Attachment-3_Layout_Drawings_Guidance_21-068_Rvsd26Jul21.pdf

PDF 5 MB Posted

Attached to
REPLACE RV PADS Federal contract opportunity
Solicitation number
140F0121R0071
Issued by
Department of the Interior Fish and Wildlife Service

View the file

Other files for this federal contract opportunity

Other files attached to REPLACE RV PADS, newest first.
File Type Posted
Sol_140F0121R0071_Amd_0001.pdf PDF
Attachment_1-B08-Solicitation_140F0121R0071_(1).pdf PDF
Attachment_5-B03-DOL_Wage_Determinationdocx.pdf PDF
Attachment_2-08_Specifications_21-068_Revised_26Jul21.pdf PDF
Attachment_4-06_Bid_Schedule_21-068_Revised_26Jul21.pdf PDF
Sol_140F0121R0071.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ATTACHMENTS LIST

RV PARKING PAD

AT

MONTE VISTA NWR

ATTACHMENT 1

ATTACHMENT 2

ATTACHMENT 3

RV PADS SITE LAYOUT WITH UTILITY CONNECTIONS

1.a. Aerial View Monte Vista NWR Location 1.b. Monte Vista Site Layout

USFWS STANDARD RV PAD LAYOUT AND DETAILS

USFWS RV PARKING PAD GUIDANCE

Attachment 1a – Aerial view of Monte Vista NWR and project location amercer Rectangle amercer Text Box Project location: Monte Vista NWR Shop Complex amercer Rectangle amercer Text Box Monte Vista NWR Headquarters

6/21/2021

1/1

Imagery ©2021 Maxar Technologies, Map data ©2021 50 ft Attachment 1.b - Monte Vista NWR Site Layout with Proposed Utility Connections (not to scale) amercer Oval amercer Rectangle amercer Rectangle amercer Rectangle amercer Polygonal Line amercer Line amercer Polygonal Line amercer Polygonal Line amercer Text Box Monte Vista NWR, Shop Complex Legend:

RED: Power - run underground from service pole Blue: Water - connect to waterline at washpad Yellow: Tapered gravel access entry to each RV pad amercer Text Box 2nd pad not in project Future plan

10'-0" 10'-0" 10'-0"

40'-0"

CONTROL

JOINT

S

W

TIE DOWN HOOKS

(8 @ EA. PAD)

FROST PROOF YARD HYDRANT

(COORDIANTE FINAL LOCATION IN FIELD)

SEWER RISER

(TO BE LOCATED IN FIELD)

T Y

P T

Y P

CONTROL

JOINT

CONTROL

JOINT

T Y

P T

Y P

T Y

P T

Y P

T Y

P T

Y P

10'-0"

5'-0"

TYP

TIE DOWN TIE DOWNTIE DOWNTIE DOWN

TIE DOWN HOOKTIE DOWN HOOKTIE DOWN HOOK

15'-0" TYP

E

ELECTRICAL PEDESTAL

(COORDIANTE FINAL

LOCATION IN FIELD)

5'-0" TYP

TYPICAL PAD PLAN1

AutoCAD SHX Text

AutoCAD SHX Text A11

AutoCAD SHX Text

FISH AND WILDLIFE SERVICE

AutoCAD SHX Text

UNITED STATES DEPARTMENT OF THE INTERIOR

AutoCAD SHX Text

REGION 6 ENGINEERING - DENVER, COLORADO

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DRAWN:

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET 1 OF

AutoCAD SHX Text

CHECKED:

AutoCAD SHX Text

VICINITY MAP

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

OR

AutoCAD SHX Text

RI

AutoCAD SHX Text

ME

AutoCAD SHX Text

RT

AutoCAD SHX Text

PA

AutoCAD SHX Text

DE

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text

NT

AutoCAD SHX Text

TE

AutoCAD SHX Text

IN

AutoCAD SHX Text E

AutoCAD SHX Text

TH

AutoCAD SHX Text

FISH AND WILDLIFE

AutoCAD SHX Text

SERVICE

AutoCAD SHX Text U.S.

AutoCAD SHX Text

U.S. FISH & WILDLIFE SERVICE

AutoCAD SHX Text

SERVICE

AutoCAD SHX Text

FISH AND WILDLIFE

AutoCAD SHX Text

TH

AutoCAD SHX Text

ME

AutoCAD SHX Text

RT

AutoCAD SHX Text

PA

AutoCAD SHX Text

DE

AutoCAD SHX Text

NT

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text

OR

AutoCAD SHX Text

RI

AutoCAD SHX Text

TE

AutoCAD SHX Text

IN

AutoCAD SHX Text E

AutoCAD SHX Text U.S.

AutoCAD SHX Text

APPROVAL SIGNATURES

AutoCAD SHX Text

ANY PRINT ACCOMPANYING THIS INVITATION TO BID MAY BE A REDUCED

AutoCAD SHX Text

REPRODUCTION OF THE WORKING DRAWINGS. IF LINE BELOW DOES NOT

AutoCAD SHX Text

MEASURE SIX INCHES IN LENGTH, THE INDICATED SCALES ARE TO BE

AutoCAD SHX Text

ADJUSTED ACCORDINGLY.

AutoCAD SHX Text

%%UNOTE TO BIDDERS:%%

AutoCAD SHX Text

REGIONAL ENGINEER

AutoCAD SHX Text

DATE

AutoCAD SHX Text

FACILITIES

AutoCAD SHX Text

SAFETY

AutoCAD SHX Text

CULTURAL RESOURCES

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

US FISH AND WILDLIFE

AutoCAD SHX Text

STANDARD RV PAD LAYOUT

AutoCAD SHX Text

RV PAD PLANS & DETAILS

AutoCAD SHX Text 06/21/21

AutoCAD SHX Text

AutoCAD SHX Text

STANDARD RV PAD LAYOUT

AutoCAD SHX Text

TYPICAL RV PAD DEATILS

AutoCAD SHX Text

DRAWING INDEX

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

COVER SHEET, RV PAD PLAN

AutoCAD SHX Text

COVER

AutoCAD SHX Text A10

AutoCAD SHX Text

SHEET #

AutoCAD SHX Text 1/3

AutoCAD SHX Text 2/2

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

NTS

amercer Text Box Monte Vista NWR RV Pad shall be gravel, 50 feet long. Provide power and water as shown on drawings.

Tie downs and sewer not in this project.

amercer

ATTACHMENT 2

LINE SIDE CABLE

TO NEXT POST

PEDESTAL SCHEDULE

TYPE

RECEPTACLES

CIRCUIT PROTECTION

ALL SHALL BE GROUNDING TYPE

(1) 20A, 120V, 2 POLE, 3 WIRE GFCI, 20A, 120V

(2) 30A, 120V, 2 POLE, 3 WIRE

GFCI, 30A, 120V

(3) 50A, 120V, 2 POLE, 3 WIRE

GFCI, 50A, 120V

NOTE: SUITABLE FOR LOOP FEED. POST CONNECTORS SHALL BE SIZED TO ACCOMMODATE

FROM #2 TO #250 MCM PER PHASE, UL LISTED, NEMA 3R CONSTRUCTION.

50A

SOCKET (4

PRONG

30A SOCKET

20A SOCKET

6x6 - W2.9xW2.9 WWF

OR #3 BAR @ 24" OC.EW.

PREFORMED STRIP OR SAW

CUT TO 1/4 THICKNESS OF SLAB

W/ JOINT FILLER, SHORE HARDINESS "A"

OF AT LEAST 80

CRUSHED GRAVEL BASE

REMOVABLE COVER

4" PLUG

4" SCH 40 PVC CHANGES

TO 4" 35 PVC SEWER

OUT SIDE OF SLAB

SLOPE TO SEPTIC

1/4" PER FOOT

6" SDR 35 PVC PIPE SLIP SLEEVE

FROST PROOF YARD

HYDRANT, DEPTH VARIES

PER LOCAL REQUIREMENTS

3/4" 200# POLY

FILL W/ GRAVEL

#4 REBAR W/ STD. HOOK AT

EACH END TO SECURE TRAILERS

6x6 REDWOOD BOX, FILLED

WITH GRAVEL FOR DRAINAGE

RV PAD DETAILS

A110

TIE-DOWN

ANCHOR LOOP3

SEWER CONNECTION2

CONCRETE SECTION1

YARD HYDRANT4

ELECTRICAL PEDESTAL5 ELECTRICAL PEDESTAL6

AutoCAD SHX Text

GFI

AutoCAD SHX Text

GFI

AutoCAD SHX Text

GFI

AutoCAD SHX Text

%%UPEDESTAL WIRING

AutoCAD SHX Text

DESIGNED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

SUB-SHEET

AutoCAD SHX Text

US FISH AND WILDLIFE

AutoCAD SHX Text

STANDARD RV PAD LAYOUT

AutoCAD SHX Text 06/21/21

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

NTS

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

NTS

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

NTS

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

NTS

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

NTS

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

NTS

RV Spot Design and Construction Guidance Legacy Region 6 Written By: Michael Wandersee/Revised Ann Erin Mercer for 2021 projects Date: 2021

1 | P a g e

PURPOSE:

This guidance document is to standardize recreational vehicle (RV) and trailers (from this point forward called RV) pads. This document will serve to assist in construction services and/or an in‐house construction guide.

GENERAL DESIGN:

The following items should be considered during the planning and construction process:

All finished surfaces of the pad shall be slightly higher than the surrounding surface

The RV pad shall be a minimum 40 feet long

Most RVs will fit within 40 feet long pad

The minimum width of the pad is 20 feet to accommodate RVs equipped with a lift chair.

The maximum slope in any direction is two percent o Gravel pads are allowed no more than five percent slope

The RV pads shall be concrete or gravel

Provide a taper approach from the access road to the pad to allow for ease of turning. The width of the taper and length required is dependent on site conditions

Water, sewer, and electrical hookups on RVs are typically on the driver’s side

Provide a single pedestal with a 50, 30, and 20 amp service for each pad

Each pad shall have a frost proof yard hydrant

A RV concrete pad shall have a minimum six inches thick concrete with five inches of gravel

A RV gravel pad shall have a minimum of seven inches of gravel

Provide a minimum setback of five feet on all sides

SPECIFICATIONS:

WATER SERVICE:

All water service line piping and appurtenances must meet the requirements of NSF/ANSI‐ 61 and NSF/ANSI‐14 Polyethylene Pipe

AWWA C901 and ASTM D2239 IPS size pipe: 200 psi pressure rating High density, ultrahigh molecular weight polyethylene pipe compound PE‐3408 or PE Non‐flare fittings: Compression type equal to Ford Pack Joint, C66‐44 or C66‐55, or McDonald MAC‐PAK with rigid stainless steel stiffeners Pipe equal to Cresline HD 200

Copper Pipe ¾‐inch diameter with minimum wall thickness of 0.045 inches.

Type “K” soft annealed seamless copper tubing suitable for installation in public water systems conforming to ASTM B88 Solder or compression type connections as manufactured by A.Y. McDonald or Ford amercer

ATTACHMENT 3 USFWS RV PARKING PAD GUIDANCE

Written By: Michael Wandersee/Revised Ann Erin Mercer for 2021 projects Date: 2021

2 | P a g e

Cross‐Linked Polyethylene (PEX) ¾‐inch with minimum wall thickness of 0.102 inches Conform to ASTM F 876 Mechanical crimp typed connections

PVC Pipe Conform to ASTM D2241, PVC 1120, SDR 21 or SDR 17 as indicated in the bid schedule.

Rubber compression ring joint conforming to ASTM D3139 Conform to ASTM D1785, Schedule 40

Saddles.

Minimum pressure rating of 200 psi Buna‐N rubber gaskets Stainless steel nuts and bolts Minimum 4 inches wide for 3‐inch diameter pipe and 5 inches wide for 4‐inch diameter pipe

PVC ASTM D2241 Pipe: Double bolt stainless steel equal to Romac 202BS, Romac 306 or Ford FS313

PVC C900 Pipe: Stainless steel single bolt saddle clamps equal to Ford FS101 or equal Ductile Iron, Asbestos Cement or HDPE Pipe: Double bolt stainless steel band equal to Ford FS202

Corporation Stops No‐Lead Brass, meeting NSF‐61, with pack joint connection Non‐flare connections for all pipe types, equal to McDonald MAC‐PAK with stainless steel stiffeners or Ford pack joint compression couplings with stainless steel stiffeners

PE Service line: A.Y. McDonald 74701B‐33, Ford FB1001‐NL, Mueller H15009N, or equal PVC Service line: Ford FB 1002‐NL, A.Y. McDonald 74701B‐44, or equal

Curb Stops No‐lead Brass, meeting NSF‐61, with pack joint connections Non‐flare connections for all pipe types Minneapolis pattern IPS polyethylene service line: Ford B66‐444M‐NL, A.Y. McDonald 76104 – 33, or equal with stainless steel stiffeners

IPS polyethylene service line greater than 1‐inch diameter: Ford B11‐555M‐NL or A.Y.

McDonald 76104‐33 with stainless steel stiffeners

PVC service line: Ford B77‐666M‐NL or B77‐777M‐NL, A.Y. McDonald 76104‐44, or equal

Curb Boxes with Stationary Rod Cast iron Minneapolis pattern, length to match bury depth Stainless steel stationary rod Pentagon plug A.Y. McDonald 5614, or equal Curb box lids: A.Y. McDonald 5607L or equal Supply one pentagon wrench and one combination key equal to A.Y. McDonald Catalog #304B, 36 inches long or equal

Provide sufficient slack in the water service line to prevent pulling joints apart and to allow for contraction due to temperature changes

3 | P a g e

Install service line:

From the main to a location at each pad Bury line consistent with water main depth. Insulate where installed above recommended frost line

Install warning tape 2 feet below finished grade Use compression couplings for all connections Use stainless steel insert stiffeners for compression connections to PE pipe No splices or joints are allowed from the point of connection to the main to a point 10 feet beyond any sewer line crossing

Install saddle at each corporation stop tapping location Connections shall be live tapped through the corporation stop with an approved tapping machine, unless specified below

Dry taps are allowed only during new water main installation, before main disinfection For connections to mains smaller than 3 inch diameter, use saddle with ¾ inch tap and transition for 1 inch diameter water service line

Install curb stops and boxes with stationary rod Set curb stops on a solid concrete block 4 inches thick by 8 inches wide by 16 inches long placed on undisturbed earth

Install stationary rod on curb stop Set the top of curb boxes flush with finished grade elevation Support curb box during the backfilling operation to prevent movement and maintain a vertical position

YARD HYDRANT:

A. Frost proof and buried below frost line B. Inlet: ¾” NPT C. Outlet: ¾” brass house thread D. Rod: Stainless steel operating rod thru Teflon packing E. Automatic self‐adjusting plunger F. Stand Pipe: 1” stainless steel G. Model Any Flow as manufactured by Merrill Manufacturing of Storm Lake, Iowa H. Accessories:

1. Hydrant assist kit provided by Seppman Enterprises, model HAK 750

2. Vacuum breaker, model NF8 as manufactured by Watts of North Andover, Massachusetts I. Set coupler vertical on precast concrete block J. Place 5 cubic feet of clean crushed rock around base of hydrant with minimal amount of rock above the valve body for drainage K. Pour 36” square concrete pad

4 | P a g e

WATER SERVICE DISINFECTION:

If water service facilities are installed and connected to newly installed water main, disinfect the service line at the same time as the water main

If water service facilities are connected to an existing water main by live tap:

Disinfect the new water service facilities prior to connecting to the corporation stop Introduce sufficient chlorine solution into the corporation stop end to the water service line to produce a minimum chlorine residual of 200 ppm when filled

After connection to corporation stop and pressurizing, flush the service line at the ball valve after three hours

After service line is sufficiently flushed, obtain a water sample for bacteriological testing.

Repeat process until a negative bacteriological report is received

Flushing chlorinated water in accordance with AWWA C651.

Waste flushed disinfection water in an environmentally safe manner. The method used is subject to the approval of the Station Manager

CONCRETE

Expansion and Isolation Joint Filler Strips:

Exterior: ASTM D 994, bituminous strip, minimum 1/2‐inch thick, height equal to joint depth

Interior: ASTM D 1752, sponge rubber, concrete gray in color, minimum 1/2‐inch thick, height equal to joint depth

Concrete mixtures Cementitious Materials: Use fly ash, pozzolan, ground granulated blast‐furnace slag, and silica fume as needed to reduce the total amount of portland cement, which would otherwise be used, by not less than 20 percent by weight

Proportion normal weight concrete mixture used for Exterior Concrete slabs, pads, and walkways as follows:

a. Minimum Compressive Strength: 3000 psi at 28 days

b. Maximum Water‐Cementitious Materials Ratio: 0.49

c. Slump Limit: 5 inches plus or minus 1 inch

d. Air Content: 3 percent, plus or minus 1 percent

Concrete mixing When air temperature is between 85 and 90 deg F (30 and 32 deg C), reduce mixing and delivery time from 1‐1/2 hours to 75 minutes; when air temperature is above 90 deg F (32 deg C), reduce mixing and delivery time to 60 minutes

Joints General: Construct joints true to line with faces perpendicular to surface plane of concrete

Contraction joins shall be placed every six feet or abutting any structure different from the sidewalk and/or slab

Contraction joints shall be cut 1/8” and filled with joint filler, with a shore hardness “A” of at least 80

Install expansion joints with HD100

5 | P a g e

Trowel and Fine‐Broom Finish: Apply a first trowel finish to non‐water and water bearing slabs. While concrete is still plastic, slightly scarify surface with a fine broom. Brooming shall be perpendicular to drainage unless otherwise indicated Treatment of surface defects

As soon as forms are removed, exposed surfaces shall be carefully examined and any irregularities shall be immediately rubbed or ground in a satisfactory manner in order to secure a smooth, uniform, and continuous surface. Concrete containing minor voids, holes, honeycombing, or similar depression defects shall be repaired

Holes left by tie‐rod cones shall be reamed with suitable toothed reamers so as to leave the surfaces of the holes clean and rough. Holes then shall be repaired in an approved manner with dry‐packed cement grout

Prior to filling any structure with water, cracks shall be "vee'd" as indicated and filled with sealant. This repair method shall be done on the water bearing face of members.

Prior to backfilling, faces of members in contact with fill which are not covered with a waterproofing membrane shall also have cracks repaired as indicated herein

GRAVEL

Aggregates The crushed stone or gravel shall consist of sound durable particles Meet the following characteristics (and limited amounts of fine soil particles):

SIEVE SIZE PERCENT PASSING

¾ inch 100

No. 4 50‐78

No. 8 37‐67

No. 40 13‐35

No. 200 4‐15

Plasticity Index 4‐12

Processing Required crushed

The fraction passing the No. 200 sieve shall not be greater than two‐thirds (2/3) of the fraction passing the No. 40 sieve

In no case shall the upper limit specified for the No. 200 sieve be exceeded In the event that all sieves are not available, the engineer shall evaluate based on the available sieves

Preparation Protect structures, utilities, sidewalks, pavements, and other facilities from damage caused by settlement, lateral movement, undermining, washout, and other hazards created by earth moving operations

Protect and maintain erosion and sedimentation controls during earth moving operations

Surface Preparation

Written By: Michael Wandersee/Revised Ann Erin Mercer for 2021 projects Date: 2021

6 | P a g e

General: Immediately before placing aggregate materials, remove loose and deleterious material from substrate surfaces. Ensure that prepared subgrade is ready to receive surfacing Stockpiled material shall be free of plants, lumps of gravel, concrete or chip‐seal material, or any structure that causes the material to cause spreading issues

Placement Place and compact surface material in layers to required elevations to avoid ponding and poor drainage

Soil Moisture Control Uniformly moisten or aerate subgrade and each subsequent fill or backfill soil layer before compaction to within 2 percent of optimum moisture content

a. Do not place gravel material on surfaces that are muddy, frozen, or contain frost or ice

b. Remove and replace, or scarify and air dry, otherwise satisfactory gravel that exceeds optimum moisture content by 2 percent and is too wet to compact to specified dry unit weight

Compaction Place aggregate materials in layers not more than 8 inches in loose depth for material compacted by heavy compaction equipment, and not more than 4 inches in loose depth for material compacted by hand‐operated tampers and/or roller with no more less than 250 pounds per inch of roller width Place aggregate materials evenly on all sides of structures to required elevations, and uniformly along the full length of each structure Compact each layer of backfill or fill soil material at 95 percent

Grading General: Uniformly grade areas to a smooth surface, free of irregular surface changes.

Comply with compaction requirements and grade to cross sections, lines, and elevations indicated Site Rough Grading: Slope grades to direct water away from buildings and to prevent ponding

ELECTRICAL

Pedestal shall be placed in a concrete pad All three services shall exist in a single pedestal with the appropriate receptacles

Install anchors required for the area Electrical installers shall be certified All work shall comply with NEC, local codes, NEMA, UL, and/or ASA A breaker shall be installed Bury depth shall be a minimum of three feet

(Septic/Sewer is not a part of this project):

SEWER SERVICE LINE

Stub out

7 | P a g e

Place cap that is identified in “Double Cleanouts” Part C Piping and fittings conform to ASTM D3034 as indicated:

Pipe Class: Schedule 40 Solvent weld joints conforming to ASTM D2855.

4‐inch nominal diameter unless otherwise indicated.

Each length of pipe shall be clearly marked with the following:

a. Manufacturer.

b. Nominal Pipe Size.

c. The PVC Cell Classification.

d. Type PSM PVC Sewer Pipe.

e. ASTM Designation.

f. Pipe Class.

Double Cleanouts:

Schedule 40 PVC DWV pipe and fittings conforming to ASTM D2665.

Supply 4‐inch slip on cap or threaded female adapter with 4‐inch diameter threaded slotted white flush plug with threaded brass insert as manufactured by Sioux Chief or approved equal.

Install a 4‐inch sewer wye in the sewer service line and connect risers of the same material from the wye to the ground surface.

a. Attach a schedule 40 PVC DWV slip‐on cap or female adapter to the end of the riser.

b. Install cleanout so cap is flush with finished grade.

Pipe installation General

a. Bed pipe according to the drawing. If imported material is required to safely bed the pipe, the contractor shall immediately halt construction and consult with the project engineer.

b. If trenching occurs, the trench shall be 4 to 6 inches wider than the pipe diameter

c. Initial backfill shall be free of clods, stones, frozen material, and organic material.

The contractor shall ensure pipe cannot move and is compacted adequately by hand in lifts of 6 inches.

d. Backfilling shall occur in 12 inch lifts. The lifts shall be compacted to 90% maximum dry density.

Bury depth

a. If minimum bury depth of three feet cannot be met, the contractor shall install 2” rigid polystyrene EPS located over centerline of pipe and is 18” wide, at a minimum.

b. All pipe shall be a minimum of 2 feet below grade

Utility Conflicts

a. Sewer shall be located under water lines

b. Pipe shall have joints equidistant from the point of crossing

c. A minimum spacing of 30 inches horizontal and 12 inches vertical.

d. Exceptions will likely require concrete to create a barrier.

Slopes:

a. Minimum slope for sewer service lines is 1/8‐inch per foot (1%).

b. Maximum slope for sewer service lines is 1/2‐inch per foot (4 %), unless otherwise specified.

8 | P a g e

GENERAL DETAILS

9 | P a g e

TOC
Atch 1 Site Layout
Atch 2 Std RV Drawings