Attachment 4 - Pacific Valley O and M.pdf

PDF 18 MB Posted

Attached to
Pacific Valley Generator Replacement Federal contract opportunity
Solicitation number
127EAV25Q0061
Issued by
Department of Agriculture Forest Service

About this file

This document is an Operation & Maintenance Manual for a mobile solar photovoltaic (PV) system and LED lighting installation at the Pacific Valley Fire Station in Los Padres National Forest. The project, completed by Trane U.S. on October 1, 2019, involved installing a comprehensive off-grid renewable energy solution consisting of five mobile solar array trailers (SA-15) with 15 LG Neon 335-watt panels per trailer, a custom battery/inverter system in the generator building, and LED lighting retrofits throughout the facility. The system is designed to generate approximately 150 kWh/day, with a battery bank capable of providing two days of autonomous power, and is configured to automatically switch to the existing generator if battery levels become low.

The manual provides detailed operational procedures, maintenance guidelines, and warranty information for the mobile solar PV system and LED lighting. Key components include three Outback Power Radian inverters, five OutBack FLEXmax 100 charge controllers, and six IBE lead-acid battery cases. The warranty coverage varies by component, with the LG Neon PV panels having a 12-year product warranty and 25-year output warranty, inverters having a 10-year limited material warranty, and LED lighting fixtures carrying a 5-year warranty against defects. The document emphasizes the importance of regular maintenance, proper generator servicing, and adherence to specific operational protocols to ensure system reliability and warranty compliance.

View the file

Other files for this federal contract opportunity

Other files attached to Pacific Valley Generator Replacement, newest first.
File Type Posted
Attachment 3 - Pacific Valley Maps Photos.pdf PDF
Attachment 2 - Statement of Work.pdf PDF
Attachment 1 - Fire Plan.pdf PDF
Attachment 5 - Wage Determination - Monterey CA.pdf PDF
127EAV25Q0061 - Pacific Valley Generator Replacement.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OPERATION & MAINTENANCE MANUAL

Contract: GS-07F-0248K/AG-9A40-D-15-0007

USDA Forest Service, Region 5, ESPC Enable AFFECT Off-Grid Renewable Project

Pacific Valley Fire Station

Los Padres National Forest

Located on Highway 1 north of Gorda, CA approximately five miles

Prepared by: Trane U.S., 4145 Del Mar Avenue, Rocklin, CA 95677

Phone: (916) 577-1100; Fax: (916) 577-1175

PREFACE

This Operation & Maintenance Manual provides for installation instructions, operating procedures, equipment wiring diagrams, product numbers, scheduled maintenance procedures, warranty information and Trane representative contacts.

The main components of this project involved installation of new LED Lighting throughout the facilities and also a Mobile Solar PV system.

Only qualified personnel shall perform any servicing and maintenance of the equipment.

SAFETY WARNING

Only qualified personnel should install and service this equipment. The installation, starting up, shutting down and servicing of the LED Lighting and Mobile Solar PV equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in this manual, tags, stickers, and the drawings, etc.

Table of Contents

1. Contacting Trane for Service & Warranty

2. Overview of Project (White Paper)

3. Construction Drawings As-Built (Mobile Solar PV & LED Lighting)

4. LED Lighting Product Data & Installation Details

5. LED Lighting Operation & Maintenance

6. Mobile Solar PV Product Data & Installation Details

7. Mobile Solar PV System Operation & Maintenance

8. Warranty

SECTION 1

Contacting Trane for Service & Warranty

Trane Service & Warranty Contact Information:

Address: Trane U.S., 4145 Del Mar Avenue, Rocklin, CA 95677

Main Office Phone & Fax: Ph: (916) 577-1100; Fax: (916) 577-1175

Primary contact: Richard Swank, phone: (916) 577-1126; email: Richard.swank@trane.com

Secondary contact (Trane Service Department): 1-866-459-4155

Project Completion:

Trane U.S. was the installing Contractor for the Pacific Valley F.S. ‘Off-Grid Mobile Solar & LED

Lighting project. The project installation was completed and commissioned on October 1, 2019.

A 30-day acceptance period occurred from October 10, 2019 and completed on November 10, 2019. Commissioning documents were produced, provided, reviewed and signed by Forest of R5 personnel on November 5, 2019.

One (1) Year Construction Warranty Period:

A one (1) year construction installation warranty period started on October 10, 2019 and will have ended on October 10, 2020. There were no noted equipment failures during this period requiring a warranted repair or product replacement.

Equipment Warranty:

Each product installed for this project may have a ‘product warranty’. Within this manual are listed each products information and manufacture warranty information. If you believe you may have a product that is covered under warranty please contact Trane U.S. first before attempting to replace the product with a like-in-kind replacement.

A product warranty typically covers a manufacturer product defect in manufacture (i.e.: an LED light fixture fails within the warranty period). Specific details of products covered are warranty are to be found in the ‘Warranty’ section of this manual.

mailto:Richard.swank@trane.com

SECTION 2

Overview of Project (Trane ‘White Paper’)

The following pages consist of the Trane ‘White Paper’ which provides for information concerning the Pacific Valley Fire Station as ‘it was’ before the ENABLE project was implemented and the inventory of the existing equipment (electrical, lighting, generator, water, fuel usage, etc.).

In the white paper there is information on the recommendations for the constructed project in regards to the Mobile Solar PV system sizing and siting. Also, the existing lighting and LED

Lighting related work is inventoried. This document is a useful reference for the Pacific Valley F.S.

site.

This document is important as it provides background knowledge of the site, and the inputs of information into IGA survey that Trane performed.

We also recommend that the final ‘Construction’ drawings in this manual be referenced for actual final installed products and details.

Contract # AG-94A40-D-15-0007 for

U.S. Forest Service ESPC ENABLE AFFECT Off-Grid Renewable Energy Project

Pacific Valley Fire Station – Los Padres National Forest

12-1-19

On September 9th and 10th, 2015, Trane did a site walk visit for the IGA Audit data collection at the Pacific Valley Fire Station located in the Los Padres National Forest. The site was ‘open’ and operating during our visit. We met with several Forest Service crew members and observed the ‘rental generator’ operation during our visit and evaluated its base load operation and full load operation. An inventory of all of the lighting, appliances, etc. was conducted. We looked at the water and propane consuming devices and appliances and made an inventory of each type.

We are providing Trane’s findings from the U.S. Forest site visit in the following five (5) Section elements: I. Location, II. Site Overview, III. Investment Grade Audit (IGA) Site Visit Findings, IV. Sustainable / Solar Siting Considerations and last, Appendix – Pictures.

I. Location

The Pacific Valley Fire Station facility is located on the Pacific Coast along Highway 1 north of San Simeon, CA approximately 35 miles. The fire station is at sea level on the coast. The best way to reach the site from the CA valley area is via Highway 101 to Highway 46 which travels west across the coastal range of mountains. At the junction of Highway 1 go north where you will pass Cambria, then San Simeon and then up to the Pacific Valley Fire Station (on the right hand side of Highway 1). The Fire Station is marked with signage and is right next to Highway 1.

