Attachment 7 - VASFHCS EHRM Project Manual Updated 3-4-21 No CBOCs.pdf
PDF 3 MB Posted
- Attached to
- Y1BG--EHRM Infrastructure Upgrades Design-Build San Francisco, CA - Project # 662-20-700
- Solicitation number
- 36C77621R0105
About this file
This notice provides information about an upcoming federal contract opportunity for Electronic Health Records Modernization infrastructure upgrades at the San Francisco VA Medical Center.
The Department of Veterans Affairs intends to solicit proposals and award a single firm-fixed-price design-build contract to provide all labor, materials, and services necessary to relocate or remodel approximately 50 telecommunications rooms and one data center. The project scope involves bringing the spaces up to VA Office of Information and Technology and EHRM infrastructure standards while maintaining IT service continuity. The design-build contractor will deliver a turnkey project in accordance with applicable standards.
The solicitation will be conducted as a two-phase design-build selection and issued in July 2021 as a total SDVOSB set-aside. The contract value is estimated between $10-20 million. The period of performance is approximately 540 calendar days from notice to proceed. Questions must be submitted in writing by the specified date.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VISN 21 CM/PM Electronic Health Records Modernization (EHRM) PHASE I Support Task
PO# 612C209
San Francisco Health Care System San Francisco VA Medical Center
Ta b l e o f C o n t e n t s
Project TeamContributors
Vicinity Map/Building Addresses
Campus Map / Building Information
Placeholder - VAMC Fiber Distances Placeholder - VAMC Fiber Distances Door Security Requirements
San Francisco VAMC - Bldg. 1 Second Floor Plan
San Francisco VAMC - Bldg. 2 Ground Floor Plan First Floor Plan Second Floor Plan Third Floor Plan Fourth Floor Plan Fifth Floor Plan
San Francisco VAMC - Bldg. 6 First Floor Plan Second Floor Plan
San Francisco VAMC – Bldg. 7 First Floor Plan
San Francisco VAMC – Bldg. 8 Second Floor Plan
San Francisco VAMC – Bldg. 9 Basement
San Francisco VAMC – Bldg. 10 Basement
San Francisco VAMC – Bldg. 11 Basement
San Francisco VAMC – Bldg. 12 Basement
Identification of Network Spaces
Network Spaces: (cont’d)
San Francisco VAMC – Bldg. 16 First Floor Plan
San Francisco VAMC – Bldg. 22 First Floor Plan
San Francisco VAMC – Bldg. 41 Ground Floor
San Francisco VAMC – Bldg. 42 First Floor Plan
San Francisco VAMC – Bldg. 200 Ground Floor Plan First Floor Plan Second Floor Plan Third Floor Plan Lower Roof - Penthouse
San Francisco VAMC – Bldg. 203 Basement Second Floor Plan
San Francisco VAMC – Bldg. 205 Mezzanine
San Francisco VAMC – Bldg. 207 Ground Floor Plan
San Francisco VAMC – Bldg. 208 Basement
San Francisco VAMC – Bldg. 210 Ground Floor Plan Second Floor Plan
San Francisco VAMC – Bldg. 211 First Floor Plan
San Francisco VAMC – T31 First Floor Plan
San Francisco VAMC – T33 First Floor Plan
Ta b l e o f C o n t e n t s
San Francisco VAMC – T35 First Floor Plan
Sheet Removed
Network Space Design: 59
Bldg. 1:
Design Matrix Enlarged Plan – Existing
Bldg. 2:
153 & 155C Design Matrix Enlarged Plan - Existing
Bldg. 2:
355 & 355D Design Matrix Enlarged Plan - Existing
Bldg. 2:
Design Matrix Enlarged Plan - Existing
Bldg. 2:
Design Matrix Enlarged Plan – Existing
Bldg. 6:
209K Design Matrix Enlarged Plan – Existing
Bldg. 7:
Design Matrix Enlarged Plan - Existing
Bldg. 8:
Design Matrix Enlarged Plan – Existing
Bldg. 9:
Basement Design Matrix Enlarged Plan – Existing
Sheet Removed
Sheet Removed
Sheet Removed
Sheet Removed
Sheet Removed
Sheet Removed
Sheet Removed
Sheet Removed
Sheet Removed
Bldg. 11:
B05 Design Matrix Enlarged Plan – Existing
Bldg. 12:
B11 Design Matrix Enlarged Plan – Existing
