Attachment 3 - Specifications - Boulder Showerhouse.pdf
PDF 439 KB Posted
- Attached to
- Boulder Showerhouse Rehab Federal contract opportunity
- Solicitation number
- 12445524Q0102
- Issued by
- Department of Agriculture Forest Service
About this file
This document is a Project Manual for the rehabilitation of shower houses located in the Boulder Campground in the Chequamegon-Nicolet National Forest. The project includes selective demolition, thermal and moisture protection, openings, finishes, specialties, plumbing, HVAC, and electrical work. The document provides detailed technical specifications for the different divisions of work required. A coordinated site visit is scheduled for August 21, 2024 at 10:00 a.m. CST. The Project Manual is part of a federal solicitation (Solicitation Number: 12445524Q0102) issued by the U.S. Department of Agriculture Forest Service for the Boulder Showerhouse Rehab project.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 4 - Wage Determination - Oconto County.pdf | ||
| Attachment 1 - Pricing Breakout - Boulder Showerhouse.xlsx | XLSX spreadsheet | |
| 12445524Q0102 - Boulder Showerhouse.pdf | ||
| Attachment 2 - Plans - Boulder Showerhouse.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT MANUAL
Boulder Campground Shower Houses Rehabilitation
Prepared by:
U.P. Engineers & Architects, Inc.
100 Portage Street
Houghton, MI 49931
October 2017
Table of Contents 00010 - 1
DOCUMENT 00010
TABLE OF CONTENTS
TECHNICAL SPECIFICATIONS
DIVISION 02 – EXISTING CONDITIONS
02 41 19.13 Selective Structure Demolition
DIVISION 07 – THERMAL AND MOISTURE PROTECTION
07 90 00 Joint Protection
DIVISION 08 – OPENINGS
08 12 13 Standard Hollow Metal Frames 08 13 13 Standard Hollow Metal Doors 08 53 00 Plastic Windows 08 71 00 Door Hardware 08 91 00 Louvers
DIVISION 09 – FINISHES
09 67 00 Fluid-Applied Flooring 09 90 00 Painting and Coating
DIVISION 10 – SPECIALTIES
10 21 13 Stainless Steel Toilet Compartments 10 28 00 Toilet, Bath, and Laundry Accessories
DIVISION 22 – PLUMBING
22 05 29 Hangers and Support for Plumbing Piping and Equipment 22 05 53 Identification for Plumbing Piping and Equipment 22 07 00 Plumbing Insulation 22 11 00 Facility Water Distribution 22 13 00 Facility Sanitary Sewerage 22 34 00 Fuel-Fired Domestic Water Heaters 22 40 00 Plumbing Fixtures
DIVISION 23 – HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 05 29 Hangers and Supports for HVAC Piping and Equipment 23 05 93 Testing, Adjusting, and Balancing for HVAC 23 07 00 HVAC Insulation 23 11 26 Facility Liquefied-Petroleum Gas Piping 23 31 00 HVAC Ducts and Casings 23 33 00 Air Duct Accessories 23 34 00 HVAC Fans 23 37 00 Air Outlets and Inlets
DIVISION 26 – ELECTRICAL
26 05 00 General Electrical Requirements 26 05 02 Minor Electrical Demolition
Table of Contents 00010 - 2
26 05 03 Equipment Wiring Connections 26 05 19 Conductors and Cables 26 05 33 Raceways and Boxes 26 05 53 Electrical Identification 26 09 23 Lighting Control Devices 26 24 16 Panelboard 26 27 26 Wiring Devices 26 51 00 Interior Lighting
END OF TABLE OF CONTENTS
[U28-17435]
SELECTIVE BUILDING DEMOLITION 024119.13 - 1
SECTION 024119.13 - SELECTIVE BUILDING DEMOLITION
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Demolishing designated building equipment and fixtures.
2. Demolishing designated construction.
3. Cutting and alterations for completion of the Work.
4. Removing designated items for reuse and Owner’s retention.
5. Protecting items designated to remain.
6. Removing demolished materials.
1.2 SUBMITTALS
A. Section 013300 - Submittal Procedures: Requirements for submittals.
B. Demolition Schedule: Indicate overall schedule and interruptions required for utility and building services.
1.3 CLOSEOUT SUBMITTALS
A. Section 017000 - Execution and Closeout Requirements: Requirements for submittals.
B. Project Record Documents: Accurately record actual locations of capped utilities, concealed utilities discovered during demolition, and subsurface obstructions.
C. Operation and Maintenance Data: Submit description of system, inspection data, and parts lists.
1.4 QUALITY ASSURANCE
A. Conform to applicable code for demolition work, dust control, products requiring electrical disconnection and re-connection.
B. Conform to applicable code for procedures when hazardous or contaminated materials are discovered.
C. Obtain required permits from authorities having jurisdiction.
1.5 SEQUENCING
A. Owner will conduct salvage operations before demolition begins to remove materials Owner chooses to retain.
SELECTIVE BUILDING DEMOLITION 024119.13 - 2
1.6 SCHEDULING
A. Schedule Work to coincide with new construction.
B. Cooperate with Owner in scheduling noisy operations and waste removal that may impact Owners operation and in adjoining spaces.
C. Coordinate utility and building service interruptions with Owner.
1. Do not disable or disrupt building fire or life safety systems without three days prior written notice to Owner.
2. Schedule tie-ins to existing systems to minimize disruption.
3. Coordinate Work to ensure fire sprinklers, fire alarms, smoke detectors, emergency lighting, exit signs and other life safety systems remain in full operation in occupied areas.
1.7 PROJECT CONDITIONS
A. Conduct demolition to minimize interference with adjacent and occupied building areas.
B. Cease operations immediately if structure appears to be in danger and notify Architect/Engineer. Do not resume operations until directed.
PART 2 - PRODUCTS
2.1 Not Used.
PART 3 - EXECUTION
3.1 PREPARATION
A. Notify affected utility companies before starting work and comply with their requirements.
B. Mark location and termination of utilities.
C. Erect, and maintain temporary barriers and security devices, including warning signs and lights, and similar measures, for protection of the public, Owner, and existing improvements indicated to remain.
D. Erect and maintain weatherproof closures for exterior openings.
E. Erect and maintain temporary partitions to prevent spread of dust, odors, and noise to permit continued Owner occupancy.