II. Site Overview

Pacific Valley Fire Station is open year round and operates 24/7. The site includes an Engine Bay, Fire Cache, Fuel Storage Shed, Diesel/Gasoline Fueling tanks, Barracks (which looks like a home), Generator Building, three (3) permanent Employee Double Wide Trailer Homes, a Second Barracks with Laundry Area and a Well Pump House.

The Engine Bay Building consists of an office area with a bathroom, a shop area, engine bay and storage area under one structure. The exterior lights are metal halide (MH), and the interior lighting is mostly fluorescent and incandescent.

The Fire Cache shed is next to the Engine Bay building and is used for storage of fire equipment and tools. The lighting in the shed consists of 2 lamp T12 fluorescent fixtures.

Next to the Fire Cache is a very small Fuel Storage ‘Shed’ with no lighting or electrical.

The Fuel Storage station area consists of two fuel tanks (one diesel and one gasoline) with electric fuel pump. There is no lighting at these tanks.

The Barracks Building (which essentially is a home) is to the north of the Engine Bay Building and consists of a converted garage area into a storage room, a kitchen area, a Living Room area and three (3) Bedrooms.

The Generator Building has two (2) Cummins 35-kW (prime) diesel generators which neither are currently being operated due to ‘air permit’ issues. We understand that these two generators do not meet emission requirements and therefore cannot be operated. A single temporary ‘rental generator’ is currently being used which is a model MQ Power 21-kW (120/240V @ 89 amps) diesel powered generator that provides electrical power to the entire site. This rental generator has been connected into the existing diesel fuel tank for its fueling and into the existing electrical switchboard to provide power to the site.

The three (3) employee Double Wide Trailer Homes consist of two (2) 8’ x 40’ and one

(1) 20’ x 50’ mobile homes. These three trailers are owned by the employees and the Forest Service rental generator provides power to them. The power panels at each trailer have 70 amp breakers however we did not see consumption amperages much above 10 to 15 amps from each trailer. We were not able to go through the private trailers as there was no one to escort us or people in them at the time of our visit. There would not be any energy conservation efforts in these private facilities as the ENABLE project would not cover private property items or retrofits.

The Second Barracks Building is near the employee Double Wide Trailer Homes. The building consisted of a kitchen area, bathrooms with toilets and showers, a couple of bedrooms and a detached laundry room next to the building. The lighting consisted of fluorescent fixtures and some CFL and incandescent bulbs.

Near the north part of the site grounds, there is a Well Pump House. The well pump pumps water up to a 20,000 gallon water storage tank above the facility on a hill where the water then gravity feeds to the facility for domestic water use. The submersible well pump is believed to be a 1-1/2 H.P., 240V, 1-phase pump estimated to be able to pump 25 GPM approximately.

There are multiple propane storage tanks around the facility, four (4) in total. There are two near the Employee Trailers; one at the Barracks (house); one at the Second Barracks.

The propane consuming appliances consist of refrigerators, barracks heaters and gas stoves. The Generator Building has a dedicated red diesel fuel tank for the generator(s).

III. Investment Grade Audit (IGA) Site Visit Findings

Findings from site visit is subdivided by primary Energy Conservation Measure categories, power generation and fuel. Photo documentation from the site visit are provided in the Appendix.

A. Electrical

The following electrical loads currently exist at the Pacific Valley Fire Station site:

Continued on next page

Electrical Notes

(1) The Pacific Valley F.S. NEPA document suggests solar system be ‘ballasted’ on the ground in an area not visible to

Highway 1 due to coastal commission. This is a historical site (Indian artifacts). Due to the complexies and cost of a ground mounted system at this site we recommend a mobile solar PV system. This would help mitigate NEPA and ground disturbance issues.

(2) Field generator measurements indicate a maximum amperage load of 89 amps based upon all available loads being

‘ON’.

(3) The lighting retrofits consist of CFL, incandescent and fluorescent lamps be changed to LED lamps. This will significantly reduce overall lighting loads.

(4) Exterior lighting would also be retrofitted to LED lamps and/or fixtures.

(5) All appliances remain ‘as is’ (i.e.: no change in load wattages).

(6) The ‘batteries’ for the mobile solar PV would be contained in the trailer with the equipment for the mobile PV system. This eliminates the need for a building to house batteries. This also eliminates any fencing around solar PV system.

B. Water

The table below summarizes Trane’s inventory of water consuming devices for the site:

Water Consuming Devices:

Item

No.

Description Recommendations Hours of

Use/Day

Notes

1 Engine Bay – Restroom Sink No Changes Recommended Intermittent Fixture remains

2 Engine Bay – Restroom Toilet No Changes Recommended Intermittent Fixture remains

3 Barracks (house) – Kitchen sink No Changes Recommended Intermittent Fixture remains

4 Barracks (house) - Bathroom #1 - Shower

No Changes Recommended Intermittent Fixture remains

5 Barracks (house) - Bathroom #1 – Sink No Changes Recommended Intermittent Fixture remains

6 Barracks (house) - Bathroom #1- Toilet No Changes Recommended Intermittent Fixture remains

7 Barracks (house) - Bathroom #2- Toilet No Changes Recommended Intermittent Fixture remains

8 Barracks (house) - Bathroom #2 – Sink No Changes Recommended Intermittent Fixture remains

9 Barracks (lower) - Kitchen Sink No Changes Recommended Intermittent Fixture remains

10 Barracks (lower) - Bathroom – Toilet #1 No Changes Recommended Intermittent Fixture remains

11 Barracks (lower) – Bathroom – Toilet #2 No Changes Recommended Intermittent Fixture remains

12 Barracks (lower) – Bathroom – Shower #1

No Changes Recommended Intermittent Fixture remains

13 Barracks (lower) – Bathroom – Shower #2

No Changes Recommended Intermittent Fixture remains

14 Barracks (lower) – Bathroom Dual Sinks No Changes Recommended Intermittent Fixture remains

15 Outside Laundry – (2) Washing Machines

No Changes Recommended Intermittent Fixture remains

NOTE: This site has minimal water usage from the fixtures listed in the above table. Most of the water consumption is from fi lling of the fire engine and washing fire equipment. Therefore, we do not recommend any fixture changes for this site.

C. Generators

There are two (2) existing Cummins 35-kW (prime) diesel generators which neither are currently being operated due to ‘air permit’ issues. We understand that these two generators do not meet emission requirements and therefore cannot be operated. Currently a single temporary ‘rental generator’ is being used to provide power to the entire site. The rental generator is an MQ Power 21-kW (120/240V @ 89 amps) diesel powered generator that provides electrical power to the entire site. During simulated load testing this generator is appropriately sized for what we observed in facility loads.

Having a ‘rental generator’ at this site averts potential maintenance costs and we do not have any information on what costs or arrangements currently exist for the rental equipment. Under normal circumstances we would expect annual generator maintenance costs to be incurred however we do not have any costs for such services. For the ENABLE project if it is allowable we foresee a stipulated average maintenance cost of $2,000 per year as we do not have actual invoices from expenses incurred.

D. Fuel – Diesel & Propane

The table below summarizes Trane’s inventory of red diesel consuming devices for the site:

No.

Description Recommendations Future Hours of Use

Notes

1 Generator #1 (Cummins #DSFAB-4657073)

Not in use.

Not AQMD permittable

Unknown Offline – not in use

2 Generator #2 (Cummins #DSFAB-4657073)

Not in use.