Bldg. 16:
Design Matrix Enlarged Plan - Existing
Bldg. 22:
Design Matrix Enlarged Plan - Existing
Bldg. 41:
G14 Design Matrix Enlarged Plan - Existing
Bldg. 42:
TC-1
Design Matrix Enlarged Plan – Existing
Bldg. 200:
GB-116C
Design Matrix Enlarged Plan - Existing
Bldg. 200:
1A-113 Design Matrix Enlarged Plan – Existing
Bldg. 200:
2A-109 Design Matrix Enlarged Plan – Existing
Bldg. 200:
2A-171A Design Matrix Enlarged Plan – Existing
Bldg. 200:
3A-157 Design Matrix Enlarged Plan – Existing
Bldg. 200:
Penthouse Design Matrix Enlarged Plan – Existing
Bldg. 203:
BA-8
Design Matrix Enlarged Plan - Existing
Bldg. 203:
2A-48 Design Matrix Enlarged Plan - Existing
Bldg. 203:
2B-22 Design Matrix Enlarged Plan - Existing
Bldg. 205:
M6 Design Matrix Enlarged Plan - Existing
Bldg. 207:
Design Matrix Enlarged Plan - Existing
Bldg. 208:
BA-115
Design Matrix Enlarged Plan – Existing
Network Space Design (cont’d)
Ta b l e o f C o n t e n t s
Network Space Design (cont’d)
Bldg. 210:
Design Matrix Enlarged Plan – Existing
Bldg. 211:
106A Design Matrix Enlarged Plan – Existing
Bldg. T31:
Design Matrix Enlarged Plan - Existing
Bldg. T33:
IDF
Design Matrix Enlarged Plan – Existing
Bldg. T35:
G09 Design Matrix Enlarged Plan – N/A
Sheet Removed
Ta b l e o f C o n t e n t s
89 99
Network Space Design (cont’d): 97
Appendix A – Power Installation Example
Appendix B – Compliance Requirements
Appendix C – Rack Labeling Standard
Appendix
Sheet Removed
Sheet Removed
Sheet Removed
Sheet Removed
Sheet Removed
Sheet Removed
Sheet Removed
Sheet Removed
P R O J E C T C O N TA C T D I R E C T O R Y
Concourse Federal Group 123 S. Royal Street Alexandria, Virginia 22314
Tim Hower, Project Manager .........................................................................................thower@concousefederal.com Lorena Alvarez.................................................................................................................IaIvarez@concousefederaI.com Mike Olson .................................................................................................................... molson@concousefederal.com Marshall Contino, Concourse A|E Vice President ........................................................ mcontino@concousefederal.com
DHE Engineering 3300 N. Central Ave. 3300 Tower Suite, 1520, Phoenix, AZ 85012
Rick Seger P.E., Principal, Electrical Engineer................................................................rseger@dheeng.com Kory Young, EIT, Senior Mechanical Engineer.................................................................kyoung@dheeng.com
VA San Francisco Health Care System
Matt Szeto, Chief, Capital Planning and Development................................................. Matthew.Szeto@va.gov Kailen Collette……………………….….................................................................................... Kailen.Collette2@va.gov
V i c i n i t y M a p B u i l d i n g A d d r e s s S a n F r a n c i s c o V A M e d i c a l C e n t e r ( V A M C ) 4 1 5 0 C l e m e n t S t r e e t S a n F r a n c i s c o , C A 9 4 1 2 1
B u i l d i n g I n f o r m a t i o n Bldg. # Bldg. Name TR Qty Levels
1 AUDIOLOGY/MENTAL HEALTH CLINIC 1 5
2 ADMINISTRATION/LABORATORY 4 7
6 A&MMS/LIBRARY/FISCAL/RESEARCH 2 4
7 CANTEEN/CHAPEL/AUDITORIUM 1 5
8 MENTAL HEALTH/RESEARCH 1 4
9 HOPTEL 1 3
10 HOPTEL 0 3
11 MENTAL HEALTH/RESEARCH 1 3
12 RESEARCH 1 3
16 RESEARCH 1 1
22 HOPTEL 1 3
41 VMU 1 2
42 RESEARCH 1 1
200 AMBULATORY CARE CLINIC 6 5
203 HOSPITAL (A & B WING) 3 5
205 ENERGY CENTER 1 2
208 COMMUNITY LIVING CENTER 1 3
210 HOSPITAL ADMINISTRATION 1 3
211 PARKING GARAGE 1 4
T31 SAFETY BUILDING 1 1
T33 PSYCHIATRY BLDG. 1 1
T35 CHILD CARE CENTER 1 1
Bldg. # Bldg. Name Data Ctr Levels
207 ADMINISTRATION 1 1
C a m p u s M a p
