Attachment 3 TED SOW Attachment for Vendor 1000kW Topside EDG - 3-18-24.pdf
PDF 166 KB Posted
- Attached to
- Diesel Generator Rental Federal contract opportunity
- Solicitation number
- N4215824QS017
About this file
This statement of work attachment outlines the technical requirements for rental of a 1,000 kW minimum standby power, 750kW continuous power diesel generator. The generator must be trailer mounted and housed in a rain-tight outdoor enclosure. It must have a minimum 24 hour fuel capacity from an onboard or external 1240 gallon maximum fuel tank. The generator must be able to operate in parallel with a naval vessel's electric plant and be no more than 10 years old. The rental period is from March 18, 2024 to September 18, 2024 with an option to extend monthly for 3 months. The related solicitation seeks proposals for this diesel generator rental to be delivered to Norfolk Naval Shipyard Building 298 in Portsmouth, Virginia under solicitation number N4215824QS017 issued by the Department of the Navy Naval Sea Systems Command.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 1 FAR 52.212-1 Addendum .pdf | ||
| Attachment 4 NNSY OPSEC Contract Requirements Enclosure 2 -- No OPSEC Plan.pdf | ||
| Attachment 2 Statement of Work 1000kW Topside EDG - 3-18-24 (002).pdf | ||
| Attachment 5 Combined Synopsis and Solicitaton .pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK ATTACHMENT
Toledo Topside Undocking / Destructive Weather Emergency Diesel Generator
Vendor shall certify that equipment being quoted meets the capabilities listed below and that vendor can assume all contractor responsibilities stated below by initialing at the bottom.
Furthermore, vendor shall provide technical specification data sheet in Tables A, B, and C for the equipment that will be provided. In order to be considered for award, this must be completed and submitted with the vendor quote.
PURPOSE OF REQUEST: Service rental from vendor to provide one (1) trailer mounted 1,000 kW minimum Standby Power, 750kW Continuous Power (COP) Diesel Generator.
LOCATION: Norfolk Naval Shipyard (NNSY), Bldg 298, Portsmouth, VA 23709
PERIOD OF PERFORMANCE: 18 March 2024 to 18 September 2024 with clause to extend month to month for 3 months if needed.
Table A
TECHNICAL CAPABILITIES STATEMENT
1,000 kW Standby Diesel Generator YES NO
Output: 450volts, 3 phase, 3 wire ungrounded.
Standby Rating of 1,000kW (minimum), Continuous Power (COP) of 750kW (minimum)
Must be equipped with a block heater and battery charging circuit and suitable pigtails for mating with NNSY 120V distribution services cans.
Diesel generator shall be capable of parallel operation with ship’s ungrounded electric plant.
Diesel generator shall be capable of paralleling with a shipboard diesel generator, diesel to be ungrounded with neutral lifted.
Safety Devices: Output circuit breaker Long Time Overcurrent trip set to 150% of Base
Load COP current rating.
Diesel generator unit dimensions shall not exceed 20’ L x 8’ W. Weight not to exceed
45,000 lbs.
Diesel fuel capacity must be capable of twenty-four (24) hour minimum run time prior to refueling at full Continuous Base Load. (onboard and/or external fuel tank included)
External fuel tank shall be 1240 gallons maximum, if utilized. Unit dimensions shall not exceed 10’ L by 8’ W, fully fueled weight not to exceed 15,000 lbs. In lieu of one (1) tank, two (2) tanks can be used with dimensions not to exceed 5’-5 3/8” by 7’-8 5/8” max weight per tank 6200lbs (fully fueled). Fuel cell lifting points shall have current capacity certifications.
Onboard/External fuel tank(s) shall allow for refueling while diesel generator is operating.
Self-contained cooling system.
Trailer mounted. Lifting points shall have current capacity certifications.
Outdoor enclosure. Unit shall be equipped with rain-tight enclosure & block heater.
1,000 kW Standby Diesel Generator (cont) YES NO
The Diesel generator shall be of recent vintage (not more than ten years old), clean, and well maintained. The generator winding shall be a minimum of 5MΩ above ground with neutral disconnected. The unit shall have been tested within two weeks of delivery and applicable test data sent with unit.
All neutral connections shall be disconnected and isolated from generator windings and any additional equipment as necessary.
Unit shall have posted operating instructions in the vicinity of the control panel that clearly state how to start, stop and operate the diesel generator and output circuit breaker. The posted instructions shall include any necessary steps for proper operation of the diesel generator in parallel with ship’s service motor generator. Operating instructions may require clarification at ship’s request after delivery, and vendor is to clarify instructions as necessary.
Unit shall be compatible with Shipyard furnished “THOF-500E”-T-500 lugged output cables (4 per phase). If mechanical lug connections are provided, they shall be sized for
500MCM (4 per phase).
Table B
Rating (kW) Rating (Amps)
Standby Power
Prime Power
Base Load Continuous
Operating Power (COP)
Table C
Load (kW) Burn Rate
(Gallons/HR)
Run Time (Hours)
Standby Power
Prime Power
Base Load Continuous
Operating Power (COP)
TECHNICAL CAPABILITY/CONTRACTOR RESPONSIBILITY CERTIFICATION
Vendor hereby certifies that vendor’s service meets or exceeds all specifications and contractor responsibilities stated in this solicitation, in their entirety, with no exceptions. ___________ (initials)
Signature Printed Name
Title Date
File details come from the government source that posted it. Updated .