This is a mechanical services drawing set for a proposed residential development project at 2 Bells Apartment located in Alagomeji, Yaba, Lagos, Nigeria. The drawings were prepared by TopKlan Mechanical, Electrical and Electronics Engineering as of May 2025 with project architect Baron Architectures.

The drawing package comprises mechanical, plumbing, HVAC, drainage, and fire-fighting system layouts across ground and first floor plans. Key systems include water supply utilizing PPR pipes connecting to existing water supplies with central water heaters (Rheem Model PROE50 T2 RH95 EC1, 50-gallon capacity) and water filtration units (General Electric Model GXWH40L). Drainage systems incorporate a proposed biodigester sewage treatment plant (2260mm diameter) discharging to public storm drains with separate rainwater discharge points. HVAC systems feature wall-mounted units (3.6-6.4 KW capacity) with outdoor condensing units, refrigerant piping, and condensate drainage. Ventilation includes inline extractor fans (EF-1 and EF-2, S&P Mixvent model with 270m³/hr flowrate) utilizing existing ventilation shafts. Fire-fighting provisions include strategically placed fire extinguishers on ground and first floors. All existing refrigerant, condensate, and water supply pipes are specified for replacement. The drawings indicate connections to existing infrastructure where applicable and provide detailed routing of all mechanical systems with standard engineering abbreviations and legends throughout.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROPOSED RESIDENTIAL DEVELOPMENT

FOR

2 BELLS APARTMENT

MECHANICAL SERVICES DRAWING

19-05-2025

MECHANICAL, ELECTRICAL AND ELECTRONICS ENGINEERING

292, Murtala Muhammed Way, Alagomeji, Yaba, Lagos Tel: 09030867276, 08023599742 Email: topklanprojects@topklan.com

SYM DESCRIPTION

HVAC PLUMBING LEGEND

SYM DESCRIPTION

SOIL WASTE PIPE

WASTE PIPE

COLD WATER PIPE

ABBR DESCRIPTION

WASTE PIPE

COLD WATER PIPE

HOT WATER PIPE

FROM ABOVE

FROM BELOW

ABBREVIATIONS

WP

CWS

HWS

TO ABOVE

TO BELOW

FA

FB

TA

TB

HIGH LEVEL

LOW LEVEL

HL

LL

CEILING CONCEALED UNITCCU

WALL UNITWU

CONDENSING UNITCU

REFRIGERANT SUPPLY

HOT WATER PIPE

RAIN WATER PIPE

CONDENSATE PIPE

CWH CENTRAL WATER HEATER

WALL MOUNTED UNIT

OUTDOOR UNIT

INLINE EXTRACTOR FAN

SOIL PIPESP

VENT PIPE

EF EXTRACTOR FAN

D R A W I N G T I T L E

DRAWN BY CHECKED BY APPROVED BY

SCALE

DATE

FILE REF

DRAWING NUMBER REVISION

Mechanical, Electrical & Electronics Engineers Rock Haven Suite Office, 4, Hughes Avenue off Murtala Muhammed Way Alagomeji, Yaba, Lagos.

Tel: 09030867276, 08023599742 Email: topklanprojects@topklan.com

ENGINEERS:

PROPOSED RESIDENTIAL DEVELOPMENT

FOR

2-BELLS APARTMENT

PROJECTS:

PROJECT ARCHITECT..

G E N E R A L N O T E S

1. SEE DWG. No. TES502/E001 FOR

LEGEND & GENERAL NOTES.

2. CONSULTANT ENGINEERS TO BE

NOTIFIED OF ANY DISCREPANCIES

BETWEEN THIS DRAWING AND THOSE

BY OTHERS

1 : 175

MECH LEGEND

TES 502

MAY, 2025

O.F F.O

M001

S.K

1 : 175

MECH LEGEND

No. Description Date

CONNECT TO EXISTING

WATER SUPPPLY

CONNECT TO EXISTING

WATER SUPPPLY

PLUMBING LEGEND

SYM DESCRIPTION

SOIL WASTE PIPE

WASTE PIPE

COLD WATER PIPE

HOT WATER PIPE

RAIN WATER PIPE

SOIL WASTE PIPESWP

WP

CWS

HWS

FA

FB

TA

TB

HL

CWH

WASTE PIPE

COLD WATER PIPE

HOT WATER PIPE

FROM ABOVE

FROM BELOW

TO ABOVE

TO BELOW

HIGH LEVEL

LOW LEVEL

CENTRAL WATER HEATER

LL

RWS RAIN WATER PIPE

VENT PIPE

D R A W I N G T I T L E

DRAWN BY CHECKED BY APPROVED BY

SCALE

DATE

FILE REF

DRAWING NUMBER REVISION

Mechanical, Electrical & Electronics Engineers 292, Murtala Muhammed Way, Alagomeji, Yaba, Lagos.

Tel: 09030867276, 08023599742 Email: topklanprojects@topklan.com

ENGINEERS:

PROPOSED RESIDENTIAL DEVELOPMENT

FOR

2-BELLS APARTMENT

PROJECTS:

PROJECT ARCHITECT..

G E N E R A L N O T E S

1. SEE DWG. No. TES502/E001 FOR

LEGEND & GENERAL NOTES.

2. CONSULTANT ENGINEERS TO BE

NOTIFIED OF ANY DISCREPANCIES

BETWEEN THIS DRAWING AND THOSE

BY OTHERS

As indicated

WATER SUPPLY SYSTEM LAYOUT

TES 502

MAY, 2025

O.F F.O

M100

S.K

1 : 100

M100-SITE PLAN

43 m²

LIVING ROOM

G04

26 m²

KITCHEN/DINING

G11/G13

3 m²

LAUN.

G14

3 m²

V.TOI.

G10

19 m²

COURTYARD

G06

20 m²

GARAGE

G01

20 m²

GARAGE

G15 Not Enclosed

COURTYARD

G20

43 m²

LIVING ROOM

G18

3 m²

V.TOI.

3 m²

LAUN.

26 m²

KITCHEN/DINING

G24/G26

W A

TE

R

H

EA

TE

R

W A

T

ER

1 m²

STORE

W A

SH

E

D

R

YE

R

W A

SH

ER

RY

ER

DW

DW

2 m²

STORE

2 m²

STORE

2 m²

STORE

G09

2 m²

STORE

G21

1 m²

CLOSET

1 m²

CLOSET

25HWS INSIDE

CEILING VOID

32CWS INSIDE

CEILING VOID

25HWS TA

32CWS TA

32CWS INSIDE

CEILING VOID

WATER FILTERATION UNIT

MAKE: GENERAL ELECTRIC

MODEL: GXWH40L

FILTER: FXHSC

25HWS INSIDE

CEILING VOID

32CWS INSIDE

CEILING VOID

25HWS TA

32CWS TA

32CWS INSIDE

CEILING VOID

CENTER WATER HEATER

CAPACITY: 50GAL

MAKE: RHEEM

MODEL: PROE50 T2 RH95 EC1

WASHING MACHINE

WASHING MACHINE

25mm STOP COCK

25mm STOP COCK

25mm STOP COCK

25mm STOP COCK

25mm STOPCOCK

WATER FILTERATION UNIT

MAKE: GENERAL ELECTRIC

MODEL: GXWH40L

FILTER: FXHSC

CENTER WATER HEATER

CAPACITY: 50GAL

MAKE: RHEEM

MODEL: PROE50 T2 RH95 EC1

PLUMBING LEGEND

SYM DESCRIPTION

SOIL WASTE PIPE

WASTE PIPE

COLD WATER PIPE

HOT WATER PIPE

RAIN WATER PIPE

SOIL WASTE PIPESWP

WP

CWS

HWS

FA

FB

TA

TB

HL

CWH

WASTE PIPE

COLD WATER PIPE

HOT WATER PIPE

FROM ABOVE

FROM BELOW

TO ABOVE

TO BELOW

HIGH LEVEL

LOW LEVEL

CENTRAL WATER HEATER

LL

RWS RAIN WATER PIPE

VENT PIPE

D R A W I N G T I T L E

DRAWN BY CHECKED BY APPROVED BY

SCALE

DATE

FILE REF

DRAWING NUMBER REVISION

Mechanical, Electrical & Electronics Engineers 292, Murtala Muhammed Way, Alagomeji, Yaba, Lagos.

Tel: 09030867276, 08023599742 Email: topklanprojects@topklan.com

ENGINEERS:

PROPOSED RESIDENTIAL DEVELOPMENT

FOR

2-BELLS APARTMENT

PROJECTS:

PROJECT ARCHITECT..

G E N E R A L N O T E S

1. SEE DWG. No. TES502/E001 FOR

LEGEND & GENERAL NOTES.

2. CONSULTANT ENGINEERS TO BE

NOTIFIED OF ANY DISCREPANCIES

BETWEEN THIS DRAWING AND THOSE

BY OTHERS

As indicated

WATER SUPPLY SYSTEM LAYOUT

TES 502

MAY, 2025

O.F F.O

M101

S.K

1 : 75

M101-GROUND FLOOR PLAN

No. Description Date

NOTE: ALL EXISTING WATER SUPPLY PIPES

TO BE REPLACED WITH PPR PIPES

C

LO

SE

T

C

LO

SE

T

C

LO

SE

T

C

LO

SE

T

CLOSET

17 m²

BEDROOM

17 m²

BEDROOM

5 m²

TERRACE

5 m²

TERRACE

5 m²

TERRACE

15 m²

BEDROOM

6 m²

CLOSET

4 m²

BATH

4 m²

BATH

16 m²

BEDROOM

5 m²

TERRACE

6 m²

CLOSET

4 m²

BATH

4 m²

BATH

4 m²

BATH

17 m²

BEDROOM

5 m²

TERRACE

17 m²

BEDROOM

17 m²

BEDROOM

5 m²

TERRACE

1 m²

STORE

8 m²

LOBBY

7 m²

LOBBY

5 m²

STAIRS

5 m²

STAIRS

25HWS FB

32CHS FB

25HWS INSIDE

CEILING VOID

25HWS INSIDE

CEILING VOID

25HWS FB

32 CWS FB

32CWS INSIDE

CEILING VOID

32CWS INSIDE

CEILING VOID

25mm STOPCOCK

25mm STOPCOCK

25mm STOPCOCK

25mm STOPCOCK

25mm STOPCOCK

PLUMBING LEGEND

SYM DESCRIPTION

SOIL WASTE PIPE

WASTE PIPE

COLD WATER PIPE

HOT WATER PIPE

RAIN WATER PIPE

SOIL WASTE PIPESWP

WP

CWS

HWS

FA

FB

TA

TB

HL

CWH

WASTE PIPE

COLD WATER PIPE

HOT WATER PIPE

FROM ABOVE

FROM BELOW

TO ABOVE

TO BELOW

HIGH LEVEL

LOW LEVEL

CENTRAL WATER HEATER

LL

RWS RAIN WATER PIPE

VENT PIPE

D R A W I N G T I T L E

DRAWN BY CHECKED BY APPROVED BY

SCALE

DATE

FILE REF

DRAWING NUMBER REVISION

Mechanical, Electrical & Electronics Engineers 292, Murtala Muhammed Way, Alagomeji, Yaba, Lagos.

Tel: 09030867276, 08023599742 Email: topklanprojects@topklan.com

ENGINEERS:

PROPOSED RESIDENTIAL DEVELOPMENT

FOR

2-BELLS APARTMENT

PROJECTS:

PROJECT ARCHITECT..

G E N E R A L N O T E S

1. SEE DWG. No. TES502/E001 FOR

LEGEND & GENERAL NOTES.

2. CONSULTANT ENGINEERS TO BE

NOTIFIED OF ANY DISCREPANCIES

BETWEEN THIS DRAWING AND THOSE

BY OTHERS

As indicated

WATER SUPPLY SYSTEM LAYOUT

TES 502

MAY, 2025

O.F F.O

M102

S.K

1 : 75

M102-FIRST FLOOR PLAN

G04

26 m²

KITCHEN/DINING

G11/G13

3 m²

LAUN.

G14

3 m²

V.TOI.

G10

19 m²

COURTYARD

G06

20 m²

GARAGE

G01

20 m²

GARAGE

G15 Not Enclosed

COURTYARD

G20

43 m²

LIVING ROOM

G18

3 m²

V.TOI.

3 m²

LAUN.

26 m²

KITCHEN/DINING

G24/G26

W A

TE

R

W A

T

ER

1 m²

STORE

W A

SH

R

YE

R

W A

RY

ER

DW

DW

2 m²

STORE

2 m²

STORE

2 m²

STORE

G09

2 m²

STORE

G21

1 m²

CLOSET

1 m²

CLOSET

PROPOSED BIODIGESTER

SEWAGE TREATMENT

PLANT

ø 2260

TO DISCHARGE INTO

PUBLIC STORM DRAIN

WITH NON RETURN

VALVE

150 mmø

CONCRETE ENCLOSURE

TO STRUCTURAL

ENGINEER DETAIL

RAINWATER DISCHARGE

TO SITE

RAINWATER DISCHARGE

TO SITE

RAINWATER DISCHARGE

TO SITE

RAINWATER DISCHARGE

TO SITE

RAINWATER DISCHARGE

TO SITE

EXISTING SEWER PIPE

UNDERGROUND

PLUMBING LEGEND

SYM DESCRIPTION

SOIL WASTE PIPE

WASTE PIPE

COLD WATER PIPE

HOT WATER PIPE

RAIN WATER PIPE

SOIL WASTE PIPESWP

WP

CWS

HWS

FA

FB

TA

TB

HL

CWH

WASTE PIPE

COLD WATER PIPE

HOT WATER PIPE

FROM ABOVE

FROM BELOW

TO ABOVE

TO BELOW

HIGH LEVEL

LOW LEVEL

CENTRAL WATER HEATER

LL

RWS RAIN WATER PIPE

VENT PIPE

D R A W I N G T I T L E

DRAWN BY CHECKED BY APPROVED BY

SCALE

DATE

FILE REF

DRAWING NUMBER REVISION

Mechanical, Electrical & Electronics Engineers 292, Murtala Muhammed Way, Alagomeji, Yaba, Lagos.

Tel: 09030867276, 08023599742 Email: topklanprojects@topklan.com

ENGINEERS:

PROPOSED RESIDENTIAL DEVELOPMENT

FOR

2-BELLS APARTMENT

PROJECTS:

PROJECT ARCHITECT..

G E N E R A L N O T E S

1. SEE DWG. No. TES502/E001 FOR

LEGEND & GENERAL NOTES.

2. CONSULTANT ENGINEERS TO BE

NOTIFIED OF ANY DISCREPANCIES

BETWEEN THIS DRAWING AND THOSE

BY OTHERS

As indicated

DRAINAGE SYSTEM LAYOUT

TES 502

MAY, 2025

O.F F.O

M200

S.K

1 : 100

M200-SITE PLAN

No. Description Date

NOTE: EXISTING PIPE ROUTES ON SITE TO BE

MAINTAINED.

ONLY RAINWATER PIPES FROM TERRACE

WILL BE NEWLY INTRODUCED

G04

26 m²

KITCHEN/DINING

G11/G13

3 m²

LAUN.

G14

3 m²

V.TOI.

G10

19 m²

COURTYARD

G06

20 m²

GARAGE

G01

20 m²

GARAGE

G15 Not Enclosed

COURTYARD

G20

43 m²

LIVING ROOM

G18

3 m²

V.TOI.

3 m²

LAUN.

26 m²

KITCHEN/DINING

G24/G26

W A

TE

R

W A

T

ER

1 m²

STORE

W A

SH

R

YE

R

W A

RY

ER

DW

DW

2 m²

STORE

2 m²

STORE

2 m²

STORE

G09

2 m²

STORE

G21

1 m²

CLOSET

1 m²

CLOSET

50RWP FA/HL

50RWP @HL/TB

50RWP FA/HL

50RWP @HL/TB

CLIPPED TO WALL

50WP TO CONNECT

TO EXISTING PIPE

ROUTE

50WP TO CONNECT

TO EXISTING PIPE

ROUTE

DISH WASHER

WASTE PIPE

50RWP FA/HL

50RWP @HL/TB

EXISTING PIPE ROUTE

TO BE RETAINED

50RWP FA/HL

50RWP @HL/TB

50RWP FA/HL50RWP FA/HL

50RWP @HL/TB

50WP TO CONNECT

TO EXISTING PIPE

ROUTE

50WP TO CONNECT

TO EXISTING PIPE

ROUTE

DISH WASHER

WASTE PIPE

100SP TO CONNECT

TO EXISTING PIPE

ROUTE

PLUMBING LEGEND

SYM DESCRIPTION

SOIL WASTE PIPE

WASTE PIPE

COLD WATER PIPE

HOT WATER PIPE

RAIN WATER PIPE

SOIL WASTE PIPESWP

WP

CWS

HWS

FA

FB

TA

TB

HL

CWH

WASTE PIPE

COLD WATER PIPE

HOT WATER PIPE

FROM ABOVE

FROM BELOW

TO ABOVE

TO BELOW

HIGH LEVEL

LOW LEVEL

CENTRAL WATER HEATER

LL

RWS RAIN WATER PIPE

VENT PIPE

D R A W I N G T I T L E

DRAWN BY CHECKED BY APPROVED BY

SCALE

DATE

FILE REF

DRAWING NUMBER REVISION

Mechanical, Electrical & Electronics Engineers 292, Murtala Muhammed Way, Alagomeji, Yaba, Lagos.

Tel: 09030867276, 08023599742 Email: topklanprojects@topklan.com

ENGINEERS:

PROPOSED RESIDENTIAL DEVELOPMENT

FOR

2-BELLS APARTMENT

PROJECTS:

PROJECT ARCHITECT..

G E N E R A L N O T E S

1. SEE DWG. No. TES502/E001 FOR

LEGEND & GENERAL NOTES.

2. CONSULTANT ENGINEERS TO BE

NOTIFIED OF ANY DISCREPANCIES

BETWEEN THIS DRAWING AND THOSE

BY OTHERS

As indicated

DRAINAGE SYSTEM LAYOUT

TES 502

MAY, 2025

O.F F.O

M201

S.K

1 : 75

M201-GROUND FLOOR PLAN

SE

T

C

LO

SE

T

C

LO

SE

T

C

LO

SE

T

CLOSET

17 m²

BEDROOM

17 m²

BEDROOM

5 m²

TERRACE

5 m²

TERRACE

5 m²

TERRACE

15 m²

BEDROOM

6 m²

CLOSET

4 m²

BATH

4 m²

BATH

16 m²

BEDROOM

5 m²

TERRACE

6 m²

CLOSET

4 m²

BATH

4 m²

BATH

4 m²

BATH

17 m²

BEDROOM

5 m²

TERRACE

17 m²

BEDROOM

17 m²

BEDROOM

5 m²

TERRACE

1 m²

STORE

8 m²

LOBBY

7 m²

LOBBY

5 m²

STAIRS

5 m²

STAIRS

50FD

50FD

50FD

50FD

50FD

50FD

100 VENT COWL

100 VENT COWL

SOIL AND WASTE PIPE

TO CONNECT TO

EXISTING ROUTE

SOIL AND WASTE PIPE

TO CONNECT TO

EXISTING ROUTE

SOIL AND WASTE PIPE

TO CONNECT TO

EXISTING ROUTE

PLUMBING LEGEND

SYM DESCRIPTION

SOIL WASTE PIPE

WASTE PIPE

COLD WATER PIPE

HOT WATER PIPE

RAIN WATER PIPE

SOIL WASTE PIPESWP

WP

CWS

HWS

FA

FB

TA

TB

HL

CWH

WASTE PIPE

COLD WATER PIPE

HOT WATER PIPE

FROM ABOVE

FROM BELOW

TO ABOVE

TO BELOW

HIGH LEVEL

LOW LEVEL

CENTRAL WATER HEATER

LL

RWS RAIN WATER PIPE

VENT PIPE

D R A W I N G T I T L E

DRAWN BY CHECKED BY APPROVED BY

SCALE

DATE

FILE REF

DRAWING NUMBER REVISION

Mechanical, Electrical & Electronics Engineers 292, Murtala Muhammed Way, Alagomeji, Yaba, Lagos.

Tel: 09030867276, 08023599742 Email: topklanprojects@topklan.com

ENGINEERS:

PROPOSED RESIDENTIAL DEVELOPMENT

FOR

2-BELLS APARTMENT

PROJECTS:

PROJECT ARCHITECT..

G E N E R A L N O T E S

1. SEE DWG. No. TES502/E001 FOR

LEGEND & GENERAL NOTES.

2. CONSULTANT ENGINEERS TO BE

NOTIFIED OF ANY DISCREPANCIES

BETWEEN THIS DRAWING AND THOSE

BY OTHERS

As indicated

DRAINAGE SYSTEM LAYOUT

TES 502

MAY, 2025

O.F F.O

M202

S.K

1 : 75

M202-FIRST FLOOR PLAN

G04

26 m²

KITCHEN/DINING

G11/G13

3 m²

LAUN.

G14

3 m²

V.TOI.

G10

19 m²

COURTYARD

G06

20 m²

GARAGE

G01

20 m²

GARAGE

G15 Not Enclosed

COURTYARD

G20

43 m²

LIVING ROOM

G18

3 m²

V.TOI.

3 m²

LAUN.

26 m²

KITCHEN/DINING

G24/G26

W A

TE

R

W A

T

ER

1 m²

STORE

W A

SH

R

YE

R

W A

RY

ER

DW

DW

2 m²

STORE

2 m²

STORE

2 m²

STORE

G09

2 m²

STORE

G21

1 m²

CLOSET

1 m²

CLOSET

WU

5.2KW

A12

2NO REF. PIPE INSIDE

CEILING VOID WU

5.2KW

A8

WU

5.2KW

A9

CU

A8

CU

A2

CU

A3

CU

A9

WU

6.4KW

A10

CU

A10

CU

A14

CU

A7

CU

A13

CU

A12

2NO REF. PIPE INSIDE

CEILING VOID

CU

A6

WU

6.4KW

A13

WU

5.2KW

A14

2NO REF. PIPE FA

2NO REF. PIPE FA

25COND. PIPE FA/TB

25COND. PIPE

FA/TB

25COND. PIPE

FA/TB

25COND. PIPE FA/TB

25COND. PIPE FA/TB

2NO REF. PIPE

FA

25COND. PIPE FA/TB

2NO REF.

PIPE INSIDE

WALL2NO REF.

PIPE INSIDE

WALL

SYM DESCRIPTION

HVAC

REFRIGERANT SUPPLY

CONDENSATE PIPE

WALL MOUNTED UNIT

OUTDOOR UNIT

INLINE EXTRACTOR FAN

FROM ABOVE

FROM BELOW

TO ABOVE

TO BELOW

FA

FB

TA

TB

HIGH LEVELHL

WALL UNITWU

CONDENSING UNITCU

D R A W I N G T I T L E

DRAWN BY CHECKED BY APPROVED BY

SCALE

DATE

FILE REF

DRAWING NUMBER REVISION

Mechanical, Electrical & Electronics Engineers 292, Murtala Muhammed Way, Alagomeji, Yaba, Lagos.

Tel: 09030867276, 08023599742 Email: topklanprojects@topklan.com

ENGINEERS:

PROPOSED RESIDENTIAL DEVELOPMENT

FOR

2-BELLS APARTMENT

PROJECTS:

PROJECT ARCHITECT..

G E N E R A L N O T E S

1. SEE DWG. No. TES502/E001 FOR

LEGEND & GENERAL NOTES.

2. CONSULTANT ENGINEERS TO BE

NOTIFIED OF ANY DISCREPANCIES

BETWEEN THIS DRAWING AND THOSE

BY OTHERS

As indicated

HVAC SYSTEM LAYOUT

TES 502

MAY, 2025

O.F F.O

M301

S.K

1 : 100

M301-GROUND FLOOR PLAN

No. Description Date

NOTE: ALL EXISTING REFRIGERANT AND CONDENSATE

PIPES WILL BE REPLACED

G04

26 m²

KITCHEN/DINING

G11/G13

3 m²

LAUN.

G14

3 m²

V.TOI.

G10

19 m²

COURTYARD

G06

20 m²

GARAGE

G01

20 m²

GARAGE

G15 Not Enclosed

COURTYARD

G20

43 m²

LIVING ROOM

G18

3 m²

V.TOI.

3 m²

LAUN.

26 m²

KITCHEN/DINING

G24/G26

W A

TE

R

W A

T

ER

1 m²

STORE

W A

SH

R

YE

R

W A

RY

ER

DW

DW

2 m²

STORE

2 m²

STORE

2 m²

STORE

G09

2 m²

STORE

G21

1 m²

CLOSET

1 m²

CLOSET

EF-1

EF-1

EF-1

EXTRACT DISK

VALVE

FLEX

DUCT

EXTRACT DISK

VALVE

FLEX

DUCT

CRCULAR

PVC DUCT100ø

EF-1EXISTING VENTILATION

SHAFT TO ROOF SLAB

EXISITNG VENTILATION

SHAFT TO ROOF SLAB

SYM DESCRIPTION

HVAC

REFRIGERANT SUPPLY

CONDENSATE PIPE

WALL MOUNTED UNIT

OUTDOOR UNIT

INLINE EXTRACTOR FAN

FROM ABOVE

FROM BELOW

TO ABOVE

TO BELOW

FA

FB

TA

TB

HIGH LEVELHL

WALL UNITWU

CONDENSING UNITCU

D R A W I N G T I T L E

DRAWN BY CHECKED BY APPROVED BY

SCALE

DATE

FILE REF

DRAWING NUMBER REVISION

Mechanical, Electrical & Electronics Engineers 292, Murtala Muhammed Way, Alagomeji, Yaba, Lagos.

Tel: 09030867276, 08023599742 Email: topklanprojects@topklan.com

ENGINEERS:

PROPOSED RESIDENTIAL DEVELOPMENT

FOR

2-BELLS APARTMENT

PROJECTS:

PROJECT ARCHITECT..

G E N E R A L N O T E S

1. SEE DWG. No. TES502/E001 FOR

LEGEND & GENERAL NOTES.

2. CONSULTANT ENGINEERS TO BE

NOTIFIED OF ANY DISCREPANCIES

BETWEEN THIS DRAWING AND THOSE

BY OTHERS

As indicated

HVAC SYSTEM LAYOUT

TES 502

MAY, 2025

O.F F.O

M301A

S.K

1 : 100

M301A-GROUND FLOOR PLAN

SE

T

C

LO

SE

T

C

LO

SE

T

C

LO

SE

T

CLOSET

17 m²

BEDROOM

17 m²

BEDROOM

5 m²

TERRACE

5 m²

TERRACE

5 m²

TERRACE

15 m²

BEDROOM

6 m²

CLOSET

4 m²

BATH

4 m²

BATH

16 m²

BEDROOM

5 m²

TERRACE

6 m²

CLOSET

4 m²

BATH

4 m²

BATH

4 m²

BATH

17 m²

BEDROOM

5 m²

TERRACE

17 m²

BEDROOM

17 m²

BEDROOM

5 m²

TERRACE

1 m²

STORE

8 m²

LOBBY

7 m²

LOBBY

5 m²

STAIRS

5 m²

STAIRS

WU

5.2KW

A7

WU

3.6KW

A1

CU

A5

WU

3.6KW

A5

CU

A1

WU

5.2KW

A6

WU

5.2KW

A3

WU

5.2KW

A2

WU

5.2KW

A4

CU

A4

OUTDOOR UNIT

AT HIGH LEVEL

25COND PIPE

TB

25COND PIPE

TB

25COND PIPE

TB

20COND PIPE

TB

2NO REF. PIPE

TB

25COND PIPE

INSIDE WALL

2NO REF. PIPE

INSIDE WALL

2NO REF. PIPE

TB

2NO REF. PIPE

INSIDE WALL

25COND PIPE

TB

2NO REF. PIPE

TB

20COND PIPE

INSIDE WALL

2NO REF. PIPE

INSIDE WALL

2NO REF. PIPE

TB

2NO REF. PIPE

INSIDE WALL

2NO REF. PIPE

INSIDE WALL

2NO REF. PIPE

INSIDE WALL

2NO REF.

PIPE

INSIDE

WALL

SYM DESCRIPTION

HVAC

REFRIGERANT SUPPLY

CONDENSATE PIPE

WALL MOUNTED UNIT

OUTDOOR UNIT

INLINE EXTRACTOR FAN

FROM ABOVE

FROM BELOW

TO ABOVE

TO BELOW

FA

FB

TA

TB

HIGH LEVELHL

WALL UNITWU

CONDENSING UNITCU

D R A W I N G T I T L E

DRAWN BY CHECKED BY APPROVED BY

SCALE

DATE

FILE REF

DRAWING NUMBER REVISION

Mechanical, Electrical & Electronics Engineers 292, Murtala Muhammed Way, Alagomeji, Yaba, Lagos.

Tel: 09030867276, 08023599742 Email: topklanprojects@topklan.com

ENGINEERS:

PROPOSED RESIDENTIAL DEVELOPMENT

FOR

2-BELLS APARTMENT

PROJECTS:

PROJECT ARCHITECT..

G E N E R A L N O T E S

1. SEE DWG. No. TES502/E001 FOR

LEGEND & GENERAL NOTES.

2. CONSULTANT ENGINEERS TO BE

NOTIFIED OF ANY DISCREPANCIES

BETWEEN THIS DRAWING AND THOSE

BY OTHERS

As indicated

HVAC SYSTEM LAYOUT

TES 502

MAY, 2025

O.F F.O

M302

S.K

1 : 100

M302-FIRST FLOOR PLAN

HVAC

REFRIGERANT SUPPLY

CONDENSATE PIPE

WALL MOUNTED UNIT

OUTDOOR UNIT

INLINE EXTRACTOR FAN

FROM ABOVE

FROM BELOW

TO ABOVE

TO BELOW

FA

FB

TA

TB

HIGH LEVELHL

WALL UNITWU

CONDENSING UNITCU

C

LO

SE

T C

LO

SE

T

C

LO

SE

T

C

LO

SE

T

CLOSET

17 m²

BEDROOM

17 m²

BEDROOM

5 m²

TERRACE

5 m²

TERRACE

5 m²

TERRACE

15 m²

BEDROOM

6 m²

CLOSET

4 m²

BATH

4 m²

BATH

16 m²

BEDROOM

5 m²

TERRACE

6 m²

CLOSET

4 m²

BATH

4 m²

BATH

4 m²

BATH

17 m²

BEDROOM

5 m²

TERRACE

17 m²

BEDROOM

17 m²

BEDROOM

5 m²

TERRACE

1 m²

STORE

8 m²

LOBBY

7 m²

LOBBY

5 m²

STAIRS

5 m²

STAIRS

EF-2

EF-2

EF-2

EF-2

EF-2

EXTRACT DISK

VALVE

FLEX

DUCT

CIRCULAR

PVC DUCT

CIRCULAR

PVC DUCT

EXTRACT

DISK

VALVE

EF-2

Flowrate: 270m3/hr Make: S&P MIXVENT-

TD 250/100

EXISTING VENTILATION

SHAFT TO ROOF SLAB

EXISITNG VENTILATION

SHAFT TO ROOF SLAB

D R A W I N G T I T L E

DRAWN BY CHECKED BY APPROVED BY

SCALE

DATE

FILE REF

DRAWING NUMBER REVISION

Mechanical, Electrical & Electronics Engineers 292, Murtala Muhammed Way, Alagomeji, Yaba, Lagos.

Tel: 09030867276, 08023599742 Email: topklanprojects@topklan.com

ENGINEERS:

PROPOSED RESIDENTIAL DEVELOPMENT

FOR

2-BELLS APARTMENT

PROJECTS:

PROJECT ARCHITECT..

G E N E R A L N O T E S

1. SEE DWG. No. TES502/E001 FOR

LEGEND & GENERAL NOTES.

2. CONSULTANT ENGINEERS TO BE

NOTIFIED OF ANY DISCREPANCIES

BETWEEN THIS DRAWING AND THOSE

BY OTHERS

As indicated

HVAC SYSTEM LAYOUT

TES 502

MAY, 2025

O.F F.O

M302A

S.K

1 : 100

M302A-FIRST FLOOR PLAN

FIRE FIGHTING

FIRE EXTINGUISHER

FE FIRE EXTINGUISHER

43 m²

LIVING ROOM

G04

26 m²

KITCHEN/DINING

G11/G13

3 m²

LAUN.

G14

3 m²

V.TOI.

G10

19 m²

COURTYARD

G06

20 m²

GARAGE

G01

20 m²

GARAGE

G15 Not Enclosed

COURTYARD

G20

43 m²

LIVING ROOM

G18

3 m²

V.TOI.

3 m²

LAUN.

26 m²

KITCHEN/DINING

G24/G26

W A

TE

R

W A

T

ER

1 m²

STORE

W A

SH

R

YE

R

W A

RY

ER

DW

DW

2 m²

STORE

2 m²

STORE

2 m²

STORE

G09

2 m²

STORE

G21

1 m²

CLOSET

1 m²

CLOSET

FE

FE

D R A W I N G T I T L E

DRAWN BY CHECKED BY APPROVED BY

SCALE

DATE

FILE REF

DRAWING NUMBER REVISION

Mechanical, Electrical & Electronics Engineers 292, Murtala Muhammed Way, Alagomeji, Yaba, Lagos.

Tel: 09030867276, 08023599742 Email: topklanprojects@topklan.com

ENGINEERS:

PROPOSED RESIDENTIAL DEVELOPMENT

FOR

2-BELLS APARTMENT

PROJECTS:

PROJECT ARCHITECT..

G E N E R A L N O T E S

1. SEE DWG. No. TES502/E001 FOR

LEGEND & GENERAL NOTES.

2. CONSULTANT ENGINEERS TO BE

NOTIFIED OF ANY DISCREPANCIES

BETWEEN THIS DRAWING AND THOSE

BY OTHERS

As indicated

FIREFIGHTING SYSTEM LAYOUT

TES 502

MAY, 2025

O.F F.O

M401

S.K

No. Description Date

1 : 100

M401-GROUND FLOOR PLAN

D R A W I N G T I T L E

DRAWN BY CHECKED BY APPROVED BY

SCALE

DATE

FILE REF

DRAWING NUMBER REVISION

Mechanical, Electrical & Electronics Engineers 292, Murtala Muhammed Way, Alagomeji, Yaba, Lagos.

Tel: 09030867276, 08023599742 Email: topklanprojects@topklan.com

ENGINEERS:

PROPOSED RESIDENTIAL DEVELOPMENT

FOR

2-BELLS APARTMENT

PROJECTS:

PROJECT ARCHITECT..

G E N E R A L N O T E S

1. SEE DWG. No. TES502/E001 FOR

LEGEND & GENERAL NOTES.

2. CONSULTANT ENGINEERS TO BE

NOTIFIED OF ANY DISCREPANCIES

BETWEEN THIS DRAWING AND THOSE

BY OTHERS

3D VIEW

TES 502

MAY, 2025

O.F F.O

M500

S.K3D VIEW