VAMC FIBER DISTANCES
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANSISCO VAMC
VAMC San Francisco Division
Building Floor Room Distance From Exisitng Server Room (Ft.) Notes Fiber type Conduit Type
207 1 107A N/A Server Room 24 strand single mode Interior - 4" EMT
1 2 214 300 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
2 5 TC-520 250 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
2 4 TC-420 400 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
2 3 TC-320 270 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
2 2 TC-220 250 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
2 1 TC-120 225 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
2 G TC-G20 200 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
6 1 113 600 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
6 2 207 625 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
7 1 107 400 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
8 2 216 480 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
9 B BASEMENT 610 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
10 B BASEMENT 750 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
11 B B05 900 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
12 B B11 690 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
16 1 11 1300 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
22 1 103 650 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
41 G G14 670 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
42 1 TC1 1100 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
CREATE REDUNDANT WAN PATH – ASSUME 1000’-0”
CONCRETE ENCASED 4” PVC OR HDPE WITH (4) 1” INTERDUCTS.
VAMC FIBER DISTANCES
SAN FRANSISCO VAMC
VAMC San Francisco Division
Building Floor Room Distance From Existing Server Room (Ft.)
Notes Fiber type Conduit Type
200 3 3A157 360 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
200 2 2B101 340 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
200 2 2A171 340 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
200 2 2A109A 340 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
200 2 1A224 320 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
200 ROOF PENTHOUSE 360 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
200 G GB116C 340 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
200 1 1A114 320 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
200 1 1A-113 320 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
200 1 1A-224 320 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
203 2 A SIDE 2A-48 645 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
203 2 B SIDE 2B-22 645 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
203 B BA8 625 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
205 1 M6 860 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
208 B BA114 1120 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
210 G GA4 390 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
210 2 203 410 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
211 1 106A 1100 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
T27 1 RESTROOM 750 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
T31 1 105 350 25 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
T33 1 1 IDF 650 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
T35 1 1-103 820 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
T28 1 800 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT
DOOR SECURITY REQUIREMENTS
SAN FRANSISCO VAMC
I D E N T I F I C AT I O N O F N E T WO R K S PAC E S
BLDG: 1
LEVEL: 2
SCALE: 1/16” = 1’-0”
DATE: 11/10/2020
N
REMEDIATE IN PLACE
TELE
ROOM 214
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANSISCO VAMC
BLDG: 2
LEVEL: GROUND FLOOR
SCALE: 1/32” = 1’-0”
DATE: 11/10/2020
N
