Pre-engineered/Modular style Bathroom, Shower and Laundry Facility
Solicitation number
FA480925Q0106
Issued by

About this file

This document is an Attachment specifying detailed facility characteristics for a pre-engineered/modular bathroom, shower, and laundry facility for Seymour Johnson Air Force Base. The facility must be at least 600 square feet, designed to withstand 123 MPH wind speeds, and include four private bathrooms (with one fully ADA compliant), a laundry room with two stacked washer/dryer units, and specific accessibility requirements. Key structural and functional specifications include an insulated standing seam metal roof, LED lighting with occupancy sensors, outdoor spigots, HVAC, proper electrical distribution, porcelain bathroom fixtures, and comprehensive accessibility features complying with federal standards.

The procurement is a nonappropriated fund purchase for the Air Force Air Combat Command, not involving federal tax dollars. The solicitation (FA480925Q0106) requires contractors to complete interior plumbing, electrical, and HVAC work, with the end user providing foundation and utility connections. Prospective offerors must submit questions by 9:00 AM Eastern Daylight Time on 28 August 2025, with careful attention to instructions and evaluation criteria to ensure proposal eligibility. The facility is intended to be enduring, not temporary, with a preference for a single unified structure that can be crane-deployed onto the provided foundation.

View the file

Other files

File Type Posted
Attachment 6 - PPQ.docx DOCX document
Attachment 6 - PPQ.docx DOCX document
Attachment 3 Price Schedule.xlsx XLSX spreadsheet
Attachment 5 WD 2015-4397 Rev 30 8 July 2025.docx DOCX document
Attachment 2 Instructions to offerors and eval.docx DOCX document
Attachment 1 Nonappropriated Fund Standard Clauses 30 May 2025.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA480925Q0106

Attachment 4

Pre-engineered/Modular style Bathroom, Shower and Laundry Facility Requirements 12 August 2025

The Contractor shall complete all plumbing, electrical, and HVAC to the interior of the facility and stub out. The end user will provide for/connect building utilities to on-site hookups and provide foundation for facility to be set onto. The intent is for the facility to be enduring. No temporary facilities/trailers. Preference is for one facility. The Contractor shall crane or set building on end user provided foundation upon delivery.

STRUCTURE

-Designed to withstand 123 MPH wind speed or higher.

-Facility must be at least 600SF.

-Small storage closet (~36SF) If the water heater or HVAC return is co-located minimum 64 sq ft.

- Opaque windows -Interior must have durable, washable/wipeable walls. (IAW NFPA 1194) -Interior must have durable, waterproof flooring (IAW NFPA 1194) -Insulated Wall and ceiling

- Exterior Doors - insulated steel door units

PLUMBING FIXTURES AND ACCESSORIES

-Must have at least 4 private bathrooms to include, toilet (ADA height IAW NFPA 1194), sink/vanity with mirror and shower (see accessibility requirements below). (at least one bathroom must meet all ADA requirements). All bathroom fixtures shall be porcelain. All flush valves and faucets shall be chrome. Provide flush valves at flushing fixtures. Provide/install one towel dispenser and one toilet paper holder per bathroom.

- Laundry room must be large enough for 2 washers (IAW ABAAS F214 & 611) and 2 dryers (IAW ABAAS F214 & 611) (Stacked units) with an open space large enough for folding laundry (for table ~32"x16") and Wi-Fi cabinet (Approximately 15" x 9" wall mounted).

- Floor drains in each shower and in each bathroom area for ease of cleaning (I.e. pressure washing as needed) -Outdoor spigot and outdoor freeze proof shower head.

- Size water heater and provide expansion tank as required per NC Building Code.

HVAC

-Provide HVAC to the facility.

-Facility must have proper ventilation (i.e exhaust fan in bathrooms IAW NFPA 1194)

ELECTRICAL

- Properly sized distribution panel to support proposed electrical requirements.

-LED lighting (with occupancy sensors) -Outdoor LED lighting between each door on the facility and on ends of the building -Minimum of 2 AFCI outlets in each bathroom.

-Minimum of 4 outdoor outlets.

ROOF

-Standing Seam Metal Roof (SSMR), 24 gauge.

Accessibility Requirements All comfort stations must comply with federal accessibility standards. These requirements determine architectural elements, such as door width and placement, stall size, and height of fixtures. They also affect siting requirements related to slope, distance, and the surface material of parking lots and sidewalks accessing the restroom. If existing comfort station buildings cannot be made accessible, then a second accessible comfort station could be constructed adjacent to the original comfort station to provide an accessible option, or signage directing visitors to the nearest accessible facility can be installed until the building can be replaced. Ensure the following amenities are within reach: toilet, toilet paper dispenser, faucet, soap dispenser, hand dryer, and waste receptacle. In addition, make floors to comfort stations flush (vertically) with the material outside of the comfort station to facilitate smoother ease on wheelchairs.

Comfort stations can be the most complicated facilities for accessibility because there are many codes associated with restrooms and restroom fixtures, including the following:

ICC ANSI 603.2.1 Turning Space (clearances). A turning space is provided within the room, 5'-7" (67") diameter minimum for new facilities or 5' (60") for existing facilities. The required turning space is not provided within a toilet compartment. See Accessible Routes checklist for more detailed standards.

Concession run campgrounds operate under the Concessions Periodic Evaluation Program, which includes standards that must be met for campgrounds including comfort stations. See: https://www.nps.gov/subjects/concessions/upload/Campground_Standards.pdf ABAAS 603.2.2 Door Swing (clearances). Doors do not swing into the clear floor space or clearance required for any fixture. Doors are permitted to swing into the required turning space. EXCEP-TION: Where the toilet room is for individual use and an accessible clear floor space is provided within the room beyond the arc of the door swing, doors are permitted to swing into the clear floor space or clearance required for any fixture.

ABAAS 603.3 Mirrors. Mirrors located above lavatories are installed with the bottom edge of the reflecting surfaces 3'-4" (40") maximum above the finished floor. Mirrors not located above countertops with lavatories are installed with the bottom edge of the reflecting surfaces 3'-4" (40") maximum above the finished floor. EXCEPTION: Other than within accessible dwelling or sleeping units, mirrors are not required over lavatories or counters if a mirror is located within the same toilet or bathing room and mounted with the bottom edge of the reflecting surfaces 2'-11" (35") maximum above the finished floor.

ABAAS 603.4 Coat Hooks and Shelves and 604.8.3 Coat Hooks and Shelves. Coat hooks are located between 1'-3" and 4' (15" and 48") above the finished floor. Shelves are located between 3'-4" and 4' (40" and 48") above the finished floor.

ABAAS 603.5 Diaper Changing Tables. Diaper changing tables are accessible to a user in a wheelchair. The top of the changing station is between 2'-4" and 2'-10" (28" and 34") above the floor, with 2'-3" (27") minimum knee clearance space under the surface. Clear floor space is provided at changing station, 2'-4" by 4'-4" (30"by 52") for new facilities or 2'-6" by 4' (30" by 48") for existing facilities from a forward approach with a 2% maximum slope in any direction on a stable, firm, and slip resistant surface.

ICC ANSI 603.6 Operable Parts. Operable parts on towel dispensers and hand dryers serving accessible lavatories are operable with one hand and do not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts is 5 pounds maximum. Reach ranges comply with Table 603.6.

ICC ANSI 606.2 Clear Floor Space. A clear floor space is provided at lavatories and sinks, 2'-6" by 4' (30" by 48") minimum for existing facilities or 2'-6" by 4'-4" (30" by 52") minimum for new facilities from a forward approach, with 2'-3" (27") minimum knee clearance and 9" toe clearance. EXCEPTION: No more than one bowl of a multi-bowl sink is required to provide accessible knee and toe clearance.

ABAAS 606.3 Height. Lavatories and sinks have rims 2'-10" (34") maximum above the finished floor.

ABAAS 606.4 Faucets. Controls for faucets are operable with one hand without tight grasping, pinching, or twisting of the wrist, and operable with no more than 5 pounds of force. Hand-operated metering faucets remain open for 10 seconds minimum. EXCEPTION: Automatic faucets are not required to comply with section 309 provided that the reach depth to activate the faucets and the reach depth to the water flow is 11" maximum.

ICC ANSI 606.5 Lavatories with enhanced reach range. Where enhanced reach range is required at lavatories, faucets and soap dispenser controls have a reach depth of 11" maximum. Water and soap outlets are provided with a reach depth of 11" maximum. The lavatory is 2'-10" (34") maximum above the finished floor, measured to the higher of the rim or counter surface. EXCEPTIONS: Enhanced reach range faucets and soap dispensers are not required on lavatories pro-vided with automatic faucets and dispensers where the reach depth to activate them is 11" maximum.

ABAAS 606.6 Exposed Pipes and Surfaces. Water supply and drainpipes under lavatories and sinks are insulated or otherwise configured to protect against contact. There are no sharp or abrasive surfaces underneath lavatories and sinks.

ABAAS 604.2 Location and 604.9.1 Location. The water closet in wheelchair compartments and ambulatory compartments has a wall or partition to the rear and to one side. The partition, except in ambulatory toilet compartments where it is between 1'-5" and 1'-7" (17" and 19") from the side wall or partition.

ABAAS 604.3.1 Clearance Width and 604.3.2 Clearance Depth. Clearance around the water closet is 5' (60") minimum measured perpendicular from the side wall and 4'-8" (56") minimum measured perpendicular from the rear wall.

ABAAS 604.3.3 Clearance Overlap. The required clearance around the toilet is permitted to overlap the toilet, grab bars, dispensers, coat hooks, shelves, accessible routes, clear floor space, turning space, and clearances required at other fixtures. No other fixtures or obstructions are located within the required water closet clearance. See figure 604.3.

ABAAS 604.4 Height. The seat height of the toilet is between 1'-5" and 1'-7" (17" and 19") measured to the top of the seat.

ABAAS 604.5 Grab Bars. Grab bars for water closets are accessible and provided on the side wall closest to the toilet and on the rear wall.

ABAAS 604.5.1.1 Side Wall Horizontal Grab Bar. The side wall horizontal grab bar is 3'-6" (42") long minimum, located 1' (12") maximum from the rear wall and extending 4'-8" (54") minimum from the rear wall.

ICC ANSI 604.5.1.2 Side Wall Vertical Grab Bar. The side wall vertical grab bar is 1'-6" (18") long minimum, with the bottom of the bar located between 3'-3" and 3'-5" (39" and 41") above the floor, and with the center line of the bar located between 3'-3" and 3'-5" (39" and 41") from the rear wall.

ABAAS 604.5.2 Rear Wall. The rear wall grab bar is 3' (36") long minimum, located 6" maximum from the side wall, and extends 3'-6" (42") minimum from the side wall. EXCEPTION: The rear grab bar is permitted to be 2' (24") long minimum, centered on the toilet, where wall space does not permit a length of 3' (36") minimum due to the location of a recessed fixture adjacent to the toilet.

ABAAS 604.6 Flush Controls. Flush controls are hand-operated or automatic and located between 1'-3" and 4' (15" and 48") above the floor. They are located on the open side of the water closet except in ambulatory accessible compartments where they can be located on either side of the water closet.

ABAAS 604.7 Dispensers. Toilet paper dispensers are operable with one hand. Where the dispenser is located above the grab bar, the outlet of the dispenser shall be located between 2' and 3' (24" and 36") from the rear wall. Where the dispenser is located below the grab bar, the outlet of the dispenser is between 1'-6" and 4' (18" and 48") above the floor. EXCEPTION: Toilet paper dispensers that accommodate a maximum of two toilet paper rolls of not more than 5-inch diameter each are permitted to be located between 7" and 9" in front of the of the water closet measured to the centerline of the dispenser. Toilet paper dispenser must not interfere with the use of the grab bar.