Attachment 7 - VASFHCS EHRM Project Manual Updated 3-4-21 No CBOCs.pdf

PDF 3 MB Posted

Attached to
Y1BG--EHRM Infrastructure Upgrades Design-Build San Francisco, CA - Project # 662-20-700
Solicitation number
36C77621R0105
Issued by

About this file

This notice provides information about an upcoming federal contract opportunity for Electronic Health Records Modernization infrastructure upgrades at the San Francisco VA Medical Center.

The Department of Veterans Affairs intends to solicit proposals and award a single firm-fixed-price design-build contract to provide all labor, materials, and services necessary to relocate or remodel approximately 50 telecommunications rooms and one data center. The project scope involves bringing the spaces up to VA Office of Information and Technology and EHRM infrastructure standards while maintaining IT service continuity. The design-build contractor will deliver a turnkey project in accordance with applicable standards.

The solicitation will be conducted as a two-phase design-build selection and issued in July 2021 as a total SDVOSB set-aside. The contract value is estimated between $10-20 million. The period of performance is approximately 540 calendar days from notice to proceed. Questions must be submitted in writing by the specified date.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VISN 21 CM/PM Electronic Health Records Modernization (EHRM) PHASE I Support Task

PO# 612C209

San Francisco Health Care System San Francisco VA Medical Center

Ta b l e o f C o n t e n t s

Project TeamContributors

Vicinity Map/Building Addresses

Campus Map / Building Information

Placeholder - VAMC Fiber Distances Placeholder - VAMC Fiber Distances Door Security Requirements

San Francisco VAMC - Bldg. 1 Second Floor Plan

San Francisco VAMC - Bldg. 2 Ground Floor Plan First Floor Plan Second Floor Plan Third Floor Plan Fourth Floor Plan Fifth Floor Plan

San Francisco VAMC - Bldg. 6 First Floor Plan Second Floor Plan

San Francisco VAMC – Bldg. 7 First Floor Plan

San Francisco VAMC – Bldg. 8 Second Floor Plan

San Francisco VAMC – Bldg. 9 Basement

San Francisco VAMC – Bldg. 10 Basement

San Francisco VAMC – Bldg. 11 Basement

San Francisco VAMC – Bldg. 12 Basement

Identification of Network Spaces

Network Spaces: (cont’d)

San Francisco VAMC – Bldg. 16 First Floor Plan

San Francisco VAMC – Bldg. 22 First Floor Plan

San Francisco VAMC – Bldg. 41 Ground Floor

San Francisco VAMC – Bldg. 42 First Floor Plan

San Francisco VAMC – Bldg. 200 Ground Floor Plan First Floor Plan Second Floor Plan Third Floor Plan Lower Roof - Penthouse

San Francisco VAMC – Bldg. 203 Basement Second Floor Plan

San Francisco VAMC – Bldg. 205 Mezzanine

San Francisco VAMC – Bldg. 207 Ground Floor Plan

San Francisco VAMC – Bldg. 208 Basement

San Francisco VAMC – Bldg. 210 Ground Floor Plan Second Floor Plan

San Francisco VAMC – Bldg. 211 First Floor Plan

San Francisco VAMC – T31 First Floor Plan

San Francisco VAMC – T33 First Floor Plan

Ta b l e o f C o n t e n t s

San Francisco VAMC – T35 First Floor Plan

Sheet Removed

Network Space Design: 59

Bldg. 1:

Design Matrix Enlarged Plan – Existing

Bldg. 2:

153 & 155C Design Matrix Enlarged Plan - Existing

Bldg. 2:

355 & 355D Design Matrix Enlarged Plan - Existing

Bldg. 2:

Design Matrix Enlarged Plan - Existing

Bldg. 2:

Design Matrix Enlarged Plan – Existing

Bldg. 6:

209K Design Matrix Enlarged Plan – Existing

Bldg. 7:

Design Matrix Enlarged Plan - Existing

Bldg. 8:

Design Matrix Enlarged Plan – Existing

Bldg. 9:

Basement Design Matrix Enlarged Plan – Existing

Sheet Removed

Sheet Removed

Sheet Removed

Sheet Removed

Sheet Removed

Sheet Removed

Sheet Removed

Sheet Removed

Sheet Removed

Bldg. 11:

B05 Design Matrix Enlarged Plan – Existing

Bldg. 12:

B11 Design Matrix Enlarged Plan – Existing

Bldg. 16:

Design Matrix Enlarged Plan - Existing

Bldg. 22:

Design Matrix Enlarged Plan - Existing

Bldg. 41:

G14 Design Matrix Enlarged Plan - Existing

Bldg. 42:

TC-1

Design Matrix Enlarged Plan – Existing

Bldg. 200:

GB-116C

Design Matrix Enlarged Plan - Existing

Bldg. 200:

1A-113 Design Matrix Enlarged Plan – Existing

Bldg. 200:

2A-109 Design Matrix Enlarged Plan – Existing

Bldg. 200:

2A-171A Design Matrix Enlarged Plan – Existing

Bldg. 200:

3A-157 Design Matrix Enlarged Plan – Existing

Bldg. 200:

Penthouse Design Matrix Enlarged Plan – Existing

Bldg. 203:

BA-8

Design Matrix Enlarged Plan - Existing

Bldg. 203:

2A-48 Design Matrix Enlarged Plan - Existing

Bldg. 203:

2B-22 Design Matrix Enlarged Plan - Existing

Bldg. 205:

M6 Design Matrix Enlarged Plan - Existing

Bldg. 207:

Design Matrix Enlarged Plan - Existing

Bldg. 208:

BA-115

Design Matrix Enlarged Plan – Existing

Network Space Design (cont’d)

Ta b l e o f C o n t e n t s

Network Space Design (cont’d)

Bldg. 210:

Design Matrix Enlarged Plan – Existing

Bldg. 211:

106A Design Matrix Enlarged Plan – Existing

Bldg. T31:

Design Matrix Enlarged Plan - Existing

Bldg. T33:

IDF

Design Matrix Enlarged Plan – Existing

Bldg. T35:

G09 Design Matrix Enlarged Plan – N/A

Sheet Removed

Ta b l e o f C o n t e n t s

89 99

Network Space Design (cont’d): 97

Appendix A – Power Installation Example

Appendix B – Compliance Requirements

Appendix C – Rack Labeling Standard

Appendix

Sheet Removed

Sheet Removed

Sheet Removed

Sheet Removed

Sheet Removed

Sheet Removed

Sheet Removed

Sheet Removed

P R O J E C T C O N TA C T D I R E C T O R Y

Concourse Federal Group 123 S. Royal Street Alexandria, Virginia 22314

Tim Hower, Project Manager .........................................................................................thower@concousefederal.com Lorena Alvarez.................................................................................................................IaIvarez@concousefederaI.com Mike Olson .................................................................................................................... molson@concousefederal.com Marshall Contino, Concourse A|E Vice President ........................................................ mcontino@concousefederal.com

DHE Engineering 3300 N. Central Ave. 3300 Tower Suite, 1520, Phoenix, AZ 85012

Rick Seger P.E., Principal, Electrical Engineer................................................................rseger@dheeng.com Kory Young, EIT, Senior Mechanical Engineer.................................................................kyoung@dheeng.com

VA San Francisco Health Care System

Matt Szeto, Chief, Capital Planning and Development................................................. Matthew.Szeto@va.gov Kailen Collette……………………….….................................................................................... Kailen.Collette2@va.gov

V i c i n i t y M a p B u i l d i n g A d d r e s s S a n F r a n c i s c o V A M e d i c a l C e n t e r ( V A M C ) 4 1 5 0 C l e m e n t S t r e e t S a n F r a n c i s c o , C A 9 4 1 2 1

B u i l d i n g I n f o r m a t i o n Bldg. # Bldg. Name TR Qty Levels

1 AUDIOLOGY/MENTAL HEALTH CLINIC 1 5

2 ADMINISTRATION/LABORATORY 4 7

6 A&MMS/LIBRARY/FISCAL/RESEARCH 2 4

7 CANTEEN/CHAPEL/AUDITORIUM 1 5

8 MENTAL HEALTH/RESEARCH 1 4

9 HOPTEL 1 3

10 HOPTEL 0 3

11 MENTAL HEALTH/RESEARCH 1 3

12 RESEARCH 1 3

16 RESEARCH 1 1

22 HOPTEL 1 3

41 VMU 1 2

42 RESEARCH 1 1

200 AMBULATORY CARE CLINIC 6 5

203 HOSPITAL (A & B WING) 3 5

205 ENERGY CENTER 1 2

208 COMMUNITY LIVING CENTER 1 3

210 HOSPITAL ADMINISTRATION 1 3

211 PARKING GARAGE 1 4

T31 SAFETY BUILDING 1 1

T33 PSYCHIATRY BLDG. 1 1

T35 CHILD CARE CENTER 1 1

Bldg. # Bldg. Name Data Ctr Levels

207 ADMINISTRATION 1 1

C a m p u s M a p

VAMC FIBER DISTANCES

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANSISCO VAMC

VAMC San Francisco Division

Building Floor Room Distance From Exisitng Server Room (Ft.) Notes Fiber type Conduit Type

207 1 107A N/A Server Room 24 strand single mode Interior - 4" EMT

1 2 214 300 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

2 5 TC-520 250 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

2 4 TC-420 400 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

2 3 TC-320 270 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

2 2 TC-220 250 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

2 1 TC-120 225 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

2 G TC-G20 200 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

6 1 113 600 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

6 2 207 625 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

7 1 107 400 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

8 2 216 480 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

9 B BASEMENT 610 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

10 B BASEMENT 750 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

11 B B05 900 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

12 B B11 690 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

16 1 11 1300 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

22 1 103 650 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

41 G G14 670 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

42 1 TC1 1100 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

CREATE REDUNDANT WAN PATH – ASSUME 1000’-0”

CONCRETE ENCASED 4” PVC OR HDPE WITH (4) 1” INTERDUCTS.

VAMC FIBER DISTANCES

SAN FRANSISCO VAMC

VAMC San Francisco Division

Building Floor Room Distance From Existing Server Room (Ft.)

Notes Fiber type Conduit Type

200 3 3A157 360 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

200 2 2B101 340 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

200 2 2A171 340 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

200 2 2A109A 340 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

200 2 1A224 320 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

200 ROOF PENTHOUSE 360 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

200 G GB116C 340 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

200 1 1A114 320 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

200 1 1A-113 320 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

200 1 1A-224 320 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

203 2 A SIDE 2A-48 645 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

203 2 B SIDE 2B-22 645 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

203 B BA8 625 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

205 1 M6 860 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

208 B BA114 1120 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

210 G GA4 390 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

210 2 203 410 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

211 1 106A 1100 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

T27 1 RESTROOM 750 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

T31 1 105 350 25 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

T33 1 1 IDF 650 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

T35 1 1-103 820 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

T28 1 800 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

DOOR SECURITY REQUIREMENTS

SAN FRANSISCO VAMC

I D E N T I F I C AT I O N O F N E T WO R K S PAC E S

BLDG: 1

LEVEL: 2

SCALE: 1/16” = 1’-0”

DATE: 11/10/2020

N

REMEDIATE IN PLACE

TELE

ROOM 214

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANSISCO VAMC

BLDG: 2

LEVEL: GROUND FLOOR

SCALE: 1/32” = 1’-0”

DATE: 11/10/2020

N

ABANDON TELECOM

ROOM TC-G20

RELOCATE TO NEW TR

ROOM 153 & 155C

GROUND FLOOR TO BE

SERVED BY 1st FLOOR

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

LEVEL: 1

SCALE: 1/32” = 1’-0”

DATE: 11/10/2020

N

ROOM 120

RELOCATE TO 153 & 155C

EXISTING CLOSET WILL SERVE AS A CHASE

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

NEW TR ROOM 153 & 155C

THIS TR TO SERVE GROUND FLOOR

AND 1st FLOOR

SCALE: 1/32” = 1’-0”

DATE: 11/10/2020

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

ROOM TC-220

RELOCATE TO ROOM 355 & 355D

EXISTING CLOSET WILL SERVE AS A CHASE

LEVEL: 3

SCALE: 1/32” = 1’-0”

DATE: 11/10/2020

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

NEW TR ROOM 355 & 355D

TR TO SERVE 2nd AND 3rd FLOOR

ROOM TC-320

RELOCATE TO ROOM 355 & 355D

EXISTING CLOSET WILL SERVE AS A CHASE

LEVEL: 4

SCALE: 1/32” = 1’-0”

DATE: 11/10/2020

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

ROOM TC-420

RELOCATE TO NEW TR ROOM 453

ABANDON EXISTING CLOSET

NEW TR ROOM 453

TR TO SERVE 4th FLOOR ONLY

LEVEL: 5

SCALE: 1/32” = 1’-0”

DATE: 11/10/2020

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

ROOM TC-520

RELOCATE TO NEW TR ROOM 553

ABANDON EXISTING TELECOM ROOM TC-520

NEW TR ROOM 553

TR TO SERVE 5th FLOOR ONLY

BLDG: 6

SCALE: 1/16” = 1’-0”

DATE: 11/10/2020

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

SWITCHBOARD

ROOM 113

RELOCATE TO NEW TR ROOM 209K

ABANDON ROOM 113

BLDG: 6

SCALE: 1/16” = 1’-0”

DATE: 11/10/2020

N

TELECOM

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

NEW TR ROOM 209K

RELOCATE TO NEW TR ROOM 209K

ABANDON ROOM 207

BLDG: 7

SCALE: 1/16” = 1’-0”

DATE: 11/10/2020

N

STOR.

RELOCATE TO ROOM 106

ABANDON 107

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

NEW TR ROOM 106

BLDG: 8

SCALE: 1/16” = 1’-0”

DATE: 11/10/2020

N

EXPAND IN PLACE

TELECOM

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: 9

LEVEL: BASEMENT

SCALE: 3/32” = 1’-0”

DATE: 11/10/2020

N

REMEDIATE IN PLACE

BASEMENT

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: 1 0

SCALE: 3/32” = 1’-0”

DATE: 11/10/2020

N

ABANDON

BASEMENT

SERVICE WILL BE PROVIDED BY

BUILDING 22

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: 1 1

SCALE: 3/32” = 1’-0”

DATE: 11/10/2020

N

REMEDIATE IN PLACE

B-05

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: 1 2

SCALE: 1/16” = 1’-0”

DATE: 11/10/2020

N

B11A

RELOCATE TO B11

ABANDON B11A

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

NEW TR ROOM B11

BLDG: 1 6

SCALE: 1/16” = 1’-0”

DATE: 11/10/2020

N

REMEDIATE IN PLACE

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: 2 2

SCALE: 1/16” = 1’-0”

DATE: 11/10/2020

N

REMEDIATE IN PLACE

RELOCATE THE RACK IN BLDG.

10 TO THIS LOCATION

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: 4 1

SCALE: 3/32” = 1’-0”

DATE: 11/10/2020

N

REMEDIATE IN PLACE

TELECOM/DATA

G14

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: 4 2

SCALE: 3/32” = 1’-0”

DATE: 11/10/2020

N

REMEDIATE IN PLACE

TELE

TC1

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: 2 0 0

SCALE: 1/32” = 1’-0”

DATE: 11/10/2020

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

REMEDIATE IN PLACE

CLOSET

GB-116C

LEGEND

LOCATION OF EXISTING

TR /DC

SCALE: 1/32” = 1’-0”

DATE: 11/10/2020

N

CLOSET

1A-224

RELOCATE TO 1A-113

ABANDON 1A-224

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

EXPAND IN PLACE

CLOSET

1A-113

CLOSET

1A-114

RELOCATE TO 1A-113

ABANDON 1A-114

LEGEND

LOCATION OF EXISTING

TR /DC

SCALE: 1/32” = 1’-0”

DATE: 11/10/2020

N

CLOSET

2B-101

RELOCATE TO 2A-171A

ABANDON 2B-101

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

REMEDIATE IN PLACE

COMPUTER/IT SERVER

2A-109EXPAND IN PLACE

SERVICE

2A-171A

LEGEND

LOCATION OF EXISTING

TR /DC

LEVEL: 3

SCALE: 1/32” = 1’-0”

DATE: 11/10/2020

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

REMEDIATE IN PLACE

SERVER RM.

3A-157

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: LOWER BLDG.200

LEVEL: PENTHOUSE

SCALE: 1/16” = 1’-0”

DATE: 11/10/2020

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

REMEDIATE IN PLACE

PENTHOUSE

(ER ADDITION TO BLDG. 200)

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: 2 0 3

SCALE: 1/32” = 1’-0”

DATE: 11/10/2020

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

EXPAND IN PLACE

STORE

BLDG. MGT.

BA-8

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: 2 0 3

SCALE: 1/32” = 1’-0”

DATE: 11/10/2020

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

REMEDIATE IN PLACE

CLOSET

2A-48

REMEDIATE IN PLACE

IRMS

2B-22

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: 2 0 5

LEVEL: MEZZANINE

SCALE: 3/32” = 1’-0”

DATE: 11/10/2020

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

REMEDIATE IN PLACE

IT CLOSET

M6

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: 2 0 7

SCALE: 3/32” = 1’-0”

DATE: 11/10/2020

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

REMEDIATE IN PLACE

DATA CENTER

LEGEND

LOCATION OF EXISTING

TR /DC

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

TELCO BA-114

RELOCATE TO BA-115

ABANDON BA-114

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

NEW TR LOCATION

BA-115

BLDG: 2 0 8

LEVEL: BASEMENT

SCALE: 1/16” = 1’-0”

DATE: 11/10/2020

BLDG: 2 1 0

SCALE: 3/32” = 1’-0”

DATE: 11/10/2020

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

TELECOM

G-104

RELOCATE TO 2nd FLOOR – ROOM 203

ABANDON G-104

LEGEND

LOCATION OF EXISTING

TR /DC

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

REMEDIATE IN PLACE

STORAGE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 2 1 0

LEVEL: 2

SCALE: 3/32” = 1’-0”

DATE: 11/10/2020

BLDG: 2 1 1

SCALE: 3/32” = 1’-0”

DATE: 11/10/2020

N

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

EXPAND IN PLACE

COMM EQUIP.

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: T 3 1

SCALE: 1/8” = 1’-0”

DATE: 11/10/2020

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

REMEDIATE IN PLACE

COMM

N

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: T 3 3

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

REMEDIATE IN PLACE

COMM

1 IDF

N

LEGEND

LOCATION OF EXISTING

TR /DC

BLDG: T 3 5

SCALE: 1/8” = 1’-0”

DATE: 11/10/2020

EXISTING TR LOCATION(S)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

REMEDIATE IN PLACE

COMM

G-09

(VERIFY LOCATION)

N

LEGEND

LOCATION OF EXISTING

TR /DC

N E T WO R K S PAC E D E S I G N

BLDG: 1

LEVEL: 2

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

TELE.

Building 1 Room 214

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate There is no air condition in this room.

Provide 1.5 ton ductless mini-split.

Condensing unit on roof.

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Room Temperature/Humidity Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Rack Temperature/Humidity Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to

BMS

X Missing grounding bus bar Install copper grounding bus bar

Piping over equipment Relocate piping or pipe trough X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual

X No condensate leak detection Needs condensate leak detection X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X Remote Controlled battery thermostat Wired thermostat No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual

X UPS has no communication to BMS Provide NIC to communicate to BMS

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

X Micro condensate pump Commercial condensate pump

X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 464.

Approximate total cable length = 76478'

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

Inadequate rack space for new equipment provide new rack as required.

LEVEL: 1

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

153 & 155C

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

TELECOM

REMOVE EXISTING DOOR.

INFILL OPENING

REMOVE EXISTING WALL

NEW TR ROOM

153 & 155C

122 SF

EXISTING TELECOM ROOM

TO BE USED AS A CHASE.

EXISTING TELECOM ROOMS

TC-G20 & 120 TO BE SERVED BY

ROOM 153 & 155C

Building 2 Room 153 & 155C

C O

O

LI

N G

"X" EXISTING ISSUES

RECOMMENDED

SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate

Needs dedicated HVAC unit.

Provide 1.5 ton ductless mini-split. Condensing unit on grade.

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Room Temperature/Humidity Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual

Piping over equipment Relocate piping or install pipe trough with floor tape-type leak detector

X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X No condensate leak detection

Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual

X Remote Controlled battery thermostat Wired thermostat

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

X UPS has no communication to BMS

Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 90.

Approximate total cable length = 14850'

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed

292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

X Inadequate rack space for new

LEVEL: 3

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

355 & 355D

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

TEL

TC-320

REMOVE PORTION OF

EXISTING WALL

INSTALL NEW 3’ DOOR

NEW WALL

EXISTING TELECOM ROOM

TO BE USED AS A CHASE.

NEW TR ROOM

355 & 355D

162 SF

EXISTING TELECOM ROOMS

TC-220 & TC-320 TO BE SERVED BY

ROOM 355 & 355D

Building 2 Room 355 & 355 D

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate

Provide TAB report to verify if additional air can be provided else provide 2-ton Liebert indoor condensing unit and fan coil.

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual

Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X No condensate leak detection Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual

X Remote Controlled battery thermostat Wired thermostat

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

X UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 90.

Approximate total cable length = 14850'

Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

LEVEL: 4

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

TC-420 RELOCATING TO ROOM 453

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

NEW TR ROOM 453

78 SF

Building 2 Room 453

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Provide 1.5 ton ductless mini-split.

Condensing unit on roof.

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual

Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X No condensate leak detection Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual

X Remote Controlled battery thermostat Wired thermostat

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

X UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 90.

Approximate total cable length = 14850'

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

LEVEL: 5

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

TC-520 RELOCATING TO ROOM 553

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

NEW TR ROOM

80 SF

Building 2 Room 553

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Provide 1.5 ton ductless mini-split.

Condensing unit on roof.

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual

Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X No condensate leak detection Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual

X Remote Controlled battery thermostat Wired thermostat

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

X UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 90.

Approximate total cable length = 14850'

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

REMOVE PORTION OF

EXISTING WALL.

INSTALL NEW DOOR

BLDG: 6

LEVEL: 2

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

209K

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

NEW TR ROOM

209K

123 SF

EXISTING TELECOM ROOMS

113 & 207 TO BE SERVED BY

ROOM 209K

REMOVE EXISTING DOOR.

INFILL DOOR OPENING

Building 6 Room 209K

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Provide 1.5 ton ductless mini-split.

Condensing unit on roof or grade.

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual

Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X No condensate leak detection Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual

X Remote Controlled battery thermostat Wired thermostat

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

X UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 288.

Approximate total cable length = 47520'

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

NEW TR

ROOM

BLDG: 7

LEVEL: 1

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

EXISTING TELECOM ROOM

107 TO BE RELOCATED TO NEW TR ROOM 106

Building 7 Room 106

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Provide 1.5 ton ductless mini-split.

Condensing unit on grade.

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual

Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X No condensate leak detection Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual

X Remote Controlled battery thermostat Wired thermostat

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

X UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 90 Approximate total cable length = 14850'

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

REMOVE EXISTING WALL.

EXPAND ROOM SOUTH

INTO ADJOINING OFFICE

NEW WALL

APPROX. SIZE

7’-10” x 10’-0”

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

TELECOM

76 SF

BLDG: 8

LEVEL: 2

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

Building 8 Room 216

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate There is no air condition in this room.

Provide 1.5 ton ductless mini-split.

Condensing unit on grade or roof.

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual

Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X No condensate leak detection Needs condensate leak detection No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual

X Remote Controlled battery thermostat Wired thermostat

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 369.

Approximate total cable length = 60761'

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

BASEMENT

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

BLDG: 9

LEVEL: BASEMENT

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

BASEMENT

BLDG. 9

TELECOM LOCATED ON

WALL IN OPEN AREA

NOTE: CONSIDER ENCLOSURE OF RACK TO

PROTECT FROM WATER.

TROUGH REQUIRED

Building 9 Basement

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Provide additional air conditioning

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual

X Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X No condensate leak detection Needs condensate leak detection No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual

Remote Controlled battery thermostat Wired thermostat

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 32.

Approximate total cable length = 5198'

Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

B05

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

STORAGE

B05

BLDG: 11

LEVEL: BASEMENT

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

LOCATION OF OPEN RACK NEEDS TO BE VERIFIED.

REQUIRES NEW TROUGH

REQUIRES REORGANIZATION

Building 11 Basement

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate There is no air condition in this room

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual

X Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X No condensate leak detection Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual

Remote Controlled battery thermostat Wired thermostat

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

UPS has no communication to BMS Provide NIC to communicate to BMS Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 80.

Approximate total cable length = 13118'

Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

B11

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

NEW TR ROOM

B11

BLDG: 12

LEVEL: BASEMENT

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

REMOVE PORTION OF

EXISTING WALL AND

WING WALL. INSTALL

NEW DOOR

INFILL EXISTING

OPENING

NOTE: CONVERT TO FULL RACK OR ADD AN ADDITIONAL RACK

Building 12 Room B11

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Provide 1.5 ton ductless mini-split.

Condensing unit on grade.

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual

X Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X No condensate leak detection Needs condensate leak detection No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual

X Remote Controlled battery thermostat Wired thermostat

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

X UPS has no communication to BMS Provide NIC to communicate to BMS Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 323 Approximate total cable length = 53213'

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

TELCO

BLDG: 16

LEVEL: 1

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

Building 16 Room 11

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Provide 1.5 ton ductless mini-split.

Condensing unit on grade.

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual

Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X No condensate leak detection Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual

X Remote Controlled battery thermostat Wired thermostat

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 18.

Approximate total cable length = 2970'

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

ELEC.

BLDG: 22

LEVEL: 1

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

Building 22 Room 103

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Provide 1.5 ton ductless mini-split.

Condensing unit on grade.

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to

BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual

Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X No condensate leak detection Needs condensate leak detection No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual

X Remote Controlled battery thermostat Wired thermostat

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

UPS has no communication to BMS Provide NIC to communicate to BMS Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 15.

Approximate total cable length = 2352'

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

G14

VA SAN FRANCISCO HEALTHCARE SYSTEM

SAN FRANCISCO VAMC

TELECOM/DATA

G14

BLDG: 41

LEVEL: 1

SCALE: 1/4” = 1’-0”

DATE: 11/10/2020

REMOVE PORTION OF

EXISTING WALL AND

INSTALL NEW 3’ DOOR

RELOCATE EXISTING

DOOR. INFILL

OPENING

NOTE: TROUGH REQUIRED (UNDER CHILLED WATER LINE)

Building 41 Room G14

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Room was warm. Provide maintenance on existing fan coil unit.

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity Monitoring Inadequate

Provide one (1) temperature and humidity sensor per rack; connect to

BMS

Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA…