Attachment 9 - Drawings 679-21-102_Part3.pdf
PDF 12 MB Posted
- Attached to
- Y1DA--679-21-102 | Correct Failing Sanitary Sewer, Water Main, and Fire Protection Deficiencies
- Solicitation number
- 36C24725R0044
About this file
This is a set of engineering drawings showing details for fire suppression systems, water lines, pavement repairs, and related infrastructure improvements at the Tuscaloosa VA Medical Center in Alabama. The drawings include plans, elevations, sections and details for replacing an existing fire pump system in Building 1, with specifications for a new 500 GPM vertical split case electric fire pump with 40 psig suction pressure. The drawings also show water line layouts, thrust blocking details, standard pipe foundation details, backflow prevention assemblies, and pavement/site repair details. Key components include mechanical joint fittings, gate valves, water meters, sampling stations, and air release assemblies.
The drawings provide construction details for water line installations including trench sections, concrete thrust blocks, mechanical couplings, and pavement restoration requirements. Specific requirements are given for pipe materials (C900 PVC and PE), minimum cover depths, clearances from other utilities, and restoration of concrete/asphalt surfaces. The drawings are part of VA Project #679-21-102 for correcting failing sanitary sewer, water main and fire protection deficiencies at the facility. Engineering firm Apogee Consulting Group prepared the drawings dated December 29, 2023.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N O
R T
H
20FT 5 00
SCALE: 1" = 10’
10 10
C-211
C
H
8"
H
L
8"x8"x4"
G
4"
4"
4"
A
A
8"
8"
L
L
A
L
M
G
J
PARTIAL ENLARGED PLAN
WATER LINE LAYOUT
PARTIAL ENLARGED PLAN
WATER LINE LAYOUT
1 1/2"
W
W
W
W
W
W
W
W
W
W
W
W
W
G
G
G
G
G
G
G
S S
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
UGE
U G
E
U G
E
UGE
U G
E
U G
E
UGE
U G
E
UGE
UGE
U G
E
UGE
SD
SD
SD
SD
SD
S D
FW
FW
FW
FW
FW
FW
FW
FW
FW
FW
FW
FW
FW
FW
FW
T
T
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
SHEET NOTES:
# KEY NOTES:
Date Checked Drawn
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
BCLC BCLC
224000
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
SHEET LAYOUT
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
TUSCALOOSA, AL, 35404
3701 LOOP ROAD
TUSCALOOSA VA MEDICAL CENTER
CORRECT FAILING SANITARY
SEWER, WATER MAIN, AND
FIRE PROTECTION DEFICIENCIES
679-21-102
Ballard Project Number
N/A
33A142
13960
DEC. 29, 2023
WATER LINE LEGEND:
A
B
C
D
E
F
G
H
J
K
L
M
LEGEND:
W
W
FW
W
N
O
P
R
U.S. Department of Veterans Affairs
LI
EN
DESCA
L A A M
A B
J A
M
E S
BR YAN
BU
T L
E R
E
NGINE
RE
PROFESSIONAL
NO. 28875
8" C900 WATER LINE
6" C900 WATER LINE
4" C900 WATER LINE
3" PE WATER LINE
2" PE WATER LINE
1" PE WATER LINE
WATER LINE BY JACK & BORE
APPROVAL BY LOCAL VA
GATE VALVES W/ BOX & PAD
NEW WATER METER & BOX
BACKFLOW PREVENTER
M.J. FITTING (TEES, BENDS & REDUCERS)
TAPPING SLEEVE & VALVE (HOT TAP)
SERVICE SADDLE & CORP STOP
SAMPLING STATION
AIR RELEASE ASSEMBLY
CUT & CAP EXIST. SERVICE LINE
CONNECT W/ COMPRESSION TYPE FITTING
CONTRACTOR SHALL SAWCUT EXISTING
CONCRETE SIDEWALK / PAVEMENT, REMOVE
& RECONSRUCT NEW SIDEWALK OR PAVEMENT
AFTER NEW WATER LINES ARE INSTALLED
(MATCH EXISTING SIDEWALK OR PAVEMENT
WIDTH, DEPTH & ELEVATIONS.
CONTRACTOR SHALL SAWCUT OR BORE
EXISTING ROADWAY OR PAVMENT AS DIRECTED
IN THE PLANS.
SAWCUT ALL CONCRETE CURBS CROSSED WITH
OPEN CUT , REMOVE AND RECONSTRUCT.
REMOVE & RE-INSTALL CHAIN LINK FENCE.
OPEN CUT EXISTING AGGREGATE SURFACE &
RESTORE TO ORIGINAL CONDITION.
OPEN CUT EXISTING LANDSCAPED AND
PLAYGROUND AREAS AND RESTORE TO
ORIGINAL CONDITION.
REMOVE EXISTING TREE, REPLACE TREE WITH
NEW TREE. (MATCH SIZE & TYPE)
CONTRACTOR SHALL SAWCUT ASPHALT
PAVEMENT, REMOVE & RESTORE AFTER NEW
WATER LINE INSTALLATION. (MATCH WIDTH,
DEPTH & ELEVATIONS.
FUTURE U.G. STEAM LINE PROJECT
FUTURE U.G. EHRM PROJECT
FUTURE ELECTRICAL PROJECT
NOTE:
NOT ALL NOTES USED ON EACH SHEET.
CONTRACTOR SHALL COORDINATE ALL
WORK WITH THE VA HOSPITAL ENGINEERING
OFFICE.
ALL ASPHALT ROADWAYS AND PARKING AREAS
SHALL BE OPEN CUT OR JACK AND BORED.
COORDINATE WITH CONSTRUCTION PLANS.
ALL BORING SHALL BE APPROVED BY LOCAL
VA.
ALL CONCRETE SIDEWALKS, ROADWAYS, OR
PARKING LOTS SURFACES THAT ARE OPEN
CUT SHALL BE RESTORED TO ORIGINAL
CONDITIONS.
1.
2.
3.
SURVEY CONTROL POINT
EXISTING BUILDINGS
NEW WATER SAMPLING STATION
NEW AIR RELEASE ASSEMBLY
NEW RPZ & ENCLOSURE
NEW M.J. FITTINGS
NEW WATER METER & BOX
NEW WATER VALVE
NEW WATER LINE BY JACK & BORE
NEW WATER LINE
EXISTING FIRE HYDRANT
EXISTING FIRE LINE
EXISTING WATER LINE
12-29-2023
R T
H
20FT 5 00
SCALE: 1" = 10’
10 10
C-212
A
C
M
A
8"x8"x4"
8" L
L
8"
A
4"
H
H 8"
4"x3"R
3"
K
1"
L
D
4"
H
8"x8"x8"
8"x4"
L
L
8"
H
L L
4"
A
C
A
G
L 4"
4"
J
J
PARTIAL ENLARGED PLAN
WATER LINE LAYOUT
PARTIAL ENLARGED PLAN
WATER LINE LAYOUT
1 1/2"
3/4"
W
W
W
W
X
X
X
X
X
X
X X
X
X
X
X
X
X
UGE
UGE
S S
S S
S S
S S
S S
S S
S S
S D
SD
SD
SD
SD
SD
FW
FW
FW
FW
FW
FW
FW
FW
FW
FW
FW
FW
FW
FW
W
W
W
W
W
W
W W
W
W W
W
W
W
W
W
W
W
W
W
W
X
X
X
X
X
X
X
X
X
X
X
X
X
G
G
G
G
G
UGE
UGE
UGE
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E U G
E
T
W
W
W
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
SHEET NOTES:
# KEY NOTES:
Date Checked Drawn
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
BCLC BCLC
224000
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
SHEET LAYOUT
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
TUSCALOOSA, AL, 35404
3701 LOOP ROAD
TUSCALOOSA VA MEDICAL CENTER
CORRECT FAILING SANITARY
SEWER, WATER MAIN, AND
FIRE PROTECTION DEFICIENCIES
679-21-102
Ballard Project Number
N/A
33A142
13960
DEC. 29, 2023
WATER LINE LEGEND:
A
B
C
D
E
F
G
H
J
K
L
M
LEGEND:
W
W
FW
W
N
O
P
R
U.S. Department of Veterans Affairs
LI
EN
DESCA
L A A M
A B
J A
M
E S
BR YAN
BU
T L
E R
E
NGINE
RE
PROFESSIONAL
NO. 28875
8" C900 WATER LINE
6" C900 WATER LINE
4" C900 WATER LINE
3" PE WATER LINE
2" PE WATER LINE
1" PE WATER LINE
WATER LINE BY JACK & BORE
APPROVAL BY LOCAL VA
GATE VALVES W/ BOX & PAD
NEW WATER METER & BOX
BACKFLOW PREVENTER
M.J. FITTING (TEES, BENDS & REDUCERS)
TAPPING SLEEVE & VALVE (HOT TAP)
SERVICE SADDLE & CORP STOP
SAMPLING STATION
AIR RELEASE ASSEMBLY
CUT & CAP EXIST. SERVICE LINE
CONNECT W/ COMPRESSION TYPE FITTING
CONTRACTOR SHALL SAWCUT EXISTING
CONCRETE SIDEWALK / PAVEMENT, REMOVE
& RECONSRUCT NEW SIDEWALK OR PAVEMENT
AFTER NEW WATER LINES ARE INSTALLED
(MATCH EXISTING SIDEWALK OR PAVEMENT
WIDTH, DEPTH & ELEVATIONS.
CONTRACTOR SHALL SAWCUT OR BORE
EXISTING ROADWAY OR PAVMENT AS DIRECTED
IN THE PLANS.
SAWCUT ALL CONCRETE CURBS CROSSED WITH
OPEN CUT , REMOVE AND RECONSTRUCT.
REMOVE & RE-INSTALL CHAIN LINK FENCE.
OPEN CUT EXISTING AGGREGATE SURFACE &
RESTORE TO ORIGINAL CONDITION.
OPEN CUT EXISTING LANDSCAPED AND
PLAYGROUND AREAS AND RESTORE TO
ORIGINAL CONDITION.
REMOVE EXISTING TREE, REPLACE TREE WITH
NEW TREE. (MATCH SIZE & TYPE)
CONTRACTOR SHALL SAWCUT ASPHALT
PAVEMENT, REMOVE & RESTORE AFTER NEW
WATER LINE INSTALLATION. (MATCH WIDTH,
DEPTH & ELEVATIONS.
FUTURE U.G. STEAM LINE PROJECT
FUTURE U.G. EHRM PROJECT
NOTE:
NOT ALL NOTES USED ON EACH SHEET.
CONTRACTOR SHALL COORDINATE ALL
WORK WITH THE VA HOSPITAL ENGINEERING
OFFICE.
ALL ASPHALT ROADWAYS AND PARKING AREAS
SHALL BE OPEN CUT OR JACK AND BORED.
COORDINATE WITH CONSTRUCTION PLANS.