ABANDON TELECOM
ROOM TC-G20
RELOCATE TO NEW TR
ROOM 153 & 155C
GROUND FLOOR TO BE
SERVED BY 1st FLOOR
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
LEVEL: 1
SCALE: 1/32” = 1’-0”
DATE: 11/10/2020
N
ROOM 120
RELOCATE TO 153 & 155C
EXISTING CLOSET WILL SERVE AS A CHASE
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
NEW TR ROOM 153 & 155C
THIS TR TO SERVE GROUND FLOOR
AND 1st FLOOR
SCALE: 1/32” = 1’-0”
DATE: 11/10/2020
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
ROOM TC-220
RELOCATE TO ROOM 355 & 355D
EXISTING CLOSET WILL SERVE AS A CHASE
LEVEL: 3
SCALE: 1/32” = 1’-0”
DATE: 11/10/2020
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
NEW TR ROOM 355 & 355D
TR TO SERVE 2nd AND 3rd FLOOR
ROOM TC-320
RELOCATE TO ROOM 355 & 355D
EXISTING CLOSET WILL SERVE AS A CHASE
LEVEL: 4
SCALE: 1/32” = 1’-0”
DATE: 11/10/2020
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
ROOM TC-420
RELOCATE TO NEW TR ROOM 453
ABANDON EXISTING CLOSET
NEW TR ROOM 453
TR TO SERVE 4th FLOOR ONLY
LEVEL: 5
SCALE: 1/32” = 1’-0”
DATE: 11/10/2020
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
ROOM TC-520
RELOCATE TO NEW TR ROOM 553
ABANDON EXISTING TELECOM ROOM TC-520
NEW TR ROOM 553
TR TO SERVE 5th FLOOR ONLY
BLDG: 6
SCALE: 1/16” = 1’-0”
DATE: 11/10/2020
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
SWITCHBOARD
ROOM 113
RELOCATE TO NEW TR ROOM 209K
ABANDON ROOM 113
BLDG: 6
SCALE: 1/16” = 1’-0”
DATE: 11/10/2020
N
TELECOM
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
NEW TR ROOM 209K
RELOCATE TO NEW TR ROOM 209K
ABANDON ROOM 207
BLDG: 7
SCALE: 1/16” = 1’-0”
DATE: 11/10/2020
N
STOR.
RELOCATE TO ROOM 106
ABANDON 107
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
NEW TR ROOM 106
BLDG: 8
SCALE: 1/16” = 1’-0”
DATE: 11/10/2020
N
EXPAND IN PLACE
TELECOM
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: 9
LEVEL: BASEMENT
SCALE: 3/32” = 1’-0”
DATE: 11/10/2020
N
REMEDIATE IN PLACE
BASEMENT
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: 1 0
SCALE: 3/32” = 1’-0”
DATE: 11/10/2020
N
ABANDON
BASEMENT
SERVICE WILL BE PROVIDED BY
BUILDING 22
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: 1 1
SCALE: 3/32” = 1’-0”
DATE: 11/10/2020
N
REMEDIATE IN PLACE
B-05
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: 1 2
SCALE: 1/16” = 1’-0”
DATE: 11/10/2020
N
B11A
RELOCATE TO B11
ABANDON B11A
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
NEW TR ROOM B11
BLDG: 1 6
SCALE: 1/16” = 1’-0”
DATE: 11/10/2020
N
REMEDIATE IN PLACE
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: 2 2
SCALE: 1/16” = 1’-0”
DATE: 11/10/2020
N
REMEDIATE IN PLACE
RELOCATE THE RACK IN BLDG.
10 TO THIS LOCATION
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: 4 1
SCALE: 3/32” = 1’-0”
DATE: 11/10/2020
N
REMEDIATE IN PLACE
TELECOM/DATA
G14
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: 4 2
SCALE: 3/32” = 1’-0”
DATE: 11/10/2020
N
REMEDIATE IN PLACE
TELE
TC1
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: 2 0 0
SCALE: 1/32” = 1’-0”
DATE: 11/10/2020
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
REMEDIATE IN PLACE
CLOSET
GB-116C
LEGEND
LOCATION OF EXISTING
TR /DC
SCALE: 1/32” = 1’-0”
DATE: 11/10/2020
N
CLOSET
1A-224
RELOCATE TO 1A-113
ABANDON 1A-224
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
EXPAND IN PLACE
CLOSET
1A-113
CLOSET
1A-114
RELOCATE TO 1A-113
ABANDON 1A-114
LEGEND
LOCATION OF EXISTING
TR /DC
SCALE: 1/32” = 1’-0”
DATE: 11/10/2020
N
CLOSET
2B-101
RELOCATE TO 2A-171A
ABANDON 2B-101
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
REMEDIATE IN PLACE
COMPUTER/IT SERVER
2A-109EXPAND IN PLACE
SERVICE
2A-171A
LEGEND
LOCATION OF EXISTING
TR /DC
LEVEL: 3
SCALE: 1/32” = 1’-0”
DATE: 11/10/2020
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
REMEDIATE IN PLACE
SERVER RM.
