For Service Providers of
Residential AdvanTex® Treatment Systems and for Homeowner Reference Another Carefully Engineered Treatment System by:
AdvanTex Treatment Systems
O P E R A T I O N & M A I N T E N A N C E M A N U A L
O M&A D V A N T E X ® M A N U A L
As the operator and service provider of an onsite wastewater treatment system, you play a crucial role. Property owners, neighbors, regulators, deal-ers, manufacturers ... all rely on your efficient and effective work.
All onsite systems require servicing, from the sim-plest of standard stone-trench systems to the most complex tertiary treatment systems. Regular serv-icing optimizes the treatment process and ensures that onsite systems are a sustainable technology.
To make servicing easier, Orenco has configured the AdvanTex® Treatment System and its compo-nents to be one of the most trouble-free and serv-ice-friendly residential treatment systems on the market. We’ve also provided this O&M Manual.
In it, you’ll find valuable information about . . .
• The AdvanTex System’s configuration and treatment process
• Performance expectations (norms) at each stage in the treatment process
• System components
• Routine cleaning and maintenance procedures and frequencies
• Routine cleaning and maintenance checklist
• Testing procedures
• Troubleshooting tips
• Sample documentation
• Equipment and tools checklist
Operation and maintenance of an onsite treat-ment system requires an understanding of all the above information. So please read through this entire manual first, before providing any service.
Then write in the Record of System Facts, on the back page. Reading the manual first and maintaining up-to-date records will save everyone time and money in the long run.
Also, at start-up and periodically thereafter, we recommend that you get together with the sys-tem user to review the Homeowner’s Manual that comes with the system, especially the “Do’s and Don’ts.” This will educate the user on preventive maintenance and on the operating and mainte-nance responsibilities of system users and author-ized personnel, as well as service-related obliga-tions of the manufacturer. Meeting periodically with the user will also allow you to track any sig-nificant changes in the household (e.g., number of occupants, changes in water use, use of deter-gents, disposal of cleaning compounds, etc.).
We’re very proud of the AdvanTex Treatment System. Like all our products, it has gone through extensive research, development, and field-testing.
Then each component is built to written specifi-cations and subjected to quality review, before shipping. In addition, our AXN models meet the requirements of ANSI-NSF Standard 40 for Class I Systems. If any component of this System does not meet your expectations, please call your authorized AdvanTex Dealer.
Your Expertise Matters
Introduction
O M&A D V A N T E X ® M A N U A L 3
AdvanTex® Treatment Systems
Table of Contents
Typical System Configuration 4
Treatment Process and Performance Expectations 6
• Processing Tank
• AdvanTex® Textile Filter
Typical Materials List 8
Tools, Equipment, and Spare Parts List 9
Routine Cleaning and Maintenance Procedures 10
• Control Panel/Pumps/Alarms
• Pumping System
• Processing Tank
• Textile Filter
• Miscellaneous
• Documentation
• Maintenance Checklist
Effluent Testing Procedures 16
• Protocol for Sampling, Testing, and Analysis
• Routine Tests, Frequencies, and Typical Values
• Supplemental Testing and Typical Values
Troubleshooting Tips for Operators: Process Treatment 18
• Troubleshooting Effluent Quality
• Troubleshooting Odor
• Troubleshooting Effluent Filter Clogging
• Troubleshooting Oily Film
• Troubleshooting Foam
O&M for Nitrogen Reduction 20
• The Process
• Signs of Effective Nitrogen Reduction
• Troubleshooting Nitrogen Reduction
Maintenance Checklist and Field Report Forms 23
Appendix 1: The Nitrogen Reduction Process and Key Indicators 28
Appendix 2: Abbreviations and Definitions 30
Appendix 3: Timer Settings 31
Notes 31
Record of System Facts Back Page
Copyright Orenco Systems®, Inc. Property of Orenco Systems®, Inc.
Do not reproduce or distribute without written authorization from Orenco: 800-348-9843.
Typical System Configuration
This 3D illustration shows a typical backyard configuration for the key elements of an AdvanTex® Treatment System, using an AX20 textile filter, which can be neatly positioned on top of or adjacent to the processing tank.
Mode 3 configuration shown here
House/Building
4. Final dispersal (shallow gravelless drainfield, STEP collection, drip system, shrub irrigation, water reuse, lagoon, wetland, etc.)
2. Watertight processing tank Provides primary treatment.
Removes a majority of contaminants.
1. Wastewater
3. AdvanTex® textile filter Provides advanced secondary treatment.
Typical System Configuration: Plan View
O M&A D V A N T E X ® M A N U A L6
54-1/2"±
157"±
12.5"
12"±
HWA/TO
RO
26.25"±
Mixing Blended Zone
28"
43.5"±
Surge Capacity 8"±
Normal Liquid Level 5.5"±
AX20
Top View
Side View
Primary Chamber Effluent
Recirc-Blend Effluent
Raw Influent
AX/AXN Filtrate
RSV
11"
Processing Tank
The processing tank provides primary wastewater treatment. The tank is an enclosed, watertight receptacle designed to collect wastewater; segre-gate settleable and floatable solids (sludge and scum); accumulate, consolidate, and store solids;
digest organic matter; and discharge treated effluent. BOD (biochemical oxygen demand) removals of greater than 65% and TSS (total suspended solids) removals of greater than 70% are easily accomplished.
The tank operates as a plug-flow type of reactor (fluid and particles enter and exit the tank in pro-gressive sequence). Wastewater separates into three distinct layers: a floating scum layer, a bottom sludge layer, and a clear zone in between, which is relatively free of large solids. A pump vault with effluent filter located at the outlet end of the tank draws liquid effluent from the clear zone, and the filtered effluent is dosed to the next step in the treatment process . . . the AdvanTex Textile Filter.
