, P
AR
TI
AL
F
IR
ST
F
LO
OR
P
LA
N
FO
R
CO
NT
IN
UO
US
RE
FE
R
TO
M 2.
- 1
, F
IR
ST
F
LO
OR
P
LA
N
FO
R
CO
NT
IN
UO
US
CONFERENCE
CORRIDOR
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
CORRIDOR
CORRIDOR
OFFICE 113
STAGE
JANITOR
CORRIDOR
STORAGE
STORAGE
DRESSING
ROOM
DRESSING
ROOM
OFFICE
OFFICE
OFFICE