Attachment_8_-_WRST_Trip_Report.pdf
PDF 2 MB Posted
- Attached to
- EO14398 ELECTRIC REPAIRS AT SIX ALASKAN N. PARKS
- Solicitation number
- 140P9726Q0046
About this file
Summary
This is a Trip Report documenting an arc flash evaluation conducted by RSA Engineering at Wrangell-St. Elias National Park & Preserve (WRST) for the U.S. Department of the Interior National Park Service Denver Service Center. The report covers site investigations conducted June 17-21, 2024, at multiple facilities including Copper Center, Glenallen, Slana, McCarthy, and Kennecott.
The evaluation assessed electrical distribution systems to provide arc flash calculations, install warning labels, and identify code deficiencies per the National Electrical Code (NEC). Arc flash analyses were performed for all three-phase equipment at Copper Center, Glenallen Main Shop, and Kennecott. Overall, electrical systems were found in good to fair condition with minimal deficiencies. Key findings include: missing dead front covers on panels, abandoned and improperly terminated conductors, incomplete panel schedules, neutral-ground bonding issues, undersized feeder conductors, unsupported conduit, missing junction box covers, inadequate working space clearances, missing AFCI/GFCI protection, and equipment lacking proper identification labels. Specific code violations were documented at numerous locations requiring remediation such as NEC 110.27 (dead front covers), NEC 250.24(A)(5) (neutral-ground bonding), NEC 240.21 (tapped conductor protection), NEC 408.4 (panel schedules), NEC 110.26 (working clearances), and NEC 210.12 (arc fault protection). The report includes one-line facility diagrams, fault contribution analysis reports, and arc flash evaluation tables with incident energy calculations and required PPE recommendations for each electrical location.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
670 W. Fireweed Ln, Ste 200 Anchorage, AK (907) 276-0521 l www.rsa-ak.com
Mechanical & Electrical Engineers
August 31, 2024
United States Department of the Interior National Park Service Denver Service Center 12795 W. Alameda Parkway P.O. Box 25287 Denver, CO 80225-0287
ATTENTION: Susan Lehmann
Dear Susan, REFERENCE: NPS Arc Flash Evaluation - WRST Trip Report
On 06/17/24 through 06/21/24 Davin Blubaugh and Aidan Blessing with RSA Engineering travelled to Wrangell-St. Elias National Park & Preserve (WRST) to investigate the electrical distribution systems. The intent of the site visits was to gather enough information on the equipment to provide an accurate arc flash calculation, provide warning labels for the equipment, and observe/record any obvious code deficiencies.
One-line diagrams have been generated for each facility based upon our site investigation. These one-line diagrams show the details of the power distribution system at each site/building, and those details are not replicated within the below report.
Arc-flash calculations were performed for all 3-phase distribution systems/equipment. The equipment operating at 120/240V, single-phase or less, was not included within the arc-flash calculations and were provided with generic arc-flash warning labels only.
In general, the electrical distribution system at all sites was in good to fair condition. Common items such as working space violations, equipment labeling, and missing junction box covers were noted throughout, but overall, the deficiencies observed were minimal. A Flir thermal imaging camera was used on all equipment to look for hot spots occurring from loose connections or damaged breakers, and no such hot spots were observed on any equipment. The following report addresses the code deficiencies and recommendations observed during our site investigation.
Copper Center:
The electrical distribution system for Copper Center begins at the Garage Building in the center of the complex roughly halfway between the Headquarters Building (Admin) and the Visitor Center.
The electrical service is fed with 480V, 3-phase underground from a Copper Valley Electric Association (CVEA) pad-mounted utility transformer to a wall-mounted tap box on the exterior of the Garage building which feeds the site fire pump and an exterior mounted Main Distribution Panel ‘MDP1’. ‘MDP1’ feeds all buildings on the site and steps down at various transformers: one located in the mezzanine of the Garage, one on the exterior of the Visitor Center, one under the Marc Building, and one outside of the Headquarters (Admin) Building.
The Visitor Center Main Distribution Panel ‘MDP2’ is located on the exterior and feeds the Visitor Center, The Exhibit Building, the Comfort Station (Restroom), and the Theater. The distribution panel on the exterior of the Marc Building (labeled ‘MBDL’ on the one-line) is a 120/240V, single-phase distribution panel which feeds the Marc Building and the Resource Building.
Reference the facility one-line diagram for electrical distribution system details.
August 30, 2024
An arc-flash analysis has been performed for the three-phase equipment within the electrical distribution system at Copper Center. The results of this analysis are included within the attachments at the end of this report.
Code Deficiencies
1. Garage Building:
a. Panel ‘GA’ is partially missing dead front cover over main lugs. Provide new dead front cover to fully enclose main lugs to protect against accidental electrical contact per NEC 110.27.
b. Neutral wire appears to be abandoned and not properly capped in garage building (Image #1). Either demolish neutral wire back to source, or properly enclose abandoned wire with junction box as required by NEC 300.15.
c. Panel ‘MDP1’ schedule is missing a label for the Marc Building feeder. Provide updated circuit directories for panelboard per NEC 408.4.
d. The neutral and ground were not bonded at Disconnect ‘DGA’ and we could not verify if the neutral was bonded within the upstream transformer. Confirm neutral and ground bond at secondary side of XFMR ‘TGA’ (located on mezzanine) and if it does not exist, provide one as required by NEC 250.24(A)(5).
2. Visitor Center:
a. Panel ‘VCO’ is partially missing dead front cover over main lugs (Image #2).
Provide new dead front cover to fully enclose main lugs to protect against accidental electrical contact per NEC 110.27.
3. Exhibit Building:
a. Junction box in crawlspace is missing a cover. Tuck in conductors and provide new junction box cover as required per NEC section 314.25.
4. Admin Building:
a. Panel ‘HQ0’ has a piece of wire being utilized as a handle-tie to connect circuit breakers #38 and #40 together for a multi-wire branch circuit (Image #3). Remove the wire and provide a listed 2-pole handle-tie device.
5. Generator Shed:
a. Panel ‘HQE1’ does not have panel schedule. Trace out circuit in panel and provide clear, evident, and distinguishable typed circuit directories for panelboard per NEC 408.4.
6. Resource Building:
a. Panel ‘RL2’ schedule is missing information on circuit breakers 7-10. Provide clear, evident, and distinguishable circuit directory for panelboard per NEC 408.4.
Electrical Recommendations
1. All Buildings - Recommend providing unique equipment id’s and clearly labeling all electrical equipment with phenolic labels denoting equipment name, amperage, voltage, and source.
2. Garage Building:
a. Panel ‘GAE’ has an abandoned conductor within the panel. Recommend demolishing abandoned conductors and associated conduit and junction boxes completely.
b. Panels ‘GA’ and ‘GAE’ have neutrals that are shared between circuits. Note that this may have not been a code requirement when the equipment was installed and therefore could be “grandfathered” but does not meet the current NEC minimum requirements. Recommend that all circuits with shared neutrals are handle-tied together.
c. No emergency lighting was observed at garage building. Recommend providing emergency lighting near ‘MDP1’ and the electrical equipment within the building to allow for troubleshooting during power outages.
3. Visitor Center:
a. Panel ‘VCO’ has neutrals that are shared between circuits. Note that this may have not been a code requirement when the equipment was installed and therefore could be “grandfathered” but does not meet the current NEC minimum requirements.
Recommend that all circuits with shared neutrals are handle-tied together.
Copper Center Cultural Center:
The Cultural Center building at Copper Center is fed underground from a separate 120/240V, single-phase CVEA pad-mounted transformer located near the main Copper Center site 3-phase transformer. The building power distribution system is limited to the service equipment and a single panel which feeds all loads for the building.
Code Deficiencies
1. Emergency lights are non-functional. Recommend repairing or replacing non-functioning emergency lights to ensure path of egress is illuminated under loss of power.
2. FACP breaker in panel was lockable, but not code required red colored. Recommend providing a new red “FIRE” lockable handle, or at a minimum paint the handle lock red.