Not AQMD permittable

Unknown Offline – not in use

3 Rental Generator MQ (Model #DCA-

40SSKU)

Leave in-place Current power generation

24/7 TBD of status of rental and future use

The table below summarizes Trane’s inventory of propane consuming devices for the site:

No.

Description Recommendations Future Hours of Use

Notes

1 Barracks (house) Hot Water Heater 40 gallon, 36,000 BTUH

Leave in-place Intermittent Leave as is since it is relatively new

2 Barracks (house) Coleman forced air heating unit. 125K BTUH

Leave in-place Intermittent Change thermostat to programmable one.

3 Barracks (near trailers) Front Room wall heater (Chamberlain)

Leave in-place Intermittent Change thermostat to programmable one.

4 Barracks (near trailers) Bathroom heater (wall) Cozy

Leave in-place Intermittent Change thermostat to programmable one.

5 Barracks (near trailers) Kitchen Gas stove (4 burner)

Leave in-place Intermittent No Change

6 Outside Laundry – Clothes Dryers (2) Leave in-place Intermittent No Change

Trane received actual ‘diesel’ fuel bills for the previous several year period at this site. The U.S. Forest Service has fairly consistent fuel costs year-to-year in the original provided Excel data chart. We have stipulated and used $39,900 average per year of annual fuel costs (based upon 2011-14 data provided). The actual fuel bills substantiate these costs.

Estimated cost/hour to operate the generator is $4.55/hour.

The following Forest Service ENABLE AFFECT table is provided with dated values as shown below from the fall of 2011 to the fall of 2014:

Los Padres Forest Fuel Consumption

Fuel Fuel Cost Notes

Pacific Valley F.S. Gallons Type $ Dollars

2012 (Oct2011-Sept2012) 11216 Diesel $39,900.00 The fuel use in this table correlates closely to fuel bills.

2012 (Oct2012-Sept2013) 10382 Diesel $37,375.00 2012 (Oct2013-Sept2014) 12050 Diesel $42,426.00

E. Other ECMs and Considerations

This site does not experience ‘snow’ conditions as it is at sea level.

IV. Sustainable / Solar Siting Considerations

The Pacific Valley Fire Station NEPA document suggests that the solar system be ground mounted as a ballasted PV system due to the historical nature of the site as an old Indian habitat area and also due to the fact that scenic Highway 1 is visible at various locations at this site including the view of the Pacific Ocean from behind the Barracks buildings. To avert the NEPA and Coastal Commission issue a mobile solar system may best be applied at this site. This would eliminate underground trenching, ballasted system, fencing and other construction activities. The location for the mobile solar system may be more flexible also.

Google Earth of Pacific Valley Fire Station

GPS coordinates: 35°55’ 59.23” N, 121°28’ 05.97” W

Well Pump

House

Barracks & Laundry

Employee Trailers

Generator

Building

Employee Trailers

Barracks (House)

Engine Bay/Office

Fuel Tanks

Fire Cache

Fuel Storage

20,000 Gal. Water Tank

Mobile Solar

PV Location

Overhead Power Cables

U.G. Power Cables

Pacific Valley Fire Station – Mobile Solar System Layout (Lead Acid)

Mobile Solar Solution is depicted below for average daily load of 146.8 kWh / day

MS-275-R3.240 (no trailer, rack in gen.bldg.) Five (5 each) SA-15 (15 panels x 330W/ea. & 23kWh/day harvest/each)

Electrical to connect SA-15’s to MS-275 (rack) (Typical 5 ea.)

Existing Electrical Panel Existing MQ Power Rental Generator

Notes:

1.) BASE PV SYSTEM (Lead Acid): Average daily load is 150 kWh/day. Proposed Mobile Solar system is 150 kWh/day.

2.) MS trailer replaced with ‘rack’ to be installed in generator building.

3.) MS-275-R3.240 (rack) w/ 3 x 80 kWh lead acid batteries. Two days of battery autonomy.

MS trailer eliminated and replaced by ‘rack’ to be mounted in generator building.

4.) Five SA-15’s (15 each x 330-watt PV modules, 23 kWh/day harvest. Physical: 32’ x 10’ deployed (including tongue);

Transport dimensions for SA-15: 32’ L x 8’-6” W x 8’-4” T Weight: ~4,000lbs

5.) Electrical conduit/wire to connect SA-15’s to MS-275 (rack) unit in generator building.

Power Cords

To/From Power

Panel & MS-275

MS trailer eliminated now

‘rack’

Existing Power Cable

Appendix - Pictures

Pacific Valley Fire Station – Mobile Solar System Location

This location is up a dirt road to an open area above the fire station and generator building. The entire area is expected to be accommodated with the main trailer with batteries and the four other solar PV panel trailers.

At SA-15 trailers above grade electrical inter-connect until U.G. trench along road back to generator building and overhead across ravine.

SECTION 3

Final Construction Drawings, Wiring Diagrams and Details

The following pages provide for the Pacific Valley Fire Station installation drawings. These drawings provide for the installed equipment location(s) and information, including detailed construction plans and wiring diagrams for the Mobile Solar PV system and the LED Lighting products that have been installed.

These systems that are installed produce and consume electricity generated from the Mobile

Solar PV system.

Electrical Hazard! DO NOT attempt to change or modify the installed LED Lighting or Mobile Solar PV system as damage to the equipment may occur and warranty may be voided.

Contact Trane U.S. for any concerns or questions in regards to the equipment (see ‘Contacts’ section in this manual).

SECTION 4

LED Lighting Product Data & Installation Details

The following pages consist of the Trane ‘LED Lighting Product Data Sheets’ and also within these sheets are the manufacturer installation information for the Pacific Valley Fire Station.

These product data sheets are your resource for the installed LED Lighting products.

Additional LED Lighting locations for these installed products may be found in Section 3 of the

Construction Drawings as-built along with the manufacturer model numbers (which are highlighted in these product data sheets and also on the construction drawings).

SUBMITTAL

“Lighting Product Data Sheets” lbjla Rectangle

GE’s ENERGY STAR® certified LED replacement lamps

Brighten lbjla Text Box Project: Pacific Valley F.S. (LPNF) Catalog No.: LED10DA19/850 Type: "A" Comments: LED Lamp (replaces incandescent & CFL lamps) Date: 3-11-19 Prepared By: Richard Swank (Trane U.S.

GE’s ENERGY STAR® certified LED lampsPERFORMANCE DATA A-Line Lamps

* The life rating is based on the hours of operation the lamp will provide before reaching 70% of its original rating (L70) ** Minimum order quantity = 6

ENERGY STAR® status: ENERGY STAR® certified. Lamps without a “ ” are not ENERGY STAR® certified.

# UL 1993 Environmental Requirements for LED LAMPS
Location, damp – Exterior or interior location that is normally or periodically subject to condensation of moisture in, on, or adjacent to, electrical equipment,
and includes partially protected locations.
Location, dry– Location not normally subject to dampness, may include a location subject to temporary dampness, i.e., building under construction,
provided ventilation is adequate to prevent an accumulation of moisture.
Location, wet– Location in which water or other liquid can drip, splash, or flow on or against electrical equipment.
Notes:1) Product descriptions ending in “/TP” indicate a carded blister or clamshell package nested in a tray for shelf display. Cards also designed for hook display.
2) LED A19 Locking device works on PC: 85791, 85792, 89898, 62182, 89899 and 89900

Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, expressed or implied, that such performance will be obtained under end-use conditions.

Directional Lamps (MR16 - GU10)

Bulb Shape

Base Type Watts

Order Code Description Volts

Case Qty**

MOL

(In) Lumens Initial CBCP

Initial Color Temp CRI

Wattage Replacement

*Rated Life

L70 (Hrs) Dimmable

ENERGY

STAR®

Status

#Location Rating

Additional Information

A-19 MED 6 69115 LED6DA19/827 120 6 4.4 480 2700 80 40W 15,000 Yes Damp White, Omnidirectional

69118 LED6DA19/830 120 6 4.4 480 3000 80 40W 15,000 Yes Damp White, Omnidirectional

69132 LED6DA19/840 120 6 4.4 480 4000 80 40W 15,000 Yes Damp White, Omnidirectional

69144 LED6DA19/850 120 6 4.4 480 5000 80 40W 15,000 Yes Damp White, Omnidirectional 10 69117 LED10DA19/827 120 6 4.4 800 2700 80 60W 15,000 Yes Damp White, Omnidirectional

69119 LED10DA19/830 120 6 4.4 800 3000 80 60W 15,000 Yes Damp White, Omnidirectional 69133 LED10DA19/840 120 6 4.4 800 4000 80 60W 15,000 Yes Damp White, Omnidirectional 69146 LED10DA19/850 120 6 4.4 800 5000 80 60W 15,000 Yes Damp White, Omnidirectional

A-21 MED 12 76037 LED12DA21/827 120 6 5.16 1100 2700 80 75W 15,000 Yes Damp White, Omni, ES 2.0

76041 LED12DA21/830 120 6 5.16 1100 3000 80 75W 15,000 Yes Damp White, Omni, ES 2.0 76045 LED12DA21/840 120 6 5.16 1100 4000 80 75W 15,000 Yes Damp White, Omni, ES 2.0 76102 LED12DA21/850 120 6 5.16 1100 5000 80 75W 15,000 Yes Damp White, Omni, ES 2.0

15 76038 LED15DA21/827 120 6 5.16 1600 2700 80 100W 15,000 Yes Damp White, Omni, ES 2.0 76043 LED15DA21/830 120 6 5.16 1600 3000 80 100W 15,000 Yes Damp White, Omni, ES 2.0 76060 LED15DA21/840 120 6 5.16 1600 4000 80 100W 15,000 Yes Damp White, Omni, ES 2.0 76117 LED15DA21/850 120 6 5.16 1600 5000 80 100W 15,000 Yes Damp White, Omni, ES 2.0

MED 16 73376 LED16A30/100/827 120 6 5.31 360/1400/900 2700 80 30/70/100 25,000 - Damp White, 3-Way 92118 LED16A30/100/5KB 120 3 5.31 360/1400/900 5000 80 30/70/100 25,000 - Damp White, 3-Way

Bulb Shape

Base Type Watts

Order Code Description Volts

Case Qty**

MOL

(In)

Lumens Initial CBCP

Initial Color Temp CRI

Wattage Replacement

*Rated Life

L70 (Hrs) Dimmable

ENERGY

STAR®

Status

#Location Rating

Additional Information

12 Volt AC/DC MR16

MR16 GU5.3 6.5 75155 LED6.5DMR16W82715 12 6 1.87 500 4900 2700 80 50W 25,000 Yes Damp Spot 15° beam, White

75153 LED6.5DMR16W83015 12 6 1.87 520 4900 3000 80 50W 25,000 Yes Damp Spot 15° beam, White

75158 LED6.5DMR16W84015 12 6 1.87 550 5000 4000 80 50W 25,000 Yes Damp Spot 15° beam, White

93226 LED6.5DMR16W82725 12 6 1.79 500 2350 2700 80 50W 25,000 Yes Damp Narrow 25° beam, White

93222 LED6.5DMR16W83025 12 6 1.79 520 2350 3000 80 50W 25,000 Yes Damp Narrow 25° beam, White

93228 LED6.5DMR16W84025 12 6 1.79 550 2400 4000 82 50W 25,000 Yes Damp Narrow 25° beam, White

93227 LED6.5DMR16W82735 12 6 1.79 500 1350 2700 80 50W 25,000 Yes Damp Flood, 35° beam, White

93223 LED6.5DMR16W83035 12 6 1.79 520 1350 3000 80 50W 25,000 Yes Damp Flood, 35° beam, White

93229 LED6.5XDMR16W84035 12 6 1.79 550 1400 4000 80 50W 25,000 Yes Damp Flood, 35° beam, White

Value 12 Volt AC/DC MR16

GU5.3 5.5 35542 LED5.5DMR1684035 12 6 1.86 460 1100 4000 80 35W 25,000 Yes Damp Flood, 35° beam, White

35535 LED5.5DMR1683035 12 6 1.86 420 1000 3000 80 35W 25,000 Yes Damp Flood, 35° beam, White

35540 LED5.5DMR1682735 12 6 1.86 400 1000 2700 80 35W 25,000 Yes Damp Flood, 35° beam, White

6 20165 LED6DMR16-32725 12 6 1.86 500 2350 2700 80 50W 25,000 Yes Damp Narrow 25° beam, White

20168 LED6DMR16-32735 12 6 1.86 500 1350 2700 80 50W 25,000 Yes Damp Flood, 35° beam, White

20156 LED6DMR16-38325 12 6 1.86 500 2350 3000 81 50W 25,000 Yes Damp Narrow 25° beam, White

20157 LED6DMR16-38335 12 6 1.86 500 1350 3000 81 50W 25,000 Yes Damp Flood, 35° beam, White 120 Volt GU10 MR16 GU10 3.5 37114 LED4D/GU1083035 120 6 2.1 300 550 3000 80 35W 25,000 Yes Dry Flood, 35º beam, White

4 89020 LED4D/GU10/NFLTP 120 3 2.1 250 720 3000 80 35W 25,000 Yes Damp Flood, 35º beam, White

6 26346 LED6D/GU10/NFL/TP 120 3 2.1 430 1100 3000 80 50W 25,000 Yes Damp Flood, 35º beam, White

37117 LED6D/GU1083035 120 6 2.1 430 1100 3000 80 50W 25,000 Yes Damp Flood, 35º beam, White lbjla Highlight lbjla Highlight lbjla Highlight

Highlight

GE’s ENERGY STAR® certified LED replacement lamps

Brighten lbjla Text Box Project: Pacific Valley F.S.

Catalog No.: LED12DP30RW83040 Type: "B" Comments: LED PAR Lamp (replaces MH PAR Lamps) Date: 3-11-19 Prepared By: Richard Swank (Trane U.S.)