3A-157
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: LOWER BLDG.200
LEVEL: PENTHOUSE
SCALE: 1/16” = 1’-0”
DATE: 11/10/2020
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
REMEDIATE IN PLACE
PENTHOUSE
(ER ADDITION TO BLDG. 200)
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: 2 0 3
SCALE: 1/32” = 1’-0”
DATE: 11/10/2020
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
EXPAND IN PLACE
STORE
BLDG. MGT.
BA-8
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: 2 0 3
SCALE: 1/32” = 1’-0”
DATE: 11/10/2020
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
REMEDIATE IN PLACE
CLOSET
2A-48
REMEDIATE IN PLACE
IRMS
2B-22
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: 2 0 5
LEVEL: MEZZANINE
SCALE: 3/32” = 1’-0”
DATE: 11/10/2020
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
REMEDIATE IN PLACE
IT CLOSET
M6
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: 2 0 7
SCALE: 3/32” = 1’-0”
DATE: 11/10/2020
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
REMEDIATE IN PLACE
DATA CENTER
LEGEND
LOCATION OF EXISTING
TR /DC
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
TELCO BA-114
RELOCATE TO BA-115
ABANDON BA-114
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
NEW TR LOCATION
BA-115
BLDG: 2 0 8
LEVEL: BASEMENT
SCALE: 1/16” = 1’-0”
DATE: 11/10/2020
BLDG: 2 1 0
SCALE: 3/32” = 1’-0”
DATE: 11/10/2020
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
TELECOM
G-104
RELOCATE TO 2nd FLOOR – ROOM 203
ABANDON G-104
LEGEND
LOCATION OF EXISTING
TR /DC
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
REMEDIATE IN PLACE
STORAGE
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 2 1 0
LEVEL: 2
SCALE: 3/32” = 1’-0”
DATE: 11/10/2020
BLDG: 2 1 1
SCALE: 3/32” = 1’-0”
DATE: 11/10/2020
N
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
EXPAND IN PLACE
COMM EQUIP.
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: T 3 1
SCALE: 1/8” = 1’-0”
DATE: 11/10/2020
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
REMEDIATE IN PLACE
COMM
N
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: T 3 3
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
REMEDIATE IN PLACE
COMM
1 IDF
N
LEGEND
LOCATION OF EXISTING
TR /DC
BLDG: T 3 5
SCALE: 1/8” = 1’-0”
DATE: 11/10/2020
EXISTING TR LOCATION(S)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
REMEDIATE IN PLACE
COMM
G-09
(VERIFY LOCATION)
N
LEGEND
LOCATION OF EXISTING
TR /DC
N E T WO R K S PAC E D E S I G N
BLDG: 1
LEVEL: 2
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
TELE.
Building 1 Room 214
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate There is no air condition in this room.
Provide 1.5 ton ductless mini-split.
Condensing unit on roof.
X Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Room Temperature/Humidity Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Rack Temperature/Humidity Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to
BMS
X Missing grounding bus bar Install copper grounding bus bar
Piping over equipment Relocate piping or pipe trough X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual
X No condensate leak detection Needs condensate leak detection X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X Remote Controlled battery thermostat Wired thermostat No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual
X UPS has no communication to BMS Provide NIC to communicate to BMS
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
X Micro condensate pump Commercial condensate pump
X Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 464.
Approximate total cable length = 76478'
X Horizontal cable run not to exceed 292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
Inadequate rack space for new equipment provide new rack as required.
LEVEL: 1
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
153 & 155C
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
TELECOM
REMOVE EXISTING DOOR.
INFILL OPENING
REMOVE EXISTING WALL
NEW TR ROOM
153 & 155C
122 SF
EXISTING TELECOM ROOM
TO BE USED AS A CHASE.
EXISTING TELECOM ROOMS
TC-G20 & 120 TO BE SERVED BY
ROOM 153 & 155C
Building 2 Room 153 & 155C
C O
O
LI
N G
"X" EXISTING ISSUES
RECOMMENDED
SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate
Needs dedicated HVAC unit.
Provide 1.5 ton ductless mini-split. Condensing unit on grade.
X Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Room Temperature/Humidity Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual
Piping over equipment Relocate piping or install pipe trough with floor tape-type leak detector
X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X No condensate leak detection
Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual
X Remote Controlled battery thermostat Wired thermostat
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
X UPS has no communication to BMS
Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 90.
Approximate total cable length = 14850'
X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed
292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
X Inadequate rack space for new
LEVEL: 3
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
355 & 355D
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
TEL
TC-320
REMOVE PORTION OF
EXISTING WALL
INSTALL NEW 3’ DOOR
NEW WALL
EXISTING TELECOM ROOM
TO BE USED AS A CHASE.
NEW TR ROOM
355 & 355D
162 SF
EXISTING TELECOM ROOMS
TC-220 & TC-320 TO BE SERVED BY
ROOM 355 & 355D
Building 2 Room 355 & 355 D
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate
Provide TAB report to verify if additional air can be provided else provide 2-ton Liebert indoor condensing unit and fan coil.
X Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to
BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual
Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X No condensate leak detection Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual
X Remote Controlled battery thermostat Wired thermostat
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
X UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 90.
Approximate total cable length = 14850'
Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
LEVEL: 4
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
TC-420 RELOCATING TO ROOM 453
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
NEW TR ROOM 453
78 SF
Building 2 Room 453
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate Provide 1.5 ton ductless mini-split.
Condensing unit on roof.
X Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to
BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual
Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X No condensate leak detection Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual
X Remote Controlled battery thermostat Wired thermostat
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
X UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 90.
Approximate total cable length = 14850'
X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
LEVEL: 5
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
TC-520 RELOCATING TO ROOM 553
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
NEW TR ROOM
80 SF
Building 2 Room 553
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate Provide 1.5 ton ductless mini-split.
Condensing unit on roof.
X Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to
BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual
Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X No condensate leak detection Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual
X Remote Controlled battery thermostat Wired thermostat
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
X UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 90.
Approximate total cable length = 14850'
X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
REMOVE PORTION OF
EXISTING WALL.
INSTALL NEW DOOR
BLDG: 6
LEVEL: 2
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
209K
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
NEW TR ROOM
209K
123 SF
EXISTING TELECOM ROOMS
113 & 207 TO BE SERVED BY
ROOM 209K
REMOVE EXISTING DOOR.
INFILL DOOR OPENING
Building 6 Room 209K
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate Provide 1.5 ton ductless mini-split.
Condensing unit on roof or grade.
X Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to
BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual
Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X No condensate leak detection Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual
X Remote Controlled battery thermostat Wired thermostat
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
X UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 288.
Approximate total cable length = 47520'
X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
NEW TR
ROOM
BLDG: 7
LEVEL: 1
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
EXISTING TELECOM ROOM
107 TO BE RELOCATED TO NEW TR ROOM 106
Building 7 Room 106
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate Provide 1.5 ton ductless mini-split.
Condensing unit on grade.
X Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to
BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual
Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X No condensate leak detection Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual
X Remote Controlled battery thermostat Wired thermostat
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
X UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 90 Approximate total cable length = 14850'
X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
REMOVE EXISTING WALL.
EXPAND ROOM SOUTH
INTO ADJOINING OFFICE
NEW WALL
APPROX. SIZE
7’-10” x 10’-0”
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
TELECOM
76 SF
BLDG: 8
LEVEL: 2
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
Building 8 Room 216
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate There is no air condition in this room.
