This document provides details for a federal solicitation to renovate an EHRM training room and administrative support space in Leavenworth, Kansas. Solicitation number 36C77622B0043 was issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas for the Leavenworth EHRM Training Room project numbered 589A6-21-702. The solicitation seeks to renovate the specified training room and administrative office space at the location provided. No further information is included regarding response dates, pricing terms, or other contract details. Attachment 3 to the solicitation contains drawings related to the renovation project requirements.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COST ESTIMATE
MECHANICAL
ELECTRICAL
ARCHITECT
NAGEL Architects + Engineers 13100 watertown plank road, suite 200 Elm Grove, WI 53122 Phone: 262.641.0746
FAX: 888.600.6207
Contact: Kenneth Shane E-mail: ken.shane@nagel.us
DESIGNER LIST AND STAMPS___________________
IMEG Corp.
1600 Baltimore, suite 300 Kansas City, MO 64108 Phone: 314.282.8127 Contact: Kate Dennis E-mail: Kate.M.Dennis@imegcorp.com
IMEG
1600 Baltimore, suite 300 Kansas City, MO 64108 Phone: 816.842.8437 Contact: Phyllip DeLoach E-mail: Phyllip.DeLoach@imegcorp.com
OCMI
6110 Executive Blvd, suite 200 Rockville, MD 20852 Phone: 785.393.7009 Contact: Sai Bypanemi E-mail: sbypaneni@ocmi.com
ABATEMENT
The Reese Group 310 E Buffalo St. #106 Milwaukee, WI 53202 Phone: 414-719-1477 Contact: Tina Reese E-mail: treese@the-reese-group.com
STRUCTURAL
Calibre-Engineering 9090 S. Ridgeline Blvd, Suite 105 Highlands Ranch, CO 80129 Phone: 303-730-0434 Contact: Ed Sabia E-mail: esabia@calibre-engineering.com
BLDG 42
BLDG 71 BLDG 88/89
BLDG 122
BLDG 90-A
DWIGHT D. EISENHOWER VAMC
4101 4TH STREET TRAFFICWAY
LEAVENWORTH, KS, 66048
CONTACT:
Trevor Huhn, COR Trevor.Huhn@va.gov 913-682-2000 x2281
MUNCIE RD
S
T H
S T
SHEET # SHEET NAME
08 - INTERIORS - I
I201 INTERIOR ELEVATIONS
I202 INTERIOR ELEVATIONS
09 - EQUIPMENT - Q
Q100 PARTIAL BASEMENT FLOOR PLANS, EQUIPMENT, BLDG 71
Q102 PARTIAL SECOND FLOOR PLANS, EQUIPMENT, BLDG 88/89
Q103 SECOND FLOOR PLANS, EQUIPMENT, BLDG 42 & 122
10 - FIRE PROTECTION - F
FP000 FIRE PROTECTION COVER SHEET
FP100 PARTIAlL BASEMENT PLANS - FIRE PROTECTION - BLDG 71
FP102 PARTIAL SECOND FLOOR PLANS - FIRE PROTECTION - BLDG 88/99
FP103 EXTERIOR VESTIBULE PLANS - FIRE PROTECTION - BLDG 90-A
FP300 FIRE PROTECTION DETAILS
13 - MECHANICAL - M
M000 MECHANICAL COVER SHEET
M001 PARTIAL SUB-BASEMENT FLOOR PLANS - MECHANICAL - BLDG 71
M100 PARTIAL BASEMENT FLOOR PLANS - MECHANICAL - BLDG 71
M102 PARTIAL SECOND FLOOR PLANS - MECHANICAL - BLDG 88/89
M103 EXTERIOR VESTIBULE PLANS - MECHANICAL - BLDG 90-A
M300 MECHANICAL DETAILS
M400 MECHANICAL DIAGRAMS
M500 MECHANICAL SCHEDULES
14 - ELECTRICAL - E
E000 ELECTRICAL COVER SHEET
E100 PARTIAL BASEMENT FLOOR PLANS - ELECTRICAL - BLDG 71
E101 PARTIAL BASEMENT FLOOR PLANS - ELECTRICAL - BLDG 71
E102 PARTIAL SECOND FLOOR PLANS - ELECTRICAL - BLDG 88/89
E103 PARTIAL SECOND FLOOR PLANS - ELECTRICAL - BLDG 88/89
E104 PARTIAL SECOND FLOOR PLANS - ELECTRICAL - BLDG 42 & 122
E105 EXTERIOR VESTIBULE PLANS - ELECTRICAL - BLDG 90-A
E300 ELECTRICAL SCHEDULES & DETAILS
15 - TECHNOLOGY - T
T000 TECHNOLOGY COVER SHEET
T100 PARTIAL BLDG 71 BASEMENT PLANS - TECHNOLOGY
T101 PARTIAL BLDG 88/89 SECOND FLOOR PLANS - TECHNOLOGY
T102 PARTIAL BLDG 42/122 SECOND FLOOR PLANS - TECHNOLOGY
T300 TECHNOLOGY DETAILS. DIAGRAMS AND SCHEDULES
SHEET # SHEET NAME
00 - GENERAL - G
G001 COVER SHEET
G002 ARCHITECTURAL ABBREVIATIONS AND SYMBOLS
G003 BUILDING CODE REVIEW & INFECTION CONTROL (ICRA)
01 - ABATEMENT - H
H100 BASEMENT FLOOR PLAN, HAZARDOUS MATERIALS, BLDG 71
H102 SECOND FLOOR PLAN, HAZARDOUS MATERIALS, BLDG 88/89
02 - STRUCTURAL - S
S001 GENERAL NOTES
S002 GENERAL NOTES
S003 SPECIAL INSPECTIONS
S104 PLAN AND DETAILS
S200 FOUNDATION DETAILS
S500 STEEL DETAILS
07 - ARCHITECTURAL - A
AD100 PARTIAL BASEMENT FLOOR PLANS, DEMOLITION, BLDG 71
AD102 PARTIAL SECOND FLOOR PLANS, DEMOLITION, BLDG 88/89
A001 PARTIAL SUB-BASEMENT FLOOR PLANS, ARCHITECTURAL, BLDG 71
A100 PARTIAL BASEMENT FLOOR PLANS, ARCHITECTURAL BLDG 71
A102 PARTIAL SECOND FLOOR PLANS, ARCHITECTURAL, BLDG 88/89
A103 SECOND FLOOR PLANS, ARCHITECTURAL, BLDG 42 & 122
A105 EXTERIOR VESTIBULE PLANS, ELEVATIONS, BLDG 90-A
A301 EXTERIOR VESTIBULE SECTION 1
A302 EXTERIOR VESTIBULE SECTION 2
A501 DETAILS
A601 SCHEDULES & DETAILS
13100 watertown plank road suite 200 elm grove, wi 53122
DEPARTMENT OF VETERANS AFFAIRS
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
NAGEL A+E PROJECT NUMBER:VA PROJECT NUMBER:
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Consultant:
Nagel Architects + Engineers project number:
Project NumberProject TitleDrawing Title Phase
C :\U se rs
\r ya nb \D oc um en ts
\2
_L ea ve nw or th E
H R
M _R ya n.
bo ur la nd
.r vt
2/ 7/
2:
:5
P
M
EHRM TRAINING AND ADMINISTRATION SPACE SUPPORT
4101 4TH STEET TRAFFICWAY
LEAVENWORTH, KS, 66048
21015589A6-21-702
G001
COVER SHEET
NAME
ADDRESS
CITY, STATE ZIP
POC
EHRM TRAINING AND
ADMINISTRATION SPACE
SUPPORT
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS
589A6-21-702
42, 71, 88/89, 122
12/17/2021 KS AR, RB
FULLY SPRINKLERED
21015
BID DOCUMENTS
SHEET INDEX________________________________________________________________________________
PROJECT SITE MAP____________________________________________________________PROJECT LOCATION MAP______________STATION INFORMATION
PERSPECTIVES__________________________________
N O
R T
H
BLDG 71BLDG 88/89
Revisions: Date:
SCHEMATIC DESIGN 35% SUBMITTAL 8/7/2021
DESIGN DEVELOPMENT 65% SUBMITTAL 9/10/2021
CONSTRUCTION DOCUMENTS 95% SUBMITTAL 10/8/2021
CONSTRUCTION DOCUMENTS 100% SUBMITTAL 10/28/2021
BID DOCUMENTS SUBMITTAL 12/17/2021
ryanb Calibre -stamp ryanb
IMEG STAMP
ryanb
IMEG STAMP
NORTH ARROW
ELEVATION REFERENCE
SYMBOL
ELEVATION REFERENCE
SYMBOL
SECTION REFERENCE
SYMBOL
ENLARGED AREA
REFERENCE SYMBOL
DOOR TAG
REVISION TAG
WINDOW TAG
ROOM TAG
COLUMN REFERENCE
SYMBOL
Name Elevation
A101
A101
SIM
A101
SIM
NORTH
PARTITION TAG
A36C G11C
ARCHITECTURAL SYMBOLS LEGEND___
ROOM NAME
111A
EQUIPMENT TAGX####
A101
SIM DETAIL REFERENCE
SYMBOL
AD101.1 MATCH LINE
AREA NOT IN CONTRACT
A ALIGN FINISH SURFACES FLUSH
WALL TAG1iEX1
FINISH WOOD
CONCRETE MASONRY UNIT (CMU)
CONCRETE, CAST-IN-PLACE
CONCRETE, PRE-CAST
FILL - PER NOTE
INTERMITTENT BLOCKING
CONT. ROUGH FRAMING
STEEL
EARTH
RIGID INSULATION
BATT INSULATION
GYPSUM BOARD
GLASS
LARGE SCALE
SECTIONS
BRICK
PLYWOOD
MATERIAL
ARCHITECTURAL MATERIAL LEGEND__
EARTH, COMPACT
ALUMINUM
FILL, POROUS
13100 watertown plank road suite 200 elm grove, wi 53122
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Nagel Architects + Engineers project number:
C :\U se rs
\r ya nb \D oc um en ts
\2
_L ea ve nw or th E
H R
M _R ya n.
bo ur la nd
.r vt
2/ 7/
2:
:5
P
M
G002
ARCHITECTURAL ABBREVIATIONS
AND SYMBOLSNAME
ADDRESS
CITY, STATE ZIP
POC
EHRM TRAINING AND
ADMINISTRATION SPACE
SUPPORT
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS
589A6-21-702
42, 71, 88/89, 122
12/17/2021 KS AR, RB
BID DOCUMENTS
FULLY SPRINKLERED
21015
SYS SYSTEM
T
T&G TONGUE & GROOVE
T/O(T.O.) TOP OF
TB TOWEL BAR
TC TERRA COTTA
TEL TELEPHONE
TEMP TEMPORARY
THK THICKNESS
THR THRESHOLD
THRU THROUGH
TOL TOLERANCE
TOT TOTAL
TOW(T.O.W.) TOP OF WALL
TPD TOILET PAPER DISPENSER
TR TREAD
TRM TRANSOM
TV TELEVISION
TYP TYPICAL
TZ TERRAZZO
U
UC UNDERCUT
UNFIN UNFINISHED
UNO(U.N.O) UNLESS NOTED OTHERWISE
UR URINAL
UTIL UTILITY
V
VA VETERAN'S AFFAIRS, DEPARTMENT OF
VAR VARNISH
VCT VINYL COMPOSITION TILE
VEH VEHICLE
VERT VERTICAL
VF VINYL FABRIC
VG VERTICAL GRAIN
VIN VINYL
VJ V-JOINT(ED)
VNR VENEER
VT VINYL TILE
W
W WEST
W WIDTH, WIDE
W/ WITH
W/D WASHER & DRYER
W/O WITHOUT
WB WOOD BASE
WC WATER CLOSET
WD WOOD
WDW WINDOW
WG WIRED GLASS
WH WALL HUNG
WHS WHEEL STOP
WI WROUGHT IRON
WM WIRE MESH
WP WATER PROOFING
WPT WORKING POINT
WR WATER REPELLANT
WSCT WAINSCOT
WT WEIGHT
WTW WALL-TO-WALL
WWF WELDED WIRE FABRIC
WWM WELDED WIRE MESH
PWD PLYWOOD
Q
QRT QUARRY TILE
QT QUARTZ TILE
QTY QUANTITY
R
RA RETURN AIR
RAD RADIUS
RB RUBBER BASE
RBT RABBET, REBATE
RBT RUBBER TILE
RC RESILIENT CHANNEL
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RE REINFORCE(D)(ING)
REF REFERENCE
REFR REFRIGERATOR
REG REGISTER
REINF REINFORCED
REM REMOVE
REQ'D REQUIRED
RESIL RESILIENT
REV REVISION
RFG ROOFING
RFH ROOF HATCH
RFL REFLECT(ED)(IVE)(OR)
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
RS RISER
RT RETURN
RWC RAINWATER CONDUCTOR
S
S SOUTH
SC SOLID CORE
SCHED SCHEDULE
SCN SCREEN
SD STORM DRAIN
SEC SECTION
SF SQUARE FEET
SFG SAFETY GLASS
SH SHELF, SHELVING
SHR SHEER
SHT SHEET
SHTG SHEATHING
SHV SHELVES
SI SQUARE INCHES
SIM SIMILAR
SL SLEEVE
SNT SEALANT
SP STANDPIPE
SP SOUNDPROOF
SPEC SPECIFICATION
SPK SPEAKER
SPKLR SPRINKLER
SPL SPECIAL
SQ SQUARE
SS STAINLESS STEEL
SSEW SANITARY SEWER
STA STATION
STC SOUND TRANSMISSION CLAS
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUS SUSPENDED
SUSP SUSPENSION
SYM SYMMETRICAL, SYMMETRY
SYN SYNTHETIC
LW LIGHTWEIGHT
M
M.O. MASONRY OPENING
M.R. MOISTURE RESISTANT
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MBR MEMBER
MC MEDICINE CABINET
MECH MECHANIC(AL)
MED MEDIUM
MEMB MEMBRANE
MET METAL
MEZZ MEZZANINE
MFR MANUFACTURER
MH MANHOLE
MIN MINUTE, MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MLD MO(U)LDING
MOD MODULAR
MOV MOVABLE
MT MOUNT(ED)(ING)
MULL MULLION
MWK MILLWORK
N
N NORTH
N/A NOT APPLICABLE
NAT NATURAL
NI NICKEL
NIC NOT IN CONTRACT
NO. NUMBER
NOM NOMINAL
NR NOISE REDUCTION
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED CONTRACTOR
INSTALLED
OPNG OPENING
OPP OPPOSITE
OPPHD OPPOSITE HAND
OVHD OVERHEAD
OWJ OPEN-WEB JOIST
P
PAR PARALLEL
PB PANIC BAR
PBD PARTICLE BOARD
PCF POUNDS PER CUBIC FOOT
PED PEDESTAL
PERF PERFORATED
PERIM PERIMETER
PERM PERMANENT
PERP PERPENDICULAR
PFN PREFINISHED
PG PLATE GLASS
PKG PARKING
PL PROPERTY LINE
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLF POUNDS PER LINEAR FOOT
PNL PANEL
PR PAIR
PRCST PRECAST
PREFAB PREFABRICATED
PRELIM PRELIMINARY
PRF PREFORMED
PROJ PROJECT
PRT PROPERTY
PSC PRESTRESSED CONCRETE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT
PTC POST-TENSIONED CONCRETE
PTD PAPER TOWEL DISPENSER
PTN PARTITION
PTR PAPER TOWEL RECEPTACLE
FUT FUTURE
G
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACT(OR)
GCMU GLAZED CONC. MASONRY UNITS
GEN GENERAL
GF GROUND FACE
GKT GASKET(ED)
GL GLASS
GLU LAM GLUE LAMINATED
GOVT GOVERNMENT
GP GALVANIZED PIPE
GPL GYPSUM LATH
GPPL GYPSUM PLASTER
GPT GYPSUM TILE
GRN GRANITE
GS(S) GALVANIZED STEEL (SHEET)
GST GLAZED STRUCTURAL TILE
GT GROUT
GWB GYPSUM WALL BOARD
GYP GYPSUM
H
HB HOSE BIBB
HBD HARDBOARD
HC HANDICAPPED
HDR HEADER
HDWD HARDWOOD
HDWR HARDWARE
HGT HEIGHT
HJT HEAD JOINT
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR
HTG HEATING
HTR HEATER
HVAC HEAT, VENTILATION, & AIR CONDITIONING
HWH HOT WATER HEATER
I
ID INSIDE DIAMETER
IN INCH
INC INCLUDING
INFECTION
CONTROL RISK
ASSESSMENT
ICRA
INSUL INSULATE(D)(ION)
INT INTERIOR
INV INVERT
J
JC JANITOR'S CLOSET
JOINT JT
K
KIT KITCHEN
KO KNOCKOUT
KP KICK PLATE
L
LAB LABORATORY
LAD LADDER
LAV LAVATORY
LB POUND
LB LAG BOLT
LBL LABEL
LH LEFT HAND
LL LIVE LOAD
LMS LIMESTONE
LP LIGHT PROOF
LPT LOW POINT
LT LIGHT
LTG LIGHTING
LTL LINTEL
LVR LOUVER
D
D DRAIN
DA DOUBLE ACTING
DEG DEGREE
DEMO DEMOLISH, DEMOLITION
DEP DEPRESSED
DEPT DEPARTMENT
DF DRINKING FOUNTAIN
DH DOUBLE HUNG
DIA DIAMETER
DIM DIMENSION
DL DEAD LOAD
DMT DEMOUNTABLE
DN DOWN
DP DAMP PROOFING
DPR DAMPER
DR DOOR
DRW DRYWALL
DS DOWNSPOUT
DT DRAIN TILE
DTL DETAIL
DW DUMBWAITER
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWR DRAWER
E
E EAST
EA. EACH
EF EXHAUST FAN
EIFS EXTERIOR INSULATION & FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSE
EP ELECTRICAL PANELBOARD
EQ EQUAL
EQUIP EQUIPMENT
ESC ESCALATOR
ESMT EASEMENT
EST ESTIMATE
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
F
F/O FACE OF
FAS FASTEN(ER)
FBD FIBERBOARD
FBO FURNISHED BY OTHERS
FD FLOOR DRAIN
FDN FIRE DEPARTMENT
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FACTORY FINISH
FG FIBERGLASS
FIN FINISH(ED)
FL FLUSH
FLR FLOOR
FN FENCE
FOB FACE OF BRICK
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FPL FIREPLACE
FR FRAME(D)(ING)
FRA FRESH AIR
FRC FIRE-RESISTANT COATING
FRT FIRE-RETARDANT
FS FULL SIZE
FT FOOT
FTG FOOTING
FUR FURRED(ING)
FURN FURNITURE
A
A/C AIR CONDITIONING
AB ANCHOR BOLT
ABV ABOVE
AC ACOUSTICAL
ACC ACCESS
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADDL ADDITIONAL
ADH ADHESIVE
ADJ ADJUSTABLE, ADJACENT
AFF(A.F.F.) ABOVE FINISH FLOOR
AGG AGGREGATE
ALT ALTERNATE
ANC ANCHOR, ANCHORAGE
ANOD ANODIZED
AP ACCESS PANEL
APX APPROXIMATE
ARCH ARCHITECT(URAL)
ASB ASBESTOS
ASC ABOVE SUSPENDED CEILING
AUTO AUTOMATIC
B
B/O(B.O.) BOTTOM OF
BD BOARD
BELOW BEL
BET BETWEEN
BITUM BITUMINOUS
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BRG BEARING
BRK BRICK
BS BOTH SIDES
BSMT BASEMENT
BUR BUILT-UP ROOFING
BVL BEVELED
BW BOTH WAYS
C
C-C CENTER TO CENTER
CAB CABINET
CALC CALCULATION
CB CATCH BASIN
CEM CEMENT
CFL COUNTER FLASH(ING)
CFT CUBIC FOOT
CHAM CHAMFER
CI CAST IRON
CIP CAST-IN-PLACE CONCRETE
CIR CIRCLE
CIRC CIRCUMFERENCE
CJ CONTROL JOINT
CK CAULK(ING)
CL CENTER LINE
CLG CEILING
CLR CLEAR
CLS CLOSURE
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
COMB COMBINATION
COMPO COMPOSITION
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACT
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CORR CORRIDOR
CPT CARPET
CRS COURSE(S)
CS COUNTERSINK
CSMT CASEMENT
CST CAST STONE
CT CERAMIC TILE
CYD CUBIC YARD
ARCHITECTURAL ABBREVIATIONS____________________________________________________________________________________________________________________________
Revisions: Date:
SCHEMATIC DESIGN 35% SUBMITTAL 8/7/2021
DESIGN DEVELOPMENT 65% SUBMITTAL 9/10/2021
CONSTRUCTION DOCUMENTS 95% SUBMITTAL 10/8/2021
CONSTRUCTION DOCUMENTS 100% SUBMITTAL 10/28/2021
BID DOCUMENTS SUBMITTAL 12/17/2021
281 SF
ANTE-CONFERENCE
ROOM
MEDICAL
MEDIA OI&T
25B
BATHROOM
CONFERENCE
ROOM
25A
PATH A
MAX OCCUPANCY 49 PER
IBC 2015 & 44 PER NFPA
CONFERENCE
DIR.
B222
NOTES - INFECTION CONTROL
1. THE INTENT OF INFECTION CONTROL ISOLATION IS TO PROTECT
PATIENTS IN THE HOSPITAL WHICH HAVE LOW IMMUNE LEVELS.
THEREFORE, CONSTRUCTION OPERATIONS NEED TO BE
DIRECTED TO CONTAIN DUST AND PARTICULATE MATTER TO THE
CONSTRUCTION AREA. CONSTRUCTION AREA PERIMETER SHALL
BE SEALED COMPLETELY WITH MIN 4 MIL POLY AND DUCT TAPE
DURING CLASS II, III, OR IV OPERATIONS.
2. PROVIDE TRIATEK ISOLATION MONITORS OR VA APPROVED
EQUAL DURING CLASS III OR CLASS IV CONSTRUCTION
OPERATIONS. EACH AREA TO BE UNDER NEGATIVE PRESSURE
(0.02"WC) DURING THESE OPERATIONS. MONITOR TO MEASURE
PRESSURE DIFFERENTIAL BETWEEN CONSTRUCTION AREA AND
ADJACENT CORRIDOR OR ROOM AS DIRECTED BY VA.
3. AS CONSTRUCTION PROGRESSES, FROM TYPE D TO TYPE C AND
THEREON, PROVIDE A REQUEST VIA "INFECTION CONTROL
CONSTRUCTION PERMIT" TO THE VA INFECTION CONTROL NURSE.
UPON AUTHORIZATION, PROCEED TO NEXT TYPE OF
CONSTRUCTION. PROVIDE AT LEAST 10 DAYS NOTICE FOR EACH
PERMIT.
4. WHERE BARRIER SEPARATES CONSTRUCTION FROM OCCUPIED
SPACE, CONSTRUCT IC (INFECTION CONTROL) CONSTRUCTION
BARRIER FROM FLOOR THRU SUSPENDED CEILINGS TO
DECK/FLOOR ABOVE. ALL IC BARRIERS TO BE CONSTRUCTED AS 1
HOUR FIRE AND SMOKE RATED BARRIERS. EXCEPTION - AT
EXISTING 1 HOUR RATED LATH AND PLASTER CEILINGS
CONSTRUCT IC BARRIER FROM FLOOR TO CEILING ABOVE. SEE
BARRIER DETAILS THIS SHEET.
5. CONTRACTOR SHALL PROVIDE NEW ACCESS DOORS AND
PROXIMITY CARD READERS AT ALL IC BARRIERS. IC BARRIERS
SHALL BE INSTALLED AND REMOVED ONLY OUTSIDE OF NORMAL
HOURS OF OPERATION FOR ADJACENT AREAS.
6. WHEN REQUIRED BY IC CONSTRUCTION CLASS, PROVIDE
BALANCING DAMPERS IN THE MAIN SUPPLY AND EXHAUST DUCT
WORK SERVING CONSTRUCTION ZONE. TEMPORARILY BALANCE
AIR FLOW TO PROVIDE NEGATIVE AIR FLOW IN CONSTRUCTION
ZONE AT ALL TIMES AS INDICATED BELOW. DAMPERS TO REMAIN
IN DUCT AFTER CONSTRUCTION IS COMPLETE AND IS TO BE
SECURED IN FINAL BALANCING POSITION PRIOR TO TURNING
SYSTEM OVER FOR OCCUPANCY.
7. THE CONTRACTOR SHALL PROVIDE ENOUGH NEGATIVE AIR
MACHINES TO COMPLETELY EXCHANGE THE REGULATED AREA
AIR VOLUME (4) FOUR ACTUAL TIMES PER HOUR. THE
COMPETENT PERSON SHALL DETERMINE THE NUMBER OF UNITS
NEEDED FOR EACH REGULATED AREA BY DIVIDING THE CUBIC
FEET IN THE REGULATED AREA BY (15) FIFTEEN AND THEN
DIVIDING THAT RESULT BY THE ACTUAL CUBIC FEET PER MINUTE
(CFM) FOR EACH UNIT TO DETERMINE THE NUMBER OF UNITS
NEEDED TO EFFECT (4) FOUR AIR CHANGES PER HOUR. PROVIDE
A STANDBY UNIT IN THE EVENT OF MACHINE FAILURE AND/OR
EMERGENCY IN AN ADJACENT AREA.
8. ALL CONSTRUCTION DEBRIS, WASTE, AND TRANSPORTATION OF
DEMOLITION ITEMS SHALL BE CONVEYED IN A COVERED
DUMPSTER CONTAINER SUCH THAT NO DEBRIS/ITEMS ARE
VISIBLE.
PATIENT RISK
GROUP
LOW RISK
GROUP
CONSTRUCTION TYPE
MEDIUM RISK
GROUP
HIGH RISK
GROUP
HIGHEST RISK
GROUP
TYPE A TYPE B TYPE C TYPE D
I
I
I
II III/IV
II
II
II II
III/IV
III/IV
III
III/IV
IV
IV
IV
INFECTION CONTROL CONSTRUCTION RISK CLASS
CHART
SEE INFECTION CONTROL SPECIFICATION FOR DETAILED INFORMATION
REGARDING CONSTRUCTION TYPE DEFINITIONS AND INFECTION
CONTROL PRECAUTIONS REQUIRED BY EACH CONSTRUCTION RISK
CLASS.
LEGEND - INFECTION CONTROL
CONSTRUCTION BARRIER; TYPE AS REQUIRED
BY INFECTION CONTROL RISK CLASS.
VIDEO
CONFERENCE
ROOM NUR
RESTROOM
NUR
202A
RESTROOM
NUR
CLOSET NUR
202B
CLOSET NUR
203A
ICRA CONSTRUCTION
BARRIER
MULTI-PURPOSE
BH
PSYCHOL. BH
229B
STORAGE
CLOSET
232A
STAIRS
STR-122-3
BUILDING EXIT
EXIT ACCESS CORRIDOR
LEGEND - LIFE SAFETY PLAN
EXIT ACCESS TRAVEL DISTANCE
SCOPE AREA
FIRE EXTINGUISHER
13100 watertown plank road suite 200 elm grove, wi 53122
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Nagel Architects + Engineers project number:
C :\U se rs
\r ya nb \D oc um en ts
\2
_L ea ve nw or th E
H R
M _R ya n.
bo ur la nd
.r vt
2/ 7/
2:
:0
P
M
G003
BUILDING CODE REVIEW &
INFECTION CONTROL (ICRA)NAME
ADDRESS
CITY, STATE ZIP
POC
EHRM TRAINING AND
ADMINISTRATION SPACE
SUPPORT
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS
589A6-21-702
42, 71, 88/89, 122
12/17/2021 KS AR, RB
BID DOCUMENTS
FULLY SPRINKLERED
21015
1/8" = 1'-0"
ICRA FLOOR PLAN, BLDG 71
1/8" = 1'-0"
ICRA FLOOR PLAN, BLDG 88/89
1/4" = 1'-0"
ICRA FLOOR PLAN, BLDG 42
1/8" = 1'-0"
ICRA FLOOR PLAN, BLDG 122
BUILDING CODE REVIEW
IBC CODE SECTION REQUIRED PROVIDED NFPA 101 SECTION REQUIRED PROVIDED
OCCUPANCY OR USE CLASSIFICATION
Single I-2 I-2 CHAPTER 6.1 HEALTHCARE HEALTHCARE Accessory Occupancy [508.4] N/A N/A CHAPTER 6.1.14 N/A N/A Incidental Uses [Table 509] N/A N/A CHAPTER 6.2 N/A N/A
SPECIAL DETAIL REQUIREMENTS PER OCCUPANCY
Special Applications [Ch 4] N/A N/A PER CHAPTER, 11-43 N/A N/A Occupancy Separations Needed? [Table 508.4] N/A N/A High Hazard Class [Section 414] N/A N/A
TYPE OF CONSTRUCTION & LIMITS [TABLE 503]
Construction Class TYPE 2A TYPE 2A NFPA 220 TYPE 2, 111 TYPE 2, 111 Allowable Area 45,000 sf 3,194 sf Area Increase: Sprinkler N/A N/A N/A N/A N/A Area Increase; Frontage N/A N/A N/A N/A N/A Total Area w/ increases N/A N/A N/A N/A N/A Allowable Height 85 N/A N/A N/A N/A Height Modifications N/A N/A N/A N/A N/A Allowable # of Stories 5 N/A N/A N/A N/A
POSITIONING ON PROPERTY [TABLE 602]
Distance to property lines (N, E, S, W) N/A N/A N/A N/A N/A Distance to other buildings N/A N/A N/A N/A N/A Distance to same building N/A N/A N/A N/A N/A Allowable Exterior Wall Openings [705] N/A N/A N/A N/A N/A
FIRE SUPPRESSION SYSTEMS
Sprinkler Requirement NFPA 13 NFPA 13 N/A Alarm & Detection System Requirement NFPA 72 NFPA 72 N/A Monitoring Services Standpipe systems Portable fire extinguishers NFPA 10 SEE G003 NFPA 10 Smoke control systems
MEANS OF EGRESS PARAMETERS
Occupant Load [Table 1004.1.2] - BUSINESS USE 49 49 [Table 7.3.1.2] 44 44 Required Exit Capacities 1 1 # of exits required [1006.2.2.1] 1 1 Exit width 36 inches SEE PROVIDED EGRESS CHART G003 CHAPTER 7.3.4 36 inches 36 inches Exit discharge N/A SEE PROVIDED EGRESS CHART G003 CHAPTER 7.7 N/A N/A Door Hardware Requirements AS REQ'D CHAPTER 7.2 Misc & Special Requirements N/A PER CHAPTER, 11-43 N/A N/A Stair Width N/A N/A CHAPTER 7.2.2 N/A N/A Common path of travel 100 ft SEE COMMON PATH CHART SHEET
G003
PER CHAPTER, 11-43 N/A N/A
Travel distance to Exits 75 ft SEE TRAVEL DISTANCE CHART
SHEET G003
PER CHAPTER, 11-43 N/A N/A
Stair enclosure N/A N/A CHAPTER 7.2.2.5 N/A N/A Vertical openings N/A N/A Accessible means of egress 1 1 CHAPTER 7.5.4 1 1 Emergency lightning N/A N/A CHAPTER 7.8-9 N/A N/A Equipment platform [505] N/A N/A Mezzanine w/o sprinkler N/A N/A CHAPTER 8.6.10 N/A N/A
OTHER ARCHITECTURAL ELEMENTS
Roof requirements N/A N/A -Access N/A N/A CHAPTER 7.2.1.5.9 N/A N/A -Rails N/A N/A
FIRE PERFORMANCE REQUIREMENTS [TABLE 601] NFPA 220 [Table 4.1.1] N/A N/A Columns N/A N/A Floor N/A N/A Roof N/A N/A Roof Covering N/A N/A Exterior Walls N/A N/A Interior Bearing Walls N/A N/A Fire Walls N/A N/A Opening Protectives N/A N/A [Table 8.3.3.2.2] N/A N/A Other partitions N/A N/A Corridors [1020.1] N/A N/A PER CHAPTER, 11-43 N/A N/A Exit passageways N/A N/A Vertical exit enclosures N/A N/A Vertical shafts N/A N/A Penthouse Walls N/A N/A Penthouse Roof N/A N/A Storage Rooms N/A N/A Occupancy separations N/A N/A [Table 6.1.14.4.1] N/A N/A Hazardous areas N/A N/A CHAPTER 6.2 N/A N/A Accessible means of egress [1009.1.2] 1 1 OR 2 other N/A N/A
SMOKE COMPARTMENT N/A N/A
ATTIC REQUIREMENTS N/A N/A
-Access N/A N/A -Smoke separations N/A N/A
CONSTRUCTION MATERIALS - FINISHES
Exit Enclosures & Passageways [Table 803.11] Corridors Rooms & Enclosed spaces
ENERGY EFFICIENCY REQUIREMENTS
Energy Conservation:
Insulation Above Deck N/A N/A N/A N/A N/A Walls Above Grade, Wood Framed N/A N/A N/A N/A N/A Walls Below Grade N/A N/A N/A N/A N/A Floors, Mass N/A N/A N/A N/A N/A Slab-on-grade Floors, Heated N/A N/A N/A N/A N/A Opaque Doors N/A N/A N/A N/A N/A Vertical Fenestration, Fixed N/A N/A N/A N/A N/A Vertical Fenestration, Operable N/A N/A N/A N/A N/A Vertical Fenestration, Entrance Doors N/A N/A N/A N/A N/A Skylights N/A N/A N/A N/A N/A
MEP REQUIREMENTS
Lighting NATURAL: 8% OF FLOOR SERVED -OR-
ARTIFICIAL: 10 FOOT CANDLES OVER AREA AT 30"
AFF
AS REQ'D N/A N/A N/A
Water Closets N/A N/A N/A N/A N/A Lavatories N/A N/A N/A N/A N/A Bathtubs/Showers N/A N/A N/A N/A N/A Drinking Fountains N/A N/A N/A N/A N/A Other (mop basin) N/A N/A N/A N/A N/A
EXIT DISTANCE
PATH A
70'-6"
Revisions: Date:
SCHEMATIC DESIGN 35% SUBMITTAL 8/7/2021
DESIGN DEVELOPMENT 65% SUBMITTAL 9/10/2021
CONSTRUCTION DOCUMENTS 95% SUBMITTAL 10/8/2021
BID DOCUMENTS SUBMITTAL 12/17/2021
MEDICAL
MEDIA OI&T
25A
BATHROOM
MEDICAL
MEDIA OI&T
25B
LEGEND - HAZARDOUS MATERIALS
ACM CEILING TILE ADHESIVE
BEIGE LEAD-CONTAINING PAINT ON PLASTER WALL
A. ALL WORK UNDER THIS CONTRACT SHALL BE DONE IN STRICT
ACCORDANCE WITH ALL APPLICABLE GENERAL STATE AND
LOCAL REGULATIONS, STANDARDS AND CODES GOVERNING
ASBESTOS ABATEMENT, LEAD BASED PAINT WORK PRACTICES,
AND ANY OTHER TRADE WORK DONE IN CONJUNCTION WITH
THE ASBESTOS ABATEMENT.
B. CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO
AVOID CREATION OF LEAD FUMES, INCLUDING THE USE OF LOW-
TEMPERATURE DEMOLITION METHODS FOR EXISTING DOORS
AND WINDOWS.
C. CONTRACTOR SHALL ISOLATE HVAC SYSTEMS IN AREA OF
ABATEMENT FROM ALL OTHER AREAS OF BUILDING.
GENERAL NOTES - HAZARDOUS MATERIAL
LEAD IN PAINT
A. A TOTAL OF FIVE (5) PAINT CHIP SAMPLES OF SUSPECT LEAD
BASED PAINT (LBP) FROM THE WALLS AND CEILINGS OF THE
AREAS DESIGNATED FOR RENOVATIONS IN THE CONFERENCE
ROOMS LOCATED IN THE BASEMENT OF BUILDING 71 AND ON
THE 2ND FLOOR OF BUILDING 88/89.
B. ACCORDING TO THE LEAD IN PAINT RESULTS OF THE COATED
SURFACES EVALUATED, ONE SUSPECT LBP CONTAINIG
MATERIAL HAD LEAD CONCENTRATIONS REPORTED ABOVE THE
FEDERAL THRESHAOLD OF MORE THAN 1.0 MILLIGRAMS PER
SQUARE CENTIMETERS (MG/CM2 , 5,000 PARTS PER MILLION (ppm)
OR 0.5 PERCENT (%) BY WEIGHT OF LEAD IN PAINT AS
ESTABLISHED BY THE UNITED STATES ENVIRONMENTAL
PROTECTION AGENCY (USEPA), AND INCLUDED THE FOLLOWING:
• B222-PC-01/GREEN PLASTER WALL - A GREEN PLASTER
BASE LAYER ON WALLS AND COLUMNS ABOVE THE DROP
CEILING IN BUILDING 88/89, ROOM B222.
THREE OF THE FOUR REMAINING PAINT CHIP SAMPLES
COLLECTED WERE FOUND TO BE LEAD-CONTAINING PAINT
BECAUSE LEAD CONCENTRATIONS WERE REPORTED ABOVE
THE LABORATORY’S LIMIT OF DETECTION (LOD) AND INCLUDED
THE FOLLOWING:
• B222-PC-02/BEIGE PLASTER CEILING BEAMS – MIDDLE
CEILING BEAM ABOVE DROP CEILING IN BUILDING 88/89,
ROOM B222.
• B222-PC-03/TAN PLASTER WALLS – SOUTH WALL, TOP
LAYER, BELOW DROP CEILING. ALSO, ONCOLUMNS.
• 25-PC-01/BEIGE PLASTER WALL – PLASTER WALL
BETWEEN 25 AND 25A, ABOVE THE DROP CEILING
C. OSHA REGULATION 29CFR 1626.62 WILL APPPLY FOR ANY
REMOVAL AND/OR PAINT DISTURBING ACTIVITIES CONDUCTED
DURING THIS RENOVATION.
D. IT SHOULD BE NOTED THAT UNDAMAGED LBP/LCP MAY BE
PRESENT ON UNTESTED BUILDING MATERIALS AND THAT
FURTHER TESTING OF THESE SURFACES MAY BE NECESSARY
BASED ON RENOVATION TECHNIQUES AND POTENTIAL LEAD
EXPOSURES. IN ACCORDANCE WITH OSHA REGULATIONS,
SAMPLING RESULTS WILL BE PROVIDED TO THE CONTRACTOR
COMPLETING ACTIVITIES THAT WILL DISTURB ANY PAINT OR
OTHER COATED SURFACES POTENTIALLY CONTAINING LEAD SO
POTENTIAL LEAD EXPOSURE ASSESSMENT CAN BE COMPLETED.
WHERE LEAD IS PRESENT, IT SHOULD BE ASSUMED THAT
WORKERS WILL BE EXPOSED TO LEAD ABOVE THE ACTION
LEVEL AND PERSONAL PROTECTIVE MEASURES SHOULD BE I
MPLEMENTED UNTIL AN EXPOSURE ASSESSMENT IS
COMPLETED I N ACCORDANCE WITH OSHA REGULATION 29 CFR
1926.62.
ASBESTOS CONTAINING MATERIAL
E. AN ASBESTOS CONTAINING MATERIAL ("ACM") IS DEFINED AS A
MATERIAL THAT CONTAINS GREATER THAN (>) 1 PERCENT (%)
ASBESTOS BY LABORATORY PLM ANALYSIS AND/OR EPA POINT
COUNT 400 METHOD.
F. BULK SAMPLES WERE COLLECTED FROM THE SITE BUILDING
AND ANALYZED FOR POLARIZED LIGHT MICROSCOPY (PLM), EPA
METHOD 600/R-93/116. ONE (1) OF THE MATERIALS SAMPLED
WAS FURTHER ANALYZED VIA EPA POINT COUNT 400 METHOD.
G. ONE SAMPLE OF THE FOLLOWING MATERIALS CONTAINING LESS
THAN (<) 1% ASBESTOS WAS VERIFIED IN ACCORDANCE WITH
THE EPA POINT COUNT 400 METHOD:
• 25A-CT1-1-31/2” BLACK CEILING TILE WITH BROWN
ADHESIVE - BROWN ADHESIVE ASSOCIATED WITH A
BLACK CEILING TILE IN THE - CONFERENCE ROOM OF
BUILDING 71 (0.75% -TRACE).
H. NO ACM WAS IDENTIFIED IN THE BUILDING 88/89 CONFERENCE
ROOM.
I. MATERIALS CONTAINING LESS THAN (<) 1% ASBESTOS MAY NOT
BE REGULATED (EITHER THE REMOVAL OR WASTE DISPOSAL.
HOWEVER, AT LEAST PORTIONS OF THE OSHA ASBESTOS IN
CONSTRUCTION STANDARD (1926.1101) STILL APPLY WHEN
THESE MATERIALS ARE DISTURBED.
J. ALL WORK UNDER THIS CONTRACT SHALL BE DONE IN STRICT
ACCORDANCE WITH ALL APPLICABLE GENERAL STATE AND
LOCAL REGULATIONS, STANDARDS AND CODES GOVERNING
ASBESTOS ABATEMENT, LEAD BASED PAINT WORK PRACTICES,
AND ANY OTHER TRADE WORK DONE IN CONJUNCTION WITH
THE ASBESTOS ABATEMENT.
GENERAL NOTES - ABATEMENT PLAN
13100 watertown plank road suite 200 elm grove, wi 53122
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Nagel Architects + Engineers project number:
C :\U se rs
\r ya nb \D oc um en ts
\2
_L ea ve nw or th E
H R
M _R ya n.
bo ur la nd
.r vt
2/ 7/
2:
:0
P
M
H100
BASEMENT FLOOR PLAN,
HAZARDOUS MATERIALS, BLDG 71NAME
ADDRESS
CITY, STATE ZIP
POC
EHRM TRAINING AND
ADMINISTRATION SPACE
SUPPORT
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS
589A6-21-702
42, 71, 88/89, 122
12/17/2021 Checker Author
BID DOCUMENTS
FULLY SPRINKLERED
21015
1/4" = 1'-0"
BASEMENT FLOOR PLAN, HAZARDOUS MATERIALS, BLDG 71
KEYNOTES - HAZARDOUS MATERIALS
1. REMOVE ALL BLACK ACOUSTICAL BOARD AND BROWN ADHESIVE FROM ANYWHERE
IN THE ROOM. (WALLS & CEILING)
Revisions: Date:
A. ALL WORK UNDER THIS CONTRACT SHALL BE DONE IN STRICT
ACCORDANCE WITH ALL APPLICABLE GENERAL STATE AND
LOCAL REGULATIONS, STANDARDS AND CODES GOVERNING
ASBESTOS ABATEMENT, LEAD BASED PAINT WORK PRACTICES,
AND ANY OTHER TRADE WORK DONE IN CONJUNCTION WITH
THE ASBESTOS ABATEMENT.
B. CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO
AVOID CREATION OF LEAD FUMES, INCLUDING THE USE OF LOW-
TEMPERATURE DEMOLITION METHODS FOR EXISTING DOORS
AND WINDOWS.
C. CONTRACTOR SHALL ISOLATE HVAC SYSTEMS IN AREA OF
ABATEMENT FROM ALL OTHER AREAS OF BUILDING.
GENERAL NOTES - HAZARDOUS MATERIAL
CONFERENCE
DIR.
B222
MECHANICAL
ROOM
B220
STOR ES
B218
ELEC CL ES
B237E
LEGEND - HAZARDOUS MATERIALS
BEIGE LEAD-CONTAINING PLASTER CEILING BEAMS
GREEN LEAD-BASED PLASTER WALL (BASE LAYER)
TAN LEAD-CONTAINING PLASTER WALL (TOP LAYER)
GREEN LEAD-BASED PLASTER COLUMN (BASE LAYER)
TAN LEAD-CONTAINING PLASTER COLUMN (TOP LAYER)
LEAD IN PAINT
A. A TOTAL OF FIVE (5) PAINT CHIP SAMPLES OF SUSPECT LEAD
BASED PAINT (LBP) FROM THE WALLS AND CEILINGS OF THE
AREAS DESIGNATED FOR RENOVATIONS IN THE CONFERENCE
ROOMS LOCATED IN THE BASEMENT OF BUILDING 71 AND ON
THE 2ND FLOOR OF BUILDING 88/89.
B. ACCORDING TO THE LEAD IN PAINT RESULTS OF THE COATED
SURFACES EVALUATED, ONE SUSPECT LBP CONTAINIG
MATERIAL HAD LEAD CONCENTRATIONS REPORTED ABOVE THE
FEDERAL THRESHAOLD OF MORE THAN 1.0 MILLIGRAMS PER
SQUARE CENTIMETERS (MG/CM2 , 5,000 PARTS PER MILLION (ppm)
OR 0.5 PERCENT (%) BY WEIGHT OF LEAD IN PAINT AS
ESTABLISHED BY THE UNITED STATES ENVIRONMENTAL
PROTECTION AGENCY (USEPA), AND INCLUDED THE FOLLOWING:
• B222-PC-01/GREEN PLASTER WALL - A GREEN PLASTER
BASE LAYER ON WALLS AND COLUMNS ABOVE THE DROP
CEILING IN BUILDING 88/89, ROOM B222.
THREE OF THE FOUR REMAINING PAINT CHIP SAMPLES
COLLECTED WERE FOUND TO BE LEAD-CONTAINING PAINT
BECAUSE LEAD CONCENTRATIONS WERE REPORTED ABOVE
THE LABORATORY’S LIMIT OF DETECTION (LOD) AND INCLUDED
THE FOLLOWING:
• B222-PC-02/BEIGE PLASTER CEILING BEAMS – MIDDLE
CEILING BEAM ABOVE DROP CEILING IN BUILDING 88/89,
ROOM B222.
• B222-PC-03/TAN PLASTER WALLS – SOUTH WALL, TOP
LAYER, BELOW DROP CEILING. ALSO, ONCOLUMNS.
• 25-PC-01/BEIGE PLASTER WALL – PLASTER WALL
BETWEEN 25 AND 25A, ABOVE THE DROP CEILING
C. OSHA REGULATION 29CFR 1626.62 WILL APPPLY FOR ANY
REMOVAL AND/OR PAINT DISTURBING ACTIVITIES CONDUCTED
DURING THIS RENOVATION.
D. IT SHOULD BE NOTED THAT UNDAMAGED LBP/LCP MAY BE
PRESENT ON UNTESTED BUILDING MATERIALS AND THAT
FURTHER TESTING OF THESE SURFACES MAY BE NECESSARY
BASED ON RENOVATION TECHNIQUES AND POTENTIAL LEAD
EXPOSURES. IN ACCORDANCE WITH OSHA REGULATIONS,
SAMPLING RESULTS WILL BE PROVIDED TO THE CONTRACTOR
COMPLETING ACTIVITIES THAT WILL DISTURB ANY PAINT OR
OTHER COATED SURFACES POTENTIALLY CONTAINING LEAD SO
POTENTIAL LEAD EXPOSURE ASSESSMENT CAN BE COMPLETED.
WHERE LEAD IS PRESENT, IT SHOULD BE ASSUMED THAT
WORKERS WILL BE EXPOSED TO LEAD ABOVE THE ACTION
LEVEL AND PERSONAL PROTECTIVE MEASURES SHOULD BE I
MPLEMENTED UNTIL AN EXPOSURE ASSESSMENT IS
COMPLETED I N ACCORDANCE WITH OSHA REGULATION 29 CFR
1926.62.
ASBESTOS CONTAINING MATERIAL
E. AN ASBESTOS CONTAINING MATERIAL ("ACM") IS DEFINED AS A
MATERIAL THAT CONTAINS GREATER THAN (>) 1 PERCENT (%)
ASBESTOS BY LABORATORY PLM ANALYSIS AND/OR EPA POINT
COUNT 400 METHOD.
F. BULK SAMPLES WERE COLLECTED FROM THE SITE BUILDING
AND ANALYZED FOR POLARIZED LIGHT MICROSCOPY (PLM), EPA
METHOD 600/R-93/116. ONE (1) OF THE MATERIALS SAMPLED
WAS FURTHER ANALYZED VIA EPA POINT COUNT 400 METHOD.
G. ONE SAMPLE OF THE FOLLOWING MATERIALS CONTAINING LESS
THAN (<) 1% ASBESTOS WAS VERIFIED IN ACCORDANCE WITH
THE EPA POINT COUNT 400 METHOD:
• 25A-CT1-1-31/2” BLACK CEILING TILE WITH BROWN
ADHESIVE - BROWN ADHESIVE ASSOCIATED WITH A
BLACK CEILING TILE IN THE - CONFERENCE ROOM OF
BUILDING 71 (0.75% -TRACE).
H. NO ACM WAS IDENTIFIED IN THE BUILDING 88/89 CONFERENCE
ROOM.
I. MATERIALS CONTAINING LESS THAN (<) 1% ASBESTOS MAY NOT
BE REGULATED (EITHER THE REMOVAL OR WASTE DISPOSAL.
HOWEVER, AT LEAST PORTIONS OF THE OSHA ASBESTOS IN
CONSTRUCTION STANDARD (1926.1101) STILL APPLY WHEN
THESE MATERIALS ARE DISTURBED.
J. ALL WORK UNDER THIS CONTRACT SHALL BE DONE IN STRICT
ACCORDANCE WITH ALL APPLICABLE GENERAL STATE AND
LOCAL REGULATIONS, STANDARDS AND CODES GOVERNING
ASBESTOS ABATEMENT, LEAD BASED PAINT WORK PRACTICES,
AND ANY OTHER TRADE WORK DONE IN CONJUNCTION WITH
THE ASBESTOS ABATEMENT.
GENERAL NOTES - ABATEMENT PLAN
13100 watertown plank road suite 200 elm grove, wi 53122
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
Nagel Architects + Engineers project number:
C :\U se rs
\r ya nb \D oc um en ts
\2
_L ea ve nw or th E
H R
M _R ya n.
bo ur la nd
.r vt
2/ 7/
2:
:0
P
M
H102
SECOND FLOOR PLAN,
HAZARDOUS MATERIALS, BLDG
88/89
NAME
ADDRESS
CITY, STATE ZIP
POC
EHRM TRAINING AND
ADMINISTRATION SPACE
SUPPORT
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS
589A6-21-702
42, 71, 88/89, 122
12/17/2021 Checker Author
BID DOCUMENTS
FULLY SPRINKLERED
21015
KEYNOTES - HAZARDOUS MATERIALS
1/4" = 1'-0"
SECOND FLOOR PLAN, HAZARDOUS MATERIALS, BLDG 88/89
Revisions: Date:
13100 watertown plank road suite 200 elm grove, wi 53122
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
STRUCTURAL:
Nagel Architects + Engineers project number:
90ACALIBRE ENGINEERING
9090 S. RIDGELINE BLVD, STE 105
HIGHLANDS RANCH, CO 80129 T: (303) 730-0434
THORNTON TOMASETTI, INC.
303 E. 17TH AVE, STE 565
DENVER, CO 80203 T: (303) 876-5700
B
IM
/C
O
O
.0
L e a v e n w o rt h
/T
T
O
.0
L E
A V
E N
W O
R T
H
R
C E
N T
R A
L .r v t
/1
/2
:0
:5
A
M
S001
GENERAL NOTES EHRM TRAINING AND
ADMINISTRATION SPACE
SUPPORT
4104 4TH ST TRAFFICWAY, LEAVENWORTH, KS
589A6-21-702
12/03/2021 JH HL
BID DOCUMENTS
589A6-21-702
GR GENERAL REQUIREMENTS
GR-1 AS USED IN THESE GENERAL NOTES:
"DRAWINGS" MEANS THE LATEST STRUCTURAL DESIGN DRAWINGS, UON.
"SPECIFICATIONS" MEANS THE LATEST PROJECT SPECIFICATIONS, UON.
“CONTRACT DOCUMENTS” IS DEFINED AS THE DESIGN DRAWINGS AND THE SPECIFICATIONS
“SER” IS DEFINED AS THE STRUCTURAL ENGINEER OF RECORD FOR THE STRUCTURE IN ITS FINAL
CONDITION.
“DESIGN PROFESSIONALS” IS DEFINED AS THE OWNER’S ARCHITECT AND SER.
“MEP” INCLUDES, BUT IS NOT LIMITED TO MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION.
“CONTRACTOR” IS DEFINED TO INCLUDE ANY OF THE FOLLOWING: GENERAL CONTRACTOR AND THEIR
SUBCONTRACTORS, CONSTRUCTION MANAGER AND THEIR SUBCONTRACTORS, STRUCTURAL STEEL
FABRICATOR OR STRUCTURAL STEEL ERECTOR.
“BASE BUILDING STRUCTURE” IS DEFINED AS THE STRUCTURAL FRAME DESIGNED BY THORNTON
TOMASETTI.
“STRUCTURE IN ITS FINAL CONDITION” MEANS ALL STRUCTURAL ELEMENTS SHOWN ON THE STRUCTURAL
CONTRACT DOCUMENTS ARE INSTALLED AND COMPLETELY CONNECTED AND INSPECTED WITH NO
OUTSTANDING NON-COMPLIANCE ISSUES.
“DELEGATED DESIGN” MEANS A SCOPE OF WORK THAT MEETS PERFORMANCE CRITERIA ESTABLISHED IN THE CONTRACT DOCUMENTS AND IS TO BE COMPLETED BY THE CONTRACTOR’S LICENSED ENGINEER.
“SERVICE LEVEL” LOADS ARE DEFINED AS NOMINAL OR UNFACTORED LOADS TO BE COMBINED USING
ALLOWABLE STRESS LOAD COMBINATIONS
“STRENGTH LEVEL” LOADS ARE DEFINED AS FACTORED LOADS TO BE COMBINED USING STRENGTH DESIGN
LOAD COMBINATIONS
GR-2 THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF THE STRUCTURAL WORK WITH THE ARCHITECTURAL, CIVIL, MEP CONTRACT DOCUMENTS, AS WELL AS ANY OTHER APPLICABLE TRADES.
GR-3 THE CONTRACTOR IS RESPONSIBLE FOR THE STABILITY OF THE STRUCTURE UNTIL THE CONSTRUCTION OF
THE STRUCTURE REACHES ITS FINAL CONDITION.
GR-4 THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE DESIGN, INSTALLATION, AND REMOVAL OF TEMPORARY BRACING AND CONSTRUCTION SUPPORTS, FOR NEW AND EXISTING STRUCTURES, AS NECESSARY TO COMPLETE THE PROJECT. NO PORTION OF THE PROJECT WHILE UNDER CONSTRUCTION IS INTENDED TO BE STABLE IN THE ABSENCE OF THE CONTRACTOR’S TEMPORARY SUPPORTS AND BRACES. CONTRACTOR SHALL RETAIN A PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE PROJECT IS LOCATED TO DESIGN
TEMPORARY BRACING AND CONSTRUCTION SUPPORTS.
GR-5 LATERAL LOAD RESISTANCE AND STABILITY OF THE STRUCTURE IN ITS FINAL CONDITION IS PROVIDED BY MOMENT FRAMES AND LATERAL STABILITY OF OTHER ELEMENTS IS PROVIDED THROUGH ROOF DECK.
GR-6 THE SPECIFICATIONS ARE AN INTEGRAL PART OF THE CONTRACT DOCUMENTS AND SHALL BE USED IN
CONJUNCTION WITH THE STRUCTURAL DRAWINGS.
GR-7 THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS AND COORDINATE WITH THE STRUCTURAL DRAWINGS, ARCHITECTURAL DRAWINGS, DRAWINGS FROM OTHER CONSULTANTS, PROJECT
SHOP DRAWINGS AND FIELD CONDITIONS.
GR-8 IN CASES OF CONFLICT BETWEEN DRAWINGS AND/OR SPECIFICATIONS AND OTHER DISCIPLINES OR EXISTING CONDITIONS, CONTRACTOR SHALL NOTIFY THE DESIGN PROFESSIONALS AND OBTAIN CLARIFICATION PRIOR
TO BIDDING AND PROCEEDING WITH WORK.
GR-9 APPLY DETAILS, SECTIONS, AND NOTES ON THE DRAWINGS WHERE CONDITIONS ARE SIMILAR TO THOSE
INDICATED BY DETAIL, DETAIL TITLE OR NOTE.
GR-10 ONLY USE DIMENSIONS INDICATED ON THE DRAWINGS. DO NOT SCALE DRAWINGS.
GR-11 ASSUME EQUAL SPACING BETWEEN ESTABLISHED DIMENSIONS, IF NOT INDICATED ON DRAWINGS.
GR-12 CENTERLINES OF COLUMNS AND FOUNDATIONS COINCIDE WITH GRID LINE INTERSECTIONS, UON.
GR-13 CENTERLINES OF GRADE BEAMS AND WALLS COINCIDE WITH CENTERLINES OF FOUNDATIONS, UON.
GR-14 CENTERLINES OF FRAMING MEMBERS COINCIDE WITH COLUMN CENTERLINES, UON.
GR-15 THE CONTRACTOR SHALL PROTECT EXISTING FACILITIES, STRUCTURES AND UTILITIES FROM DAMAGE.
GR-16 THE CONTRACTOR SHALL VERIFY THAT CONSTRUCTION LOADS DO NOT EXCEED THE CAPACITY OF THE
STRUCTURE AT THE TIME THE LOAD IS APPLIED.
GR-17 THE CONTRACTOR SHALL COORDINATE THE BOTTOM OF BASE PLATE ELEVATIONS WITH THE AS-BUILT TOP OF
SUPPORT ELEVATIONS.
GR-18 THE CONTRACTOR SHALL VERIFY ALL OPENING SIZES AND LOCATIONS WITH OTHER DISCIPLINES. THE DRAWINGS DO NOT SHOW ALL OPENINGS REQUIRED. ADDITIONAL OPENINGS, BLOCKOUTS AND SLEEVES MAY BE REQUIRED BY OTHER DISCIPLINES AND SHALL BE CONSTRUCTED USING THE TYPICAL DETAILS AND/OR THE CRITERIA INDICATED ON THE DRAWINGS. OPENINGS REQUIRED BUT NOT SHOWN ON THE STRUCTURAL
DRAWINGS MUST BE APPROVED BY THE SER.
GR-19 ELEVATIONS INDICATED ON STRUCTURAL DRAWINGS ARE BASED ON A PROJECT DATUM INDICATED ON THE
ARCHITECTURAL DRAWINGS.
GR-20 SEE ARCHITECTURAL AND MEP CONTRACT DOCUMENTS FOR ADDITIONAL INFORMATION RELATING TO
THE COORDINATION OF STRUCTURAL COMPONENTS INCLUDING, BUT NOT LIMITED TO:
ARCHITECTURAL:
PLAN DIMENSIONS AND PROJECT DATUM
SITING OF BUILDING GRID LINES WITH RESPECT TO CITY BENCHMARKS
SITE PREPARATION
BACKFILLING MATERIALS AND REQUIREMENTS
PAVING AND SITE ELEMENTS OUTSIDE OF BUILDING ENVELOPE
EXISTING SITE UTILITIES
SLAB EDGE DIMENSIONS
FINISH ELEVATIONS
WATERPROOFING AND DAMP-PROOFING DETAILS
RAMP GEOMETRY, PITS, SLAB SLOPES AND DEPRESSIONS
EMBEDMENTS, INSERTS, BLOCKOUTS, ETC.
EXACT OPENING SIZES FOR PIPES, DUCTS, ETC.
CONCRETE FINISHES AND TOPPING SLABS
CONCRETE CURBS AND HOUSEKEEPING PADS
FIRE RATINGS
MEP:
PIPE AND DUCT SIZES FOR OPENING AND SLEEVE COORDINATION
FLOOR DRAINS
UNDERFLOOR AND PERIMETER DRAINAGE SYSTEMS
EQUIPMENT CURBS
CONDUITS AND EMBEDMENTS IN WALLS AND SLABS
CD CODES AND DESIGN CRITERIA
CD-1 PERFORM ALL CONSTRUCTION IN CONFORMANCE WITH THE BUILDING AND DESIGN CODES REFERENCED WITHIN THESE DOCUMENTS. THE PROJECT DOCUMENTS REFER TO THE FOLLOWING CODES AND STANDARDS, UON:
INTERNATIONAL BUILDING CODE, 2018 EDITION WITH CITY OF LEAVENWORTH, KS CODE OF ORDINANCE
AMENDMENTS
VA PG 18-1, MASTER CONSTRUCTION SPECIFICATIONS
VA PG 18-3, DESIGN AND CONSTRUCTION PROCEDURES
STRUCTURAL CONCRETE:
"BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE"
THE AMERICAN CONCRETE INSTITUTE (ACI 318-14)
STRUCTURAL STEEL:
"SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS”, (AISC 360-16) CONFORMING TO THE PROVISIONS OF LOAD RESISTANCE FACTOR DESIGN, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC-LRFD)
CD-2 LIVE LOADS (SERVICE LEVEL):
ENTRYWAY 100 PSF
ROOFS 20 PSF
CD-3 SUPERIMPOSED DEAD LOADS (SERVICE LEVEL):
ROOF 15 PSF
CD-4 RISK CATEGORY: IV
CD-5 SNOW LOADS (SERVICE LEVEL):
FLAT ROOF SNOW LOAD (Pf): 20.2 PSF GROUND SNOW LOAD (Pg) 20 PSF SNOW EXPOSURE FACTOR (Ce): 1.0 SNOW LOAD IMPORTANCE FACTOR (Is): 1.2 THERMAL FACTOR (Ct): 1.2
SNOW DRIFTING SEE 2/S002
CD-6 WIND LOAD DESIGN DATA (STRENGTH LEVEL):
MAIN WIND FORCE RESISTING SYSTEM
BASIC WIND SPEED, V 123 MPH
EXPOSURE C
INTERNAL PRESSURE COEFFICIENT ± 0.18
COMPONENT AND CLADDING DESIGN PRESSURES a=[3’-0”]
EFFECTIVE WIND AREA= 10 SF WALL= 32.7 PSF WALL END ZONE= 40.2 PSF
ROOF EFFECTIVE WIND AREA = 10 SF
ROOF= 33.0 PSF ROOF EDGE = 55.3 PSF ROOF CORNER= 83.3 PSF
OVERHANG EDGE= 47.5 PSF OVERHANG CORNER= 78.2 PSF
CD-7 SEISMIC LOAD DESIGN DATA (STRENGTH LEVEL):
SEISMIC IMPORTANCE FACTOR (Is) 1.5 Ss 0.092 g S1 0.065 g SDS 0.098 g SD1 0.104 g
SITE CLASS D (ASSUMED)
SEISMIC DESIGN CATEGORY C
LATERAL SYSTEM DESCRIPTION STEEL SYSTEM NOT SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE
SEISMIC RESPONSE COEFFICIENT (Cs) 0.049
RESPONSE MODIFICATION FACTOR (R) 3
ANALYSIS PROCEDURE DESCRIPTION EQUIVALENT LATERAL FORCE
DESIGN BASE SHEAR 530 LB
CD-8 IN CASES WHERE THE CONTRACTOR DETERMINES THAT SUSPENDED OR FLOOR MOUNTED EQUIPMENT LOADS EXIST WHICH EXCEED DESIGN LOADS INDICATED ON CONTRACT DOCUMENTS, CONTRACTOR SHALL SUBMIT LOAD DATA TO DESIGN PROFESSIONALS FOR REVIEW PRIOR TO PROCEEDING WITH WORK.
CD-9 DISTRIBUTE THE MAXIMUM LOAD HUNG FROM ANY STRUCTURAL MEMBER FOR DUCTWORK, PIPING ETC OVER THE MEMBER’S TRIBUTARY AREA IN A WAY THAT THE MEP DESIGN SUPERIMPOSED DEAD LOADS LISTED IN CONTRACT DOCUMENTS ARE NOT EXCEEDED. THE CONTRACTOR SHALL COORDINATE THE LOADS OF ALL TRADES AND PROVIDE ADDITIONAL SUPPORT OR DISTRIBUTION FRAMING AS REQUIRED TO ACHIEVE THE
ALLOWABLE LOAD DISTRIBUTION.
CD-10 SERVICEABILITY
LIVE LOAD DEFLECTION IS LESS THAN L/360
LONG-TERM TOTAL DEFLECTION IS LESS THAN L/240
EXTERIOR EDGE BEAMS HAVE BEEN DESIGNED TO LIMIT LIVE LOAD MIDSPAN VERTICAL DEFLECTION TO 1/360
OF THE SPAN OR 3/8", WHICHEVER IS LESS.
EXTERIOR EDGE BEAMS HAVE BEEN DESIGNED TO LIMIT DEAD PLUS SUPERIMPOSED DEAD LOAD MIDSPAN
VERTICAL DEFLECTION TO 1/240 OF THE SPAN OR 3/8”, WHICHEVER IS LESS.
LATERAL DRIFT DUE TO WIND LOADS IS LESS THAN OR EQUAL TO H/400
CD-11 THERE HAVE BEEN NO LOAD RESTRICTION FACTORS APPLIED TO THE STRUCTURAL DESIGN FOR THE
PURPOSES OF SELECTING FIREPROOFING ASSEMBLIES.
DE DEMOLITION
DE-1 THE CONTRACTOR IS FULLY RESPONSIBLE FOR THE MEANS AND METHODS OF DEMOLITION AND THE INTEGRITY AND STABILITY OF THE EXISTING STRUCTURE DURING DEMOLITION UNTIL THE WORK IS COMPLETED. THE CONTRACTOR SHALL PROVIDE SHORING IN REQUIRED LOCATIONS WHERE EXISTING
CONSTRUCTION TO REMAIN WILL BE AFFECTED BY DEMOLITION. CONTRACTOR SHALL RETAIN A
PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE PROJECT IS LOCATED TO DESIGN SHORING.
DE-2 THE CONTRACTOR IS RESPONSIBLE FOR REPAIRS TO ANY STRUCTURAL ELEMENTS WHICH ARE TO REMAIN AND THAT HAVE BEEN DAMAGED DURING THE DEMOLITION PROCESS TO THE COMPLETE SATISFACTION OF THE OWNER. THE REPAIRS SHALL BE AT NO EXPENSE TO THE OWNER. ALL REPAIR WORK SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE PROJECT IS LOCATED AND
SUBMITTED TO THE SER FOR REVIEW AND APPROVAL PRIOR TO COMMENCING REPAIR WORK.
DE-3 ALL EXISTING FRAMING IS INDICATED FOR REFERENCE ONLY AND IS TO BE FIELD VERIFIED BY THE CONTRACTOR. VERIFY THE EXACT EXTENT OF DEMOLITION AT THE SITE. DETERMINE THE NATURE AND EXTENT OF DEMOLITION THAT WILL BE NECESSARY BY COMPARING THE CONTRACT DOCUMENTS WITH THE EXISTING CONSTRUCTION. IMMEDIATELY NOTIFY THE DESIGN PROFESSIONALS OF ANY INCONSISTENCIES.
DE-4 THE CONTRACTOR SHALL USE THE STRUCTURAL CONTRACT DOCUMENTS IN CONJUNCTION WITH THE ARCHITECTURAL AND MEP DEMOLITION CONTRACT DOCUMENTS. IN THE EVENT OF CONFLICTS, THE
CONTRACTOR SHALL IMMEDIATELY NOTIFY THE DESIGN PROFESSIONALS.
DE-5 THE CONTRACTOR SHALL USE QUALIFIED, EXPERIENCED PERSONNEL FOR DEMOLITION AND REMOVAL OPERATIONS. PERFORM DEMOLITION AND REMOVAL OPERATIONS IN A CAREFUL AND ORDERLY MANNER TO PREVENT HAZARDS TO PERSONS, DAMAGE TO PROPERTY, AND THE SPREADING OF DUST AND DEBRIS.
DE-6 DO NOT PERMIT PORTIONS OF THE STRUCTURE TO FALL NOR DEBRIS TO DROP EXCEPT BY METHODS WHICH
WILL INSURE INTEGRITY OF THE STRUCTURE.
DE-7 PRIOR TO THE START OF WORK, VERIFY THAT THE SCOPE OF DEMOLITION INDICATED ON THE CONTRACT DOCUMENTS SHALL NOT DAMAGE, CUT OR DISRUPT SERVICE OF ANY MECHANICAL SYSTEM, ELECTRICAL
SYSTEM OR UTILITY EMBEDDED IN THE EXISTING STRUCTURE.
DE-8 DO NOT REMOVE MORE OF THE EXISTING STRUCTURE THAN INDICATED ON CONTRACT DOCUMENTS. DO NOT
DAMAGE, MAR, CUT OR DEFACE THE REMAINING STRUCTURE OR MATERIALS TO BE REUSED.
DE-9 THE CONTRACTOR SHALL INCLUDE IN HIS BID THE COST OF REMOVING DEMOLISHED MATERIALS FROM THE
SITE IN ACCORDANCE WITH ALL APPLICABLE LAWS, CODES, AND REGULATIONS.
DE-10 WHERE NEW OPENINGS IN EXISTING CONCRETE SLABS OR WALLS ARE TO BE CREATED, THE DEMOLITION CONTRACTOR SHALL CORE HOLES AT THE OUTSIDE CORNERS OF THE NEW OPENING PRIOR TO DEMOLITION.
SAW-CUT AND DEMOLISH SLAB OR WALL ONLY AFTER THE INSTALLATION OF ALL REQUIRED NEW STRUCTURAL FRAMING AND/OR REINFORCEMENT IN PLAN OR SECTION, UON. SAW CUTTING SHALL BE STRAIGHT AND SHALL NOT EXTEND INTO EXISTING SLAB OR WALL TO REMAIN NOR BEYOND THE HOLES
CORED AT THE CORNERS OF THE NEW OPENING.
SU SUBMITTALS
SU-1 THE CONTRACTOR IS TO REVIEW EACH SUBMITTAL PRIOR TO FORWARDING TO DESIGN PROFESSIONALS. THE
CONTRACTOR IS TO STAMP EACH SUBMITTAL VERIFYING THAT THE FOLLOWING IS ADDRESSED:
1. THE SHOP DRAWING IS REQUESTED.
2. THE SHOP DRAWING IS BASED ON THE LATEST DESIGN.
3. THE DESIGN PROFESSIONALS’ COMMENTS FROM ANY PREVIOUS SUBMITTALS ARE ADDRESSED.
4. THE WORK IS COORDINATED AMONG ALL CONSTRUCTION TRADES.
5. REVISIONS FROM PREVIOUS SUBMITTALS ARE CLEARLY MARKED BY CIRCLING OR CLOUDS.
6. SUBMITTAL IS COMPLETE.
7. SUBMITTAL DOES NOT INCLUDE SUBSTITUTION REQUEST
8. SUBMITTAL SHALL INCLUDE A STAMP INDICATING PROJECT NAME AND LOCATION, SUBMITTAL NUMBER, SPECIFICATION SECTION NUMBER.
THE SER SHALL RETURN, WITHOUT COMMENT, SUBMITTALS WHICH THE CONTRACTOR HAS NOT STAMPED OR
WHICH DO NOT MEET THE ABOVE REQUIREMENTS.
SU-2 THE SER’S REVIEW OF SUBMITTALS SHALL BE FOR GENERAL CONFORMANCE WITH THE DESIGN INTENT. NO
WORK SHALL BE STARTED WITHOUT SUCH REVIEW.
SU-3 FOR COMPONENTS THAT REQUIRE ENGINEERING BY THE CONTRACTOR, PROVIDE A NOTE ON EACH SHOP DRAWING, WRITTEN AND SIGNED BY THE SUPPLIER'S ENGINEER, INDICATING THAT THE SHOP DRAWING IS IN
CONFORMANCE WITH THE CALCULATIONS OF THE CONTRACTOR'S ENGINEER.
SU-4 THE FOLLOWING ITEMS REQUIRE SUBMITTALS FOR STRUCTURAL REVIEW AS OUTLINED IN THE
SPECIFICATIONS:
032000 S CONCRETE REINFORCING LAYOUT
033000 CONCRETE MIX DESIGNS
051000 S STRUCTURAL STEEL
053000 S ROOF DECK
S = SHOP DRAWINGS REQUIRED
SU-5 THE ITEMS IN THIS SECTION REFER TO LOADS IMPOSED BY CONTRACTOR DESIGNED SYSTEMS, SPECIFICALLY:
EXTERIOR CLADDING SYSTEMS
WHERE CONTRACTOR LOADS IMPOSED DO NOT EXCEED AND/OR CONNECTION CONDITIONS DO NOT DIFFER FROM WHAT IS INDICATED IN THE STRUCTURAL DRAWINGS, SUBMIT FOR RECORD A LETTER SEALED AND SIGNED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE PROJECT IS LOCATED STATING
THE FOLLOWING:
“THE CONTRACTOR DESIGNED SYSTEM HAS BEEN DESIGNED TO IMPOSE LOADS ON THE BASE BUILDING STRUCTURE THAT ARE WITHIN THE LOAD LIMITS AND AT THE LOCATIONS INDICATED ON THE STRUCTURAL
DRAWINGS.”
WHERE CONTRACTOR LOADS IMPOSED FOR THE FOLLOWING ITEMS EXCEED AND/OR CONNECTION
CONDITIONS DIFFER FROM WHAT IS SHOWN IN THE STRUCTURAL DRAWINGS, SUBMIT FOR APPROVAL TO SER LOADS IMPOSED ON THE PRIMARY STRUCTURAL FRAME DUE TO THE DEAD, LIVE, AND WIND/SEISMIC LOADS
INDICATED ON THE CONTRACT DOCUMENTS.
SUBMITTAL SHALL LIST THE DESIGN LOADS USED AND BE SEALED AND SIGNED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE PROJECT IS LOCATED. SUBMITTAL SHALL INCLUDE LOCATION, MAGNITUDE AND DIRECTION OF UNFACTORED IMPOSED LOADS, GRAPHICALLY REPRESENTED IN THEIR APPROPRIATE LOCATIONS ON A COPY OF THE CONTRACT DOCUMENT STRUCTURAL FRAMING PLANS OR ELEVATIONS AS APPROPRIATE. DETAIL REFERENCES IN THE CONNECTIONS APPLICABLE AT EACH
LOCATION SHALL BE NOTED ON THE SUBMITTAL DRAWINGS.
FOR EXTERIOR WALL ASSEMBLIES, THE LOADS IMPOSED SUBMITTAL SHALL BE COMPREHENSIVE INDICATING THE LOADS IMPOSED ON THE BASE BUILDING STRUCTURE AND SHALL INCLUDE THE REACTIONS BASED ON THE ACTUAL LOADS OF THE ENTIRE ASSEMBLY, INCLUDING BUT NOT LIMITED TO GLAZING, CLADDING, METAL
STUD BACKUP, AND MULLIONS.
FOR MEP SYSTEMS, THE LOADS IMPOSED SUBMITTAL SHALL BE COMPREHENSIVE INDICATING THE LOADS IMPOSED ON THE BASE BUILDING STRUCTURE AND SHALL INCLUDE THE REACTIONS BASED ON THE ACTUAL LOADS OF THE ENTIRE MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION SYSTEM, INCLUDING
BUT NOT LIMITED TO PIPING, DUCTS, ELECTRICAL RACEWAYS, AND EQUIPMENT WEIGHTS.
A SUBSTITUTION REQUEST MAY BE REQUIRED WHERE CONTRACTOR LOADS IMPOSED EXCEED AND/OR
CONNECTION CONDITIONS DIFFER FROM THE BASIS OF DESIGN.
FN FOUNDATIONS
FN-1 THE FOUNDATION DESIGN IS BASED ON THE IBC SECTION 1806.2 - PRESUMPTIVE LOAD-BEARING VALUES. NO
GEOTECHNICAL REPORT HAS BEEN PROVIDED TO THE SER.
FN-2 FOUNDATIONS HAVE BEEN DESIGNED BASED ON THE FOLLOWING DESIGN VALUES
ASSUMED SOIL MATERIAL: CLAY, SANDY CLAY, SILTY CLAY, CLAYEY SILT, SILT, OR SANDY SILT
NET ALLOWABLE BEARING CAPACITY: 1,500 PSF
FROST DEPTH: 36 IN
DESIGN VALUES SHALL BE FIELD VERIFIED BY QUALIFIED GEOTECHNICAL ENGINEER RETAINED BY THE
OWNER.
FN-3 CONTRACTOR SHALL BE RESPONSIBLE TO ADEQUATELY PROTECT ALL EXCAVATION. WHERE NECESSARY, SHEET AND SHORE THE EXCAVATION WITH ALL REQUIRED TIEBACKS AND BRACING AS DETERMINED BY
CONTRACTOR’S ENGINEER.
FN-4 CONTRACTOR SHALL VERIFY WALL EXISTING BUILDING FOUNDATIONS IN FIELD PRIOR TO CONSTRUCTION.
ENSURE EXISTING BUILDING FOUNDATIONS ARE NOT UNDERMINED DURING CONSTRUCTION. NOTIFY SER IF
NEW FOUNDATIONS CONFLICT WITH OR UNDERMINE EXISTING FOUNDATIONS.
CM CONCRETE MATERIALS
CM-1 CONCRETE STRENGTH SHALL MEET THE FOLLOWING 28-DAY COMPRESSIVE STRENGTHS (f' c), UON:
FOOTINGS 4,000 PSI
SLAB ON GRADE 4,500 PSI
CM-2 PROVIDE NORMALWEIGHT CONCRETE WITH CURED DENSITY OF 145 +/- 5 PCF, AND AGGREGATE CONFORMING TO ASTM C33, UON. WHERE INDICATED, PROVIDE LIGHTWEIGHT CONCRETE WITH CURED DENSITY OF 112+/-3
PCF AND AGGREGATE CONFORMING TO ASTM C330.
CM-3 THE USE OF CALCIUM CHLORIDE AND OTHER CHLORIDE CONTAINING AGENTS IS PROHIBITED. THE USE OF RECYCLED CONCRETE IS PROHIBITED. PLACEMENT WITHIN AND CONTACT BETWEEN ALUMINUM ITEMS, INCLUDING ALUMINUM CONDUIT, AND CONCRETE IS PROHIBITED.
CM-4 ALL CAST-IN-PLACE CONCRETE WILL EXPERIENCE DIFFERING VARIATIONS OF CRACKING. ANY ELEMENT EXPOSED TO DIRECT WEATHER AND/OR TEMPERATURE VARIATIONS DURING CONSTRUCTION OR IN THE FINAL CONDITION IS TO BE TREATED AND REGULARLY MAINTAINED TO PREVENT PROPAGATION OF CRACKS AND WATER PENETRATION. THE CONTRACTOR SHALL DEVELOP A REGULAR MAINTENANCE PROGRAM AND SUBMIT
IT TO THE OWNER.
RE CONCRETE REINFORCEMENT
RE-1 ALL CONCRETE SHALL INCLUDE REINFORCEMENT. IF REINFORCEMENT IS NOT SPECIFICALLY INDICATED ON
THE DRAWINGS VERIFY WITH THE SER.
RE-2 REINFORCEMENT SHALL CONFORM TO THE FOLLOWING STANDARDS AND MATERIAL PROPERTIES UON:
DEFORMED BARS: ASTM A615 GRADE 60
WELDED WIRE REINFORCEMENT ASTM A1064
RE-3 DETAIL REINFORCEMENT BASED ON THE PROJECT REQUIREMENTS, ACI-318 AND ACI-315, UON.
RE-4 WHERE A 90-DEG, 135 –DEG OR 180-DEG HOOK IS GRAPHICALLY…