Bulb Shape

Base Type Watts

Order Code Description Volts

Case Qty**

MOL

(In)

Lumens Initial CBCP

Initial Color Temp CRI

Wattage Replacement

*Rated Life L70 (Hrs) Dimmable

ENERGY

STAR®

Status

#Location Rating

Additional Information

BR30

MED 10 68160 LED10DR303/827W 120 6 5.4 700 2700 80 65W 25,000 Yes Damp Frosted, White body

68161 LED10DR303/830W 120 6 5.4 700 3000 80 65W 25,000 Yes Damp Frosted, White body 69107 LED10DR303/850W 120 6 5.4 700 3000 80 65W 25,000 Yes Damp Frosted, White body

BR40

MED 13 64176 LED13DBR40/827 120 6 6.3 1070 2700 80 85W 25,000 Yes Damp Frosted, White body

14708 LED13DBR40/830 120 6 6.3 1070 3000 80 85W 25,000 Yes Damp Frosted, White body 69108 LED13BR40/850 120 3 6.34 1070 5000 80 85W 25,000 Yes Damp Frosted, White body

Bulb Shape

Base Type Watts

Order Code Description Volts

Case Qty**

MOL

(In)

Lumens Initial CBCP

Initial Color Temp CRI

Wattage Replacement

*Rated Life

L70 (Hrs) Dimmable

ENERGY

STAR®

Status

#Location Rating

Additional Information

Compact PAR30 - Low Glare - Visual Comfort Lens™ PAR30 MED 12 84374 LED12DP30RW93015 120 6 3.74 860 9400 3000 90 75W 25,000 Yes Damp Spot, 15° beam, White

84379 LED12DP30RW93025 120 6 3.74 900 3900 3000 90 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 84380 LED12DP30RW93040 120 6 3.74 900 1800 3000 90 75W 25,000 Yes Damp Flood, 40˚ beam, White 84392 LED12DP30RW92725 120 6 3.74 850 3500 2700 90 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 84395 LED12DP30RW92740 120 6 3.74 850 1700 2700 90 75W 25,000 Yes Damp Flood, 40˚ beam, White 84384 LED12DP30RW83025 120 6 3.74 1050 4800 3000 80 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 42131 LED12DP30RW83040 120 6 3.74 1050 2400 3000 80 75W 25,000 Yes Damp Flood, 40˚ beam, White 42133 LED12DP30RW82725 120 6 3.74 1000 4700 2700 80 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 42134 LED12DP30RW82740 120 6 3.74 1000 2200 2700 80 75W 25,000 Yes Damp Flood, 40˚ beam, White 73583 LED12DP30RB82740 120 6 3.74 1000 2200 2700 80 75W 25,000 Yes Damp Flood, 40˚ beam, Black

Compact PAR30 - Long Neck - Low Glare - Visual Comfort Lens™ PAR30L MED 12 84399 LED12DP3LRW93025 120 6 4.72 900 3900 3000 90 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White

84400 LED12DP3LRW93040 120 6 4.72 900 1800 3000 90 75W 25,000 Yes Damp Flood, 40˚ beam, White 84407 LED12DP3LRW92740 120 6 4.72 850 1700 2700 90 75W 25,000 Yes Damp Flood, 40˚ beam, White 42136 LED12DP3LRW83025 120 6 4.72 1050 4800 3000 80 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 42137 LED12DP3LRW83040 120 6 4.72 1050 2400 3000 80 75W 25,000 Yes Damp Flood, 40˚ beam, White 42141 LED12DP3LRW82725 120 6 4.72 1000 4700 2700 80 75W 25,000 Yes Damp Narrow Flood, 25° beam, White 42144 LED12DP3LRW82740 120 6 4.72 1000 2200 2700 80 75W 25,000 Yes Damp Flood, 40˚ beam, White

Bulb Shape

Base Type Watts

Order Code Description Volts

Case Qty**

MOL

(In)

Lumens Initial CBCP

Initial Color Temp CRI

Wattage Replacement

*Rated Life

L70 (Hrs) Dimmable

ENERGY

STAR®

Status

#Location Rating

Additional Information

Compact PAR16 PAR16 MED 4 26383 LED4D/P16/NFLTP 120 3 2.8 260 720 3000 80 40W 25,000 Yes Dry Flood, 35º beam, White

6 26384 LED6D/P16/NFLTP 120 3 2.8 380 1100 3000 80 60W 25,000 Yes Dry Flood, 35º beam, White

Compact PAR20 PAR20 MED 7 93327 LED7DP203B830/20 120 6 3.5 520 3600 3000 80 50W 25,000 Yes Damp Narrow Flood, 20° beam Black

93347 LED7DP203W830/20 120 6 3.5 520 3600 3000 80 50W 25,000 Yes Damp Narrow Flood, 20° beam 93348 LED7DP203W830/35 120 6 3.5 520 1200 3000 80 50W 25,000 Yes Damp Flood, 35° beam 93349 LED7DP203B827/20 120 6 3.5 500 3600 2700 80 50W 25,000 Yes Damp Narrow Flood, 20° beam Black 93354 LED7DP203B827/35 120 6 3.5 500 1150 2700 80 50W 25,000 Yes Damp Flood, 35° beam Black 93360 LED7DP203W827/20 120 6 3.5 500 3600 2700 80 50W 25,000 Yes Damp Narrow Flood, 20° beam 93362 LED7DP203W827/35 120 6 3.5 500 1150 2700 80 50W 25,000 Yes Damp Flood, 35° beam

GE’s ENERGY STAR® certified LED lampsPERFORMANCE DATA

Reflector Lamps

Directional Lamps (PAR30 - Low Glare - Visual Comfort Lens™)

Directional Lamps (PAR16 - PAR20)

* The life rating is based on the hours of operation the lamp will provide before reaching 70% of its original rating (L70) ** Minimum order quantity = 6

ENERGY STAR® status: ENERGY STAR® certified. Lamps without a “ ” are not ENERGY STAR® certified.

# UL 1993 Environmental Requirements for LED LAMPS
Location, damp – Exterior or interior location that is normally or periodically subject to condensation of moisture in, on, or adjacent to, electrical equipment,
and includes partially protected locations.
Location, dry– Location not normally subject to dampness, may include a location subject to temporary dampness, i.e., building under construction,
provided ventilation is adequate to prevent an accumulation of moisture.
Location, wet– Location in which water or other liquid can drip, splash, or flow on or against electrical equipment.
Notes:1) Product descriptions ending in “/TP” indicate a carded blister or clamshell package nested in a tray for shelf display. Cards also designed for hook display.
2) LED A19 Locking device works on PC: 85791, 85792, 89898, 62182, 89899 and 89900

Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, expressed or implied, that such performance will be obtained under end-use conditions.