Provide 1.5 ton ductless mini-split.
Condensing unit on grade or roof.
Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to
BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual
Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X No condensate leak detection Needs condensate leak detection No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual
X Remote Controlled battery thermostat Wired thermostat
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 369.
Approximate total cable length = 60761'
X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
BASEMENT
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
BLDG: 9
LEVEL: BASEMENT
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
BASEMENT
BLDG. 9
TELECOM LOCATED ON
WALL IN OPEN AREA
NOTE: CONSIDER ENCLOSURE OF RACK TO
PROTECT FROM WATER.
TROUGH REQUIRED
Building 9 Basement
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
Cooling inadequate Provide additional air conditioning
Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to
BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual
X Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X No condensate leak detection Needs condensate leak detection No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual
Remote Controlled battery thermostat Wired thermostat
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 32.
Approximate total cable length = 5198'
Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
B05
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
STORAGE
B05
BLDG: 11
LEVEL: BASEMENT
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
LOCATION OF OPEN RACK NEEDS TO BE VERIFIED.
REQUIRES NEW TROUGH
REQUIRES REORGANIZATION
Building 11 Basement
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
Cooling inadequate There is no air condition in this room
Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to
BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual
X Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X No condensate leak detection Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual
Remote Controlled battery thermostat Wired thermostat
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
UPS has no communication to BMS Provide NIC to communicate to BMS Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 80.
Approximate total cable length = 13118'
Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
B11
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
NEW TR ROOM
B11
BLDG: 12
LEVEL: BASEMENT
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
REMOVE PORTION OF
EXISTING WALL AND
WING WALL. INSTALL
NEW DOOR
INFILL EXISTING
OPENING
NOTE: CONVERT TO FULL RACK OR ADD AN ADDITIONAL RACK
Building 12 Room B11
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate Provide 1.5 ton ductless mini-split.
Condensing unit on grade.
Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to
BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual
X Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X No condensate leak detection Needs condensate leak detection No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual
X Remote Controlled battery thermostat Wired thermostat
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
X UPS has no communication to BMS Provide NIC to communicate to BMS Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 323 Approximate total cable length = 53213'
X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
TELCO
BLDG: 16
LEVEL: 1
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
Building 16 Room 11
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate Provide 1.5 ton ductless mini-split.
Condensing unit on grade.
X Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to
BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual
Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X No condensate leak detection Needs condensate leak detection X No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual
X Remote Controlled battery thermostat Wired thermostat
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
UPS has no communication to BMS Provide NIC to communicate to BMS X Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 18.
Approximate total cable length = 2970'
X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
ELEC.
BLDG: 22
LEVEL: 1
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
Building 22 Room 103
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate Provide 1.5 ton ductless mini-split.
Condensing unit on grade.
Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to
BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special Telecommunications Systems Design Manual
Piping over equipment Relocate piping or pipe trough X TR ground bar not connected to Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X No condensate leak detection Needs condensate leak detection No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications Systems Design Manual
X Remote Controlled battery thermostat Wired thermostat
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
UPS has no communication to BMS Provide NIC to communicate to BMS Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 15.
Approximate total cable length = 2352'
X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed 292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
G14
VA SAN FRANCISCO HEALTHCARE SYSTEM
SAN FRANCISCO VAMC
TELECOM/DATA
G14
BLDG: 41
LEVEL: 1
SCALE: 1/4” = 1’-0”
DATE: 11/10/2020
REMOVE PORTION OF
EXISTING WALL AND
INSTALL NEW 3’ DOOR
RELOCATE EXISTING
DOOR. INFILL
OPENING
NOTE: TROUGH REQUIRED (UNDER CHILLED WATER LINE)
Building 41 Room G14
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate Room was warm. Provide maintenance on existing fan coil unit.
Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21- 30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS
Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity Monitoring Inadequate
Provide one (1) temperature and humidity sensor per rack; connect to
BMS
Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA…