Attachment 2 - Plans - Boulder Showerhouse.pdf

PDF 3 MB Posted

Attached to
Boulder Showerhouse Rehab Federal contract opportunity
Solicitation number
12445524Q0102
Issued by
Department of Agriculture Forest Service

About this file

This document is a set of construction plans and specifications for the rehabilitation of two showerhouse buildings located in the Chequamegon-Nicolet National Forest in Wisconsin. The project scope includes replacing floor finishes, windows, bathroom partitions, air intake louvers, plumbing fixtures, and making other improvements to the two showerhouse buildings. The plans provide detailed drawings and schedules for mechanical, plumbing, and electrical work required. A related federal contract opportunity is also provided, which describes the rehabilitation project and indicates that a site visit will be held on August 21, 2024 for interested contractors. The solicitation is being issued by the U.S. Department of Agriculture Forest Service.

View the file

Other files for this federal contract opportunity

Other files attached to Boulder Showerhouse Rehab, newest first.
File Type Posted
Attachment 4 - Wage Determination - Oconto County.pdf PDF
Attachment 1 - Pricing Breakout - Boulder Showerhouse.xlsx XLSX spreadsheet
12445524Q0102 - Boulder Showerhouse.pdf PDF
Attachment 3 - Specifications - Boulder Showerhouse.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT LOCATION

PROJECT SITE

VICINITY MAP:

SHEET OF

United States Department of Agriculture

Forest Service

INDEX OF SHEETS

SHEET SHEET TITLE DATE

G001 COVER SHEET

A101

SITE MAP, PLAN, AND SECTIONS

A201 ELEVATIONS

A400 INTERIOR ELEVATIONS

M001 MECHANICAL & PLUMBING ABBREVIATIONS & SYMBOLS

M101 EXISTING MECHANICAL PLAN

M102 MECHANICAL PLAN

M501 MECHANICAL DETAILS

M601 MECHANICAL SCHEDULES

E001 ELECTRICAL ABBREVIATIONS

E101 EXISTING ELECTRICAL PLAN

E102 ELECTRICAL PLAN

BOULDER CAMPGROUND

FROM THE CHEQUAMEGON-NICOLET NATIONAL FOREST

HEADQUARTERS OFFICE, TRAVEL EAST ON N RIVER ROAD TO

WI-47 S. TURN RIGHT ONTO WI-47 S FOR 14.4 MILES. CONTINUE

ONTO US-45N/US-8 E FOR 10.7 MILES. TURN RIGHT ONTO COUNTY

ROAD S FOR 2.0 MILES. TURN RIGHT ONTO WI-55 S FOR 38.4

MILES. TURN LEFT ONTO COUNTY HIGHWAY WW FOR .6 MILES.

TURN LEFT ONTO CAMPGROUND DRIVE FOR 1.3 MILES TO REACH

BOULDER CAMPGROUND IN WHITE LAKE, WI, 54491.

WISCONSIN

OCONTO COUNTY

CHEQUAMEGON-NICOLET NATIONAL FOREST

(R09) EASTERN REGION

SHOWER HOUSES REHABILITATION

RECOMMENDED BY:

APPROVED:

FOREST ENGINEER

DISTRICT RANGER

DATE

DATE

DIRECTOR OF ENGINEERING DATE

FOREST SUPERVISOR DATE

RO FACILITIES PROGRAM MANAGER DATE

/19

/20

:2 8 J

AR

NO

LD

C

:\U

SE

RS

\A

GA

RR

IS

ON

\D

OC

UM

EN

TS

\C

HE

QU

AM

EG

ON

NI

CO

LE

T\

BO

UL

DE

RS

HO

W

ER

HO

US

ES

\B

OU

LD

ER

_D

W G\

U2 8-

5_

US

FS

-B

OU

LD

ER

_U

SF

S_

CO

VE

R_

SH

EE

T.

DW

G;

FOREST HEADQUARTERS OFFICES

500 HANSON LAKE ROAD

RHINELANDER, WI 54501

mbeuning Oval mbeuning Oval mbeuning Typewritten Text The project includes two shower houses as circled in the picture above.

Work is identical in each of the two shower houses.

A101

A101

A101

A101

A400

A400

A400

A400

A400

Men's

Restroom

Utility

Women's

Restroom

Open

Breezeway

Janitor

Shower

"B"

Family Restroom and Shower

Shower

"A"

Pipe Alley

1 4

1 4

1 4

1 4

2 5 2 5 2 5

2 5 2 5 2 5 2 5

7 7 7

11 11 11

11 11 11

D-O1

D-O7

D-O2

D-O3

D-O4

D-O5

D-O6

15 15 15

15 15

REMOVE AND REPLACE FLOOR FINISH

AND BASE.

REMOVE AND REPLACE WINDOW.

REMOVE AND REPLACE BATHROOM

PARTITIONS.

4 REPAINT CMU WALL AREA.

REMOVE AND REPLACE AIR INTAKE LOUVER.

SEE MECHANICAL.

KEY NOTES

PAINT WALLS

REMOVE EXISTING FLUSH VALVE. WALL-MOUNT WATER

CLOSET/ URINAL TO REMAIN. SEE PLUMBING.

REPLACE SHOWER W/ ADA-COMPLIANT

FIXTURE.

PROVIDE ADA-COMPLIANT, VANDAL-

RESISTANT FOLDING SHOWER BENCH.

REPLACE LAVATORY AND FAUCET. SEE

PLUMBING.

STRIP AND REFINISH T&G BREEZEWAY

CEILING.

REMOVE AND REPLACE SEALANT AT

CONCRETE EXPANSION JOINTS.

INSTALL NEW LOCKABLE 3-ROLL STAINLESS STEEL

TP HOLDERS PROVIDE LOCKS FOR ALL HOLDERS,

ALL KEYED ALIKE

(http://www.rvparksupplies.com/p/DISPENSERTOILETPAPER3/)

OR EQUAL

REPLACE BENCH BRACKETS AND RETAIN AND

RE-USE EXISTING PLANKS.

REPAINT DOORS AND FRAMES, ADD

SWEEPS AND DOOR HOLDERS.

WINDOW SCHEDULE

LOCATION OPERATION R.O. (W x H) PROTECTION GLAZING HARDWARE NOTES

WOMEN'S GLIDER 4' - 0" x 1' - 4" IMPACT OBSCURE KEYED OPENING STOP

WOMEN'S GLIDER 4' - 0" x 1' - 4" IMPACT OBSCURE KEYED OPENING STOP

WOMEN'S GLIDER 4' - 0" x 1' - 4" IMPACT OBSCURE KEYED OPENING STOP

WOMEN'S GLIDER 4' - 0" x 1' - 4" IMPACT OBSCURE KEYED OPENING STOP

MEN'S GLIDER 4' - 0" x 1' - 4" IMPACT OBSCURE KEYED OPENING STOP

MEN'S GLIDER 4' - 0" x 1' - 4" IMPACT OBSCURE KEYED OPENING STOP

MEN'S GLIDER 4' - 0" x 1' - 4" IMPACT OBSCURE KEYED OPENING STOP

MEN'S GLIDER 4' - 0" x 1' - 4" IMPACT OBSCURE KEYED OPENING STOP

SHOWER "A" GLIDER 2' - 8" x 1' - 4" IMPACT OBSCURE KEYED OPENING STOP

SHOWER "B" GLIDER 2' - 8" x 1' - 4" IMPACT OBSCURE KEYED OPENING STOP

FAMILY R.R. GLIDER 2' - 8" x 1' - 4" IMPACT OBSCURE KEYED OPENING STOP

JANITOR GLIDER 2' - 8" x 1' - 4" IMPACT OBSCURE KEYED OPENING STOP

LOUVER SCHEDULE

LOCATION R.O. (W x H) MATERIAL NOTES HARDWARE NOTES

WOMEN'S 4' - 0" x 1' - 4" STAINLESS VISIBILITY BAFFLE VANDAL-RESISTANT

WOMEN'S 4' - 0" x 1' - 4" STAINLESS VISIBILITY BAFFLE VANDAL-RESISTANT

WOMEN'S 4' - 0" x 1' - 4" STAINLESS VISIBILITY BAFFLE VANDAL-RESISTANT

WOMEN'S 4' - 0" x 1' - 4" STAINLESS VISIBILITY BAFFLE VANDAL-RESISTANT

MEN'S 4' - 0" x 1' - 4" STAINLESS VISIBILITY BAFFLE VANDAL-RESISTANT

MEN'S 4' - 0" x 1' - 4" STAINLESS VISIBILITY BAFFLE VANDAL-RESISTANT

MEN'S 4' - 0" x 1' - 4" STAINLESS VISIBILITY BAFFLE VANDAL-RESISTANT

MEN'S 4' - 0" x 1' - 4" STAINLESS VISIBILITY BAFFLE VANDAL-RESISTANT

SHOWER "A" 4' - 0" x 1' - 4" STAINLESS VISIBILITY BAFFLE VANDAL-RESISTANT

SHOWER "B" 4' - 0" x 1' - 4" STAINLESS VISIBILITY BAFFLE VANDAL-RESISTANT

FAMILY R.R. 2' - 8" x 1' - 4" STAINLESS VISIBILITY BAFFLE VANDAL-RESISTANT

DOOR SCHEDULE

LOCATION MARK SIZE MATERIAL FRAME HARDWARE NOTES

BUILDING #1 D-04 3' - 0" x 7' - 0" x 1 3/4" STEEL STEEL RETAIN EXISTING

BUILDING #3 D-01 3' - 0" x 7' - 0" x 1 3/4" STEEL STEEL RETAIN EXISTING

BUILDING #3 D-02 3' - 0" x 7' - 0" x 1 3/4" STEEL STEEL RETAIN EXISTING

DOOR NOTES:

1. CONFIRM AND MATCH EXISTING DOORS, INCLUDING OPERATION

2. ALL OTHER DOORS TO REMAIN

3. ALL DOORS (NEW AND PROPOSED) SHALL HAVE SWEEPS AND DOOR HOLDERS INSTALLED.

NOTE:

PROJECT DESIGN DOCUMENTS INCLUDES RENOVATIONS TO THREE IDENTICAL BUILDINGS.

SCOPE OF WORK DEFINED OF THESE PAGES SHALL BE PERFORMED AT

THE TWO REMAINING LOCATIONS/ BUILDNGS THAT HAVE NOT BEEN RENOVATED YET.

ACTUAL CONDITIONS MAY VARY.

A101

11 11

A101

5 5 5

2 2 2

BOULDER LAKE

SHOWER

BUILDING

#1

SHOWER

BUILDING

#3

("GROUP")

SHOWER

BUILDING

#2

ENGINEERING

ARCHITECTURE

PLANNING

SURVEYING

ENVIRONMENTAL

PROJECT TITLE:

OWNER:

PROJECT LOCATION:

PROJECT NO:

DRAWN BY:

CHECKED:

APPROVED:

1 2 3 4 5

D

C

B

A

© U.P. Engineers & Architects, Inc.