Bulb Shape

Base Type Watts

Order Code Description Volts

Case Qty**

MOL

(In)

Lumens Initial CBCP

Initial Color Temp CRI

Wattage Replacement

*Rated Life

L70 (Hrs) Dimmable

ENERGY

STAR®

Status

#Location Rating

Additional Information

Single Optics 15W PAR38 MED 15 32213 LED15DP38W830/40 120 6 5.04 1300 2300 3000 81 90W 25,000 Yes Wet Flood, 40° beam, White, STIR

Directional Lamps (PAR30 - STIR)

Bulb Shape

Base Type Watts

Order Code Description Volts

Case Qty**

MOL

(In)

Lumens Initial CBCP

Initial Color Temp CRI

Wattage Replacement

*Rated Life

L70 (Hrs) Dimmable

ENERGY

STAR®

Status

#Location Rating

Additional Information

Compact PAR30 PAR30 MED 12 98755 LED12DP303W83035 120 6 3.66 950 2600 3000 80 75W 25,000 Yes Damp Flood, 35˚ beam, White, STIR

Compact PAR30 Long Neck PAR30L MED 12 98811 LED12DP3L3W83035 120 6 4.61 950 2600 3000 80 75W 25,000 Yes Damp Accent, 35˚ beam, White, STIR lbjla Highlight lbjla Highlight lbjla Highlight

HALO OUTDOOR™

PS502100EN

February 25, 2019 2:04 PM

SPECIFICATION FEATURES

Construction

• Durable die-cast aluminum housing with UV stable clear lens

• Powder coated bronze or white finish

• Optically enhanced reflector improves efficiency and delivered lumens

• Tool-less head and motion sensor adjustment

• Wall or eave mounted to recessed or surface junction boxes

Optics

• Two-stage optics for maximum coverage

• Field selectable CCT: 3000K, 4000K and 5000K

Electrical

• 120VAC, 60Hz (Select SKUs)

• 120-277VAC, 60Hz (Select SKUs)

• Maintenance-free LEDs with 70,000 hours of life

• Fixture operating temperature of -30°C to 40°C

• External supply wiring 75°C minimum

• Integral photocell allows for nighttime ON / daytime OFF operation (Integrated sensor SKUs only)

Select Motion SKUs

• Motion sensor detects motion 180° or 270° up to 50 feet

• Selectable duration to keep floodlights on up to 12 minutes

• Adjustable sensitivity

• Integral photocell prevents lights from turning on with motion during daylight hours

• Manual override allows fixture to operate as a standard dusk-to-dawn for up to 6 hours

Warranty

• Five year limited warranty, consult website for details.

www.eaton.com/lighting/legal

Compliance

• UL certified for US and Canada for wet locations

• EMI/RFI emissions per FCC 47CFR Part 15B

• Contains no mercury or lead and RoHS compliant.

• Photometric testing in accordance with IES LM-79-08

• Lumen maintenance projections in accordance with IES LM-80-08 and TM-21-11

DIE CAST

FLOOD SERIES

SINGLE, TWIN,

TRIPLE FLOODS

The HALO LED Die Cast floodlight series utilizes selectable CCT functionality, advanced two-stage optics and multiple mounting options for a versatile outdoor lighting solution. Multiple lumen packages and integrated control options address a wide range of outdoor general lighting and security applications. The durable die-cast aluminum housing is available in bronze or white powder coat finish, ensuring years of reliable, maintenance-free operation.

DESCRIPTION

Catalog # Type

Date

Project

Comments

Prepared by

DIMENSIONS

Suitable for recessed or surface mount electrical junction boxes

FSL303T and FSL203T

FSS153T

6.3˝ [160mm]

Front View Side View

6.6˝ [167mm]

Wall Mount Eave Mount

6.2˝ [158mm]

5.1˝ [130mm]

Front View Side View

6.1˝ [155mm]

Wall Mount Eave Mount

5.9˝ [150mm] lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight

Specifications and dimensions subject to change without notice.

Eaton 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.eaton.com/lighting

PHOTOMETRY

DIE CAST FLOOD SERIES

SINGLE, TWIN, TRIPLE FLOODS

ORDERING INFORMATION

DIMENSIONS

Sample Number: FSS153TIB or MST203T18W

Module Lumens CRI/CCT Options Colors

FSS = Flood Single Small FSL = Single Large Flood FTS = Flood Twin Small FHS = Flood Triple Small MSS = Motion Small Single MST = Motion Small Twin MSH = Motion Small Triple

15 = 1500 lumens (nominal) 20 = 2000 lumens (nominal) 30 = 3000 lumens (nominal)

3T = Selectable CCT 3000K, 4000K, & 5000K

I = Integrated Photocell 18 = 180* Motion Sensor 27 = 270* Motion Sensor

B �= Bronze W = White

PS502100EN

February 25, 2019 2:04 PM

Note: Specifications and Dimensions subject to change without notice.

FC

L

CB W

Area Coverage Mounting

Height Length

(L) Width (W)

Area (Sq. Ft.)

Max FC

MST203T

Series

10 ft.

15 ft.

20 ft.

4.3 1.9 1.1

Note: Bronze fixture at a typical mounting angle of 30° from vertical All figures based on minimum footcandle (FC) of 0.5 and 4000K CCT.

Note: Specifications and Dimensions subject to change without notice.

FC

L

CB W

Area Coverage Mounting

Height Length

(L) Width (W)

Area (Sq. Ft.)

FSL303T

Series

10 ft.

15 ft.

20 ft.

25 ft.

FSL203T

Series

10 ft.

15 ft.

20 ft.

FSS153T

Series

10 ft.

15 ft.

20 ft.

Note: Bronze fixture at a typical mounting angle of 30° from vertical All figures based on minimum footcandle (FC) of 0.5.

10.3˝ [261 mm]

11.4˝ [291 mm]

Front View Side View

6.7˝ [170 mm]

8.72˝ [209 mm]

Front View Side View

MST203T MHS303T

lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight change without notice.

Eaton 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.eaton.com/lighting

PS502100EN

February 25, 2019 2:04 PM

Series Voltage Power (W) Delivered Lumens (Lm)

Efficacy (Lm/W)

CCT CRI Controls

FSS153TB 120-277V 17.3 1503 86.9 3000K,4000K,5000K 84 None

FSS153TW 120-277V 17.3 1503 86.9 3000K,4000K,5000K 84 None

FSS153TIB 120V 17.3 1503 86.9 3000K,4000K,5000K 84 Integrated Photocell

FSS153TIW 120V 17.3 1503 86.9 3000K,4000K,5000K 84 Integrated Photocell

FSL203TB 120-277V 22.5 1916 85.2 3000K,4000K,5000K 84 None

FSL203TW 120-277V 22.5 1916 85.2 3000K,4000K,5000K 84 None

FSL203TIB 120V 22.5 1916 85.2 3000K,4000K,5000K 84 Integrated Photocell

FSL203TIW 120V 22.5 1916 85.2 3000K,4000K,5000K 84 Integrated Photocell

FSL303TB 120-277V 31.6 2900 91.8 3000K,4000K,5000K 84 None

FSL303TW 120-277V 31.6 2900 91.8 3000K,4000K,5000K 84 None

FSL303TIB 120V 31.6 2900 91.8 3000K,4000K,5000K 84 Integrated Photocell

FSL303TIW 120V 31.6 2900 91.8 3000K,4000K,5000K 84 Integrated Photocell

FTS203TB 120-277V 22.8 2034 89.2 3000K,4000K,5000K 84 None

FTS203TW 120-277V 22.8 2034 89.2 3000K,4000K,5000K 84 None

FHS303TB 120-277V 31.8 2853 89.7 3000K,4000K,5000K 84 None

FHS303TW 120-277V 31.8 2853 89.7 3000K,4000K,5000K 84 None

MSH303T18B 120V 31.8 2853 89.7 3000K,4000K,5000K 84 180* Motion Sensor

MSH303T18W 120V 31.8 2853 89.7 3000K,4000K,5000K 84 180* Motion Sensor

MSS153T18B 120V 17.3 1503 86.9 3000K,4000K,5000K 84 180* Motion Sensor

MSS153T18W 120V 17.3 1503 86.9 3000K,4000K,5000K 84 180* Motion Sensor

MST203T18B 120V 22.8 2034 89.2 3000K,4000K,5000K 84 180* Motion Sensor

MST203T18W 120V 22.8 2034 89.2 3000K,4000K,5000K 84 180* Motion Sensor

MST203T27B 120V 22.8 2034 89.2 3000K,4000K,5000K 84 270* Motion Sensor

MST203T27W 120V 22.8 2034 89.2 3000K,4000K,5000K 84 270* Motion Sensor

DIE CAST FLOOD SERIES

SINGLE, TWIN, TRIPLE FLOODS

PHOTOMETRY

lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight

Metalux

WNLED

LED

Uti l i ty LED Wraparound

SPECIFICATION FEATURES

Construction Housing consists of die formed cold rolled steel. Ends formed with the housing for strength and provisions for continuous row aligners. Steel end plates with 7/8” KO and light-seal embossment.

