This document provides details for a sole source procurement solicitation to rehabilitate transformers and poles for the Bureau of Reclamation. The solicitation issued by the Department of the Interior Bureau of Reclamation is for informational purposes only and intends to award a sole source contract to Sierra Electric Cooperative, Inc. The requirement is for Sierra Electric Cooperative, Inc. to rehab transformers and poles owned by the cooperative in the Dam Site area of the Elephant Butte Historic District. No response date, award date, or pricing terms are included.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

Existing 480/277V MDP Panel

Transformer T1 Panelboard L1A Panelboard D1A

PAD 2

Transformer T2 Panelboard L1B

PAD 3

Transformer T3 Panelboard L1C

PAD 4

Transformer T4 Panelboard L1D

PAD 5

UGE RV park 1

UGE RV park 3

UGE RV park 2

480V lift station service

PAD 6

Mini power center L3A Panelboard D3A

PAD 1

DC Fast Charger 1

Existing 500kVA Utility transformer

DC Fast Charger 2

14,400V-240/120V Utility Single-Phase Transformer Panelboard D2A

PAD 7

503+06

500+00

604+16

600+00

703+20

700+00

800+00

802+82

111+12

0+

5+

110+00

RV Utility Hookup Pedestal (see 60185)

Construction Prohibited Area

Future contract Comfort Station

REFERENCE DRAWINGS

RV CONNECTION ELECTRICAL,SEWER, &

WATER 24-D-60185

CASITA SINGLE LNE DIAGRAM 24-D-60193

RV PARK SINGLE LINE DIAGRAM 24-D-60194

CHARGING STATION SINGLE LINE DIAGRAM 24-D-60195

SITE LIGHTING PLAN 24-D-60201

Point Table

Pad #

Northing

782294.19

782124.31

781913.60

781611.78

781416.53

781531.54

780934.31

Easting

2921489.93

2921957.98

2922146.82

2922267.88

2922320.12

2922337.13

2922094.71

EXPLANATION

DEVICE LOCATION DESCRIPTION

D1A CASITAS 3

AND 4

480V PANELBOARD FOR T1, T2, T3,

AND T4

D2A RV PARK 240/120V PANELBOARD FOR RV

SITES

D3A LODGE/REST-

AURANT 480V PANELBOARD FOR L3A

L1A CASITAS 3

240/120V PANELBOARD FEEDS

CASITAS 1 THRU 5

L1B CASITAS 8

AND 9

CASITAS 6 THRU 10

L1C CASITAS 13

AND 14

CASITAS 11 THRU 13 AND RV SITES

1 AND 2

L1D ACROSS

CASITA 16

CASITAS 14 THRU 17 AND RV SITE 3

AND NEW LIGHT POLES

L3A LODGE/REST-

AURANT

FEEDS CHARGING STATION AND

LIGHTS

MDP WELCOME

CENTER 480V MAIN DISTRIBUTION CENTER

PAD 1 LODGE/REST-

AURANT

ELECTRICAL/FIBER UTILITY PAD IN

RESTAURANT AREA AND LIGHTS

PAD 2 CASITAS 3

ELECTRICAL/FIBER UTILITY PAD TO

FEED CASITAS 1-5

PAD 3 CASITAS 8

ELECTRICAL/FIBER UTILITY PAD TO

FEED CASITAS 6-10

PAD 4 CASITAS 13

ELECTRICAL PAD TO FEED CASITAS

11-13 AND RV SITES 1 AND 2

PAD 5 ACROSS

ELECTRICAL PAD ITO FEED CASITAS

14-17, RV SITE 3, AND LIGHTS

PAD 6 LIFT STATION FEEDS LIFT STATION AND NETWORK

SWITCH

PAD 7 RV PARK ELECTRICAL/FIBER UTILITY PAD IN

RV PARK AREA

T1 CASITAS 3

480-240/120V TRANSFORMER FEEDS

L1A

T2 CASITAS 8

L1B

T3 CASITAS 13

L1C

T4 ACROSS

L1D

DESIGNED

DRAWN

CHECKED

TECH. APPR.

APPROVED

PEER REVIEWER -

Lisa Billy

Donna Johnson

A

LW

YS

T H

IN

K

S

FE

TY

SHEET

D

C

B

U

R

EA

O

F

EC

LA

M

TI

N

.S

EP

TM

EN

TH

E

TE

IO

ut oC

4.

0S

LM

IL

-D -6

-R

-1 .D

W G

V

ED

-0 9-

Y

EK

PR

JE

EL

TT

PO

ER

TO

IV

IS

ES

IR

IC

TR

LI

EM

ELECTRICAL

SITE PLAN

DENVER, CO

24-D-60192

PLAN

1" = 100'

NOTES

1. DC Fast Charger locations will be finalized in field in coordination with COR.

2. RV Pedestal locations as shown.

3. For site lighting see drawing 24-D-60201

0 100' 200'

AutoCAD SHX Text

AutoCAD SHX Text lbilly

Typewritten Text

Supervisory Electrical Engineer

Electrical Engineer

Rectangle

Callout

Approximate utility transformer location, 3-phase

Callout

Approximate utility transformer location, 1-phase

Rectangle

3 PHASE - 4 WIRE

500KVA

24.94 kV - 480Y/277 V

200:5A

800A

GFP

600A

(NEW)

200A

400A

400A

MARINA RESTAURANT

SWITCHBOARD MDP (EXISTING)

KW METER

SPARE SPARE SPARE

D1A-1

125A

D1A (NEW)

T2 (NEW)

1 PHASE

50KVA

480-240/120 V

T3 (NEW)

75KVA

T4 (NEW)

75KVA

D1A-2

125A

D1A-3

D1A-5

LIFT STATION

(EXISTING)

D1A-4

40A

L1D

L1C

L1B

L1A

SEE DRAWING

24-D-60196

T1 (NEW)

50KVA

3 4 5 76

8 9 10 11

10HP

800A, 480/277V, 3-PHASE, 14 kAIC

600A, 480V, 3-PHASE, 10 kAIC

UTILITY TRANSFORMER

(EXISTING)

KW METER KW METER

DS1

25A

1. 100A main service panels at Casitas not in drawing.

2. Existing kWh meters on Marina and Restaurant services in

MDP are Leviton 2000 Series.

3. Transformer 1 and Panel L1A feed Casitas 1 thru 5.

4. Transformer 2 and Panel L1B feed Casitas 6 thru 10.

5. Transformer 3 and Panel L1C feed Casitas 11 thru 13, RV sites 1 and 2.

6. Transformer 4 and Panel L1D feed Casitas 14 thru 17, RV site

3, and two new light poles by the boat entrance.

7. Provide RMC prior to above grade. Elbow, vertical run, and above grade conduit shall be RMC. Provide Schedule 80 PVC for buried conduit.

8. Fused disconnect switch at Pad 6 with grounding electrode and ground rod.

D1A PAD 2 480V DISTRIBUTION PANEL

DS1 PAD 6 FUSED DISCONNECT SWITCH FOR

LIFT STATION SERVICE

L1A PAD 2 240/120V PANEL

L1B PAD 3 240/120V PANEL

L1C PAD 4 240/120V PANEL

L1D PAD 5 240/120V PANEL

MDP WELCOME

CENTER 480V DISTRIBUTION PANEL

T1 PAD 2 240/120V TRANSFORMER

T2 PAD 3 240/120V TRANSFORMER

T3 PAD 4 240/120V TRANSFORMER

T4 PAD 5 240/120V TRANSFORMER

ELECTRICAL SITE PLAN 24-D-60192

CASITAS CABLE AND CONDUIT SCHEDULE 24-D-60199

CASITAS PANEL SCHEDULES 24-D-60196

CASITAS AND RV PARK PANEL SCHEDULES 24-D-60197

LEGEND

FEEDER NUMBER

LB

LY

CASITAS

SINGLE LINE DIAGRAM

24-D-60193

Donna Johnson P.E.

ra ft

Sheets and Views

22 x 34

2023-09-19T04:56:36-0600

ERIC MENDLIN

2023-09-19T06:08:08-0600

JOHN KELLY

1-PHASE, 3 WIRE

167KVA

14.4kV - 240/120 V

D2A (NEW)

700A, 240/120V, SINGLE PHASE,

10kAIC

24-D-60197

800:5A

KW METER NOTES

1. Provide RMC prior to above grade. Elbow, vertical run, and

D2A PAD 7 240V DISTRIBUTION PANEL

RV PARK AND CHARGING STATIONS CABLE AND

CONDUIT SCHEDULE 24-D-60200

CASITA AND RV PARK PANEL SCHEDULES 24-D-60197

RV PARK

24-D-60194

Donna Johnson, P.E.

Sheets and Views

22 x 34

FEEDER NUMBER: Off

ARow1:

A:

2023-09-19T04:59:55-0600

ERIC MENDLIN

2023-09-19T06:09:31-0600

JOHN KELLY

3-PHASE

150KVA

24.94KV-480/277V

T5 (NEW)

15kVA 480-208/120V

3 PHASE - 4 WIRE

250A

25A

50A3

100A

24-D-60198

DC Charger

D3A (NEW)

L3A (NEW)

100A, 208/120V, 3-PHASE, 10

kAIC

100A

3 DC Charger

250A, 480/277V, 3-PHASE, 10 kAIC

250:5A

KW METER

D3A PAD 1 NEW DISTRIBUTION PANEL

L3A PAD 1 15kVA MINI POWER CENTER

1. Provide RMC prior to above grade. Elbow, vertical run, and above grade conduit shall be RMC. Provide Schedule 80 PVC for buried conduit.

RV PARK AND CHARGING STATIONS CABLE AND

CONDUIT SCHEDULE 24-D-60200

CHARGING STATIONS PANEL SCHEDULE 24-D-60198

CHARGING STATIONS

24-D-60195

Sheets and Views

22 x 34

2023-09-19T04:58:37-0600

ERIC MENDLIN

2023-09-19T06:09:47-0600

JOHN KELLY

CASITAS SINGLE LINE DIAGRAM 24-D-60193

AL

AY

SA

¦D_DT¦

¦STATUS¦

PANEL SCHEDULES

PEER REVIEWER

£TT£

£AT£

£AA£

£TA£

- Electrical Engineer

Sheets and Views

22 x 34

2023-09-19T04:58:20-0600

ERIC MENDLIN

2023-09-19T06:10:06-0600

JOHN KELLY

CASITAS AND RV PARK

PANEL SCHEDLUES

24-D-60197

1. Conductors feeding panelboard D1A are rated for 570A. Per

National Electric Code, the load on this panel shall be less than 570A.

Sheets and Views

22 x 34

2023-09-19T04:56:03-0600

ERIC MENDLIN

2023-09-19T06:10:25-0600

JOHN KELLY

SITE LIGHTING PLAN 24-D-60201

CHARGING STATIONS SINGLE LINE DIAGRAM 24-D-60195

1. Spare for Comfort Station in L3A Panelboard.

CHARGING STATIONS

PANEL SCHEDULES

24-D-60198

Sheets and Views

22 x 34

2023-09-19T04:56:57-0600

ERIC MENDLIN

2023-09-19T06:10:41-0600

JOHN KELLY

CABLE AND CONDUIT SCHEDULE

FEEDER

NUMBER

CONDUIT SIZE

-TYPE CONDUCTORS PURPOSE ORIGIN DESTINATION NOTES

1 DIRECT BURIED 3[1 - 350MCM + 3/0 AWG-G] SERVICE ENTRANCE SECTION UTILITY TRANSFORMER

SECONDARY PANELBOARD MDP EXISTING SERVICE ENTRANCE

2 2 [3" - PVC SCH 80] 2[3 - 300MCM + 1 AWG-G] 480V SERVICE TO D1A PANELBOARD MDP PANELBOARD D1A TRANSITION TO RMC PRIOR TO VERTICAL BEND

3 1.5" - PVC SCH 80 3 - 1 AWG + 6 AWG-G POWER TO TRANSFORMER T1 D1A TRANSFORMER T1 TRANSITION TO RMC PRIOR TO VERTICAL BEND

4 1.5" - PVC SCH 80 3 - 1 AWG + 6 AWG-G POWER TO TRANSFORMER T2 D1A TRANSFORMER T2 TRANSITION TO RMC PRIOR TO VERTICAL BEND

5 2.5" - PVC SCH 80 3 - 3/0 AWG + 6 AWG-G POWER TO TRANSFORMER T3 D1A TRANSFORMER T3 TRANSITION TO RMC PRIOR TO VERTICAL BEND

6 1.5" - PVC SCH 80 3 - 6 AWG + 8 AWG-G POWER TO LIFT STATION PANELBOARD D1A LIFT STATION TRANSITION TO RMC PRIOR TO VERTICAL BEND

7 3" - PVC SCH 80 3 - 3/0 AWG + 6 AWG-G POWER TO TRANSFORMER T4 D1A TRANSFORMER T4 TRANSITION TO RMC PRIOR TO VERTICAL BEND

8 2.5" - LFMC 3 - 4/0 AWG + 2 AWG-G POWER TO PANEL L1A T1 L1A TRANSITION TO RMC PRIOR TO VERTICAL BEND

9 2.5" - LFMC 3 - 4/0 AWG + 2 AWG-G POWER TO PANEL L1B T2 L1B TRANSITION TO RMC PRIOR TO VERTICAL BEND

10 3" - LFMC 3 - 500 MCM + 1/0 AWG-G POWER TO PANEL L1C T3 L1C TRANSITION TO RMC PRIOR TO VERTICAL BEND

11 3" - LFMC 3 - 500 MCM + 1/0 AWG-G POWER TO PANEL L1D T4 L1D TRANSITION TO RMC PRIOR TO VERTICAL BEND

12 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 1 POWER L1A EXISTING CASITA 1 SERVICE

PANEL TRANSITION TO RMC PRIOR TO VERTICAL BEND

13 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 2 POWER L1A EXISTING CASITA 2 SERVICE

14 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 3 POWER L1A EXISTING CASITA 3 SERVICE

15 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 4 POWER L1A EXISTING CASITA 4 SERVICE

16 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 5 POWER L1A EXISTING CASITA 5 SERVICE

17 0.75" - RMC 2 - 12 AWG + 12 AWG-G ISP ACCESS POINT POWER L1A ISP ACCESS POINT TRANSITION TO RMC PRIOR TO VERTICAL BEND

18 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 6 POWER L1B EXISTING CASITA 6 SERVICE

19 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 7 POWER L1B EXISTING CASITA 7 SERVICE

20 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 8 POWER L1B EXISTING CASITA 8 SERVICE

21 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 9 POWER L1B EXISTING CASITA 9 SERVICE

22 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 10 POWER L1B EXISTING CASITA 10 SERVICE

23 0.75" - RMC 2 - 12 AWG + 12 AWG-G ISP ACCESS POINT POWER L1B ISP ACCESS POINT TRANSITION TO RMC PRIOR TO VERTICAL BEND

24 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 11 POWER L1C EXISTING CASITA 11 SERVICE

25 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 12 POWER L1C EXISTING CASITA 12 SERVICE

26 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 13 POWER L1C EXISTING CASITA 13 SERVICE

27 1.5" - PVC SCH 80 3 - 4 AWG + 8-AWG-G RV SITE 1 POWER L1C RV SITE 1 PEDESTAL TRANSITION TO RMC PRIOR TO VERTICAL BEND

28 1.5" - PVC SCH 80 3 - 4 AWG + 8-AWG-G RV SITE 2 POWER L1C RV SITE 2 PEDESTAL TRANSITION TO RMC PRIOR TO VERTICAL BEND

29 1.5" - PVC SCH 80 3 - 4 AWG + 8-AWG-G RV SITE 3 POWER L1D RV SITE 3 PEDESTAL TRANSITION TO RMC PRIOR TO VERTICAL BEND

30 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 14 POWER L1D EXISTING CASITA 14 SERVICE

31 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 15 POWER L1D EXISTING CASITA 15 SERVICE

32 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 16 POWER L1D EXISTING CASITA 16 SERVICE

33 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 17 POWER L1D EXISTING CASITA 17 SERVICE

34 0.75" - RMC 2 - 12 AWG + 12 AWG-G ISP ACCESS POINT POWER L1D ISP ACCESS POINT TRANSITION TO RMC PRIOR TO VERTICAL BEND

CABLE AND CONDUIT

SCHEDULE

24-D-60199

1. Panelboard MDP is existing, feeder conduit and conductor to exit side of MDP panelboard and proceed below grade to Panelboard D1A.

2. Provide RMC prior to above grade. Elbow, vertical run and

Sheets and Views

22 x 34

2023-09-19T04:57:47-0600

ERIC MENDLIN

2023-09-19T06:10:57-0600

JOHN KELLY

CHARGING STATIONS SINGLE LINE DIAGRAM 24-D-60195

CABLE AND CONDUIT SCHEDULE

FEEDER

NUMBER

CONDUIT SIZE

-TYPE CONDUCTORS PURPOSE ORIGIN DESTINATION NOTES

35 2 [3" - PVC SCH 80] 2[3 - 400MCM] + 2/0 AWG-G] RV PARK FEED UTILITY TRANSFORMER PANELBOARD D2A TRANSITION TO RMC PRIOR TO VERTICAL BEND

36 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 4 POWER D2A RV SITE 4 TRANSITION TO RMC PRIOR TO VERTICAL BEND

37 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 5 POWER D2A RV SITE 5 TRANSITION TO RMC PRIOR TO VERTICAL BEND

38 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 6 POWER D2A RV SITE 6 TRANSITION TO RMC PRIOR TO VERTICAL BEND

39 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 7 POWER D2A RV SITE 7 TRANSITION TO RMC PRIOR TO VERTICAL BEND

40 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 8 POWER D2A RV SITE 8 TRANSITION TO RMC PRIOR TO VERTICAL BEND

41 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 9 POWER D2A RV SITE 9 TRANSITION TO RMC PRIOR TO VERTICAL BEND

42 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 10 POWER D2A RV SITE 10 TRANSITION TO RMC PRIOR TO VERTICAL BEND

43 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 11 POWER D2A RV SITE 11 TRANSITION TO RMC PRIOR TO VERTICAL BEND

44 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 12 POWER D2A RV SITE 12 TRANSITION TO RMC PRIOR TO VERTICAL BEND

45 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 13 POWER D2A RV SITE 13 TRANSITION TO RMC PRIOR TO VERTICAL BEND

46 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 14 POWER D2A RV SITE 14 TRANSITION TO RMC PRIOR TO VERTICAL BEND

47 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 15 POWER D2A RV SITE 15 TRANSITION TO RMC PRIOR TO VERTICAL BEND

48 1" - PVC SCH 80 2 - 12 AWG + 12-AWG-G LIGHT POLES 1, 2, 3 POWER D2A LIGHT POLES TRANSITION TO RMC PRIOR TO VERTICAL BEND

49 1" - PVC SCH 80 2 - 12 AWG + 12-AWG-G LIGHT POLES 4, 5, 6 POWER D2A LIGHT POLES TRANSITION TO RMC PRIOR TO VERTICAL BEND

50 0.75" - RMC 2 - 12 AWG + 12-AWG-G ISP ACCESS POINT POWER D2A ISP ACCESS POINT TRANSITION TO RMC PRIOR TO VERTICAL BEND

51 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 16 POWER D2A RV SITE 16 TRANSITION TO RMC PRIOR TO VERTICAL BEND

52 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 17 POWER D2A RV SITE 17 TRANSITION TO RMC PRIOR TO VERTICAL BEND

53 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 18 POWER D2A RV SITE 18 TRANSITION TO RMC PRIOR TO VERTICAL BEND

54 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 19 POWER D2A RV SITE 19 TRANSITION TO RMC PRIOR TO VERTICAL BEND

55 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 20 POWER D2A RV SITE 20 TRANSITION TO RMC PRIOR TO VERTICAL BEND

56 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 21 POWER D2A RV SITE 21 TRANSITION TO RMC PRIOR TO VERTICAL BEND

57 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 22 POWER D2A RV SITE 22 TRANSITION TO RMC PRIOR TO VERTICAL BEND

58 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 23 POWER D2A RV SITE 23 TRANSITION TO RMC PRIOR TO VERTICAL BEND

59 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 24 POWER D2A RV SITE 24 TRANSITION TO RMC PRIOR TO VERTICAL BEND

60 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 25 POWER D2A RV SITE 25 TRANSITION TO RMC PRIOR TO VERTICAL BEND

61 1" - PVC SCH 80 3 - 4/0 AWG + 2 AWG-G CHARGING STATION FEED UTILITY TRANSFORMER PANELBOARD D3A TRANSITION TO RMC PRIOR TO VERTICAL BEND

62 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G DC FAST CHARGER 1 POWER D3A DC FAST CHARGER 1 TRANSITION TO RMC PRIOR TO VERTICAL BEND

63 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G DC FAST CHARGER 2 POWER D3A DC FAST CHARGER 2 TRANSITION TO RMC PRIOR TO VERTICAL BEND

64 1" - PVC SCH 80 3 - 10 AWG + 10 AWG-G D3A TO L3A D3A L3A TRANSITION TO RMC PRIOR TO VERTICAL BEND

65 1" PVC SCH 80 FUTURE INSTALL COMFORT STATION SPARE L3A COMFORT STATION NOTE 3

66 1" PVC SCH 80 2 - 10 AWG + 10 AWG-G D 0 SERIES LIGHTS L3A LIGHT POLES TRANSITION TO RMC PRIOR TO VERTICAL BEND

67 1" PVC SCH 80 2 - 10 AWG + 10 AWG-G D 1 SERIES LIGHTS L3A LIGHT POLES TRANSITION TO RMC PRIOR TO VERTICAL BEND

68 1" PVC SCH 80 2 - 10 AWG + 10 AWG-G BOLLARDS L3A LIGHT POLES TRANSITION TO RMC PRIOR TO VERTICAL BEND

69 0.75" - RMC 2 - 12 AWG + 12 AWG-G ISP ACCESS POINT POWER L3A ISP ACCESS POINT TRANSITION TO RMC PRIOR TO VERTICAL BEND

RV PARK AND CHARGING

STATIONS

CABLE AND CONDUIT

SCHEDULE

24-D-60200

1. Minimum RV distribution circuit length from Panel "D2A" to RV Pedestal shall be 40' to maintain available fault current rating below 10k AIC.

2. Provide RMC prior to above grade. Elbow, vertical run and

3. Provide pull string for future conductors.

Sheets and Views

22 x 34

2023-09-19T04:58:04-0600

ERIC MENDLIN

2023-09-19T06:11:14-0600

JOHN KELLY