DESIGNED BY:

DATE:ISSUED FOR:

100 PORTAGE STREET

HOUGHTON, MI 49931

(906) 482-4810

424 SOUTH PINE STREET

ISHPEMING, MI 49849

(906) 485-1011

707 ASHMUN ST.

SAULT STE. MARIE, MI 49783

(906) 635-0511

1701 DUNLAP AVE. SUITE B

MARINETTE, WI 54143

(715) 732-4188

2906 N. STEPHENSON AVE. SUITE 2

IRON MOUNTAIN, MI 49801

(906) 779-0937

P U

U

S D

A

F

S U

S F

S

C

N N

F

M o n d o

B o u l d e r

D w g s B o u l d e r b a s e

D

W G

U

U

S F

S B o u l d e r

B a s e

F

I N

A L r v t

A

M

A101

PLAN & SECTIONS

BOULDER LAKE

RECREATION

AREA

U.S. DEP'T OF

AGRICULTURE

FOREST SERVICE

CHEQ.-NICOLET

NATIONAL

FOREST

U28-17435

JA

KC

TP

JA

Issue DateProject Status

1/4" = 1'-0"

FLOOR PLAN

REVIEW SET 8/9/17

INTERNAL REVIEW 9-26-17

REVIEW 10-10-17

95% (FINAL) SET 10-18-17

FINAL 10-31-17

1/4" = 1'-0"

CROSS SECTION

1/4" = 1'-0"

LONG SECTION

AutoCAD SHX Text

BUILDING KEY

AutoCAD SHX Text

PREVIOUSLY RENOVATED

A101

FAMILY R.R. LOUVER

IN BREEZEWAY

5 5 5 5 5

2 2 2 2

A101

55 5 5 5

2 2 2 2

A101

A101

ENGINEERING

ARCHITECTURE

PLANNING

SURVEYING

ENVIRONMENTAL

PROJECT TITLE:

OWNER:

PROJECT LOCATION:

PROJECT NO:

DRAWN BY:

CHECKED:

APPROVED:

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

© U.P. Engineers & Architects, Inc.

DESIGNED BY:

DATE:ISSUED FOR:

100 PORTAGE STREET

HOUGHTON, MI 49931

(906) 482-4810

424 SOUTH PINE STREET

ISHPEMING, MI 49849

(906) 485-1011

707 ASHMUN ST.

SAULT STE. MARIE, MI 49783

(906) 635-0511

1701 DUNLAP AVE. SUITE B

MARINETTE, WI 54143

(715) 732-4188

2906 N. STEPHENSON AVE. SUITE 2

IRON MOUNTAIN, MI 49801

(906) 779-0937

A

M

A201

EXTERIOR ELEVATIONS

BOULDER LAKE

RECREATION

AREA

U.S. DEP'T OF

AGRICULTURE

FOREST SERVICE

CHEQ.-NICOLET

NATIONAL

FOREST

U28-17435

JA

KC

TP

JA

Issue DateProject Status

1/4" = 1'-0"

RIGHT ELEVATION

1/4" = 1'-0"

LEFT ELEVATION

1/4" = 1'-0"

REAR ELEVATION

1/4" = 1'-0"

FRONT ELEVATION

REVIEW SET 8/9/17

INTERNAL REVIEW 9-26-17

REVIEW 10-10-17

95% (FINAL) SET 10-18-17

FINAL 10-31-17

4 4

Alternate 1: Ceiling-hung toilet partitions will require custom structural harness to accommodate existing vaulted ceiling

2 2 2 2

4 4

5 5 5 5

(2) ROBE HOOKS

Alternate 1: Ceiling-hung toilet partitions will require custom structural harness to accommodate existing vaulted ceiling

2 2 2 2

4 41

5 5 5 5

(2) ROBE HOOKS

REMOVE AND REPLACE FLOOR FINISH

AND BASE.

REMOVE AND REPLACE WINDOW.

REMOVE AND REPLACE BATHROOM

PARTITIONS.

4 REPAINT CMU WALL AREA.

REMOVE AND REPLACE AIR INTAKE LOUVER.

SEE MECHANICAL.

KEY NOTES

REPLACE TOILET/ URINAL.

SEE PLUMBING.

REPLACE SHOWER W/ ADA-COMPLIANT

FIXTURE. SEE PLUMBING.

PROVIDE ADA-COMPLIANT, VANDAL-

RESISTANT FOLDING SHOWER BENCH.

REPLACE LAVATORY AND FAUCETS. SEE

PLUMBING.

REMOVE AND REPLACE SEALANT AT

CONCRETE EXPANSION JOINTS.

REMOVE AND REPLACE BENCH PLANKS AND

SUPPORTING BRACKETS. SEE (22) THIS SHEET.

REPAINT DOORS AND FRAMES, ADD RUBBER

FOOTED DOOR HOLDERS AND REPLACEABLE

SWEEPS TO ALL DOORS.

REMOVE EXISTING AND INSTALL NEW 3-ROLL

STAINLESS STEEL TP HOLDERS WITH LOCKING

BAR WITH PADLOCKS ALL KEYED ALIKE ALL T0ILET

STALLS.

1/2" dia. stainless steel

"StrongBolt" Wedge Anchor by

Simpson or equal.

Quantity and location per bracket manufacturer.

Plastic Wall Mounted

Bench Bracket by

Robinson Steel Co. or equal.

ENGINEERING

ARCHITECTURE

PLANNING

SURVEYING

ENVIRONMENTAL

PROJECT TITLE:

OWNER:

PROJECT LOCATION:

PROJECT NO:

DRAWN BY:

CHECKED:

APPROVED:

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

© U.P. Engineers & Architects, Inc.

DESIGNED BY:

DATE:ISSUED FOR:

100 PORTAGE STREET

HOUGHTON, MI 49931

(906) 482-4810

424 SOUTH PINE STREET

ISHPEMING, MI 49849

(906) 485-1011

707 ASHMUN ST.

SAULT STE. MARIE, MI 49783

(906) 635-0511

1701 DUNLAP AVE. SUITE B

MARINETTE, WI 54143

(715) 732-4188

2906 N. STEPHENSON AVE. SUITE 2

IRON MOUNTAIN, MI 49801

(906) 779-0937

P U

D

A

F

S U

S F

S

C

N N

F

M o n o u l d e r

D w g s B o u l d e r b a s e

D

W G

U

U

S F

S B o u l d e r

B a s e

F

I N

A L r v t

A

M

A400

INTERIOR ELEVATIONS

BOULDER LAKE

RECREATION

AREA

U.S. DEP'T OF

AGRICULTURE

FOREST SERVICE

CHEQ.-NICOLET

NATIONAL

FOREST

U28-17435

JA

KC

TP

JA

Issue DateProject Status

REVIEW SET 8/9/17

INTERNAL REVIEW 9-26-17

REVIEW 10-10-17

95% (FINAL) SET 10-18-17

FINAL 10-31-17

1/4" = 1'-0"

Women's - End Wall

1/4" = 1'-0"

Women's - Entry Wall

1/4" = 1'-0"

Women's - Plumbing Wall

1/4" = 1'-0"

Women's - Vent Wall

1/4" = 1'-0"

"B" - Vent

1/4" = 1'-0"

"B" - Entry

1/4" = 1'-0"

"B" - Plumbing

1/4" = 1'-0"

"B" - End

1/4" = 1'-0"

Fam. - Back

1/4" = 1'-0"

Fam. - Entry

1/4" = 1'-0"

Fam. - Plumbing

1/4" = 1'-0"

Fam. - Divider & Window

1/4" = 1'-0"

Men's - End Wall

1/4" = 1'-0"

Men's - Entry Wall

1/4" = 1'-0"

Men's - Plumbing Wall

1/4" = 1'-0"

Men's - Vent Wall

1/4" = 1'-0"

"A" - Entry

1/4" = 1'-0"

"A" - Vent

1/4" = 1'-0"

"A" - End

1/4" = 1'-0"

"A" - Plumbing

1 1/2" = 1'-0"

Bench

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PLUMBING PIPING

DUCTWORK

ST

G

G

ST

V

V

SAN

HWC

SAN

EA24x14

EA24x14

EA24x14

HW

CW

HWC

OA24x14

OA24x14

OA24x14

RA24x14

SA24x14

SA24x14

S

D

SA24x14

RA24x14

RA24x14

CW

HW

G

ST

CW

V

SAN

HWC

HW

GAS - NEW

GAS - EXISTING

GAS - DEMO

DOMESTIC COLD WATER - EXISTING

DOMESTIC COLD WATER - DEMO

DOMESTIC COLD WATER - NEW

DOMESTIC HOT WATER - EXISTING

DOMESTIC HOT WATER - DEMO

DOMESTIC HOT WATER - NEW

DOMESTIC HOT WATER RECIRC - EXISTING

DOMESTIC HOT WATER RECIRC DEMO

DOMESTIC HOT WATER RECIRC - NEW

SANITARY - EXISTING

SANITARY - DEMO

SANITARY

- NEW

VENT - EXISTING

VENT - DEMO

VENT

- NEW

STORM - EXISTING

STORM - DEMO

STORM - NEW

ABBREVIATIONS

PIPING "T"

HUMIDIFIER

PIPING 90

STRAINER

SYMBOL LEGEND

CAP

NOTES

REDUCED PRESSURE

PRINCIPLE BACK

FLOW PREVENTER

INLINE PUMP

BALANCE VALVE

PRESSURE RELIEF VALVE

3-WAY CONTROL VALVE

2-WAY CONTROL VALVE

GLOBE VALVE

GATE VALVE

CHECK VALVE

CIRCUIT SETTER

BUTTERFLY VALVE

BALL VALVE

EXHAUST AIR DUCT DOWN

EXHAUST AIR DUCT UP

RETURN AIR DUCT DOWN

RETURN AIR DUCT UP

SUPPLY AIR DUCT DOWN

SUPPLY AIR DUCT UP

PRESSURE SENSOR

HUMIDITY SENSOR

TEMPERATURE SENSOR

AIR FLOW

HUMIDISTAT - 48" A.F.F.

THERMOSTAT - 48" A.F.F.

DUCT SMOKE DETECTOR

MOTORIZED DAMPER

FIRE / SMOKE DAMPER

(RATING DETERMINED BY WALL TYPE)

VOLUME CONTROL DAMPER

SQUARE TO ROUND TRANSITION

RETURN OR EXHAUST REGISTER

SUPPLY REGISTER

RELIEF AIR HOOD - ROOF

FRESH AIR INTAKE HOOD - ROOF

EXHAUST FAN - ROOF

RETURN OR EXHAUST AIR GRILLE

LINEAR DIFFUSER

SUPPLY AIR DIFFUSER

PIPE BREAK

PIPE DOWN

PIPE UP

CLEAN OUT

GAS METER

UNION

HOSE BIBB

ELECTRIC BELL

SIAMESE CONNECTION

BARE FIN TUBE ELEMENT

FIN TUBE ELEMENT WITH COVER

EXTERNALLY INSULATED DUCTWORK

INTERNALLY LINED DUCTWORK

SUPPLY AIR DUCT - EXISTING

SUPPLY AIR DUCT - DEMO

SUPPLY AIR DUCT - NEW

RETURN AIR DUCT - EXISTING

RETURN AIR DUCT - DEMO

RETURN AIR DUCT - NEW

OUTSIDE AIR DUCT - EXISTING

OUTSIDE AIR DUCT - DEMO

OUTSIDE AIR DUCT - NEW

EXHAUST AIR DUCT - EXISTING

EXHAUST AIR DUCT - DEMO

EXHAUST AIR DUCT - NEW

GAS VALVE OR PLUG VALVE

METER

CONNECTION TO EXISTING

ACCU AIR COOLED CONDENSING

UNIT

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

AI ANALOG INPUT

AO ANALOG OUTPUT

APD AIR PRESSURE DROP

AS AIR SEPERATOR

B BOILER

BB BASEBOARD

BC BOOSTER COIL

BDD BACKDRAFT DAMPER

BFG BELOW FINISHED GRADE

BFP BACKFLOW PREVENTER

BHP BRAKE HORSE POWER

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

BT BATH TUB

BTU BRITISH THERMAL UNITS

BTUH BRITISH THERMAL UNITS PER HOUR

C CONVECTOR

CA COMPRESSED AIR

CB CATCH BASIN

CC COOLING COIL

CCF 100 CUBIC FEET

CD CEILING DIFFUSER

CF CUBIC FEET

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFP CLEAN OUT FERRULE AND PLUG

CH CHILLER

CI CAST IRON

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CO CLEAN OUT

CO CARBON MONOXIDE

COND CONDENSATE

CO2 CARBON DIOXIDE

CT COOLING TOWER

CU CONDENSING UNIT

CU FT CUBIC FOOT

CUH CABINET UNIT HEATER

CW COLD WATER

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

D DIFFUSER

DB DRY BULB

DEG F DEGREE FAHRENHEIT

DF DRINKING FOUNTAIN

DI DIGITAL INPUT

DIA DIAMETER

DN DOWN

DO DIGITAL OUTPUT

DWV DRAIN, WASTE AND VENT

EA EACH

EAT ENTERING AIR TEMPERATURE

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

EG EXHAUST AIR GRILLE

ELEV ELEVATION

ER EXHAUST AIR REGISTER

EUH ELECTRIC UNIT HEATER

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EWT ENTERING WATER

TEMPERATURE

EX EXISTING

EXH EXHAUST

F FURNACE

FAI FRESH AIR INTAKE

FBO FURNISHED BY OTHERS

FC FAN COIL

FD FLOOR DRAIN

FD FIRE DAMPER

FIN FIN TUBE RADIATION

FLG FLANGE

FP FIRE PROTECTION

FPM FEET PER MINUTE

FT FOOT OR FEET

F&T FLOAT AND THERMOSTATIC TRAP

G GAS (NATURAL)

GAL GALLON

GC GENERAL CONTRACTOR

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GT GREASE TRAP

H HYDROGEN

HB HOSE BIBB

HC HEATING COIL

HCO HORIZONTAL CLEANOUT

HP HORSE POWER

HTR HEATER

HVAC HEATING, VENTILATING & AIR COND

HW HOT WATER

HWC HOT WATER RECIRCULATING

HWR HOT WATER RETURN

HWS HOT WATER SUPPLY

HX HEAT EXCHANGER

IE INVERT ELEVATION

IF INLINE FAN

IN INCH OR INCHES

IP IRON PIPE

INV INVERT

IWH INSTANTANEOUS WATER HEATER

JAN JANITOR

JC JANITOR'S CLOSET

JS JANITOR'S SINK

LAT LEAVING AIR TEMPERATURE

LAV LAVATORY

LBS POUNDS

LHWR LOW TEMPERATURE HOT WATER

RETURN

LHWS LOW TEMPERATURE HOT WATER

SUPPLY

LIQ LIQUID (REFRIGERATION)

LV LOUVER

LP PROPANE GAS (LIQUID)

LWT LEAVING WATER TEMPERATURE

M METER

MAU MAKE-UP AIR HANDLING UNIT

MAX MAXIMUM

MB MOP BASIN

MBH BRITISH THERMAL UNITS (1000)

MBTUH BRITISH THERMAL UNITS (1000)

MC MECHANICAL CONTRACTOR

MCA MINIMUM CIRCUIT AMPACITY

MD MOTORIZED DAMPER

MECH MECHANICAL

MIN MINIMUM

MOCP MAXIMUM OVER CURRENT

PROTECTION

OA OUTDOOR AIR

OAI OUTDOOR AIR INTAKE

OC ON CENTER

OD OVERFLOW DRAIN

ODP OPEN DRIP PROOF

OXY OXYGEN

P PUMP

PC PLUMBING CONTRACTOR

PD PNEUMATIC OPERATED DAMPER

PIV POST INDICATING VALVE

PRV PRESSURE REDUCING VALVE

PT PRESSURE TEMPERATURE PLUG

PTAC PACKAGED TERMINAL AIR COND. UNIT

PVAC PROCESS VACUUM

S SINK

SA SUPPLY AIR

SAD SUPPLY AIR DIFFUSER

SAF SUPPLY AIR FAN

SAN SANITARY SEWER

SD SMOKE DETECTOR

SG SUPPLY AIR GRILLE

SH SHOWER HEAD

SHC STEAM HEATING COIL

SR SUPPLY REGISTER

SS STAINLESS STEEL

ST STORM

STM STEAM

SUCT SUCTION (REFRIGERATION)

TCC TEMPERATURE CONTROL CONTRACTOR

TCD TEMPERATURE CONTROL DAMPER

TCP TEMPERATURE CONTROL PANEL

TD TRANSFER DUCT

TG TRANSFER AIR GRILLE

TT THERMOSTATIC TRAP

TYP TYPICAL

UG UNDERGROUND

UH UNIT HEATER

UV UNIT VENTILATOR

V VENT

VAC VACUUM

VAV VARIABLE AIR VOLUME BOX

VD VOLUME DAMPER

VFD VARIABLE FREQUENCY DRIVE

VS VENT STACK (SANITARY)

VTR VENT THRU ROOF (SANITARY)

VUV VERTICAL UNIT VENTILATOR

W WASTE

WB WET BULB

WC WATER CLOSET

W/O WITHOUT

WH WATER HEATER

WSHP WATER SOURCE HEAT PUMP

NOTE:

NOT ALL ABBREVIATIONS AND/OR SYMBOLS ARE

USED IN THIS SET OF DOCUMENTS.

N2O NITROUS OXIDE

NC NORMALLY CLOSED

NIC NOT INCLUDED OR NOT IN CONTRACT

NIT NITROGEN

NO NORMALLY OPEN

KW KILOWATT

R REGISTER

RA RETURN AIR

RD ROOF DRAIN

RET RETURN

RF RETURN FAN

RG RETURN AIR GRILLE

RPZ REDUCED PRESSURE ZONE BACKFLOW

PREVENTER

RR RETURN REGISTER

RTU ROOF TOP UNIT

MECHANCIAL/PLUMBING AND FIRE PROTECTION GENERAL NOTES

1. THE CONTRACTOR SHALL PROVIDE ALL EQUIPMENT, MATERIALS AND OPERATIONS AND

PERFORM ALL LABOR REQUIRED FOR INSTALLATIONS AS INDICATED THE DRAWINGS, IN THE

SPECIFICATIONS AND AS REQUIRED BY LOCAL, STATE AND FEDERAL CODES, AND AS MAY BE

REASONABLY IMPLIED TO ACCOMPLISH COMPLETE MECHANICAL SYSTEMS.

2. ALL CLOSE ELECTRICAL DISCONNECTS REQUIRED PER NEC CODE SHALL BE FURNISHED AND

INSTALLED BY THE ELECTRICAL CONTRACTOR UNLESS NOTED OTHERWISE.

3. CONTRACTOR SHALL PROVIDE PRODUCTS AS SPECIFIED ON THE DRAWINGS AND

SPECIFICATIONS, HOWEVER, WHERE THE WORDS "EQUAL TO" ARE USED, ADDITIONAL PRODUCTS

MAY BE SUBMITTED AS PROPOSED SUBSTITUTIONS, BUT REQUIRE APPROVAL FROM OWNER.

4. DESIGN DRAWINGS SHOW GENERAL ARRANGEMENT AND EXTENT OF WORK. THE DRAWINGS

ARE DIAGRAMMATIC AND MAY NOT NECESSARILY BE DRAWN TO SCALE FOR PURPOSE OF CLARITY

AND LEGIBILITY. IT IS INTENDED THAT ALL ITEMS BE LOCATED SYMMETRICALLY WITH ARCHITECTURAL

ELEMENTS WHERE FEASIBLE AND BE INSTALLED TO AVOID OBSTRUCTIONS AND PRESERVE

HEADROOM. CONTRACTOR SHALL REVIEW PLANS OF OTHER TRADES WITH HIS OWN WORK TO AVOID

CONFLICTS AND INTERFERENCES. CONTRACTOR MUST MAKE USE OF ALL SOURCES OF INFORMATION

INCLUDING DRAWINGS OF EQUIPMENT FURNISHED BY OTHERS. FAILURE TO REVIEW WORKING

SPACES OR CHECK DIMENSIONS IN QUESTION SHALL NOT WARRANT CONFLICTS. DRAWINGS AND

SPECIFICATIONS ARE INTENDED TO BE COMPLIMENTARY.

5. MOTORS SHALL BE PROVIDED BY MECHANICAL CONTRACTOR AS REQUIRED BY THE

EQUIPMENT FURNISHED BY THE MECHANICAL CONTRACTOR. MOTORS TO BE SUITABLE FOR LOAD, DUTY, VOLTAGE, FREQUENCY, HAZARD, SERVICE AND LOCATION INTENDED. SINGLE PHASE MOTORS

MUST HAVE INTEGRAL THERMAL OVERLOAD PROTECTION IN ADDITION TO THAT PROVIDED IN MOTOR

CONTROLLERS. MOTORS TO CONFORM IN DESIGN AND PERFORMANCE TO THE MOTOR STANDARDS

OF NEMA. MOTORS RATED FOR CONTINUOUS DUTY UNDER FULL LOAD WITH A MAXIMUM

TEMPERATURE RISE OF 105 DEG F FOR OPEN, 125 DEG F FOR DRIP PROOF AND 130 DEG F FOR

EXPLOSION PROOF AND TOTALLY ENCLOSED TYPES. SUPPLY MOTORS WITH BELT DRIVES WITH

ADJUSTABLE BASES, REMOVABLE BELT GUARDS AND VARIABLE PITCH DRIVE PULLEY SELECTED SO

THAT MIDPOINT OF VARIABLE RANGE OF PULLEY WILL DRIVE EQUIPMENT AT RATED SPEED. MOTORS

1 HP AND LARGER SHALL BE THREE PHASE (UNLESS OTHERWISE LISTED).

6. MOTOR CONTROLLERS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR FOR

MOTORS FURNISHED BY THE MECHANICAL CONTRACTOR. MOTOR CONTROLLERS SHALL BE OF SIZES

AND TYPES AS NEEDED TO MEET THE OPERATIONAL CONDITIONS AS REQUIRED BY THE SEQUENCE

OF OPERATION. ELECTRICAL CONTRACTOR TO FURNISH AND INSTALL THE POWER CIRCUIT, LOCAL

DISCONNECT AND CONNECTION TO MOTOR TERMINALS. MECHANICAL CONTRACTOR TO MOUNT

MOTOR CONTROLLERS AND CONTROL COMPONENTS AND WIRE AND MAKE ALL FINAL CONTROL

CONNECTIONS BETWEEN DEVICES.

7. THE DRAWINGS INDICATE KNOWN UTILITY AND DRAINAGE LINES IN ACCORDANCE WITH THE

INFORMATION FURNISHED TO THE ENGINEER. RESPONSIBILITY FOR LOCATING, UNCOVERING,

DISPOSING OR MAINTAINING ALL EXISTING UTILITY LINES TO REST SOLELY WITH THE CONTRACTOR.

VERIFY LOCATIONS AND DEPTHS OF SERVICE CONNECTION POINTS BEFORE PROCEEDING WITH

CONSTRUCTION.

8. CONTRACTOR SHALL CHECK EXISTING PREMISES BEFORE SUBMISSION OF BIDS TO CHECK

ALL CONDITIONS WHICH MAY EFFECT THE PERFORMANCE OF THE WORK INVOLVED. NO

ALLOWANCES OR EXTRA PAYMENT WILL BE MADE DUE TO CONTRACTOR'S FAILURE TO EXAMINE SITE

AND FULLY DISCERN WORKING CONDITIONS.

9. MECHANICAL CONTRACTOR SHALL RECEIVE, PROPERLY HOUSE, HANDLE, HOIST, AND

DELIVER TO PROPER LOCATION EQUIPMENT AND OTHER MATERIALS REQUIRED FOR THIS CONTRACT.

10. THE CONTRACTOR SHALL OBTAIN PERMITS, ARRANGE FOR INSPECTIONS, AND PAY FEES AND

EXPENSES IN CONNECTION THEREWITH, AS A PART OF THE WORK REQUIRING SUCH PERMITS. EVERY

EFFORT IS MADE TO DESCRIBE THE WORK REQUIREMENTS IN CONFORMITY WITH APPLICABLE

CODES.

11. THE CONTRACTOR SHALL REVIEW ANY ALTERNATES OF OTHER TRADES, AND PRICE THEIR BID

TO ACCOUNT FOR ITEMS AFFECTING HIS WORK.

12. PIPING PASSING THROUGH CORRIDORS, TUNNELS, CHASES, ETC. SHALL BE CONSIDERED FOR

PROPER DRAINAGE. CONSULT WITH THE OTHER CONTRACTORS AND AVOID CONFLICT WITH

LOCATION OF PIPING. ORDER OF PRIORITY FOR ALL PIPING AND CONDUITS TO BE INSTALLED SHALL

BE AS FOLLOWS WITH THE HIGHEST PRIORITY LISTED FIRST.

A. PLUMBING DRAIN LINES

B. CONDENSATE LINES

C. DUCTWORK

D. FIRE PROTECTION

E. HOT AND COLD WATER PIPING

F. ELECTRICAL CONDUIT

13. WORK ASSIGNMENTS INFERRED BY THE DRAWINGS AND NOTES INCLUDED IN THESE PROJECT

DOCUMENTS ARE INFORMATIONAL ONLY AND ARE NOT INTENDED TO RELIEVE THE BIDDING

CONTRACTOR OF HIS OBLIGATION TO THE OWNER TO PROVIDE A COMPLETE AND COORDINATED

PROJECT. COMPREHENSIVE SUBCONTRACTOR COORDINATION AND FINAL WORK ASSIGNMENTS TO

SUBCONTRACTORS ARE THE SOLE RESPONSIBILITY OF THE BIDDING CONTRACTOR.

M

M

P

H

T

H

T

M

ENGINEERING

ARCHITECTURE

PLANNING

SURVEYING

ENVIRONMENTAL

PROJECT TITLE:

OWNER:

PROJECT LOCATION:

PROJECT NO:

DRAWN BY:

CHECKED:

APPROVED:

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

© U.P. Engineers & Architects, Inc.

DESIGNED BY:

DATE:ISSUED FOR:

100 PORTAGE STREET

HOUGHTON, MI 49931

(906) 482-4810

424 SOUTH PINE STREET

ISHPEMING, MI 49849

(906) 485-1011

707 ASHMUN ST.

SAULT STE. MARIE, MI 49783

(906) 635-0511

1701 DUNLAP AVE. SUITE B

MARINETTE, WI 54143

(715) 732-4188

2906 N. STEPHENSON AVE. SUITE 2

IRON MOUNTAIN, MI 49801

(906) 779-0937

P U

D

A

F

S U

S F

S

C

N N

F

M o n o u l d e r

D w g s B o u l d e r b a s e

D

W G

U

U

S F

S B o u l d e r

M E

P

F I N

A L r v t

A

M

M001

MECHANICAL AND

PLUMBING

ABBREVIATIONS AND

SYMBOLS

BOULDER LAKE

RECREATION

AREA

U.S. DEP'T OF

AGRICULTURE

FOREST SERVICE

CHEQ/NICOLET

NATIONAL

FOREST

U28-17435

JH

TP

TP

JH

12"x10"12"x8" x x

10"x4" x x

8"x8"

8"x8"

5 5 5 5 5

55555

8 8

6 6 6

8 8 8

EXISTING ELEC. PANEL

EXISTING PRESSURE TANKS

MENS RESTROOM

UTILITY

WOMENS RESTROOM

OPEN

BREEZEWAY

JANITOR

SHOWER "B"

FAMILY RESTROOM

SHOWER "A"

KEY NOTES

REMOVE EXISTING INLINE EXHAUST FAN AND ASSOCIATED WIRING

AND CONTROLS.

REMOVE EXISTING EXHAUST DUCTWORK AND ASSOCIATED

SUPPORTS.

REMOVE EXISTING WALL LOUVER AND ASSOCIATED DUCTWORK

CONNECTION.

REMOVE EXISTING EXHAUST GRILLE AND ASSOCIATED DUCTWORK.

REMOVE EXISTING INTAKE LOUVER.

REMOVE EXISTING FLUSH VALVE. WALL-MOUNT WATER CLOSET TO

REMAIN.

REMOVE EXISTING FLUSH VALVE. WALL-MOUNT URINAL TO REMAIN.

REMOVE EXISTING FAUCET, CONTROL VALVE, WALL-MOUNT

SENSOR, TRAP, STOPS AND SUPPLY LINES. EXISTING WALL-MOUNT

LAVATORY FIXTURE TO REMAIN.

REMOVE EXISTING WALL-MOUNT SHOWER.

EXISTING GAS WATER HEATER TO REMAIN,DEMO RECIRC PUMP

AND ASSOCIATED PIPING.

ENGINEERING

ARCHITECTURE

PLANNING

SURVEYING

ENVIRONMENTAL

PROJECT TITLE:

OWNER:

PROJECT LOCATION:

PROJECT NO:

DRAWN BY:

CHECKED:

APPROVED:

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

© U.P. Engineers & Architects, Inc.

DESIGNED BY:

DATE:ISSUED FOR:

100 PORTAGE STREET

HOUGHTON, MI 49931

(906) 482-4810

424 SOUTH PINE STREET

ISHPEMING, MI 49849

(906) 485-1011

707 ASHMUN ST.

SAULT STE. MARIE, MI 49783

(906) 635-0511

1701 DUNLAP AVE. SUITE B

MARINETTE, WI 54143

(715) 732-4188

2906 N. STEPHENSON AVE. SUITE 2

IRON MOUNTAIN, MI 49801

(906) 779-0937

P U

D

A

F

S U

S F

S

C

N N

F

M o n o u l d e r

D w g s B o u l d e r b a s e

D

W G

U

U

S F

S B o u l d e r

M E

P

F I N

A L r v t

A

M

M101

EXISTING MECHANICAL

PLAN

BOULDER LAKE

RECREATION

AREA

U.S. DEP'T OF

AGRICULTURE

FOREST SERVICE

CHEQ/NICOLET

NATIONAL

FOREST

U28-17435

JH

TP

TP

JH

95% (FINAL) SET 10-18-17

FINAL 10-31-17

1/4" = 1'-0"

EXISTING ATTIC MECHANICAL PLAN

1/4" = 1'-0"

EXISTING MECHANICAL PLAN

NOTE:

PLANS BASED ON SHOWER/TOILET BUILDING #3.

BUILDING #2 ARE IDENTICAL BUT THE INSTALLED SYSTEMS MAY VARY

SLIGHTLY BETWEEN BUILDINGS. IT IS THE CONTRACTOR'S RESPONSIBILTY TO FIELD-VERIFY

EXISTING CONDITIONS IN EACH BUILDING.

PROJECT SHALL INCLUDE RENOVATIONS AT ALL THREE BATHROOM/SHOWER BUILDINGS.

16"x12" x x

14"x8"

12"x8"

EG-1

280 CFM

EG-1

280 CFM

EG-1

280 CFM

EG-1

280 CFM

EG-2

125 CFM

12"x8"

8"x6"

8"x6" x x x

EA

EA

R A

EA 23"x23"

EF-1

EL-1

8x6 EA DN

8x6 EA DN

8x6 EA DN

8x6 EA DN

8x6 EA

VOLUME DAMPER (TYP)

SH-2

SH-1

WC-1 WC-1

EXISTING DF

TO REMAIN

U-1

L-1 L-1 L-1

WC-1 WC-1 WC-1

L-1 L-1 L-1

SH-2

EG-2

125 CFM

EG-2

180 CFM

EG-2

75 CFM

EG-2

125 CFM

IL-1IL-1 IL-1 IL-1 IL-1

IL-1IL-1 IL-1 IL-1 IL-1

IL-2

L-1

WC-2

IL-2

8x6 EA UP

8x6 EA UP

8x6 EA UP

8x6 EA UP

EXISTING ELEC. PANEL

EXISTING PRESSURE TANKS

6 7

6 66

EXISTING LP GAS

SERVICE

MENS RESTROOM

UTILITY

WOMENS RESTROOM

OPEN

BREEZEWAY

JANITOR

SHOWER "B"

FAMILY

RESTROOM

SHOWER "A"

PROPOSED WATER SOFTENER

AND BRINE TANK

WS-1

KEY NOTES

PROVIDE SPRING VIBRATION ISOLATORS MOUNTED SECURELY TO

STRUCTURE.

WATER HEATER REPLACED SINCE PLAN DEVELOPMENT (DO NOT REPLACE

WATER HEATER), KEEP IN PLACE, MODIFY PIPING AND INSTALL

ACCESSORIES AS INDICATED ON SHEET M501.

PROVIDE (2) INTAKE LOUVER TYPE IL-2 IN THIS LOCATION. ONE

HIGH AND ONE LOW ON WALL. SEE ELEVATIONS.

INSTALL DUCT IN EXISTING OPENING. ENLARGE OPENING AS

REQUIRED.

INSTALL LOUVER IN EXISTING OPENING. ENLARGE AS REQUIRED. PROVIDE

TRIM TO MATCH EXISTING.

INSTALL FLUSH VALVE ON EXISTING WATER CLOSET. MODIFY AND

CONNECT TO EXISTING PIPING. REUSE EXISTING OPENINGS IN

WALL. PROVIDE STAINLESS COVER OVER ALL UNUSED OPENINGS.

PATCH TO MATCH EXISTING.

INSTALL FLUSH VALVE ON EXISTING URINAL. MODIFY AND CONNECT

TO EXISTING PIPING. REUSE EXISTING OPENINGS IN WALL. PROVIDE

STAINLESS COVER OVER ALL UNUSED OPENINGS. PATCH TO

MATCH EXISTING.

INSTALL SENSOR-OPERATED FAUCET ON EXISTING LAVATORY.

MODIFY AND CONNECT TO EXISTING PIPING. PROVIDE STAINLESS

COVER OVER ALL UNUSED OPENINGS. PATCH TO MATCH EXISTING.

INSTALL PROPOSED SHOWER IN EXISTING LOCATION. MODIFY AND

CONNECT TO EXISTING PIPING. PROVIDE COMPLETE STAINLESS

SHROUD TO CEILING. PATCH ALL UNUSED OPENINGS TO MATCH EXISTING.

EXTEND PIPING AS BY DETAILS ON SHEET M501, RECIRC PUMP, ETC.

ENGINEERING

ARCHITECTURE

PLANNING

SURVEYING

ENVIRONMENTAL

PROJECT TITLE:

OWNER:

PROJECT LOCATION:

PROJECT NO:

DRAWN BY:

CHECKED:

APPROVED:

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

© U.P. Engineers & Architects, Inc.

DESIGNED BY:

DATE:ISSUED FOR:

100 PORTAGE STREET

HOUGHTON, MI 49931

(906) 482-4810

424 SOUTH PINE STREET

ISHPEMING, MI 49849

(906) 485-1011

707 ASHMUN ST.

SAULT STE. MARIE, MI 49783

(906) 635-0511

1701 DUNLAP AVE. SUITE B

MARINETTE, WI 54143

(715) 732-4188

2906 N. STEPHENSON AVE. SUITE 2

IRON MOUNTAIN, MI 49801

(906) 779-0937

P U

D

A

F

S U

S F

S

C

N N

F

M o n o u l d e r

D w g s B o u l d e r b a s e

D

W G

U

U

S F

S B o u l d e r

M E

P

F I N

A L r v t

A

M

M102

MECHANICAL PLAN

BOULDER LAKE

RECREATION

AREA

U.S. DEP'T OF

AGRICULTURE

FOREST SERVICE

CHEQ/NICOLET

NATIONAL

FOREST

U28-17435

JH

TP

TP

JH

95% (FINAL) SET 10-18-17

FINAL 10-31-17

1/4" = 1'-0"

ATTIC MECHANICAL PLAN

1/4" = 1'-0"

PROPOSED MECHANICAL PLAN

NOTE:

PLANS BASED ON SHOWER/TOILET BUILDING #3.

BUILDING #1 AND BUILDING #2 ARE IDENTICAL BUT THE INSTALLED SYSTEMS MAY VARY

SLIGHTLY BETWEEN BUILDINGS. IT IS THE CONTRACTOR'S RESPONSIBILTY TO FIELD-VERIFY

EXISTING WALL

MOUNT LAVATORY

120v PLUG-IN ADAPTER

FAUCET

(SEE SCHEDULE)

FLEXIBLE

SUPPLY LINES

EXISTING SHROUD

1/4 TURN ANGLE

SHUT-OFF VALVE W/

ESCUTCHEON

120v RECEPTACLE

CONTROL MODULE

TEMPERED WATER

TO FIXTURES

REMOVE EXISTING

WATER HEATER

REMOVE EXISTING HOT

WATER STORAGE TANK

THERMOMETER

(TYP)

COLD WATER TO

FIXTURES

HOT WATER TO

FIXTURES

EXISTING MIXING

VALVE TO REMAIN

TEMPERATURE AND

PRESSURE RELIEF

VALVE

REMOVE EXISTING VENTING

PATCH OPENINGS IN ROOF/CEILING

1-1/4"

1-1/4"

1"

1"

1"

1"

1-1/2"

CW TO BLOW-OFF AND

PRESSURE TANKS

FROM WELL

2"

EXISTING MIXING

VALVE TO REMAIN

EX. 1-1/4"

EX. 1-1/4"

EX. 1"

EX. 2"

1-1/4"

1-1/4"

4" HIGH CONCRETE

PAD PAD OR

EQUIVALENT

1-1/4"

1-1/4"

EX. 1-1/2"

PROPOSED WATER

SOFTENER AND BRINE

TANK

INSULATION

STAND-OFF

HANDLE WITH

LOCKING QUADRANT

INSIDE END BEARING

1/8" CLEARANCE

ALL AROUND

DAMPER BLADE

OUTSIDE END

BEARING

DUCT

INSULATION

INSULATION

STAND-OFF

HANDLE WITH

LOCKING QUADRANT

INSIDE END BEARING

STIFFEN BLADE AS REQUIRED

INSULATION

DAMPER BLADE

HANDLE WITH

LOCKING QUADRANT

DUCT

INSULATION STAND-OFF

SECTION (SQUARE DUCT) SECTION (ROUND DUCT)

SIDE ELEVATION

1.

2.

NOTES:

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR

INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE

SIMILAR FOR MULTI-BLADE DAMPERS AND ROUND DAMPERS.

1/2" ROUND ROD

PIN

DUCT INSULATION

(SEE SCHEDULE)

PROVIDE BACK DRAFT

DAMPER

PITCH DUCT UP

SEAL JOINTS WITH SILICONE

CAULK PERIMETER

VERIFY WALL CONSTRUCTION

O P

E N

I N

G

S

I Z

E

F

I E

L D

V

E R

I F

Y

DRAINABLE FIXED BLADE LOUVER

(SEE SCHEDULE)

IN-LINE EXHAUST FAN

(SEE MECHANICAL PLANS)

FLEXIBLE DUCT

CONNECTION (TYP)

EXHAUST DUCT TO

LOUVER

EXHAUST DUCT FROM

TOILET/SHOWER

ROOMS

CENTER DUCT ON FAN

WHERE POSSIBLE

SPRING VIBRATION

ISOLATORS

THREADED ROD FASTENED

SECURELY TO STRUCTURE

COORDINATE POWER

REQUIREMENTS WITH

ELECTRICAL CONTRACTOR

ENGINEERING

ARCHITECTURE

PLANNING

SURVEYING

ENVIRONMENTAL

PROJECT TITLE:

OWNER:

PROJECT LOCATION:

PROJECT NO:

DRAWN BY:

CHECKED:

APPROVED:

1 2 3 4 5

D

C

B

A

D

C

B

A

© U.P. Engineers & Architects, Inc.

DESIGNED BY:

DATE:ISSUED FOR:

100 PORTAGE STREET

HOUGHTON, MI 49931

(906) 482-4810

424 SOUTH PINE STREET

ISHPEMING, MI 49849

(906) 485-1011

707 ASHMUN ST.

SAULT STE. MARIE, MI 49783

(906) 635-0511

1701 DUNLAP AVE. SUITE B

MARINETTE, WI 54143

(715) 732-4188

2906 N. STEPHENSON AVE. SUITE 2

IRON MOUNTAIN, MI 49801

(906) 779-0937

P U

D

A

F

S U

S F

S

C

N N

F

M o n o u l d e r

D w g s B o u l d e r b a s e

D

W G

U

U

S F

S B o u l d e r

M E

P

F I N

A L r v t

A

M

M501

MECHANICAL DETAILS

BOULDER LAKE

RECREATION

AREA

U.S. DEP'T OF

AGRICULTURE

FOREST SERVICE

CHEQ/NICOLET

NATIONAL

FOREST

U28-17435

JH

TP

TP

JH

95% (FINAL) SET 10-18-17

FINAL 10-31-17

NOT TO SCALE.

A4

LAVATORY DETAIL

NOT TO SCALE.

D4

EXISTING WATER HEATER DETAIL

B4

NOT TO SCALE.

WATER SOFTENER DETAIL

NOT TO SCALE.

C3

DAMPER DETAIL

NOT TO SCALE.

A3

WALL LOUVER DETAIL

NOT TO SCALE.

B3

EXHAUST FAN DETAIL

AutoCAD SHX Text NOTE THAT WATER HEATER WAS REPLACED AFTER PLAN DEVELOPMENT. CONTRACTOR RESPONSIBLE FOR ENSURING ALL ACCESSORIES, CONNECTIONS, AND EXTENSION ARE PROVIDED AS INDICATED BUT WATER HEATER WILL NOT BE REPLACED WITH THIS CONTRACT.

AutoCAD SHX Text NOTE THAT WATER HEATER WAS REPLACED AFTER PLAN DEVELOPMENT. CONTRACTOR RESPONSIBLE FOR VERIFYING EXISTING CONDITIONS.

mbeuning Rectangle mbeuning Typewritten Text Reference Only

Water Heater Already Replaced

PLUMBING FIXTURE SCHEDULE

ID MANUFACTURER MODEL

NUMBER

MATERIAL

1.

2.

3.

4.

5.

PROVIDE WITH 120V PLUG IN WITH 120v ADAPTER, 0.5 gpm VANDAL RESISTANT AERATOR, NEW SUPPLY LINES, P-TRAP AND 1/4-TURN CHROME STOPS.

PROVIDE WITH AXIS SHOWER HEAD WITH BALL JOINT, ADA-COMPLIANT AIR METERING VALVE, 30" SLIDE BAR, VERTICAL SHROUD TO CEILING, VANDAL RESISTANT SCREWS.

PROVIDE WITH AXIS SHOWER HEAD WITH BALL JOINT, AIR METERING VALVE, VERTICAL SHROUD TO CEILING, VANDAL RESISTANT SCREWS.

VERIFY INSTALLATION DIMENSIONS.

REMOVE EXISTING SENSOR. PROVIDE STAINLESS COVER AT ALL UNUSED JUCTION BOXES.

TRIM

MANUF.

NOTESTRIM

MODEL

HOT

WATER

(IN)

COLD

WATER

(IN)

SANITARY

(IN)

DESCRIPTIONADA

L-1 SLOAN SF-2300 CHROME - - - -

ELECTRONIC LAVATORY FAUCET FOR

EXISTING WALL MOUNT LAVATORY

YES 1,5

WC-1 SLOAN ROYAL 111-1.6 - - - 1" -

FLUSH VALVE FOR EXISTING

WALLMOUNT WATER CLOSET

YES CHROME 4,5

TEMP.

WATER

(IN)

1/2"

SH-1 BRADLEY WS-1X-HN STAINLESS STEEL - 1/2" 1/2" -BARRIER-FREE WALL SHOWERYES 2-

SH-2 BRADLEY WS-1WCA STAINLESS STEEL - 1/2" 1/2" -WALL SHOWER 3-

U-1 SLOAN REGAL 180-1 XL - - - 1" -

FLUSH VALVE FOR EXISTING

WALLMOUNT URINAL

YES CHROME 4,5-

FAN SCHEDULE

ID MANUF.

EF-1 GREENHECK

MODEL

NUMBER

SQ-160-VG 1750

AIR

FLOW

(CFM)

VOLTS

PH

NOTES

1,2,3

ELECTRICAL

1.

2.

3.

PROVIDE WITH FACTORY LOW VOLTAGE CONTROL TRANSFORMER AND SPEED CONTROLLER.

COORDINATE ELECTRICAL REQUIREMENTS WITH ELECTRICAL CONTRACTOR.

PROVIDE SPRING ISOLATION MOUNTED SECURELY TO STRUCTURE.

0.50

EXT.

SP.

(FT)

RPM DUCT

CONNECTION

(IN)

23"x23"

DESCRIPTION

EXHAUST FAN

H.P.

3/4

AMPS

13.8

DUCT INSULATION SCHEDULE

SYSTEM TYPE

INSUL.

TYPE

INSULATION OR

LINER

THICKNESS

EXHAUST DUCTS (EXTERNALLY INSULATED) D-1, D-2, D-3 1-1/2"

DUCTWORK INSULATION TYPE SCHEDULE

INSULATION

TYPE

D-1

DESCRIPTION

ASTM C1290, TYPE III, FLEXIBLE GLASS FIBER, COMMERCIAL GRADE WITH FACTORY APPLIED

REINFORCED FOIL JACKET MEETING ASTM C1136, TYPE II, MAX. OPERATING TEMPERATURE: 250 DEG

F, DENSITY: 1.5 LBS/CU FT.

D-2

ASTM C612, TYPE IA OR IB, RIGID GLASS FIBER, WITH FACTORY APPLIED ALL SERVICE FACING

MEETING ASTM C1136, TYPE II, DENSITY: 6.0 LBS/CU FT.

D-3

ASTM C534, TYPE II, FLEXIBLE, CLOSED CELL ELASTOMERIC INSULATION, SHEET, SERVICE

TEMPERATURE RANGE: MINUS 58 TO 180 DEG F.

LOUVER SCHEDULE

ID DESCRIPTION

SIGHTPROOF INTAKE LOUVER

MANUFACTURER

GREENHECK 32"Wx16"H

DIMENSIONS

(IN)

NOTES

1,2,32"

THICKNESS

(IN)

1.

2.

3.

PROVIDE WITH INSECT SCREEN.

CONTRACTOR SHALL FIELD-VERIFY EACH OPENING TO VERIFY EXISTING DIMENSIONS.

COLOR TO BE SELECTED BY ARCHITECT.

PRESS.

DROP

(IN WG)

5.04

FREE

AREA

(SQ.FT.)

VELOCITY

(FT/MIN)

IL-2

MODEL

NUMBER

SED-202

CFM

MATERIAL

ALUMINUM

EXHAUST LOUVER GREENHECK 27"Wx30"H 1,34" 0.04 2.54 493EL-1 ESD-403 1250ALUMINUM

SIGHTPROOF INTAKE LOUVER GREENHECK 48"Wx16"H 1,2,32" - 5.04 496IL-1 SED-202 -ALUMINUM

DIFFUSER, GRILLE, REGISTER SCHEDULE

ID DESCRIPTION MANUFACTURER

MOUNTING

FRAME

NOTES

1.

2.

SURFACE MOUNT BORDER WITH EXTERNAL FASTENERS.

LOCATE IN EXISTING OPENING, ADJUST OPENING SIZE AS REQUIRED.

MATERIAL

MODEL

NUMBER

MODULE

SIZE

(IN)

STAINLESS EXHAUST GRILLE TITUS SURFACE 1,212"x8" STAINLESSEG-1 350R-SS 14"x10"

STAINLESS EXHAUST GRILLE TITUS SURFACE 1,28"x6" STAINLESSEG-2 350R-SS 10"x8"

DUCT

SIZE

(IN)

PLUMBING PIPE INSULATION SCHEDULE

SYSTEM TYPE

DOMESTIC HOT WATER SUPPLY P-1

INSUL.

TYPE

ALL SIZES

PIPE

SIZES

1"

INSULATION

THICKNESS

DOMESTIC COLD WATER SUPPLY

P-1

P-2

1-1/4" AND SMALLER

1-1/2" AND LARGER

1/2"

1"

PIPING INSULATION TYPE SCHEDULE

INSULATION

TYPE

P-1

DESCRIPTION

ASTM C547, MOLDED GLASS FIBER PIPE INSULATION, OPERATING TEMPERATURE RANGE: 0 TO 850

DEG F, VAPOR BARRIER JACKET: ASTM C1136, TYPE I, FACTORY APPLIED REINFORCED FOIL DRAFT

WITH SELF SEALING ADHESIVE JOINTS.

P-2

ASTM C534, TYPE I, FLEXILE, CLOSED CELL ELASTOMERIC INSULATION, TUBULAR, OPERATING

TEMPERATURE RANGE: MINUS 70 TO 180 DEG F.

WATER SOFTENER SCHEDULE

ID MANUFACTURER

WS-1 WATER RIGHT

MODEL

NUMBER

IMPRESSION IM-1054 48,800 @ 21.0

INPUT

CAPACITY

(GRAINS/LBS)

VOLTS

PH

HP

AMPS

NOTES

1,2,3

ELECTRICAL

1.

2.

3.

PROVIDE PIPING CONNECTION PER WATER HEATER DETAIL.

PROVIDE 4" CONCRETE HOUSEKEEPING PAD. SEE DETAIL B4/M501.

PROVIDE WATER SOFTENING SYSTEM FOR BUILDING #2 AND BUILDING #3. PROVIDE INSTALLATION EQUAL TO CURRENTLY INSTALLED SYSTEM AT BUILDING #1.

1.5

MEDIA

(CU.FT.)

MAX WATER

HARDNESS

(GPG)

18x33

BRINE

TANK

SIZE

(IN)

1"

WATER

CONN.

(IN)

1.0

MAX IRON

(PPM)

14.3 @ 15.0

PEAK FLOW

RATE

(GPM @ PSI)

10x62

MEDIA

TANK

SIZE

(IN)

ENGINEERING

ARCHITECTURE

PLANNING

SURVEYING

ENVIRONMENTAL

PROJECT TITLE:

OWNER:

PROJECT LOCATION:

PROJECT NO:

DRAWN BY:

CHECKED:

APPROVED:

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

© U.P. Engineers & Architects, Inc.

DESIGNED BY:

DATE:ISSUED FOR:

100 PORTAGE STREET

HOUGHTON, MI 49931

(906) 482-4810

424 SOUTH PINE STREET

ISHPEMING, MI 49849

(906) 485-1011

707 ASHMUN ST.

SAULT STE. MARIE, MI 49783

(906) 635-0511

1701 DUNLAP AVE. SUITE B

MARINETTE, WI 54143

(715) 732-4188

2906 N. STEPHENSON AVE. SUITE 2

IRON MOUNTAIN, MI 49801

(906) 779-0937

P U

D

A

F

S U

S F

S

C

N N

F

M o n o u l d e r

D w g s B o u l d e r b a s e

D

W G

U

U

S F

S B o u l d e r

M E

P

F I N

A L r v t

A

M

M601

MECHANICAL

SCHEDULES

BOULDER LAKE

RECREATION

AREA

U.S. DEP'T OF

AGRICULTURE

FOREST SERVICE

CHEQ/NICOLET

NATIONAL

FOREST

U28-17435

JH

TP

TP

JH

FAAP

FACP

ELECTRICAL ABBREVIATIONS, SYMBOLS AND NOTES

ABBREVIATIONS AND SYMBOLS LEGEND NOTES & DETAILS

ELR

CARBON MONOXIDE DETECTOR

1. IT SHALL BE THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO NOTIFY OTHER

CONTRACTORS TO ARRANGE CLEARANCES AND ACCESS OPENINGS FOR ALL LARGE ELECTRICAL

EQUIPMENT.

2. IT SHALL BE UNDERSTOOD THAT THE ACT OF SUBMITTING A BID BY THE CONTRACTOR

CARRIES WITH IT THE AGREEMENT TO ALL ITEMS AND CONDITIONS REFERRED OR INDICATED OR

IMPLIED ON THE DRAWINGS AND THE SPECIFICATIONS AND NO CONSIDERATION WILL BE

GRANTED FOR ANY ALLEGED MISUNDERSTANDING OF MATERIALS TO BE FURNISHED FOR WORK

TO BE DONE.

3. THE ELECTRICAL INSTALLATION SHALL COMPLY WITH RULES AND REGULATIONS OF THE

LATEST EDITION OF THE OCCUPATIONAL SAFETY AND HEALTH ACT, NATIONAL ELECTRICAL CODE, STATE ELECTRICAL CODE, LOCAL MUNICIPAL CODE AND ANY OTHER BOARD HAVING

JURISDICTION OVER THE ELECTRICAL INSTALLATION.

4. THE ELECTRICAL CONTRACTOR SHALL NOT ASSUME THAT ANY DRAWING OR

SPECIFICATION FORMING A PART OF THE CONTRACT DOCUMENTS AUTHORIZES THE VIOLATION

OF ANY CODE, REGULATION OR STANDARD. WHERE CONFLICTS ARISE, IT SHALL BE DEEMED THAT

THE CONTRACTOR HAS ESTIMATED THE COST OF ALL WORK TO BE COMPLETED IN ACCORD WITH

THE PREVAILING CODE.

5. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS FOR ELECTRICAL WORK AND

SHALL PAY ALL REQUIRED FEES AND SALES OR USE TAX AND FINES AS APPLICABLE TO THIS

BRANCH OF WORK.

6. UPON COMPLETION OF THE WORK, THE CONTRACTOR SHALL DELIVER TO THE OWNER

WITHOUT COST ALL REQUIRED CERTIFICATES OF INSPECTION AND APPROVAL.

7. THE INTENT AND OBJECT OF THESE SPECIFICATIONS AND DRAWINGS IS TO INCLUDE A

COMPLETE WIRING SYSTEM FROM SERVICE PANEL TO EACH AND EVERY OUTLET INDICATED OR

SPECIFIED, INCLUDING CONNECTING ALL ELECTRICAL DEVICES AND/OR EQUIPMENT FURNISHED

BY THE OWNER OR OTHER CONTRACTORS.

8. THE DRAWINGS, WHICH CONSTITUTE A PART OF THE CONTRACT, ARE DIAGRAMMATIC AND

INDICATE THE GENERAL ARRANGEMENT OF CIRCUITS AND OUTLETS, LOCATION OF SWITCHES,

PANELBOARD AND OTHER WORK, BUT EXTREME ACCURACY IS NOT GUARANTEED AND FIELD

VERIFICATION OF ALL LOCATIONS AND DIMENSIONS IS DIRECTED.

9. GROUND ALL EQUIPMENT INCLUDING CONDUIT, RECEPTACLES, LIGHTING, MOTORS, PIPING

AS PER ARTICLE 250 OF THE NATIONAL ELECTRICAL CODE, AND AS SHOWN ON THESE DRAWINGS.

10. PROVIDE ONLY MATERIALS THAT ARE NEW OF THE TYPE AND QUALITY SPECIFIED, WHERE

UNDERWRITERS LABORATORIES HAVE ESTABLISHED STANDARDS FOR SUCH MATERIALS,

PROVIDE ONLY MATERIALS BEARING THE U.L. LABEL.

11. ARCHITECTURAL DRAWINGS SHOWING DIMENSIONS FOR ELECTRICAL DEVICES TAKE

PRECEDENCE OVER THE ELECTRICAL DRAWINGS.

12. SYSTEMS SHALL BE FREE FROM SHORTS AND GROUNDS. TEST FOR MECHANICAL AND

ELECTRICAL DEFECTS. VERIFY CORRECT CONNECTION OF HOT, NEUTRAL AND GROUND

CONDUCTORS. ALL CONDUCTORS SHALL BE COLOR CODED AND LABELED WITH ZONE

IDENTIFICATION FOR THE CASE OF LIGHTING.

13. WHEN MATERIAL AND/OR WORKMANSHIP IS FOUND NOT TO COMPLY WITH THE SPECIFIED

REQUIREMENTS, WITHIN THREE DAYS AFTER RECEIPT OF NOTICE OF SUCH NON-COMPLIANCE,

REMOVE THE NON-COMPLYING ITEMS FROM THE JOB AND REPLACE WITH NEW ITEMS MEETING

THE REQUIREMENTS. COSTS FOR REPAIR OF NON-COMPLIANCE WORK SHALL BE BY THE

CONTRACTOR WITH NO ADDITIONAL COST TO THE OWNER.

14. UPON COMPLETION OF THE WORK, THOROUGHLY CLEAN ALL DEVICES AND EQUIPMENT.

15. ALL TELECOM, TV CABLE AND DATA CABLE SHALL BE DEDICATED RUNS FROM THE OUTLET

LOCATIONS TO THE BACKBOARD LOCATION.

16. WORK ASSIGNMENTS INFERRED BY THE DRAWINGS AND NOTES INCLUDED IN THESE

PROJECT DOCUMENTS ARE INFORMATIONAL ONLY AND ARE NOT INTENDED TO RELIEVE THE

BIDDING CONTRACTOR OF HIS OBLIGATION TO THE OWNER TO PROVIDE A COMPLETE AND

COORDINATED PROJECT. COMPREHENSIVE SUBCONTRACTOR COORDINATION AND FINAL WORK

ASSIGNMENTS TO SUBCONTRACTORS ARE THE SOLE RESPONSIBILITY OF THE BIDDING

CONTRACTOR.

LUMINARE - SURFACE MOUNT FLUORESCENT OR INCANDESCENT

LUMINARE - RECESSED FLUORESCENT OR INCANDESCENT

LUMINARE - STANDARD FLUORESCENT STRIP LIGHT

LIGHT FIXTURE - RECESSED FLUORESCENT OR LED

HEAT DETECTOR

DUAL LEVEL SWITCHING - SWITCH OUTER (2) LAMPS SEPARATE

FROM CENTER LAMP

FIRE ALARM HORN/STROBE (CEILING MOUNTED)

FIRE ALARM BOOSTER PANEL

FIRE ALARM SPEAKER

END OF LINE RESISTOR

FIRE ALARM HORN/STROBE (WALL MOUNTED)

MAGNETIC DOOR HOLD OPEN

GONG

DUCT SMOKE DETECTOR

TAMPER SWITCH

FLOW SWITCH

FIRE ALARM HORN/STROBE (WALL MOUNTED)

MANUAL PULL STATION

SMOKE DETECTOR

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

FIRE SAFETY AND ALARM SYMBOLS

GENERAL NOTES:

PHOTO CELL

OCCUPANCY SENSOR (WALL MOUNTED)

PANEL - RECESSED

PANEL - SURFACE MOUNT

AUTOMATIC TRANSFER SWITCH (ATS)

DISCONNECT

NORMALLY OPEN SWITCH

NORMALLY CLOSED SWITCH

CIRCUIT BREAKER WITH SIZE AS NOTED

NORMALLY OPEN CONTACT

NORMALLY CLOSED CONTACT

FUSED SWITCH

ELECTRIC METER

GROUND

IN-LINE FUSE

TRANSFORMER

STARTER DISCONNECT

THERMOSTAT

CONNECTION TO MOTOR

FUSED DISCONNECT

DISCONNECT

TELEPHONE/DATA OUTLET. PROVIDE 1"CONDUIT WITH PULL

STRING PER LOCATION. DATA CABLES AND TERMINATIONS BY

OTHERS.

SWITCH - PILOT

SWITCH - DIMMER

TYPICAL DEVICE MOUNTING HEIGHT

NOTE:

VERIFY HEIGHTS SHOWN COMPLY WITH LOCAL BUILDING CODE.

47"

1'-6"

6"

MAX.

SYMBOL

EXIT

BOTTOM OF

FINISHED CEILING

SYMBOL

FIRE ALARM

SYMBOL

LIGHTING SWITCH

SYMBOL

120V CONVENIENCE

RECEPTACLE

SYMBOL

TELEPHONE AND

COMPUTER

TOP OF FINISHED FLOOR

47"

6'-8"

SYMBOL

FIRE ALARM

MANUAL PULL

STATION

OCCUPANCY SENSOR (CEILING MOUNTED)

ABBREVIATIONS

LIGHTING SYMBOLS

SWITCH - PUSH BUTTON

SWITCH - TIME CLOCK

SWITCH - SINGLE POLE, TIMED

SWITCH - SINGLE POLE, KEYED

SWITCH - FOUR WAY

SWITCH - THREE WAY

SWITCH - SINGLE POLE

A AMPERES

AV PANELBOARD AV

AV AUDIO/VIDEO

A/V AUDIO/VIDEO

C PANELBOARD KPP-C

C.B. CIRCUIT BREAKER

GFCI GROUND FAULT CIRCUIT INTERUPTING

GFI GROUND FAULT CIRCUIT INTERUPTING

KVA KILO-VOLT AMPS (ELECTRIC POWER)

QT QUAD TUBE (FLUORESCENT LAMP)

TT TWIN TUBE (FLUORESCENT LAMP)

TYP TYPICAL

V VOLT

4W FOUR WIRE

3ø THREE PHASE

JUNCTION BOX

JUNCTION BOX

TELEVISION CABLE OUTLET

CLOCK - WALL MOUNTED

AMPLIFIER

INTERCOM

SPEAKER - CEILING MOUNTED

SPEAKER - WALL MOUNTED

WIRELESS ACCESS POINT (WAP)

TELEPHONE/DATA OUTLET - FLOOR MOUNTED

POLE RECEPTACLE

ISOLATED GROUND RECEPTACLE

TOP SWITCHED RECEPTACLE

GROUND FAULT INTERUPTING RECEPTACLE. PROVIDE WEATHER-

PROOF WHILE IN USE COVER WHERE LOCATED OUTDOORS.

QUAD RECEPTACLE (GFI PROTECTED WHERE REQUIRED)

FLOOR RECEPTACLE (GFI PROTECTED WHERE REQUIRED)

DUPLEX RECEPTACLE

MISCELLANEOUS SYMBOLSSWITCHES AND RECEPTACLE SYMBOLS

TELEPHONE, DATA AND COMMUNICATION SYMBOLS

CO

F

S

F

F

FS

S

D

S

TS

M

H

J

J

D

S

SS

S

P

S

S

T

S

S

S

K

S

IG

G

PC

L

N E

M

T

M

C

A

IC

S

S

T

V

A

LIGHT FIXTURE - EMERGENCY (WALL MOUNT)

LIGHT FIXTURE - EXIT/EMERGENCY (DIRECTIONAL ARROWS

WHERE INDICATED ON PLANS) (WALL OR CEILING MOUNT)

OS

S

COUNTERTOP RECEPTACLE (GFCI WHERE REQUIRED)

CTR

LIGHT FIXTURE - SURFACE FLUORESCENT OR LED

C

B

TC

F

M

SECURITY CAMERA (OUTDOOR/INDOOR PER PLAN)

DOOR ALARM KEYPAD. PROVIDE 1"CONDUIT WITH PULL STRING PER

LOCATION. DATA CABLES AND TERMINATIONS BY OTHERS.

DL

LIGHT FIXTURE SCHEDULE

ID MANUFACTURER CATALOG

NUMBER

1.

2.

3.

NOTES:

PROVIDE SHOP DRAWINGS FOR ALL FIXTURES, LAMPS AND BALLASTS.

ALL FIXTURES 120V EXCEPT AS NOTED

SUBSTITUTIONS MUST BE APPROVED IN WRITING BY ENGINEER PRIOR TO BIDDING.

DESCRIPTION

A

FAIL-SAFE FPS-4-LD4-2STD-40-OPL-UNV-EDC1-ABP-NSF

9"x48" SURFACE-MOUNT VANDAL

RESISTANT FIXTURE

BALLASTS(S)

REMARKS

PHILIPS 14.5A19/LED/827/ND 120V

SELF-BALLASTED LED

"A" STYLE LAMP

B

ENGINEERING

ARCHITECTURE

PLANNING

SURVEYING

ENVIRONMENTAL

PROJECT TITLE:

OWNER:

PROJECT LOCATION:

PROJECT NO:

DRAWN BY:

CHECKED:

APPROVED:

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

© U.P. Engineers & Architects, Inc.

DESIGNED BY:

DATE:ISSUED FOR:

100 PORTAGE STREET

HOUGHTON, MI 49931

(906) 482-4810

424 SOUTH PINE STREET

ISHPEMING, MI 49849

(906) 485-1011

707 ASHMUN ST.

SAULT STE. MARIE, MI 49783

(906) 635-0511

1701 DUNLAP AVE. SUITE B

MARINETTE, WI 54143

(715) 732-4188

2906 N. STEPHENSON AVE. SUITE 2

IRON MOUNTAIN, MI 49801

(906) 779-0937

P U

D

A

F

S U

S F

S

C

N N

F

M o n o u l d e r

D w g s B o u l d e r b a s e

D

W G

U

U

S F

S B o u l d e r

M E

P

F I N

A L r v t

A

M

E001

ELECTRICAL

ABBREVIATIONS

BOULDER LAKE

RECREATION

AREA

U.S. DEP'T OF

AGRICULTURE

FOREST SERVICE

CHEQ/NICOLET

NATIONAL

FOREST

U28-17435

JH

PM

TP

PM

G GG

G

G

G GG

G

PC

4 4 4

2 2 2

4 4 4

EXISTING ELEC. PANEL

EXISTING ELEC. METEREXISTING LIFT STATION

ALRM PANEL

PANEL-A

MENS

RESTROOM

UTILITY

MENS RESTROOM

OPEN

BREEZEWAY

JANITOR

SHOWER "B"

FAMILY RESTROOM

SHOWER "A"

EXISTING LIGHT FIXTURE TO REMAIN

(SWITCHED FROM BELOW)

A-20

REMOVE POWER AND CONTROLS SERVING EXISTING INLINE

EXHAUST FAN. SALVAGE WIRE FOR REUSE.

KEY NOTES

REMOVE POWER AND CONTROL WIRING SERVING EXISTING WATER

CLOSET FLUSH VALVE. SALVAGE WIRE FOR REUSE.

REMOVE POWER AND CONTROL WIRING SERVING EXISTING URINAL

FLUSH VALVE. SALVAGE WIRE FOR REUSE.

REMOVE POWER AND CONTROL WIRING SERVING EXISTING

FAUCET.

REMOVE POWER AND CONTROL WIRING SERVING GAS WATER

HEATER AND RECIRC PUMP.

REMOVE EXISTING LIGHT FIXTURE AND BACK BOX. SALVAGE

WIRE/CIRCUIT FOR REUSE. PROVIDE J-BOX IN ATTIC. PATCH

CEILING OR WALL TO MATCH EXISTING.

REMOVE EXISTING MOTION SENSOR. CONNECT WIRING TO KEEP

LIGHTS IN SERVICE. PROVIDE SEALED J-BOX COVER, COVER TO

MATCH CEILING.

REMOVE EXISTING PHOTOCELL AND WIRING. REWIRE EXISTING

CIRCUIT FOR 24/7 OPERATION.

ENGINEERING

ARCHITECTURE

PLANNING

SURVEYING

ENVIRONMENTAL

PROJECT TITLE:

OWNER:

PROJECT LOCATION:

PROJECT NO:

DRAWN BY:

CHECKED:

APPROVED:

1 2 3 4 5

D

C

B

A

D

C

B

A

© U.P. Engineers & Architects, Inc.

DESIGNED BY:

DATE:ISSUED FOR:

100 PORTAGE STREET

HOUGHTON, MI 49931

(906) 482-4810

424 SOUTH PINE STREET

ISHPEMING, MI 49849

(906) 485-1011

707 ASHMUN ST.

SAULT STE. MARIE, MI 49783

(906) 635-0511

1701 DUNLAP AVE. SUITE B

MARINETTE, WI 54143

(715) 732-4188

2906 N. STEPHENSON AVE. SUITE 2

IRON MOUNTAIN, MI 49801

(906) 779-0937

P U

D

A

F

S U

S F

S

C

N N

F

M o n o u l d e r

D w g s B o u l d e r b a s e

D

W G

U

U

S F

S B o u l d e r

M E

P

F I N

A L r v t

A

M

E101

EXISTING ELECTRICAL

PLAN

BOULDER LAKE

RECREATION

AREA

U.S. DEP'T OF

AGRICULTURE

FOREST SERVICE

CHEQ/NICOLET

NATIONAL

FOREST

U28-17435

JH

PM

TP

PM

95% (FINAL) SET 10-18-17

FINAL 10-31-17

1/4" = 1'-0"

EXISTING ELECTRICAL PLAN

1/4" = 1'-0"

EXISTING ATTIC ELECTRICAL PLAN

NOTE:

PLANS BASED ON SHOWER/TOILET BUILDING #3.

BUILDING #1 AND BUILDING #2 ARE IDENTICAL BUT THE INSTALLED SYSTEMS MAY VARY

SLIGHTLY BETWEEN BUILDINGS. IT IS THE CONTRACTOR'S RESPONSIBILTY TO FIELD-VERIFY

G GG

G

G

G GG

G

WH-1

EXISTING ELEC. PANEL

PANEL-A

A-13

A-14

A-16

A

A

A

A

A

A

MENS RESTROOM

UTILITY

WOMENS RESTROOM

OPEN

BREEZEWAY

JANITOR

SHOWER "B"

FAMILY RESTROOM

SHOWER "A"

B B

B B

(TYP 3)

A

A

(TYP 3)

PROPOSED WATER

SOFTENER

WS-1

A-18

EF-1

A-20

BBB B

1 PROVIDE POWER AND CONTROLS FOR PROPOSED EXHAUST FAN.

KEY NOTES

PROVIDE POWER TO PROPOSED WATER HEATER. EXTEND

EXISTING WIRING AND CONDUIT AS REQUIRED.

PROVIDE 120V RECEPTACLE FOR FAUCET CONTROLS LOCATED

BELOW EXISTING LAVATORY.

CONNECT PROPOSED LIGHT FIXTURE TO EXISTING LIGHTING

CIRCUIT IN THIS AREA. EXTEND WIRE AND CONDUIT AS REQUIRED.

PROVIDE WIRING FOR EXHAUST FAN SPEED CONTROL (REMOTE

MOUNTED) SEE MECHANICAL..

ENGINEERING

ARCHITECTURE

PLANNING

SURVEYING

ENVIRONMENTAL

PROJECT TITLE:

OWNER:

PROJECT LOCATION:

PROJECT NO:

DRAWN BY:

CHECKED:

APPROVED:

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

© U.P. Engineers & Architects, Inc.

DESIGNED BY:

DATE:ISSUED FOR:

100 PORTAGE STREET

HOUGHTON, MI 49931

(906) 482-4810

424 SOUTH PINE STREET

ISHPEMING, MI 49849

(906) 485-1011

707 ASHMUN ST.

SAULT STE. MARIE, MI 49783

(906) 635-0511

1701 DUNLAP AVE. SUITE B

MARINETTE, WI 54143

(715) 732-4188

2906 N. STEPHENSON AVE. SUITE 2

IRON MOUNTAIN, MI 49801

(906) 779-0937

P U

D

A

F

S U

S F

S

C

N N

F

M o n o u l d e r

D w g s B o u l d e r b a s e

D

W G

U

U

S F

S B o u l d e r

M E

P

F I N

A L r v t

A

M

E102

ELECTRICAL PLAN

BOULDER LAKE

RECREATION

AREA

U.S. DEP'T OF

AGRICULTURE

FOREST SERVICE

CHEQ/NICOLET

NATIONAL

FOREST

U28-17435

JH

PM

TP

PM

95% (FINAL) SET 10-18-17

FINAL 10-31-17

1/4" = 1'-0"

PROPOSED ELECTRICAL PLAN

1/4" = 1'-0"

ATTIC ELECTRICAL PLAN

Legend:

Total Amps: 14 A 11 A

Total Load: 1732 VA 1372 VA

A-29 WOMENS AND FAMILY SHOWER OUTLETS 20 A 1 0 VA 0 VA 1 20 A ATTIC LIGHTS A-30

A-27 MENS LIGHTS 20 A 1 0 VA 0 VA 1 20 A MECHANICAL RM LIGHTS A-28

A-25 MENS OUTLETS 20 A 1 0 VA 0 VA 1 20 A MENS RM OUTLETS A-26

A-23 WOMENS LIGHTS 20 A 1 0 VA 0 VA 1 20 A LOW VOLTAGE TRANSFORMER A-24

A-21 WOMENS HAND DRYER 20 A 1 0 VA 0 VA 1 20 A CIRCULATING PUMP A-22

A-19 MENS HAND DRYER 20 A 1 0 VA 1012 VA 1 20 A EXHAUST FAN A-20

A-17 FAMILY HAND DRYER 20 A 1 0 VA 180 VA 1 20 A WATER SOFTENER A-18

A-15 WATER COOLER 20 A 1 180 VA 180 VA 1 20 A MENS LAVATORY RECEPTACLES A-16

A-13 WATER HEATER 20 A 1 1012 VA 540 VA 1 20 A WOMENS LAVATORY RECEPTACLES A-14

A-11 -- -- -- 0 VA 0 VA -- -- -- A-12

A-9 Spare 30 A 2 0 VA 0 VA 2 30 A Spare A-10

A-7 -- -- -- 0 VA 0 VA -- -- -- A-8

A-5 Spare 30 A 2 0 VA 0 VA 2 30 A WELL A-6

A-3 -- -- -- 0 VA 0 VA -- -- -- A-4

A-1 Spare 30 A 2 0 VA 0 VA 2 30 A PUMP/lLIFT STATION CONTROL/ALARM A-2

CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT

Notes:

Enclosure: MCB Rating: 200 A

Mounting: Surface Wires: 3 Mains Rating: 200 A

Supply From: Phases: 1 Mains Type:

Location: Volts: 120/240 Single A.I.C. Rating:

Branch Panel:PANEL-A

NOTE:

PLANS BASED ON SHOWER/TOILET BUILDING #3.

BUILDING #1 AND BUILDING #2 ARE IDENTICAL BUT THE INSTALLED SYSTEMS MAY VARY

SLIGHTLY BETWEEN BUILDINGS. IT IS THE CONTRACTOR'S RESPONSIBILTY TO FIELD-VERIFY

EXISTING CONDITIONS IN EACH BUILDING.

PROJECT SHALL INCLUDE RENOVATIONS AT ALL THREE BATHROOM/SHOWER BUILDINGS.

PANEL SCHEDULE BASED ON BUILDING #2

NEW WIRE NEW WIRE

NEW WIRE

NOTE:

CIRCUIT NUMBERS MAY VARY AT BUILDING #1 AND #3. PROVIDE NEW BREAKERS FOR RECEPTACLES AND WATER HEATER AT BUILDING #3.

A101
Sheets and Views
Layout1
A201
Sheets and Views
Layout1
A400
Sheets and Views
Layout1
E001
Sheets and Views
Layout1
E101
Sheets and Views
Layout1
E102
Sheets and Views
Layout1
M001
Sheets and Views
Layout1
M101
Sheets and Views
Layout1
M102
Sheets and Views
Layout1
M501
Sheets and Views
Layout1
M601
Sheets and Views
Layout1
TITLE
Sheets and Views
36x24 EXPANDED

File details come from the government source that posted it. Updated .