Driver cover can be removed without tools.

Controls WNLED is Powered by Fifth Light, with standard a 0-10V continuous dimming driver that works with any 0-10V control/ dimmer.

Combine with energy saving products like occupancy sensors, daylighting controls and lighting relay panels to maximize energy savings. Dimming range is 10% to 100%; varies by control device.

Electrical Long-Life LED system coupled with electrical driver to deliver optimal performance. LED’s available in 3000K, 3500K, 4000K and 5000K with a min. 80 CRI. Projected life at 70% lumen maintenance is nearly 150,000 hours with TM21 rating up to L88 > 60,000 hours. Electronic drivers are available for 120-277V applications. A 0-10V dimming driver is standard.

Emergency Battery Pack Option Optional 120V-277V integral emergency battery pack is available in 7-watts or 14-watts to meet critical life-safety lighting requirements. The 90-minute batteries provide constant power to the LED system, ensuring code compliance. The patented EZ Key prevents accidental discharge of the battery during construction.

Finish Multistage iron phosphate pretreatment ensures maximum bonding and rust inhibitor. High reflective paint after fabrication, baked white enamel finish is standard.

Channel/Wireway Cover Die formed heavy gauge steel.

Tight fit for ease of maintenance.

Shielding Acrylic, high performance, frost blend. Sides have inside linear prisms and bottom has pyramidal prisms for low brightness control.

Instal lation Fixture may be surface, pendant, or stem mounted. See accessories below for ordering information.

Compliance Indoor luminaires are cULus listed for 25ºC ambient environments, damp location listed, RoHS compliant, and LED modules comply with IESNA LM-79 and LM-80 standards. DesignLights Consortium® Qualified and classified for DLC Standard, refer to www.designlights.org for details.

Suitable for use in clothes closets when installed in accordance with the NEC 410.16 spacing requirements. Can be used for State of California Title 24 high efficacy luminaire.

Our updated WNLED series is a versatile utility based, traditionally styled LED wraparound series which can be used in a broad range of commercial, schools, institutional, retail and residential applications.

This high quality luminaire series utilizes the latest solid state LED lighting and advanced electronic driver technology which provides optimal lighting performance and maximizing energy savings. WNLED is designed to provide long service life eliminating re-lamping issues and minimizing maintenance common with traditional fluorescent.

DESCRIPTION

PS519062EN

February 8, 2019 2:59 PM

1-13/16" [46mm]

19" [483mm] 20-5/8" [523mm]

1-1/8" [29mm]

24" [610mm]

8-3/16" [208mm]

1" [25mm]1" [25mm]

6" [152mm]

7-5/8" [194mm]

2'

1-1/8" [29mm]

42-15/16" [1090mm] 44-1/2" [1131mm]1-13/16"

[46mm]

7/8" [22mm] K.O. (5)

Ground Screw Bump Ceiling Stand-Off Embossments

48" [1219mm]

42-7/16" [1078mm]

40-7/16" [1027mm]

3" [76mm]

4-1/2" [114mm]

6" [152mm]

7-5/8" [194mm]

4'

MOUNTING DATA

2-1/2" [63mm]

7-5/8" [194mm]

6" [152mm]

ENERGY AND PERFORMANCE DATA BY CATALOG NUMBER

Lumen Type Length Catalog Number

Nominal 3500K Lumens Wattage lm/W

Standard 2 ft. 2WNLED-LD4-28SL-F-UNV-L8XX-CD1-U 2786 27.5 101

Standard 4 ft. 4WNLED-LD4-32SL-F-UNV-L8XX-CD1-U 3298 28.0 118

Standard 4 ft. 4WNLED-LD4-40SL-F-UNV-L8XX-CD1-U 4062 36.0 113

Standard 4 ft. 4WNLED-LD4-50SL-F-UNV-L8XX-CD1-U 4966 46.6 107

California Title 24 Non-Residential

Compliant

Catalog #

Project

Comments

Prepared by

Type

Date lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight change without notice.

Eaton 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.eaton.com/lighting

WNLED

Catalog No. Wt.

2WNLED 5 lbs.

4WNLED 9 lbs.

SHIPPING DATA

Series (3)

WNLED=Utility LED Wraparound

S A M P L E N U M B E R : 4 W N L E D - L D 4 - 4 0 S L - F - U N V - L 8 4 0 - C D 1 - U

Packaging U=Unit Pack

Lamp Type

LD4=LED

LED Lumens Output

28SL=2800 (1)

32SL=3200

40SL=4000

50SL=5000

Voltage 347=347V (2)

480=480V (2)

UNV=Universal Voltage 120-277

Number of Drivers 1=1 Driver

Lens F=Frost Acrylic (standard)

Length 2=2 ft.

4=4 ft.

A C C E S S O R I E S SCF=Fixed Stem Set (Specify Length) SCS=Swivel Stem Set (Specify Length) SCA=Adjustable 48" Stem Set A1B/Spacer-U=Spacer 1-1/2" to 2-1/2" from ceiling (Use 2 per fixture) WN-2A-U=2' Replacement Lens WN-4A-U=4' Replacement Lens

NOTES: (1) 2 ft. model. (2) 4 ft. model only. (3) DesignLights Consortium® Qualified and classified for DLC Standard, refer to www.designlights.org for details. (4) With integral test switch/indicator/laser test. For approximate delivered lumens multiply the lumens per watt of the desired fixture by the wattage of the emergency battery pack (100 lm/W x 7=700 lumens). IES-format photometry for luminaire under emergency operation available.

(5) 5LTD DALI driver available for all lumen unit only. (6) Emergency options not available for 2 ft. versions. Requires larger cover which changes the appearance. (7) Emergency options use taller ballast cover that alters appearance.

Specifications & dimensions subject to change without notice. Consult your Eaton Representative for availability and ordering information.