Because the AdvanTex Treatment System operates in the recirculating mode, the filtrate from the Textile Filter returns to the processing tank in one of two ways: to the back (outlet end) of the tank in Mode 1 and to the front (inlet end) of the tank in Mode 3. This plumbing configura-tion affects effluent quality. Effluent quality is also contingent upon a number of other condi-tions inside the tank:
• strength and characteristics of incoming waste (see “Raw Influent,” page 7)
• average flows within design range (typically 40-60 gallons per person per day)
• adequate long-term solids retention for thorough digestion
• watertightness of tank (for proper stratification of incoming waste to prevent treatment short circuiting and hydraulic overloading)
• proper size of tank (for minimum 24-hour hydraulic retention time through the tank’s clear zone, at average flow rates and when sludge and scum are developed fully)
If the above conditions are met, you can expect treatment performance per the table on page 7.
Treatment Process/Performance Expectations
AdvanTex Textile Filter
The AdvanTex textile filter provides secondary wastewater treatment. The filter is a sturdy, watertight fiberglass basin filled with an engi-neered textile material. This lightweight, highly absorbent textile material treats a tremendous amount of wastewater in a small space.
The AdvanTex filter operates in the recirculating mode, just like a recirculating sand or gravel fil-ter, but loading rates are typically 5-20 times higher, for a number of reasons. For one thing, the textile media has a very large surface area— about 5 times greater than that of an equivalent volume of sand. Textile also has a greater void volume (for free flow of oxygen) and greater water-holding capacity.
Wastewater percolates both through and between the textile media. A visible biological film nor-mally develops on the filter medium within a few days. BOD5 and TSS reductions occur almost immediately.
Within the filter, aerobic conditions exist that are ideal for microbes that convert ammonia to nitrate (nitrification). Other conditions exist, too, that result in further nitrogen reduction within the media. Some AdvanTex filters are configured (Mode 3) so that the filtrate recirculates back to the high-carbon, low-oxygen environment at the inlet end of the processing tank, which is ideal for microbes that reduce nitrates to nitrogen gas (denitrification). Harmless nitrogen gas is then released freely back into the atmosphere. The acclimation period for nitrification may range from four to eight weeks, or longer in colder climates.
AdvanTex filtrate effluent quality is dependent upon proper management of the recirc/blend effluent flowing into the filter (which, in turn, is dependent on the conditions described on the previous page). If proper conditions are met, and with typical average daily flows of 40-60 gallons per capita per day, you can expect the following treatment performance:
Performance Expectations
BOD5 TSS TKN
mg/L mg/L mg/L
Raw Influent1 450 500 70
Primary Chamber Effluent 150 40 65
Processing Tank Recirc/Blend Effluent2 15-40 10-20 —4
AXN Filtrate3 5 5 —4
1 Source: Crites & Tchobanoglous. Small and Decentralized Wastewater Management Systems,
p. 180, 183, 1998. McGraw-Hill. Based on 50 gpcd.
2 Will vary with recirc ratios and mode configuration.
The numbers here represent a recirc ratio between 2:1 and 4:1 and are derived from Orenco and third-party testing in Mode 1.
3 Actual performance results, based on a six-month accumulative average from NSF (National Sanitation Foundation) testing on the AX20N at 500 gpd, using composite sampling. See page 17 for additional information on treatment performance.
Performance and servicing frequencies will tend to vary relative to the mass load being treated.
Procedures for treating excessively high loads will require engineering review. For more information, please review AdvanTex Design Criteria.
4 Dependent on treatment system configuration and recirc ratios.
Treatment Process/Performance Expectations (continued)
Orenco’s AdvanTex Treatment Systems come in multiple models and configurations. Following is a typical materials list (excluding the processing tank) for an AdvanTex AX20 system that requires a pump basin (some do not).
Processing Tank Access Equipment
Two Access Risers necessary:
One 24" dia., w/Lid
One 30" dia., w/Lid & necessary Grommets
Treatment System Equipment
PVC Splice Box
Universal Biotube® Pump Vault
Discharge Assembly
Float Switch Assembly
Orenco Pump, 115V
MVP or VCOM AdvanTex AXB Panel, 115V
Recirculating Splitter Valve Assembly
AdvanTex AX20 Filter (7.5' x 3' x 2.5') w/Vent Assembly
Anti-Flotation Flanges
Pump Basin Equipment
PVC Pump Basin, 24" dia., w/Lid
PVC Splice Box
Discharge Assembly
Float Switch Assembly
Orenco Pump, 115V
Top View
Primary Chamber Effluent
Recirc-Blend Effluent
Raw Influent
AX/AXN Filtrate
Top View
Min. 23" Dia.
Tank Opening (with cover removed)
Discharge Pump Basin
AdvanTex Filter
Primary Chamber Effluent
Typical Materials List
Module AX20, 1B shown.
Actual configuration may vary slightly to fit site.
O M&A D V A N T E X ® M A N U A L 9
Tools, Equipment, and Spare Parts List
Many of the recommended maintenance and troubleshooting procedures require specialized tools, equipment, and spare parts. At a mini-mum, we recommend you keep the following items on hand:
Tools and Equipment anemometer (call for information) beakers or bottles camera (preferably digital) calculator channel lock pliers—6" and 12" crimping tool—10 to 22 AWG drill (cordless, with spare batteries, charger) drill bit set—1/16" to 1/2" electrical tester (voltage and amperage) extension cord flashlight with spare batteries/bulb funnel hacksaw with spare blades hammer heat gun (torch) hole saw (vari-bits: 3/4" and 1-3/8") hose with nozzle and backflow prevention device pencil
Mirror on a Stick (available from Prototek) pressure gauge (0 to 100 psi, 0 to 200 psi) backpack pressure washer (portable) screwdriver set (straight blade and Phillips) shovel
SMUG device snake (building sewer) squirt-height gauge stir sticks tape measure watch or stopwatch wire strippers wrench (24" pipe wrench) wrench (lid bolt)
30 gal. garbage can
30 gal. garbage bags
Spare Parts control panel parts:
— breakers
— contactors fuses epoxy floats heat shrink tubing insulated butt connectors king connectors lid bolts
PVC fittings (3/4" to 2")
PVC glue/primer
PVC pipe (3/4" to 2")
Hygiene and Clean-Up bleach/water solution hand cleanser paper towels protective clothing eye protection rubber gloves towels and rags
Miscellaneous Patience and good humor!
Orenco Systems requires regular inspection and maintenance of AdvanTex Treatment Systems as a condition of purchase. All activities are to be performed three-to-six months after system start-up; and an annual field-service inspection, including sampling, is to be scheduled in late spring or in early summer. For AXN systems, there is to be a minimum of four inspections during the first two years, and then annual inspections thereafter.
Following is a list of the routine cleaning and maintenance procedures we recommend or require. Failure to provide required maintenance will void the AdvanTex Treatment System warranty.
Copies of inspection and maintenance reports, along with any additional documentation, must be forwarded to and retained by the Authorized AdvanTex Treatment System Dealer who sold the system. If there is no Dealer, then the documen-tation must be forwarded to Orenco Systems, Inc., 814 Airway Avenue, Sutherlin, OR 97479, ATTN: Systems Engineering.
Control Panel/Pumps/Alarms
WARNING: Only qualified/certified electri-cians or service providers should perform maintenance on electrical equipment.
1 Check pump operations. Place the MOA switch (Manual, Off, Automatic) to Manual and make sure the pump runs. Then switch back to Automatic and continue to check the automatic operation of the alarm floats, the recirc timer on the floats, the discharge timer on/off, and timer overrides. Refer to the installation, operation, and setting instructions for the control panel that comes with the system. A set of instructions is stored in a plastic pocket on the inside of the panel door.*
2 Check voltages and motor run amps and record them on the Field Maintenance Report Form. If the voltage drop exceeds National Electric Code (NEC) requirements, have an electrician verify the service line and check pump windings.
3 Verify that the programmable timer settings for all pumps are correct. With MVP panels, you can check timer settings using the digital timer’s function keys and large LCD display. With VeriComm® panels (shown here), you can check timer settings online or at the panel, using a lap-top computer or PDA. If the timer settings have been changed, the current setting and date of change should be written on your Timer Setting Instructions and Record of System Facts, at the back of this Manual. Place the date and your ini-tials by the recorded change. Appendix 3 gives typical timer settings for households of various sizes.
*If the instructions are missing, you can obtain another set from Orenco’s online Document Library, at www.orenco.com, or by calling Orenco at 800-348-9843, or by calling your local AdvanTex Dealer.
Routine Cleaning & Maintenance Procedures
NOTE:
Be sure to set the MOA switch back to Auto after testing.
VeronicaLamboySantan Highlight
4 Read and record the elapsed time meter (ETM) and cycle counter (CT) values (from the panel’s logic controller or from the Web-based telemetry software) on the Field Maintenance Report Form.
ETMs and CTs are valuable troubleshooting tools if problems occur with the system. ETM and CT data signal high water usage, low water usage or tank leakage, and excessive pumping, among other operating situations.
5 Confirm operation of audible and visual alarms per the installation, operation, and setting instructions for the control panel that comes with the system.
Pumping System
Pump systems should be inspected annually to ensure that they are operating properly. Unscrew the stainless steel bolts that fasten the fiberglass lid over the pumping equipment. Remove the fiberglass lid for an inspection that includes these steps:
1 Verify that there are no obvious holes or leaks in the riser or around the perimeter of the riser connection to the tank. Wetness or water marks may be an indication of weeping.
2 Inspect splice box to ensure lid and connec-tions are secure.
3 Verify that floats are in good condition and properly secured to the float tree. Verify that float cords are neatly wrapped inside the riser so that they cannot interfere with the operation of the floats.
4 Verify float operation. With MOA switch in Automatic, simulate system operation by lifting the floats in the same order that the liquid would lift them (bottom first, top last).
5 Determine whether the Biotube effluent filter needs cleaning by testing the change in the tank’s liquid level when the pump is on. Turn the recirc pump on by flipping the MOA switch in the control panel to Manual. Watch the liquid level inside the screened vault as the pump is running for about 30 seconds to deter-mine if there is any noticeable liquid level differential between it and the tank liquid level. Return the MOA switch to Auto. When the liquid level difference between the inside and outside of the vault is about two inches or more, or if the low-level alarm is activated, the Biotube cartridge may need to be cleaned.
If the Biotube needs cleaning, do the following:
• Turn circuit breaker off at service panel
• Switch MOA and circuit breakers in control panel to “Off”
• Slide Biotube cartridge out of vault
• If necessary, the RSV valve may be removed to allow room in the riser for cleaning the Biotube
— Pull RSV out of its Quick Disconnect hol-ster (see photo next page) and place it in a plastic trash can
— Hose off the trash can into the tank after replacing the RSV
NOTE: Refer to RSV installation instructions for details on how an RSV works.
• Hold Biotube cartridge over open inlet of tank or primary compartment
• Carefully spray build-up into tank
• If there are significant solids in vault, remove and clean it too
6 Pull the pump and place it on a cleanable surface, like the riser lid, or in a plastic trash can. Check the intake screen; wash off particles as necessary. Record the kinds of particles (cigarette butts, hair, lint, gum, kitty litter, cloth wipes, grease build-up, etc.) on the Field Maintenance Report form. Report findings to user (for education).
