About this file
The document is an Asbestos Testing Report for Building 34 at F.E. Warren Air Force Base in Cheyenne, Wyoming, conducted by Asbestos & Technical Services, Inc. on April 25, 2024. The comprehensive inspection involved taking 40 total samples across the 1st, 2nd, and 3rd floors, examining various materials including vinyl cove bases, carpet, drywall, floor sealants, glue, and concrete surfaces. Critically, the report conclusively found no asbestos-containing materials (ACM) in any of the samples tested, which is significant for the related carpet replacement solicitation (FA461325Q0012) for the Security Forces Group building.
The testing report was prepared using EPA and OSHA guidelines, with samples analyzed through polarized light microscopy at CA Labs. The inspection methodology included non-destructive sampling protocols and followed industry standards for identifying potentially hazardous materials. The report emphasizes that while the inspection was thorough, it cannot guarantee absolute elimination of all potential asbestos-containing materials, and recommends stopping work and testing any newly discovered suspect materials during future renovation or demolition activities.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SF 30 - FA461325Q00120004.pdf | ||
| SF 30 - FA461325Q00120003.pdf | ||
| Attachment 6 - Post Site Visit Questions and Answers.pdf | ||
| Attachment 7 - Brand Name or Equal JA (Redacted).pdf | ||
| SF 30 - FA461325Q00120001.pdf | ||
| Attachment 5 - Hazmat Auth Request.pdf | ||
| Attchment 2 - B34 Drawings.pdf | ||
| Solicitation - FA461325Q0012.pdf | ||
| Attachment 1 - Performance Work Statement 03 Feb 25.pdf | ||
| Attachment 4 - Salient Characteristics.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Asbestos & Technical Services, Inc P.O. Box 2574
Cheyenne, WY 82003
307-214-0904
Asbestos & Lead Inspection Report
April 30, 2024
Chris Carter
Project: FE Warren AFB, Building 34 (1st Floor, 2nd Floor, Attic -Carpet Replacement)
Cheyenne, WY 82001
Dear Mr. Carter, On April 25, 2024, ATS performed an asbestos inspection of the above-mentioned project. The purpose of the survey is to identify asbestos containing material (ACM) using nondestructive sampling protocols.
Inspection, sampling and analytical procedures were performed in general accordance with the Environmental Protection
Agency’s (EPA) interpretations, and guidelines of the Asbestos Hazardous Emergency Response Act (AHERA).
Asbestos containing materials as defined by the Occupational Safety and Health Administration (OSHA), the Environmental
Protection Agency and the State of Wyoming are material with asbestos concentration greater than 1% (>1%) by volume.
However, OSHA governs asbestos exposures to employees above the Permissible Exposure Limit regardless of asbestos containing material concentration.
No inspection can eliminate the uncertainty regarding the presence of ACM. ATS’s level of diligence and investigative procedures are intended to reduce, but not eliminate potential uncertainty regarding the presence of ACM. The determinations in this report should not be constructed as a guarantee that all ACM present in the subject property has been included in this report.
The inspection was performed in a manner consistent with the level of care and expertise exercised by members of the asbestos inspection and assessment profession. Those entities and persons involved with the inspection and generation of this report do not imply or guarantee that all potential ACM on or in the building has been identified and sampled.
Historically, asbestos has been added as a component to over 3,000 materials and products produced in the United States.
The inspection was intended to identify those accessible materials that were reasonable suspect and that were most likely to contain asbestos in quantities subject to regulation, based on existing industry and regulatory standards.
If suspect material is discovered during renovation or demolition, work needs to be stopped and suspect material needs to be tested prior to proceeding.