F. Prevent movement of structure; provide temporary bracing and shoring required to ensure safety of existing structure.
SELECTIVE BUILDING DEMOLITION 024119.13 - 3
G. Provide appropriate temporary signage including signage for exit or building egress.
H. Do not close or obstruct building egress path.
I. Do not disable or disrupt building fire or life safety systems without 3 days prior written notice to Owner.
3.2 SALVAGE REQUIREMENTS
A. Coordinate with Owner to identify building components and equipment required to be removed and delivered to Owner.
B. Tag components and equipment Owner designates for salvage.
C. Protect designated salvage items from demolition operations until items can be removed.
D. Carefully remove building components and equipment indicated to be salvaged.
E. Disassemble as required to permit removal from building.
F. Package small and loose parts to avoid loss.
G. Mark equipment and packaged parts to permit identification and consolidation of components of each salvaged item.
H. Prepare assembly instructions consistent with disassembled parts. Package assembly instructions in protective envelope and securely attach to each disassembled salvaged item.
I. Deliver salvaged items to Owner. Obtain signed receipt from Owner.
3.3 DEMOLITION
A. Conduct demolition to minimize interference with adjacent and occupied building areas.
B. Maintain protected egress from and access to adjacent existing buildings at all times.
C. Do not close or obstruct roadways or sidewalks without permits.
D. Cease operations immediately when structure appears to be in danger and notify Architect/Engineer.
E. Disconnect and remove designated utilities within demolition areas.
F. Cap and identify abandoned utilities at termination points when utility is not completely removed. Annotate Record Drawings indicating location and type of service for capped utilities remaining after demolition.
G. Demolish in orderly and careful manner. Protect existing improvements and supporting structural members.
SELECTIVE BUILDING DEMOLITION 024119.13 - 4
H. Carefully remove building components indicated to be reused.
1. Disassemble components as required to permit removal.
2. Package small and loose parts to avoid loss.
3. Mark components and packaged parts to permit reinstallation.
4. Store components, protected from construction operations, until reinstalled.
I. Remove demolished materials from site except where specifically noted otherwise. Do not burn or bury materials on site.
J. Remove materials as Work progresses. Upon completion of Work, leave areas in clean condition.
K. Remove temporary Work.
L. Patch existing remaining surfaces adjacent to demolition work to provide a seamless finish between new and existing surfaces.
M. Contractor shall be responsible for restoration of installed construction that is damaged as a result of construction and cutting and patching activities.
END OF SECTION 024119
JOINT PROTECTION 079000 - 1
SECTION 079000 - JOINT PROTECTION
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Sealants and joint backing.
2. Accessories.
1.2 REFERENCE STANDARDS
A. ASTM International:
1. ASTM C834 - Standard Specification for Latex Sealants.
2. ASTM C920 - Standard Specification for Elastomeric Joint Sealants.
3. ASTM C1193 - Standard Guide for Use of Joint Sealants.
4. ASTM D1056 - Standard Specification for Flexible Cellular Materials - Sponge or
Expanded Rubber.
5. ASTM D1667 - Standard Specification for Flexible Cellular Materials - Poly(Vinyl
Chloride) Foam (Closed-Cell).
6. ASTM D2628 - Standard Specification for Preformed Polychloroprene Elastomeric Joint
Seals for Concrete Pavements.
B. South Coast Air Quality Management District:
1. SCAQMD Rule 1168 - Adhesive and Sealant Applications.
1.3 SUBMITTALS
A. Section 013300 - Submittal Procedures: Requirements for submittals.
B. Product Data: Submit manufacturer information indicating sealant chemical characteristics, performance criteria, substrate preparation, limitations, and color availability.
C. Samples: Submit two samples, 2 by 1/8 inches in size, illustrating sealant colors for selection.
D. Manufacturer Instructions: Submit special procedures, surface preparation requirements, and perimeter conditions requiring special attention.
E. Warranty: Include coverage for installed sealants and accessories failing to achieve airtight seal, watertight seal, exhibit loss of adhesion or cohesion, and sealants which do not cure.
JOINT PROTECTION 079000 - 2
1.4 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing products specified in this Section with minimum three years' documented experience.
B. Applicator: Company specializing in performing Work of this Section with minimum three years' documented experience.
1.5 AMBIENT CONDITIONS
A. Section 016000 – Product Requirements.
B. Maintain temperature and humidity as recommended by sealant manufacturer during and after installation.
PART 2 - PRODUCTS
2.1 JOINT SEALERS
A. Manufacturers:
1. BASF Building Systems
2. DAP Products Inc.
3. Dow Corning Corporation
4. Substitutions: As specified in Section 016000 - Product Requirements.
2.2 JOINT SEALERS BY APPLICATION
A. High-Performance General-Purpose Exterior (Nontraffic) Sealant:
1. Material: Polyurethane.
2. Comply with ASTM C920, Grade NS, Class 25, Uses M, G, and A.
3. Type: Single-component.
4. Color: Standard; match finished surfaces.
5. Applications:
a. Control, expansion, and soft joints in masonry.
b. Joints between concrete and other materials.
c. Joints between metal frames and other materials.
d. Other exterior nontraffic joints for which no other sealant is indicated.
B. General-Purpose Traffic-Bearing Sealant:
1. Material: Polyurethane.
2. Comply with ASTM C920, Grade P, Class 25, Use T.
3. Type: Single-component.
4. Color: Standard; match finished surfaces.
5. Applications: Exterior pedestrian traffic-bearing joints.
JOINT PROTECTION 079000 - 3
C. Exterior Foam Expansion Joint Sealer:
1. Description: Precompressed foam sealer recommended by manufacturer for traffic-bearing use.
2. Material: Polyurethane with water repellent.
3. Color: Black.
4. Size: As required to provide weathertight seal when installed.
5. Applications: Exterior wall expansion joints.
6.
D. General Purpose Interior Sealant:
1. Material: Acrylic-emulsion latex.
2. Comply with ASTM C834.
3. Type: Single-component; paintable.
4. Color: Standard; match finished surfaces.
5. Applications:
a. Interior wall and ceiling control joints.
b. Joints between door and window frames and wall surfaces.
c. Other interior joints for which no other type of sealant is indicated.
E. Sanitary Sealant:
1. Material: Silicone.
2. Comply with ASTM C920, Uses M and A.
3. Type: Single-component; mildew resistant.
4. Color: Clear.
5. Applications:
a. Joints between plumbing fixtures and floor and wall surfaces.
b. Joints between bathroom countertops and wall surfaces.