ALL BORING SHALL BE APPROVED BY LOCAL
VA.
ALL CONCRETE SIDEWALKS, ROADWAYS, OR
PARKING LOTS SURFACES THAT ARE OPEN
CUT SHALL BE RESTORED TO ORIGINAL
EXISTING BUILDINGS
NEW WATER SAMPLING STATION
NEW AIR RELEASE ASSEMBLY
NEW RPZ & ENCLOSURE
NEW M.J. FITTINGS
NEW WATER METER & BOX
NEW WATER VALVE
NEW WATER LINE BY JACK & BORE
NEW WATER LINE
EXISTING FIRE HYDRANT
EXISTING FIRE LINE
R T
H
20FT 5 00
SCALE: 1" = 10’
10 10
C-213
PARTIAL ENLARGED PLAN
WATER LINE LAYOUT
PARTIAL ENLARGED PLAN
WATER LINE LAYOUT
L 8"
H
8"
A
D
H
8" H
4"
L
8"x4"L
4"x3"
L
8"x8"x8"
H 8"
G
GGG
A
R 1"
L
J
8"x1"
1"
F
K 1"
J
L
K 1"
R
E
G
R
L 2"
J
N
8"x2"
A
G G
E
L 8"
A
R
L
E
L
8"
A A
2"
2"
H
SS
N
8"x2"
SS
H 2"
J
2"
2"
2"
2"
N
8"x2"
SS
H 2"
H
SS
1"
N
5/8"
5/8"
5/8"
5/8"
WWW
W
W
WWWWWWW
W
W
W
W W
W
CO
G G
G G G G G G G G
GGGGGG
G
G G
G
GG
G
STM STM
S T
M
STM STM STM STM
STM
STM
UGE
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
UGE
FW
FW
FW
FW
FW
FW
FW FW FW
FW FW
FW
UGEUGEUGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
SS
SS
SS
FW
FW
F
W FW
W
W
W
W W W W W
W
W
W
W W W W W
W
S D
S D
SD
W
WWW
W
WW
W
WWWW
CO
G G G G G G G
G G
G
GGG
G
G
G G
G
GG
G
GG
STM STM STM
STM
UGE
UGE
STM
STM
S T
M
S T
M
S T
M
STM
STM STM
FW
FW
FW
FW
FW FW
F W
AC AC
W W W
W
W W W W W W W W W W
W
W W W
W
W
W
SD
SD
SD
S D
S D
SD SDSD SD
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
SHEET NOTES:
# KEY NOTES:
Date Checked Drawn
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
BCLC BCLC
224000
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
SHEET LAYOUT
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
TUSCALOOSA, AL, 35404
3701 LOOP ROAD
TUSCALOOSA VA MEDICAL CENTER
CORRECT FAILING SANITARY
SEWER, WATER MAIN, AND
FIRE PROTECTION DEFICIENCIES
679-21-102
Ballard Project Number
N/A
33A142
13960
DEC. 29, 2023
WATER LINE LEGEND:
A
B
C
D
E
F
G
H
J
K
L
M
LEGEND:
W
W
FW
W
N
O
P
R
U.S. Department of Veterans Affairs
LI
EN
DESCA
L A A M
A B
J A
M
E S
BR YAN
BU
T L
E R
E
NGINE
RE
PROFESSIONAL
NO. 28875
8" C900 WATER LINE
6" C900 WATER LINE
4" C900 WATER LINE
3" PE WATER LINE
2" PE WATER LINE
1" PE WATER LINE
WATER LINE BY JACK & BORE
APPROVAL BY LOCAL VA
GATE VALVES W/ BOX & PAD
NEW WATER METER & BOX
BACKFLOW PREVENTER
M.J. FITTING (TEES, BENDS & REDUCERS)
TAPPING SLEEVE & VALVE (HOT TAP)
SERVICE SADDLE & CORP STOP
SAMPLING STATION
AIR RELEASE ASSEMBLY
CUT & CAP EXIST. SERVICE LINE
CONNECT W/ COMPRESSION TYPE FITTING
CONTRACTOR SHALL SAWCUT EXISTING
CONCRETE SIDEWALK / PAVEMENT, REMOVE
& RECONSRUCT NEW SIDEWALK OR PAVEMENT
AFTER NEW WATER LINES ARE INSTALLED
(MATCH EXISTING SIDEWALK OR PAVEMENT
WIDTH, DEPTH & ELEVATIONS.
CONTRACTOR SHALL SAWCUT OR BORE
EXISTING ROADWAY OR PAVMENT AS DIRECTED
IN THE PLANS.
SAWCUT ALL CONCRETE CURBS CROSSED WITH
OPEN CUT , REMOVE AND RECONSTRUCT.
REMOVE & RE-INSTALL CHAIN LINK FENCE.
OPEN CUT EXISTING AGGREGATE SURFACE &
RESTORE TO ORIGINAL CONDITION.
OPEN CUT EXISTING LANDSCAPED AND
PLAYGROUND AREAS AND RESTORE TO
ORIGINAL CONDITION.
REMOVE EXISTING TREE, REPLACE TREE WITH
NEW TREE. (MATCH SIZE & TYPE)
CONTRACTOR SHALL SAWCUT ASPHALT
PAVEMENT, REMOVE & RESTORE AFTER NEW
WATER LINE INSTALLATION. (MATCH WIDTH,
DEPTH & ELEVATIONS.
FUTURE U.G. STEAM LINE PROJECT
FUTURE U.G. EHRM PROJECT
NOTE:
NOT ALL NOTES USED ON EACH SHEET.
CONTRACTOR SHALL COORDINATE ALL
WORK WITH THE VA HOSPITAL ENGINEERING
OFFICE.
ALL ASPHALT ROADWAYS AND PARKING AREAS
SHALL BE OPEN CUT OR JACK AND BORED.
COORDINATE WITH CONSTRUCTION PLANS.
ALL BORING SHALL BE APPROVED BY LOCAL
VA.
ALL CONCRETE SIDEWALKS, ROADWAYS, OR
PARKING LOTS SURFACES THAT ARE OPEN
CUT SHALL BE RESTORED TO ORIGINAL
EXISTING BUILDINGS
NEW WATER SAMPLING STATION
NEW AIR RELEASE ASSEMBLY
NEW RPZ & ENCLOSURE
NEW M.J. FITTINGS
NEW WATER METER & BOX
NEW WATER VALVE
NEW WATER LINE BY JACK & BORE
NEW WATER LINE
EXISTING FIRE HYDRANT
EXISTING FIRE LINE
C-300
M.J. TAPPING VALVE
POLYETHYLENE ENCASEMENT
AT ALL FITTINGS PER
AWWA C105
3/4 " CORP. STOP
FOR DISINFECTION
EXISTING WATER LINE
NEW C900 WATER MAIN
NATIVE SOIL
MIN. 12" EACH
SIDE OF PIPE
COMPACTED 95% OF STANDARD
PROCTOR DENSITY IN LIFTS OF
FIRM SUPPORT ENTIRE
BARRELL LENGTH
BELL HOLES
BASE AS REQUIRED
PAVEMENT SURFACE
NO GREATER THAN 8" COMPACTED
THICKNESS.
SIDE ELEVATION
BY TYPICAL SECTION
TRACER WIRE #10 GA
STRANDED COPPER
NATIVE SOIL
BACKFILL WITH
NATIVE MATERIAL
TYPE 1 BEDDING
TYPE 1 & 6 BEDDING
SELECT BACKFILL MATERIAL-
PIPE O.D.
+ 8" (MIN.)
PIPE O.D. = 24"
MINIMUM 12"
MINIMUM 45^
W id th
S.S. EPOXY COATED
TAPPING SADDLE
(MUELLER H-304SS)
SLOPE TO DRAIN
CONCRETE PAD WHEN NOT
LOCATED IN PAVED
5 1/4" DIA. SCREW TYPE
(HEAVY ROADWAY TYPE)
STREET OR SIDEWALK.
#10 GAUGE STRANDED COPPER TRACER WIRE
2’ DIAMETER x 6" THICK
CONTRACTOR SHALL DRILL HOLE IN VALVE
TRACER WIRE
3M MODEL DBR
SPLICE KIT
1- 80lb. BAG
SACKRETE
UNDER VALVE
7"
CAST IRON COVER
IN STREET OR DRIVEWAY.
WATER
60"
NORMAL
PIPE DEPTH
WATER MAIN
1/4 " TYP.
WATER MAIN
PAD AROUND VALVE BOX,
WHEN NOT LOCATED
WATER COVER TO BE
PAINTED MEDIUM BLUE.
WITH THE WORD
"WATER" ON TOP.
1/4 " TYP.
ATTACHED TO C.I. VALVE BOX
BOLT CONNECTOR OR AN APPROVED EQUAL.
W/ A THOMAS & BETTS TYPE "H" SPLIT
BOX TO ACCOMMODATE SPLITBOLT
CONNECTOR.
NO SCALE
SERIES 1300-C RESTRAINT DEVICE
or APPROVED EQUAL.
NO SCALE
CONCRETE
THRUST
BLOCK
NO SCALE
NO SCALE
NO SCALE
WIRE NUT
SPLICE CAP
PLASTIC NON-REMOVABLE
"3M" ELECTRICAL PRODUCTS DIVISION
PART NO. 054007-09964
(OR APPROVED EQUAL)
DIRECT BURY SPICE KIT -
LOCATOR
WIRE
LOCATOR WIRE SPLICE DETAIL
WATER LINE
TRENCH SECTION
STANDARD GATE VALVE
INSTALLATION DETAIL
STANDARD PIPE FOUNDATION DETAILS
DUCTILE IRON, POLYVINYL CHLORINE (PVC) OR POLYETHYLENE (PE) PIPE
M.J. TAPPING SLEEVE
M.J. TAPPING VALVE
EXISTING WATER LINE
POLYETHYLENE ENCASEMENT
AT ALL FITTINGS PER
AWWA C105
NEW WATER MAIN
3/4 " CORP. STOP
FOR DISINFECTION
MINIMUM 12"
MINIMUM 45^
W id th
ENCLOSURE
3/4 " BRONZE
BALL VALVE
ANCHOR POST
W/ LOCKABLE BOX
NOTE:
SAMPLE STATION SHALL
BE GIL-EH101 OR APPROVED
EQUAL BY ENGINEER
REMAINDER OF
BACKFILL PLACED
PER SPECIFICATIONS
TRENCH BOTTOM
EXCAVATE BELL HOLE AT PIPE JOINTS
FOR UNIFORM SUPPORT ALONG THE
LENGTH OF THE PIPE.
(NO SEPARATE PAYMENT)
PLACED PER SPECS.
INITIAL BACKFILL
6"(MIN.)-12"(MAX.)
MARKER TAPE
PLACE TRACE WIRE
TOP ‘ PIPE IN OPEN
TRENCHING AREAS
(TYP.)
TAPE TRACE WIRE
TO TOP OF PIPE
WHERE BOREING
IS INDICATED (TYP.)
6"
GROUT BEFORE
SETTING FRAME
VULCAN MANHOLE FRAME
& COVER MODEL #VM-72
NATURAL
GROUND
24" RCP TONGUE
& GROOVE JOINT
1/2" SHUT-OFF VALVE &
BACK FLUSHING HOSE
AIR RELEASE VALVE
1" BLOW OFF
CURB STOP (SIZE EQUAL
TO AIR RELEASE VALVE)
BRONZE TAPPING SADDLE
MAIN LINE
M
IN
C
O V
E R
SAMPLING STATION DETAIL
TYPE 2 BEDDING
PIPE O.D. +
T Y
P
NEW WATER LINE
CONC. THRUST BLOCK
SIMILAR TO TEE
SEE THRUST BLOCKING
DETAIL SHEET
S.S. TAPPING SLEEVE &
VALVE DETAIL
M.J. TAPPING SLEEVE &
VALVE DETAIL
NO SCALE
AIR RELEASE ASSEMBLY
NO SCALE
NOTE:
TRACE WIRE SHALL BE SECURELY TAPED
TO PIPE IN BORING SITUATIONS. CONTRACTOR
SHALL TEST WIRE AFTER INSTALLATION OF PIPE.
M.J. JOINTS WITH MEGALUG OR FORD UNI-FLANGED
NO SCALE
NO SCALE
2’ SQUARE, 6" THICK
REINF. CONCRETE
WV-00
OR EQUAL WITH A
M.J. - MECHANICAL JOINT
NOTE:
1. TAP TO BE PERFORMED
BY UTILITY CONTRACTOR
2. ALL M.J. CONNECTIONS SHALL
INSTALLED WITH MEGALUG
R.J. GLAND ADAPTERS OR
APPROVED EQUAL.
IDENTIFICATION TAG
(AR-#00)
ENGRAVED BRONZE
VALVE PLATE
W/ NUMBER
ENGRAVED BRONZE
PLATE W/ NUMBER
2’-0"
SQUARE
#3 BAR
NO. 3 BAR ALL
AROUND (WITH 1"
OVERLAP)
CONTRACTOR SHALL
PRESENT WATER VALVE
NUMBERING PLAN TO VA
FOR PRIOR APPROVAL
C.I. VALVE BOX W/ EXTENSIONS
WATER VALVE &
MISC. WATER LINE DETAILS
DUCTILE IRON OR
CAST IRON PIPE
COUPLING
FACE OF BUILDING
(SEE MECH. PLANS)
MECHANICAL
PVC WATER OR FIRE WATER
FINISHED, INSTALLED &
AIR TESTED AGAINST
TEMP. PLUG.
5’ OR AS CALLED
FOR IN PLANS
NO SCALE
MECHANICAL COUPLING
CONNECTION DETAIL
NATIVE SOIL
Engineers Architects
Revisions: Date
Drawing Title
Location
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
224000
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
TUSCALOOSA, AL, 35404
3701 LOOP ROAD
TUSCALOOSA VA MEDICAL CENTER
Approved
Project Title VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
Date Checked Drawn
BCLC BCLC
CORRECT FAILING SANITARY
SEWER, WATER MAIN, AND
FIRE PROTECTION DEFICIENCIES
679-21-102
N/A
DEC. 29, 2023 27
U.S. Department of Veterans Affairs
LI
EN
DESCA
L A A M
A B
J A
M
E S
BR YAN
BU
T L
E R
E
NGINE
RE
PROFESSIONAL
NO. 28875
C-301
NOTES
1. Each Mechanical Joint fitting and/or Restraint Device shall be wrapped in
2. Thrust blocking will not be required to restrain Mechanical Joint fittings that are installed for water line conflicts.
8 mil. polyethelene encasement (polywrap).
3. Water line installation shall clear obstruction(s) by a distance of no less than one (1) foot - six (6) inches. Measurement shall be from outside face of obstruction to outside diameter of pipe being installed.
Iron Mechanical Joint Anchoring Kit manufactured by Independent Pipe Products
5. Contractor shall install #10 guage, Type TW stranded copper wire along the top of PVC or PE pipe for detection purposes.
CONFLICT DETAIL
4" DIA. TO 12" DIA. WATER LINE
(VERTICAL or HORIZONTAL)
WATER LINE CONFLICT
TO MECHANICAL JOINT TEE
Fitting
(2) Standard 20’ Lengths of Pipe
(or approved equal), Restraint Device required.
w/ Ford Uni-Flanged Series 1390-C ,
(2) Standard 20’ Lengths of Pipe
(or approved equal), Restraint Device required.
w/ Ford Uni-Flanged Series 1390-C , Restraint Device, or approved equal, for all Mechanical Joint fittings (TYP).
Ford Uni-Flanged Series 1390-C
Restraint Device, or approved equal, (TYP.)
Fitting
(2) Standard 20’ Lengths of Pipe
(or approved equal), Restraint Device required.
w/ Ford Uni-Flanged Series 1390-C , Ford Uni-Flanged Series 1390-C
Restraint Device, or approved equal, (TYP.)
M.J. VALVE
Restraint Device, or approved equal, for all Mechanical Joint fittings (TYP).
P.E. Pipe
45%%d or 90%%d M.J.
Fitting45%%d or 90%%d M.J. Fitting
M.J. TEE
NO SCALE
NO SCALE
4. Contractor may use Fuseable Polyvinyl Chlorine (PVC) Pipe and Fittings to go under or around conflicts with Restraint Device(s). Connector for Polyvinyl Chlorine (PVC) Pipe to Mechanical Joint Fitting shall be a Ductile
(or approved equal) for 6" thru 12" Ductile Iron Pipe Size.
45%%d or 90%%d M.J. Fitting
45%%d or 90%%d M.J.
45%%d or 90%%d M.J.
Restraint Device, or approved equal, (TYP.)
Ductile Iron Long Sleeve or Couple w/
Ductile Iron Long Sleeve or Couple w/ for all Mechanical Joint fittings (TYP).
PVC PIPE AT CONFLICTS
CHANGE IN DIRECTION AND
UNDER PAVEMENT DETAIL
END PIPE
DEFLECTION
FLOW LINE OF EXIST.
OR NEW DRAINAGE CHANNEL
EXIST. OBSTRUCTION,
DITCH OR CANAL
END PIPE
DEFLECTION
NEW PVC
WATER LINE
EXISTING CONFLICT PIPE
(SIZE & DEPTH VARIES)
NATURAL GRADE
TRACE WIRE TOP ‘ PIPE
M
IN
O R
D E
E P
E R
30’ PIPE DEFLECTION (MIN.) 30’ PIPE DEFLECTION (MIN.)
WATER LINE DEFLECTION DETAIL
NO SCALE
M
IN
PVC WATER LINE ADJUSTMENT FOR
CROSSING ABOVE CONFLICTS
6 FEET OR DEEPER
NO SCALE
SEE CHART
THIS SHEET
S E
E C
H A
R T
T H
IS
S
H E
E T
WATER LINE CLEARANCE CHART
UTILITY TYPE
SEWER
SEWER FORCE MAIN
CHILLED WATER
STORM SEWER / DRAIN
DUCT BANK / PIPED UTILITY
6’ (MIN.)
10’
HORIZ. VERTICAL
6’ (MIN.)
10’
6’ (MIN.)
5’ (MIN.)
3’ (MIN.)
18"(MIN.)
18"(MIN.)
18"(MIN.)
18"(MIN.)
18"(MIN.)
24"
FUSABLE C900 PVC WATER LINE
SEE PLANS FOR SIZES
Engineers Architects
Revisions: Date
Drawing Title
Location
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
224000
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
TUSCALOOSA, AL, 35404
3701 LOOP ROAD
TUSCALOOSA VA MEDICAL CENTER
Approved
Project Title VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
Date Checked Drawn
BCLC BCLC
CORRECT FAILING SANITARY
SEWER, WATER MAIN, AND
FIRE PROTECTION DEFICIENCIES
679-21-102
N/A
DEC. 29, 2023 27
U.S. Department of Veterans Affairs
LI
EN
DESCA
L A A M
A B
J A
M
E S
BR YAN
BU
T L
E R
E
NGINE
RE
PROFESSIONAL
C-302
2.
TRACE WIRE TOP ‘ PIPE (TYP.)
TWO WIRE CLAMPS REQ’D.
@ EACH SPLICE (TYP.)
DISTANCE AS REQ’D.
TO CLEAR OBSTRUCTION
PE 45^ ELBOW
PE 45^ ELBOW
NEW PE WATER LINE
PE 45^ ELBOW
NEW PE WATER LINE
PE 45^ ELBOW
6" PE TRANSITION FITTING
(PVC-SJA) (DIPS) W/
BELL RESTRAINT RING 6" PE TRANSITION FITTING
(PVC-SJA) (DIPS) W/
BELL RESTRAINT RING
NEW PE WATER LINE
M.J. 90^ BEND
M.J. TEE
(SEE PLANS
FOR SIZES )
V A
R
IE
S
S E
E P
L A
N S
CONC. THRUST
(C-900 OR DUCTILE IRON)
(C-900 OR DUCTILE IRON)
(C-900 OR DUCTILE IRON)
NOTE:
CONTRACTOR HAS OPTION OF PUTTING M.J FITTINGS WITH1.
RETAINER GLANDS AND CONCRETE THRUST OR EQUAL.
ALL THREAD RODS RUNNING FROM FITTING TO FITTING AND
THRUST RODS
SEE NOTE NO. 1
TRACE WIRE TOP ‘ PIPE (TYP.)
@ EACH SPLICE (TYP.)
DISTANCE AS REQ’D.
TO CLEAR OBSTRUCTION
CONCRETE THRUST, OR M.J FITTINGS WITH MEGALUG
w/ R.J. CONNECTION w/ R.J. CONNECTION w/ R.J. CONNECTION w/ R.J. CONNECTION
& CONC. THRUST
& CONC. THRUST
& CONC. THRUST & CONC. THRUST
POLYETHYLENE ENCASEMENT
AT ALL FITTINGS PER
AWWA C105
M.J 45^ ELBOW
NEW PVC
WATER LINE
NEW PVC WATER LINE
M.J 45^ ELBOW
NEW PVC WATER LINE
M.J 45^ ELBOW
M.J 45^ ELBOW
NEW PVC WATER LINE
NEW PVC
WATER LINE
CONTRACTOR SHALL COORDINATE THIS WORK WITH
TWO WIRE CLAMPS REQ’D.