7 Visually inspect the Recirculating Splitter Valve and verify that the liquid level in the tank is within the normal range. If low, the ball mech-anism could be jammed in the seated position.
Remove, disassemble, and inspect. If high, the RSV may require cleaning because it is not mak-ing a tight seal when seated. Remove, disassem-ble, and inspect.
NOTE: The figure below shows the RSV adja-cent to the inlet of the processing tank, which is typical for Mode 3 systems (Mode 1 systems have the RSV in the second compartment of the tank — the Recirc Chamber). To read dimen-sional specifications, see full-sized drawing in Installation Guide, Appendix 2.
Processing Tank
1 If possible, verify no inlet flow when all house-hold appliances are turned off. Access the inlet inspection port for visual verification of lack of flow. If the inlet inspection port is not readily accessible, then listen for trickling water at the access port. This could indicate faulty fixtures or leaky plumbing. Check building sewer cleanout for flow. If faulty plumbing isn’t the problem, the sound of trickling water could indicate I & I (infiltration and inflow) from ground or surface water. In that case, further investigation is necessary.
2 Inspect the processing tank for the following:
• Liquid depth (should be about 60-70% of the total inside depth of the tank)
• Odor (should be musty, not pungent)
• Color/consistency of scum (should be dark brown with a consistency that varies from dense and crusty to soft and amorphous)
• Effluent characteristics (should be no oily sheen or foam)
• Sludge and scum thickness (records should indicate typical growth accumulation of 1" of scum and 2" of sludge per year for 3-4 occupants)
Measurements of solids accumulation help to determine when the septic tank needs pumping.
A recommendation for pumping should be made when the bottom of the scum layer is within 3" of the flow-through port of the baffle or when there is an accumulation of sludge to a depth within 6" below the flow-through port. After the first year’s measurement of septic tank sludge and scum thickness, measurements need to be taken only about every three years, until the thicknesses approach their maximum depths.
Textile Filter
1 Inspect for ponding.* The filter should not be saturated. Effluent should move freely through the media.
2 While manifold is pressurized, check for prop-er positioning of orifice shields over each orifice.
(See photo, step 3, page 14.)
* If there is ponding in the textile filter because of a build-up of oil and grease, scrape a sample of the biomat and have it analyzed by an environmental lab to determine its characteristic. If there is ponding of indeterminate cause, coupled with a pungent odor, it may be necessary to clean the textile media. (Excessive cleaning will retard nitrifica-tion. Only clean as often as necessary.) The textile media hangs in individual sheets, and these sheets can be pulled out for cleaning (if necessary). First, remove the Recirculating Splitter Valve.
Use a hose with spray nozzle or “low-pressure” pressure-washer, connected to the nearest spigot. Wash the biomat into the underdrain and it will flow back to the tank, as long as the Recirculating Splitter Valve has been removed.
When done, replace RSV.
Access Riser
Access Riser
Inlet
Normal L.L.
Top of scum at alarm
Scum
Sludge
A = 3"±
B = 6"± 3"
Remember: clean filter only if ponding and odor occur.
3 Verify that there is equal spray on and under all orifice shields. (Each orifice shield should show signs of organic biomat build-up on and underneath it. In this case, a clean orifice shield top is not better!)
4 Check for clogged orifices (orifice shields with-out spray or biomat build-up underneath). You should be able to observe uniform water droplets dancing around orifice shields while dosing.
5 Assess the character and color of the biomat. If it seems appropriate, take a photo and comment on the growth and characteristics of the biologi-cal mat under and around the orifice shields.
Biomats are natural and normally appear light-brown to dark-brown and gelatinous in texture.
If the mat appears too light (yellowish with the texture of lard, wax, or margarine), the grease and oil concentrations should be checked.
If routine DO measurements show a decrease in DO, the biomat may be retarding oxygen trans-fer. Make sure there is no ponding or ventilation problem, then clean the sheets if necessary.
6 Check the odor emitting from the filter. If a strong or offensive odor (e.g., smell of rotten eggs, rotten cabbage, etc.) is emitted, measure the DO level in the filtrate and recirculation cham-ber and adjust the recirc time, if necessary.
(Normally, systems will smell musty, earthy, or moldy but not pungent).
7 Check squirt height and compare residual pres-sure against the start-up value. This may take longer than just cleaning and flushing the mani-fold, but will help establish frequency of cleaning.
If the squirt height is 40-50% higher than the start-up value, clean and flush the manifold.
(A 50% increase in squirt height signals approxi-mately 18% orifice blockage.) To flush laterals you can run the pump or use a bottle brush or pressure washer. Brushing or pressure washing is best. (When you flush the laterals, biosolids slough into the bottom of the filter, flushing the underdrain at the same time, then return to the tank.) Verify again that all orifices are clear.
Re-check squirt height.
8 Regardless of squirt height, be sure to open the flush valves and run the pump for two-to-three minutes to flush solids and biomass from the pod’s underdrain back into the tank. This only takes a couple of minutes and can be done while accomplishing other tasks.
9 Verify passive ventilation and air flow. Use an anemometer (available through Orenco) to measure the air flowing through the system.
1-3 cubic feet per minute (cfm) is typical. The following chart shows how much airflow is needed* to handle the indicated strength of BOD5 and ammonia:
Flushing with pump
Flushing with pressure washer or bottle brush
Unit Flow BOD5 Ammonia Req. Air Flow (gpd) (mg/L) (mg/L) (cfm)
AX20 500 150 65 0.8
*Ultimately, treatment is accomplished and final effluent quality provides the effective measure of treatment per-formance and capacity. Typical dissolved oxygen levels in the filtrate effluent will range from 3.5 to 5 mg/L DO.
In the above photo, the measurement on the meter shows air velocity of 124 feet/minute, which, after mathemati-cal conversion, means that 2.7 cfm (cubic feet/minute) is being drawn through the vent line. Slight atmospheric conditions are more than sufficient to cause two or more air changes to occur every hour.
Record inlet air flow and outlet air flow, where applicable, to ensure there isn’t a large difference between them. A large difference means that leaking or bypassing is occurring. Clean vent pipe as necessary.
Miscellaneous
1 Exercise all mechanical valves. Fully open and close valves to ensure they have not failed or become stuck in one position.
2 Before leaving the site ...
a) Review the Maintenance Checklist to ensure all activities have been performed.
b)Be particularly careful to ensure the following:
— Valves are back in their recommended positions
— Control panel has been set back to automatic and circuit breakers have all been switched back on
— Household water lines have been turned back on (if they were turned off earlier in the visit for I & I evaluation)
— Lids and lid bolts are properly in place and tightened
Documentation
1 Complete all documentation and submit any required reports to the appropriate parties/ agencies. Be sure to send a copy to the AdvanTex Dealer.
CAUTION! While providing O&M services, be sure to use proper personal protection equip-ment, such as rubber gloves and eye protection, as well as protective clothing, to cover parts of the body that will be exposed to wastewater or effluent. When finished, use proper personal hygiene.
O M&A D V A N T E X ® M A N U A L16
Effluent Testing Procedures
Orenco Systems recommends regular testing of effluent from AdvanTex Treatment Systems as part of system maintenance. Copies of test results and additional comments/documentation must be forwarded to and retained by the Authorized AdvanTex Treatment System Dealer who sold the system. If no Dealer was involved in the sale, then documentation must be forwarded to Orenco Systems, Inc., 814 Airway Avenue, Sutherlin, OR 97479, ATTN: Systems Engineering.
Protocol for Sampling, Testing, and Analysis
Sampling Locations — For residential systems, sample the discharge filtrate at the filtrate splitter valve. This location is illustrated on your system drawings. Pull the RSV out of its Quick Disconnect holster and lay it on a flat surface.
Take the sample at the RSV inlet.
To take a sample that accurately represents the system’s effluent quality, do two things:
1. Wash down, brush, or wipe the RSV inlet before taking the sample so that dislodged solids will not contaminate the sample.
2. Don’t run the pump manually to force a quick sample. Take the sample during normal system operation.
Sampling Schedule — Typically schedule full-scale annual sampling events for spring.
Sampling and Storage Methods — Sampling equipment, minimum sample size, and storage procedures should conform to those recommend-ed in the most current edition of Standard Methods for the Examination of Water and Wastewater, American Public Health Association (APHA), available from the Water Environment Federation, 703-684-2400.
Analytical Methods — Analytical methods should conform to Standard Methods, cited above.
Routine Tests, Frequencies, and Typical Values
While regional requirements vary, Orenco recom-mends that the following effluent tests be per-formed three to six months after system start-up.
An annual field-service inspection, including sam-pling, is to be scheduled in late spring or in early summer. For AXN systems, there must be at least four inspections during the first two years, with sampling once a year as described on the Field Sampling Report Form, and then annual inspec-tions with sampling thereafter.
These tests can be performed in the field; they cost very little and do not require lab work.
However, they are very useful in assessing system performance and maintenance.
Parameter Methodology Typical Values*
Clarity Visual1 Clear (15± NTUs)
Odor Sniff 2 Non-offensive (musty is OK; rotten egg or cabbage is not OK)
Biotube® Visual No liquid level differential inside/outside vault Norm: 1-2 year cleaning interval for recirculating systems
Oily film Visual; inside None; no red, blue, the pump vault green, or orange sheen
Foam Visual; inside tank None pH Field 3 6-9
*Source: These typical values are recommended by various sources. Biotube parameters are based on Orenco research and development.
1 To check for clarity, service providers can carry a sample bottle of typical effluent, to compare against, or can use a portable turbidity meter.
Always put effluent sample in a clear glass container or beaker to evaluate clarity. Using a small, removable sticker, write the date and place it low on the beaker.
VeronicaLamboySantan Highlight
2 To check for odor, service providers can simply sniff the effluent sample or can use a sulfide measuring packet or an olfactory snifter device for detection of odors.
3 To check for pH, service providers can use litmus paper, a pocket pH meter, or a benchtop pH meter.
Supplemental Testing and Typical Values
If effluent is cloudy or smells pungent or if the biomat on the textile filter appears greasy, waxy, or oily, further tests and troubleshooting of the filtrate should be performed. The following filtrate tests provide invaluable information for troubleshooting and diagnosing problems and causes:
Parameter Methodology Typical Values (mg/L)
AX1
Mode 1 Mode 3
BOD5 Grab 10± 10±
TSS Grab 10± 10±
TN Grab 25± 5-15±
G&O Grab <1
DO Field2 2.5-6± pH Field 6-8±
1 AX values are based on Orenco and third-party testing.
2 To check for Dissolved Oxygen, use a DO meter, avail-able from VWR Scientific, Cole-Parmer, or Hach.
3 Typical nitrogen reduction ranges from 60-80%±, with sufficient carbon source and alkalinity.
Relationship Between Test Results and Loading Rates
As noted on pages 6-7, filtrate quality is depend-ent on a number of factors, including influent characteristics and loading rates. The following charts show how low-to-moderate loading rates produce BOD and TSS of <5mg/L, while higher loading rates produce BOD and TSS in the range of 15-25 mg/L.
NovaTec
48.3 gpd/ft2
4 mo.
NovaTec 60 gpd/ft2
10 mo.
NovaTec 60 gpd/ft2
10 mo.
NovaTec
48.3 gpd/ft2
4 mo.
Once you know the typical values for wastewater treatment system performance (see pages 6, 7, 16, and 17), you can be proactive and trou-bleshoot nontypical process indicators, before sys-tem performance is affected.
Troubleshooting Effluent Quality
If your effluent samples are cloudy and color/tur-bidity is significantly higher than expected (15 to 30 NTUs), do the following:
• Perform cBOD5 and TSS tests
• Check the Biotube® filter for clogging
• Check to see if the textile filter smells of chem-icals (medication, chlorine, etc.) or has a gran-ular or crusty appearance. (For example, a white crystalline crust could signal that water softener discharge or industrial strength deter-gents have been flushed into the system.)
• Check to see if the recirc ratio is too high or the pump dose time is too long
If the effluent cBOD is high and TSS low, a large amount of soluble cBOD has not yet been con-sumed. That would likely be because the recirc ratio is too low for the influent strength or insuf-ficient start-up time has elapsed. Typical organic reduction within the first 24 hours in residential systems is about 75% or greater. As the biomat begins to develop, greater reductions in the solu-ble cBOD will occur (typically within the first 7-10 days). With a higher influent strength, the soluble cBOD would not be readily removed until the biomat on the media is established.
If none of these troubleshooting steps made a dif-ference, interview the user about system abuse, especially in the area of harmful chemicals, sol-vents, or strong cleaning agents. Be sure to check that no water softener backwash is dis-charging into the processing tank! Water sof-tener backwash can be extremely high in salts, which can disrupt system performance, espe-cially nitrogen reduction processes!
If no system abuse is uncovered, call Orenco to explore the following design remedies, in this order:
1. Expanded tankage (e.g., additional grease/oil tank)
2. Pretreatment (e.g., additional aeration)
3. Larger filter area (e.g., additional module)
Troubleshooting Odor
If the tank or textile filter smells like rotten eggs or cabbage:
• Check Dissolved Oxygen levels
• Use a DO meter or Colorimetric Kit
• Note filtrate DO levels that are <2.5 or >6 mg/L
Filtrate DO that’s <2.5 mg/L indicates insuffi-cient oxygen. If the filtrate DO is <2.5 mg/L:
• Check filter surface for evidence of clogging
• Check to ensure the pump is working
• Check to ensure ventilation is occurring
• Check to ensure the recirc ratio isn’t too low;
increase if too low
• Check to ensure influent strength isn’t too high (see AdvanTex Design Criteria)
• Check to ensure hydraulic retention time isn’t too high
Filtrate DO that’s >6 mg/L indicates excessive aeration. If the filtrate DO is >6 mg/L:
Troubleshooting Tips for Operators:
Process Treatment
Septic Tank Recirc/Blend Filtrate
• Check to ensure recirc ratio isn’t too high
• Check to see if influent flows are below normal
• If influent flows are below normal or recirc ratio is too high, reduce recirc ratio
Troubleshooting Biotube Filter Clogging
If a visual inspection of the Biotube filter for bio-mass build-up shows the need for cleaning more often than once every 1-2 years (which is typical for recirculating systems), try the following:
• Verify the pump isn’t running too long (typically 3 cycles/hour)
• Ensure the recirc ratio isn’t too high
• Verify normal DO levels; if high, reduce recirc ratio
• Check for below normal influent flows
• Check influent Grease & Oil and TSS; if excessive, a review of component sizes may be required
Troubleshooting Oily Film
All signs of oil or grease anywhere in the system (in the tank, in the vault, on the effluent or tex-tile filter) must be investigated. Ask the system user to identify the probable source:
• Recent change of car oil?
• Canning meat or poultry?
• Excessive use of garbage disposal?
• Excessive use of bath or mineral oils?
(Jacuzzi® tub?)
• Excessive use of detergents?
If the system user can’t identify the probable source, try the following:
• Sample/test effluent for BOD5 and Grease & Oil
• Sample/test at all process steps, including influent (if possible)
• Label, date, and photograph all samples
• Use standard glass beakers and set samples in front of a common, uniform background, when photographing
• Check biomat accumulation at AdvanTex Filter
• Note if biomat is yellowish and wax-like or lard-like. If so, scrape biomat sample for analysis:
— Photograph/document biomat sample
— Send to lab with effluent samples
Note: Excessive Grease & Oil (>25 mg/L) is typically a design and management concern with commercial applications.
Troubleshooting Foam
Foam indicates that microbes are producing excessive gas byproducts. Foam rarely occurs in packed bed filters (and AdvanTex is a packed bed filter). If foam is present:
• Verify the pump isn’t running too long
• Ensure the recirc ratio isn’t too high
• Ask residents about detergent use
As an aid to troubleshooting, Appendix 3 gives typical timer settings for households of various sizes.
AdvanTex Treatment Systems do an excellent job of reducing nitrogen, especially in the Mode 3 configuration, where Total Nitrogen* is typically reduced to 10 mg/L ±, with influent TKN of 55- 65 mg/L. Because many people purchase AdvanTex for its nitrogen reducing capabilities, and because nitrogen reduction is a complex, many-staged process, it’s important to under-stand the process, its related factors, the signs of effective nitrogen reduction, and how to keep the process optimized.
It’s also important to know the Total Nitrogen limits required by the system user’s permit. Some regulatory agencies have no requirement; some require a specific percentage reduction of a cer-tain kind of nitrogen (90-95% nitrification of ammonia nitrogen, for example); and some require that Total Nitrogen be reduced to levels at or near drinking water quality at the point of final dispersal.
Finally, because influent characteristics greatly affect the amount of nitrogen reduction possible from any given system, it’s vital to know the alkalinity of your waste source and the local/ regional norms for organic and ammonia nitrogen.
The Process
In nitrogen reduction, ammonia is converted to nitrate and then reduced through bacterial action to nitrogen gas, which can be released harmlessly to the atmosphere. Optimum nitrogen reduction requires the following:
• Adequate alkalinity of approximately 250± mg/L or higher (lab test shows levels)
• pH of 6-8. Fixed film microbial processes gen-erally thrive between pH 5.5 and 9. Treatment problems typically result from rapid changes in pH rather than extreme long-term mean val-ues, although long-term levels can result in less efficient process activity
• Filtrate DO level of 2.5-8 mg/L, process tank DO level of <1 mg/L
• Adequate time for the nitrifying bacteria to develop (one to three months)
• Adequate temperature (below 40° F retards the process)
• Good organic removal
For a thorough description of the nitrogen reduc-tion process, see Appendix 1. In residential waste-water, the ammonia level is typically about 60 mg/L and the Total Nitrogen level is typically about 65 mg/L.
Signs of Effective Nitrogen Reduction
Service providers frequently ask us, “How do I know if my wastewater treatment system is reducing nitrogen?” A thorough description of key indicators is included in the Appendix.
Following is a brief summary:
• Clear, odorless filtrate effluent (a “see and sniff” test is generally considered sufficient)
• Normal-looking biomat on the textile filter (light-brown to dark-brown and gelatinous in texture)
Additional Filtrate Tests Will Show ...
• Typically, low BOD5 and high clarity
• DO of 2.5-6 mg/L and odorless or odor that is not a nuisance
• Relatively low ammonia and high nitrate levels, since nitrification converts ammonia to nitrate
O&M For Nitrogen Reduction
* Total Nitrogen is the sum of organic and ammonia nitrogen, nitrate nitrogen, and nitrite nitrogen.
(TN=ON + NH3-n + NO3-n + NO2-n ... or ... TN=TKN-n + NO3-n + NO2-n)
Troubleshooting Nitrogen Reduction
If you suspect that the System is not meeting expectations for nitrogen reduction, troubleshoot each of the critical factors that contribute to opti-mum nitrogen reduction, to determine a cause.
Filtrate Alkalinity Too Low — Available alka-linity determines the degree of nitrification possi-ble for any wastewater treatment system, because it takes 7.14 parts alkalinity to nitrify 1 part ammonia.
If filtrate alkalinity is too low:
• Check the recirc ratio; a high recirc ratio increases alkalinity consumption*
• Check influent TKN or ammonia levels and source alkalinity
If a large quantity of nitrification is required, it may be necessary to add a buffering compound to the system, to raise alkalinity levels.
Filtrate pH Too Low — Nitrification is particu-larly sensitive to pH but tends to thrive at levels between pH 7.2 and 9. The nitrification process releases hydrogen that consumes alkalinity and causes pH levels to drop.
A pH level of <6 retards microbial activity of all kinds, including denitrification. Maintaining an alkalinity of 50 to 80 in the effluent is typically sufficient to maintain pH levels above 5.5. If the filtrate pH level is too low:
• Check influent alkalinity level (pH drops when too much available alkalinity is consumed)
• Check recirc ratios; reduce if too high*
• Ask system user about chemical discharges into the system, including carpet cleaners, chlorine, and photo developing agents
Filtrate DO Levels Outside Range of 2.5-6 mg/L — If your filtrate DO is too low (indicating insufficient oxygen), you may experi-ence periodic sulfide odors during dosing events, or perhaps a more lasting smell within the filter pod. Try the following:
• Check for surface clogging/ponding and clean as necessary
• Check air flow through the vent assembly
• Check the recirc ratio; if it’s too low (<2:1±) increase as necessary*
If your filtrate DO is too high (indicating excessive aeration), it’s likely that excessive recirculation or insufficient hydraulic retention time are factors. Try the following:
• Decrease the recirc ratio*
High Filtrate Ammonia Levels — Because ammonia is consumed during nitrification, high ammonia levels are a sign that something is amiss. Try the following:
• Check for surface clogging/ponding and clean as necessary
• Check for sufficient aeration (measure DO)
• Ensure no blockage of air flow into textile filter (indicated by thick biomat development or a build-up of grease and oils)
• Ensure no blockage in the manifold, causing ...
— Localized hydraulic overloading, saturation
— Short circuiting
• Check for sufficient alkalinity; if insufficient, consider supplemental buffering. Call Orenco Engineering for assistance, if necessary.
*Keep in mind that a recirc ratio that’s too high can generate a highly aerobic biomat growth on the pump filter; and a recirc ratio that’s too low can tend to liberate periodic odors during dosing events. So search for the optimum ratio (typically between 2 and 4:1)
O M&A D V A N T E X ® M A N U A L22
Low Filtrate Nitrate Levels — Residential packed bed filters normally yield 98+ percent nitrification (ammonia to nitrate). Therefore the ammonia levels in the filtrate should be low and the nitrate levels higher. Some denitrification typ-ically is experienced through the packed bed fil-ter. So the normal nitrate level may vary. Be sure you are familiar with the mode of operation, as some AdvanTexmodes are configured to produce lower nitrate levels. If it appears that nitrification is dropping off:
• Check the recirc ratio; adjust as necessary* (high recirc ratios may drive pH too low for effective nitrification/denitrification and low recirc ratios may not provide sufficient aeration)
• Verify incoming ammonia levels
• Check recirc/blend for sufficient organic food source (high BOD — see Table, page 7 — may cause greater oxygen demand through the filter, reducing nitrification)
Adequate Time and Temperature — Nitrifying bacteria require one to two months to develop, and extremely cold temperatures (below 40° F) retard that process. If the AdvanTex Treatment System has been installed in a very cold climate, nitrification may not “kick in” for several months until warmer temperatures are reached. Typically, a June-September installation provides the necessary temperatures for a 30-60 day nitrification start-up time. Once nitrifiers colonize, they typically continue to nitrify through normal winter conditions. Only in severely cold regions should additional insulation be necessary.
*Keep in mind that a recirc ratio that’s too high can generate a highly aerobic biomat growth on the pump filter; and a recirc ratio that’s too low can tend to liberate periodic odors during dosing events. So search for the optimum ratio (typically between 2 and 4:1)
Field Maintenance Report 23
AdvanTexTreatment Systems While regional regulations may vary, Orenco Systems requires that the following inspection and maintenance activities be performed, by a qualified provider, on all AdvanTex Treatment Systems sold. All activities are to be performed three-to-six months after system start-up; and an annual field-service inspection, including sam-pling, is to be scheduled in late spring or in early summer. For AXN systems, there is to be a minimum of four inspections during the first two years, and then annual inspections thereafter. Copies of inspection and mainte-nance reports and additional comments/documentation are to be forwarded to the AdvanTex Dealer, or if no Dealer, to Orenco Systems, 814 Airway Avenue, Sutherlin, OR 97479.
Date: __________________ Site: ______________________________ Operator: ______________________________
Maintenance Activity Activity Check-Off/Notes A) Inspect Control/Alarm Panel
1) Check pump operations in manual mode �� __________________________
2) Check/record pump amperage and voltage �� __________________________
Voltage at rest: ______ Amps at rest: ______ Amps while pumping: ______
3) Check timer settings �� __________________________
4) Record elapsed time meter and counter readings (if applicable) �� __________________________
5) Confirm operation of audible and visual alarms �� __________________________
B) Inspect/Test Pumping System
1) Verify no leaks in riser �� __________________________
2) Inspect splice box for moisture and secure connections �� __________________________
3) Verify condition of and correct operation of all floats �� __________________________
4) Verify neat wrap of float cords �� __________________________
5) Pull pump and clean intake screen if necessary �� __________________________
6) Visually inspect recirculating splitter valve and liquid level �� __________________________
C) Inspect Effluent Filters/Pump Screens
1) Clean as needed �� __________________________
2) Visually inspect and comment on biomat growth �� __________________________
D) Inspect Processing Tank
1) Verify no inlet flow �� __________________________
2) Inspect liquid depth, odor, scum color, effluent characteristics �� __________________________
3) Measure sludge and scum; recommend tank pumping, if necessary �� __________________________
E) Inspect AdvanTex Filter
1) Inspect for ponding; assess character and color of biomat �� __________________________
2) Check squirt height �� __________________________
3) Verify proper orifice position, equal spray under orifices, no clogged orifices �� __________________________
4) Check for odors; adjust recirculating time if necessary �� __________________________
Normal: �� Musty �� Earthy �� Moldy
Pungent: �� Sulfide �� Cabbage �� Decay
5) Clean and flush manifold (if necessary) �� __________________________
6) Re-check squirt height �� __________________________
7) Flush underdrain �� __________________________
8) Inspect intake vent and clean as necessary �� __________________________
F) Miscellaneous
1) Exercise all valves �� __________________________
2) Return valves, control panel to proper settings �� __________________________
3) Submit required documentation �� __________________________
VeronicaLamboySantan Highlight
24 Field Alarm Report Form
Alarm Call Addendum
Conditions Leading to Call
�� Alarm �� Tank Overflow
�� Odor �� Surface Runoff
�� Noise �� Sewage Backup
�� Other:
Odor
Normal: �� Musty �� Earthy �� Moldy
Pungent: �� Sulfide �� Cabbage �� Decay
Date/Time Discovered: /
Method of Detection:
Alarm Pump
�� High Liquid Level �� On
�� Low Liquid Level �� Off
�� Off
Tank Liquid Level Circuit Breaker
�� Normal �� On
�� High �� Off
�� Low �� Tripped
�� Switched
Cause of Malfunction
Mechanical Physical or Process-Related
�� Control Panel �� Power
�� Pump �� Back Pressure
�� Float Switch �� Air Bound
�� Screened Vault �� Sludge & Scum
�� Hose & Valve �� Clog
�� Check Valve �� Infiltration/Inflow
�� Building Sewer �� Exfiltration
�� Service Line �� Siphoning
�� Other:______________ �� Other:________________
Repair: _________________________________________
Replace: _______________________________________
Operator Responding:____________________________
Date/Time Responded: ___________________________
Total Field Time: _________________________________
Total Travel Time: ________________________________
Alarm call by: ___________________________________
Alarm call Date/Time: ____________________________
Notes: ______________________________________________________________________________________________
Date: _______________________________________________________________________________________________
Inspector: ___________________________________________________________________________________________
Address: ____________________________________________________________________________________________
System Type: ________________________________________________________________________________________
The following effluent tests can be easily and routinely performed in the field. Perform annually, or as frequently as necessary per the methodology indicated. For AXN systems, there is to be a minimum of four sampling events the first two years and then annual sampling thereafter. Record your results/observations in the space provided:
Parameter Methodology Typical Field Observations Pre-Test Lab Concurrence
Clarity Visual1 Clear (15 ± NTUs) _____________________
Odor Sniff2 Non-offensive (no _____________________ ________________________ smell of rotten eggs _____________________ ________________________ or cabbage; a musty, _____________________ ________________________ earthy, or moldy odor _____________________ ________________________ is normal) _____________________ ________________________
Oily film Visual; inside tank None (no red, blue, _____________________ green, or orange _____________________ sheen) _____________________
Foam Visual; inside tank None _____________________ pH Field 6-9 _____________________
Date_________________ Date: ___________________
Signature Signature
Field Sampler Lab Technician