This document is a Focus Asbestos Survey report for Building 560 at Pope Air Force Base in North Carolina, prepared by Ayuda Management Corporation for the Directorate of Public Works. The survey was conducted on August 21, 2025, to support a project to install electrical and fiber optic lines (Project Number P2-00009-25). The building is a two-story brick structure approximately 181,150 square feet, constructed in 1990, and currently used by the 14 ASOS and 18 Weather Squadron.

The comprehensive asbestos inspection involved visual examination and sampling of suspect asbestos-containing materials (ACM) by a North Carolina-accredited inspector. Bulk samples were collected and analyzed by a NVLAP certified laboratory. Critically, the survey concluded that no asbestos-containing materials were detected in thermal system insulation, miscellaneous materials, or surfacing materials tested. The report includes detailed floor plans showing sample locations, chain of custody documentation, photographs of sampled materials, and provides explicit "Do and Don't" guidelines for handling potential asbestos-containing materials during future renovation or maintenance activities.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Focus Asbestos Survey to Install Electrical and Fiber Optic Lines

Building 560 Fort Bragg, North Carolina

Prepared by Bruce E. Billings, Ayuda Management Corporation For the Directorate of Public Works, Fort Bragg, North Carolina

Building 560 was inspected for asbestos by Bruce Billings, Inspector certification number: NC12397 on August 21, 2025.

Introduction

Scope of the Investigation

This report documents the focused asbestos inspection and survey of Building 560 at Fort Bragg, North Carolina for project number P2-00009-25. The work description is detailed in the Facilities Engineering Work Request DA Form 4283 and is attached in this report. The work is to install power and fiber optic communication lines in Building 560 workstations.

Background

Building 560 is a two story brick structure with a flat EPDM roof. Ceilings are suspended with ceiling tiles attached in hallways and rooms. Bathroom ceilings are sheetrock. The floor system is concrete throughout the building and is covered with 12” x 12” inch vinyl floor tiles with ceramic tiles in bathrooms. Building 560 is currently used as the 14 ASOS and 18 Weather Squadron building. Building 560 is approximately 181,150 square feet and was constructed in 1990.

Description of study

Investigation

Building 560 was visually inspected for suspected asbestos containing materials (ACM) by a North Carolina accredited inspector. Bulk samples of all suspect ACM’s were collected. This report details ACM as identified at the time of inspection only. Samples of materials to be disturbed during the course of work to be performed were taken and sent to a NVLAP certified laboratory for analysis. The approximate location where asbestos containing bulk sample were obtained are shown on the building floor plan included in this report. However, if suspect materials are discovered during renovation in concealed spaces, renovation activities should stop and the materials sampled by a North Carolina accredited asbestos inspector.

In compliance with the AHERA regulations, material is considered an Asbestos Containing Material (ACM) when it contains greater than one percent asbestos. Likewise, in this report, any material containing concentrations greater than one percent asbestos will be considered “positive”. Occasionally, materials containing less than one percent asbestos, or not sampled, are assumed to be a “positive” asbestos containing material at the discretion of the inspectors. A narrative discussion of the AHERA ACM types (i.e., thermal systems insulation, miscellaneous and surfacing materials) found in the building is included in this report where relevant. Bulk sample information appears, estimated quantities of individual asbestos containing materials, material characterization of asbestos containing materials appears on the Asbestos Table.

Conclusions

Thermal System Insulation

TSI is insulation material applied to pipes, fittings, tanks, ducts, or on other interior structural components to prevent heat loss or gain, or water condensation, or for other purposes. Asbestos was not detected in the TSI materials sampled in Building 560 at the time of sampling.

Miscellaneous Materials

Miscellaneous materials include building material on structural components, structural members or fixtures, such as floor and ceiling tiles, and do not include surfacing or TSI. Asbestos was not detected in the miscellaneous materials sampled in Building 560 at the time of the sampling.

Surfacing

Surfacing material is friable material that is sprayed on, troweled on, or otherwise applied to surfaces for decorative or other purposes. Asbestos was not detected in the surfacing material sampled in Building 560 at the time of sampling.

ASBESTOS-CONTAINING MATERIAL WAS NOT DETECTED.

Analytical Report

Chain of Custody

Sample Locations

NOT TO SCALE

DA Form 4283

Photos of Sampled Materials

Accreditations

Focus Asbestos Survey to Install Electrical and Fiber Optic Lines
Building 560 Fort Bragg, North Carolina
Introduction
Scope of the Investigation
Investigation
Conclusions
Miscellaneous Materials
Surfacing

File details come from the government source that posted it. Updated .