NEW PVC
WATER LINE
NEW PVC
WATER LINE
EXISTING S.D. PIPE, SEWER LINE,
DITCH OR OTHER OBSTRUCTION
EXISTING S.D. PIPE, SEWER LINE,
DITCH OR OTHER OBSTRUCTION
PE 90^ BEND
PE TRANSITION FITTING
(DIMJA-KIT) (DIPS)
M.J. TEE OR M.J. 90^ BEND
(SEE PLANS FOR SIZES )
NEW PE WATER LINE
NEW PVC WATER LINE
NEW PVC WATER LINE
NEW PVC WATER LINE
POLYETHYLENE ENCASEMENT
AT ALL FITTINGS PER
AWWA C105
THRUST RODS
SEE NOTE NO. 1
CONTRACTOR WILL HAVE THE OPTION
TO JACK & BORE WATERLINE. PE 45^
ELBOWS WILL NOT BE REQUIRED
CONCRETE THRUST BLOCK
W/ #4 REBAR WRAPPED
AROUND FITTING (TYP.)
LETON WATER SYSTEM.
EXISTING
SANITARY SEWER
FINISHED GRADE
NEW WATER
MAIN
EXISTING
SANITARY SEWER
NEW WATER MAIN
1’-6" MIN.
FINISHED GRADE
TYPICAL COVER OR
AS APPROVED BY ENGINEER
T H
IS
S
H E
E T
NO SCALE NO SCALE
PE WATER LINE ADJUSTMENT PE VERTICAL WATER LINE ADJUSTMENT
NO SCALE NO SCALE
PVC / D.I. WATER LINE ADJUSTMENT M.J. VERTICAL. WATER LINE ADJUSTMENT
T H
IS
S
H E
E T
T H
IS
S
H E
E T
T H
IS
S
H E
E T
NO SCALE
WATER / SANITARY SEWER CLEARANCES
10’ STANDARD
6’ MIN. (SPECIAL CONDITIONS)
WATER LINE CLEARANCE CHART
UTILITY TYPE
SEWER
SEWER FORCE MAIN
CHILLED WATER
STORM SEWER / DRAIN
DUCT BANK / PIPED UTILITY
6’ (MIN.)
10’
HORIZ. VERTICAL
6’ (MIN.)
10’
6’ (MIN.)
5’ (MIN.)
3’ (MIN.)
18"(MIN.)
18"(MIN.)
18"(MIN.)
18"(MIN.)
18"(MIN.)
24"
V A
R
IE
S
S E
E P
L A
N S
S E
E C
H A
R T
S E
E C
H A
R T
M
IN
S E
E C
H A
R T
S E
E C
H A
R T
PVC WATER LINE
ADJUSTMENT DETAILS
Engineers Architects
Revisions: Date
Drawing Title
Location
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
224000
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
TUSCALOOSA, AL, 35404
3701 LOOP ROAD
TUSCALOOSA VA MEDICAL CENTER
Approved
Project Title VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
Date Checked Drawn
BCLC BCLC
CORRECT FAILING SANITARY
SEWER, WATER MAIN, AND
FIRE PROTECTION DEFICIENCIES
679-21-102
N/A
DEC. 29, 2023 27
U.S. Department of Veterans Affairs
LI
EN
DESCA
L A A M
A B
J A
M
E S
BR YAN
BU
T L
E R
E
NGINE
RE
PROFESSIONAL
C-303
6" D.I. PIPE
M
IN
M
IN
RELIEF VALVE OUTLET
LOWEST POINT OR
4" THICK CONC. SLAB
PIPE
JACKS
4" PVC PIPE
(AWA C900)
NO SCALE
ASSEMBLY W/ VALVES
*WATTS REGULATOR CO.
MODEL 957 OR EQUAL
STRAINER FLG. 90^ BEND
FLOW
FLOW
NO SCALE
ASSEMBLY W/ VALVES
M
IN
C L
R
6"
MIN.
CLR.
TO BUILDING
STRAINER
4" THICK CONC. SLAB
33 3/8 "/31 3/8 "/30 9/16 "
4" PVC PIPE
(AWA C900)
GATE VALVE W/ N.R.S.
2 1/2 " F.D.
CONNECTION
GATE VALVE W/ N.R.S.
3" OR 4" LONG FLG.
D.I. SPOOL W/
THREADED FLG.
FOR F.D. CONNECTOR
2 1/2 " F.D.
CONNECTION
1/4 TURN FULL PORT
BRONZE BALL SHUT-OFF
VALVE #1
VALVE #2
BRONZE BALL SHUT-OFF
1/4 TURN FULL PORT
CHECK
VALVE #1
RELIEF VALVE
LOWEST POINT OR RELIEF
VALVE OUTLET
MIN.
12" MIN.
60" MAX.
OUTLET *WATTS REGULATOR CO.
MODEL 909M1 OR EQUAL
RPZ #1
RPZ #2
NO SCALE
12"
STRAINER
FLOW
FLOW
BRASS OR BRONZE
FITTING (CLASS 250)
TEST COCK #1
CHECK
6"
VALVE #2
BRONZE BALL SHUT-OFF
1/4 TURN FULL PORT
CHECK
VALVE #1
BRONZE BALL SHUT-OFF
1/4 TURN FULL PORT
BRASS OR BRONZE
FITTING (CLASS 250)
STRAINER
BRASS OR BRONZE
TEE (CLASS 250)
BRASS OR BRONZE
FITTING (CLASS 250)
BRASS OR BRONZE
FITTING (CLASS 250)
COMPRSSION
FITTING
COMPRSSION
FITTING
COMPRSSION
FITTING
COMPRSSION
FITTING
NO SCALE
1/4 TURN FULL PORT
BRONZE BALL SHUT-OFF
VALVE #1
TEST COCK #1
PVC PIPE
PVC PIPE
1/4 TURN FULL PORT
BRONZE BALL SHUT-OFF
VALVE #2
BACKFLOW PREVENTION
& METER DETAILS
3"
3"
1"
3"
1"
3"
3"
4"
4"
4"
4"
4"
3"
6"
* EXISTING - MAINTENANCE REQ’D.
REMOVE SILT FROM VAULT
** EXISTING - LEAVE AS IS
NO WORK
** EXISTING - LEAVE AS IS
NO WORK
BLDG.# SIZE RPZ Model# #Req’d.
BLDG.# SIZE RPZ Model# #Req’d.
17 2
1"
1"
PLAN VIEW
2" OR 1" RPZ BACKFLOW PREVENTION
ASSEMBLY W/ GATE VALVES
1/4 TURN FULL PORT
BRONZE BALL SHUT-OFF
2 1/2 " F.D.
HOSE NOZZLE
W/ CAP
VALVE
SIZE ADAPTER
2 1/2 " F.D.
HOSE NOZZLE
W/ CAP
SIZE ADAPTER
6"
12 1/8 "/10 1/8 "/10"
4", 3" & 2 1/2 " REDUCED
PRESSURE ZONE
19 1/2 "/14 3/8 " 5 15/16 "/3 3/4 "
4", 3" & 2 1/2 " RPZ
2", & 1" RPZ ASSEMBLY
RPZ ASSEMBLY
PVC PIPE
M.J. TEE
PVC PIPE
1" 2
FLOW
FLOW
90^ M.J. BEND (BOTTOM)
90^ FLG. BEND (TOP)
ROTATE AS REQ’D.
6" LONG FLG.
D.I. SPOOL W/
THREADED FLG.
FOR F.D. CONNECTOR
90^ M.J. BEND (BOTTOM)
90^ FLG. BEND (TOP)
ROTATE AS REQ’D.
GATE VALVE W/ N.R.S.
GATE VALVE W/ N.R.S.
INSULATED ALUMINUM
ENCLOSURE
INSULATED ALUMINUM
ENCLOSURE
INSULATED ALUMINUM
ENCLOSURE
4" THICK CONC.
MAINTENANCE PAD
4" THICK CONC.
MAINTENANCE PAD
INSULATED ALUMINUM
ENCLOSURE
GATE VALVE W/ N.R.S.
GATE VALVE W/ N.R.S.
NOTE:
ALL PIPES IN ENCLOSURE SHALL BE
WRAPPED WITH PIPE INSULATION
NOTE:
ALL PIPES IN ENCLOSURE SHALL BE
WRAPPED WITH PIPE INSULATION
NOTE:
CONTRACTOR SHALL INSTALL
ANY MISC. ITEMS / FITTINGS AS NEEDED
TO COMPLETE THIS INSTALLATION PER
VA & MFR REQUIREMENTS
NOTE:
CONTRACTOR SHALL INSTALL
ANY MISC. ITEMS / FITTINGS AS NEEDED
TO COMPLETE THIS INSTALLATION PER
VA & MFR REQUIREMENTS
PLAN VIEW
3", & 2 1/2" RPZ BACKFLOW PREVENTION
ASSEMBLY W/ GATE VALVES
ELEVATION VIEW
3", & 2 1/2" RPZ BACKFLOW PREVENTION
ASSEMBLY W/ GATE VALVES
ELEVATION VIEW
2" OR 1" RPZ BACKFLOW PREVENTION
ASSEMBLY W/ GATE VALVES
1"
2 1/2 "
60" MIN.
2"
DIP
ADJ. S.S.
SUPPORT
12"X12"X4" SUMP
FLOW
4"
ACCESS HATCH
WITH SAFETY
GRATING
6", 4" OR 3"
PVC PIPE
6", 4" OR 3"
PVC PIPE
4.
5.
6.
7.
8.
9.
ACCESS HATCH NOTES:
PROVIDE AN HIW SERIES (SINGLE LEAF) ACCESS FRAME AND COVER (WITH SAFETY
GRATE). AS MANUFACTURED BY HALLIDAY PRODUCTS. OR APPROVED EQUAL.
FRAME AND COVER SHALL HAVE A 1/4 " THICK, ONE-PIECE, MILL FINISH, EXTRUDED
ALUMINUM CHANNEL FRAME. INCORPORATING A CONTINUOUS COCRETE ANCHOR.
A 1 1/2 " DRAINAGE COUPLING SHALL BE LOCATED IN THE FRONT LEFT CORNER OF THE
CHANNEL FRAME. THE INSIDE OF THE FRAME SHALL HAVE A DOOR SUPPORT LEDGE
ON TWO (2) SIDES.
BOTH FRAME AND LEDGE SHALL BE SUPPORTED BY A FULL BED OF CLASS A CONCRETE.
THE DOOR PANEL SHALL BE 1/4 " ALUMINUM DIAMOND PLATE, REINFORCED TO
WITHSTAND A LIVE LOAD OF THE H-20 DESIGNATION.
DOOR SHALL OPEN TO 90 DEGREES AND AUTOMATICALLY LOCK WITH A STAINLESS
STEEL HOLD OPEN ARM WITH ALUMINUM RELEASE HANDLE.
FOR EASE OF OPERATION, DOOR SHALL INCORPORATE ENCLOSED STAINLESS STEEL
COMPRESSION SPRING ASSISTS. DOOR SHALL CLOSE FLUSH WITH THE FRAME.
HINGES AND ALL FASTENING HARDWARE SHALL BE STAINLESS STEEL.
UNIT SHALL LOCK WITH STAINLESS STEEL SLAM LOCK WITH REMOVABLE KEY AND HAVE
A NON-CORROSIVE HANDLE.
UNIT SHALL BE GUARANTEED AGAINST DEFECTS IN MATERIAL AND/OR WORKMANSHIP
FOR A PERIOD OF 10 YEARS.
NOTES:
SUITABLE FOR USE IN
OFF STREET LOCATION
WHERE NOT SUBJECTED TO
HIGH DENSITY TRAFFIC.
PROVIDE FULL BED OF
CLASS "A" CONCRETE
UNDER FRAME AND
SUPPORT ANGLES.
COVER SHOWN IN
OPEN POSITION
A CLEAR
OPENING
3 1/2 "
DRAINPIPE
PRIMER
REQUIRED
1/4 " THICK
EXTRUDED
ALUM. FRAME
CONT. CONCRETE
ANCHOR
METER VAULT PLAN
ACCESS HATCH PLAN
ACCESS HATCH PROFILE
METER VAULT ELEVATION
S.S. HINGES WITH
TAMPER PROOF
FASTENERS
S.S. & ALUM.
POSITIVE LOCKING
HOLD OPEN ARM
WITH S.S. SPRING
ASSIST
1 1/2 " PIPE COUPLING
LIFTING HANDLE
S.S. SLAM LOCK
"B" OVERALL
"A" CLEAR OPENING 6 3/4 "5 3/4 "
A
B
12"
MIN.
8"
MIN.
18"
MIN.
30"X30" HATCH
FLOW
BYPASS LINE REQ. WHEN SERVICE
CAN NOT BE INTERRUPTED (I.E.
HOSPITAL, SCHOOLS)
FLOW
12"
12"
WAFER CHECK
VALVE
STRAINER FLG.
TURBINE METER FLG.
BASE TEE FLG.
SUMP
SPOOL PIECE FLG.
DIP
NRS VALVE FLG.
(TYP.)
LINK-TYPE
COMPRESSION SEAL
W/ WALL SLEEVE
POLYPROPYLENE
STEP
C
2" BLIND FLG.
TAPPED 2" W/
2" BRASS PLUG
WATER SERVICE INSTALLATION
(2" AND SMALLER SERVICE LINES)
NO SCALE
STRUCTURE
5’ MIN.
METER BOX COVER W/LID & LID BOLT
W/ TOUCH PAD SET FLUSH TO FINISH
GRADE
CURB BOX
GRADE LINE
TRACER WIRE THAT EXTENDS A
MIN. OF 2’ ABOVE GRADE SHALL
BE COLIED IN THE METER BOX
CURB STOP
WATER MAIN
BLOCKING PAD
CORP. STOP
SERVICE
LATERAL
TRACER WIRE SHALL
PENETRATE VALVE BOX
APPROXIMATELY 6" BELOW
GRADE
METER
METER BOX 30" LONG
SHUT OFF VALVE
METER SETTER
CLEARANCE SHALL BE EQUAL
DISTANCE EACH SIDE OF SETTER
4"Hx3"W NOTCH
IN METER PIT
MIN.
12" MIN.
CLEARANCE
M
IN
12" OF 85% COMPACTED SOIL
METER CHAMBER TO BE SET
ON A FLAT BRICK
COUPLING
(IF NEEDED)
(SEE NOTE 6)
NOTES:
CENTER METER IN BOX, MIN 3" CLEARANCE ON ALL SIDES.
TRENCH, INSTALL, AND BACKFILL SERVICE LINE IN ACCORDANCE WITH VA SPECIFICATIONS.
SERVICE LINE MATERIALS SHALL MEET VA SPECIFICATIONS.
PROVIDE TRACE WIRE ALONG WATER SERVICE LINE. TRACE WIRE SHALL EXTEND INTO THE
CURB BOX AND METER PIT AND TERMINATE IN THE METER PIT.
IF WATER SERVICE BETWEEN MAIN AND WATER METER IS REPLACED WITH NON-METALIC PIPING, THERE SHALL BE A MINIMUM LENGTH OF TEN (10) FT OF METALLIC PIPING BETWEEN THE
BUILDING STRUCTURE AND METER PIT TO MAINTAIN PROPER GROUNDING OF BUILDING’S
ELECTRICAL SYSTEM.
CONCRETE STRUCTURE NOTES:
PRECAST CONCRETE METER VAULT SHALL BE DESIGNED FOR THE FOLLOWING
CONDITIONS STATED BELOW (1.1 THROUGH 1.5). SUBMIT CALCULATIONS TO
THE ENGINEER FOR REVIEW. ALL CALCULATIONS SHALL BE SIGNED AND SEALED
BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF ALABAMA:
1.1. STRUCTURE FILLED TO TOP WITH NO EXTERNAL SOIL PRESSURE.
1.2. STRUCTURE EMPTY WITH SOIL BACKFILL TO FINISHED GRADE. ASSUME
SOIL DRY DENSITY AT 95 LBS/C.F. ASSUME SOIL SATURATED TO
FINISHED GRADE.
1.3. STRUCTURE SHALL NOT FLOAT WITH SATURATED SOIL TO FINISHED
GRADE. ASSUME SOIL LOAD ON CONCRETE LIP AT 32 LBS/C.F. A
SAFETY FACTOR OF 1.5 SHALL BE PROVIDED IN THE FLOATATION
CALCULATIONS.
1.4. SOIL BEARING PRESSURE OF 2,500 PSI.
1.5. EFFECTS OF ALL VERTICAL LOADS ANTICIPATED ON THE FINISHED
STRUCTURE SHALL BE INCLUDED IN THE ANALYSIS AND DESIGN.
LOADING FROM PIPING AND EQUIPMENT, HOIST, SUPERSTRUCTURES,
SNOW, H-20 LIVE LOAD, AND ACTUAL DEPTH OF SOIL COVER SHALL
BE INCLUDED.
PRECAST VAULT STEPS SHALL BE MADE OF POLYPROPYLENE ENCASED STEEL
AS MANUFACTURED BY M.A. INDUSTRIES AND SHALL CONFORM TO ASTM
C478.
THE EXTERIOR OF ALL PRECAST PRODUCTS SHALL BE COATED WITH TWO
COATS OF BITUMASTIC PAINT, 16 TO 20 MIL DFT, TO FINISH GRADE USE
PROMASTIC 900 COAL TAR WATERPROOFING MANUFACTURED BY PROGUARD
COATING, INC., OR APPROVED EQUAL.
ALL ALUMINUM IN CONTACT WITH CONCRETE SHALL BE PAINTED WITH 2
COATS OF COAL TAR EPOXY OR ISOLATED FROM THE CONCRETE WITH 1/8 "
THICK NEOPRENE PADDING. ALL STEEL THRUST RESTRAINT ANGLES SHALL BE
WIRE BRUSHED AND PAINTED WITH 2 COATS OF COAL TAR EPOXY.
ALL PIPE COUPLINGS IN CONTACT WITH SOIL SHALL BE WIRE BRUSHED AND
PAINTED WITH 2 COATS OF COAL TAR EPOXY.
ALL CONCRETE ANCHORS AND HARDWARE SHALL BE STAINLESS STEEL.
PROVIDE COMMON KEYED LOCKS FOR ALL HATCHES, PANELS, DOORS AND
QUICK DISCONNECT CAPS ASSOCIATED WITH THIS PROJECT.
ALL CONCRETE STRUCTURES SHALL BE CONSTRUCTED WATERTIGHT. ALL
STRUCTURES SHALL BE WATERTIGHT AND SHALL BE TESTED FOR WATER
TIGHTNESS BY FILLING PRECAST STRUCTURE WITH WATER PRIOR TO BACK
FILLING. AN ACCEPTABLE LEAKAGE IS DEFINED AS A LOSS OF LESS THAN
1/2 " IN 24 HOURS AND NO VISIBLE LEAKS. REPAIR OF LEAKS IS REQUIRED
USING METHODS APPROVED BY THE VA.
DUAL SEAL II GASKETS DISTRIBUTED BY DUEL SEAL CORP., OR APPROVED
EQUAL.
SHALL MEET ASTM C923 REQUIREMENTS.
JOINTS IN STRUCTURE SHALL BE SEALED WITH BITUMEN CONSEAL.
CS-102-B JOINT SEALANT MATERIAL MANUFACTURED BY CONCRETE
SEALANTS, INC.
CONCRETE STRUCTURES SHALL MEET THE REQUIREMENTS OF ASTM C478.
CONCRETE fc=3,500 PSI AT 28 DAYS. TYPE III CEMENT. AI ENTRAINMENT
7% | 2%. ASTM C33 NO.57 OR NO.67 COURSE AGGREGATE.
REINFORCEMENT: WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185
BAR REINFORCEMENT SHALL BE GRADE 60. CONFORMING TO ASTM A615.
VERTICAL BAR REINFORCEMENT REQUIRED BETWEEN BASE SLAB AND FIRST
VERTICAL SECTION OF STRUCTURE.
9.
10.
11.
12.
13.
14.
15.
WATER METER NOTES:
ALL PIPE AND FITTINGS TO BE THE SAME SIZE AS THE METER. REDUCERS
ARE PERMITTED ONLY WITH PRIOR AUTHORIZATION FROM ENGINEER.
ALL PIPING BETWEEN THE TEES UPSTREAM AND DOWNSTREAM OF THE
METER SHALL BE DUCTILE IRON PIPE.
NEWLY CONSTRUCTED WATER LINES SHALL BE DISINFECTED IN ACCORDANCE
WITH VA SPECIFICATIONS.
WATER METERS 1 1/2 " AND GREATER SHALL BE NEPTUNE OR PRIOR
APPROVED EQUAL..
TRACER WIRE REQUIRED FROM EXISTING WATER MAIN TO METER VAULT.
ROUND METER VAULTS MAY BE SUBMITTED AS AN ALTERNATE TO THE
DEPICTED RECTANGULAR BOX. MINIMUM CLEARANCE SHALL STILL BE
PROVIDED.
THRUST BLOCKS REQUIRED ON ALL BYPASS LINE FITTINGS.
VALVE
VALVE
33 2" 2
2 1/2 " 957 2
909M1
909M1
909M1
909M1
909M1
909M1
909M1
909M1
909M1
909M1
BLDG.# SIZE RPZ Model# #Req’d.
2"
1"
5/8 "
1 1/2 "
5/8 "
3/4 "
5/8 "
5/8 "
3/4 "
5/8 "
5/8 "
3/4 "
BLDG.# SIZE
WATER METER CHART
1"
1 1/2 "
1 1/2 "
BLDG.# SIZE
1 1/2 "
5/8 "
5/8 "
1 1/2 "
3/4 "
1 1/2 "
3"
5/8 "
3/4 "
3/4 "
3/4 "
5/8 "
5/8 "
3/4 "
NORMAL
OPERATING
RANGE
80%
CAPACITY
(GPM)
METER
SIZE
3/4 "
1"
1 1/2 "
2"
3"
4"
5/8 " 0.1 - 20 GPM
0.1 - 35 GPM
0.4 - 55 GPM
0.8 - 125 GPM
1.5 - 160 GPM
0.75 - 500 GPM
1.5 - 1250 GPM
Engineers Architects
Revisions: Date
Drawing Title
Location
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
224000
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
TUSCALOOSA, AL, 35404
3701 LOOP ROAD
TUSCALOOSA VA MEDICAL CENTER
Approved
Project Title VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
Date Checked Drawn
BCLC BCLC
CORRECT FAILING SANITARY
SEWER, WATER MAIN, AND
FIRE PROTECTION DEFICIENCIES
679-21-102
N/A
DEC. 29, 2023 27
U.S. Department of Veterans Affairs
LI
EN
DESCA
L A A M
A B
J A
M
E S
BR YAN
BU
T L
E R
E
NGINE
RE
PROFESSIONAL
C-304
BACKFLOW PREVENTION
ENCLOSURE & PAD DETAILS
Bldg. # Size RPZ’s Enclosure Size Pad Size
WxLxH WxLxT
9"
6"
L W
CBA
52.5" (3") 16.75" (3")
* FIRE CONNECT FITTING SIDE
28" (3")
D E
F
1111 1111 11 11 11
#3 BARS CONT.
6"
9"
#3 BARS CONT.
4" THICK CONC. SLAB
W/ 6X6 #6/6 WWF
BFP ENCLOSURE
L
W
CBA*
* FIRE CONNECT FITTING SIDE
28" (2")
28" (1")
D E
F
(2
/2
(2
/2
6"
4"
" 1111 1111 11 11 11
#3 BARS CONT.
4"
6"
#3 BARS CONT.
4" THICK CONC. SLAB
W/ 6X6 #6/6 WWF
BFP ENCLOSURE
L
W
PLAN VIEW
ALUMINUM ENCLOSURE
NO SCALE NO SCALE
NO SCALE NO SCALE
NO SCALE
* FIRE CONNECT FITTING SIDE
4" THICK CONC. PAD
6" SQ. BLOCKOUT FOR
RISER PIPES (TYP.)
9" SQ. BLOCKOUT FOR
RISER PIPES (TYP.)
(2
/2
14" (2") 12" (1")
PLAN VIEW
2" OR 1" BACKFLOW PREVENTION PAD
SECTION VIEW
2" OR 1" BACKFLOW PREVENTION PAD
57" (2 1/2 ")28" (2 1/2 ") 14" (2 1/2 ")
INSULATED ALUMINUM ENCLOSURE
(CUSTOM SIZE)
REMOVABLE PANEL/DOORREMOVABLE PANEL/DOOR
R E
M O
V A
B L
E
P A
N E
L /D
O O
R
REMOVABLE PANEL/DOOR REMOVABLE PANEL/DOOR
PLAN VIEW
3" & 2 1/2" BACKFLOW PREVENTION PAD
SECTION VIEW
3" & 2 1/2" BACKFLOW PREVENTION PAD
C L
R
C L
R
1"
1"
23"3
2 1/2 " 60"x56"x36" 68"x64"x4"
72"x72"x38" 82"x86"x4"
1"
1"
1"
1"
1"
1"
6 1" 2
33 2" 2
2 1/2 " 60"x56"x36" 68"x64"x4"
50"x70"x36" 60"x82"x4"
33" (1")
40" (2")
50"x60"x36" 60"x72"x4"
50"x60"x36"
50"x60"x36"
50"x60"x36"
50"x60"x36"
60"x72"x4"
60"x72"x4"
60"x72"x4"
60"x72"x4"
50"x60"x36"
50"x60"x36"
60"x72"x4"
60"x72"x4"
50"x60"x36"
50"x60"x36"
60"x72"x4"
60"x72"x4"
BLDG. 135
NO SCALE
EXISTING CONCRETE VAULT WALL1
33 3/16 "
66"|
LIMITS OF REMOVAL
DEMOLITION NOTES:
EXISTING CONCRETE BUILDING WALL
SHUT OFF VALVES TO BYPASS WATER SERVICE
AND DRAIN WATER FROM LINE.
UNBOLT AND REMOVE EXISTING 4" BACKFLOW
PRZ ASSEMBLY AND STORE FOR REINSTALLATION.
CUT AND REMOVE 24"| OF EXISTING 4" S.S.
PIPE AND FLANGE.
BLDG. 135
EXISTING CONCRETE VAULT WALL1
EXISTING CONCRETE BUILDING WALL
INSTALL EXIST. 4" RPZ
BACKLOW ASSEMBLY
4"x4"x4" FLG. TEE
BRANCH FACING UP
EXISTING FLANGE
TO REMAIN IN PLACE
NEW 4" FLG. GATE VALVE
PLAN VIEW
EXISTING WATERLINE IN VAULT
NO SCALE
INSTALLATION NOTES:
INSTALL NEW THREADED
COMPANION FLANGE ON
S.S. PIPE
.6
PLAN VIEW
NEW WATERLINE CONNECTION
LAYOUT
NO SCALE
ELEVATION VIEW
NEW WATERLINE CONNECTION
LAYOUT
TOP OF EXISTING
CONCRETE VAULT WALL
BOTTOM OF EXISTING
CONCRETE VAULT
TO RPZ BACKFLOW
PREVENTOR
INSTALL EXIST. 4" RPZ
BACKLOW ASSEMBLY
INSTALL NEW THREADED
COMPANION FLANGE ON
S.S. PIPE
4"x4"x4" FLG. TEE
BRANCH FACING UP
NEW 4" FLG. SLEEVE
W/ UNI-FLG. (10"| LONG)
NEW 4" FLG. SLEEVE
W/ UNI-FLG. (10"| LONG)
NEW 4" FLG.
GATE VALVE
NEW 4" FLG.
GATE VALVE
NEW 4" FLG x PE D.I. PIPE
(FIELD VERIFY LENGTH)
NEW 4" D.I. WATER LINE
W/ INSULATION JACKET
NEW 4" FLG.
90^ FITTING
CORE EXISTING WALL
FOR PIPE INSTALLATION
GROUT VOID BETWEEN
PIPE & CORE
FIELD VERIFY LENGTH
F
IE
L D
V E
R
IF
Y
EXISTING 90^ BEND
(TO REMAIN)
EXISTING 4" S.S. WATER LINE
W/ INSULATION JACKET
(TO REMAIN)
EXISTING 4" S.S. WATER LINE
W/ INSULATION JACKET
(TO REMAIN)
EXISTING 90^ BEND
(TO REMAIN)
EXISTING 4" S.S. WATER LINE
W/ INSULATION JACKET
(TO REMAIN)
EXISTING 4" S.S. WATER LINE
W/ INSULATION JACKET
(TO REMAIN)
EXISTING 4" S.S. WATER LINE
W/ INSULATION JACKET
(TO REMAIN)
EXISTING 90^ BEND
(TO REMAIN)
EXISTING FLANGE
TO REMAIN IN PLACE
THREAD 4" S.S. PIPE AND INSTALL 4"
COMPANION FLANGE.
INSTALL EXISTING 4" RPZ BACKFLOW
ASSEMBLY.
INSTALL 4" TEE AND 4" VALVE, BOLT TEE
TO EXISTING FLANGE.
FIELD VERIFY SLEEVE LENGTH AND INSTALL.
INSTALL WALL BRACKETS AS NEEDED FOR
SUPPORT, MATCH EXISTING BRACKETS.
INSTALL 4" FLG. VALVE ON TOP OF TEE AND
TURN WATER SUPPLY BACK ON.
CORE VAULT WALL FOR 4" D.I. PIPE, INSTALL
PIPE AND FITTING TO COMPLETE THE CONNECTION.
GROUT VOID BETWEEN D.I. PIPE AND CORE HOLE,
INSTALL PIPE INSULATION JACKET.
CUT EXISTING
4" S.S. PIPE &
INSULATION JACKET
*IF IT IS NOT POSSIBLE TO THREAD
4" S.S. PIPE, THEN AN A M.J. COUPLING
IS ACCEPTABLE
T O
C L
E A
R D
O O
R W
A Y
F
IE
L D
V E
R
IF
Y
Engineers Architects
Revisions: Date
Drawing Title
Location
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
224000
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
TUSCALOOSA, AL, 35404
3701 LOOP ROAD
TUSCALOOSA VA MEDICAL CENTER
Approved
Project Title VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
Date Checked Drawn
BCLC BCLC
CORRECT FAILING SANITARY
SEWER, WATER MAIN, AND
FIRE PROTECTION DEFICIENCIES
679-21-102
N/A
DEC. 29, 2023 27
U.S. Department of Veterans Affairs
LI
EN
DESCA
L A A M
A B
J A
M
E S
BR YAN
BU
T L
E R
E
NGINE
RE
PROFESSIONAL
C-305
EXISTING
BASE
EXISTING
BASE
6" COMPACTED
SAND-CLAY-GRAVEL
MATERIAL (BASE COURSE)
EXISTING GRAVEL
OR DIRT SURFACE
7’-0" MAX.
NEW AGGREGATE
(SURFACE COURSE)
EXISTING
BASE
EXISTING
BASE
7’-0" MAX.
NEW 3" THICK HOT MIX
ASPHALT CONCRETE
(SURFACE COURSE)
TACK COAT
TACK COAT
4" THICK CONCRETE PAD
3500 PSI @ 28 DAYS
#4 BARS @ 12" o.c.e.w.
AT ROADS OR STREETS
ONLY
EXISTING
BASE
EXISTING
BASE
5’-0" MAX.
6" THICK CONCRETE PAD
3500 PSI @ 28 DAYS
EXISTING
CONCRETE
DRIVEWAY
#5 BARS @ 12" o.c.e.w.
EXISTING ASPHALT
SURFACE
12"
12"
SEE TRENCH SECTION
NO SCALE NO SCALE NO SCALE
CONCRETE DRIVE OR ROAD
REPAIR DETAIL
ASPHALT DRIVE OR ROAD
REPAIR DETAIL
DIRT, GRAVEL & TEMPORARY
DRIVE REPAIR DETAIL
12"
12"
SEE TRENCH SECTION
12" 12"
SEE TRENCH SECTION
CURB and GUTTER DETAIL
6" MONOLITHIC BARRIER TYPE
NO SCALE
24"
TREE
PROTECTION
AREA
ENTER
TREE PROTECTION SIGN NOTES
N.T.S.
TREE
PROTECTION
AREA
ENTER
2 3/8 " POSTS
12 GAUGE 2" OPENING
CHAIN LINK FABRIC WITH
BARBS TOP AND BOTTOM
3/4 " STRETCHER BAR AT CORNERS
18" GEOTEXTILE SILT FENCE
ON OUTSIDE OF CHAIN LINK
FENCE BURY IN 4" DEEP TRENCH
3/4 " STRETCHER BAR BANDS
MINIMUM 18" SPACING
SIGNAGE
(SEE DETAIL)
WIRE TIES AT
MINIMUM 18"
SPACING
TENSION WIRE TOP AND
BOTTOM WITH HOG RINGS
AT 2’ MIN. SPACING
TREE PROTECTION SIGNS TO BE MADE OF
DURABLE WEATHERPROFF MATERIAL.
LETTERS TO BE MINIMUM 3" HIGH.
PLACE SIGNS ON EACH END OF TREE
PROTECTION FENCE AND AT MINIMUM 50
FOOT INTERVALS THEREAFTER.
PROVIDE NO LESS THAN ONE SIGN PER
TREE PROTECTION AREA.
ATTACH SIGNS SECURELY TO FENCE POSTS.
PROMPTLY REPAIR OR REPLACE ANY
SIGNS DAMAGED OR REMOVED.
1.
2.
3.
4.
5.
6.
1/8 "
1"
4"
SIDEWALK SECTION
4"
4"
3/4 "
SIDEWALK
"TOOLED JOINT"
SIDEWALK
"EXPANSION JOINT"
TOOLED JOINT
TYPICAL & MAXIMUM JOINT SPACING
TO EQUAL WIDTH
PORTLAND CONC. (TYP.)
(MIN. 3500 P.S.I. @ 28 DAYS)
4" SCARFIED & RECOMPACTED
SUBGRADE NOT LESS THAN 90%
STD. PROCTOR DENSITY (ASTM 698)
(TYP.)
(MAX. SPACING @ 25’ ANY DIRECTION)
REDWOOD EXPANSION BOARD
N.T.S.
PORTLAND CONC. (TYP.)
N.T.S.
VARIES
SIDEWALK WIDTH
SLOPE 14" PER. FT.
(MIN. 3500 P.S.I. @ 28 DAYS)
PORTLAND CONC. (TYP.)
TOOLED EDGE
FINISH GRADE
6:1 (MAX.)6:1 (MAX.)
TOOLED EDGE
10’-0" MAXIMUM 10’-0" MAXIMUM
N.T.S.
(MATCH EXISTING)
11 11 11
11 11 11 11
11 11 11
14" RADIUS
(MIN. 3500 P.S.I. @ 28 DAYS)
W/ 6x6 #6/6 WWF
W/ 6x6 #6/6 WWF
W/ 6x6 #6/6 WWF
1/2 " R.
SLOPE
(MATCH EXIST.)
6" 18"
1/2 " R. 1/2 " R.
2’-0"
1’-0"
CC
1’-0" 1’-0"
BAR DETAILS
N.T.S.
SEE BAR DETAIL
GUTTER LINE
PAVEMENT REPAIR DETAILS &
MISC. SITE DETAILS
#4 BARS
TREE PROTECTION FENCING DETAIL
INTERSECTING JOINTS
SHALL BE 90^ . (TYP.)
12" 12" 12" 12"
1/2 " 1 1/4 "
SMOOTH BAR
3/4 "
EXPANSION JOINT (EJ)
CONSTRUCTION JOINT (CJ)
N.T.S.
3/4 "
3/4 "
3/16 "
1/2 "
3/16 "
JOINT DETAIL "A" JOINT DETAIL "B"
T /4
/4
/4
R 1/
2 "
@ 24" O. C. (DEFORMED)
#6 BARS x 30" LONG
34" PREMOULDED FILLER
JOINT SEALANT W/
(SEE DETAIL "B")
TOOLED EDGE (1/2" R.)
12 OF PAVEMENT THICKNESS
N.T.S.
3/4" THICK REDWOOD EXPANSION JOINT.
APPROVED ASPHALTIC SEALANT.
PREMOLDED FILLER
1/2" R.
1/2" TO 3/4" MIN.
12 OF PAVEMENT
THICKNESS
3/4" MIN.
#6 SMOOTH BAR 1’-6"
LONG @ 18" O.C.
WITH BAR GREASED
PLASTIC TUBE
JOINT SEALANT JOINT SEALANT
34" RED WOOD
JOINT FILLER
SAWED JOINT
FOAM FILLER
MATERAL
N.T.S.N.T.S.
M A
T C
H
E X
IS
T
M A
T C
H
E X
IS
T
CONCRETE PAVEMENT JOINT DETAILS
Engineers Architects
Revisions: Date
Drawing Title
Location
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
224000
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
TUSCALOOSA, AL, 35404
3701 LOOP ROAD
TUSCALOOSA VA MEDICAL CENTER
Approved
Project Title VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
Date Checked Drawn
BCLC BCLC
CORRECT FAILING SANITARY
SEWER, WATER MAIN, AND
FIRE PROTECTION DEFICIENCIES
679-21-102
N/A
DEC. 29, 2023 27
U.S. Department of Veterans Affairs
LI
EN
DESCA
L A A M
A B
J A
M
E S
BR YAN
BU
T L
E R
E
NGINE
RE
PROFESSIONAL
C-306
V
CU. YDS.
0.25
0.25
0.5
0.25
0.75
SCHEDULE OF DIMENSIONS FOR MASS CONCRETE THRUST BLOCKS
D
D
1. No special pay item for reinforcement rods required in
2. Size of tee refers to branch size.
3. Place reinforcement rods as shown in all concrete thrust blocks and over valves.
18"MIN.
UNDISTURBED SOIL
C
VOLUME OF CONCRETE (V)
AS REQUIRED TO HOLD BEND
FLO
W
FLOW
C
B
UNDISTURBED
SOIL
FLOW
B
FLO
W
1/2 W
A
W
FLO
W
A
A
OR 1/2d + 12" MIN.
WHICHEVER IS GREATER
2" to 6" DIAMETER PIPES
(3"+1/2d) 8" to 12" DIAMETER PIPES
(6"+1/2d)
UNDISTURBED
SOIL
D overbends.
OR 1/2d + 12" MIN.
WHICHEVER IS GREATER
1/2d
1/2d OR 3"
WHICHEVER IS GREATER
UNDISTURBED SOIL
D
C
UNDISTURBED
SOIL
FLOW
SOIL
FT.-IN.
1’-0"
1’-0"
1’-0"
1’-0"
1’-0"
1’-0"
B
FT.-IN.
0’-9"
1’-0"
1’-4"
0’-10"
1’-8"
2’-0"
3"
6"
8"
4"
2"
10"
12"
2’-6"
3’-6"
4’-0"
5’-0"
1’-0"
2’-0"
TYPE OF
FITTING
SIZE
PIPE
DIMENSION
TYPICAL
90%%d
FT.-IN.
A
2’-0" 1’-0"
2’-6"
4’-0"
3’-0"
2’-0"
1’-4"
1’-8"
1’-0"
1’-0" 0’-9"
0’-10"
1’-0" 1’-0"
2’-0"
2’-0"
2’-0"
2’-0"
1’-4"
1’-8"
1’-0"
1’-0"
0’-9"
0’-10"
HORIZONTAL BENDS
FT.-IN.
45%%d
FT.-IN.
A B
22 1/2%%d
FT.-IN.
A
FT.-IN.
B
FT.-IN.
45%%d
FT.-IN.
VERTICAL UNDER BENDS
2’-6"
2’-0"
1’-6"
3’-0"
3’-6"
4’-0"
1’-0"
1’-4"
1’-8"
2’-0"
0’-9"
0’-10"
1’-3" 2’-0"
2’-6"
1’-10"
2’-2"
3’-6"
2’-6"
3’-0"
0’-9"
0’-11"
1’-0"
1’-6"
FT.-IN.
11 1/4%%d
B
FT.-IN.
A A
90%%d
FT.-IN.
B
FT.-IN.
A
1’-6"
2’-0"
2’-6"
2’-6"
1’-0"
1’-0"
1’-6"
2’-0"
2’-0"
2’-0"
1’-0"
1’-0"
B
FT.-IN.FT.-IN.
B A
11 1/4%%d
FT.-IN.
A B
VERTICAL OVER BENDS
SQ. FT.
1-#3
2-#4
4-#4
1-#4
5-#4
5-#57.25
3.25
6.25
4 8
0.5
0.5
(FOR 2000 P.S.F. SOIL)
REIN.
RODS
90%%d
SQ. FT.CU. YDS.
V BA
45%%d
V BA
1-#4
4-#4
2-#4
3-#4
1.5
1-#3
1-#4
0.25
0.25
0.5 1-#4
1-#4
1-#5
2-#44
1-#3
1-#4
22 1/2%%d
SQ. FT.RODS
REIN.
CU. YDS.
V REIN.
RODS
BA
NOTES:
1/2d
D B
W = DITCH WIDTH
d = INSIDE PIPE DIAMETER
LEGEND
1/2 W
W
F F
1/2d
W C
C
W
C
UNDISTURBED
SOIL
12" MIN.
FLOW
E
SOIL
UNDISTURBED
12" MIN.
E
W
12" MIN.
B
OR 1/2d + 12" MIN.
WHICHEVER IS GREATER
1/2d OR 3" MIN.
WHICHEVER IS GREATER
WHICHEVER IS GREATER
1/2d OR 3" MIN.
D B
1/2 W
12" X 10"
1-#4
1-#4
1-#4
1-#4
1-#3
1-#3
1’-0"2’-6"
4’-0"
3’-0"
3’-6"
2’-6"
1’-6"
2’-0"
1’-6"
1’-6"
1’-0"
1’-0"
11 1/4%%d
SQ. FT.
BA
RODS
REIN.
DEADENDS
FT.-IN.FT.-IN.
A B
TEES &
1’-0"
1’-4"
1’-8"
1’-8"
2’-0"
2’-0"
2’-0"
10" X 8"
12" X 6"
12" X 8"
10" X 6"
8" X 6"
6" X 4"
1’-0"
1’-0"
2’-0"
1’-6"
1’-0"
1’-0"
0’-6"
FT.-IN.
B
REDUCERS
FT.-IN.
C
1’-0" 0’-8" 0’-6" 0’-8" 0’-6" 0’-8" 0’-6" 0’-8" 0’-7" 0’-7" 0’-7" 0’-7"
0’-9"
0’-11"
1’-3"
1’-10"
2’-2"
2’-6"
0’-7" 0’-7"
0’-9"
0’-11"
1’-3"
1’-10"
2’-2"
2’-6"
0’-7" 0’-7"
0’-9"
0’-11"
1’-3"
1’-10"
2’-2"
2’-6"
1 2 1-#3 0.5 1 1-#3 0.25 1 1-#3 N/A N/A N/A 1’-6" 1’-0"
UNDISTURBED SOIL
UNDISTURBED SOIL
UNDISTURBED SOIL
UNDISTURBED
SOIL
for 100 P.S.I.
4. Volume of concrete for vertical overbends shall be sized
5. All ductile iron fittings shall be wrapped with an 8 mil.
Polyethylene film.
UNDISTURBED
SOIL
REDUCER
CU. YDS.
B
1/2d
1/2 W
12" MIN.
12" MIN.
A
1/2 d
A
W
1/2d
B
12" M
IN.
A
12" MIN.
D
12" MIN.
REINFORCING BAR RETURNED
BELOW PIPE WITH 180%%d HOOK.
SEE SCHEDULE
FOR SIZE & NUMBER.
UNDISTURBED
SOIL
NOTE:
ALL M.J. FITTING SHALL BE INSULATED USING R.J. RETAINER GLAND
(MEGALUG OR APPROVED EQUAL). ANY FITTING WHERE R.J. ADAPTERS
CAN NOT BE USED, CONCRETE THRUST BLOCKING SHALL BE USED
AS AN ALTERNATE FOR JOINT RESTRAINT DEVICES.
W = TRENCH WIDTH
1/2 W
WATER LINE THRUST
BLOCKING DETAILS
ELEVATION - VERTICAL OVER BEND
THRUST BLOCKING
ELEVATION - VERTICAL UNDER BEND
THRUST BLOCKING THRUST BLOCKING THRUST BLOCKING
DEAD END
PLAN - HORIZONTAL BEND
THRUST BLOCKING THRUST BLOCKING
TEE
SECTION A-A SECTION E-E
SECTION B-B
SECTION C-C
SECTION D-D
SECTION F-F
22 1/2%%d
Engineers Architects
Revisions: Date
Drawing Title
Location
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
/1
/2
:2 :5
A
M
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs # ' COPYRIGHT Apogee Consulting Group, P.A.
F il e P a th
224000
1009 Bayou Place
Alexandria, LA 71303
Surveyors
Tel. (318) 445-6571 Fax. (318) 448-0257
EngineersArchitects
Ballard Project Number
TUSCALOOSA, AL, 35404
3701 LOOP ROAD
TUSCALOOSA VA MEDICAL CENTER
Approved
Project Title VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
Date Checked Drawn
BCLC BCLC
CORRECT FAILING SANITARY
SEWER, WATER MAIN, AND
FIRE PROTECTION DEFICIENCIES
679-21-102
N/A
DEC. 29, 2023 27
U.S. Department of Veterans Affairs
LI
EN
DESCA
L A A M
A B
J A
M
E S
BR YAN
BU
T L
E R
E
NGINE
RE
PROFESSIONAL
S SS
NOTE: NOT ALL SYMBOLS MAY BE USED ON THIS PROJECT
SEMI-RECESSED SPRINKLER HEAD
UPRIGHT SPRINKLER HEAD
FIRE LINEFL
CONCEALED SPRINKLER HEAD
PENDANT SPRINKLER HEAD
SIDEWALL SPRINKLER HEAD
FIRE DEPARTMENT CONNECTION (FDC)
FIRE DRAINDRAIN
POINT OF NEW CONNECTION
LIMIT OF DEMOLITION
NEW WORK KEYNOTE
DEMOLITION KEYNOTE
FIRE PROTECTION CONTRACTORFPC
TAMPER SWITCH
FLOW SWITCH
CHECK VALVE
GATE VALVE
EXTERIOR ALARM GONG (WATER ACTIVATED)
TEST AND DRAIN ASSEMBLY
BACKFLOW PREVENTER
T&D
TS
FS
ORDINARY HAZARD
GROUP 1 OCCUPANCY
DETAIL OR SECTION MARK
SHOWN ON DRAWING
DETAIL MODULE NUMBER
ORDINARY HAZARD
GROUP 2 OCCUPANCY
LIGHT HAZARD
FIRE SUPPRESSION SYMBOLS & ABBREVIATIONS
THE FIRE PROTECTION DRAWING IS DESIGNED TO BE IN CONFORMANCE WITH NFPA 13.
IT IS A PERFORMANCE BASED DRAWING INDICATING THE EXTENT OF FIRE PROTECTION
WORK FOR THE AREA THAT THIS DRAWING REPRESENTS. THIS DRAWING IS “FOR
INFORMATION ONLY”, AS A REFERENCE FOR THE FIRE PROTECTION CONTRACTOR TO
BASE THE DESIGN OF THE FIRE PROTECTION SYSTEM ON. THE CONTRACTOR SHALL
VERIFY THE EXACT CONDITIONS THAT THIS DRAWING REPRESENTS, INCLUDING ANY
PERCEIVED CONCEALED SPACES, AND THE BUILDING TYPE AND CONSTRUCTION,
PRIOR TO THE START OF WORK. REFER TO NFPA 13, AND THE PROJECT
SPECIFICATIONS FOR OTHER FIRE PROTECTION REQUIREMENTS.
1. LOCATIONS SHOWN FOR EXISTING FIRE PROTECTION PIPE AND EQUIPMENT ARE APPROXIMATE. FIELD VERIFY THE EXACT LOCATIONS OF EXISTING FIRE PROTECTION LINES AND EQUIPMENT INCLUDING RISERS AND VALVES PRIOR TO START OF
WORK.
2. COORDINATE WITH COR FOR ANY SHUTDOWNS OR PLANNED INTERRUPTIONS OF THE FIRE PROTECTION SERVICE. GIVE THE
COR THREE (3) DAYS NOTICE PRIOR TO PLANNED SHUTDOWN OR INTERRUPTION.
3. COORDINATE DEMOLITION OF FIRE PROTECTION PIPING WITH OTHER PIPING WHICH IS NOT TO BE REMOVED. PROTECT
OTHER PIPING WHICH IS NOT TO BE REMOVED FROM DAMAGE, DIRT, AND DEBRIS.
4. FIRE PROTECTION RELATED EQUIPMENT AND PIPING WHICH IS REMOVED FROM THE BUILDING IS TO BE TAKEN OFFSITE AND
DISPOSED OF.
FIRE SUPPRESSION DEMOLITION GENERAL NOTES
1. USE NFPA-13 (CURRENT EDITION), “PLANS AND CALCULATIONS” CHAPTER AS A GUIDELINE WHEN PREPARING SUBMITTALS FOR REVIEW. DISREGARD ONLY THOSE ITEMS NOT APPLICABLE TO THE INDIVIDUAL BUILDING SYSTEM. FIRE PROTECTION MATERIALS, EQUIPMENT AND INSTALLATION SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA-13 FOR THE
INSTALLATION OF AUTOMATIC SPRINKLER SYSTEM.
2. INSTALLATION SHALL COMPLY WITH NFPA AND VA REQUIREMENTS. SYSTEM SHALL ALSO BE IN COMPLIANCE WITH ALL
REQUIRED PLUMBING CODES.
3. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS AND ROOM FINISH SCHEDULE WHICH INDICATE CEILING HEIGHTS.
COORDINATE WITH ARCHITECT'S REFLECTED CEILING PLAN FOR LOCATION OF SPRINKLER HEADS IN AREAS WITH CEILINGS.
LOCATE HEADS IN AREAS WITHOUT CEILINGS AS REQUIRED BY NFPA AND VA REQUIREMENTS FOR THE APPROPRIATE
HAZARD CLASSIFICATION.
4. THIS FACILITY IS FULLY SPRINKLERED. FIRE SUPPRESSION SYSTEM SHALL BE WET PIPE TYPE SYSTEM WITH COMPLETE SPRINKLER PROTECTION UNLESS NOTED OTHERWISE. SYSTEM TO BE DESIGNED AS REQUIRED BY NFPA AND VA
REQUIREMENTS FOR THE APPROPRIATE HAZARD CLASSIFICATION.
5. PIPING IS SHOWN IN SCHEMATIC FORM TO INDICATE APPROXIMATE ARRANGEMENT OF EQUIPMENT AND PIPING. SPRINKLER CONTRACTOR SHALL DESIGN THE SYSTEM AND ROUTE PIPING AS REQUIRED FOR CONFORMANCE WITH ACTUAL BUILDING CONDITIONS AND NFPA REQUIREMENTS. COORDINATE SPRINKLER WORK WITH ALL OTHER TRADES TO AVOID CONFLICT.
6. SUPPORT NEW PIPING AND EQUIPMENT FROM STRUCTURE. PROVIDE ALL SUPPLEMENTAL STEEL TO SPAN BETWEEN PRIMARY BUILDING STRUCTURAL MEMBERS. DESIGN SUPPLEMENTAL STEEL AND SUPPORTS INCLUDING REACTION LOADS
AT PRIMARY BUILDING STRUCTURAL MEMBERS.
7. CLEAN ENTIRE WORK AREA OF ALL DUST, DIRT, AND OTHER DEBRIS. MAINTAIN WORK AREA IN CLEAN CONDITION.
8. PROVIDE ALL LABOR, MATERIALS, TOOLS, EQUIPMENT, ETC. REQUIRED FOR COMPLETE AND FUNCTIONAL SYSTEM AS
SPECIFIED AND INDICATED ON THE DRAWINGS.
9. REPAIR OR REPLACE NON-CONFORMING AND INADEQUATE WORK AT NO ADDITIONAL COST TO THE VA.
10. PROVIDE FIRE STOPS / SEALANT AT ALL PIPE PENETRATIONS THROUGHOUT FIRE RATED WALLS. REVIEW ARCHITECTURAL
PLANS PRIOR TO BIDDING AND INDICATE PENETRATIONS ON SPRINKLER LAYOUT SUBMITTAL.
11. FLOW AND TAMPER SWITCHES ARE TO BE PURCHASED AND INSTALLED AS WORK OF DIVISION 21. PROVIDE WIRING TO FLOW
AND TAMPER SWITCHES AS WORK OF DIVISION 26.
12. WATER SERVICE AND DETECTOR TYPE REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER TO BE PROVIDED AND TESTED AS WORK OF DIVISION 22. INCORPORATE ASSOCIATED PRESSURE DROP OF SELECTED BACKFLOW PREVENTER
DEVICE IN HYDRAULIC CALCULATIONS.
FIRE SUPPRESSION GENERAL NOTES
1. DURING THE TIME THAT THE FIRE PROTECTION RENOVATION WORK IS BEING PERFORMED, AND THE FIRE PROTECTION SYSTEM IS OUT OF COMMISSION, CONTRACTOR SHALL HAVE SUFFICIENT PERSONNEL ONSITE TO KEEP A “FIRE WATCH” ON THE FACILITY IN ACCORDANCE WITH VA REQUIREMENTS. AN OUT OF SERVICE TAG MUST BE PLACED AT THE FIRE ALARM PANEL AND THE FIRE DEPARTMENT CONNECTION. REFER TO INTERNATIONAL FIRE CODE CHAPTER 9, SECTION 901.7.
2. FIRE WATCH…