This is a Statement of Work/Specifications for HVAC system replacement at the Federal Bureau of Prisons Federal Prison Camp (FPC) Bryan in Bryan, Texas. The Federal Bureau of Prisons intends to purchase supplies and materials for in-house replacement of two HVAC units located in the ICC Building at 1100 Ursuline Avenue, Project 25Z5AB8. All supplies and materials must be submitted with complete product detail sheets and specifications.
The Material and Supplies Requirements specify two 25-ton single-packaged air conditioning units with gas heat, rated 208/230V/3PH/60HZ with Puron Advance R454B refrigerant. The units must feature direct drive technology with vane axial indoor fan design, cooling operating range from 40°F to 115°F, and IGC solidstate control with on-board diagnostics and LED error code designation. Additional required specifications include corrosive-resistant composite condensate pan per ASHRAE 62 Standard with sloping design, tool-less filter access doors, field convertible vertical to horizontal airflow configuration, scroll compressors with internal line-break overload protection, 24-volt control circuits with resettable circuit breaker protection, low and high pressure switch protection, totally enclosed condenser motors with permanently lubricated bearings, louvered hail guards, hinged access panels, E-coated coils, single point gas/electric/controls connections, full perimeter base rail with rigging adapters and forklift slots, stainless steel gas heat exchanger, and phase monitor protection. Delivery of supplies must occur between 8:00 AM and 2:00 PM, Monday through Friday, excluding federal holidays, with direct shipment to the institution.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
I. REQURIEMENTS
A. Scope of Work
STATEMENT OF WORK/SPECIFICATIONS
REPLACE HVAC SYSTEM ICC BUILDING
FPC BRYAN - PROJECT 25ZSAB8
The Federa l Bureau of Prisons (FBOP), Federal Prison Camp (FPC) Bryan intends to purchase supplies and materials for in-house HVAC replacement of two HVAC units in the ICC Building, located at 1100 Ursuline Ave .
Bryan, TX 77803
All supplies and materials must be submitted with full product detail sheets and specifi ca tions .
B. Material and Supplies Requ irements
1. TWO 25 Ton Single-Packaged Air Conditioning with Gas Heat Unit 208/230V /3PH/60HZ Puron Advance R454B Refrigerant Direct Drive Technology Indoor Fan System with Vane Axia l Design Coo ling Operating Range up to 115 F and down to 40F IGC Solidstate Control for On-Board Diagnostics with LED Error Code Designation & Burner Control Logic Corrosive-Resistant Composite Condensate Pan in Accordance with ASH RAE 62 Standard, Sloping Design
Tool-less Filter Access Doors Fie ld Convertible from Vertical to Horizontal Airflow Configuration
Scroll Compressors with Internal Line-Break Overload 24-volt Control Circuit Protected with Resettable Ci rcuit Breaker Low Pressure and High Pressure Switch Protection Tota lly Enclosed Condenser Motors with Permanently Lubricated Bearings Louvered Hail Guards
Hinged Access Panels
E-Coated Coils Single Point Gas, Electric and Controls Connections Ful l Perimeter Base Rail with Built-in Rigging Adapters and Fork Truck Slots
Stainless Stee l Gas Heat Exchanger Phase Monitor Protection
C. Delivery of Supplies