This document provides details for a sole source procurement solicitation to rehabilitate transformers and poles for the Bureau of Reclamation. The solicitation issued by the Department of the Interior Bureau of Reclamation is for informational purposes only and intends to award a sole source contract to Sierra Electric Cooperative, Inc. The requirement is for Sierra Electric Cooperative, Inc. to rehab transformers and poles owned by the cooperative in the Dam Site area of the Elephant Butte Historic District. No response date, award date, or pricing terms are included.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
Existing 480/277V MDP Panel
Transformer T1 Panelboard L1A Panelboard D1A
PAD 2
Transformer T2 Panelboard L1B
PAD 3
Transformer T3 Panelboard L1C
PAD 4
Transformer T4 Panelboard L1D
PAD 5
UGE RV park 1
UGE RV park 3
UGE RV park 2
480V lift station service
PAD 6
Mini power center L3A Panelboard D3A
PAD 1
DC Fast Charger 1
Existing 500kVA Utility transformer
DC Fast Charger 2
14,400V-240/120V Utility Single-Phase Transformer Panelboard D2A
PAD 7
503+06
500+00
604+16
600+00
703+20
700+00
800+00
802+82
111+12
0+
5+
110+00
RV Utility Hookup Pedestal (see 60185)
Construction Prohibited Area
Future contract Comfort Station
REFERENCE DRAWINGS
RV CONNECTION ELECTRICAL,SEWER, &
WATER 24-D-60185
CASITA SINGLE LNE DIAGRAM 24-D-60193
RV PARK SINGLE LINE DIAGRAM 24-D-60194
CHARGING STATION SINGLE LINE DIAGRAM 24-D-60195
SITE LIGHTING PLAN 24-D-60201
Point Table
Pad #
Northing
782294.19
782124.31
781913.60
781611.78
781416.53
781531.54
780934.31
Easting
2921489.93
2921957.98
2922146.82
2922267.88
2922320.12
2922337.13
2922094.71
EXPLANATION
DEVICE LOCATION DESCRIPTION
D1A CASITAS 3
AND 4
480V PANELBOARD FOR T1, T2, T3,
AND T4
D2A RV PARK 240/120V PANELBOARD FOR RV
SITES
D3A LODGE/REST-
AURANT 480V PANELBOARD FOR L3A
L1A CASITAS 3
240/120V PANELBOARD FEEDS
CASITAS 1 THRU 5
L1B CASITAS 8
AND 9
CASITAS 6 THRU 10
L1C CASITAS 13
AND 14
CASITAS 11 THRU 13 AND RV SITES
1 AND 2
L1D ACROSS
CASITA 16
CASITAS 14 THRU 17 AND RV SITE 3
AND NEW LIGHT POLES
L3A LODGE/REST-
AURANT
FEEDS CHARGING STATION AND
LIGHTS
MDP WELCOME
CENTER 480V MAIN DISTRIBUTION CENTER
PAD 1 LODGE/REST-
AURANT
ELECTRICAL/FIBER UTILITY PAD IN
RESTAURANT AREA AND LIGHTS
PAD 2 CASITAS 3
ELECTRICAL/FIBER UTILITY PAD TO
FEED CASITAS 1-5
PAD 3 CASITAS 8
ELECTRICAL/FIBER UTILITY PAD TO
FEED CASITAS 6-10
PAD 4 CASITAS 13
ELECTRICAL PAD TO FEED CASITAS
11-13 AND RV SITES 1 AND 2
PAD 5 ACROSS
ELECTRICAL PAD ITO FEED CASITAS
14-17, RV SITE 3, AND LIGHTS
PAD 6 LIFT STATION FEEDS LIFT STATION AND NETWORK
SWITCH
PAD 7 RV PARK ELECTRICAL/FIBER UTILITY PAD IN
RV PARK AREA
T1 CASITAS 3
480-240/120V TRANSFORMER FEEDS
L1A
T2 CASITAS 8
L1B
T3 CASITAS 13
L1C
T4 ACROSS
L1D
DESIGNED
DRAWN
CHECKED
TECH. APPR.
APPROVED
PEER REVIEWER -
Lisa Billy
Donna Johnson
A
LW
YS
T H
IN
K
S
FE
TY
SHEET
D
C
B
U
R
EA
O
F
EC
LA
M
TI
N
.S
EP
TM
EN
TH
E
TE
IO
ut oC
4.
0S
LM
IL
-D -6
-R
-1 .D
W G
V
ED
-0 9-
Y
EK
PR
JE
EL
TT
PO
ER
TO
IV
IS
ES
IR
IC
TR
LI
EM
ELECTRICAL
SITE PLAN
DENVER, CO
24-D-60192
PLAN
1" = 100'
NOTES
1. DC Fast Charger locations will be finalized in field in coordination with COR.
2. RV Pedestal locations as shown.
3. For site lighting see drawing 24-D-60201
0 100' 200'
AutoCAD SHX Text
AutoCAD SHX Text lbilly
Typewritten Text
Supervisory Electrical Engineer
Electrical Engineer
Rectangle
Callout
Approximate utility transformer location, 3-phase
Callout
Approximate utility transformer location, 1-phase
Rectangle
3 PHASE - 4 WIRE
500KVA
24.94 kV - 480Y/277 V
200:5A
800A
GFP
600A
(NEW)
200A
400A
400A
MARINA RESTAURANT
SWITCHBOARD MDP (EXISTING)
KW METER
SPARE SPARE SPARE
D1A-1
125A
D1A (NEW)
T2 (NEW)
1 PHASE
50KVA
480-240/120 V
T3 (NEW)
75KVA
T4 (NEW)
75KVA
D1A-2
125A
D1A-3
D1A-5
LIFT STATION
(EXISTING)
D1A-4
40A
L1D
L1C
L1B
L1A
SEE DRAWING
24-D-60196
T1 (NEW)
50KVA
3 4 5 76
8 9 10 11
10HP
800A, 480/277V, 3-PHASE, 14 kAIC
600A, 480V, 3-PHASE, 10 kAIC
UTILITY TRANSFORMER
(EXISTING)
KW METER KW METER
DS1
25A
1. 100A main service panels at Casitas not in drawing.
2. Existing kWh meters on Marina and Restaurant services in
MDP are Leviton 2000 Series.
3. Transformer 1 and Panel L1A feed Casitas 1 thru 5.
4. Transformer 2 and Panel L1B feed Casitas 6 thru 10.
5. Transformer 3 and Panel L1C feed Casitas 11 thru 13, RV sites 1 and 2.
6. Transformer 4 and Panel L1D feed Casitas 14 thru 17, RV site
3, and two new light poles by the boat entrance.
7. Provide RMC prior to above grade. Elbow, vertical run, and above grade conduit shall be RMC. Provide Schedule 80 PVC for buried conduit.
8. Fused disconnect switch at Pad 6 with grounding electrode and ground rod.
D1A PAD 2 480V DISTRIBUTION PANEL
DS1 PAD 6 FUSED DISCONNECT SWITCH FOR
LIFT STATION SERVICE
L1A PAD 2 240/120V PANEL
L1B PAD 3 240/120V PANEL
L1C PAD 4 240/120V PANEL
L1D PAD 5 240/120V PANEL
MDP WELCOME
CENTER 480V DISTRIBUTION PANEL
T1 PAD 2 240/120V TRANSFORMER
T2 PAD 3 240/120V TRANSFORMER
T3 PAD 4 240/120V TRANSFORMER
T4 PAD 5 240/120V TRANSFORMER
ELECTRICAL SITE PLAN 24-D-60192
CASITAS CABLE AND CONDUIT SCHEDULE 24-D-60199
CASITAS PANEL SCHEDULES 24-D-60196
CASITAS AND RV PARK PANEL SCHEDULES 24-D-60197
LEGEND
FEEDER NUMBER
LB
LY
CASITAS
SINGLE LINE DIAGRAM
24-D-60193
Donna Johnson P.E.
ra ft
Sheets and Views
22 x 34
2023-09-19T04:56:36-0600
ERIC MENDLIN
2023-09-19T06:08:08-0600
JOHN KELLY
1-PHASE, 3 WIRE
167KVA
14.4kV - 240/120 V
D2A (NEW)
700A, 240/120V, SINGLE PHASE,
10kAIC
24-D-60197
800:5A
KW METER NOTES
1. Provide RMC prior to above grade. Elbow, vertical run, and
D2A PAD 7 240V DISTRIBUTION PANEL
RV PARK AND CHARGING STATIONS CABLE AND
CONDUIT SCHEDULE 24-D-60200
CASITA AND RV PARK PANEL SCHEDULES 24-D-60197
RV PARK
24-D-60194
Donna Johnson, P.E.
Sheets and Views
22 x 34
FEEDER NUMBER: Off
ARow1:
A:
2023-09-19T04:59:55-0600
ERIC MENDLIN
2023-09-19T06:09:31-0600
JOHN KELLY
3-PHASE
150KVA
24.94KV-480/277V
T5 (NEW)
15kVA 480-208/120V
3 PHASE - 4 WIRE
250A
25A
50A3
100A
24-D-60198
DC Charger
D3A (NEW)
L3A (NEW)
100A, 208/120V, 3-PHASE, 10
kAIC
100A
3 DC Charger
250A, 480/277V, 3-PHASE, 10 kAIC
250:5A
KW METER
D3A PAD 1 NEW DISTRIBUTION PANEL
L3A PAD 1 15kVA MINI POWER CENTER
1. Provide RMC prior to above grade. Elbow, vertical run, and above grade conduit shall be RMC. Provide Schedule 80 PVC for buried conduit.
RV PARK AND CHARGING STATIONS CABLE AND
CONDUIT SCHEDULE 24-D-60200
CHARGING STATIONS PANEL SCHEDULE 24-D-60198
CHARGING STATIONS
24-D-60195
Sheets and Views
22 x 34
2023-09-19T04:58:37-0600
ERIC MENDLIN
2023-09-19T06:09:47-0600
JOHN KELLY
CASITAS SINGLE LINE DIAGRAM 24-D-60193
AL
AY
SA
¦D_DT¦
¦STATUS¦
PANEL SCHEDULES
PEER REVIEWER
£TT£
£AT£
£AA£
£TA£
- Electrical Engineer
Sheets and Views
22 x 34
2023-09-19T04:58:20-0600
ERIC MENDLIN
2023-09-19T06:10:06-0600
JOHN KELLY
CASITAS AND RV PARK
PANEL SCHEDLUES
24-D-60197
1. Conductors feeding panelboard D1A are rated for 570A. Per
National Electric Code, the load on this panel shall be less than 570A.
