1. ALL DIMENSIONS SHALL BE VERIFIED CAREFULLY AND ANY DISCREPANCIES BROUGHT TO THE IMMEDIATE ATTENTION
OF THE VA COR.
2. GENERAL CONTRACTOR SHALL PROTECT EXISTING CORRIDORS, ELEVATORS, DOORS, ETC. ALL DAMAGE RESULTING FROM RENOVATION, DEMOLITION OR TRANSPORTATION OF MATERIALS ASSOCIATED WITH THIS PROJECT MUST BE
REPAIRED.
3. NOTIFY THE VA COR PRIOR TO ANY HAMMER DRILLING, SAW CUTTING, OR CORE DRILLING. THIS MUST BE SCHEDULED
7 DAYS IN ADVANCE.
4. THE VA COR SHALL BE GIVEN THREE WEEKS NOTICE, IN WRITING, BEFORE ANY UTILITY SYSTEM SHUTDOWN IS
REQUIRED.
5. REPAIR OR REPLACE ALL PROPERTY OF THE OWNER DAMAGED BY CONSTRUCTION, INCLUDING BUT NOT LIMITED TO:
EQUIPMENT, FLOORS, BASES, CEILING TILES, AND WALLS.
6. IT WILL BE THE RESPONSIBILITY OF THE CONTRACTOR TO IMMEDIATELY REPAIR ANY DAMAGED UTILITY LINES AND
FIRE SPRINKLER PIPING DURING DEMOLITION AND CONSTRUCTION.
7. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO BE FOR ASSISTANCE AND GUIDANCE, BUT EXACT LOCATIONS, DISTANCES, LEVELS, QUANTITIES SHALL BE GOVERNED BY ACTUAL CONDITIONS FOUND AT THE JOB SITE AND MUST BE VERIFIED BY THE CONTRACTOR. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND BECOME FAMILIAR WITH ALL AREAS OF THE EXISTING BUILDING AFFECTED BY THE WORK, PRIOR TO COMMENCING THE WORK.
GENERAL NOTES : GENERAL NOTES - JOHN J. PERSHING VAMC SPECIFIC :
GENERAL
1. CONTRACTOR IS RESPONSIBLE FOR BECOMING FAMILIAR WITH THE WORK AND ALL AREAS OF THE EXISTING BUILDING AFFECTED BY THE WORK, CAREFULLY VERIFYING ALL DIMENSIONS, AND BRINGING ANY DISCREPANCIES TO THE IMMEDIATE ATTENTION OF THE COR.
2. CONTRACTOR WILL INCLUDE INFORMATION DESCRIBING COMPLIANCE WITH ICRA REQUIREMENTS IN THE NARRATIVE.
3. CONTRACTOR WILL OBTAIN A PERMIT PRIOR TO BEGINNING WORK ABOVE CEILINGS.
4. CONTRACTOR MUST OBTAIN HOT WORK PERMITS DAILY FOR WELDING, SOLDERING, TORCH CUTTING, AND BURNING 24 HOURS PRIOR TO THE START OF WORK FROM THE COR. FIRE WATCH IS REQUIRED. CONTRACTOR WILL FURNISH FIRE EXTINGUISHERS. CONTRACTOR MUST ACQUIRE AND HOLD THESE PERMITS AT THE WORK SITE AT ALL TIMES.
5. NO SMOKING IS PERMITTED ON VA PROPERTY.
6. CONTRACTOR SHALL PROTECT THE EXISTING FACILITY AND REPAIR ANY DAMAGED UTILITY AND RESULTING FROM THE WORK.
7. CONTRACTOR WILL NOTIFY THE COR SEVEN DAYS PRIOR TO ANY CORE DRILLING.
8. CONTRACTOR WILL PROVIDE THREE WEEKS NOTICE IN WRITING PRIOR THESHUT DOWN OF ANY UTILITY.
9. CONTRACTOR WILL NOTIFY THE COR OF ANY DAMAGED FIRE SPRINKLER COMPONENTS AND REPAIR IMMEDIATELY.
10.CONTRACTOR WILL LEGALLY REMOVE AND DISPOSE OF ALL DEBRIS PER THE VA APPROVED WASTE MANAGEMENT PLAN.
PROTECTION COORDINATION & REQUIREMENTS
1. CONTRACTOR SHALL MAINTAIN ALL SITE AREAS IN A SAFE CONDITION AT ALL TIMES.
2. CONTRACTOR IS RESPONSIBLE FOR PROVIDING PROTECTION FOR BUILDING, SYSTEMS, OCCUPANTS, AND PEDESTRIANS AT ALL TIMES DURING CONSTRUCTION.
3. CONTRACTOR SHALL SUBMIT SAFETY PLAN TO COR FOR REVIEW AND APPROVAL INDICATING ALL SAFETY MEASURES TO BE IMPLEMENTED DURING CONSTRUCTION.
4. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL REQUIRED PPE AND SAFE WORKING CONDITIONS FOR ALL WORKERS PER OSHA REQUIREMENTS.
5. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING 8-FOOT HIGH FENCING (CHAIN LINK AND ABLE TO BE LOCKED) IN AREAS WHERE WORK IS BEING PERFORMED, INCLUDING LAY
DOWN AND SET-UP AREAS.
6. THE CONTRACTOR SHALL PROVIDE A SPOTTER/ QUALIFIED SAFETY PERSON ON THE GROUND IN AREAS WHERE WORK IS BEING PERFORMED.
MECHANICAL SYSTEMS
1. CONTRACTOR SHALL PROTECT MECHANICAL UNITS INCLUDING AIR HANDLERS, COMPRESSORS, AND PIPING AS NECESSARY, AND CONTRACTOR SHALL MAINTAIN AIR FLOW (INTAKE & EXHAUST) AT EQUIPMENT AT ALL TIMES. INTAKES ADJACENT TO WORK AREAS SHALL BE FILTERED FROM DUST AND DEBRIS WITH MINIMUM MERV13 FILTER CLOTH.
POWER
1. COR WILL DETERMINE AVAILABILITY OF POWER SUPPLY (IF ANY) AT THE TIME OF THE AWARD OF THE CONSTRUCTION CONTRACT.
2. IF THE VA IS UNABLE TO PROVIDE A TEMPORARY ELECTRICAL CONNECTION DURING CONSTRUCTION, THE CONTRACTOR WILL BE REQUIRED TO PROVIDE ELECTRICITY TO SUPPORT THE WORK. CONTRACTOR WILL REQUEST AN AREA TO USE THE GENERATOR AT LEAST SEVEN (7) CALENDAR DAYS PRIOR TO USE. CONTRACTOR IS RESPONSIBLE FOR PROTECTING
OUTSIDE BUILDING AIR INTAKES FROM EXHAUST FOR THE DURATION OF THE PROJECT.
3. CONTRACTOR SHALL REQUEST POWER SHUTDOWNS OF EQUIPMENT THROUGH COR. CONTRACTOR SHALL NOT SHUTDOWN EQUIPMENT OR ENGAGE WITH VA BREAKERS OR
DISCONNECTS ON ACTIVE EQUIPMENT.
ACCESS AND MATERIAL STAGING
1. ROOF ACCESS WILL BE COORDINATED WITH THE COR.
2. COR WILL DETERMINE AVAILABILITY OF ACCESS AND STAGING AREAS AND IDENTIFY POTENTIAL LOCATIONS (IF ANY) AT THE TIME OF THE ISSUANCE OF THE NOTICE TO PROCEED.
AREA FOR STAGING OR STORAGE MAY NOT BE AVAILABLE TO THE CONTRACTOR DURING CONSTRUCTION.
3. STORAGE IS NOT PERMITTED AROUND AHU INTAKES.
4. ALL HOIST MOVEMENTS MUST TAKE PLACE AFTER HOURS OR ON WEEKENDS, UNLESS APPROVED BY COR. A LIFT PLAN MUST BE SUBMITTED TWO WEEKS PRIOR TO ALL HOIST MOVEMENTS FOR APPROVAL. ALL LIFT WORK SHALL COMPLY WITH VA SPECIFICATIONS AND OSHA 29 CFR 1926 SUBPART CC.
5. CONTRACTOR SHALL PLAN STAGING AND STORAGE AREAS TO MINIMIZE IMPACT TO EXISTING INFRASTRUCTURE AND ALLOW FOR ACCESS TO EXISTING EQUIPMENT.
6. CONTRACTOR SHALL INCLUDE REQUESTS FOR ACCESS AND STAGING AREAS IN THE NARRATIVE AND SCHEDULE.
SECURITY REQUIREMENTS
1. ROOF ACCESS POINTS / DOORS SHALL BE KEPT LOCKED AT ALL TIMES TO PREVENT UNAUTHORIZED PERSONS FROM ENTERING ROOF OR MECHANICAL ROOMS / STAIRS LEADING TO
ROOF. DOORS SHALL NOT BE PROPPED OPEN.
2. ALL MATERIAL AND EQUIPMENT SHALL BE KEPT IN A SECURED STATE AT ALL TIMES.
3. EXTERIOR STORAGE AREAS SHALL BE SECURED AND KEPT LOCKED AT ALL TIMES EXCEPT WHEN ADDING OR REMOVING MATERIALS.
4. CONTRACTOR SHALL SUPPLY TEMPORARY GUARD RAILS ON ROOFTOP WHERE GUARD RAILS ARE NOT ALREADY INSTALLED AS REQUIRED. CONTRACTOR SHALL FOLLOW ALL OHSA
REQUIREMENTS.
MEDICAL CENTER OPERATIONS
1. BUILDING AREAS WILL BE OCCUPIED AT ALL TIMES. CONTRACTOR WILL SCHEDULE THE WORK TO MINIMIZE DISRUPTION TO PATIENT COMFORT AND MEDICAL CENTER OPERATIONS.
2. CONTRACTOR SHALL PROVIDE A SCHEDULE THAT PROJECTS THE WORK FOR A MINIMUM OF FOUR WEEKS IS REQUIRED.
FOR COR APPROVAL THROUGHOUT THE DURATION OF THE PROJECT. CONTRACTOR SHOULD INCLUDE STAGING/STORAGE AREA AND TEMPORARY POWER REQUESTS IN THE
SCHEDULE INFORMATION.