Total samples taken: 40
FIELD NOTES AND SAMPLE LOCATIONS:
Sample #/Description Location:
1ST FLOOR – INTERIOR:
• 042524-B34-1 Grey vinyl cove base and tan glue on drywall Room #151
• 042524-B34-2 Blue and tan rolled carpet flooring on wood Room #151
• 042524-B34-3 Drywall with orange-peel texture Room #151
• 042524-B34-4 Yellow floor sealant under carpet, on wood Hall
• 042524-B34-5 Grey carpet square and tan glue Hall
• 042524-B34-6 Grey cove base and drywall texture Room #180
• 042524-B34-7 Blue and tan rolled carpet Room #180
• 042524-B34-8 Brown cove base Room #180
• 042524-B34-9 Blue and tan carpet Room #169
• 042524-B34-10 Floor sealants under carpet Room #169
• 042524-B34-11 Grey carpet square Hall
• 042524-B34-12 Floor sealants Hall
• 042524-B34-13 Black and grey high traffic carpet South Entrance
• 042524-B34-14 Grey transition strip South Entrance
• 042524-B34-15 Black and grey high traffic carpet South Entrance
• 042524-B34-16 Brown cove base Hall
• 042524-B34-17 Drywall with orange-peel texture Hall
• 042524-B34-18 Light brown cove base Room #104
• 042524-B34-19 Pink/purple/blue rolled carpet Room #104
2ND FLOOR – INTERIOR:
• 042524-B34-20 Remnant black glue near elevator transition Hall #240
• 042524-B34-21 Drywall with orange-peel texture Hall #240
• 042524-B34-22 Caulking and remnant orange glue near wall to floor corner Hall
• 042524-B34-23 Tan carpet (remnant) Hall
• 042524-B34-24 Remnant orange/brown glue on painted CMU block wall, North Hall
• 042524-B34-25 Drywall with orange-peel texture Hall
• 042524-B34-26 Grey and black striped carpet square Hall
• 042524-B34-27 Blue and tan rolled carpet Room #292
• 042524-B34-28 Tan glue on wood floor Room #292
• 042524-B34-29 Grey cove base Room #292
• 042524-B34-30 Grey cove base Room #214
• 042524-B34-31 Drywall with orange-peel texture Room #214
• 042524-B34-32 Pink/orange vinyl transition bar Room #214
3RD FLOOR – INTERIOR:
• 042524-B34-33 CMU mortar, Northwest wall Room #304C
• 042524-B34-34 Remnant orange/brown glue on painted CMU block wall, North Room #304C
• 042524-B34-35 Sealants on CMU block wall Room #304C
• 042524-B34-36 Brown and grey striped carpet square Hallway
• 042524-B34-37 Black mastic on wood underlayment Room #312
• 042524-B34-38 Terrazzo rock flooring Room #312
• 042524-B34-39 Concrete floor fill Room #312
• 042524-B34-40 Plaster and skim-coat Room #312
FINDINGS:
None of the samples collected above were found to contain asbestos. Please refer to the attached CA Lab results.
Please feel free to contact me with any questions.
Sincerely, Nate Challenger
Asbestos Building Inspector
Attn:
Customer Project:
Reference #: Date: 04/30/24
Analysis and Method
Discussion
Qualifications
CA Labs Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road Carrollton, TX 75006 Phone 972-242-2754 Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32 Baton Rouge, LA 70809 Phone 225-751-5632 Fax 225-751-5634
Materials Characterization - Bulk Asbestos Analysis Laboratory Analysis Report - Polarized Light
Asbestos & Technical Services P.O. Box 2574
Cheyenne, WY 82003
David Blackwell
042524-B34, FE Warren AFB, B34
CAL24043269AS
Summary of polarized light microscopy (PLM / Stereomicroscopy bulk asbestos analysis) using the methods described in 40CFR Part 763
Appendix E to Subpart E (Interim and EPA 600 / R-93 / 116 (Improved). The sample is first viewed with the aid of a stereomicroscope. Numerous liquid slide preparations are created for analysis under the polarized microscope where identifications and quantifications are preformed. Calibrated liquid refractive oils are used as liquid mouting medium. These oils are used for identification (dispersion staining). A calibrated visual estimation is reported, should any asbestiform mineral be present. Other techniques such as acid washing are used in conjugation with refractive oils for detection of smaller quantities of asbestos. All asbestos percentages are based on calibrated visual estimation traceable to NIST standards for regulated asbestos. Traceability to measurement and calibration is achieved by using known amounts and types of asbestos from standards where analyst and laboratory accuracy are measured. As little as 0.001% asbestos can be detected in favorable samples, while detection in unfavorable samples may approach the detection limit of 0.50% (well above the laboratory definition of trace).
Vermiculite containing samples may contain trace amounts of actinolite/tremolite. When not detected by PLM, these samples should be analyzed using TEM methods and / or water separation techniques. Suspected actinolite/vermiculite presence will be indicated through the sample comment section of this report.
Fibrous talc containing samples may contain a regulated asbestos fiber known as anthophyllite. Under certain conditions the same fiber may actually contain both talc and anthophyllite (a phenomenon called intergrowth). Again, TEM detection methods are recommended. CA Labs PLM report comments will denote suspected amounts of asbestiform anthophyllite with talc, where further analysis is recommended.
Some samples (floor tiles, surfacings, etc.) may contain fibers too small to be detectable by PLM analysis and should be analyzed by TEM bulk protocols.
A "trace asbestos" will be reported if the analyst observes far less than 1% asbestos. CA Labs defines "trace asbestos" as a few fibers detected by the analyst in several preparations and will indicate as such under these circumstances.
Since allowable variation in quantification of samples close to 1% is high, <1% may be reported. Such results are ideal for point counting, and the technique is mandatory for friable samples (NESHAP, Nov. 1990 and clarification letter 8 May 1991) under 1% percent asbestos or "trace asbestos".
In order to make all initial PLM reports issued from CA Labs NESHAP compliant, all <1% asbestos results (except floor tiles) will be point counted at no additional charge.
CA Labs is accredited by the National Voluntary Accreditation Program (NVLAP) for selected test methods for airborne fiber analysis (TEM), and for bulk asbestos fiber analysis (PLM). CA Labs is also accredited by AIHA LAP, LLC. in the PLM asbestos field of testing for Industrial Hygiene. All analysts have completed college courses or hold a degree in a natural science (geology, biology, or environmental science). Recognition by a state professional board in one these disciplines is preferred, but not required. Extensive in-house training programs are used to augment the educational background of the analyst. The Laboratory Director and Quality Manager have received supplemental McCrone Research training for asbestos identification. Analysis performed at Crisp Analytical Labs, LLC 1929 Old Denton Road Carrollton, TX 75006
Dallas NVLAP Lab Code 200349-0 TEM/PLM TDSHS 30-0235 AIHA LAP, LLC Laboratory #102929
Labs
A
C
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 6 10/30/2023) Page 1 of 10
Customer Project: 042524-B34, FE Warren AFB, B34 CA Labs Project #: CAL24043269AS
No Asbestos Detected.
Glossary of abbreviations (non-asbestos fibers and non-fibrous minerals):
CA Labs Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road Carrollton, TX 75006 Phone 972-242-2754 Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32 Baton Rouge, LA 70809 Phone 225-751-5632 Fax 225-751-5634
Overview of Project Sample Material Containing Asbestos
Laboratory
Sample ID
Sample # Layer # Analysts Physical Description of
Subsample
Asbestos type / calibrated visual estimate percent
List of Affected
Building Material
Types
Dallas NVLAP Lab Code 200349-0 TEM/PLM TDSHS 30-0235 AIHA LAP, LLC Laboratory #102929 ca - carbonate gypsum - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastinite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
This report relates to the items tested as received. This report is not to be used by the customer to claim product certification, approval or endorsement by NVLAP, NIST, AIHA LAP, LLC, or any other agency of the federal government. This report may not be reproduced except in full without written permission from CA Labs. These results are submitted pursuant to CA Labs' current terms and sale, condition of sale, including the company's standard warranty and limitations of liability provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted.
Unless notified in writing to return the samples covered by this report, CA Labs will store the samples for a period of ninety (90) days before discarding. A shipping or handling fee may be assessed for the return of any samples.
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 6 10/30/2023) Page 2 of 10
Customer Info: Attn:
Date:
Phone #
Fax #
Justin Cox Senior Analyst
Analyst Julio Robles
CA Labs Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road Carrollton, TX 75006 Phone 972-242-2754 Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32 Baton Rouge, LA 70809 Phone 225-751-5632 Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
David Blackwell CA Labs Project #:
Asbestos & Technical Services CAL24043269AS
P.O. Box 2574
Cheyenne, WY 82003
Customer Project:
042524-B34, FE Warren AFB, B34 Turnaround Time: 4/30/2024
2 Days Samples Rec'd: 4/26/24 10:30AM
307-214-0904 Date Of Sampling: 4/25/2024
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
36964
042524-B34-
1 1-1 Cove Base/ gray baseboard y None Detected 100% gy,ma
36964 1-2 tan mastic y None Detected 100% gy,bi
36965
042524-B34-
2 2-1 Carpet/ blue carpeting y None Detected 100% sy
36965 2-2 tan mastic y None Detected 100% gy,bi
36966
042524-B34-
3 3-1
100% gy,bi,ot
Drywall/ tan drywall with brown paper n None Detected 15% ce
5-1
85% qu,gy
36967
042524-B34-
4 4-1 Floor Sealant/ tan mastic with debris n None Detected
Dallas NVLAP Lab Code 200349-0 TEM/PLM TDSHS 30-0235 AIHA LAP, LLC Laboratory #102929
Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
Carpet/ black carpeting y None Detected 100% sy36968
042524-B34-
Approved Signatories:
Technical Manager ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
Tanner Rasmussen
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
10. TEM analysis suggested
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 6 10/30/2023) Page 3 of 10
Phone #
Fax #
Justin Cox Senior Analyst
Analyst Julio Robles
CA Labs Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road Carrollton, TX 75006 Phone 972-242-2754 Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32 Baton Rouge, LA 70809 Phone 225-751-5632 Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
David Blackwell CA Labs Project #:
Asbestos & Technical Services CAL24043269AS
P.O. Box 2574
Cheyenne, WY 82003
Customer Project:
042524-B34, FE Warren AFB, B34 Turnaround Time: 4/30/2024
2 Days Samples Rec'd: 4/26/24 10:30AM
307-214-0904 Date Of Sampling: 4/25/2024
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
36969
042524-B34-
6 6-1 Cove Base/ gray baseboard y None Detected 100% gy,ma
36969 6-2 tan mastic y None Detected 100% gy,bi
36970
042524-B34-
7 7-1 Carpet/ black carpeting y None Detected 100% sy
36971
042524-B34-
8 8-1 Cove Base/ brown baseboard y None Detected 100% gy,ma
36972
042524-B34-
9 9-1
100% gy,bi
Carpet/ blue carpeting y None Detected 100% sy
10-2
36973
042524-B34-
10 10-1 Floor Sealant/ tan mastic y None Detected
100% qu,ca
Dallas NVLAP Lab Code 200349-0 TEM/PLM TDSHS 30-0235 AIHA LAP, LLC Laboratory #102929
Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
gray grouting y None Detected36973
Approved Signatories:
Technical Manager ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
Tanner Rasmussen
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 6 10/30/2023) Page 4 of 10
Phone #
Fax #
Justin Cox Senior Analyst
Analyst Julio Robles
CA Labs Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road Carrollton, TX 75006 Phone 972-242-2754 Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32 Baton Rouge, LA 70809 Phone 225-751-5632 Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
David Blackwell CA Labs Project #:
Asbestos & Technical Services CAL24043269AS
P.O. Box 2574
Cheyenne, WY 82003
Customer Project:
042524-B34, FE Warren AFB, B34 Turnaround Time: 4/30/2024
2 Days Samples Rec'd: 4/26/24 10:30AM
307-214-0904 Date Of Sampling: 4/25/2024
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
36974
042524-B34-
11 11-1 Carpet/ black carpeting y None Detected 100% sy
36975
042524-B34-
12 12-1 Floor Sealant/ tan mastic y None Detected 100% gy,bi
36975 12-2 gray grouting y None Detected 100% qu,ca
36976
042524-B34-
13 13-1 Carpet/ black carpeting y None Detected 100% sy
36977
042524-B34-
14 14-1
100% sy
Transition Strip/ brown baseboard y None Detected
16-1
100% gy,ma
36978
042524-B34-
15 15-1 Carpet/ black carpeting y None Detected
100% gy,ma
Dallas NVLAP Lab Code 200349-0 TEM/PLM TDSHS 30-0235 AIHA LAP, LLC Laboratory #102929
Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
Cove Base/ brown baseboard y None Detected36979
042524-B34-
Approved Signatories:
Technical Manager ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
Tanner Rasmussen
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 6 10/30/2023) Page 5 of 10
Phone #
Fax #
Justin Cox Senior Analyst
Analyst Julio Robles
CA Labs Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road Carrollton, TX 75006 Phone 972-242-2754 Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32 Baton Rouge, LA 70809 Phone 225-751-5632 Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
David Blackwell CA Labs Project #:
Asbestos & Technical Services CAL24043269AS
P.O. Box 2574
Cheyenne, WY 82003
Customer Project:
042524-B34, FE Warren AFB, B34 Turnaround Time: 4/30/2024
2 Days Samples Rec'd: 4/26/24 10:30AM
307-214-0904 Date Of Sampling: 4/25/2024
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
36980
042524-B34-
17 17-1 Drywall/ white surfaced white compound n None Detected
100% mi,qu,bi,ca
36980 17-2 tan drywall with brown paper n None Detected 15% ce 85% qu,gy
36981
042524-B34-
18 18-1 Carpet/ brown baseboard y None Detected 100% gy,ma
36982
042524-B34-
19 19-1 Cove Base/ gray carpeting y None Detected 100% sy
36983
042524-B34-
20 20-1
100% mi,qu,bi,ca
Transition Strip/ tan mastic with debris n None Detected
22-1
100% gy,bi,ot
36984
042524-B34-
21 21-1 Drywall/ white surfaced white compound n None Detected
100% qu,bi,ca
Dallas NVLAP Lab Code 200349-0 TEM/PLM TDSHS 30-0235 AIHA LAP, LLC Laboratory #102929
Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
Caulking/ white surfaced red caulking n None Detected36985
042524-B34-
Approved Signatories:
Technical Manager ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
Tanner Rasmussen
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 6 10/30/2023) Page 6 of 10
Phone #
Fax #
Justin Cox Senior Analyst
Analyst Julio Robles
CA Labs Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road Carrollton, TX 75006 Phone 972-242-2754 Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32 Baton Rouge, LA 70809 Phone 225-751-5632 Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
David Blackwell CA Labs Project #:
Asbestos & Technical Services CAL24043269AS
P.O. Box 2574
Cheyenne, WY 82003
Customer Project:
042524-B34, FE Warren AFB, B34 Turnaround Time: 4/30/2024
2 Days Samples Rec'd: 4/26/24 10:30AM
307-214-0904 Date Of Sampling: 4/25/2024
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
36986
042524-B34-
23 23-1 Carpet/ gray carpeting y None Detected 100% sy
36987
042524-B34-
24 24-1 Drywall/ white surfaced white compound n None Detected
100% mi,qu,bi,ca
36988
042524-B34-
25 25-1 Cove Base/ black baseboard y None Detected 100% gy,ma
36989
042524-B34-
26 26-1 Carpet/ gray carpeting y None Detected 100% sy
36990
042524-B34-
27 27-1
100% gy,bi
Carpet/ blue carpeting y None Detected 100% sy
29-1
36991
042524-B34-
28 28-1 Glue/ tan mastic y None Detected
100% gy,ma
Dallas NVLAP Lab Code 200349-0 TEM/PLM TDSHS 30-0235 AIHA LAP, LLC Laboratory #102929
Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
Cove Base/ gray baseboard y None Detected36992
042524-B34-
Approved Signatories:
Technical Manager ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
Tanner Rasmussen
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 6 10/30/2023) Page 7 of 10
Phone #
Fax #
Justin Cox Senior Analyst
Analyst Julio Robles
CA Labs Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road Carrollton, TX 75006 Phone 972-242-2754 Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32 Baton Rouge, LA 70809 Phone 225-751-5632 Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
David Blackwell CA Labs Project #:
Asbestos & Technical Services CAL24043269AS
P.O. Box 2574
Cheyenne, WY 82003
Customer Project:
042524-B34, FE Warren AFB, B34 Turnaround Time: 4/30/2024
2 Days Samples Rec'd: 4/26/24 10:30AM
307-214-0904 Date Of Sampling: 4/25/2024
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
36993
042524-B34-
30 30-1 Cove Base/ gray baseboard y None Detected 100% gy,ma
36993 30-2 tan mastic y None Detected 100% gy,bi
36994
042524-B34-
31 31-1 Drywall/ white drywall with brown paper n None Detected 15% ce 85% qu,gy
36995
042524-B34-
32 32-1 Transition Bar/ brown baseboard y None Detected 100% gy,ma
36995 32-2
100% sy tan mastic y None Detected
34-1
100% gy,bi
36996
042524-B34-
33 33-1 Carpet/ brown carpeting y None Detected
100% gy,ma
Dallas NVLAP Lab Code 200349-0 TEM/PLM TDSHS 30-0235 AIHA LAP, LLC Laboratory #102929
Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
Cove Base/ brown baseboard y None Detected36997
042524-B34-
Approved Signatories:
Technical Manager ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
Tanner Rasmussen
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 6 10/30/2023) Page 8 of 10
Phone #
Fax #
Justin Cox Senior Analyst
Analyst Julio Robles
CA Labs Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road Carrollton, TX 75006 Phone 972-242-2754 Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32 Baton Rouge, LA 70809 Phone 225-751-5632 Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
David Blackwell CA Labs Project #:
Asbestos & Technical Services CAL24043269AS
P.O. Box 2574
Cheyenne, WY 82003
Customer Project:
042524-B34, FE Warren AFB, B34 Turnaround Time: 4/30/2024
2 Days Samples Rec'd: 4/26/24 10:30AM
307-214-0904 Date Of Sampling: 4/25/2024
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
36997 34-2 tan mastic y None Detected 100% gy,bi
36998
042524-B34-
35 35-1 Drywall/ tan surfaced white compound n None Detected
100% mi,qu,bi,ca
36998 35-2 tan drywall with brown paper n None Detected 10% ce 90% qu,gy
36999
042524-B34-
36 36-1 Carpet/ gray carpeting y None Detected 100% sy
37000
042524-B34-
37 37-1
100% qu,ma,ot
Mastic/ black felt y None Detected 35% ce
39-1
65% qu,bi
37001
042524-B34-
38 38-1 Terrazzo/ red terrazzo tile y None Detected
100% qu,ca
Dallas NVLAP Lab Code 200349-0 TEM/PLM TDSHS 30-0235 AIHA LAP, LLC Laboratory #102929
Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
Floor Sealant/ gray concrete y None Detected37002
042524-B34-
Approved Signatories:
Technical Manager ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
Tanner Rasmussen
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 6 10/30/2023) Page 9 of 10
Phone #
Fax #
Justin Cox Senior Analyst
Analyst Julio Robles
CA Labs Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road Carrollton, TX 75006 Phone 972-242-2754 Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32 Baton Rouge, LA 70809 Phone 225-751-5632 Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
David Blackwell CA Labs Project #:
Asbestos & Technical Services CAL24043269AS
P.O. Box 2574
Cheyenne, WY 82003
Customer Project:
042524-B34, FE Warren AFB, B34 Turnaround Time: 4/30/2024
2 Days Samples Rec'd: 4/26/24 10:30AM
307-214-0904 Date Of Sampling: 4/25/2024
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
37003
042524-B34-
40 40-1 Plaster/ green surfaced white finishing compound n None Detected
100% qu,bi,ca
37003 40-2 gray plaster y None Detected 100% qu,bi,ca
Dallas NVLAP Lab Code 200349-0 TEM/PLM TDSHS 30-0235 AIHA LAP, LLC Laboratory #102929
Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay) Approved Signatories:
Technical Manager
Tanner Rasmussen
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 6 10/30/2023) Page 10 of 10
Cheyenne, WY 82003
Asbestos & Lead Inspection Report
February 10, 2023
Chris Carter
Project: FE Warren AFB, Building 34 (SFG 2nd Floor Carpet Replacement)
Cheyenne, WY 82001
Dear Mr. Carter, On February 7, 2023, ATS performed an asbestos inspection of the above-mentioned project. The purpose of the survey is to identify asbestos containing material (ACM) using nondestructive sampling protocols.
Inspection, sampling and analytical procedures were performed in general accordance with the Environmental Protection
Agency’s (EPA) interpretations, and guidelines of the Asbestos Hazardous Emergency Response Act (AHERA).
Asbestos containing materials as defined by the Occupational Safety and Health Administration (OSHA), the Environmental
Protection Agency and the State of Wyoming are material with asbestos concentration greater than 1% (>1%) by volume.
However, OSHA governs asbestos exposures to employees above the Permissible Exposure Limit regardless of asbestos containing material concentration.
No inspection can eliminate the uncertainty regarding the presence of ACM. ATS’s level of diligence and investigative procedures are intended to reduce, but not eliminate potential uncertainty regarding the presence of ACM. The determinations in this report should not be constructed as a guarantee that all ACM present in the subject property has been included in this report.
The inspection was performed in a manner consistent with the level of care and expertise exercised by members of the asbestos inspection and assessment profession. Those entities and persons involved with the inspection and generation of this report do not imply or guarantee that all potential ACM on or in the building has been identified and sampled.
Historically, asbestos has been added as a component to over 3,000 materials and products produced in the United States.
The inspection was intended to identify those accessible materials that were reasonable suspect and that were most likely to contain asbestos in quantities subject to regulation, based on existing industry and regulatory standards.
If suspect material is discovered during renovation or demolition, work needs to be stopped and suspect material needs to
Total samples taken: 9
2ND FLOOR – INTERIOR:
• 020723-B34-1 Grey vinyl cove base and tan glue on drywall Room #292
• 020723-B34-2 Grey brick mortar and red brick wall Room #292
• 020723-B34-3 CMU mortar, Northwest wall Room #292
• 020723-B34-4 Remnant orange/brown glue on painted CMU block wall, North Room #292
• 020723-B34-5 Sealants on CMU block wall Room #290D
• 020723-B34-6 Pale yellow and painted paper wrapped pipe insulation Room #290D
• 020723-B34-7 Off-white fitting material and painted cloth wrap Room #290D
• 020723-B34-8 Brown insulation and tar paper (below roof deck) Room #290D
• 020723-B34-9 Black cove base and brown glue on CMU wall Hallway #290
FINDINGS:
None of the samples collected above were found to contain asbestos. Please refer to the attached CA Lab results.
LEAD INSPECTION NOTES:
On February 7, 2023, ATS performed non-invasive/non-destructive inspection services for FE Warren AFB, Building 34, Cheyenne Wyoming in the proposed work area. The purpose of this inspection was to identify where lead-based (LBP) may reside for planned building renovations and determine if corrective measures should be taken to minimize possible exposure. ATS tested the following:
Total samples taken: 4 (homogeneous throughout renovation areas)
Lead Analysis Location: Color Change:
• L-01, Tan paint on grey paint on drywall Interior- Room #290 - Side D NO
Testing Method: 3M Lead Test (swab) Kit.
RESULTS: After a 5-minute wait time, the sample collected above did not show signs of changing color and ATS assumes that the associated paint layers for Hallway #290 and the adjacent offices (5 areas) does not contain lead paint.
PHOTOS:
Background for Lead Test Kits:
On April 22, 2008, EPA published the Lead Renovation, Repair and Painting (RRP) rule, which, among other things, established performance recognition criteria for lead test kits for use as an option to determine if regulated lead-based paint is not present in target housing and child-occupied facilities. Currently, the EPA is reviewing the application and expansion of the RRP rule to include public and commercial buildings. According to the EPA, the use of an EPA-recognized lead test kit, when used by a trained professional, can reliably determine that regulated lead-based paint is not present by virtue of a negative result. The EPA recognizes that when used by a Certified Renovator, the 3M™ Lead Check™ lead test kit can reliably determine that regulated lead-based paint is not present on wood, ferrous metal (alloys that contain iron), or drywall and plaster surfaces. The results of swab testing are not quantitative. A positive result may indicate the presence of lead-based paint and should be dealt with by an EPA- RRP contractor or certified Lead Abatement firm.
IN
SP
EC
TIO
N
F.E. W A
R R
EN
A
.F.B ., B
, C H
EY
EN
N E W
Y:
B U
LK
SA
M P
LES FR
O
M
FEB
R U
A R
Y
, 2
N
D
FLO
O R
SFG
(n o t to scale
B u lk S a m p le
L o c a tio n s
N o n -d e te c t
T ra c e (0
-1
A
C M
(a b o v e
.0
T ra c e (0
-1
A
SB
ESTO
S &
TEC
H
N
IC
A L
SER
V
IC
ES, IN
C
N O R T H
2 3
5 6
A
D
B
C
S w ip e
S a m p le L o c a tio n s
N o
C o lo r C h a n g e C o lo r C h a n g e
S ta irs
L
Attn:
Reference #: Date: 02/09/23
Analysis and Method
Discussion
Qualifications
CA Labs
Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Materials Characterization - Bulk Asbestos Analysis Laboratory Analysis Report - Polarized Light
Asbestos & Technical Services David Blackwell
P.O. Box 2574
Cheyenne, WY 82003 020723-B34, FE Warren AFB, B34
CAL23021129AS
Summary of polarized light microscopy (PLM / Stereomicroscopy bulk asbestos analysis) using the methods described in 40CFR Part 763
Appendix E to Subpart E (Interim and EPA 600 / R-93 / 116 (Improved). The sample is first viewed with the aid of a stereomicroscope. Numerous liquid slide preparations are created for analysis under the polarized microscope where identifications and quantifications are preformed. Calibrated liquid refractive oils are used as liquid mouting medium. These oils are used for identification (dispersion staining). A calibrated visual estimation is reported, should any asbestiform mineral be present. Other techniques such as acid washing are used in conjugation with refractive oils for detection of smaller quantities of asbestos. All asbestos percentages are based on calibrated visual estimation traceable to NIST standards for regulated asbestos. Traceability to measurement and calibration is achieved by using known amounts and types of asbestos from standards where analyst and laboratory accuracy are measured. As little as 0.001% asbestos can be detected in favorable samples, while detection in unfavorable samples may approach the detection limit of 0.50% (well above the laboratory definition of trace).
Vermiculite containing samples may contain trace amounts of actinolite/tremolite. When not detected by PLM, these samples should be analyzed using TEM methods and / or water separation techniques. Suspected actinolite/vermiculite presence will be indicated through the sample comment section of this report.
Fibrous talc containing samples may contain a regulated asbestos fiber known as anthophyllite. Under certain conditions the same fiber may actually contain both talc and anthophyllite (a phenomenon called intergrowth). Again, TEM detection methods are recommended. CA Labs PLM report comments will denote suspected amounts of asbestiform anthophyllite with talc, where further analysis is recommended.
Some samples (floor tiles, surfacings, etc.) may contain fibers too small to be detectable by PLM analysis and should be analyzed by TEM bulk protocols.
A "trace asbestos" will be reported if the analyst observes far less than 1% asbestos. CA Labs defines "trace asbestos" as a few fibers detected by the analyst in several preparations and will indicate as such under these circumstances.
Since allowable variation in quantification of samples close to 1% is high, <1% may be reported. Such results are ideal for point counting, and the technique is mandatory for friable samples (NESHAP, Nov. 1990 and clarification letter 8 May 1991) under 1% percent asbestos or "trace asbestos".
In order to make all initial PLM reports issued from CA Labs NESHAP compliant, all <1% asbestos results (except floor tiles) will be point counted at no additional charge.
CA Labs is accredited by the National Voluntary Accreditation Program (NVLAP) for selected test methods for airborne fiber analysis (TEM), and for bulk asbestos fiber analysis (PLM). CA Labs is also accredited by AIHA LAP, LLC. in the PLM asbestos field of testing for Industrial Hygiene. All analysts have completed college courses or hold a degree in a natural science (geology, biology, or environmental science). Recognition by a state professional board in one these disciplines is preferred, but not required. Extensive in-house training programs are used to augment the educational background of the analyst. The Laboratory Director and Quality Manager have received supplemental McCrone Research training for asbestos identification. Analysis performed at Crisp Analytical Labs, LLC 1929 Old Denton Road Carrollton, TX 75006
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929
Labs
A
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 4 2/25/2020) Page 1 of 5
Customer Project: 020723-B34, FE Warren AFB, B34 CA Labs Project #: CAL23021129AS
Glossary of abbreviations (non-asbestos fibers and non-fibrous minerals):
CA Labs
Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Overview of Project Sample Material Containing Asbestos
Laboratory
Sample ID
Sample # Layer # Analysts Physical Description of
Subsample
Asbestos type / calibrated visual estimate percent
List of Affected
Building Material
Types
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929 ca - carbonate gypsum - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastinite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay)
This report relates to the items tested. This report is not to be used by the customer to claim product certification, approval or endorsement by NVLAP, NIST, AIHA LAP, LLC, or any other agency of the federal government. This report may not be reproduced except in full without written permission from CA Labs. These results are submitted pursuant to CA Labs' current terms and sale, condition of sale, including the company's standard warranty and limitations of liability provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted. Unless notified in writing to return the samples covered by this report, CA Labs will store the samples for a period of ninety (90) days before discarding. A shipping or handling fee may be assessed for the return of any samples.
Labs
A
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 4 2/25/2020) Page 2 of 5
Customer Info: Attn: Customer Project:
Phone #
Fax #
John Monaco Senior Analyst
Analyst Julio Robles
CA Labs
Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
David Blackwell CA Labs Project #:
Asbestos & Technical Services 020723-B34, FE Warren AFB, B34
CAL23021129AS
P.O. Box 2574
Cheyenne, WY 82003 Turnaround Time: 2/9/2023
24 Hours Samples Rec'd: 2/9/23 10:30AM
307-214-0904 Date Of Sampling: 2/7/2023
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
10750 B34-1 B34-1-
1 Cove Base/ gray baseboard y None Detected 100% gy,ma
10750 B34-1-
2 tan mastic y None Detected 100% gy,bi
10751 B34-2 B34-2-
Drywall/ tan surfaced white compound n None Detected 100% qu,bi,ca
10751 B34-2-
2 pink drywall with brown paper n None Detected 20% ce 80% qu,gy
10752 B34-3 B34-3-
Carpet/ black and blue carpeting y None Detected 100% sy
10752 B34-3-
2 tan mastic y None Detected 100% gy,bi
10753 B34-4 B34-4-
Adhesive/ tan mastic with brown wooden fragments n None Detected 30% ce 70% gy,bi
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
ca - carbonate gy - gypsum bi - binder or - organic ma - matrix mi - mica ve - vermiculite ot - other pe - perlite qu - quartz fg - fiberglass mw - mineral wool wo - wollastonite ta - talc sy - synthetic ce - cellulose br - brucite ka - kaolin (clay) pa - palygorskite (clay) Approved Signatories:
Julio Robles Technical Manager
Analyst Tanner Rasmussen
1. Fire Damage significant fiber damage - reported percentages reflect unaltered fibers
2. Fire Damage no significant fiber damages effecting fibrous percentages
3. Actinolite in association with Vermiculite
4. Layer not analyzed - attached to previous positive layer and contamination is suspected
5. Not enough sample to analyze
6. Anthophyllite in association with Fibrous Talc
7. Contamination suspected from other building materials
8. Favorable scenario for water separation on vermiculite for possible analysis by another method
9. < 1% Result point counted positive
10. TEM analysis suggested
Labs
A
/data/wordandspreadsheets/templates/asbestos/PLMReport.xls (Revision 4 2/25/2020) Page 3 of 5
Phone #
Fax #
John Monaco Senior Analyst
Analyst Julio Robles
CA Labs
Dedicated to QualityDedicated to QualityDedicated to QualityDedicated to Quality
Crisp Analytical, L.L.C.
1929 Old Denton Road
Carrollton, TX 75006
Phone 972-242-2754
Fax 972-242-2798
CA Labs, L.L.C.
12232 Industriplex, Suite 32
Baton Rouge, LA 70809
Phone 225-751-5632
Fax 225-751-5634
Polarized Light Asbestiform Materials Characterization
David Blackwell CA Labs Project #:
Asbestos & Technical Services 020723-B34, FE Warren AFB, B34
CAL23021129AS
P.O. Box 2574
Cheyenne, WY 82003 Turnaround Time: 2/9/2023
24 Hours Samples Rec'd: 2/9/23 10:30AM
307-214-0904 Date Of Sampling: 2/7/2023
Purchase Order #:
Laboratory
Sample ID
Sample # Com ment
Layer
Analysts Physical Description of
Subsample
Homo-geneo us
(Y/N)
Asbestos type / calibrated visual estimate percent
Non-asbestos fiber type / percent
Non-fibrous type / percent
10754 B34-5 B34-5-
Adhesive/ tan mastic with brown wooden fragments n None Detected 30% ce 70% gy,bi
10755 B34-6 B34-6-
1 Carpet/ blue carpeting y None Detected 100% sy
10755 B34-6-
2 tan mastic y None Detected 100% gy,bi
10756 B34-7 B34-7-
1 Cove Base/ gray baseboard y None Detected 100% gy,ma
10756 B34-7-
2 tan mastic y None Detected 100% gy,bi
10757 B34-8 B34-8-
Drywall/ white surfaced white compound n None Detected 100% qu,bi,ca
10757 B34-8-
2 white drywall with brown paper n None Detected 20% ce 80% qu,gy
Dallas NVLAP Lab Code 200349-0 TEM/PLM TCEQ# T104704513-15-3 TDH 30-0235
AIHA LAP, LLC Laboratory #102929 Analysis Method: Interim (40CFR Part 763 Appendix E to Subpart E) / Improved (EPA-600 / R-93/116). All samples received in good condition unless noted.
Preparation Method: HCL acid washing for carbonate based samples, chemical reduction for organically bound components, oil immersion for identification of asbestos types by dispersion attaining / becke line method.
ca -…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .