This document contains a solicitation for a requirements-type contract to purchase mobile electric power plants. The United States Coast Guard is seeking to award a firm fixed price contract, consisting of a one-year base period and four one-year options, for the supply of mobile electric power plants or equivalent alternatives. The solicitation is set aside for small businesses with less than 1,250 employees. The technical specifications attached as an appendix describe the required power, fuel capacity, enclosure, and other features of the mobile electric power plants. Offers are due by July 13, 2020, and award is anticipated on or about August 12, 2020. Traceability to the original equipment manufacturer, ITW GSE Inc., is required for the brand name items, while documentation of traceability is required for any equivalent alternative proposals.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Technical Worksheet

OFFEROR: _____________________________________
Cage Code: ________________________________________
Technical CriteriaDoes the offeror Meet requirement?Comments
Are you proving a quotation for the brand name part number? If yes, you can stop here. If no, please continue to complete the remainder of the form.
**FOR ALTERNATE PARTS ONLY**
PROVIDE THE MANUFACTURER AND PART NUMBER OF THE QUOTED ITEM:
OVERALL REQUIREMENTS
Diesel motor-driven generator set
Four (4) wheel trailer mounted design
Enclosed canopy/cabinet for generator set
Non self-propelled
Continuous operation from -25 to +125 degrees Fahrenheit ambient temperatures
Electrical generating system that meets MIL-STD-704F
Meets Electromagnetic Interference (EMI) requirements of MIL-STD-461
Fuel tank with at least eight (8) hours run time, at max full load
Fuel shutoff valve
Fuel tank low point drain valve
Manual Emergency shut off push button with reset
Unit operating flashing beacon or strobe (360 degree visible; amber)
Mounted five (5) pound ABC fire extinguisher
Edge/corner clearance lighting
Reflective edge/corner markings
TRAILER/CHASSIS
Not to Exceed (NTE)
Length (With Towbar up): 115 inches maximum
Width: 80 inches maximum
Height: 80 inches maximum
Weight (Dry): 5000 pounds maximum
Towable to 10 Miles per Hour (MPH) minimum
Tropical rust proofing package
Interior/exterior paint color: Commercial Semi-gloss White
Tow bar with parking brake
Towing eye
Rear mounted Pintle hitch (5000 pound minimum capability)
Fork lift pockets
ENGINE
Standard, commercial, diesel engine
Tier 4 Final Diesel (four (4) to six (6) cylinders)
12v starting system
Compliant with EPA regulations in effect at the time of manufacture
Diesel Exhaust Fluid (DEF) tank with at least eight (8) hours run time
Fuel strainer and fuel filter
Engine cold weather starting
Engine block heater
ENGINE INSTRUMENTS
Flood or back lighting
Panel light switch
Engine oil pressure gauge
Coolant temperature gauge
Air service indicator
Def service indicator
Fuel gauge
Hour meter
No load delayed shut down
ENGINE PROTECTION
Low coolant level warning indication
Low fuel flashing beacon or strobe (360 degree visible; blue)
Quarter (1/4) tank remaining
Critical low DEF shutdown with indication.
No less than 10 minutes run time remaining.
Overspeed Governor with reset
Low oil pressure shutdown with indication
High coolant temperature shutdown with indication
Intake air restriction indication
ELECTRICAL POWER
Generator Specifications - Alternating Current (AC)
Continuous 90kVA (kilo-Volt Ampere), 72 kW (kilowatt)
Three-phase, 4 Wire, Grounded neutral
115/200 VAC (Volts Alternating Current)
400Hz (Hertz)
Military (E & F) 24 volt DC signal Interlock
50 foot minimum 60 foot maximum single jacket AC cable with Scuff Guard
TRANSFORMER/RECTIFIER
Direct Current (DC)
28.5 vDC (Volts Direct Current)
2000 amps peak
600+ amps continuous
Simultaneous operation with 400Hz AC
30 foot banded DC cable
GENERATOR INSTRUMENTS
Flood or back lighting
Panel light switch
Load contactor indicating light
Frequency meter
Voltmeter
Ammeter
Fault indicating
Fault indicating reset
ELECTRICAL GENERATING SYSTEM ADJUSTMENTS
Frequency control
Voltage control
Line drop compensation
Cable length compensation
Cable size compensation
Test-bank switch
GENERATOR PROTECTION
Over voltage
Under voltage
Over frequency
Under frequency
Overload
LIFTING, SLINGING, AND TIE DOWN PROVISIONS FOR TRANSPORT
Fork lift pockets
Highway transportable
Air transportable
UNIT IDENTIFICATION PLATE – permanently secured to an interior panel
Nomenclature
Manufacturer and model number
Manufacturer’s serial number (SN) Asset NSN number (to be assigned)
Dry weight (lbs)
Gross weight, max (lbs)
Date of delivery
Warranty month expiration
Contract number
USCG Property
OPERATING INSTRUCTIONS PLATE – (Normal/Cold weather)
Permanently secured to exterior
WARNING/CAUTION LABELS
Permanently affixed, where required
OPERATOR'S MANUAL
Normal, cold, and hot environment operation and service
MAINTENANCE MANUAL
Servicing of all major components
Removal/replacement of all major components
Illustrated parts breakdown list
Service and parts support
Distributors list
Two (2) complete CD Rom manuals
Two (2) printed operation manuals
Standard Warranty - Please include warranty information