1. No further electrical recommendations for this area.
Copper Center Box Cabins:
The Box Cabin area at Copper Center is fed underground from a 120/240V, single-phase pole-mounted CVEA utility transformer. The site electrical system is limited to the service equipment, a panel in the “Main House”, a Cabin distribution panel, Cabin disconnects, and individual enclosed circuit breakers feeding each Cabin (reference the one-line for system details).
1. Conductors from Combination Meterbase/Disconnect (CMD) to panel ‘Cabin Distribution’ are undersized for the existing 200A upstream overcurrent protection device. Recommend intercepting the circuit at the CMD and adding a 100A breaker within 10-feet of the CMD
(per NEC 240.21) or (worst case) replace the #2 AWG conductors with #3/0 AWG copper conductors that are properly sized for 200A 2-Pole breaker per NEC 310.16.
2. CMD does not have a panel schedule. Provide clear, evident, and distinguishable circuit directory for panelboard per NEC 408.4.
3. PVC Conduits is unsupported on all box cabins typical (Image #4), and is not properly seated in the Cabin Distribution Panel. Properly secure/support and fasten PVC in accordance with NEC 352.30.
Electrical Recommendations
1. Panel ‘Main House’ and Panels ‘Cabin 1’ through ‘Cabin 8’ do not have Arc Fault
Interrupting Circuits (AFCI) protected breakers. Recommend providing new AFCI breakers for all panels and providing dual AFCI/GFCI breakers for circuits that currently have GFCI breakers per NEC 210.12. This was likely not a code requirement at the time of installation, but has since been added to the NEC.
2. Recommend providing unique equipment id’s and clearly labeling all electrical equipment with phenolic labels denoting equipment name, amperage, voltage, and source.
Gulkana Hangar:
The Gulkana Hangar is a single-phase service fed underground from a nearby pole-mounted CVEA utility transformer. The building electrical system is limited to the service equipment, two panels, an exterior generator and associated generator transfer switch/panel combination device which feeds standby power to minimal equipment in the building. Reference the one-line for system details.
1. There is conduit separation at the CMD exposing conductors (Image #5). Correct conduit installation to conceal/protect conductors.
2. The #8 AWG copper conductors feeding the ATS/Panel combination device in the Hangar are tapped off of the line side of the main lugs of the Hangar Panel. There is no overcurrent device at the point of termination in the ATS/Panel which is a violation of NEC 240.21 for tapped conductors. Recommend adding a 30A, 2-pole breaker within the Hangar Panel to feed the ATS/Panel. Note, this will require rearranging breakers/circuits within the panel to allow for a new 2-pole breaker.
3. Panel ‘SAR’ in the southwest corner of the building does not have a panel schedule. Provide clear, evident, and distinguishable circuit directory for panelboard per NEC 408.4.
Electrical Recommendations
4. Recommend providing unique equipment id’s and clearly labeling all electrical equipment
Glenallen Main Shop:
The Main Shop building in Glenallen is fed with a 120/208V, 3-phase service overhead from a bank of three (3) 10kVA pole-mounted CVEA utility transformers. The service equipment and MDP is located on the outside of the Shop building and feeds the Mechanical Shop panels, Carpenter Shop Panels, Shed Building, and Storage Garage. Reference the one-line for system details.
An arc-flash analysis has been performed for the three-phase equipment within the electrical distribution system at the Glenallen Main Shop. The results of this analysis are included within the attachments at the end of this report.
1. The CMD and MDP mounted on the exterior of the shop are installed too high off of the ground for adequate access per NEC 240.24 and the enclosure below the CMD violates the required working clearances per NEC 110.26 (Image #6). A platform could be built to access the equipment, but the enclosure below the CMD would need to be relocated.
Alternatively, the CMD and MDP could be lowered and shifted over, however, that would require additional work relocating conduit and wire.
2. The MDP is missing blank space fillers exposing the interior of the panel. Provide additional blank space filler plates.
3. The Carpenter shop main panel (labeled as ‘CSL1’ on the one-line) is missing blank space fillers exposing the interior of the panel. Provide additional blank space filler plates.
4. The Shed Panel (labeled as ‘SBL1’ on the one-line) is inaccessible due to the amount of stored materials in front (Image #7). Remove stored items to allow for adequate NEC
110.26 working space.
5. The Storage Garage panel (labeled as ‘SGL1’ on the one-line) is missing blank space fillers exposing the interior of the panel. Provide additional blank space filler plates
1. The Mechanical Shop main panel (labeled as ‘MSL1’ on the one-line diagram) and several breakers within the panel are manufactured by Zinsco. All of Zinsco’s electrical equipment was recalled years ago due to fire hazards and failures. Recommend replacing this panel and all breakers with a new panel.
Glenallen Pumphouse:
The Pumphouse building in Glenallen is fed with a 120/240V, 1-phase service underground from a 10kVA pad-mounted CVEA utility transformer. The service equipment is a CMD on the exterior of the building which feeds the Pumphouse interior panel and also feeds the adjacent Trail Maintenance Building. Reference the one-line for system details.
1. No code deficiencies were noted for the Pumphouse or Trail Maintenance Buildings.
Electrical Recommendations
1. Recommend providing unique equipment id’s and clearly labeling all electrical equipment
Glenallen Housing:
The Glenallen Housing area is comprised of two main multi-family dwelling buildings, Building A (4-housing unit and a shared Boiler Room) and Building B (2-housing unit and a shared Boiler Room).
Each building is fed underground from the same pad-mounted CVEA utility transformer located on the west end of the site. Each building has a multi-meter pack for service equipment to individually meter each unit and respective Boiler Room. Reference the one-line for system details.
1. Panel ‘DA’ within the Garage of Unit A2 has a NEC 110.26 working space violation with the
HRV ductwork (Image #8). Recommend relocating the ductwork out of the panel working space.
1. No further recommendations for the Glenallen Housing area.
Slana Visitor Center:
The Slana Visitor Center is fed overhead from a 120/240V, single-phase, pole-mounted CVEA utility transformer to a CMD mounted to the exterior of the Garage Building. The CMD feeds to the Garage Panel which feeds out to the Sleeping Cabins, Bunkhouse and Visitor Center Buildings. The CMD also has a separate feeder to the Fish Weir Office. Reference the one-line for system details.
1. The Garage Building panel has missing knockouts exposing the interior of the panel to dirt/dust/debris. Provide knockout fillers to seal panel.
2. The #12 AWG copper feeder conductors from the Garage Building Panel to Sleeping Cabin
#1 and #2 are undersized for the 30A breaker in the Panel. Recommend replacing the 30A, 2-pole breaker with a new 20A, 2-pole breaker.
3. The feeders from the Garage Panel to the exterior mounted Bunkhouse ECB and from the
Bunkhouse ECB to the exterior mounted Visitor Center ECB do not contain an Equipment
Grounding Conductor (EGC) and at least a portion of the conduits are non-metallic PVC, meaning that the conduit cannot serve as a ground path for the feeders. Provide an EGC within the feeder conduit per NEC 250.122 requirements.
4. There are several locations onsite where the neutral wire and ground wire are bonded within enclosures. The neutral and ground should only be bonded in one location at the service
CMD. Remove all neutral to ground bonds downstream of the service equipment. This was noted at the Enclosed Circuit Breaker (ECB) on the exterior of the bunkhouse, the ECB on the exterior of the Visitor Center, Sleeping Cabin #1 panel, and the Sleeping Cabin #2 panel, although a thorough investigation of all equipment should take place to ensure all grounds and neutrals are properly isolated.
5. The Bunkhouse Panel has a NEC 110.26 working space clearance violation with the water heater installed in front of the Panel. Recommend relocating the water heater to provide adequate NEC clearances (Image 9).
6. The disconnect on the exterior of the Fish Weir Office is not properly grounded, the EGC needs to be identified with green tape (currently white conductor), and the conduit feeding the equipment is separated from the enclosure (Image #10). Recommend connecting the incoming EGC to the enclosure, provide green tape on EGC, and correct the conduit installation.
Electrical Recommendations
1. Recommend demolishing the Old Generator Breaker and associated feeder between the breaker and the Manual Transfer Switch (MTS) as the generator is no longer present and the equipment is not needed.