2.3 ACCESSORIES
A. Primer:
1. Type: Non-staining.
2. As recommended by sealant manufacturer to suit application.
B. Joint Cleaner:
1. Type: Non-corrosive and non-staining.
2. As recommended by sealant manufacturer.
3. Compatible with joint forming materials.
C. Joint Backing:
1. Description: Round foam rod, compatible with sealant.
2. Comply with ASTM D1667, closed-cell PVC.
JOINT PROTECTION 079000 - 4
3. Size: Oversized 30 to 50 percent larger than joint width.
D. Bond Breaker:
1. Description: Pressure-sensitive tape.
2. As recommended by sealant manufacturer to suit application.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Section 017000 - Execution and Closeout Requirements: Requirements for application examination.
B. Verify that substrate surfaces and joint openings are ready to receive Work of this Section.
C. Verify that joint backing and release tapes are compatible with sealant.
3.2 PREPARATION
A. Section 017000 - Execution and Closeout Requirements: Requirements for application preparation.
B. Comply with ASTM C1193.
C. Remove loose materials and foreign matter that could impair adhesion of sealant.
D. Clean and prime joints.
E. Protect elements surrounding Work of this Section from damage or disfiguration.
3.3 APPLICATION
A. Comply with ASTM C1193.
B. Measure joint dimensions and size joint backers to achieve following:
1. Width to Depth Ratio: 2:1.
2. Neck Dimension: No greater than 1/2 of joint width.
3. Surface Bond Area on Each Side: Not less than 75 percent of joint width.
C. Install bond breaker where joint backing is not used.
D. Apply sealant free of air pockets, foreign embedded matter, ridges, and sags.
E. Joint Tooling: Concave.
F. Precompressed Foam Sealant:
JOINT PROTECTION 079000 - 5
1. Do not stretch.
2. Avoid joints except at corners, ends, and intersections.
3. Apply with face 1/8 to 1/4 inch below adjoining surface.
G. Compression Gaskets:
1. Avoid joints except at ends, corners, and intersections.
2. Seal joints with adhesive.
3. Install with face 1/8 to 1/4 inch below adjoining surface.
3.4 CLEANING
A. Section 017000 - Execution and Closeout Requirements: Requirements for cleaning.
B. Clean adjacent soiled surfaces.
3.5 PROTECTION
A. Section 017000 - Execution and Closeout Requirements: Requirements for protecting finished Work.
B. Protect sealants until cured.
END OF SECTION 079000
STANDARD HOLLOW METAL FRAMES 081213.13 - 1
SECTION 081213.13 - STANDARD HOLLOW METAL FRAMES
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes non-rated steel frames.
B. Related Sections:
1. Section 081314 - Standard Steel Doors.
1.2 REFERENCES
A. American National Standards Institute:
1. ANSI A250.8 - Recommended Specifications for Standard Steel Doors and Frames.
B. ASTM International:
1. ASTM A653/A653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.
1.3 SUBMITTALS
A. Section 013300 - Submittal Procedures: Submittal procedures.
B. Shop Drawings: Indicate frame elevations, reinforcement, anchor types and spacing, location of cut-outs for hardware, and finish.
C. Product Data: Submit frame configuration and finishes.
D. Manufacturer's Installation Instructions: Submit special installation instructions.
E. Manufacturer's Certificate: Certify products meet or exceed specified requirements.
1.4 QUALITY ASSURANCE
A. Conform to requirements of ANSI A250.8.
1.5 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum three years documented experience.
STANDARD HOLLOW METAL FRAMES 081213.13 - 2
1.6 DELIVERY, STORAGE, AND HANDLING
A. Section 016000 - Product Requirements: Product storage and handling requirements.
B. Accept frames on site in manufacturer's packaging. Inspect for damage.
C. Break seal on-site to permit ventilation.
1.7 COORDINATION
A. Section 013000 - Administrative Requirements: Coordination and project conditions.
B. Coordinate Work with frame opening construction, door, and hardware installation.
C. Sequence installation to accommodate required door hardware electric wire connections.
PART 2 - PRODUCTS
2.1 STANDARD STEEL FRAMES
A. Manufacturers:
1. Amweld Building Products, Inc.
2. Ceco Door Products
3. LaForce, Inc.
4. Republic Builders Products
5. Steelcraft
6. Substitutions: Section 016000 - Product Requirements.
B. Product Description: Standard shop fabricated steel frames, fire rated and non-rated types.
1. Exterior Frames:
a. Level 3, nominal 16 gage/0.053 inch thick material, base metal thickness.
2.2 ACCESSORIES
A. Removable Stops: Rolled steel channel shape, mitered corners; prepared for countersink style tamper proof screws.
B. Bituminous Coating: Non-asbestos fibered asphalt emulsion.
C. Primer: ANSI A250.10 rust inhibitive type.
D. Silencers: Resilient rubber fitted into drilled hole.
E. Weatherstripping: Resilient rubber set in steel retainer.
STANDARD HOLLOW METAL FRAMES 081213.13 - 3
2.3 FABRICATION
A. Fabricate frames for knock down field assembly.
B. Fabricate frames with hardware reinforcement plates welded in place. Provide mortar guard boxes.
C. Prepare frames for silencers. Provide three single silencers for single doors on strike side.
Provide two single silencers on frame head at double doors without mullions.
D. Attach fire rated label to each fire rated frame.
E. Fabricate frames to suit masonry wall coursing with 4 inch head member.
2.4 SHOP FINISHING
A. Steel Sheet: Galvanized to ASTM A653/A653M.
B. Primer: Baked.
C. Factory Finish: Thermosetting epoxy of color to match existing.
D. Coat inside of frame profile with bituminous coating to minimum thickness of 1/16 inch.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Section 013000 - Administrative Requirements: Coordination and project conditions.
B. Verify opening sizes and tolerances are acceptable.
3.2 INSTALLATION
A. Install frames in accordance with ANSI A250.8.
B. Coordinate with masonry wall construction for anchor placement.
3.3 ERECTION TOLERANCES
A. Section 014000 - Quality Requirements: Tolerances.
B. Maximum Diagonal Distortion: 1/16 inch measured with straight edges, crossed corner to corner.
END OF SECTION 081213.13
STANDARD HOLLOW METAL DOORS 081313.13 - 1
SECTION 081313.13 - STANDARD HOLLOW METAL DOORS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes non-rated, steel doors.
B. Related Sections:
1. Section 081213 - Standard Hollow Metal Frames.
2. Section 087100 - Door Hardware.
3. Section 099000 - Painting and Coating: Field painting of doors.
1.2 REFERENCES
A. American National Standards Institute:
1. ANSI A250.8 - Recommended Specifications for Standard Steel Doors and Frames.
B. ASTM International:
1. ASTM A653/A653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.
2. ASTM C1363 - Standard Test Method for the Thermal Performance of Building Assemblies by Means of a Hot Box Apparatus.
3. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials.
4. ASTM E413 - Classification for Rating Sound Insulation.
C. Hollow Metal Manufacturers Association:
1. HMMA 810 - Hollow Metal Doors.
D. Steel Door Institute:
1. SDI 108 - Recommended Selection and Usage Guide for Standard Steel Doors.
1.3 SUBMITTALS
A. Section 013300 - Submittal Procedures: Requirements for submittals.
B. Shop Drawings: Indicate door elevations, internal reinforcement, closure method, and cut-outs for glazing and finishes.
C. Product Data: Submit door configurations, location of cut-outs for hardware reinforcement.
STANDARD HOLLOW METAL DOORS 081313.13 - 2
D. Samples: Submit two samples of door face metal, 12x12 inch in size illustrating shop finish colors and surface texture.
E. Manufacturer's Installation Instructions: Submit special installation instructions.
1.4 QUALITY ASSURANCE
A. Perform Work in accordance with ANSI A250.8.
1.5 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing Products specified in this section with minimum ten years’ experience.
B. Installer: Company specializing in performing work of this section with minimum 3 years’ experience.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Section 016000 - Product Requirements: Requirements for transporting, handling, storing, and protecting products.
B. Accept doors on site in manufacturer's packaging. Inspect for damage.
C. Break seal on site to permit ventilation.
1.7 COORDINATION
A. Section 013000 - Administrative Requirements: Requirements for coordination.
B. Coordinate Work with door opening construction, door frame, and door hardware installation.
C. Coordinate installation to accommodate door hardware electric wire connections.
PART 2 - PRODUCTS
2.1 STANDARD STEEL DOORS
A. Manufacturers:
1. Amweld Building Products, Inc.
2. Ceco Door Products
3. LaForce, Inc.
4. Republic Builders Products
5. Steelcraft
6. Substitutions: Section 016000 - Product Requirements.
STANDARD HOLLOW METAL DOORS 081313.13 - 3
B. Product Description:
1. Exterior Doors (Insulated): ANSI A250.8, 1-3/4 inch thick.
a. Level 3 - Extra Heavy Duty, Model 1, full flush design.
2.2 COMPONENTS
A. Face: Steel sheet in accordance with ANSI A250.
B. End Closure: Channel, 0.04 inches thick, flush.
C. Core: polystyrene foam or mineral fiberboard with vertical steel stiffeners.
2.3 FABRICATION
A. Fabricate doors with hardware reinforcement welded in place.
2.4 SHOP FINISHING
A. Steel Sheet: Galvanized to ASTM A653/A653M A60.
B. Primer: Baked.
C. Shop Finish: Baked enamel of color as selected to match existing.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Section 013000 - Administrative Requirements: Verification of existing conditions before starting work.
B. Verify opening sizes and tolerances are acceptable.
3.2 INSTALLATION
A. Install doors in accordance with ANSI A250.8.
B. Coordinate installation of doors with installation of frames specified in Section 081214 and hardware specified in Section 087100.
C. Touch-up damaged shop finishes.
STANDARD HOLLOW METAL DOORS 081313.13 - 4
3.3 ERECTION TOLERANCES
A. Section 014000 - Quality Requirements: Tolerances.
B. Maximum Diagonal Distortion: 1/16 inch measured with straight edge, corner to corner.
3.4 ADJUSTING
A. Section 017000 - Execution and Closeout Requirements: Requirements for adjusting.
B. Adjust door for smooth and balanced door movement.
PLASTIC WINDOWS 085300 - 1
SECTION 085300 - PLASTIC WINDOWS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Factory fabricated tubular, extruded plastic windows.
2. Factory glazing.
3. Operating hardware.
4. Insect screens.
B. Related Requirements:
1. Section 079000 - Joint Protection: Perimeter sealant and backup materials.
1.2 REFERENCE STANDARDS
A. American Architectural Manufacturers Association:
1. AAMA 101 - NAFS - North American Fenestration Standard/Specification for windows, doors, and skylights.
2. AAMA 1503 - Voluntary Test Method for Thermal Transmittance and Condensation Resistance of Windows, Doors and Glazed Wall Sections.
B. American Society of Civil Engineers:
1. ASCE 7 - Minimum Design Loads for Buildings and Other Structures.
C. ASTM International:
1. ASTM D3656/D3656M - Standard Specification for Insect Screening and Louver Cloth
Woven from Vinyl-Coated Glass Yarns.
2. ASTM E283 - Standard Test Method for Determining Rate of Air Leakage Through
Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen.
3. ASTM E330/E330M - Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference.
4. ASTM E331 - Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference.
5. ASTM E1105 - Standard Test Method for Field Determination of Water Penetration of Installed Exterior Windows, Skylights, Doors, and Curtain Walls, by Uniform or Cyclic Static Air Pressure Difference.
D. Glass Association of North America:
1. GANA Glazing Manual.
PLASTIC WINDOWS 085300 - 2
E. National Fenestration Rating Council:
1. NFRC 100 - Procedure for Determining Fenestration Product U-factors.
1.3 SUBMITTALS
A. Section 013300 - Submittal Procedures: Requirements for submittals.
B. Product Data: Submit component dimensions, anchorage and fasteners, glass, internal drainage, and typical details.
C. Shop Drawings: Indicate opening dimensions, framed opening tolerances, affected related Work, and installation requirements.
D. Samples (required for unspecified alternative only):
1. Submit one full unit.
E. Manufacturer's Certificates:
1. Certify that products meet or exceed specified requirements.
1.4 QUALITY ASSURANCE
A. Fiberglass windows: Fabricate and label window assemblies according to AAMA 101 for types of required windows.
B. Insulated Glass: Fabricate insulated glass units according to GANA Glazing Manual.
C. Perform Work according to industry standards.
1.5 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing products specified in this Section with minimum three years' documented experience.
B. Installer: Company specializing in performing Work of this Section with minimum three years' documented experience.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Section 016000 - Product Requirements: Requirements for transporting, handling, storing, and protecting products.
B. Inspection: Accept materials on Site in manufacturer's original packaging and inspect for damage.
PLASTIC WINDOWS 085300 - 3
C. Handling: Jig, brace, and box window frame assemblies for transport to minimize flexing of members and joints.
D. Store materials according to manufacturer instructions.
E. Protection:
1. Protect materials from moisture and dust by storing in clean, dry location remote from construction operations areas.
2. Covering:
a. Protect finished surfaces with wrapping.
b. Do not use adhesive papers or sprayed coatings that bond when exposed to sunlight or weather.
3. Provide additional protection according to manufacturer instructions.
1.7 AMBIENT CONDITIONS
A. Section 015000 - Temporary Facilities and Controls: Requirements for ambient condition control facilities for product storage and installation.
B. Minimum Conditions: Do not install glazing materials when ambient temperature is less than 40 deg. F.
C. Subsequent Conditions: Maintain minimum temperature of 40 deg. F during and for 12 hours after installation of glazing materials.
1.8 WARRANTY
A. Section 017000 - Execution and Closeout Requirements: Requirements for warranties.
B. Furnish ten-year manufacturer's warranty for hardware and other non-glass components.
C. Furnish ten-year manufacturer's warranty for insulated glass units from seal failure, interpane dusting or misting, and replacement of same.
D. Furnish ten-year manufacturer's warranty for integrity and fade resistance of factory-applied exterior color finishes.
PART 2 - PRODUCTS
2.1 FIBERGLASS WINDOWS
A. Manufacturers:
1. Marvin Integrity
2. Milgard Ultra
3. Pella Impervia
4. Substitutions: As specified in Section 016000 - Product Requirements.
PLASTIC WINDOWS 085300 - 4
B. Description:
1. Reinforced fiberglass windows, sash, glass and glazing, insect screens, and operating hardware.
2. Window Configuration: Horizontal sliding.
C. Performance and Design Criteria:
1. Primary Performance Requirements: Comply with AAMA 101, Designation R15, Residential or better.
2. Wind-Load Deflection: Comply with AAMA 101.
3. Assembly: Without damage to components or deterioration of seals, accommodate movement between window and perimeter framing, and deflection of lintel.
4. Air and Vapor Seal: Maintain continuous air barrier and vapor retarder throughout assembly.
5. System Internal Drainage: Drain to exterior by weep drainage network water entering joints, condensation occurring in glazing channels, and migrating moisture occurring within system.
6. Thermal Movement: Design sections to permit movement caused by thermal expansion and contraction of plastic to suit glass, infill, and perimeter opening construction.
7. Maximum Air Infiltration:
a. 0.3 cfm/sq. ft. of wall area, measured at reference differential pressure across assembly of 1.57 psf.
b. Testing: Comply with ASTM E283.
8. Thermal Performance:
a. Comply with ICC IECC for climate zone in which Project is located, as measured according to NFRC 100.
9. Water Leakage:
a. None.
b. Measurement: Comply with ASTM E547, with test pressure difference as defined by AAMA 101.
2.2 MATERIALS
A. Frame and Sash:
1. Reinforced fiberglass.
B. Insulating Glass:
1. Description: Sealed double-pane units.
2. Outer Pane: Obscure glass.
3. Inner Pane: Clear float glass.
4. Pane Thickness: As determined by size or wind and suction loads.
C. Hardware:
1. Sash Lock:
a. Description: Lever handle with cam lock.
PLASTIC WINDOWS 085300 - 5
D. Operable Sash Weather Stripping:
1. Material: Resilient plastic.
2. Type: Permanently resilient.
3. Profile: To effect weather seal.
E. Insect Screens:
1. Frame:
a. Description: Rolled form aluminum frame
b. Nominal Size: Similar to operable glazed unit.
c. Color: Manufacturer's standard dark brown.
2. Screens:
a. Fiberglass
b. Mesh Size: 18 by 16.
c. Color: Charcoal.
2.3 FABRICATION
A. Joints:
1. Ensure that joints and connections are flush, hairline, and weathertight.
B. Form snap-in glass stops, closure molds, weatherstops, and flashings of extruded plastic for tight fit into window frame section.
C. Fabricate components with minimum clearances and shim spacing around perimeter of assembly, yet enabling installation and dynamic movement of perimeter seal.
D. Arrange fasteners to be concealed from view.
E. Drainage:
1. Permit internal drainage weep holes and channels to migrate moisture to exterior.
2. Furnish internal drainage of glazing spaces to exterior through weep holes.
F. Insect Screens:
1. Assemble insect screen frame, and miter and reinforce frame corners.
2. Fit mesh taut into frame and secure.
3. Fit frame with four spring-loaded steel pin retainers.
G. Glazing:
1. Factory glaze window units.
PLASTIC WINDOWS 085300 - 6
2.4 FINISHES
A. Exterior Surfaces: Manufacturer's standard dark brown.
B. Interior Surfaces: Manufacturer's standard dark brown.
C. Screens: Manufacturer's standard dark brown frames with light screening.
D. Hardware: Anodized aluminum to dark bronze color.
2.5 ACCESSORIES
A. Fasteners and Anchors: Galvanized steel.
B. Limit Stops: Galvanized steel. Security hardware/ access to limit stops.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Section 017000 - Execution and Closeout Requirements: Requirements for installation examination.
B. Verify that wall openings and adjoining air and vapor seal materials are ready to receive Work of this Section.
C. Verify that opening dimensions and clearances are properly sized.
3.2 INSTALLATION
A. Attach window frame and shims to perimeter opening; accommodate construction tolerances and other irregularities.
B. Align window plumb and level, free of warping or twisting.
C. Maintain dimensional tolerances and alignment with adjacent Work.
D. Thermal Barrier:
1. Spray foam insulation in shim spaces at perimeter of assembly to maintain continuity of thermal barrier.
E. Coordinate attachment and seal of perimeter air and of vapor retarder materials.
F. Install operating hardware.
PLASTIC WINDOWS 085300 - 7
3.3 TOLERANCES
A. Section 014000 - Quality Requirements: Requirements for tolerances.
B. Maximum Variation from Level or Plumb: 1/16 in./3 ft. noncumulative, or 1/8 in./10 ft., cumulative, whichever is less.
3.4 ADJUSTING
A. Section 017000 - Execution and Closeout Requirements: Requirements for starting and adjusting.
B. Adjust hardware for smooth operation and to ensure weathertight closure.
3.5 CLEANING
A. Section 017000 - Execution and Closeout Requirements: Requirements for cleaning.
B. Remove protective material from prefinished surfaces.
C. Washing:
1. Wash surfaces by method recommended by sealant and window manufacturer.
2. Rinse and wipe surfaces clean.
D. Remove labels and visible markings.
END OF SECTION 085300
DOOR HARDWARE 087100 - 1
SECTION 087100 - DOOR HARDWARE
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Hardware for steel doors.
1.2 REFERENCE STANDARDS
A. Builders Hardware Manufacturers Association:
1. ANSI/BHMA Directory of Certified Products
2. ANSI/BHMA A156.1 - Butts and Hinges.
3. ANSI/BHMA A156.2 - Bored & Preassembled Locks and Latches.
4. ANSI/BHMA A156.3 - Exit Devices.
5. ANSI/BHMA A156.4 - Door Controls - Closers.
6. ANSI/BHMA A156.5 - Cylinders and Input Devices for Locks.
7. ANSI/BHMA A156.6 - Architectural Door Trim.
8. ANSI/BHMA A156.7 - Template Hinge Dimensions.
9. ANSI/BHMA A156.8 - Door Controls - Overhead Stops and Holders.
10. ANSI/BHMA A156.12 - Interconnected Locks & Latches.
11. ANSI/BHMA A156.13 - Mortise Locks.
12. ANSI/BHMA A156.14 - Sliding and Folding Door Hardware.
13. ANSI/BHMA A156.15 - Release Devices.
14. ANSI/BHMA A156.16 - Auxiliary Hardware.
15. ANSI/BHMA A156.17 - Self Closing Hinges.
16. ANSI/BHMA A156.18 - Materials and Finishes.
17. ANSI/BHMA A156.21 - Thresholds.
B. Intertek Testing Services (Warnock Hersey Listed):
1. WH - Listed Product and Code Compliance Directory.
C. NFPA:
1. NFPA 80 - Standard for Fire Doors and Other Opening Protectives.
2. NFPA 252 - Standard Methods of Fire Tests of Door Assemblies.
D. UL:
1. UL - Building Materials Directory.
2. UL 10B - Standard for Fire Tests of Door Assemblies.
3. UL 305 - Standard for Panic Hardware.
DOOR HARDWARE 087100 - 2
1.3 SUBMITTALS
A. Section 013300 - Submittal Procedures: Requirements for submittals.
B. Product Data: Submit manufacturer information.
C. Shop Drawings:
1. Indicate locations and mounting heights of each type of hardware.
2. Submit schedules and manufacturer's parts lists.
D. Finish Hardware List:
1. Designate items of hardware furnished for each opening or place of installation, identified by floor name or number and door number as used in door schedule on Drawings.
2. Show door number and location, handing, door and frame material, manufacturer and catalog numbers, finishes, and keying information.
3. Explain abbreviations.
E. Manufacturer's Certificate: Certify that products meet or exceed specified requirements.
F. Manufacturer Instructions: Submit special procedures and perimeter conditions requiring special attention.
1.4 CLOSEOUT SUBMITTALS
A. Section 017000 - Execution and Closeout Requirements: Requirements for submittals.
B. Project Record Documents: Record actual locations of installed cylinders and their master key code.
C. Operation and Maintenance Data: Submit manufacturer information regarding operating hardware, lubrication requirements, and inspection procedures related to preventative maintenance.
D. Keys: Deliver with identifying tags to Owner by secure shipment direct from supplier.
1.5 MAINTENANCE MATERIAL SUBMITTALS
A. Section 017000 - Execution and Closeout Requirements: Requirements for maintenance materials.
B. Tools: Furnish special wrenches and tools applicable for each different and special hardware component.
1.6 QUALITY ASSURANCE
A. Perform Work according to:
DOOR HARDWARE 087100 - 3
1. ANSI/BHMA A156 series.
2. NFPA 80.
3. UL 305.
B. Furnish hardware marked and listed in BHMA Certified Products Directory.
1.7 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing products specified in this Section with minimum three years' documented experience.
B. Supplier:
1. Company specializing in supplying commercial door hardware as specified in this Section, with minimum three years' documented experience.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Section 016000 - Product Requirements: Requirements for transporting, handling, storing, and protecting products.
B. Handling:
1. Package hardware items individually with necessary fasteners, instructions, and installation templates.
2. Label and identify each package with door opening code to match hardware schedule.
C. Store materials according to manufacturer instructions.
D. Protection:
1. Protect materials from moisture and dust by storing in clean, dry location remote from construction operations areas.
2. Provide additional protection according to manufacturer instructions.
1.9 COORDINATION
A. Section 013000 – Administrative Requirements: Coordination and project conditions.
B. Coordinate Owner’s keying requirements during course of Work.
1.10 WARRANTY
A. Section 017000 - Execution and Closeout Requirements: Requirements for warranties.
B. Furnish two-year manufacturer's warranty for locksets and door closers.
DOOR HARDWARE 087100 - 4
PART 2 - PRODUCTS
2.1 DOOR HARDWARE
A. Closers:
1. Manufacturers:
a. Hager Companies
b. Yale Security
c. DORMA USA, Inc.
d. Substitutions: As specified in Section 016000 - Product Requirements.
2. Description:
a. Type: Modern, with cover.
b. Comply with ANSI/BHMA A156.4.
c. Mounting: Surface.
d. Operation: Full rack and pinion, with steel spring and nonfreezing hydraulic fluid.
3. Adjustability: Furnish controls for regulating closing, latching, speeds, and back checking.
4. Arms:
a. Type: To suit individual condition.
b. Furnish parallel-arm closers at reverse-bevel doors and where doors swing full 180 degrees.
5. Location:
a. Exterior Doors: Inside of door.
b. Interior Doors: Room side of door.
c. Other Doors: Pull side of door.
6. Maximum Operating Pressure:
a. Interior Doors: 5 lbf.
b. Exterior Doors: 8.5 lbf.
c. Fire-Rated Doors: 15 lbf.
B. Door Controls and Overhead Holders:
1. Manufacturers:
a. Hager Companies
b. Yale Security
c. DORMA USA, Inc.
d. Substitutions: As specified in Section 016000 - Product Requirements.
2. Manual Door Holders: Comply with ANSI/BHMA A156.8, Grade 1 types.
C. Push-Pulls, Protection Plates, Gaskets, Thresholds, and Trim:
DOOR HARDWARE 087100 - 5
1. Manufacturers:
a. Hager Companies
b. Substitutions: As specified in Section 016000 - Product Requirements.
2. Description: Furnish as indicated in Schedule, with accessories as required for complete operational door installations.
3. Push-Pulls:
a. Comply with ANSI/BHMA A156.6.
b. Minimum Thickness: 0.050 inch.
c. Pull Type: Match existing.
d. Furnish bolts to secure from opposite door face.
e. Pull Plates: Minimum thickness of 0.050 inch.
4. Kickplates, Mop Plates:
a. Comply with ANSI/BHMA A156.6.
b. Height: As indicated on hardware schedule.
c. Width: 1 inch less than door width.
d. Material:
1) Stainless steel.
2) Thickness: Minimum 0.050 inch.
5. Weatherstripping: Continuous at top and sides of exterior doors.
a. Comply with ANSI/BHMA A156.21.
6. Thresholds: Maximum height of 1/2 inch, ADA compliant.
a. Comply with ANSI/BHMA A156.21.
7. Wall Stops:
a. Size: 3 inches.
b. Description: Convex pad with no visible screws.
c. Comply with ANSI/BHMA A156.1, Grade 1.
8. Floor Stops:
a. Description: Standard floor type, with no visible screws.
b. Comply with ANSI/BHMA A156.1, Grade 1.
2.2 FINISHES
A. Finishes:
1. Comply with ANSI/BHMA A156.18.
2. Typical Exterior Exposed and High Use Interior Door Hardware:
a. Satin-Finished Stainless Steel: Comply with BHMA 630.
DOOR HARDWARE 087100 - 6
3. Typical Interior Door Hardware:
a. Satin-Finished Stainless Steel: Comply with BHMA 630.
4. Typical Interior Toilet Room Door Hardware:
a. Satin-Finished Stainless Steel: Comply with BHMA 630.
5. Closers:
a. Finish appearance to match door hardware on same face of door.
b. Clear Anodized Satin Aluminum: Comply with BHMA 628.
c. Primed for Painting: Comply with BHMA 600.
6. Other Items: Furnish manufacturer's standard finishes to match similar hardware types on same door, and maintain acceptable finish considering anticipated use and BHMA category of finish.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Section 017000 - Execution and Closeout Requirements: Requirements for installation examination.
B. Verify that doors and frames are ready to receive door hardware.
C. Verify that dimensions are as indicated by manufacturer.
3.2 INSTALLATION
A. According to manufacturer instructions.
B. Mounting Heights from Finished Floor to Center Line of Hardware Item:
1. Comply with manufacturer recommendations and applicable codes, if not otherwise indicated.
2. Push/Pulls: 42 inches.
3.3 FIELD QUALITY CONTROL
A. Section 017000 - Execution and Closeout Requirements: Requirements for testing, adjusting, and balancing.
DOOR HARDWARE 087100 - 7
3.4 ADJUSTING
A. Section 017000 - Execution and Closeout Requirements: Requirements for starting and adjusting.
B. Adjust hardware for smooth operation.
3.5 PROTECTION
A. Section 017000 - Execution and Closeout Requirements: Requirements for protecting finished Work.
B. Do not permit adjacent Work to damage hardware or hardware finish.
3.6 ATTACHMENTS
A. Hardware Schedule: As indicated on drawings.
END OF SECTION 087100
LOUVERS 089100 - 1
SECTION 089100 - LOUVERS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Fixed louvers.
2. Frames and accessories.
B. Related Requirements:
1. Section 079000 - Joint Protection: Sealant at louver perimeter.
2. Section 099000 - Painting and Coating: Field painting.
1.2 REFERENCE STANDARDS
A. Air Movement and Control Association International, Inc.:
1. AMCA 500-L - Laboratory Methods of Testing Louvers for Rating.
B. ASTM International:
1. ASTM A653/A653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.
2. ASTM A666 - Standard Specification for Annealed or Cold-Worked Austenitic Stainless Steel Sheet, Strip, Plate, and Flat Bar.
3. ASTM E1996 - Standard Specification for Performance of Exterior Windows, Curtain Walls, Doors, and Impact Protective Systems Impacted by Windborne Debris in Hurricanes.
C. South Coast Air Quality Management District:
1. SCAQMD Rule 1168 - Adhesive and Sealant Applications.
1.3 COORDINATION
A. Section 013000 - Administrative Requirements: Requirements for coordination.
1.4 SUBMITTALS
A. Section 013300 - Submittal Procedures: Requirements for submittals.
B. Product Data: Submit manufacturer information describing design characteristics, maximum recommended air velocity, design free area, materials, and finishes.
LOUVERS 089100 - 2
C. Shop Drawings:
1. Indicate louver layout plan and elevations, opening and clearance dimensions, and tolerances.
2. Indicate head, jamb, and sill details in coordination with adjacent materials.
3. Indicate blade configuration, screens, required blankout areas, and frames.
1.5 QUALITY ASSURANCE
A. Certification:
1. Perform Work according to AMCA Certification for Water Penetration, Air Performance, and Wind-Driven Rain according to AMCA 500-L.
2. Attach AMCA seal to louvers.
B. Perform Work according to industry standards.
1.6 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing products specified in this Section with minimum three years' documented experience.
1.7 DELIVERY, STORAGE, AND HANDLING
A. Section 016000 - Product Requirements: Requirements for transporting, handling, storing, and protecting products.
B. Inspection: Accept materials on Site in manufacturer's original packaging and inspect for damage.
C. Store materials according to manufacturer instructions.
D. Protection:
1. Protect materials from moisture and dust by storing in clean, dry location remote from construction operations areas.
2. Provide additional protection according to manufacturer instructions.
1.8 EXISTING CONDITIONS
A. Field Measurements:
1. Verify field measurements prior to fabrication.
2. Indicate field measurements on Shop Drawings.
LOUVERS 089100 - 3
1.9 WARRANTY
A. Section 017000 - Execution and Closeout Requirements: Requirements for warranties.
B. Furnish 10-year manufacturer's warranty for louver finish.
PART 2 - PRODUCTS
2.1 WALL LOUVERS - FIXED BAFFLE STYLE
A. Manufacturers:
1. Greenheck, Inc.
2. Substitutions: As specified in Section 016000 - Product Requirements.
B. Material: Stainless steel.
C. Panel Size:
1. Dimensions: to fit existing masonry openings.
D. Blades: Sightproof; inverted V-style.
2.2 MATERIALS
A. Stainless Steel:
1. Comply with ASTM A666.
2. Type: 316.
3. Temper: Soft.
4. Surface: Smooth.
B. Insect Screens:
1. Description: Galvanized-steel mesh, set in galvanized-steel frame.
2. Size: 18 by 16 mesh.
2.3 FABRICATION
A. Louver Frame:
1. Shape: Channel.
2. Corner Joints: Welded.
3. Minimum Material Thickness: 18 gage.
B. Screens:
1. Furnish screen mesh in shaped frame.
2. Reinforce corner construction.
LOUVERS 089100 - 4
2.4 ACCESSORIES
A. Fasteners and Anchors: Stainless-steel type.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Section 017000 - Execution and Closeout Requirements: Requirements for installation examination.
B. Verify that prepared openings are ready to receive Work of this Section.
C. Verify that opening dimensions are as prepared by louver manufacturer.
3.2 INSTALLATION
A. Install louvers level and plumb.
B. Align louver assembly to ensure moisture is shed from flashings and diverted.
C. Fasteners:
1. Secure louvers in opening framing.
2. Type:
a. Concealed.
b. Removable for maintenance purposes.
D. Screens:
1. Install insect screen and frame on exterior wall side of louvers.
3.3 ADJUSTING
A. Section 017000 - Execution and Closeout Requirements: Requirements for starting and adjusting.
3.4 CLEANING
A. Section 017000 - Execution and Closeout Requirements: Requirements for cleaning.
B. Clean surfaces and components.
END OF SECTION 089100
FLUID-APPLIED FLOORING 096700 - 1
SECTION 096700 - FLUID-APPLIED FLOORING
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes fluid-applied flooring and cove base.
1.2 REFERENCES
A. ASTM International:
1. ASTM C 307 – Standard Test Method for Tensile Strength of Chemical-Resistant
Mortar, Grouts, and Monolithic Surfacings.
2. ASTM C 579 – Standard Test Methods for Compressive Strength of Chemical-Resistant
Mortars, Grouts, Monolithic Surfacings, and Polymer Concretes.
3. ASTM C 580 – Standard Test Method for Flexural Strength and Modulus of Elasticity of
Chemical-Resistant Mortars, Grouts, Monolithic Surfacings, and Polymer Concretes.
4. ASTM D 635 – Standard Test Method for Rate of Burning and/or Extent and Time of
Burning of Plastics in a Horizontal Position.
5. ASTM D 3960 – Standard Practice for Determining Volatile Organic Compound (VOC)
Content of Paints and Related Coatings.
6. ASTM D 4226 – Standard Test Methods for Impact Resistance of Rigid Poly(Vinyl
Chloride) (PVC) Building Products.
7. ASTM D 4541 – Standard Test Method for Pull-Off Strength of Coatings Using Portable
Adhesion Testers.
8. ASTM F 1869 – Standard Test Method for Measuring Moisture Vapor Emission Rate of
Concrete Subfloor Using Anhydrous Calcium Chloride.
9. ASTM F 2170 – Standard Test Method for Determining Relative Humidity in Concrete
Floor Slabs Using in situ Probes.
10. ASTM G 21 – Standard Practice for Determining Resistance of Synthetic Polymeric
Materials to Fungi.
B. International Concrete Repair Institute (ICRI):
1. ICRI 310.2R – Selecting and Specifying Concrete Surface Preparation for Sealers, Coatings, Polymer Overlays, and Concrete Repair.
1.3 PREAPPLICATION MEETINGS
A. Convene preapplication meeting 2 weeks before start of application of flooring system.
B. Require attendance of parties directly affecting work of this Section, including Contractor, Architect, applicator, and owner’s representative.
C. Review materials, moisture testing of concrete, protection of in-place conditions, surface preparation, application, protection, and coordination with other work.
FLUID-APPLIED FLOORING 096700 - 2
1.4 SUBMITTALS
A. Section 013300 - Submittal Procedures: Submittal procedures.
B. Product Data: Submit manufacturer’s product data, including surface preparation and application instructions.
C. Samples:
1. Colorants Added to Materials: Submit manufacturer’s samples of colorants.
2. Flooring Surface: Submit manufacturer’s samples of flooring surface showing texture and sheen.
D. Manufacturer's Certificate: Certify products meet or exceed specified requirements.
E. Applicator’s Project References: Submit applicator’s list of successfully completed resinous flooring system projects, including project name and location, name of architect, and type and quantity of flooring systems applied.
F. Manufacturer's Installation Instructions: Submit special procedures, perimeter conditions requiring special attention, and cleaning procedures.
G. Care and Maintenance Instructions: Submit manufacturer’s care and maintenance instructions, including cleaning instructions.
H. Warranty Documentation: Submit manufacturer’s standard warranty.
1.5 CLOSEOUT SUBMITTALS
A. Section 017000 - Execution and Closeout Requirements: Closeout procedures.
B. Operation and Maintenance Data: Submit maintenance procedures, recommended maintenance materials, procedures for stain removal, repairing surface, and suggested schedule for cleaning.
1.6 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum ten years documented experience.
B. Installer:
1. Applicator regularly engaged, for a minimum of 5 years, in application of resinous flooring systems of similar type to that specified.
2. Employ persons trained for application of resinous flooring systems.
FLUID-APPLIED FLOORING 096700 - 3
1.7 DELIVERY, STORAGE, AND HANDLING
A. Section 016000 - Product Requirements: Product storage and handling requirements.
B. Delivery Requirements: Deliver materials to site in manufacturer’s original, unopened containers and packaging, with labels clearly identifying product name, manufacturer, and batch number.
C. Storage and Handling Requirements:
1. Store and handle materials in accordance with manufacturer’s instructions.
2. Keep materials in manufacturer’s original, unopened containers and packaging until application.
3. Store materials in clean, dry area indoors between 65 and 80 degrees F (18 and 27 degrees C).
4. Store materials out of direct sunlight.
5. Keep materials from freezing.
6. Protect materials during storage, handling, and application to prevent contamination or damage.
1.8 ENVIRONMENTAL REQUIREMENTS
A. Section 016000 - Product Requirements.
B. Apply flooring system under the following ambient conditions:
1. Ambient and Concrete Floor Temperatures: Between 40 and 85 degrees F (4 and 29 degrees C).
2. Material Temperature: Between 50 and 80 degrees F (10 and 27 degrees C).
3. Relative Humidity: Maximum 80 percent.
4. Dew Point: Floor temperature more than 5 degrees over dew point.
C. Do not apply flooring system under ambient conditions outside manufacturer’s limits.
PART 2 - PRODUCTS
2.1 FLUID-APPLIED FLOORING
A. Manufacturers:
1. Tennant Company
2. Sherwin-Williams Company, General Polymers
3. Laticrete, Inc.
4. Dex-o-Tex
5. Substitutions: Section 016000 - Product Requirements.
B. Single Source: Provide materials from single manufacturer.
FLUID-APPLIED FLOORING 096700 - 4
2.2 COMPONENTS
A. Fluid-Applied Flooring: Slurry, cementitious-polyurethane flooring system, with aggregate broadcast, for resurfacing concrete floors.
1. Anti-Slip Surface: Meets ADA recommendations.
B. Base Coat: 1/8 inch thick; color as selected.
C. Traction Aggregate: 40-mesh broadcast sand.
D. Cove
1. Stainless steel “birds beak” cove…