3. DEMOLITION WORK AND WORK WITH TOOLS THAT TRANSMIT VIBRATIONS AND NOISE THROUGH THE BUILDING STRUCTURE ARE PERMITTED ONLY DURING THE HOURS OF 5PM - 8PM
MONDAY THROUGH FRIDAY.
WORK AREA PREPARATION & PROTECTION
1. CONTRACTOR MUST PROVIDE WALK-OFF MATS AND ANY OTHER METHODS OF PROTECTION NEEDED DURING THE CONSTRUCTION/REPAIR PROCESS, IN ORDER TO PROTECT
STAIRWELLS AND CORRIDORS FROM DIRT AND DEBRIS.
2. CONTRACTOR MUST INSTALL FILTERS OVER ROOF DRAINS TO PREVENT DEBRIS FROM ENTERING ROOF DRAIN. REMOVE DEBRIS FROM ROOFS ON A DAILY BASIS.
3. CONTRACTOR SHALL PROVIDE WALK-OFF MATS AT ROOF SURFACES WHERE CONSTRUCTION TRAFFIC AND DEBRIS WILL AFFECT EXISTING ROOF.
4. ALL PROTECTION MEASURES MUST BE APPROVED BY COR PRIOR TO START OF WORK.
ENVIRONMENTAL HAZARDS (ACM - ASBESTOS CONTAINING MATERIALS)
1. ALL ASBESTOS ABATEMENT OR ENCLOSURE WORK SHALL BE PERFORMED BY PROPERLY TRAINED/LICENSED ASBESTOS ABATEMENT
CONTRACTOR WITHIN A FULL CONTAINMENT UNDER NEGATIVE PRESSURE (NPE).
2. ALL HVAC AIR INTAKES WITHIN NPE SHALL BE SHUT DOWN AND ISOLATED WITH CRITICAL BARRIERS DURING ACTIVE ACM REMOVAL OR ENCLOSURE WORK. WORK TO BE SCHEDULED WITH GENERAL CONTRACTOR AND OWNER TO ACCOMMODATE CONSTRUCTION AND FACILITY REQUIREMENTS.
3. WORKERS PERFORMING ACM REMOVAL OR ENCLOSURE SHALL DON, AT MINIMUM, HALF FACE AIR PURIFYING RESPIRATORS WITH P100 FILTERS, DISPOSABLE DUST SUITS (WITH BOOT COVERS) AND GLOVES DURING ACTIVE TASKS, WHICH SHALL BE SUPPLEMENTED WITH USE OF POWERED AIR PURIFYING RESPIRATORS.
4. ACM REMOVAL WORK AREAS SHALL BE PREPARED IN ACCORDANCE WITH THE FOLLOWING: A) ALL FLOORS, CEILINGS AND WALLS SHALL BE ISOLATED USING 2-LAYERS OF 6-MIL POLY SHEETING; B) OSHA ASBESTOS SIGNAGE AT ENTRANCE TO REGULATED AREAS; C)SINGLE-POINT OF ENTRY WITH 3-STAGE WET DECONTAMINATION STATION TO ALLOW WORKERS TO REMOVE PPE, WASH AND VACUUM THEMSELVES OFF PRIOR TO EXITING THE REGULATED WORK AREA; D) MAINTAINED UNDER NEGATIVE PRESSURE (-0.02 IN WG OR
BETTER) USING HEPA FILTERED AIR
MACHINES WITH EXHAUST ROUTED TO OUTDOORS; E) MINIMUM OF 4 AIR CHANGES PER HOUR; F) CLEAN/CHANGE ROOM SUFFICIENT FOR WORKERS TO CHANGE INTO STREET CLOTHES (OPAQUE POLY REQUIRED AS NEEDED FOR PRIVACY); G) RENEWABLE ADHESIVE MATS IMMEDIATELY OUTSIDE OF REGULATED WORK AREA TO ENSURE FOOT TRAFFIC DOES
NOT SPREAD DUST/DEBRIS TO OTHER AREAS OF FACILITY.
5. ACM WORK TO BE PERFORMED USING THE FOLLOWING CONTROLS: A) HEPA FILTERED VACUUM FOR CONTINUOUS AND FINAL CLEANUP; B) ONLY MANUAL REMOVAL MEANS/TOOLS
ARE ALLOWED TO DISTURB ACM (MECHANICAL TOOLS PROHIBITED FOR ACM REMOVAL).
6. REGULATED WORK AREA IS TO BE CLEANED BY CONTRACTOR FOLLOWING COMPONENT REMOVAL USING STANDARD HEPA VACUUM & WET WIPING METHODS AND VISUALLY INSPECTED AND CLEARANCE SAMPLED BY VA REPRESENTATIVE TO VERIFY COMPLETION OF SCOPE.
7. VPIH (VA PROFESSIONAL INDUSTRIAL HYGIENIST) IS TO BE RESPONSIBLE FOR PERIMETER AIR MONITORING AND FINAL CLEARANCE AIR SAMPLING/VISUAL INSPECTION
REQUIREMENTS.
8. CONTRACTOR TO BE RESPONSIBLE FOR OSHA EMPLOYEE EXPOSURE MONITORING REQUIREMENTS.
9. ALL WASTE PRODUCED DURING REMEDIATION PHASE SHALL BE COLLECTED, CONTAINERIZED, LABELED, CHARACTERIZED AND DISPOSED IN ACCORDANCE WITH SPECIFICATIONS
10. ALL WASTE CONTAINERS, EQUIPMENT, ETC. SHALL BE WET WIPED PRIOR TO LEAVING REGULATED WORK AREA.
11. WORK IS TO BE PERFORMED DURING OFF HOURS FROM 5:00 PM - 8:00 PM MONDAY THROUGH FRIDAY AND WEEKEND WORK FRIDAY 6 PM THROUGH SUNDAY. WORK IS PROHIBITED
ON FEDERAL HOLIDAYS.
12. ASBESTOS RELATED MATERIALS ARE PRESENT AND MAY NOT SHOWN ON DRAWINGS FOR CLARITY. KNOWN ASBESTOS MATERIALS INCLUDE FIRE DOORS, SOILS, DOOR AND WINDOW CAULKS, WINDOWS GLAZING, FLOOR TILE GROUPS AND ASSOCIATED UNDERLYING ASBESTOS MASTIC, FOUNDATION WATERPROOFING, TRANSITE AT WINDOW CONVECTORS, ASBESTOS DRYWALL ADHESIVES WHERE APPLIED TO WALL BLOCKS, GREEN MARBLE WALL PANELS, ACOUSTICAL LOBBY PLASTER, BLACK OR WHITE DUCT SEAM SEALANTS AND APPLICATIONS, SINK SOUND PROOFING, VIBRATION ISOLATION DUCT JOINTS, ASBESTOS PIPE INSULATION AND MUDDED FITTINGS, AND ZALBESTOS COATED DUCTWORK. PROTECT AS
NECESSARY.
13. AT INTERIOR REGULATED AREAS (NPE), WHERE THE COMBINED FOOTPRINT OF WORK CHAMBER, DECONTAMINATION CHAMBERS AND LOADOUT DOES NOT FIT WITHIN THE ROOM, THE DECON/LOADOUT CONFIGURATION MAY EXTEND INTO 1/2 WIDTH OF THE HALLWAY AS REQUIRED TO ALLOW PASSAGE IN CORRIDOR.
DRAWING SCHEDULE
PROJECT No.
Owner: Structural: Mechanical & Plumbing: Electrical: Fire Protection: Telecom: Interior:Architectural:
657A4-21-702
06/23/2022100% CONSTRUCTION DOCUMENTS
657A4-21-702 EHRM Training and Admin Space Support John J Pershing VA Medical Center (VAMC)
1500 North Westwood Blvd.
Poplar Bluff, MO 63901
John J. Pershing VA Medical Center Atriax Group PLLC
102 3rd Ave. NE Hickory, NC 28601
01-G1
Poplar Bluff, MO 63901
SHEET # DRAWING TITLE
SHEET
ISSUE
DATE
GENERAL
01-G1 COVER & SHEET INDEX 06/23/2022
01-G2 NOTES, ABBREVIATIONS, LEGENDS 06/23/2022
01-G3 UL DESIGN ASSEMBLY 06/23/2022
LOCATION MAP
AERIAL VIEW
MEDICAL CENTER DIRECTOR:
ASSISTANT DIRECTOR:
ASSOCIATE DIRECTOR:
CHIEF OF STAFF:
DIRECTOR OF PATIENT SERVICES:
CHIEF OF FACILITIES MANAGEMENT:
INFECTION CONTROL PRACTITIONER:
SAFETY OFFICER:
INTEGRATED PROJECT TEAM
APPROVAL SIGNATURES
01-A1 CONFERENCE RM 45A FLOOR, FINISH, EQUIPMENT AND CEILING PLANS 06/23/2022
01-A2 CONFERENCE RM 5054 FLOOR, FINISH, EQUIPMENT AND CEILING PLANS 06/23/2022
01-A3 CONFERENCE RM 5025/A FLOOR, FINISH, AND CEILING PLANS 06/23/2022
01-A4 CONFERENCE RM 5025/A EQUIPMENT PLANS - FOR REFERENCE ONLY 06/23/2022
01-A5 SCHEDULES AND DETAILS 06/23/2022
01-A6 WALL SECTIONS AND DETAILS 06/23/2022
01-A7 EXIT PROTECTION PLAN 06/23/2022
01-A8 CONSTRUCTION SIGNAGE 06/23/2022
01-S1 STRUCTURAL GENERAL NOTES 06/23/2022
01-S2 STRUCTURAL PLANS, SECTIONS AND DETAILS 06/23/2022
01-S3 STRUCTURAL SECTIONS AND DETAILS 06/23/2022
STRUCTURAL
FIRE PROTECTION
01-F1 FIRE PROTECTION PLANS 06/23/2022
MECHANICAL
01-M1 MECHANICAL SYMBOLS AND ABBREVIATIONS 06/23/2022
01-M2 CONFERENCE RM 45A MECHANICAL PLANS 06/23/2022
01-M3 CONFERENCE RM 5054 MECHANICAL PLANS 06/23/2022
01-M4 CONFERENCE RM 5025/A MECHANICAL PLANS 06/23/2022
01-M5 ROOF MECHANICAL PLANS 06/23/2022
01-M6 MECHANICAL DETAILS 06/23/2022
01-M7 MECHANICAL SCHEDULES 06/23/2022
01-M8 MECHANICAL CONTROLS 06/23/2022
01-M9 MECHANICAL CONTROLS 06/23/2022
ELECTRICAL
01-E1 ELECTRICAL SYMBOLS AND ABBREVIATIONS 06/23/2022
01-E2 CONFERENCE RM 45A ELECTRICAL DEMOLITION AND LIGHTING PLANS 06/23/2022
01-E3 CONFERENCE RM 45A POWER AND LOW VOLTGE PLANS 06/23/2022
01-E4 CONFERENCE RM 5054 ELECTRICAL DEMOLITION AND LIGHTING PLANS 06/23/2022
01-E5 CONFERENCE RM 5054 POWER AND LOW VOLTAGE PLANS 06/23/2022
01-E6 CONFERENCE RM 5025/A DEMOLITION AND LIGHTING PLANS 06/23/2022
01-E7 CONFERENCE RM 5025/A POWER AND LOW VOLTAGE PLANS 06/23/2022
01-E8 ROOF ELECTRICAL PLANS 06/23/2022
01-E10 ELECTRICAL SCHEDULES 06/23/2022
ARCHITECTURAL
ALUMINUM
CONCRETE
GLASS
RIGID INSULATION
BRICK IN SECTION
CONCRETE MASONRY UNIT
EARTH
GYPSUM / PLASTER
STEEL
PEA GRAVEL
STONE
BATT INSULATION
PRECAST
GRAVEL
SAND
WOOD - SOLID
PLYWOOD
BRICK
CULTURED STONE
EXTERIOR COMPOSITE
PANEL
WOOD BLOCKING
WOOD SHIM
MATERIALS LEGEND SYMBOLS LEGEND
SEE DISCIPLINE SHEETS FOR DISCIPLINE SPECIFIC SYMBOLS
1t
A02
Room Name
0-0000
NET SF
0 GRID LINE
ROOM No.
DOOR No.
WINDOW TYPE
WALL TYPE
NORTH ARROW
N
SPECIALTY
EQUIPMENT /
FURNITURE TAG
SCOPE NOTE
CENTER LINE
FLOW ARROW
INTERIOR
ELEVATION
DETAIL
SPOT
ELEVATION
MARKERS
REVISION No.
REVISION
CLOUD
EXTERIOR
ELEVATION
BUILDING SECTION
A301
A201
A211
A501
4 2
DETAIL
SHEET
DETAIL
SHEET
DETAIL
SHEET
DETAIL
SHEET
SECTION
MARKERS
GYP BD
10'-0" CEILING TAG
SD CD
CL
WALL SECTION
A301
DETAIL
SHEET
SMOKE PARTITION
1 - HOUR FIRE BARRIER
1 - HOUR FIRE SMOKE BARRIER
2 - HOUR FIRE BARRIER
Sheet No. Sequence Sheet Type Building Number
01-A1 SHEET No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
NC Engineering License No.: P-0214 NC Architectural License No.: 51254
C U s e rs \M a ry
\D o c u m e n ts \E
H R
M -P o p la r
B lu ff A
R C
H
R m a ry .m o o re r@ a tr ia x g ro u p .c o m
.r v t
/2
/2
:0
:3
P
M
01-G2
NOTES, ABBREVIATIONS, LEGENDS 657A4-21-702 EHRM Training and
Admin Space Support
John J Pershing VA Medical Center (VAMC)
657A4-21-702
06/23/2022 SC HP
100% CONSTRUCTION
DOCUMENTS
Poplar Bluff, MO 63901
TEMP TEMPERATURE
TEMP TEMPORARY
THK THICKNESS
THRES THRESHOLD
THRU THROUGH
TK BD TACK BOARD
TKP TACKABLE PANELING
TOC TOP OF CONCRETE
TOS TOP OF SLAB
TOW TOP OF WALL
TPD TOILET PAPER DISPENSER
TR ACCENT RAIL
TRTD TREATED
TRZ INTERIOR POURED EPOXY RESIN
TERRAZO
TV TELEVISION
TYP TYPICAL
UC UNDERCUT
UGND UNDERGROUND
UL UNDERWRITER'S LABORATORY
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
UR URINAL
V VOLT
VAC VACUUM
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VENT VENTILATE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VNR VENEER
VOL VOLUME
VP VACUUM PUMP
VP VANISHING POINT
VP VAPOR PRESSURE
VP VENEER PLASTER
VPC VENEER PLASTIC CEILING/SOFFIT
VR VAPOR RETARDER
VRR VINYL (ACROVYN) RAIL
VS VENT STACK
VS VOLUMETRIC SWITCH
VS SHEET VINYL
VT SOLID VINYL TILE
VTR VENT THRU ROOF
VTS VINYL TRANSITION STRIP
VWC VINYL WALLCOVERING
W WIDE
W WEST
W / W WALL TO WALL
W/ WITH
W/D WASHER / DRYER
W/O WITHOUT
WB WOOD BASE
WC WATER CLOSET
WC WALLCOVERING
WD WOOD
WDH WOOD HAND RAIL
WDM WOOD WALL MOULDINGS
WDP WOOD PANELING
WDR WOOD CHAIR, CRASH, OR HAND RAIL
WDS ATHLETIC/ACOUSTIC ISOLATED WOOD
FLOORING
WDSHV WOOD SHELVING
WDT WOOD TILE OR PARQUET FLOORING
WDV WOOD VENEER
WDW WINDOW
WF WIDE FLANGE
WGL WIRED GLASS
WH WALL HUNG
WI WROUGHT IRON
WP WATERPROOF
WP WORKING POINT
WPM WATERPROOF MEMBRANE
WR WEATHER RESISTANT
WR WIRE ROPE
WRP WATER REPELLENT
WT WEIGHT
WWF WELDED WIRE FABRIC
XPS EXTRUDED POLYSTYRENE
YD YARD
PREFIN PRE-FINISHED
PRF POLYURETHANE SPORTS FLOORING
PROP PROPERTY
PRST PRESSURE TREATED
PS POURED SEALANT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT(ED)
PT/E EPOXY PAINT
PT/F FLAT PAINT
PT/HG HIGH GLOSS PAINT
PT/SG SEMIGLOSS PAINT
PTD PAPER TOWEL DISPENSER
PTN PARTITION
PV PAVED
PVC POLYVINYL CHLORIDE
PVG PAVING
Q HEAT TRANSFER
Q RATE OF FLOW
QT QUARRY TILE
QTY QUANTITY
QZF QUARTZ FLOORING
QZR QUARTZ RESIN
QZT QUARTZ TILE
R RISER
R RADIUS
RA RETURN AIR
RB RUBBER BASE
RB RUBBER BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REC RECESSED
RECPT RECEPTACLE
REF REFERENCE
REF REFRIGERATOR
REFL REFLECTED
REG REGISTER
REINF REINFORCE(D)
REQ REQUIRED
RESIL RESILIENT
REST RESTROOM
RET RETURN
REV REVISE / REVISION
RF RESILIENT FLOORING
RFG ROOFING
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
RR RAILROAD
RR ROLL ROOFING
RS RAPID START
RS ROUGH SAWN
RS RUBBER SHEET
RSF RUBBER SHEET FLOORING
RST REINFORCING STEEL
RT RIGHT
RTF RUBBER TILE FLOORING
RTS RUBBER TRANSITION STRIP
RWD REDWOOD
RWL RAIN WATER LEADER
S SOUTH
SAN SANITARY
SC SOLID CORE
SCHED SCHEDULE
SCRN SCREEN
SCT STRUCTURAL CLAY TILE
SD SOAP DISPENSER
SECT SECTION
SF SQUARE FEET
SGL SINGLE
SH SINGLE HUNG
SHR SHOWER
SHR HD SHOWER HEAD
SHT SHEET
SHTHG SHEATHING
SIM SIMILAR
SL SEA LEVEL
SL SPOT LIGHT
SLDG SLIDING
SND SANITARY NAPKIN DISPENSER
SNDU SANITARY NAPKIN DISPOSAL UNIT
SPC SUSPENDED PLASTER CEILING
SPEC SPECIFY / SPECIFICATION
SPH SOLID PHENOLIC POLYMER (TRESPA)
SPKR SPEAKER
SPR SOLID POLYMER RESIN (3FORM)
SQ SQUARE
SQIN SQUARE INCH(ES)
SSP SOLID SURFACE POLYMER (CORIAN)
SSPR SOLID POLYMER (CORIAN) RUB RAIL
SST STAINLESS STEEL
SSTR STAINLESS STEEL RUB RAIL
ST SINGLE THROW
ST STAIRS
ST STREET
ST STAIN
STA STATION
STD STANDARD
STIF STIFFENER
STON STONE
STOR STORAGE
STRUCT STRUCTURE / STRUCTURAL
SUH SUSPENDED UNIT HEATER
SURF SURFACE
SUSP SUSPENDED
SVP VINYL SOLID PANEL (ACROVYN)
SW SWITCH
SYMM SYMMETRICAL
SYNTH SYNTHETIC
SYS SYSTEM
T TREAD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
T/S TUB / SHOWER
TB TOWEL BAR
TC TERRA COTTA
TCZ CEMENTITIOUS TERRAZZO
TEL TELEPHONE
HD HAND DRYER
HDBD HARDBOARD
HDR HEADER
HDW HARDWARE
HDWD HARDWOOD
HDWL HEADWALL
HM HOLLOW METAL
HNDRL HANDRAIL
HORIZ HORIZONTAL
HP HEAT PUMP
HP HIGH PRESSURE
HP HORSEPOWER
HR HAND RAIL
HS HAND SINK
HT HEIGHT
HVAC HEATING / VENTILATION / AIR
CONDITIONING
HW HOT WATER
HWP HOT WATER PUMP
HYD HYDRANT
IC IRONING CABINET
ID INSIDE DIAMETER
IN INCH / INCHES
INCL INCLUDE(D) / INCLUDING
INSUL INSULATE / INSULATION
INT INTERIOR
INV INVERT
ITS INTERTEK TESTING SERVICES
J-BOX JUNCTION BOX
JAN CLO JANITOR'S CLOSET
JS JANITOR'S SINK
KIT KITCHEN
L ANGLE
L LITER
LAB LABORATORY
LAM LAMINATE(D)
LAV LAVATORY
LB(S) POUND(S)
LC LINEN CLOSET
LF LINEAR FOOT (FEET)
LH LEFT HAND
LIB LIBRARY
LINO LINOLEUM
LKR LOCKER
LNO LINOLEUM
LPT LOW POINT
LT LIGHT
LTF LINOLEUM TILE FLOORING
LTWT LIGHT WEIGHT
LVR LOUVER
m METER
MACH MACHINE
MAT WALK-OFF MAT
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MB MAIL BOX
MB MIXING BOX
MBH MOP/BROOM HOLDER
MC MEDICINE CABINET
MCP ACOUSTIC LAY-IN METAL CEILING PADS
ME MECHANICAL ENGINEER
MECH MECHANICAL
MED MEDIUM
MEZZ MEZZANINE
MFR MANUFACTURE(R)
MH MANHOLE
MIN MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MKR BD MARKER BOARD
MLDG MOULDING
mm MILLIMETER
MO MASONRY OPENING
MR MOISTURE RESISTANT
MS MOP SINK
MSB MOP SERVICE BASIN
MTD MOUNTED
MTL METAL
MTS METAL TRANSITION STRIP
MULL MULLION
MVBL MOVABLE
MW MICROWAVE
N NORTH
NA NOT AVAILABLE / APPLICABLE
NAT NATURAL
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OF / CI OWNER FURNISHED / CONTRACTOR
INSTALLED
