ATTACHMENTS LIST
RV PARKING PAD
AT
MONTE VISTA NWR
ATTACHMENT 1
ATTACHMENT 2
ATTACHMENT 3
RV PADS SITE LAYOUT WITH UTILITY CONNECTIONS
1.a. Aerial View Monte Vista NWR Location 1.b. Monte Vista Site Layout
USFWS STANDARD RV PAD LAYOUT AND DETAILS
USFWS RV PARKING PAD GUIDANCE
Attachment 1a – Aerial view of Monte Vista NWR and project location amercer Rectangle amercer Text Box Project location: Monte Vista NWR Shop Complex amercer Rectangle amercer Text Box Monte Vista NWR Headquarters
6/21/2021
1/1
Imagery ©2021 Maxar Technologies, Map data ©2021 50 ft Attachment 1.b - Monte Vista NWR Site Layout with Proposed Utility Connections (not to scale) amercer Oval amercer Rectangle amercer Rectangle amercer Rectangle amercer Polygonal Line amercer Line amercer Polygonal Line amercer Polygonal Line amercer Text Box Monte Vista NWR, Shop Complex Legend:
RED: Power - run underground from service pole Blue: Water - connect to waterline at washpad Yellow: Tapered gravel access entry to each RV pad amercer Text Box 2nd pad not in project Future plan
10'-0" 10'-0" 10'-0"
40'-0"
CONTROL
JOINT
S
W
TIE DOWN HOOKS
(8 @ EA. PAD)
FROST PROOF YARD HYDRANT
(COORDIANTE FINAL LOCATION IN FIELD)
SEWER RISER
(TO BE LOCATED IN FIELD)
T Y
P T
Y P
CONTROL
JOINT
CONTROL
JOINT
T Y
P T
Y P
T Y
P T
Y P
T Y
P T
Y P
10'-0"
5'-0"
TYP
TIE DOWN TIE DOWNTIE DOWNTIE DOWN
TIE DOWN HOOKTIE DOWN HOOKTIE DOWN HOOK
15'-0" TYP
E
ELECTRICAL PEDESTAL
(COORDIANTE FINAL
LOCATION IN FIELD)
5'-0" TYP
TYPICAL PAD PLAN1
AutoCAD SHX Text
AutoCAD SHX Text A11
AutoCAD SHX Text
FISH AND WILDLIFE SERVICE
AutoCAD SHX Text
UNITED STATES DEPARTMENT OF THE INTERIOR
AutoCAD SHX Text
REGION 6 ENGINEERING - DENVER, COLORADO
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET 1 OF
AutoCAD SHX Text
CHECKED:
AutoCAD SHX Text
VICINITY MAP
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
OR
AutoCAD SHX Text
RI
AutoCAD SHX Text
ME
AutoCAD SHX Text
RT
AutoCAD SHX Text
PA
AutoCAD SHX Text
DE
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text
NT
AutoCAD SHX Text
TE
AutoCAD SHX Text
IN
AutoCAD SHX Text E
AutoCAD SHX Text
TH
AutoCAD SHX Text
FISH AND WILDLIFE
AutoCAD SHX Text
SERVICE
AutoCAD SHX Text U.S.
AutoCAD SHX Text
U.S. FISH & WILDLIFE SERVICE
AutoCAD SHX Text
SERVICE
AutoCAD SHX Text
FISH AND WILDLIFE
AutoCAD SHX Text
TH
AutoCAD SHX Text
ME
AutoCAD SHX Text
RT
AutoCAD SHX Text
PA
AutoCAD SHX Text
DE
AutoCAD SHX Text
NT
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text
OR
AutoCAD SHX Text
RI
AutoCAD SHX Text
TE
AutoCAD SHX Text
IN
AutoCAD SHX Text E
AutoCAD SHX Text U.S.
AutoCAD SHX Text
APPROVAL SIGNATURES
AutoCAD SHX Text
ANY PRINT ACCOMPANYING THIS INVITATION TO BID MAY BE A REDUCED
AutoCAD SHX Text
REPRODUCTION OF THE WORKING DRAWINGS. IF LINE BELOW DOES NOT
AutoCAD SHX Text
MEASURE SIX INCHES IN LENGTH, THE INDICATED SCALES ARE TO BE
AutoCAD SHX Text
ADJUSTED ACCORDINGLY.
AutoCAD SHX Text
%%UNOTE TO BIDDERS:%%
AutoCAD SHX Text
REGIONAL ENGINEER
AutoCAD SHX Text
DATE
AutoCAD SHX Text
FACILITIES
AutoCAD SHX Text
SAFETY
AutoCAD SHX Text
CULTURAL RESOURCES
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
US FISH AND WILDLIFE
AutoCAD SHX Text
STANDARD RV PAD LAYOUT
AutoCAD SHX Text
RV PAD PLANS & DETAILS
AutoCAD SHX Text 06/21/21
AutoCAD SHX Text
AutoCAD SHX Text
STANDARD RV PAD LAYOUT
AutoCAD SHX Text
TYPICAL RV PAD DEATILS
AutoCAD SHX Text
DRAWING INDEX
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
COVER SHEET, RV PAD PLAN
AutoCAD SHX Text
COVER
AutoCAD SHX Text A10
AutoCAD SHX Text
SHEET #
AutoCAD SHX Text 1/3
AutoCAD SHX Text 2/2
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
NTS
amercer Text Box Monte Vista NWR RV Pad shall be gravel, 50 feet long. Provide power and water as shown on drawings.
Tie downs and sewer not in this project.
amercer
ATTACHMENT 2
LINE SIDE CABLE
TO NEXT POST
PEDESTAL SCHEDULE
TYPE
RECEPTACLES
CIRCUIT PROTECTION
ALL SHALL BE GROUNDING TYPE
(1) 20A, 120V, 2 POLE, 3 WIRE GFCI, 20A, 120V
(2) 30A, 120V, 2 POLE, 3 WIRE
GFCI, 30A, 120V
(3) 50A, 120V, 2 POLE, 3 WIRE
GFCI, 50A, 120V
NOTE: SUITABLE FOR LOOP FEED. POST CONNECTORS SHALL BE SIZED TO ACCOMMODATE
FROM #2 TO #250 MCM PER PHASE, UL LISTED, NEMA 3R CONSTRUCTION.
50A
SOCKET (4
PRONG
30A SOCKET
20A SOCKET
6x6 - W2.9xW2.9 WWF
OR #3 BAR @ 24" OC.EW.
PREFORMED STRIP OR SAW
CUT TO 1/4 THICKNESS OF SLAB
W/ JOINT FILLER, SHORE HARDINESS "A"
OF AT LEAST 80
CRUSHED GRAVEL BASE
REMOVABLE COVER
4" PLUG
4" SCH 40 PVC CHANGES
TO 4" 35 PVC SEWER
OUT SIDE OF SLAB
SLOPE TO SEPTIC
1/4" PER FOOT
6" SDR 35 PVC PIPE SLIP SLEEVE
FROST PROOF YARD
HYDRANT, DEPTH VARIES
PER LOCAL REQUIREMENTS
3/4" 200# POLY
FILL W/ GRAVEL
#4 REBAR W/ STD. HOOK AT
EACH END TO SECURE TRAILERS
6x6 REDWOOD BOX, FILLED
WITH GRAVEL FOR DRAINAGE
RV PAD DETAILS
A110
TIE-DOWN
ANCHOR LOOP3
SEWER CONNECTION2
CONCRETE SECTION1
YARD HYDRANT4
ELECTRICAL PEDESTAL5 ELECTRICAL PEDESTAL6
AutoCAD SHX Text
GFI
AutoCAD SHX Text
GFI
AutoCAD SHX Text
GFI
AutoCAD SHX Text
%%UPEDESTAL WIRING
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
SUB-SHEET
AutoCAD SHX Text
US FISH AND WILDLIFE
AutoCAD SHX Text
STANDARD RV PAD LAYOUT
AutoCAD SHX Text 06/21/21
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
NTS
RV Spot Design and Construction Guidance Legacy Region 6 Written By: Michael Wandersee/Revised Ann Erin Mercer for 2021 projects Date: 2021
1 | P a g e
PURPOSE:
This guidance document is to standardize recreational vehicle (RV) and trailers (from this point forward called RV) pads. This document will serve to assist in construction services and/or an in‐house construction guide.
GENERAL DESIGN:
The following items should be considered during the planning and construction process:
All finished surfaces of the pad shall be slightly higher than the surrounding surface
The RV pad shall be a minimum 40 feet long
Most RVs will fit within 40 feet long pad
The minimum width of the pad is 20 feet to accommodate RVs equipped with a lift chair.
The maximum slope in any direction is two percent o Gravel pads are allowed no more than five percent slope
The RV pads shall be concrete or gravel
Provide a taper approach from the access road to the pad to allow for ease of turning. The width of the taper and length required is dependent on site conditions
Water, sewer, and electrical hookups on RVs are typically on the driver’s side
Provide a single pedestal with a 50, 30, and 20 amp service for each pad
Each pad shall have a frost proof yard hydrant
A RV concrete pad shall have a minimum six inches thick concrete with five inches of gravel
A RV gravel pad shall have a minimum of seven inches of gravel
Provide a minimum setback of five feet on all sides
SPECIFICATIONS:
WATER SERVICE:
All water service line piping and appurtenances must meet the requirements of NSF/ANSI‐ 61 and NSF/ANSI‐14 Polyethylene Pipe
AWWA C901 and ASTM D2239 IPS size pipe: 200 psi pressure rating High density, ultrahigh molecular weight polyethylene pipe compound PE‐3408 or PE Non‐flare fittings: Compression type equal to Ford Pack Joint, C66‐44 or C66‐55, or McDonald MAC‐PAK with rigid stainless steel stiffeners Pipe equal to Cresline HD 200
Copper Pipe ¾‐inch diameter with minimum wall thickness of 0.045 inches.
Type “K” soft annealed seamless copper tubing suitable for installation in public water systems conforming to ASTM B88 Solder or compression type connections as manufactured by A.Y. McDonald or Ford amercer
ATTACHMENT 3 USFWS RV PARKING PAD GUIDANCE
Written By: Michael Wandersee/Revised Ann Erin Mercer for 2021 projects Date: 2021
2 | P a g e
Cross‐Linked Polyethylene (PEX) ¾‐inch with minimum wall thickness of 0.102 inches Conform to ASTM F 876 Mechanical crimp typed connections
PVC Pipe Conform to ASTM D2241, PVC 1120, SDR 21 or SDR 17 as indicated in the bid schedule.
Rubber compression ring joint conforming to ASTM D3139 Conform to ASTM D1785, Schedule 40
Saddles.
Minimum pressure rating of 200 psi Buna‐N rubber gaskets Stainless steel nuts and bolts Minimum 4 inches wide for 3‐inch diameter pipe and 5 inches wide for 4‐inch diameter pipe
PVC ASTM D2241 Pipe: Double bolt stainless steel equal to Romac 202BS, Romac 306 or Ford FS313
PVC C900 Pipe: Stainless steel single bolt saddle clamps equal to Ford FS101 or equal Ductile Iron, Asbestos Cement or HDPE Pipe: Double bolt stainless steel band equal to Ford FS202
Corporation Stops No‐Lead Brass, meeting NSF‐61, with pack joint connection Non‐flare connections for all pipe types, equal to McDonald MAC‐PAK with stainless steel stiffeners or Ford pack joint compression couplings with stainless steel stiffeners
PE Service line: A.Y. McDonald 74701B‐33, Ford FB1001‐NL, Mueller H15009N, or equal PVC Service line: Ford FB 1002‐NL, A.Y. McDonald 74701B‐44, or equal
Curb Stops No‐lead Brass, meeting NSF‐61, with pack joint connections Non‐flare connections for all pipe types Minneapolis pattern IPS polyethylene service line: Ford B66‐444M‐NL, A.Y. McDonald 76104 – 33, or equal with stainless steel stiffeners
IPS polyethylene service line greater than 1‐inch diameter: Ford B11‐555M‐NL or A.Y.
McDonald 76104‐33 with stainless steel stiffeners
PVC service line: Ford B77‐666M‐NL or B77‐777M‐NL, A.Y. McDonald 76104‐44, or equal
Curb Boxes with Stationary Rod Cast iron Minneapolis pattern, length to match bury depth Stainless steel stationary rod Pentagon plug A.Y. McDonald 5614, or equal Curb box lids: A.Y. McDonald 5607L or equal Supply one pentagon wrench and one combination key equal to A.Y. McDonald Catalog #304B, 36 inches long or equal
Provide sufficient slack in the water service line to prevent pulling joints apart and to allow for contraction due to temperature changes
3 | P a g e
Install service line:
From the main to a location at each pad Bury line consistent with water main depth. Insulate where installed above recommended frost line
Install warning tape 2 feet below finished grade Use compression couplings for all connections Use stainless steel insert stiffeners for compression connections to PE pipe No splices or joints are allowed from the point of connection to the main to a point 10 feet beyond any sewer line crossing
Install saddle at each corporation stop tapping location Connections shall be live tapped through the corporation stop with an approved tapping machine, unless specified below
Dry taps are allowed only during new water main installation, before main disinfection For connections to mains smaller than 3 inch diameter, use saddle with ¾ inch tap and transition for 1 inch diameter water service line
Install curb stops and boxes with stationary rod Set curb stops on a solid concrete block 4 inches thick by 8 inches wide by 16 inches long placed on undisturbed earth
Install stationary rod on curb stop Set the top of curb boxes flush with finished grade elevation Support curb box during the backfilling operation to prevent movement and maintain a vertical position
YARD HYDRANT:
A. Frost proof and buried below frost line B. Inlet: ¾” NPT C. Outlet: ¾” brass house thread D. Rod: Stainless steel operating rod thru Teflon packing E. Automatic self‐adjusting plunger F. Stand Pipe: 1” stainless steel G. Model Any Flow as manufactured by Merrill Manufacturing of Storm Lake, Iowa H. Accessories:
1. Hydrant assist kit provided by Seppman Enterprises, model HAK 750
2. Vacuum breaker, model NF8 as manufactured by Watts of North Andover, Massachusetts I. Set coupler vertical on precast concrete block J. Place 5 cubic feet of clean crushed rock around base of hydrant with minimal amount of rock above the valve body for drainage K. Pour 36” square concrete pad
4 | P a g e
WATER SERVICE DISINFECTION:
If water service facilities are installed and connected to newly installed water main, disinfect the service line at the same time as the water main
If water service facilities are connected to an existing water main by live tap:
Disinfect the new water service facilities prior to connecting to the corporation stop Introduce sufficient chlorine solution into the corporation stop end to the water service line to produce a minimum chlorine residual of 200 ppm when filled
After connection to corporation stop and pressurizing, flush the service line at the ball valve after three hours
After service line is sufficiently flushed, obtain a water sample for bacteriological testing.
Repeat process until a negative bacteriological report is received
Flushing chlorinated water in accordance with AWWA C651.
Waste flushed disinfection water in an environmentally safe manner. The method used is subject to the approval of the Station Manager
CONCRETE
Expansion and Isolation Joint Filler Strips:
Exterior: ASTM D 994, bituminous strip, minimum 1/2‐inch thick, height equal to joint depth
Interior: ASTM D 1752, sponge rubber, concrete gray in color, minimum 1/2‐inch thick, height equal to joint depth
Concrete mixtures Cementitious Materials: Use fly ash, pozzolan, ground granulated blast‐furnace slag, and silica fume as needed to reduce the total amount of portland cement, which would otherwise be used, by not less than 20 percent by weight
Proportion normal weight concrete mixture used for Exterior Concrete slabs, pads, and walkways as follows:
a. Minimum Compressive Strength: 3000 psi at 28 days
b. Maximum Water‐Cementitious Materials Ratio: 0.49
c. Slump Limit: 5 inches plus or minus 1 inch
d. Air Content: 3 percent, plus or minus 1 percent
Concrete mixing When air temperature is between 85 and 90 deg F (30 and 32 deg C), reduce mixing and delivery time from 1‐1/2 hours to 75 minutes; when air temperature is above 90 deg F (32 deg C), reduce mixing and delivery time to 60 minutes
Joints General: Construct joints true to line with faces perpendicular to surface plane of concrete
Contraction joins shall be placed every six feet or abutting any structure different from the sidewalk and/or slab
Contraction joints shall be cut 1/8” and filled with joint filler, with a shore hardness “A” of at least 80
Install expansion joints with HD100
5 | P a g e
Trowel and Fine‐Broom Finish: Apply a first trowel finish to non‐water and water bearing slabs. While concrete is still plastic, slightly scarify surface with a fine broom. Brooming shall be perpendicular to drainage unless otherwise indicated Treatment of surface defects
As soon as forms are removed, exposed surfaces shall be carefully examined and any irregularities shall be immediately rubbed or ground in a satisfactory manner in order to secure a smooth, uniform, and continuous surface. Concrete containing minor voids, holes, honeycombing, or similar depression defects shall be repaired
Holes left by tie‐rod cones shall be reamed with suitable toothed reamers so as to leave the surfaces of the holes clean and rough. Holes then shall be repaired in an approved manner with dry‐packed cement grout
Prior to filling any structure with water, cracks shall be "vee'd" as indicated and filled with sealant. This repair method shall be done on the water bearing face of members.
Prior to backfilling, faces of members in contact with fill which are not covered with a waterproofing membrane shall also have cracks repaired as indicated herein
GRAVEL
Aggregates The crushed stone or gravel shall consist of sound durable particles Meet the following characteristics (and limited amounts of fine soil particles):
SIEVE SIZE PERCENT PASSING
¾ inch 100
No. 4 50‐78
No. 8 37‐67
No. 40 13‐35
No. 200 4‐15
Plasticity Index 4‐12
Processing Required crushed
The fraction passing the No. 200 sieve shall not be greater than two‐thirds (2/3) of the fraction passing the No. 40 sieve
In no case shall the upper limit specified for the No. 200 sieve be exceeded In the event that all sieves are not available, the engineer shall evaluate based on the available sieves
Preparation Protect structures, utilities, sidewalks, pavements, and other facilities from damage caused by settlement, lateral movement, undermining, washout, and other hazards created by earth moving operations
Protect and maintain erosion and sedimentation controls during earth moving operations
Surface Preparation
Written By: Michael Wandersee/Revised Ann Erin Mercer for 2021 projects Date: 2021
6 | P a g e
General: Immediately before placing aggregate materials, remove loose and deleterious material from substrate surfaces. Ensure that prepared subgrade is ready to receive surfacing Stockpiled material shall be free of plants, lumps of gravel, concrete or chip‐seal material, or any structure that causes the material to cause spreading issues
Placement Place and compact surface material in layers to required elevations to avoid ponding and poor drainage
Soil Moisture Control Uniformly moisten or aerate subgrade and each subsequent fill or backfill soil layer before compaction to within 2 percent of optimum moisture content
a. Do not place gravel material on surfaces that are muddy, frozen, or contain frost or ice
b. Remove and replace, or scarify and air dry, otherwise satisfactory gravel that exceeds optimum moisture content by 2 percent and is too wet to compact to specified dry unit weight
Compaction Place aggregate materials in layers not more than 8 inches in loose depth for material compacted by heavy compaction equipment, and not more than 4 inches in loose depth for material compacted by hand‐operated tampers and/or roller with no more less than 250 pounds per inch of roller width Place aggregate materials evenly on all sides of structures to required elevations, and uniformly along the full length of each structure Compact each layer of backfill or fill soil material at 95 percent
Grading General: Uniformly grade areas to a smooth surface, free of irregular surface changes.
Comply with compaction requirements and grade to cross sections, lines, and elevations indicated Site Rough Grading: Slope grades to direct water away from buildings and to prevent ponding
ELECTRICAL
Pedestal shall be placed in a concrete pad All three services shall exist in a single pedestal with the appropriate receptacles
Install anchors required for the area Electrical installers shall be certified All work shall comply with NEC, local codes, NEMA, UL, and/or ASA A breaker shall be installed Bury depth shall be a minimum of three feet
(Septic/Sewer is not a part of this project):
SEWER SERVICE LINE
Stub out
7 | P a g e
Place cap that is identified in “Double Cleanouts” Part C Piping and fittings conform to ASTM D3034 as indicated:
Pipe Class: Schedule 40 Solvent weld joints conforming to ASTM D2855.
4‐inch nominal diameter unless otherwise indicated.
Each length of pipe shall be clearly marked with the following:
a. Manufacturer.
b. Nominal Pipe Size.
c. The PVC Cell Classification.
d. Type PSM PVC Sewer Pipe.
e. ASTM Designation.
f. Pipe Class.
Double Cleanouts:
Schedule 40 PVC DWV pipe and fittings conforming to ASTM D2665.
Supply 4‐inch slip on cap or threaded female adapter with 4‐inch diameter threaded slotted white flush plug with threaded brass insert as manufactured by Sioux Chief or approved equal.
Install a 4‐inch sewer wye in the sewer service line and connect risers of the same material from the wye to the ground surface.
a. Attach a schedule 40 PVC DWV slip‐on cap or female adapter to the end of the riser.
b. Install cleanout so cap is flush with finished grade.
Pipe installation General
a. Bed pipe according to the drawing. If imported material is required to safely bed the pipe, the contractor shall immediately halt construction and consult with the project engineer.
b. If trenching occurs, the trench shall be 4 to 6 inches wider than the pipe diameter
c. Initial backfill shall be free of clods, stones, frozen material, and organic material.
The contractor shall ensure pipe cannot move and is compacted adequately by hand in lifts of 6 inches.
d. Backfilling shall occur in 12 inch lifts. The lifts shall be compacted to 90% maximum dry density.
Bury depth
a. If minimum bury depth of three feet cannot be met, the contractor shall install 2” rigid polystyrene EPS located over centerline of pipe and is 18” wide, at a minimum.
b. All pipe shall be a minimum of 2 feet below grade
Utility Conflicts
a. Sewer shall be located under water lines
b. Pipe shall have joints equidistant from the point of crossing
c. A minimum spacing of 30 inches horizontal and 12 inches vertical.
d. Exceptions will likely require concrete to create a barrier.
Slopes:
a. Minimum slope for sewer service lines is 1/8‐inch per foot (1%).
b. Maximum slope for sewer service lines is 1/2‐inch per foot (4 %), unless otherwise specified.
8 | P a g e
GENERAL DETAILS
9 | P a g e
| TOC |
| Atch 1 Site Layout |
| Atch 2 Std RV Drawings |
| Atch 3 USFWS RV Pad Guidance |