Driver Type CD=0-10V Dimming Driver (10% - 100% Dimming)

Options Emergency (7)

CCT

L830=3000K L835=3500K L840=4000K L850=5000K

EL7W=7-watt, 120V-277V emergency battery pack installed (4), (6)

EL14W=14-watt 120V-277V emergency battery pack installed (4), (6)

ORDERING INFORMATION

4WNLED-LD4-32SL-

F-UNV-L835-CD1-U

Electronic Driver

Linear LED 3500K

Spacing criterion:

(II) 1.2 x mounting height, (⊥) 1.2 x mounting height

Lumens: 3298

Input Watts: 28.0W

Efficacy: 117.8 lm/W

Test Report:

4WNLED-LD4-32SL-F-

UNV-L835-CD1-U.IES

C a n d l e p owe r

Angle Along II 45° Across ⊥

1124 1124 1124 1124 1120 1116 1103 1102 1100 1069 1071 1071 1023 1029 1031 966 975 978 899 913 918 826 845 853 747 771 781 669 695 707 586 615 631 504 535 554 422 455 476 342 377 400 265 302 327 190 231 257 121 164 190 56 100 125 0 44 70

C o e ffi c i e n t s o f U t i l i z a t i o n

Effective floor cavity refl ectance 20% rc 80% 70% 50% 30% 10% 0% rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0

RCR

118 118 118 118 114 114 114 114 108 108 108 102 102 102 97 97 97 94 107 102 97 93 103 99 95 91 94 90 87 89 86 84 84 82 80 78 97 89 82 76 94 86 80 74 82 76 72 78 73 69 74 70 67 64 88 78 69 63 85 76 68 62 72 65 60 68 63 58 65 60 57 54 81 69 60 53 78 67 59 53 64 57 51 61 55 50 58 53 49 46 74 62 52 46 72 60 52 45 57 50 44 55 48 43 52 47 42 40 69 55 46 40 66 54 46 40 52 44 39 50 43 38 47 42 37 35 64 50 41 35 62 49 41 35 47 40 34 45 39 34 43 38 33 31 59 46 37 32 57 45 37 31 43 36 31 41 35 30 40 34 30 28 55 42 34 28 54 41 33 28 40 33 28 38 32 27 37 31 27 25 52 39 31 26 50 38 31 26 37 30 25 35 29 25 34 29 24 23

Z o n a l L u m e n S u m m a r y

Zone Lumens % Fixture 0-30

0-40

0-60

0-90

0-180

855 25.9

1381 41.9

2390 72.5

3109 94.3

3298 100.0

0˚ 15˚ 30˚

45˚

60˚

75˚

90˚

PHOTOMETRICS

4WNLED-LD4-40SL-

F-UNV-L835-CD1-U

Electronic Driver

Linear LED 3500K

Spacing criterion:

(II) 1.2 x mounting height, (⊥) 1.2 x mounting height

Lumens: 4062

Input Watts: 36.0W

Effi cacy: 112.8 lm/W

Test Report:

4WNLED-LD4-

40SL-F-UNV-L835-

CD1-U.IES

C a n d l e p owe r

Angle Along II 45° Across ⊥

1386 1386 1386 1385 1380 1375 1360 1357 1354 1318 1320 1320 1261 1266 1268 1190 1201 1203 1109 1125 1128 1018 1042 1048 922 951 964 823 857 868 721 759 773 620 660 678 521 561 584 421 464 492 326 372 403 234 285 317 148 201 233 70 123 154 1 57 89

C o e ffi c i e n t s o f U t i l i z a t i o n

Effective fl oor cavity refl ectance 20% rc 80% 70% 50% 30% 10% 0% rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0

RCR

118 118 118 118 114 114 114 114 108 108 108 102 102 102 97 97 97 94 107 102 97 93 103 99 95 91 94 90 87 89 86 84 84 82 80 78 97 89 82 76 94 86 80 74 82 76 72 78 73 69 74 70 67 64 88 78 69 63 85 76 68 62 72 65 60 68 63 58 65 61 57 54 81 69 60 53 78 67 59 53 64 57 51 61 55 50 58 53 49 46 74 62 52 46 72 60 52 45 57 50 44 55 48 43 52 47 42 40 69 55 46 40 66 54 46 40 52 44 39 50 43 38 47 42 37 35 64 50 41 35 62 49 41 35 47 40 34 45 39 34 43 38 33 31 59 46 37 32 57 45 37 31 43 36 31 41 35 30 40 34 30 28 55 42 34 28 54 41 33 28 40 33 28 38 32 27 37 31 27 25 52 39 31 26 50 38 31 26 37 30 25 35 29 25 34 29 24 23

Z o n a l L u m e n S u m m a r y

Zone Lumens % Fixture 0-30

0-40

0-60

0-90

0-180

1054 25.9

1702 41.9

2945 72.5

3832 94.3

4062 100.0

0˚ 15˚ 30˚

45˚

60˚

75˚

90˚

Approximate Color Temperature Multiplier

5000K 1.03

4000K 1.00

3000K 0.98

CCT TABLE

PS519062EN

February 8, 2019 2:59 PM lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Text Box NOTE: Dimming control is not provided however fixture has that ability for future.

Metalux

WSNLED

LED

Premium LED Wraparound

SPECIFICATION FEATURES

Construction Housing consists of die formed cold rolled steel. Ends formed with the housing for strength and provisions for continuous row aligners. Steel end plates with 7/8” KO and light-seal embossment.

Driver cover can be removed without tools.

Controls WSNLED is Powered by Fifth Light, with standard a 0-10V continuous dimming driver that works with any 0-10V control/ dimmer. Combine with energy saving products like occupancy sensors, daylighting controls and lighting relay panels to maximize energy savings.

Dimming range is 10% to 100%;

varies by control device. Other driver options include step-dim or, go fully digital with the Digital Addressable Lighting Interface (DALI) drivers.

Electrical Long-Life LED system coupled with electrical driver to deliver optimal performance. LED’s available in 3000K, 3500K, 4000K and 5000K with a min. 80 CRI. Projected life at 70% lumen maintenance is nearly 150,000 hours with TM21 rating up to L87 > 60,000 hours. Electronic drivers are available for 120-277V applications. A 0-10V dimming driver is standard.

Emergency Battery Pack Option Optional 120V-277V integral emergency battery pack is available in 7-watts or 14-watts to meet critical life-safety lighting requirements. The 90-minute batteries provide constant power to the LED system, ensuring code compliance. The patented EZ Key prevents accidental discharge of the battery during construction.

Finish Die formed heavy gauge steel.

Tight fit for ease of maintenance.

Channel/Wireway Cover Die formed heavy gauge steel.

Tight fit for ease of maintenance.

Shielding Acrylic end caps with a frost finish to improve aesthetics and illumination. Clear acrylic lens coupled with LED optical materials providing superior brightness control while improving overall light distribution and aesthetics.

This distribution is further enhanced through the use of embedded prisms within the lens on both side and bottom.

Instal lation Fixture may be surface, pendant, or stem mounted. See accessories below for ordering information.

Compliance Indoor luminaires are cULus listed for 25ºC ambient environments, damp location listed, RoHS compliant, and LED modules comply with IESNA LM-79 and LM-80 standards. DesignLights Consortium® Qualified and classified for DLC Standard, refer to www.designlights.org for details.

Suitable for use in clothes closets when installed in accordance with the NEC 410.16 spacing requirements. Can be used for State of California Title 24 high efficacy luminaire.

WSNLED is a premium featured, traditionally styled LED wraparound series which can be used in a broad range of commercial, institutional, retail and industrial applications. This newly designed platform is a high quality luminaire utilizing Eaton's latest solid state lighting and electronic driver technologies offering superior aesthetics, optimal optical performance and energy efficiency.