Slana Ranger Residence:
The Slana Ranger Residence is fed overhead from a 120/240V, single-phase, pole-mounted CVEA utility transformer to a CMD mounted to the exterior of the Garage Building. The CMD feeds to the Garage Panel which feeds out to the Residence. Reference the one-line for system details.
1. The Garage Panel has duct tape covering several open spaces in the panel (Image #11).
Provide approved blank spaces fillers in-lieu of duct tape.
2. The Garage Panel schedule does not appear to be accurate as there is an unlabeled circuit breaker in spaces 21 & 23. Provide clear, evident, and distinguishable circuit directory for panelboard per NEC 408.4.
3. The feeders from the Garage Panel to the exterior mounted Residence Panelboard do not contain an Equipment Grounding Conductor (EGC) and at least a portion of the conduit is non-metallic PVC, meaning that the conduit cannot serve as a ground path for the feeders.
Provide an EGC within the feeder conduit per NEC 250.122 requirements.
4. The Panel inside of the Ranger Residence (Labeled Panel ‘B’ on the one-line) has numerous flexible conduits that require adequate supporting per NEC 348.30 (Image #12).
Electrical Recommendations
Slana Freed Property:
The Slana Freed Property is fed overhead from a 120/240V, single-phase, pole-mounted CVEA utility transformer to a CMD mounted to the exterior of the main House. The CMD feeds to the interior House Panel which feeds the Cabins on site. The CMD also feeds an abandoned Waste Water Treatment Building behind the House. Reference the one-line for system details.
1. The House Panel is located in the kitchen and does not have adequate working clearances per NEC 110.26. The only way to provide adequate clearances would be to remove some of the counter and cabinets or relocate the panel (Image #13).
Electrical Recommendations
1. Recommend removing the feeder and electrical equipment associated with the abandoned
Waste Water Treatment Building.
McCarthy West Side Complex:
The McCarthy West Side Complex consists of an Electrical Building, Support Building, Communication Cabin, and Well House. The site is powered via a propane generator and solar/battery system housed within the Electrical Building and all loads are distributed out from there to the other buildings at 120/240V, single-phase. Reference the one-line for system details.
1. Support Building Panel is missing blank space filler. Provide blank space filler for panel.
Electrical Recommendations
McCarthy Airport:
The McCarthy Airport building consists primarily of an Electrical/Boiler Room and a Ranger Station Office area. The site is powered via a propane cogeneration unit and a solar/battery system housed within the Electrical/Boiler Room. All building loads are powered from a panel in the Electrical/Boiler Room and another smaller panel in the Ranger Station office at 120/240V, single-phase. Reference the one-line for system details.
1. No code deficiencies noted for the McCarthy Airport.
1. The wiring interface between the cogeneration unit and the solar/battery system was not very well documented. Recommend displaying a single schematic diagram within the building showing the major system components (cogen unit, solar panels, batteries, inverters, panels, etc) for ease of maintenance and troubleshooting.
Kennecott:
The power distribution system for the main historic site at Kennecott begins at the Electrical connexes (labeled as Power Plant or ‘NP’ on the one-line) located on the south end of the site. The Power Plant was recently upgraded back in 2021/2022 with four (4) new solar arrays, charge controllers, 74kWh battery bank, inverters, power distribution panels, and a new 25kW diesel generator. The project was designed by Design Alaska with Construction Drawings dated 3/11/2021 and the equipment was supplied and installed by RMC engineering out of Juneau, AK. This new Power Plant provides power to all of the NPS buildings at Kennecott, with the exception of Silk Stocking Row and the National Creek Water Treatment Shed, which both have their own onsite microgrids (reference next sections).
The AC side of the site distribution begins at Panel ‘A’ within the new power plant and steps up the site voltage to 480V, 3-phase for distribution. From the new Power Plant the site distribution routes underground to the north to hit various distribution panels and step-down transformers throughout the site. The one-line diagram provided documents the entire electrical distribution system and references the buildings each piece of equipment is located within. Reference the one-line for system details.
An arc-flash analysis has been performed for the three-phase equipment within the electrical distribution system at Kennecott. The results of this analysis are included within the attachments at the end of this report.
1. The Wash House Panel (labeled as Panel ‘WHL1’ on the one-line) does not have adequate
NEC 110.26 working clearances due to the stacked washer/dryer in front of the Panel
(Image #14).
2. The 120/208V Distribution Panel in the Transformer (Old Gen Shed) Building (labeled as
Panel ‘TBDL’ on the one-line diagram and labeled ‘MDP1’ in the field) is downstream of a step-down transformer and requires a Main Circuit Breaker (MCB) per NEC 408.36 (Image
#15). Recommend providing an additional 225A, 3-pole breaker in an available space within the panel and moving the line side terminations from the main lugs to the new circuit breaker.
3. The Panel in the General Manager’s Office is located in a closet under the stairs and does not have adequate NEC 110.26 working space headroom (Image #16).
Electrical Recommendations
1. Recommend placing a system one-line diagram at major electrical distribution panel locations and denoting a “You are here” location identifier to assist with maintenance and troubleshooting of the electrical system. Suggested locations would be the New Power
Plant, Rec Center electrical shed, Transformer Building (Old Gen Shed), Leaching Plant, and the Old Power Plant.
Kennecott Silk Stocking Row:
Silk Stocking Row consists of a Garage Building that houses the main electrical equipment, an adjacent Generator Shed, the North House and the South House. The site is powered via a small diesel generator and a battery/inverter system. The battery inverter system is within the Garage Building and feeds a Garage Panel that feeds the Garage loads as well as panels in the North and South Houses at 120/240V, single-phase. Reference the one-line for system details.
1. The North House Panel is installed within a cabinet thus violating adequate NEC 110.26 working space requirements (Image #17). Suggest removing the cabinet to allow for proper clearances.
Electrical Recommendations
Kennecott National Creek Water Treatment Shed:
The Water Treatment Shed has a small solar/battery system that feeds a sine-wave inverter and a single 20A, 120V circuit breaker for the shed loads. Reference the one-line for system details.
1. The Water Treatment Shed Panel does not have a panel schedule, though the single receptacle it feeds is fairly apparent (Image #18). Provide clear, evident, and distinguishable circuit directory for panelboard per NEC 408.4.
2. Given the nature of the small shed, there is not sufficient NEC 110.26 working clearance for the Panel.
1. No further recommendations for the Water Treatment Shed.
(REFERENCED IMAGES LOCATED ON THE FOLLOWING PAGES)
Image #1 – Garage Building abandoned conductor
Image #2 – Visitor Center Panel ‘VC0’ missing main lug cover
Image #3 – Admin Building Panel ‘HQ0’ unlisted handle-tie
Image #4 – Box Cabin PVC conduit needing supports
Image #5 – Gulkana Hangar conduit separation
Image #6 – Glenallen Shop CMD and MDP NEC 110.26 & 240.24 violation
Image #7 – Shed Building panel NEC
110.26 clearance issues
Image #8 – Glenallen Housing Unit A2 Panel ‘DA’ NEC 110.26 violation
Image #9 – Bunkhouse Panel NEC 110.26 working space violation
Image #10 – Slana VC Fish Weir Office Disconnect issues (reference report)
Image #11 – Slana Ranger Residence Garage Panel duct tape
Image #12 – Slana Ranger Residence Interior Panel flex conduit
Image #13 – Slana Freed House Panel NEC 110.26 violation
Image #14 – Kennecott Wash House Panel NEC 110.26 working space violation
Image #15 – Kennecott Transformer Bldg Distribution Panel needing MCB
Image #16 – Kennecott GMO Panel NEC
110.26 working space violation
Image #17 – Kennecott Silk Stocking North House NEC 110.26 violation
Image #18 – Kennecott National Creek Shed Panel missing schedule and NEC
110.26 violation
If you have any questions concerning the above, please do not hesitate to call.
Sincerely, Davin Blubaugh Senior Electrical Engineer db/ab 24-0347/M3144 Attachments
UTIL-0001
S
P
XFMR-UTILITY
CBL-0001
BUS-TAP BOX
InitSymRMS 3P 5493.31 A InitSymRMS SLG 5163.53 A
CBL-0002 CBL-0003
DISC-SERVICE
InitSymRMS 3P 5334.86 A InitSymRMS SLG 4940.83 A
PD-SERV DISC
DISC-DFP
InitSymRMS 3P 5416.95 A InitSymRMS SLG 5041.81 A
PD-FP
CBL-0004 CBL-0005
MC-FP
MTR-FP
CBL-0006
PANEL-MDP1
InitSymRMS 3P 5319.53 A InitSymRMS SLG 4919.60 APD-FEDR-GA
CBL-0007
DISC-DGA
InitSymRMS 3P 2972.17 A InitSymRMS SLG 3054.89 A
PD-GA
CBL-0008
CBL-0009
PANEL-GA
InitSymRMS 3P 2942.32 A InitSymRMS SLG 3002.07 A
PD-FEDR-WTCP
PANEL-WTCP
InitSymRMS 3P 2677.54 A InitSymRMS SLG 2559.13 A
CBL-0010
PD-FEDR-VC
CBL-0011
CBL-0012
PANEL-MDP2
InitSymRMS 3P 3652.67 A InitSymRMS SLG 3971.01 A
PD-FEDR-VC1
PANEL-VC1
InitSymRMS 3P 3240.59 A InitSymRMS SLG 3208.77 A
CBL-0014
PD-MDP2
PD-FEDR-VC0
PANEL-VC0
InitSymRMS 3P 3237.42 A InitSymRMS SLG 3211.03 A
CBL-0015
PD-FEDR-VCEL
CBL-0016
DISC-DVCEL
InitSymRMS 3P 2695.67 A InitSymRMS SLG 2301.28 A
PD-GA0
S
P
XFMR-TGA
S
P
XFMR-TVC
CBL-0017
MTR-VCEL
PD-FEDR-HQ
CBL-0013
DISC-DHQ
InitSymRMS 3P 3652.31 A InitSymRMS SLG 3971.70 A
PD-GA1
CBL-0018
CBL-0019
PANEL-HQ
InitSymRMS 3P 3407.69 A InitSymRMS SLG 3505.82 APD-FEDR-HQ0
PANEL-HQ0
InitSymRMS 3P 3259.48 A InitSymRMS SLG 3246.67 A
CBL-0020
S
P
XFMR-THQ
PD-FEDR-HQB
PANEL-HQB
InitSymRMS 3P 3325.43 A InitSymRMS SLG 3366.37 A
CBL-0021
PD-FEDR-HQ1
PANEL-HQ1
InitSymRMS 3P 2988.30 A InitSymRMS SLG 2803.82 A
CBL-0022
PD-FEDR-HQ2
PANEL-HQ2
InitSymRMS 3P 2864.96 A InitSymRMS SLG 2616.83 A
CBL-0023
PD-FEDR-HQEL
CBL-0024
DISC-DHQEL
InitSymRMS 3P 3148.38 A InitSymRMS SLG 3033.13 A
PD-GA2
CBL-0025
MTR-HQEL
WRST - ARC FLASH ANALYSIS - COPPER CENTER
FACILITY ONE-LINE DIAGRAM
AUGUST 31, 2024
DAPPER Fault Analysis Input Report (English)
Project: Copper Center
Base Project
Utilities
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
-------- Contribution Data -------- PU (100 MVA Base)
X PUR PUX/RUnitsDuty
UTIL-0001 BUS-0001 12,470 MVA 9,999.00In 1,000,000
SLG:
3P:
MVA 9,999.00
Pos:
Zero:333,333
0.0001
0.00010.0000
0.0000
Motors
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
--------- Contribution Data --------
Base kVA Xd" X/R
PU (100 MVA Base)
R PU X PU
# of
Motors
MTR-FP BUS-0007 480 40.11 0.1507 4.90 76.717 375.834In1
MTR-HQEL BUS-0027 208 15.04 0.1507 4.90 204.577 1,002.225In1
MTR-VCEL BUS-0026 208 15.04 0.1507 4.90 204.577 1,002.225In1
Cables
Cable
Name
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
Cable
Name
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-0002
BUS-TAP BOX
1 50 500 PVC Pos:
Zero:
0.6380 1.0113
2.4891
CBL-0001 In
2.0095
MagneticCopper
BUS-TAP BOX
DISC-SERVICE
1 30 500 PVC Pos:
Zero:
0.3828 0.6068
1.4935
CBL-0002 In
1.2057
MagneticCopper
BUS-TAP BOX
DISC-DFP
1 3 6 PVC Pos:
Zero:
0.6641 0.0892
0.2197
CBL-0003 In
2.0927
MagneticCopper
DISC-SERVICE
PANEL-MDP1
1 3 500 PVC Pos:
Zero:
0.0383 0.0607
0.1493
CBL-0004 In
0.1206
MagneticCopper
DISC-DFP
BUS-0006
1 40 6 PVC Pos:
Zero:
8.8542 1.1892
2.9288
CBL-0005 In
27.9028
MagneticCopper
BUS-0008
BUS-0007
1 10 6 PVC Pos:
Zero:
2.2135 0.2973
0.7322
CBL-0006 In
6.9757
MagneticCopper
PANEL-MDP1
BUS-0022
1 60 2 PVC Pos:
Zero:
5.2604 1.5234
3.7500
CBL-0007 In
16.5781
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-0023
DISC-DGA
1 25 1/0 PVC Pos:
Zero:
7.3965 3.1204
7.6796
CBL-0008 In
23.3104
MagneticCopper
DISC-DGA
PANEL-GA
1 3 1/0 PVC Pos:
Zero:
0.8876 0.3744
0.9216
CBL-0009 In
2.7972
MagneticCopper
PANEL-GA
PANEL-WTCP
1 20 2 PVC Pos:
Zero:
9.3380 2.7043
6.6568
CBL-0010 In
29.4286
MagneticCopper
PANEL-MDP1
BUS-0024
1 150 1/0 PVC Pos:
Zero:
8.3333 3.5156
8.6523
CBL-0011 In
26.2630
MagneticCopper
BUS-0025
PANEL-MDP2
1 30 500 PVC Pos:
Zero:
2.0386 3.2313
7.9535
CBL-0012 In
6.4210
MagneticCopper
PANEL-MDP1
BUS-0032
1 200 3/0 PVC Pos:
Zero:
6.9878 4.5052
11.0938
CBL-0013 In
22.0226
MagneticCopper
PANEL-MDP2
PANEL-VC1
1 25 2 PVC Pos:
Zero:
11.6725 3.3804
8.3210
CBL-0014 In
36.7858
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
PANEL-MDP2
PANEL-VC0
1 30 1 PVC Pos:
Zero:
11.0947 3.9525
9.7286
CBL-0015 In
34.9621
MagneticCopper
PANEL-MDP2
DISC-DVCEL
1 75 2 PVC Pos:
Zero:
35.0176 10.1412
24.9630
CBL-0016 In
110.3573
MagneticCopper
DISC-DVCEL
BUS-0026
1 20 2 PVC Pos:
Zero:
9.3380 2.7043
6.6568
CBL-0017 In
29.4286
MagneticCopper
BUS-0033
DISC-DHQ
1 30 500 PVC Pos:
Zero:
2.0386 3.2313
7.9535
CBL-0018 In
6.4210
MagneticCopper
DISC-DHQ
PANEL-HQ
1 50 500 PVC Pos:
Zero:
3.3977 5.3855
13.2558
CBL-0019 In
10.7017
MagneticCopper
PANEL-HQ
PANEL-HQ0
1 10 2 PVC Pos:
Zero:
4.6690 1.3522
3.3284
CBL-0020 In
14.7143
MagneticCopper
PANEL-HQ
PANEL-HQB
1 10 3/0 PVC Pos:
Zero:
1.8607 1.1996
2.9540
CBL-0021 In
5.8640
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
PANEL-HQ
PANEL-HQ1
1 30 2 PVC Pos:
Zero:
14.0070 4.0565
9.9852
CBL-0022 In
44.1429
MagneticCopper
PANEL-HQ
PANEL-HQ2
1 40 2 PVC Pos:
Zero:
18.6760 5.4087
13.3136
CBL-0023 In
58.8573
MagneticCopper
PANEL-HQ
DISC-DHQEL
1 20 2 PVC Pos:
Zero:
9.3380 2.7043
6.6568
CBL-0024 In
29.4286
MagneticCopper
DISC-DHQEL
BUS-0027
1 20 2 PVC Pos:
Zero:
9.3380 2.7043
6.6568
CBL-0025 In
29.4286
MagneticCopper
2-Winding Transformers
Xformer
Name Bus Conn. Volts FLA
Nominal kVA
Z PU (100 MVA Base)
R pu jX pu
In/Out
Service
------------------Primary & Secondary---------------
XFMR-TGA BUS-0022 D 480 90
BUS-0023
WG 208 208
75.0 Pos:
Zero:
56.8067
56.8067
25.8213
25.8213
In
XFMR-THQ BUS-0032 D 480 135
BUS-0033
WG 208 312
112.5 Pos:
Zero:
28.0818
28.0818
38.3787
38.3787
Xformer
Name Bus Conn. Volts FLA
Nominal kVA
Z PU (100 MVA Base)
R pu jX pu
In/Out
Service
------------------Primary & Secondary---------------
XFMR-TVC BUS-0024 D 480 135
BUS-0025
WG 208 312
112.5 Pos:
Zero:
28.0818
28.0818
38.3787
38.3787
XFMR-UTILITY BUS-0001 D 12,470 12
BUS-0002
WG 480 311
225.0 Pos:
Zero:
8.6667
8.6667
21.3333
21.3333
DAPPER Fault Contribution Complete Report
Comprehensive Short Circuit Study Settings
Three Phase Fault
Single Line to Ground
Line to Line Fault
Line to Line to Ground
All BusesFaulted Bus
Yes
Yes
Yes
No
No
Motor Contribution
Transformer Tap
Xformer Phase Shift
Yes
Yes
Bus Voltages
Branch Currents
Phase or Sequence
Fault Current Calculation
Asym Fault Current at Time 0.50
First Bus From Fault
First Branch From Fault
Report phase quantities
Asymmetrical RMS (with DC offset and Decay)
Cycles
Project: Copper Center
Bus Name
-------------Initial Symmetrical Amps-----------
3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG
----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---
---------Contributions---------
DISC-DFP 5,417 005,042 5,777 005,306
InCABLECBL-0005 331 00203310 00193 InCABLECBL-0003 5,451 005,1075,111 004,852 5,042
DISC-DGA 2,972 003,055 2,972 003,055
InCABLECBL-0009 0 0000 000 InCABLECBL-0008 2,972 003,0552,972 003,055 3,055
DISC-DHQ 3,652 003,972 3,717 004,031
InCABLECBL-0019 272 00197267 00194 InCABLECBL-0018 3,463 003,8473,402 003,790 3,972
DISC-DHQEL 3,148 003,033 3,183 003,048
InCABLECBL-0025 273 00174270 00174
InCABLECBL-0024 2,935 002,8892,903 002,875 3,033
DISC-DVCEL 2,696 002,301 2,702 002,302
InCABLECBL-0017 271 00154270 00154
Bus Name
-------------Initial Symmetrical Amps-----------
3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG
----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---
---------Contributions---------
InCABLECBL-0016 2,476 002,1732,470 002,172 2,301
DISC-SERVICE 5,335 004,941 5,738 005,263
InCABLECBL-0004 236 00144220 00136 InCABLECBL-0002 5,504 005,1205,117 004,806 4,941
PANEL-GA 2,942 003,002 2,943 003,002
InCABLECBL-0010 0 0000 000 InCABLECBL-0009 2,943 003,0022,942 003,002 3,002
PANEL-HQ 3,408 003,506 3,470 003,557
InCABLECBL-0022 0 0000 000 InCABLECBL-0021 0 0000 000 InCABLECBL-0023 0 0000 000 InCABLECBL-0020 0 0000 000 InCABLECBL-0024 274 00187269 00184 InCABLECBL-0019 3,214 003,3823,156 003,333 3,506
PANEL-HQ0 3,259 003,247 3,302 003,272
InCABLECBL-0020 3,302 003,2723,259 003,247 3,247
PANEL-HQ1 2,988 002,804 3,009 002,811
InCABLECBL-0022 3,009 002,8112,988 002,804 2,804
PANEL-HQ2 2,865 002,617 2,880 002,621
InCABLECBL-0023 2,880 002,6212,865 002,617 2,617
PANEL-HQB 3,325 003,366 3,381 003,407
InCABLECBL-0021 3,381 003,4073,325 003,366 3,366
PANEL-MDP2 3,653 003,971 3,706 004,023
InCABLECBL-0014 0 0000 000 InCABLECBL-0015 0 0000 000 InCABLECBL-0016 269 00195266 00192 InCABLECBL-0012 3,455 003,8403,404 003,791 3,971
PANEL-VC0 3,237 003,211 3,259 003,221
InCABLECBL-0015 3,259 003,2213,237 003,211 3,211
PANEL-VC1 3,241 003,209 3,260 003,217
InCABLECBL-0014 3,260 003,2173,241 003,209 3,209
PANEL-WTCP 2,678 002,559 2,678 002,559
InCABLECBL-0010 2,678 002,5592,678 002,559 2,559
Arc Flash Evaluation Report
Project: Copper Center
Base Project
Working
Distance
(in)
Arc
Duration
Breaker
Opening
Time
(sec.)
Trip/
Delay
Time
(sec.)
Protective
Device Name
Incident
Energy
(cal/cm2)
ArcFlash
Boundary
(in)
Bus Name
Bus
Bolted
Fault
(kA)
Bus
Arcing
Fault
(kA)
PPEProt
Bolted
Fault
(kA)
Prot
Arcing
Fault
(kA)
Arc
Type
Bus kV
2.000MaxTripTime @2.0s 15.6789.87 18.00
0.480DISC-DFP 4.905.42 4.03 3.64 0.000 2.000 In Box Arc-rated shirt & pants or arc-rated coverall or arc-rated arc flash suit
2.000PD-FEDR-GA 5.1044.50 18.000.208DISC-DGA 2.972.97 1.22 1.22 0.000 2.000 In Box Arc-rated shirt & pants or arc-rated coverall or arc-rated arc flash suit
2.000PD-FEDR-HQ 5.9749.13 18.00
0.208DISC-DHQ 3.403.65 1.53 1.42 0.000 2.000 In Box Arc-rated shirt & pants or
1.957PD-FEDR-HQEL 4.8943.37 18.00
0.208DISC-DHQEL 2.903.15 1.30 1.20 0.000 1.957 In Box Arc-rated shirt & pants or
2.000PD-FEDR-VCEL 4.1739.27 18.00
0.208DISC-DVCEL 2.472.70 1.10 1.00 0.000 2.000 In Box Arc-rated shirt & pants or
Working
Distance
(in)
Arc
Duration
Breaker
Opening
Time
(sec.)
Trip/
Delay
Time
(sec.)
Protective
Device Name
Incident
Energy
(cal/cm2)
ArcFlash
Boundary
(in)
Bus Name
Bus
Bolted
Fault
(kA)
Bus
Arcing
Fault
(kA)
PPEProt
Bolted
Fault
(kA)
Prot
Arcing
Fault
(kA)
Arc
Type
Bus kV
2.000MaxTripTime @2.0s 15.3888.81 18.000.480DISC-SERVICE 4.825.33 3.96 3.58 0.000 2.000 In Box Arc-rated shirt & pants or arc-rated coverall or arc-rated
2.000PD-GA 5.0444.19 18.00
0.208PANEL-GA 2.942.94 1.21 1.21 0.000 2.000 In Box Arc-rated shirt & pants or
2.000PD-GA1 5.4946.62 18.00
0.208PANEL-HQ 3.163.41 1.42 1.31 0.000 2.000 In Box Arc-rated shirt & pants or
2.000PD-FEDR-HQ0 4.5441.39 18.00
0.208PANEL-HQ0 3.263.26 1.16 1.16 0.000 2.000 In Box Arc-rated shirt & pants or arc flash suit
2.000PD-FEDR-HQ1 4.1439.07 18.000.208PANEL-HQ1 2.992.99 1.06 1.06 0.000 2.000 In Box Arc-rated shirt & pants or arc-rated coverall or arc-rated
2.000PD-FEDR-HQ2 4.5741.54 18.00
0.208PANEL-HQ2 2.862.86 1.17 1.17 0.000 2.000 In Box Arc-rated shirt & pants or
2.000PD-FEDR-HQB 5.3545.87 18.00
0.208PANEL-HQB 3.333.33 1.38 1.38 0.000 2.000 In Box Arc-rated shirt & pants or arc flash suit
0.024PD-MDP2 0.083.26 18.000.208PANEL-MDP2 3.403.65 1.53 1.42 0.000 0.024 In Box No Arc-rated PPE Required
(in)
Arc
Duration
Breaker
Opening
Time
(sec.)
Trip/
Delay
Time
(sec.)
Protective
Device Name
Incident
Energy
(cal/cm2)
ArcFlash
Boundary
(in)
Bus Name
Bus
Bolted
Fault
(kA)
Bus
Arcing
Fault
(kA)
PPEProt
Bolted
Fault
(kA)
Prot
Arcing
Fault
(kA)
Arc
Type
Bus
2.000PD-FEDR-VC0 4.5641.48 18.00
0.208PANEL-VC0 3.243.24 1.15 1.15 0.000 2.000 In Box Arc-rated shirt & pants or
2.000PD-FEDR-VC1 4.5641.50 18.00
0.208PANEL-VC1 3.243.24 1.15 1.15 0.000 2.000 In Box Arc-rated shirt & pants or
2.000PD-FEDR-WTCP 4.5441.37 18.00
0.208PANEL-WTCP 2.682.68 1.09 1.09 0.000 2.000 In Box Arc-rated shirt & pants or
UTIL-CVEA
S
P
XFMR-UTIL
CBL-SERVICE
PD-SERV DISC
CBL-MDP
MDP
InitSymRMS 3P 1333.87 A InitSymRMS SLG 1243.49 A
PD-FEDR SB PD-FEDR MS PD-FEDR CS
CBL-SHED-DISC CBL-MECH SHOP CBL-CARP SHOP
DISC-DSB
InitSymRMS 3P 1069.76 A InitSymRMS SLG 896.45 A
PANEL-SBL1
InitSymRMS 3P 1054.08 A InitSymRMS SLG 877.91 A
CBL-SHED-PNL
PD-SBL1
PANEL-MSL1
InitSymRMS 3P 1265.52 A InitSymRMS SLG 1146.44 A
PD-MSL1
PANEL-CSL1
InitSymRMS 3P 1195.51 A InitSymRMS SLG 1052.54 A
PD-CSL1
PD-CARPENTER SHOP SUB PANEL
PANEL-CSL2
InitSymRMS 3P 1188.11 A InitSymRMS SLG 1042.85 A
CBL-CSL2
DISC-SERVICE
InitSymRMS 3P 1338.08 A InitSymRMS SLG 1249.60 A
WRST - ARC FLASH ANALYSIS - GLENALLEN
Project: Glennallen Main Shop
Base Project
Utilities
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
-------- Contribution Data -------- PU (100 MVA Base)
X PUR PUX/RUnitsDuty
UTIL-CVEA BUS-0001 12,470 MVA 9,999.00In 1,000,000
SLG:
3P:
MVA 9,999.00
Pos:
Zero:333,333
0.0001
0.00010.0000
0.0000
Cables
Cable
Name
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
MDP
PANEL-CSL1
1 75 1/0 PVC Pos:
Zero:
22.1894 9.3611
23.0388
CBL-CARP SHOP In
69.9311
MagneticCopper
PANEL-CSL1
PANEL-CSL2
1 3 2 PVC Pos:
Zero:
1.4007 0.4056
0.9985
CBL-CSL2 In
4.4143
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
DISC-SERVICE
MDP
1 3 3/0 PVC Pos:
Zero:
0.5582 0.3599
0.8862
CBL-MDP In
1.7592
MagneticCopper
MDP
PANEL-MSL1
1 35 1/0 PVC Pos:
Zero:
10.3550 4.3685
10.7514
CBL-MECH SHOP In
32.6345
MagneticCopper
BUS-0002
DISC-SERVICE
1 135 1/0 XLP Pos:
Zero:
65.5279 14.0417
35.6971
CBL-SERVICE In
104.1582
Non-MagneticAluminum
MDP
DISC-DSB
1 160 1/0 PVC Pos:
Zero:
47.3373 19.9704
49.1494
CBL-SHED-DISC In
149.1864
MagneticCopper
DISC-DSB
PANEL-SBL1
1 8 2 PVC Pos:
Zero:
3.7352 1.0817
2.6627
CBL-SHED-PNL In
11.7715
MagneticCopper
2-Winding Transformers
Xformer
Name Bus Conn. Volts FLA
Nominal kVA
Z PU (100 MVA Base)
R pu jX pu
In/Out
Service
------------------Primary & Secondary---------------
XFMR-UTIL BUS-0001 D 12,470 2
BUS-0002
WG 208 96
30.0 Pos:
Zero:
125.0000
125.0000
68.0000
68.0000
Three Phase Fault
Single Line to Ground
Line to Line Fault
Line to Line to Ground
All BusesFaulted Bus
Yes
Yes
Yes
No
No
Motor Contribution
Transformer Tap
Xformer Phase Shift
Yes
Yes
Bus Voltages
Branch Currents
Phase or Sequence
Fault Current Calculation
Asym Fault Current at Time 0.50
First Bus From Fault
First Branch From Fault
Report phase quantities
Asymmetrical RMS (with DC offset and Decay)
Cycles
Project: Glennallen Main Shop
Bus Name
-------------Initial Symmetrical Amps-----------
3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG
----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---
---------Contributions---------
DISC-DSB 1,070 00896 1,070 00896
InCABLECBL-SHED-PNL 0 0000 000 InCABLECBL-SHED-DISC 1,070 008961,070 00896 896
DISC-SERVICE 1,338 001,250 1,338 001,250
InCABLECBL-MDP 0 0000 000 InCABLECBL-SERVICE 1,338 001,2501,338 001,250 1,250
MDP 1,334 001,243 1,334 001,243
InCABLECBL-SHED-DISC 0 0000 000 InCABLECBL-MECH SHOP 0 0000 000 InCABLECBL-CARP SHOP 0 0000 000 InCABLECBL-MDP 1,334 001,2431,334 001,243 1,243
PANEL-CSL1 1,196 001,053 1,196 001,053
InCABLECBL-CSL2 0 0000 000 InCABLECBL-CARP SHOP 1,196 001,0531,196 001,053 1,053
3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG
----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---
---------Contributions---------
PANEL-CSL2 1,188 001,043 1,188 001,043
InCABLECBL-CSL2 1,188 001,0431,188 001,043 1,043
PANEL-MSL1 1,266 001,146 1,266 001,146
InCABLECBL-MECH SHOP 1,266 001,1461,266 001,146 1,146
PANEL-SBL1 1,054 00878 1,054 00878
InCABLECBL-SHED-PNL 1,054 008781,054 00878 878
Project: Glennallen Main Shop
Base Project
Working
Distance
(in)
Arc
Duration
Breaker
Opening
Time
(sec.)
Trip/
Delay
Time
(sec.)
Protective
Device Name
Incident
Energy
(cal/cm2)
ArcFlash
Boundary
(in)
Bus Name
Bus
Bolted
Fault
(kA)
Bus
Arcing
Fault
(kA)
PPEProt
Bolted
Fault
(kA)
Prot
Arcing
Fault
(kA)
Arc
Type
Bus
2.000PD-FEDR SB 1.6421.86 18.00
0.208DISC-DSB 1.071.07 0.40 0.40 0.000 2.000 In Box Arc-rated shirt & pants or arc flash suit
2.000MaxTripTime @2.0s 2.1125.61 18.000.208DISC-SERVICE 0.001.34 0.51 0.00 0.000 2.000 In Box Arc-rated shirt & pants or arc-rated coverall or arc-rated
2.000PD-SERV DISC 2.1025.55 18.00
0.208MDP 1.331.33 0.51 0.51 0.000 2.000 In Box Arc-rated shirt & pants or
2.000PD-FEDR CS 1.8623.65 18.00
0.208PANEL-CSL1 1.201.20 0.45 0.45 0.000 2.000 In Box Arc-rated shirt & pants or arc flash suit
2.000PD-CARPENTER
SHOP SUB PANEL
1.8423.54 18.00
0.208PANEL-CSL2 1.191.19 0.45 0.45 0.000 2.000 In Box Arc-rated shirt & pants or
(in)
Arc
Duration
Breaker
Opening
Time
(sec.)
Trip/
Delay
Time
(sec.)
Protective
Device Name
Incident
Energy
(cal/cm2)
ArcFlash
Boundary
(in)
Bus Name
Bus
Bolted
Fault
(kA)
Bus
Arcing
Fault
(kA)
PPEProt
Bolted
Fault
(kA)
Prot
Arcing
Fault
(kA)
Arc
Type
Bus kV
2.000PD-MSL1 1.9824.62 18.000.208PANEL-MSL1 1.271.27 0.48 0.48 0.000 2.000 In Box Arc-rated shirt & pants or arc-rated coverall or arc-rated
2.000PD-SBL1 1.6121.64 18.00
0.208PANEL-SBL1 1.051.05 0.40 0.40 0.000 2.000 In Box Arc-rated shirt & pants or
GEN-0001
Isc 3P 561 A
Isc SLG 561 A
PD-GEN
BUS-GEN
Isc 3P 561 A
Isc SLG 561 A
BUS-PDP PP
Isc 3P 556 A
Isc SLG 552 A
CBL-0001
Isc 3P 556 A
Isc SLG 552 A
PANEL A-NP
Isc 3P 552 A
Isc SLG 547 A
PD-PNL A-MCB
CBL-0002
Isc 3P 552 A
Isc SLG 547 A
PD-SITE-FEDR
CBL-0004
Isc 3P 550 A
Isc SLG 544 A
PD-PNL B FEDR
CBL-0005
Isc 3P 546 A
Isc SLG 538 A
BUS-PANEL B-NP
Isc 3P 546 A
Isc SLG 538 A
BUS-IN-GRADE JB
Isc 3P 203 A
Isc SLG 276 A
CBL-0006
Isc 3P 203 A
Isc SLG 276 A
DISC-DDB
Isc 3P 202 A
Isc SLG 274 A
CBL-0007
Isc 3P 202 A
Isc SLG 274 A
CBL-0008
Isc 3P 202 A
Isc SLG 273 A
PD-0005
CBL-0009
Isc 3P 369 A
PD-DBL1
PANEL-DBL1
Isc 3P 369 A
CBL-0010
Isc 3P 193 A
Isc SLG 246 A
S
P
XFMR-TRC
Isc 3P 356 A
PD-RCDL
PANEL-RCDL
Isc 3P 354 A
S
P
XFMR-TDB
Isc 3P 373 A
S
P
XF2-SITE
Isc 3P 206 A
Isc SLG 288 A
DISC-DRC
Isc 3P 193 A
Isc SLG 246 A
PD-0006
CBL-0011
Isc 3P 193 A
Isc SLG 246 A
PANEL-RCDH
Isc 3P 193 A
Isc SLG 246 A
PD-RCDH
PD-FEDR RCDL
CBL-0012
Isc 3P 193 A
Isc SLG 246 A
CBL-0013
Isc 3P 354 A
PD-FEDR TB
S
P
XFMR-TTB
Isc 3P 391 A
PANEL-TBDL
Isc 3P 391 A
CBL-0014
Isc 3P 182 A
Isc SLG 213 A
CBL-0015
Isc 3P 391 A
CBL-0016
Isc 3P 182 A
Isc SLG 213 A
PANEL-TBDH
Isc 3P 182 A
Isc SLG 213 A
PD-TBDH
PD-TBDL
PD-FEDR LP
PD-FEDR GS
CBL-0017
Isc 3P 381 A
PD-MDP GS PANEL-MDP GS
Isc 3P 381 A
PD-FEDR SUB A
PANEL SUB-A GS
Isc 3P 381 A
CBL-0018
Isc 3P 381 A
PANEL-LPDH
Isc 3P 168 A
Isc SLG 179 A
S
P
XFMR-TLP
Isc 3P 330 A
PD-LPDL
PANEL-LPDL
Isc 3P 329 A
CBL-0019
Isc 3P 329 A
PD-480V DIST MCB-LP
CBL-0020
Isc 3P 168 A
Isc SLG 179 A
PD-208V DIST PNL FEDR-LP
CBL-0021
Isc 3P 167 A
Isc SLG 179 A
DISC-DOP
Isc 3P 159 A
Isc SLG 162 A
CBL-0022
Isc 3P 159 A
Isc SLG 161 A
PD-0007
CBL-0023
Isc 3P 273 A
PD-OPDL
PANEL-OPDL
Isc 3P 273 A
S
P
XFMR-TOP
Isc 3P 273 A
CBL-0024
Isc 3P 159 A
Isc SLG 162 A
BUS-PNL LP LINESIDE TAP
Isc 3P 168 A
Isc SLG 179 A
CBL-0025
Isc 3P 168 A
Isc SLG 179 A
WRST - ARC FLASH ANALYSIS - KENNECOTT
Project: Kennecott
Base Project
Generators
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
-------- Contribution Data --------
Base kVA X" X/R
PU (100 MVA Base)
R PU X PU
GEN-0001 208BUS-GEN 31.25 4.01In 0.15
0.15
0.15
4.01
4.01
119.6202 480.0000
119.62
480.0000119.6202
480.00
Pos:
Zero:
Neg:
Cables
Cable
Name
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-GEN
BUS-PDP PP
1 20 2 PVC Pos:
Zero:
9.3380 2.7043
6.6568
CBL-0001 In
29.4286
MagneticCopper
BUS-PDP PP
PANEL A-NP
1 20 1/0 EDPM/CPEPos:
Zero:
6.0558 2.0340
5.1729
CBL-0002 In
9.6293
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
PANEL A-NP
BUS-0019
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-0004 In
8.8286
MagneticCopper
PANEL A-NP
BUS-PANEL B-NP
1 20 2 PVC Pos:
Zero:
9.3380 2.7043
6.6568
CBL-0005 In
29.4286
MagneticCopper
BUS-0018
BUS-IN-GRADE
JB
1 180 2 PVC Pos:
Zero:
15.7813 4.5703
11.2500
CBL-0006 In
49.7344
MagneticCopper
BUS-IN-GRADE
JB
DISC-DDB
1 20 2 PVC Pos:
Zero:
1.7535 0.5078
1.2500
CBL-0007 In
5.5260
MagneticCopper
DISC-DDB
BUS-0016
1 20 2 PVC Pos:
Zero:
1.7535 0.5078
1.2500
CBL-0008 In
5.5260
MagneticCopper
BUS-0017
PANEL-DBL1
1 20 2 PVC Pos:
Zero:
9.3380 2.7043
6.6568
CBL-0009 In
29.4286
MagneticCopper
BUS-IN-GRADE
JB
DISC-DRC
1 450 2 PVC Pos:
Zero:
39.4531 11.4258
28.1250
CBL-0010 In
124.3359
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
DISC-DRC
PANEL-RCDH
1 5 2 PVC Pos:
Zero:
0.4384 0.1270
0.3125
CBL-0011 In
1.3815
MagneticCopper
PANEL-RCDH
BUS-0022
1 10 2 PVC Pos:
Zero:
0.8767 0.2539
0.6250
CBL-0012 In
2.7630
MagneticCopper
BUS-0023
PANEL-RCDL
1 10 2 PVC Pos:
Zero:
4.6690 1.3522
3.3284
CBL-0013 In
14.7143
MagneticCopper
PANEL-TBDH
BUS-0024
1 10 2 PVC Pos:
Zero:
0.8767 0.2539
0.6250
CBL-0014 In
2.7630
MagneticCopper
BUS-0025
PANEL-TBDL
1 5 4/0 PVC Pos:
Zero:
0.7396 0.5744
1.4146
CBL-0015 In
2.3310
MagneticCopper
PANEL-RCDH
PANEL-TBDH
1 600 2 PVC Pos:
Zero:
52.6042 15.2344
37.5000
CBL-0016 In
165.7813
MagneticCopper
PANEL-TBDL
PANEL-MDP GS
1 100 4/0 PVC Pos:
Zero:
14.7929 11.4876
28.2914
CBL-0017 In
46.6208
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
PANEL-MDP GS
PANEL SUB-A GS
1 3 2 PVC Pos:
Zero:
1.4007 0.4056
0.9985
CBL-0018 In
4.4143
MagneticCopper
BUS-0026
PANEL-LPDL
1 10 2 PVC Pos:
Zero:
4.6690 1.3522
3.3284
CBL-0019 In
14.7143
MagneticCopper
PANEL-TBDH
BUS-PNL LP
LINESIDE TAP
1 800 2 PVC Pos:
Zero:
70.1389 20.3125
50.0000
CBL-0020 In
221.0417
MagneticCopper
PANEL-LPDH
BUS-0034
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
CBL-0021 In
1.6578
MagneticCopper
DISC-DOP
BUS-0039
1 50 2 PVC Pos:
Zero:
4.3837 1.2695
3.1250
CBL-0022 In
13.8151
MagneticCopper
BUS-0040
PANEL-OPDL
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-0023 In
8.8286
MagneticCopper
BUS-PNL LP
LINESIDE TAP
DISC-DOP
1 500 2 PVC Pos:
Zero:
43.8368 12.6953
31.2500
CBL-0024 In
138.1510
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-PNL LP
LINESIDE TAP
PANEL-LPDH
1 1 2 PVC Pos:
Zero:
0.0877 0.0254
0.0625
CBL-0025 In
0.2763
MagneticCopper
2-Winding Transformers
Xformer
Name Bus Conn. Volts FLA
Nominal kVA
Z PU (100 MVA Base)
R pu jX pu
In/Out
Service
------------------Primary & Secondary---------------
XF2-SITE BUS-0019 D 208 83
BUS-0018
WG 480 36
30.0 Pos:
Zero:
102.1367
102.1367
45.9600
45.9600
XFMR-TDB BUS-0016 D 480 36
BUS-0017
W 208 83
30.0 Pos:
Zero:
123.5100
,300.0000
101.7133
,300.0000
XFMR-TLP BUS-0034 D 480 36
BUS-0026
W 208 83
30.0 Pos:
Zero:
97.5200
,300.0000
80.3100
XFMR-TOP BUS-0039 D 480 18
BUS-0040
W 208 42
15.0 Pos:
Zero:
202.2467
,600.0000
166.5533
,600.0000
In
XFMR-TRC BUS-0022 D 480 36
BUS-0023
W 208 83
30.0 Pos:
Zero:
128.6567
,300.0000
105.9500
Xformer
Name Bus Conn. Volts FLA
Nominal kVA
Z PU (100 MVA Base)
R pu jX pu
In/Out
Service
------------------Primary & Secondary---------------
XFMR-TTB BUS-0024 D 480 90
BUS-0025
W 208 208
75.0 Pos:
Zero:
38.0827
,320.0000
31.3613
,320.0000
Three Phase Fault
Single Line to Ground
Line to Line Fault
Line to Line to Ground
All BusesFaulted Bus
Yes
Yes
Yes
No
No
Motor Contribution
Transformer Tap
Xformer Phase Shift
Yes
Yes
Bus Voltages
Branch Currents
Phase or Sequence
Fault Current Calculation
Asym Fault Current at Time 0.50
First Bus From Fault
First Branch From Fault
Report phase quantities
Asymmetrical RMS (with DC offset and Decay)
Cycles
Project: Kennecott
Bus Name
-------------Initial Symmetrical Amps-----------
3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG
----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---
---------Contributions---------
BUS-GEN 561 00561 668 00668
InCABLECBL-0001 0 0000 000 InGENGEN-0001 668 00668561 00561 561
BUS-PANEL B-NP 546 00538 625 00604
InCABLECBL-0005 625 00604546 00538 538
BUS-PDP PP 556 00552 651 00640
InCABLECBL-0002 0 0000 000 InCABLECBL-0001 651 00640556 00552 552
DISC-DDB 202 00274 212 00281
InCABLECBL-0008 0 0000 000 InCABLECBL-0007 212 00281202 00274 274
DISC-DOP 159 00162 161 00163
InCABLECBL-0022 0 0000 000 InCABLECBL-0024 161 00163159 00162 162
3 Phase SLG LLG LL LLG LLSLG3 Phase SLG LLG
----------------Asymmetrical Amps---------------- ---Init Sym Neutral Amps---
---------Contributions---------
DISC-DRC 193 00246 200 00249
InCABLECBL-0011 0 0000 000 InCABLECBL-0010 200 00249193 00246 246
PANEL A-NP 552 00547 640 00627
InCABLECBL-0005 0 0000 000 InCABLECBL-0004 0 0000 000 InCABLECBL-0002 640 00627552 00547 547
PANEL SUB-A GS 381 000 386 000
InCABLECBL-0018 386 000381 000
PANEL-DBL1 369 000 377 000
InCABLECBL-0009 377 000369 000
PANEL-LPDH 168 00179 169 00179
InCABLECBL-0021 0 0000 000
InCABLECBL-0025 169 00179168 00179 179
PANEL-LPDL 329 000 331 000
InCABLECBL-0019 331 000329 000
PANEL-MDP GS 381 000 387 000
InCABLECBL-0018 0 0000 000 InCABLECBL-0017 387 000381 000
PANEL-OPDL 273 000 274 000
InCABLECBL-0023 274 000273 000
PANEL-RCDH 193 00246 200 00249
InCABLECBL-0016 0 0000 000 InCABLECBL-0012 0 0000 000 InCABLECBL-0011 200 00249193 00246 246
PANEL-RCDL 354 000 360 000
InCABLECBL-0013 360 000354 000
PANEL-TBDH 182 00213 185 00214
InCABLECBL-0014 0 0000 000 InCABLECBL-0020 0 0000 000 InCABLECBL-0016 185 00214182 00213 213
PANEL-TBDL 391 000 397 000
InCABLECBL-0017 0 0000 000 InCABLECBL-0015 397 000391 000
Project: Kennecott
Base Project
Working
Distance
(in)
Arc
Duration
Breaker
Opening
Time
(sec.)
Trip/
Delay
Time
(sec.)
Protective
Device Name
Incident
Energy
(cal/cm2)
ArcFlash
Boundary
(in)
Bus Name
Bus
Bolted
Fault
(kA)
Bus
Arcing
Fault
(kA)
PPEProt
Bolted
Fault
(kA)
Prot
Arcing
Fault
(kA)
Arc
Type
Bus
2.000MaxTripTime @2.0s 0.7913.88 18.00
0.208BUS-GEN 0.000.56 0.20 0.00 0.000 2.000 In Box No Arc-rated PPE Required
2.000PD-PNL B FEDR 0.7713.62 18.00
0.208BUS-PANEL B-NP 0.550.55 0.20 0.20 0.000 2.000 In Box No Arc-rated PPE Required
2.000PD-GEN 0.7813.79 18.000.208BUS-PDP PP 0.560.56 0.20 0.20 0.000 2.000 In Box No Arc-rated PPE Required
2.000PD-SITE-FEDR 0.4711.35 18.00
0.480DISC-DDB 0.200.20 0.20 0.20 0.000 2.000 In Box No Arc-rated PPE Required
2.000PD-FEDR LP 0.3710.08 18.00
0.480DISC-DOP 0.160.16 0.16 0.16 0.000 2.000 In Box No Arc-rated PPE Required
(in)
Arc
Duration
Breaker
Opening
Time
(sec.)
Trip/
Delay
Time
(sec.)
Protective
Device Name
Incident
Energy
(cal/cm2)
ArcFlash
Boundary
(in)
Bus Name
Bus
Bolted
Fault
(kA)
Bus
Arcing
Fault
(kA)
PPEProt
Bolted
Fault
(kA)
Prot
Arcin…
This is the start of the file's text. The full file is on GovTribe.