OFF OFFICE
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OZ OUNCE
PAR PARALLEL
PAR PARAPET
PART PARTIAL
PAT PATTERN
PBD PARTICLE BOARD
PCC PRECAST CONCRETE
PED PEDESTAL
PERF PERFORATED
PERIM PERIMETER
PERP PERPENDICULAR
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAS PLASTIC
PLAS PLASTER
PLYWD PLYWOOD
PR PAIR
PREFAB PREFABRICATED
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DET DETAIL
DF DRINKING FOUNTAIN
DH DOUBLE HUNG
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISP DISPENSER
DIV DIVISION
DMPF DAMPPROOFING
DR DOOR / DRAIN
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
DWR DRAWER
E EAST
EA EACH
EF EACH FACE
EG VERTICAL END GUARDS
EHD ELECTRIC HAND DRYER
EIFS EXTERIOR INSULATION AND FINISH
SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EM ELECTROMAGNETIC
EM EXPANDED METAL
EMER EMERGENCY
ENCL ENCLOSED / ENCLOSURE
ENGR ENGINEER
ENTR ENTRANCE
EOS EDGE OF SLAB
EPB ELECTRIC PANEL BOARD
EQ EQUAL(LY)
EQUIP EQUIPMENT
ER POURED EPOXY
ERF POURED EPOXY FLOORING
ESCAL ESCALATOR
EST ESTIMATE
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXF EXTERIOR FINISH
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FA FIRE ALARM
FAB FABRIC
FAI FRESH AIR INTAKE
FBRK FIREBRICK
FCP PREFABRICATED FABRIC CEILING PANEL
FCU FAN COIL UNIT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF EL FINISH FLOOR ELEVATION
FGL FIBERGLASS
FH FIRE HOSE
FHC FIRE HOSE CABINET
FIN FINISH(ED)
FIN FLR FINISHED FLOOR
FIN FLR FINISH FLOOR
FIXT FIXTURE
FLASH FLASH(ING)
FLR FLOOR
FLRSK FLOOR SINK
FLUOR FLUORESCENT
FM FACTORY MUTUAL
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUDS
FOW FACE OF WALL
FP FIREPROOF
FPL FIREPLACE
FR FRAME
FRG FIBER REINFORCED GYPSUM
FRP FIBERGLASS REINFORCED PLASTIC
FRT FIRE RETARDANT TREATED
FSP FIRE STAND PIPE
FSTNR FASTENER
FTG FOOTING
FURG FURRING
FUT FUTURE
FWC FABRIC WALL COVER
FWP NON-ACOUSTIC STRETCHED FABRIC
PANEL WALL INSTALATION
G GROUND
GA GAGE
GALV GALVANIZE(D)
GB GRAB BAR
GC GENERAL CONTRACTOR
GDISP GARBAGE DISPOSAL
GEN GENERAL
GFP GFRP OR GFRG FREESTANDING PANEL
GFRG GLASS FIBER REINFORCED GYPSUM
GFRP GLASS FIBER REINFORCED POLYMER
GL GLASS / GLAZING
GL BLK GLASS BLOCK
GLT GLASS MOSIAC TILE
GLZ GLAZING
GLZ CMU GLAZED CONCRETE MASONRY UNIT
GPM GALLONS PER MINUTE
GR GROSS
GR LN GRADE LINE
GRAN GRANITE
GT GREASE TRAP
GT GROSS TON
GT GROUT
GYP GYPSUM
GYP BD GYPSUM BOARD
H HIGH
HC HOLLOW CORE
HCP HANDICAPPED
HD HEAVY DUTY
@ AT
A/C AIR CONDITIONER / CONDITIONING
ACC ACCESSIBLE
ACCSY ACCESSORY
ACOUS INSUL ACOUSTICAL INSULATION
ACOUS PNL ACOUSTICAL PANELS
ACP LAY-IN ACOUSTIC PANEL CEILING PADS
ACS DR ACCESS DOOR
ACS FLR ACCESS FLOOR
ACS PNL ACCESS PANEL
ACST ACOUSTICAL
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADDL ADDITIONAL
ADDM ADDENDUM
ADJ ADJUSTABLE / ADJACENT
ADMIN ADMINISTRATION
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AHR ANCHOR
AHU AIR HANDLING UNIT
ALNMT ALIGNMENT
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATELY
APPVD APPROVED
APT APARTMENT
ARCH ARCHITECT(URAL)
ASPH ASPHALT
ASTM AMERICAN SOCIETY FOR TESTING
MATERIALS
ATC ACOUSTICAL TILE CEILING
AUTO AUTOMATIC
AVG AVERAGE
AWP WALL-MOUNTED SOUND ABSORPTION
PANEL
AWT ACOUSTIC WALL TREATMENT
BD BOARD
BITUM BITUMINOUS
BL BASELINE
BL BLACK
BLDG BUILDING
BM BEAM
BO BLOWOFF
BOT BOTTOM
BR BEDROOM
BRG BEARING
BS BOTH SIDES
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT UP ROOFING
BW BOTH WAYS
C CELSIUS
C CHANNEL
C TO C CENTER TO CENTER
CAB CABINET
CB CATCH BASIN
CCT CUBICLE CURTAIN TRACK
CEM CEMENT
CEM PLAS CEMENT PLASTER (STUCCO)
CER CERAMIC
CG CORNER GUARD
CH CHILLER
CH COAT HOOK
CHBD CHALKBOARD
CHFR CHAMFER
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTERLINE
CL D CLOTHES DRYER
CLG CEILING
CLG HT CEILING HEIGHT
CLL CONTRACT LIMIT LINE
CLO CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CO CARBON MONOXIDE
CO CASED OPENING
CO CERTIFICATE OF OCCUPANCY
CO CLEANOUT
CO COMPANY
CO CUTOUT
COL COLUMN
COMB COMBINATION
CONC CONCRETE
CONC FLR SEALED CONCRETE FLOOR
CONSTR CONSTRUCTION
CONT CONTINUE
CONT CONTROLLER
CONV CONVERT
CORR CORRIDOR / CORRUGATED
CPT CARPET
CR CLOSET ROD
CR CONTROL RELAY
CR CONTROL ROOM
CR CRASH RAIL
CS CAST STONE
CS CONTROL SWITCH
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTR CENTER
CU COPPER
CU FT CUBIC FOOT
CU YD CUBIC YARD
CUB CUBICLE CURTAIN
CURT CURTAIN
CW CASEMENT WINDOW
CW CHEMICAL WASTE LINE
CW CLOCKWISE
CW COLD WATER PIPING
D DEEP
Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
NC Engineering License No.: P-0214 NC Architectural License No.: 51254
C U s e rs \M a ry
\D o c u m e n ts \E
H R
M -P o p la r
B lu ff A
R C
H
R m a ry .m o o re r@ a tr ia x g ro u p .c o m
.r v t
/2
/2
:0
:4
P
M
01-G3
UL DESIGN ASSEMBLY 657A4-21-702 EHRM Training and
Admin Space Support
John J Pershing VA Medical Center (VAMC)
657A4-21-702
06/23/2022 SC HP
100% CONSTRUCTION
DOCUMENTS
Poplar Bluff, MO 63901
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
NC Engineering License No.: P-0214 NC Architectural License No.: 51254
018701 Red Oak Blvd.
Suite 500 Charlotte, NC 28217
(704) 522-0495 www.brittpeters.com BPA Project No. 21530
C U s e rs
\m ri c k h e r\
O n e
D ri v e
B ri tt P e te rs
A s s o c ia te s \D o c u m e n ts
\P o p la r B lu ff V
A M
C
S tr u c
R
M
S R ic k h e r.
rv t
/2
/2
:3
:4
A
M
01-S1
STRUCTURAL GENERAL NOTES 657A4-21-702 EHRM Training and
Administrative Space Support
John J. Pershing VA Medical Center (VAMC)
657A4-21-702
06/23/2022 MSR RES
100% CONSTRUCTION
DOCUMENTS
Poplar Bluff, MO
1.0. CODES AND STANDARDS:
1.1. INTERNATIONAL BUILDING CODE 2018 EDITION INCLUDING ALL SUBSEQUENT
SUPPLEMENTS AND AMENDMENTS THERETO.
1.2. "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES", AMERICAN
SOCIETY OF CIVIL ENGINEERS, ASCE 7-16.
1.3. "SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS", PUBLICATION 360-16 BY THE
AMERICAN INSTITUTE OF STEEL CONSTRUCTION, AND AS AMENDED IN SPECIFICATIONS.
1.4. "SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS", PUBLICATION 341-16 BY
THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION.
1.5. "STRUCTURAL WELDING CODE - STEEL (AWS D1.1-11)" AND "STRUCTURAL WELDING
CODE REINFORCING STEEL (AWS D1.4-11)", AMERICAN WELDING SOCIETY.
1.6. "STANDARD FOR STEEL ROOF DECK", SDI RD-2017, STEEL DECK INSTITUTE.
1.7. "NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL
FRAMING, S240-15, AMERICAN IRON AND STEEL INSTITUTE.
2.0. SPECIFICATIONS:
2.1. THE STRUCTURAL GENERAL NOTES ARE NOT A SUBSTITUTE OR A REPLACEMENT
FOR THE PROJECT SPECIFICATIONS. THESE NOTES ARE INTENDED AS A GUIDE TO
THE DESIGN AND/OR CONSTRUCTION REQUIREMENTS ESTABLISHED FOR THIS PROJECT.
NO CONTRACTOR SHOULD ATTEMPT TO DESIGN, BID, OR CONSTRUCT ANY PORTION OF
THE WORK HEREIN WITHOUT CONSULTING THE PROJECT SPECIFICATIONS. WHERE
CONFLICTS OCCUR BETWEEN THESE NOTES AND THE SPECIFICATIONS, THE MORE
STRINGENT REQUIREMENT SHALL APPLY UNLESS A WRITTEN CLARIFICATION IS
ISSUED BY THE STRUCTURAL ENGINEER.
2.2. CONTRACTOR AND STRUCTURAL STEEL FABRICATOR SHOULD ACQUAINT THEMSELVES WITH
THE REQUIREMENTS FOR DOMESTICALLY PRODUCED BOLTS AND FOR STEEL CONNECTION
DESIGN REQUIREMENTS, INCLUDING SIGNED AND SEALED SHOP DRAWINGS AND
CONNECTION DESIGN CALCULATIONS, NOTED HEREIN AND IN THE STRUCTURAL STEEL
SPECIFICATIONS. REQUIREMENTS ARE MANDATORY. REFER TO SPECIFICATION
SECTION 051200 "STRUCTURAL STEEL"
2.3. STRUCTURAL STEEL SHALL BE FABRICATED BY A QUALIFIED FABRICATOR WHO PARTICIPATES
IN THE AISC CERTIFICATION PROGRAM AND IS DESIGNATED AS AN AISC CERTIFIED
PLANT "STANDARD FOR STEEL BUILDING STRUCTURES (STD)" AND THE STRUCTURAL
STEEL FABRICATOR MUST DEMONSTRATE A CONSISTENT RECORD OF AT LEAST TEN (10)
SUCCESSFUL PROJECTS OF EQUAL OR GREATER MAGNITUDE OVER THE PRECEDING FIVE
(5) YEARS. CONTRACTOR SHALL SUBMIT EVIDENCE TO THE ARCHITECT VERIFYING
HIS PROPOSED FABRICATOR'S COMPLIANCE. FABRICATOR'S CREDENTIALS MUST BE IN
COMPLIANCE WITHIN 48 HOURS OF BID.
2.4. STRUCTURAL STEEL SHALL BE ERECTED BY A QUALIFIED INSTALLER WHO MUST
DEMONSTRATE A CONSISTENT RECORD OF AT LEAST TEN (10) SUCCESSFUL
PROJECTS OF EQUAL OR GREATER MAGNITUDE OVER THE PRECEDING FIVE (5) YEARS.
CONTRACTOR SHALL SUBMIT EVIDENCE TO THE ARCHITECT VERIFYING HIS ERECTOR'S
COMPLIANCE. ERECTOR'S CREDENTIALS MUST BE IN COMPLIANCE WITHIN 48 HOURS OF BID.
3.0. DESIGN LOADS:
3.1. SUPERIMPOSED GRAVITY LOADS:
AREA LIVE LOAD DEAD LOAD
MINIMUM UNIFORM ROOF LOAD 20 PSF 25 PSF
ALL FRAMED FLOORS, U.N.O. 100 PSF 5 PSF
LIVE LOADS ARE REDUCED IN CONFORMANCE WITH ASCE 7-10
SECTION 4.8 "REDUCTION IN LIVE LOADS"
3.2. SEISMIC LOADS:
RISK CATEGORY IV
RISK IMPORTANCE FACTOR "IE" 1.50
THE SEISMIC FORCES GENERATED BY THIS ADDITION ARE RESISTED BY
THE ORIGINAL BUILDING LATERAL SYSTEM.
3.3. WIND LOADS PER ASCE 7-16:
BASIC WIND SPEED (3-SECOND GUST) 116 MPH
RISK CATEGORY IV
ASCE 7 EXPOSURE CATEGORY B
THE LATERAL FORCES GENERATED BY THE WIND ARE RESISTED BY
THE ORIGINAL BUILDING LATERAL SYSTEM.
WIND PRESSURES FOR CLADDING AND OTHER COMPONENTS VARY WITH SHAPE
FACTORS FOR THOSE COMPONENTS - SEE APPROPRIATE ASCE 7-10 SECTIONS
3.4. DRIFTING SNOW LOADS PER ASCE 7-16:
50 YEAR GROUND SNOW LOAD "PG" 15.0 PSF
RISK CATEGORY IV
IMPORTANCE FACTOR "I" 1.20
ROOF EXPOSURE TYPE PARTIAL
EXPOSURE FACTOR "CE" 1.00
THERMAL FACTOR "CT" 1.00
MINIMUM ROOF SNOW LOAD (PG*I) 18.0 PSF
FLAT ROOF SNOW LOAD "PF" 12.6 PSF
RAIN-ON-SNOW SURCHAGE 5.0 PSF
FLAT ROOF DESIGN SNOW LOAD 18.0 PSF
4.7. CONNECTION DESIGN: SEE SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
A. FABRICATOR IS RESPONSIBLE FOR THE DESIGN OF CONNECTIONS NOT DESIGNED
ON THE STRUCTURAL DRAWINGS.
B. ALL CONNECTIONS SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER REGISTERED
IN THE STATE WHERE THE PROJECT IS LOCATED. SHOP DRAWING CONTAINING
CONNECTION DESIGNS SHALL BE SIGNED AND SEALED. A NOTE INDICATING
"CONNECTION DESIGN ONLY" SHOULD ACCOMPANY THE SEAL. FABRICATOR SHALL
SUBMIT SIGNED AND SEALED CALCULATIONS FOR ALL CONNECTIONS DESIGNED AS
PART OF HIS WORK AND APPEARING ON HIS SHOP DRAWINGS.
C. GENERALLY, CONNECTIONS SHOWN ON THE DRAWINGS ARE SCHEMATIC AND ARE
INTENDED TO SHOW THE RELATIONSHIP OF THE MEMBERS.
D. CONNECTIONS SHALL BE DESIGNED FOR THE REACTIONS AS SHOWN ON THE DRAWINGS,
WITH A MINIMUM REACTION OF 10 KIPS. IF NO REACTION IS SHOWN ON PLAN,
DESIGN CONNECTIONS FOR ONE-HALF (1/2) THE MAXIUMUM TOTAL UNIFORM LOAD
ON THE MEMBER, AS DEFINED IN TABLE 3-6, "MAXIUMUM TOTAL UNIFORM LOAD"
IN THE AISC "SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS",
PUBLICATION 360-16.
E. MEMBER FORCES AND REACTIONS HAVE BEEN REDUCED IN CONFORMANCE TO CODE
PROVISIONS RELATED TO COMBINATIONS OF LOADS THAT INCLUDE WIND AND
SEISMIC FORCES. NO FURTHER REDUCTIONS IN FORCES OR INCREASES IN
ALLOWABLE STRESSES ARE PERMITTED.
F. CONNECTIONS SHOWN ON DRAWINGS ARE ULTIMATE (LRFD) LOAD REACTIONS.
G. CONNECTIONS MAY BE BOLTED OR WELDED, U.N.O. ON THE DRAWINGS.
4.8. BOLTED CONNECTIONS:
A. SLIP CRITICAL CONNECTIONS WITH A325SC OR A490SC BOLTS SHALL BE USED
IN ALL BOLTED MOMENT PLATE CONNECTIONS. OVERSIZED OR LONG-SLOTTED
HOLES ARE PERMITTED.
B. BEARING-TYPE CONNECTIONS WITH A325N OR A490N BOLTS SHALL BE USED FOR
ALL OTHER BOLTED CONNECTIONS. OVERSIZED AND LONG-SLOTTED HOLES ARE
NOT PERMITTED U.N.O. IN SINGLE TAB PLATE CONNECTIONS ONLY BEARING-
TYPE FASTENERS ARE PERMITTED, FASTENERS SHALL NOT BE TORQUED, AND
SHORT SLOTTED HOLES ARE REQUIRED.
C. ANCHOR BOLTS OR OTHER BOLTS, WHERE INDICATED, SHALL CONFORM TO ASTM
F1554 GR36 U.N.O.
D. PROTRUDING BOLT HEADS, SHAFTS OR NUTS SHALL NOT EXTEND NOR PROHIBIT
THE APPLICATION OF ARCHITECTURAL FINISHES OR PLACEMENT OF STEEL DECK
AT ITS CORRECT LOCATION AND ELEVATION.
E. CONNECTION DESIGNER IS RESPONSIBLE FOR VERIFYING THE AXIAL CAPACITY
AFTER A SECTION IS REDUCED FOR BOLT HOLES. MEMBER SIZE MAY BE
INCREASED OR PLATES ADDED TO MAINTAIN REQUIRED CAPACITY.
F. SHOP DRAWINGS SHALL INDICATE THE TYPE OF BOLT USED IN EACH
CONNECTION, ALLOWABLE VALUES FOR THE VARIOUS BOLT TYPES AND CAPACITY
OF EACH CONNECTION SHOWN.
G. DOMESTIC (AMERICAN) FASTENERS ARE REQUIRED IN ALL
STRUCTURAL STEEL WORK ON THIS PROJECT. IMPORTED FASTENERS ARE
PROHIBITED.
4.9. WELDED CONNECTIONS:
A. ALL WELDING SHALL BE IN ACCORDANCE WITH THE "STRUCTURAL WELDING CODE
- STEEL" (AWS D1.1) OF THE AMERICAN WELDING SOCIETY.
B. ELECTRODES FOR WELDING SHALL COMPLY WITH THE REQUIREMENTS OF AWS
D1.1 TABLE 4.1.1.
C. SHOP DRAWINGS SHALL INDICATE WELD TYPE, REQUIRED ELECTRODES AND
CAPACITY FOR EACH CONNECTION DETAILED ON THE SHOP DRAWINGS.
D. PERFORM VISUAL INSPECTIONS OF ALL WELDS.
E. PERFORM NON-DESTRUCTIVE TESTS OF WELDS AS FOLLOWS:
1. PARTIAL PENETRATION WELDS - ONE SPOT TEST PER WELD USING
MAGNETIC PARTICLE TESTING TECHNIQUES.
2. FULL PENETRATION WELDS - TEST ENTIRE LENGTH OF ALL WELDS.
USE RADIOGRAPHIC OR ULTRASONIC TESTING TECHNIQUES.
4.10. WHERE CANTILEVER BEAMS OCCUR ON PLAN AND THE SIZE IS NOTED ONLY FOR THE
BACK-SPAN, THE CANTILEVER IS INTENDED TO BE THE SAME SIZE AS THE BACK-
SPAN.
4.11. SPLICING OF STEEL MEMBERS, UNLESS SHOWN ON THE DRAWINGS, IS PROHIBITED
WITHOUT WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER.
4.12. NO CHANGE IN SIZE OR POSITION OF ANY STRUCTURAL ELEMENT NOR HOLES, SLOTS,
CUTS, ETC. SHALL BE MADE UNLESS DETAILED AND NOTED AS A PROPOSED CHANGE
ON THE SHOP DRAWINGS AND REVIEWED AND ACCEPTED BY THE STRUCTURAL
ENGINEER.
4.13. NO FINAL BOLTING OR WELDING SHALL BE PERFORMED UNTIL AS MUCH OF THE
STRUCTURE AS WILL BE STIFFENED THEREBY HAS BEEN PROPERLY ALIGNED.
4.14. FABRICATE ALL BEAMS WITH MILL CAMBERS UP.
4.15. U.N.O. BEAMS ARE EQUALLY SPACED BETWEEN COLUMNS.
4.16. MINIMUM PLATE THICKNESS SHALL BE 3/8" U.N.O.; MINIMUM BOLT DIAMETER SHALL
BE 3/4" U.N.O.; MINIMUM SHOP WELD SHALL BE 3/16" AND MINIMUM FIELD WELD
SHALL BE 1/4" U.N.O.
4.17. ALL RE-ENTRANT CORNERS (SUCH AS COPES AND BLOCKS) SHALL BE CUT AND SHAPED
NOTCH FREE WITH A RADIUS OF AT LEAST 1/2".
4.18. FIELD USE OF GAS CUTTING TORCHES IS PROHIBITED FOR CORRECTING FABRICATION
ERRORS IN PRIMARY STRUCTURAL FRAMING.
4.19. PARAGRAPH 4.4.1 OF THE AISC CODE OF STANDARD PRACTICE SHALL BE SUPERSEDED
BY THE FOLLOWING: INDICATION OF COMPLIANCE BY THE
OWNER OF SHOP DRAWINGS PREPARED BY THE FABRICATOR INDICATES THAT THE
FABRICATOR HAS CORRECTLY INTERPRETED THE CONTRACT REQUIREMENTS. SUCH
INDICATION DOES NOT RELIEVE THE FABRICATOR OF THE RESPONSIBILITY ASSIGNED
TO HIM FOR THE DESIGN AND DETAILING OF CONNECTIONS ASSIGNED TO HIM, NOR
FOR THE ACCURACY OF DIMENSIONS ON THE SHOP DRAWINGS, NOR FOR GENERAL FIT
UP OF PARTS TO BE ASSEMBLED IN FIELD.
4.20. PARAGRAPHS 7.2 THROUGH 7.6 OF THE AISC CODE OF STANDARD PRACTICE SHALL BE
SUPERSEDED AS FOLLOWS: ALL REFERENCES TO "OWNER" SHALL BE REPLACED
WITH REFERENCES TO "CONTRACTOR".
4.21. EXPANSION BOLTS SHALL PROVIDE A MINIMUM SAFETY FACTOR OF FOUR (4) TIMES
THE FOLLOWING MINIMUM SERVICE LOAD CAPACITIES, U.N.O.
SLEEVE ANCHORS (2000 PSI MASONRY) WEDGE ANCHORS (3000 PSI CONCRETE)
DIA. SHEAR TENSION DIA. SHEAR TENSION
1/4" 270 LB. 300 LB. 1/2" 1950 LB. 1250 LB.
1/2" 930 LB. 600 LB. 3/4" 3750 LB. 2250 LB.
4.22. FOR ALL ROOF BEAMS PROVIDE L2X2X1/4" X-BRACING AT 1/4 POINTS ALONG THEIR
LENGTH, UNO.
5.2. STEEL DECK AT ROOFS AND PENTHOUSES SHALL BE GALVANIZED PER ASTM A525 G60.
5.3. STEEL ROOF DECK:
A. STEEL ROOF DECK SHALL BE DESIGNED TO FUNCTION AS A DIAPHRAGM FOR
TRANSMISSION OF LATERAL LOADS. CONNECTIONS OF DECK UNITS TO EACH OTHER
AND TO SUPPORTS SHALL BE DESIGNED BY THE DECK MANUFACTURER CONSISTENT
WITH THE DECK PROPERTIES AND SHALL BE DESIGNED TO TRANSMIT A SHEAR
FORCE PER LINEAL FOOT AT THE DIAPHRAGM BOUNDARIES DENOTED AS "Q=XX PLF"
(MINIMUM 200 PLF) WHERE SHOWN ON THE DRAWINGS.
B. FASTEN STEEL ROOF DECK UNITS TO STEEL SUPPORTING MEMBERS BY NOT LESS
THAN 5/8" DIAMETER FUSION WELDS OR ELONGATED WELDS OF EQUAL PERIMETER.
ALTERNATIVELY, FASTEN WITH "HILTI" X-ENP-19, X-EDN19 OR X-EDNK22
FASTENERS CONFORMING TO THE REQUIREMENTS OF THE "HILTI" PUBLISHED
INSTALLATION INSTRUCTIONS. ATTACHMENTS SHALL BE SPACED NOT MORE THAN
12" O/C. AT EVERY SUPPORT AND AT CLOSER SPACINGS WHERE REQUIRED FOR
DIAPHRAGM SHEAR RESISTANCE.
C. FOR STEEL ROOF DECK SPANS EXCEEDING 5'-0", MECHANICALLY FASTEN SIDE
LAPS AT MID-SPAN USING "HILTI" #10 SELF-TAPPING SCREW OR "HILTI" S-SLC01
OR S-SLC02 SIDELAP CONNECTORS AS SHOWN ON DRAWINGS. PROVIDE ADDITIONAL
SIDELAP FASTENERS WHERE REQUIRED FOR LATERAL FORCE RESISTANCE.
D. DO NOT HANG PIPES, DUCTS OR ELECTRICAL COMPONENTS FROM STEEL ROOF DECK.
E. SUSPENDED CEILINGS CAN BE SUPPORTED DIRECTLY FROM THE ROOF DECK AS LONG
AS THE SYSTEM WEIGHT DOES NOT EXCEED 5 PSF AND THE ATTACHMENT OF THE
SYSTEM TO THE DECKING DOES NOT EXCEED 80 POUNDS OR DAMAGE THE DECKING
IN ANY WAY. THE CONTRACTOR IS RESPONSIBLE FOR THE ATTACHMENT.
5.4. STEEL DECK SUBMITTALS: STEEL DECK MANUFACTURER SHALL SUBMIT SHOP DRAWINGS
FOR REVIEW AND ACCEPTANCE BY THE STRUCTURAL ENGINEER INDICATING DECK TYPE,
GAUGE AND PROTECTIVE TREATMENT, AS WELL AS TYPE, SIZE AND LAYOUT OF DECK
CONNECTIONS.
5.5. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMISSION AND
SHALL BEAR THE CONTRACTOR'S APPROVAL STAMP ACCEPTING RESPONSIBILITY FOR
DIMENSIONS, QUANTITIES AND COORDINATION WITH THE OTHER TRADES.
5.6. DRAWINGS MAY BE ELECTRONICALLY SUBMITTED, PROVIDED LEGIBILITY IS MAINTAINED.
REVIEW COMMENTS ONLY WILL BE ELECTRONICALLY FORWARDED TO THE CONTRACTOR.
5.7. CONTRACTOR SHALL PROVIDE IN HIS SCHEDULE FOR A SHOP DRAWING REVIEW AND
RETURN TIME OF A MINIMUM OF FIFTEEN (15) WORKING DAYS IN THE STRUCTURAL
ENGINEER'S OFFICE.
6.0 LIGHT GAGE STEEL FRAMING:
6.1. ALL MEMBERS SHALL BE DESIGNED IN ACCORDANCE WITH THE MOST RECENT EDITION
OF THE AMERICAN IRON AND STEEL INSTITUTE (AISI) "SPECIFICATION FOR THE
DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS".
6.2. ALL FRAMING MEMBERS SHALL BE FORMED FROM CORROSION-RESISTANT STEEL,
CORRESPONDING TO THE REQUIREMENTS OF ASTM A653, WITH A MINIMUM YIELD
STRENGTH OF 50 KSI FOR MEMBERS WITH THICKNESSES OF 54 MILS AND HIGHER AND
33 KSI FOR MEMBERS WITH THICKNESSES OF 33 AND 43 MILS.
6.3. ALL MEMBERS SHOWN ARE STANDARD DESIGNATIONS OF "STEEL STUD MANUFACTURERS
ASSOCIATION".
6.4. MEMBERS INDICATED ON THE STRUCTURAL DRAWINGS ARE BASED ON MINIMUM
PROPERTIES OF PRODUCTS PRODUCED BY "STEEL STUD MANUFACTURERS ASSOCIATION".
SUBSTITUTION OF MATERIALS IS ACCEPTABLE, PRIOR TO SUBMISSION OF SHOP DRAWINGS
SUBJECT TO APPROVAL OF THE STRUCTURAL ENGINEER.
6.5. MEMBER CONFIGURATIONS AND CONNECTIONS SHOWN ON THE DRAWINGS ARE SCHEMATIC
AND ARE INTENDED ONLY TO SHOW RELATIONSHIPS OF MEMBERS AND INFORMATION
FOR PRICING AND BIDDING PURPOSES.
6.6. CONTRACTOR/FABRICATOR IS RESPONSIBLE FOR THE DESIGN AND DETAILING OF ALL
LIGHTGAGE STEEL FRAMING AND SHALL RETAIN A PROFESSIONAL ENGINEER
REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED TO PERFORM SUCH.
THE ENGINEER SHALL SEAL AND SIGN BOTH CALCULATIONS AND SHOP DRAWINGS.
UPON COMPLETION OF THE LIGHTGAGE FRAMING ERECTION THE ENGINEER SHALL
FURNISH A LETTER STATING THAT THE LIGHTGAGE FRAMING WAS INSTALLED IN
ACCORDANCE WITH THE APPROVED SHOP DRAWINGS.
6.7. SUBMIT CALCULATIONS AND SHOP DRAWINGS FOR DETAILS, FABRICATION, AND
ERECTION OF LIGHTGAGE STEEL FRAMING:
A. COORDINATE CALCULATIONS WITH SHOP DRAWINGS.
B. DRAWINGS SHALL CLEARLY INDICATE LOCATION OF DETAILS FOR ERECTION.
C. DRAWINGS SHALL INCLUDE LAYOUT, SPACING, TYPE, MATERIAL MEMBER
PROPERTIES AND ALL DETAILS OF CONNECTIONS INCLUDING TYPE, SIZE, AND
SPACING OF CONNECTORS.
D. PROVIDE CALCULATIONS FOR ALL TYPICAL AND NON-TYPICAL CONNECTIONS AND
FOR ATTACHMENT TO PRIMARY STRUCTURAL FRAME.
6.8. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMISSION AND
SHALL BEAR THE CONTRACTOR'S APPROVAL STAMP ACCEPTING RESPONSIBILITY FOR
DIMENSIONS, QUANTITIES AND COORDINATION WITH THE OTHER TRADES.
6.9. DRAWINGS MAY BE ELECTRONICALLY SUBMITTED, PROVIDED LEGIBILITY IS MAINTAINED.
REVIEW COMMENTS ONLY WILL BE ELECTRONICALLY FORWARDED TO THE CONTRACTOR.
6.10. CONTRACTOR SHALL PROVIDE IN HIS SCHEDULE FOR A SHOP DRAWING REVIEW AND
RETURN TIME OF A MINIMUM OF FIFTEEN (15) WORKING DAYS IN THE STRUCTURAL
ENGINEER'S OFFICE.
6.11. ALL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR ATTACHMENT TO
PERPENDICULARMEMBERS OR AS REQUIRED FOR AN ANGULAR FIT TIGHT AGAINST
ABUTTING MEMBERS.
6.12. AXIALLY LOADED STUDS SHALL BE INSTALLED IN A MANNER WHICH WILL ASSURE THAT
THEIR ENDS ARE POSITIONED TIGHT AGAINST THE INSIDE OF RUNNER WEBS PRIOR TO
FASTENING. PROVIDE WEAK-AXIS HORIZONTAL BRACING AT 36 INCHES MAXIMUM
VERTICAL SPACING, BOTH STUD FLANGES. HORIZONTAL BRACING SHALL BE 1-1/2" X
20 GA. STRAPS AND CS TYPE RUNNER SOLID BRIDGING AT EACH END OF WALL,
ADJACENT TO WALL OPENINGS, AND AT 8'-0" O/C. MAXIMUM.
6.13. FLOOR OR ROOF JOISTS AND RAFTERS SHALL HAVE SOLID BLOCKING, A FITTED
CS TYPE CLOSURE OR JOIST SECTION, PLACED BETWEEN OUTER JOISTS, OVER ALL
INTERIOR SUPPORTS, ADJACENT TO OPENINGS AND AT 8'-0" O/C. MAXIMUM.
BETWEEN SOLID BLOCKING PROVIDE STRAP BRACING OF 1-1/2" X 20 GA. STRAPS.
JOIST BRIDGING SHALL BE PROVIDED AT MID-SPAN OR AT 8'-0' O/C. MAXIMUM FOR
SPANS EXCEEDING 15"-0".
6.14. WHERE STUDS FRAME TO STRUCTURAL FLOOR OR ROOF MEMBERS SUBJECT TO
DEFLECTION FROM TRANSIENT OR LIVE LOADING, EITHER A DEEP LEG DOUBLE TRACK
OR A "Z" CLIP ASSEMBLY SHALL BE PROVIDED AT THE TOP RUNNER TO ACCOMMODATE
VERTICAL STRUCTURAL MOVEMENT. FAILURE TO PROVIDE TOP CONNECTIONS CAPABLE
OF ACCOMMODATING MOVEMENT MAY RESULT IN CRUSHING AND BUCKLING OF THE STUD
MEMBERS AND DAMAGE TO ARCHITECTURAL COMPONENTS OR FINISHES.
6.15. COORDINATE FIREPROOFING REQUIREMENTS FOR LIGHT GAGE ATTACHMENT TO
STRUCUTRAL STEEL.
6.16. FASTENING OF COMPONENTS SHALL BE BY SELF-DRILLING SCREWS OR BY WELDING AS
DEFINED BELOW U.N.O. ON THE DRAWINGS.
7.0. INSPECTION AND TESTING:
7.1. AN INDEPENDENT TESTING LABORATORY SHALL BE RETAINED IN ACCORDANCE WITH
THE PROJECT SPECIFICATIONS TO PERFORM TESTING OF FOUNDATION BEARING
STRATA, ENGINEERED FILLS, CONCRETE, GROUT, STEEL, AND WELDING. SEE
PROJECT SPECIFICATIONS FOR REQUIREMENTS.
7.2. THE CONTRACTOR, IN CONJUNCTION WITH THE TESTING LABORATORY AND IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS, SHALL DETERMINE THE FREQUENCY
OF THE TESTING NECESSARY TO INSURE THAT THE DESIGN REQUIREMENTS ARE
BEING MET.
7.3. THE TESTING AGENCY SHALL VERIFY THAT ALL WELDERS HAVE SATISFACTORILY
PASSED AWS QUALIFICATION TESTS FOR THE WELDS WHICH THEY WILL PERFORM.
7.4. THE CONTRACTOR AND TESTING AGENCY SHALL REQUIRE THAT AWS QUALIFICATION
TESTS FOR WELDING OF MATERIAL LESS THAN 1/8" IN THICKNESS ARE PASSED
BY WELDERS EXPECTED TO ERECT LIGHTGAGE FRAMING MATERIALS. THESE
TESTS ARE NOT THE SAME AS FOR MATERIALS 1/8" OR GREATER IN THICKNESS (I.E.
STRUCTURAL STEEL MATERIALS)
7.5. ALL WELDING SHALL BE INSPECTED AND TESTED IN ACCORDANCE WITH AWS D1.1 OR
D1.3 AS APPROPRIATE TO THE MATERIAL THICKNESS.
7.6. THE TESTING AGENCY SHALL VERIFY THAT THE METAL DECK IS ATTACHED TO THE
STRUCTURAL STEEL IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND
APPROVED SHOP DRAWINGS.
7.7. CONCRETE TESTING SHALL BE IN ACCORDANCE WITH ACI 301 CHAPTER 16 AND
APPROPRIATE AND WITH THE PROJECT SPECIFICATIONS.
8.0. CONSTRUCTION AND SAFETY:
8.1. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL SAFETY REGULATIONS, PROGRAMS
AND PRECAUTIONS RELATED TO ALL WORK ON THIS PROJECT.
8.2. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE PROTECTION OF PERSONS AND
PROPERTY EITHER ON OR ADJACENT TO THE PROJECT AND SHALL PROTECT SAME
AGAINST INJURY, DAMAGE OR LOSS.
8.3. MEANS AND METHODS OF CONSTRUCTION AND ERECTION OF STRUCTURAL MATERIALS ARE
SOLELY THE CONTRACTOR'S RESPONSIBILITY.
8.4. STRUCTURAL DRAWINGS ARE INTENDED TO BE USED IN CONJUNCTION WITH THE
DRAWINGS OF OTHER CONSULTANTS AND TRADES. THE CONTRACTOR SHALL COORDINATE
THE VARIOUS REQUIREMENTS.
8.5. NO OPENINGS NOR ANY CHANGES IN SIZE, DIMENSION OR LOCATION SHALL BE MADE
IN ANY STRUCTURAL ELEMENTS WITHOUT WRITTEN APPROVAL OF THE STRUCTURAL
ENGINEER.
8.6. OPENINGS 1'-0" OR LESS ON A SIDE ARE GENERALLY NOT SHOWN ON THE STRUCTURAL
DRAWINGS. REFER TO DRAWINGS OF OTHER CONSULTANTS FOR SUCH OPENINGS.
8.7. FIREPROOFING OF STRUCTURAL ELEMENTS IS NOT SHOWN ON THE STRUCTURAL
DRAWINGS. REFER TO THE SPECIFICATIONS AND ARCHITECTURAL DRAWINGS FOR FIRE
RATING REQUIREMENTS, MATERIALS AND METHODS.
8.8. THE CONTRACTOR IS RESPONSIBLE FOR LIMITING THE AMOUNT OF CONSTRUCTION LOAD
IMPOSED ON THE STRUCTURE. SUCH LOADS SHALL NOT EXCEED THE CAPACITY OF THE
STRUCTURE AT ANY TIME.
8.9. THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION, AND ANY
TEMPORARY BRACING OR SUPPORT REQUIRED TO ACCOMMODATE THE CONTRACTOR'S
MEANS AND METHODS ARE THE RESPONSIBILITY OF THE CONTRACTOR.
8.10. THE CONTRACTOR SHALL INFORM THE STRUCTURAL ENGINEER, CLEARLY AND
EXPLICITLY IN WRITING, OF ANY DEVIATION OR SUBSTITUTION OF REQUIREMENTS
OF THE CONTRACT DOCUMENTS. CONTRACTOR IS NOT RELIEVED OF ANY REQUIREMENTS
OF THE CONTRACT DOCUMENTS BY VIRTUE OF THE STRUCTURAL ENGINEER'S REVIEW
OF SHOP DRAWINGS, PRODUCT DATA, ETC., UNLESS THE CONTRACTOR HAS CLEARLY
AND EXPLICITLY INFORMED THE STRUCTURAL ENGINEER IN WRITING OF ANY
DEVIATIONS OR SUBSTITUTIONS AT TIME OF SUBMISSION, AND THE STRUCTURAL
ENGINEER HAS GIVEN WRITTEN APPROVAL FOR THE SPECIFIC DEVIATIONS OR
SUBSTITUTIONS.
8.11. ALL THINGS WHICH, IN THE OPINION OF THE CONTRACTOR, APPEAR TO BE
DEFICIENCIES, OMISSIONS, CONTRADICTIONS OR AMBIGUITIES IN THE DRAWINGS OR
SPECIFICATIONS, SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL
ENGINEER. CORRECTIONS OR WRITTEN INTERPRETATIONS SHALL BE ISSUED BEFORE
AFFECTED WORK MAY PROCEED.
8.12. IF THE CONTRACTOR CANNOT CONSTRUCT ANY PORTION OF THE WORK IDENTIFIED IN
THE DRAWINGS IN ACCORDANCE WITH THESE DRAWINGS AND SPECIFICATIONS, THEN
THE CONTRACTOR IS RESPONSIBLE FOR CONTACTING THE STRUCTURAL ENGINEER PRIOR
TO PROCEEDING WITH THE WORK. WORK THAT DOES NOT COMPLY WITH THE DRAWINGS
MAY REQUIRE REMOVAL, TESTING, OR ENGINEERING EVALUATION AT THE
CONTRACTOR'S EXPENSE.
8.13. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO ORDERING
MATERIALS OR PROCEEDING WITH NEW WORK IN AREAS AFFECTED BY EXISTING
CONDITIONS. STRUCTURAL ENGINEER SHALL BE INFORMED IN WRITING OF
CONFLICTS BETWEEN EXISTING AND PROPOSED NEW CONSTRUCTION.
8.14 CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL DIMENSIONS SHOWN ON THE
CONTRACT DOCUMENTS. INCONSISTENCIES ON THE STRUCTURAL DRAWINGS OR
BETWEEN THE STRUCTURAL DRAWINGS AND ANY OTHER CONTRACT, SHOP, FABRICATION,
OR OTHER DRAWINGS OR INFORMATION SHALL BE BROUGHT TO THE ATTENTION OF THE
STRUCTURAL ENGINEER PRIOR TO PROCEEDING WITH AFFECTED WORK.
8.15. DO NOT SCALE THESE DRAWINGS, USE THE DIMENSIONS SHOWN.
8.16. CONTRACTOR SHALL PROVIDE IN HIS SCHEDULE FOR A SHOP DRAWING REVIEW AND
RETURN TIME OF A MINIMUM OF FIFTEEN (15) WORKING DAYS IN THE STRUCTURAL
ENGINEER'S OFFICE.
9.0 STRUCTURAL ABBREVIATIONS:
ABBREV. DEFINITION ABBREV. DEFINITION
A.B. ANCHOR BOLTS HOF HORIZONTAL OUTER FAC
ABV ABOVE HK HOOK
ADDNL ADDITIONAL HORZ HORIZONTAL
AFF ABOVE FINISHED FLOOR IF INNER FACE
ALT ALTERNATE INT INTERIOR
ARCH ARCHITECTURAL JT JOINT
B, BOT BOTTOM K KIPS (1000 LBS)
B/XXX BOTTOM OF XXX L, LEN LENGTH
BAL. BALANCE LAT LATERAL
BB BOND BEAM LBS POUNDS
BCX BOTTOM CHORD EXTENSION LE LEFT END
BL BRICK LEDGE LLH LONG LEG HORIZONTAL
BLDG BUILDING LLO LONG LEG OUTSTANDING
BLW BELOW LLV LONG LEG VERTICAL
BM BEAM LONG LONGITUDINAL
BRG BEARING MAS MASONRY
BRK BRICK MAX MAXIMUM
BTWN BETWEEN MECH MECHANICAL
CFMF COLD-FORMED METAL FRAMING MFR MANUFACTURER
CJ CONST., CONTROL JOINT MIN MINIMUM
CL,CLR CLEAR MTL METAL
CMU CONC. MASONRY UNIT NOM NOMINAL
COL COLUMN OC, O/C ON CENTER
CONC CONCRETE OF OUTER FACE, OPP. FACE
CONN CONNECTION OH OPPOSITE HAND
CONST CONSTRUCTION OPP OPPOSITE
CONT CONTINUOUS OPNG OPENING
CTR CENTER PC PRECAST
CTRD CENTERED PL PLATE
DBA DEFORMED BAR ANCHOR RE RIGHT END
DET,DTL DETAIL REINFG REINFORCING
DIM DIMENSION REINF REINFORCEMENT
DK DECK REQD REQUIRED
DWGS DRAWINGS RET RETAINING
DWL DOWEL SOG SLAB ON GRADE
EA EACH SC SLIP CRITICAL
EE EACH END SCHED SCHEDULE
EF EACH FACE SECT SECTION
EFF EFFECTIVE S, SHRT SHORT
EJ EXPANSION JOINT SL SLAB
EL,ELEV ELEVATION SPA SPACING
EOC EDGE OF CONCRETE STFNR STIFFENER
EOD EDGE OF DECK STL STEEL
EOM EDGE OF MASONRY SUPPL SUPPLIER
EOS EDGE OF SLAB SUPT SUPPORT
ES EACH SIDE T TOP
EW EACH WAY T/XXX TOP OF XXX
EXIST EXISTING TCX TOP CHORD EXTENSION
EXP EXPANSION THK THICK, THICKNESS
EXT EXTERIOR, EXTENSION TO THROUGHOUT
FK FOOT-KIPS TRAN TRANSVERSE
FL, FLR FLOOR TYP TYPICAL
FOB FACE OF BRICK UNO UNLESS NOTED OTHERWISE
FOM FACE OF MASONRY VERT VERTICAL
FOS FACE OF STUD VEF VERTICAL EACH FACE
FP FULL PENETRATION VIF VERTICAL INNER FACE
FS FOOTING STEP VOF VERTICAL OUTER FACE
FT FOOT, FEET W WIDE, WIDTH
FTG FOOTING WWF WELDED WIRE FABRIC
GB GRADE BEAM WWM WELDED WIRE MAT
GEN GENERAL XE EXTENDED END JOIST
HEF HORIZONTAL EACH FACE
HIF HORIZONTAL INNER FACE
4.0. STRUCTURAL STEEL:
4.1. ALL STRUCTURAL STEEL SHALL BE OF THE GRADES INDICATED BELOW, UNLESS NOTED
OTHERWISE ON PLANS OR DETAILS:
A. WIDE FLANGE SHAPES ASTM A992 GR50.
B. OTHER ROLLED SHAPES ASTM A36 TYPICALLY, U.N.O.
C. ANCHOR BOLTS ASTM F1554 GR36 U.N.O.
D. STRUCTURAL TUBING (SQUARE AND RECTANGULAR) ASTM A500, GRADE B, FY=46 KSI.
E. STRUCTURAL TUBING (ROUND) ASTM A500, GRADE B, FY=42 KSI.
F. PLATES AND BARS ASTM A36 U.N.O.
G. MISCELLANEOUS ASTM A36 U.N.O.
4.2. ALL STRUCTURAL STEEL SHALL BE DETAILED AND, FABRICATED IN ACCORDANCE WITH
THE AISC CODE OF STANDARD PRACTICE AS MODIFIED IN THESE NOTES AND THE
PROJECT SPECIFICATIONS.
4.3. SUBMIT SHOP DRAWINGS FOR DETAILS, FABRICATION, AND ERECTION OF STRUCTURAL
STEEL. COMPLY WITH AISC "STEEL CONSTRUCTION MANUAL", AISC "DETAILING FOR
STEEL CONSTRUCTION", AND AISC "ENGINEERING FOR STEEL CONSTRUCTION"
PUBLICATIONS.
4.4. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMISSION.
DRAWINGS SHALL BEAR THE CONTRACTOR'S APPROVAL STAMP ACCEPTING
RESPONSIBILITY FOR DIMENSIONS, QUANTITIES AND COORDINATION WITH THE OTHER
TRADES.
4.5. DRAWINGS MAY BE ELECTRONICALLY SUBMITTED, PROVIDED LEGIBILITY IS MAINTAINED.
REVIEW COMMENTS ONLY WILL BE ELECTRONICALLY FORWARDED TO THE CONTRACTOR.
4.6. CONTRACTOR SHALL PROVIDE IN HIS SCHEDULE FOR A SHOP DRAWING REVIEW AND
RETURN TIME OF A MINIMUM OF FIFTEEN (15) WORKING DAYS IN THE STRUCTURAL
ENGINEER'S OFFICE.
6.18. WELDED CONNECTIONS:
A. CONTRACTOR SHALL REQUIRE THAT AWS QUALIFICATION TESTS FOR WELDING
OF MATERIAL LESS THAN 1/8" IN THICKNESS ARE SATISFACTORILY PASSED BY
WELDERS EXPECTED TO ERECT LIGHTGAGE FRAMING MATERIALS. THESE TESTS
ARE NOT THE SAME AS FOR STRUCTURAL STEEL WELDING QUALIFICATION.
B. USE GAS METAL ARC WELDING (GMAW) FOR 20 GA. OR LIGHTER MEMBERS. AWS
E-705-3, E-705-5, E-705-6 WIRE ELECTRODES OF .030" TO .035" DIAMETER
SHALL BE USED WITH CARBON DIOXIDE, ARGON-OXYGEN, OR ARGON-CARBON
DIOXIDE GAS SHIELDING. WELDING EQUIPMENT SHALL PROVIDE 60 TO 100
AMPERES AT 25 VOLTS USING 220-VOLT 3-PHASE ELECTRIC SERVICE.
C. SHIELDED METAL ARC WELDING (SMAW) SHALL BE USED FOR 18 GA. AND HEAVIER
MEMBERS. AWS E-6012, E-6013, OR E-7014 ELECTRODES OF 3/32" OR…