Sheets and Views
22 x 34
2023-09-19T04:56:03-0600
ERIC MENDLIN
2023-09-19T06:10:25-0600
JOHN KELLY
SITE LIGHTING PLAN 24-D-60201
CHARGING STATIONS SINGLE LINE DIAGRAM 24-D-60195
1. Spare for Comfort Station in L3A Panelboard.
CHARGING STATIONS
PANEL SCHEDULES
24-D-60198
Sheets and Views
22 x 34
2023-09-19T04:56:57-0600
ERIC MENDLIN
2023-09-19T06:10:41-0600
JOHN KELLY
CABLE AND CONDUIT SCHEDULE
FEEDER
NUMBER
CONDUIT SIZE
-TYPE CONDUCTORS PURPOSE ORIGIN DESTINATION NOTES
1 DIRECT BURIED 3[1 - 350MCM + 3/0 AWG-G] SERVICE ENTRANCE SECTION UTILITY TRANSFORMER
SECONDARY PANELBOARD MDP EXISTING SERVICE ENTRANCE
2 2 [3" - PVC SCH 80] 2[3 - 300MCM + 1 AWG-G] 480V SERVICE TO D1A PANELBOARD MDP PANELBOARD D1A TRANSITION TO RMC PRIOR TO VERTICAL BEND
3 1.5" - PVC SCH 80 3 - 1 AWG + 6 AWG-G POWER TO TRANSFORMER T1 D1A TRANSFORMER T1 TRANSITION TO RMC PRIOR TO VERTICAL BEND
4 1.5" - PVC SCH 80 3 - 1 AWG + 6 AWG-G POWER TO TRANSFORMER T2 D1A TRANSFORMER T2 TRANSITION TO RMC PRIOR TO VERTICAL BEND
5 2.5" - PVC SCH 80 3 - 3/0 AWG + 6 AWG-G POWER TO TRANSFORMER T3 D1A TRANSFORMER T3 TRANSITION TO RMC PRIOR TO VERTICAL BEND
6 1.5" - PVC SCH 80 3 - 6 AWG + 8 AWG-G POWER TO LIFT STATION PANELBOARD D1A LIFT STATION TRANSITION TO RMC PRIOR TO VERTICAL BEND
7 3" - PVC SCH 80 3 - 3/0 AWG + 6 AWG-G POWER TO TRANSFORMER T4 D1A TRANSFORMER T4 TRANSITION TO RMC PRIOR TO VERTICAL BEND
8 2.5" - LFMC 3 - 4/0 AWG + 2 AWG-G POWER TO PANEL L1A T1 L1A TRANSITION TO RMC PRIOR TO VERTICAL BEND
9 2.5" - LFMC 3 - 4/0 AWG + 2 AWG-G POWER TO PANEL L1B T2 L1B TRANSITION TO RMC PRIOR TO VERTICAL BEND
10 3" - LFMC 3 - 500 MCM + 1/0 AWG-G POWER TO PANEL L1C T3 L1C TRANSITION TO RMC PRIOR TO VERTICAL BEND
11 3" - LFMC 3 - 500 MCM + 1/0 AWG-G POWER TO PANEL L1D T4 L1D TRANSITION TO RMC PRIOR TO VERTICAL BEND
12 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 1 POWER L1A EXISTING CASITA 1 SERVICE
PANEL TRANSITION TO RMC PRIOR TO VERTICAL BEND
13 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 2 POWER L1A EXISTING CASITA 2 SERVICE
14 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 3 POWER L1A EXISTING CASITA 3 SERVICE
15 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 4 POWER L1A EXISTING CASITA 4 SERVICE
16 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 5 POWER L1A EXISTING CASITA 5 SERVICE
17 0.75" - RMC 2 - 12 AWG + 12 AWG-G ISP ACCESS POINT POWER L1A ISP ACCESS POINT TRANSITION TO RMC PRIOR TO VERTICAL BEND
18 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 6 POWER L1B EXISTING CASITA 6 SERVICE
19 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 7 POWER L1B EXISTING CASITA 7 SERVICE
20 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 8 POWER L1B EXISTING CASITA 8 SERVICE
21 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 9 POWER L1B EXISTING CASITA 9 SERVICE
22 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 10 POWER L1B EXISTING CASITA 10 SERVICE
23 0.75" - RMC 2 - 12 AWG + 12 AWG-G ISP ACCESS POINT POWER L1B ISP ACCESS POINT TRANSITION TO RMC PRIOR TO VERTICAL BEND
24 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 11 POWER L1C EXISTING CASITA 11 SERVICE
25 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 12 POWER L1C EXISTING CASITA 12 SERVICE
26 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 13 POWER L1C EXISTING CASITA 13 SERVICE
27 1.5" - PVC SCH 80 3 - 4 AWG + 8-AWG-G RV SITE 1 POWER L1C RV SITE 1 PEDESTAL TRANSITION TO RMC PRIOR TO VERTICAL BEND
28 1.5" - PVC SCH 80 3 - 4 AWG + 8-AWG-G RV SITE 2 POWER L1C RV SITE 2 PEDESTAL TRANSITION TO RMC PRIOR TO VERTICAL BEND
29 1.5" - PVC SCH 80 3 - 4 AWG + 8-AWG-G RV SITE 3 POWER L1D RV SITE 3 PEDESTAL TRANSITION TO RMC PRIOR TO VERTICAL BEND
30 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 14 POWER L1D EXISTING CASITA 14 SERVICE
31 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 15 POWER L1D EXISTING CASITA 15 SERVICE
32 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 16 POWER L1D EXISTING CASITA 16 SERVICE
33 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G CASITA 17 POWER L1D EXISTING CASITA 17 SERVICE
34 0.75" - RMC 2 - 12 AWG + 12 AWG-G ISP ACCESS POINT POWER L1D ISP ACCESS POINT TRANSITION TO RMC PRIOR TO VERTICAL BEND
CABLE AND CONDUIT
SCHEDULE
24-D-60199
1. Panelboard MDP is existing, feeder conduit and conductor to exit side of MDP panelboard and proceed below grade to Panelboard D1A.
2. Provide RMC prior to above grade. Elbow, vertical run and
Sheets and Views
22 x 34
2023-09-19T04:57:47-0600
ERIC MENDLIN
2023-09-19T06:10:57-0600
JOHN KELLY
CHARGING STATIONS SINGLE LINE DIAGRAM 24-D-60195
CABLE AND CONDUIT SCHEDULE
FEEDER
NUMBER
CONDUIT SIZE
-TYPE CONDUCTORS PURPOSE ORIGIN DESTINATION NOTES
35 2 [3" - PVC SCH 80] 2[3 - 400MCM] + 2/0 AWG-G] RV PARK FEED UTILITY TRANSFORMER PANELBOARD D2A TRANSITION TO RMC PRIOR TO VERTICAL BEND
36 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 4 POWER D2A RV SITE 4 TRANSITION TO RMC PRIOR TO VERTICAL BEND
37 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 5 POWER D2A RV SITE 5 TRANSITION TO RMC PRIOR TO VERTICAL BEND
38 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 6 POWER D2A RV SITE 6 TRANSITION TO RMC PRIOR TO VERTICAL BEND
39 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 7 POWER D2A RV SITE 7 TRANSITION TO RMC PRIOR TO VERTICAL BEND
40 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 8 POWER D2A RV SITE 8 TRANSITION TO RMC PRIOR TO VERTICAL BEND
41 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 9 POWER D2A RV SITE 9 TRANSITION TO RMC PRIOR TO VERTICAL BEND
42 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 10 POWER D2A RV SITE 10 TRANSITION TO RMC PRIOR TO VERTICAL BEND
43 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 11 POWER D2A RV SITE 11 TRANSITION TO RMC PRIOR TO VERTICAL BEND
44 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 12 POWER D2A RV SITE 12 TRANSITION TO RMC PRIOR TO VERTICAL BEND
45 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 13 POWER D2A RV SITE 13 TRANSITION TO RMC PRIOR TO VERTICAL BEND
46 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 14 POWER D2A RV SITE 14 TRANSITION TO RMC PRIOR TO VERTICAL BEND
47 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 15 POWER D2A RV SITE 15 TRANSITION TO RMC PRIOR TO VERTICAL BEND
48 1" - PVC SCH 80 2 - 12 AWG + 12-AWG-G LIGHT POLES 1, 2, 3 POWER D2A LIGHT POLES TRANSITION TO RMC PRIOR TO VERTICAL BEND
49 1" - PVC SCH 80 2 - 12 AWG + 12-AWG-G LIGHT POLES 4, 5, 6 POWER D2A LIGHT POLES TRANSITION TO RMC PRIOR TO VERTICAL BEND
50 0.75" - RMC 2 - 12 AWG + 12-AWG-G ISP ACCESS POINT POWER D2A ISP ACCESS POINT TRANSITION TO RMC PRIOR TO VERTICAL BEND
51 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 16 POWER D2A RV SITE 16 TRANSITION TO RMC PRIOR TO VERTICAL BEND
52 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 17 POWER D2A RV SITE 17 TRANSITION TO RMC PRIOR TO VERTICAL BEND
53 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 18 POWER D2A RV SITE 18 TRANSITION TO RMC PRIOR TO VERTICAL BEND
54 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 19 POWER D2A RV SITE 19 TRANSITION TO RMC PRIOR TO VERTICAL BEND
55 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 20 POWER D2A RV SITE 20 TRANSITION TO RMC PRIOR TO VERTICAL BEND
56 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 21 POWER D2A RV SITE 21 TRANSITION TO RMC PRIOR TO VERTICAL BEND
57 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 22 POWER D2A RV SITE 22 TRANSITION TO RMC PRIOR TO VERTICAL BEND
58 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 23 POWER D2A RV SITE 23 TRANSITION TO RMC PRIOR TO VERTICAL BEND
59 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 24 POWER D2A RV SITE 24 TRANSITION TO RMC PRIOR TO VERTICAL BEND
60 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G RV SITE 25 POWER D2A RV SITE 25 TRANSITION TO RMC PRIOR TO VERTICAL BEND
61 1" - PVC SCH 80 3 - 4/0 AWG + 2 AWG-G CHARGING STATION FEED UTILITY TRANSFORMER PANELBOARD D3A TRANSITION TO RMC PRIOR TO VERTICAL BEND
62 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G DC FAST CHARGER 1 POWER D3A DC FAST CHARGER 1 TRANSITION TO RMC PRIOR TO VERTICAL BEND
63 1.5" - PVC SCH 80 3 - 1 AWG + 8-AWG-G DC FAST CHARGER 2 POWER D3A DC FAST CHARGER 2 TRANSITION TO RMC PRIOR TO VERTICAL BEND
64 1" - PVC SCH 80 3 - 10 AWG + 10 AWG-G D3A TO L3A D3A L3A TRANSITION TO RMC PRIOR TO VERTICAL BEND
65 1" PVC SCH 80 FUTURE INSTALL COMFORT STATION SPARE L3A COMFORT STATION NOTE 3
66 1" PVC SCH 80 2 - 10 AWG + 10 AWG-G D 0 SERIES LIGHTS L3A LIGHT POLES TRANSITION TO RMC PRIOR TO VERTICAL BEND
67 1" PVC SCH 80 2 - 10 AWG + 10 AWG-G D 1 SERIES LIGHTS L3A LIGHT POLES TRANSITION TO RMC PRIOR TO VERTICAL BEND
68 1" PVC SCH 80 2 - 10 AWG + 10 AWG-G BOLLARDS L3A LIGHT POLES TRANSITION TO RMC PRIOR TO VERTICAL BEND
69 0.75" - RMC 2 - 12 AWG + 12 AWG-G ISP ACCESS POINT POWER L3A ISP ACCESS POINT TRANSITION TO RMC PRIOR TO VERTICAL BEND
RV PARK AND CHARGING
STATIONS
CABLE AND CONDUIT
SCHEDULE
24-D-60200
1. Minimum RV distribution circuit length from Panel "D2A" to RV Pedestal shall be 40' to maintain available fault current rating below 10k AIC.
2. Provide RMC prior to above grade. Elbow, vertical run and
3. Provide pull string for future conductors.
Sheets and Views
22 x 34
2023-09-19T04:58:04-0600
ERIC MENDLIN
2023-09-19T06:11:14-0600
JOHN KELLY
File details come from the government source that posted it. Updated .