Attachment_3_142010-26-0150.pdf

PDF 714 KB Posted

Attached to
NWS HVAC PREVENTIVE MAINTENANCE (PM) WFO AND NEXRA
Solicitation number
1305M326Q0391
Issued by

About this file

This document is an Installation Instructions and Maintenance Operations Manual for the VAPORSTREAM Models VLC and VLDI electric steam humidifiers manufactured by DRI-STEEM Humidifier Company.

The manual provides comprehensive technical guidance for installing and maintaining both the standard VLC model and the VLDI variant designed for deionized or reverse osmosis water applications. The VLC model operates with softened or unsoftened water and requires water conductivity of 100 micromhos/cm minimum for the probe-type level control system to function. The VLDI model produces chemical-free steam and requires no maintenance water waste or downtime. The document includes detailed mechanical specifications and capacities across multiple heater configurations (ranging from 1 to 12 heaters) and unit sizes, with steam output capabilities from 2-1 to 100-4 models producing 2 to 285 lbs/hr respectively. Electrical requirements are specified for single-phase and three-phase connections at various voltages (120V through 600V), with current draw specifications and kiloWatt ratings provided for each model.

Installation instructions cover six mounting methods including floor stand, trapeze hanger, wall brackets, below-duct, remote vapor hose, and air handling unit configurations. Critical installation requirements include level mounting in both directions, minimum 18-inch clearance for cover removal, proper vapor hose pitching (minimum 2 inches per foot back to humidifier), and condensate drain line sizing with appropriate water seals. The manual specifies piping requirements for steam, water, and drain systems; addresses dispersion tube installation for horizontal and vertical ducts; and provides guidance on the optional weather cover. Recommended maintenance procedures differ between VLC and VLDI models, with VLC requiring periodic cleaning of tanks, probes, and skim overflow ports depending on water hardness, while VLDI requires minimal maintenance when mineral-free water is used. The document includes replacement parts lists, a maintenance service record template, and a two-year limited warranty covering defects in materials and workmanship for two years after installation or 27 months from shipment date, whichever is earlier.

View the file

Other files

File Type Posted
Sol_1305M326Q0391_Amd_0001.pdf PDF
Attachment_4_142010-26-0150.pdf PDF
Attachment_2_142010-26-0150.pdf PDF
Attachment_1_142010-26-0150.pdf PDF
Attachment_6_142010-26-0150.pdf PDF
Greenville_WD_2015-4433.txt TXT text file
Sol_1305M326Q0391.pdf PDF
Attachment_5_142010-26-0150.pdf PDF
Attachment_7_142010-26-0150.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

READ AND SAVE THESE INSTRUCTIONS

VAPORSTREAM

Models VLC and VLDI

ELECTRIC STEAM HUMIDIFIERS

Installation Instructions and

Maintenance Operations Manual

For Toll-Free Technical Support, Call 1-800-328-4447

CUL LISTEDUL LISTED

TO THE PURCHASER AND THE INSTALLER

Thank you for purchasing VAPORSTREAM® Model VLC equipment. We have designed and built this equipment to give you total satisfaction and many years of trouble-free service. Proper installation and operating practices will assure you of achieving that objective. We therefore urge you to become familiar with the contents of this manual.

This manual covers material for both VAPORSTREAM Model VLC and VAPORSTREAM Model VLDI humidifiers. Most of the application material will apply to both units. When information differs for the two units, it will be noted as such.

DRI-STEEM Humidifier Company

VAPORSTREAM Models VLC and VLDI

Mechanical Specifications and Capacities

Mechanical Specifications

VAPORSTREAM Model VLC AREA-TYPE Humidifier

Mounting Methods Mounting Procedures Electrical

Dispersion Tube Installation

Optional Weather Cover Weather Cover Dimensions

RAPID-SORB® Assembly and Installation Horizontal Duct Installation Vertical Duct Installation

Piping Methods Drain Piping Make-up Water Piping

Piping Diagrams: Steam, Water and Drain

Start-up Procedure

Operation

Recommended Maintenance

Trouble-Shooting Guide

Replacement Parts

Maintenance Service Record

Two-Year Limited Warranty

TABLE OF CONTENTS

VAPORSTREAM® MODELS VLC AND VLDI

VAPORSTREAM VLC

Electric Humidifier State-of-the-art technology in a simple, low-maintenance humidifier.

This humidifier is designed to be used with either softened or unsoftened water (preferably soft-ened). The probe-type level control system requires water conductivity of 100 micromhos/cm (2 grains/gal) minimum to function, and therefore will not operate on water treated by reverse osmosis or deionization.

However, VAPORSTREAM® Model VLC humidifiers are available for use with these water types. The stan-dard humidifier can be converted in the field to a VLDI model. See below.

VAPORSTREAM VLDI

Option For use with deionized or reverse osmosis water. This unit produces chemical-free steam and reliable, accurate humidification control. It is virtually maintenance-free with no wasted water, no wasted heat, and very little or no downtime.

OM-628

Control Cabinet

Probes

VAPOR-LOGIC®

Raised Heater

Dispersion Tube

Duct

Cover

Cover Knobs

Evaporating Chamber Skimmer Port Outlet Fill Valve

Needle Valve

Manual or Electric Drain Valve

Clean-out Tray

Thermal Cut-Out

OM-1000

Cover Knobs

Cover

Overflow

Float Valve

Low-Water Cut-Off

3/4" SST Drain Valve

MECHANICAL SPECIFICATIONS AND CAPACITIES

Capacity Notes Approximately 172 BTUs (400 kJ) are required to raise the temperature of one pound (Kg) of water from 40° to 212° F (4° to 100°C). An additional 970 BTUs (2250 kJ) are required to change one pound (Kg) of water to water vapor.

The addition of ¾" (25 mm) rigid foil faced fiberglass insula-tion (optional) on all surfaces of evaporating chamber will increase unit efficiency by approximately 2%.

Another factor to consider is condensation steam loss from hoses and tubes. Use the following steam loss guidelines:

• vapor hose: 0.15 lbs/ft/hr (223 g/m/h)

• insulated pipe: 0.05 lbs/ft/hr (74 g/m/h)

• dispersion tubes: 0.5 lbs/ft/hr (744 g/m/h)

Table 4-1: Mechanical Specifications and Capacities

* Heater stage identifies the number of contactors.

** Three-phase power supply connection. All heater loads are wired delta.

ledoM rebmun maetS seiticapac ruohrep sretaeH

)A()spma(wardtnerruC

Wk

.sbL .gK esahp-elgniS **esahp-eerhT

.ytQ *segatS V021 V802 V042 V084 V006 V802 V042 V084 V006

1-2IDLV/CLV 7.5 6.2 1 1 7.61 6.9 3.8 2.4 3.3 2

1-3 6.8 0.4 1 1 0.52 4.41 5.21 3.6 0.5 3

1-4 4.11 2.5 1 1 3.33 2.91 7.61 3.8 7.6 4

1-5 2.51 9.6 1 1 6.52 2.22 1.11 9.8 33.5

1-6IDLV/CLV 1.71 8.7 3 1 8.82 0.52 5.21 0.01 7.61 4.41 2.7 8.5 6

1-9 7.52 7.11 3 1 3.34 5.73 8.81 0.51 0.52 7.12 8.01 7.8 9

1-21 2.43 5.51 3 1 0.52 0.02 3.33 9.82 4.41 5.11 21

1-61 6.54 7.02 3 1 3.33 7.62 4.44 5.83 2.91 4.51 61

1-12 9.95 2.72 3 1 8.34 0.53 3.52 2.02 12

1-52 3.17 3.23 3 1 7.14 1.03 1.42 52

2-21IDLV/CLV 2.43 5.51 6 2 7.75 0.05 0.52 0.02 3.33 9.82 4.41 5.11 21

2-81 3.15 3.32 6 2 5.68 0.57 5.73 0.03 0.05 3.34 7.12 3.71 81

2-42 4.86 0.13 6 2 0.05 0.04 6.66 7.75 9.82 1.32 42

2-23 2.19 4.14 6 2 7.66 3.35 8.88 0.77 5.83 8.03 23

2-24 7.911 3.45 6 2 5.78 0.07 5.05 4.04 24

2-05 5.241 6.46 6 2 3.38 1.06 1.84 05

3-81IDLV/CLV 3.15 3.32 9 3 5.68 0.57 5.73 0.03 0.05 3.34 7.12 3.71 81

3-72 0.77 0.53 9 3 8.921 5.211 3.65 0.54 9.47 0.56 5.23 0.62 72

3-63 6.201 5.64 9 3 0.57 0.06 9.99 6.68 3.34 6.43 63

3-84 8.631 1.26 9 3 0.001 0.08 2.331 5.511 7.75 2.64 84

3-36 6.971 5.18 9 3 3.131 0.501 8.57 6.06 36

3-57 8.312 0.79 9 3 0.521 2.09 2.27 57

4-42IDLV/CLV 4.86 0.13 21 4 4.511 0.001 0.05 0.04 6.66 7.75 9.82 1.32 42

4-63 6.201 5.64 21 4 1.371 0.051 0.57 0.06 9.99 6.68 3.34 6.43 63

4-84 8.631 1.26 21 4 0.001 0.08 2.331 5.511 7.75 2.64 84

4-46 4.281 7.28 21 4 3.331 7.601 6.771 0.451 0.77 6.16 46

4-48 4.932 7.801 21 4 0.571 0.041 0.101 8.08 48

4-001 0.582 3.921 21 4 7.661 3.021 2.69 001

MECHANICAL SPECIFICATIONS

Table 5-1: Mechanical Specifications

Table 5-2: Control Cabinet Dimensions

* In addition to the shipping weight of the humidifier.

Figure 5-1: Dimensions

B

Back View

A

OM-626Front ViewSide View

C

* Refer to table 5-2 for Control Cabinet dimensions

Model Number

A (width) B (height) C (length) Weight empty (lbs)

Weight empty (kg)

Weight full

(lbs)

Weight full (kg)

Control cabinet sizesin. mm in. mm in. mm

VLC/VLDI 2-1 20.25 515 16.85 430 7.52 190 35 16 79 36 M

3-1 20.25 515 16.85 430 7.52 190 35 16 79 36 M

4-1 20.25 515 16.85 430 7.52 190 35 16 79 36 M

5-1 20.25 515 16.85 430 7.52 190 35 16 79 36 M

VLC/VLDI 6-1 22.00 560 18.38 465 12.85 325 57 26 157 71 M

9-1 22.00 560 18.38 465 12.85 325 57 26 157 71 M

12-1 22.00 560 18.38 465 12.85 325 57 26 157 71 M

16-1 22.00 560 18.38 465 12.85 325 57 26 157 71 M

21-1 22.00 560 18.38 465 12.85 325 57 26 157 71 M

25-1 22.00 560 18.38 465 12.85 325 57 26 157 71 M

VLC/VLDI 12-2 22.00 560 18.38 465 20.35 515 79 36 237 108 M

18-2 22.00 560 18.38 465 20.35 515 79 36 237 108 M

24-2 22.00 560 18.38 465 20.35 515 79 36 237 108 M

32-2 22.00 560 18.38 465 20.35 515 79 36 237 108 M

42-2 22.00 560 18.38 465 20.35 515 79 36 237 108 M

50-2 22.00 560 18.38 465 20.35 515 79 36 237 108 M

VLC/VLDI 18-3 22.00 560 18.38 465 27.85 705 110 50 326 148 L

27-3 22.00 560 18.38 465 27.85 705 110 50 326 148 L

36-3 22.00 560 18.38 465 27.85 705 110 50 326 148 L

48-3 22.00 560 18.38 465 27.85 705 110 50 326 148 L

63-3 22.00 560 18.38 465 27.85 705 110 50 326 148 L

75-3 22.00 560 18.38 465 27.85 705 110 50 326 148 L

VLC/VLDI 24-4 22.00 560 18.38 465 35.35 900 153 70 427 194 XL

36-4 22.00 560 18.38 465 35.35 900 153 70 427 194 XL

48-4 22.00 560 18.38 465 35.35 900 153 70 427 194 XL

64-4 22.00 560 18.38 465 35.35 900 153 70 427 194 XL

84-4 22.00 560 18.38 465 35.35 900 153 70 427 194 XL

100-4 22.00 560 18.38 465 35.35 900 153 70 427 194 XL

Size Inches mm Shipping weight*

M 14 w x 16h x 6d 355 w x 400 h x 150d 32 lbs. 15 kg

L 20w x 20h x 7d 500 w x 500 h x 180d 55 lbs. 25 kg

XL 24w x 24h x 7d 600w x 600h x 1180d 73 lbs. 33 kg

VAPORSTREAM® MODEL VLC AREA-TYPE HUMIDIFIER

AREA-TYPE Humidifier Application Information The operating characteristics of AREA-TYPE steam humidifiers should be considered when selecting humidi-fier capacities and choosing mounting locations.

Steam discharge from the humidifier quickly cools and turns to visible, warm, microscopic drops or particles of water (fog) which are lighter than air.

Should this fog contact any solid surface (columns, beams, ceiling, pipes, etc.) before it disappears, it may collect and drip, as water.

The greater the space relative humidity, the higher and farther the "fog" will carry and rise in the space before disappearing.

The table at right states the vertical (rise), horizontal (throw), and width (spread) dimensions that can be expected with the AREA-TYPE humidifiers.

To avoid steam impingement on surrounding areas, these dimensions should be observed.

Note: Tank dimension "C," in figure 5-1 on page 5, must be at least 12.85" (325 mm) and output should not exceed 285 lbs/hr (130 Kg/h).

Table: 6-1: Minimum Distance for Rise, Spread and Throw

OM-681

Heaters

Steam Chute �

Fan

Figure 6-1: Principle of Operation Steam created in the evaporating chamber (1) flows up through the chute (2), and is distributed into the space (3) via the fan.

Space temp.

Space

RH

lbs/hr kg/hr lbs/hr kg/hr lbs/hr kg/hr lbs/hr kg/hr lbs/hr kg/hr lbs/hr kg/hr

60° F 16° C

30%

Rise 1 ft. 0.5 m 4 ft. 1.5 m 6 ft. 2.0 m 7 ft. 2.5 m 8 ft. 2.5 m 9 ft. 3.0 m

Spread 2 ft. 1.0 m 4 ft. 1.5 m 5 ft. 2.0 m 7 ft. 2.5 m 8 ft. 2.5 m 9 ft. 3.0 m

Throw 6 ft. 2.0 m 10 ft. 3.0 m 12 ft. 4.0 m 13 ft. 4.0 m 15 ft. 5.0 m 17 ft. 5.5 m

40%

Rise 1 ft. 0.5 m 4 ft. 1.5 m 6 ft. 2.0 m 8 ft. 2.5 m 9 ft. 3.0 m 10 ft. 3.0 m

Spread 2 ft. 1.0 m 4 ft. 1.5 m 5 ft. 2.0 m 7 ft. 2.5 m 9 ft. 3.0 m 10 ft. 3.0 m

Throw 6 ft. 2.0 m 10 ft. 3.0 m 12 ft. 4.0 m 14 ft. 4.5 m 16 ft. 5.0 m 18 ft. 5.5 m

50%

Rise 1 ft. 0.5 m 4 ft. 1.5 m 6 ft. 2.0 m 8 ft. 2.5 m 9 ft. 3.0 m 10 ft. 3.0 m

Spread 2.5 ft. 1.0 m 5 ft. 2.0 m 5 ft. 2.0 m 7 ft. 2.5 m 9 ft. 3.0 m 10 ft. 3.0 m

Throw 6 ft. 2.0 m 10 ft. 3.0 m 12 ft. 4.0 m 14 ft. 4.5 m 16 ft. 5.0 m 18 ft. 5.5 m

70° F 21° C

30%

Rise 1 ft. 0.5 m 3 ft. 1.0 m 4 ft. 1.5 m 5 ft. 2.0 m 5 ft. 2.0 m 7 ft. 2.5 m

Spread 1.5 ft. 0.5 m 3 ft. 1.0 m 4 ft. 1.5 m 5 ft. 2.0 m 5 ft. 2.0 m 7 ft. 2.5 m

Throw 4 ft. 1.5 m 8 ft. 2.5 m 10 ft. 3.0 m 11 ft. 3.5 m 12 ft. 4.0 m 14 ft. 4.5 m

40%

Rise 1 ft. 0.5 m 3 ft. 1.0 m 4 ft. 1.5 m 5 ft. 2.0 m 6 ft. 2.0 m 7 ft. 2.5 m

Spread 2 ft. 1.0 m 3 ft. 1.0 m 4 ft. 1.5 m 5 ft. 2.0 m 6 ft. 2.0 m 7 ft. 2.5 m

Throw 4 ft. 1.5 m 8 ft. 2.5 m 11 ft. 3.5 m 12 ft. 4.0 m 13 ft. 4.0 m 15 ft. 5.0 m

50%

Rise 1 ft. 0.5 m 3 ft. 1.0 m 4 ft. 1.5 m 5 ft. 2.0 m 5 ft. 2.0 m 7 ft. 2.5 m

Spread 2 ft. 1.0 m 3 ft. 1.0 m 4 ft. 1.5 m 5 ft. 2.0 m 5 ft. 2.0 m 7 ft. 2.5 m

Throw 4 ft. 1.5 m 8 ft. 2.5 m 11 ft. 3.5 m 12 ft. 4.0 m 14 ft. 4.5 m 16 ft. 5.0 m

Figure 7-1: VLC Mounting Methods

1. Floor Stand Method 2. Trapeze Hanger Method 3. Wall Brackets Method

4. Mounting Unit Below Duct Mounting humidifier 18" (460 mm) below duct is recommended to facilitate cover removal.

Mounting Procedures For proper operation of the electrode probe water level control and the skimmer system, the humidifier must be mounted level in both directions.

Access,18" minimum (460 mm), for periodic removal of the top cover is recommended. The cover is removed for inspection and cleaning of the evaporating chamber. In most cases, scale that forms on the heating elements continuously flakes off as it forms and the loose scale

MOUNTING METHODS

OM-648

24 ¾" (630 mm)

Two-piece Escutcheon Plate fastens to bottom of duct (duct omitted for clarity)

Cover of VAPORSTREAM®

Humidifier

OM-65

settles to the bottom. A clean-out tray on the floor of the tank may be removed periodically through the front clean-out opening. Allow space for withdrawal of the tray when install-ing the humidifier.

In some installations, an overflow drain pan may be neces-sary to prevent possible damage to flooring. This may be caused by a rapid or sudden drainage of the contents of the humidifier. The drain pan must be connected to the sanitary waste water system.

DRI-STEEM

wall brackets (optional) 2 required

A

Secure rods to overhead construction

Angle or channel of size required

OM-647

Threaded rod of size required

Cleanout

Steam Dispersion Tube

Provide 18" (460 mm) min. clearance under duct for cover removalDRI-STEEM support legs (optional)

OM-646

Clamp

Vapor Hose

Bottom of Duct

2 piece Escutcheon Plate

Cover of VAPORSTREAM Humidifier

18" min.

(460 mm)

Cut hole in duct large enough to allow passage of hose clamp

OM-66

Steam Dispersion Tube tinU snoisnemiD

Arof )sehcnini( snoisnemiD Arof

)mmni( retaeh3 91 084 retaeh6 91 084 retaeh9 03 067 retaeh21 63 519

5. Mounting Units Away from Duct(s) Using Vapor Hose

MOUNTING METHODS

Electrical The current characteristics, and capacity requirements should be checked against the nameplates. The control cabinet should be mounted in a location convenient for service. All wiring must be in accordance with all local codes, and with VAPORSTREAM® Model VLC wiring diagram. The diagram is inside the control cabinet. The wiring between the control cabinet and humidifier must be rated at 105°C minimum.

Airflow

Air Handling Unit Casing

Humidifier Centered in Air Handling Unit

OM-653

6. Mounting In Air Handling Unit Gasketed Access Door

Supply Air Duct

Set unit level. Locate unit so that steam dispersion assembly is in the most active part of the air stream.

Air Handling Unit Coil Section

Filter and Mixing Box

Outdoor and Return Airflow into Air Handling Unit

Caution: Only qualified electrical personnel should perform installation procedures.

Vapor hose. (Pitch back min. 2" per foot (165 mm/m) to humidifier with supports to prevent sagging.) Maximum length 10' (3 m). Humidifier must be mounted level.

OM-638

Stainless steel dispersion tube in middle of duct. Pitch as shown in figure 9-1 on page 9.

Dispersion Tube Installation with Condensate Drain

Vapor Hose When a vapor hose and stainless steel dispersion tube are used, they should be pitched back to the humidifier.

A minimum slope of 2" per foot (165 mm/m) (with no “low spots”) is recommended. Vapor hose should be sup-ported to prevent sags or low spots. When this is not possible due to duct elevation or an obstruction, alternate arrangements should be used as shown in figure 15-1 or 15-2.

Any condensate that forms in the vapor hose must be removed. Preferably, it should be returned to an open drain with a water seal of sufficient height to contain the duct static pressure, as shown in figure 10-1.

The condensate can also be returned to the VAPORSTREAM® VLC, as shown in figure 10-2, with an air vent. This method requires a water seal and an air gap to prevent back pressure from the VLC chamber. Exces-sive back pressures imposed on the humidifier may lead to dispersion tube(s) spitting, lost water seals, or leaking gaskets. When the distance between the humidifier and the dispersion tube(s) exceeds 10 feet (3 m), consult factory for special recommendations.

Hard Piping (when used)

• Hard piping should have a minimum I.D. of 1½" (35 mm).

• A minimum pitch of 2" per foot (165 mm/m) back to the humidifier must be maintained.

• 90° elbows are not recommended; use two 45° elbows one foot apart instead.

• Thin-walled tubing will heat up faster and cause less start up loss than heavy-walled pipe.

• Insulating the rigid piping will reduce output loss due to condensation.

Tube Mounting

• Mount dispersion tubes pitched as stated above.

• Tubelets must discharge perpendicular to air flow.

• Return line piping material must be suitable for 212°F

(100°C) water.

Min. Condensate Drain Line Sizing

• One or two tubes: 3/4" (20 mm) I.D.

• Three or more tubes: 1" (25 mm) I.D.

Figure 9-1: Single Tube

½" O.D. Stainless Steel (condensate drain)

Movable Duct Plate (Can be mounted within limits of 2.5" (65 mm).)¼" NPT Coupling

.625 Dia.

"B" Dia. (TYP)

A

A

A 2.5" (65 mm)

2"/ft (165 mm/m) Pitch Mounting Nut

Pre-molded High Temperature Resin Steam Tubelets

Insertion Length

OM-351

Table 9-1: Dispersion Tube Capacities

A

3.25" (85 mm)

1/8"/ft (10 mm/m) Pitch

DISPERSION TUBE INSTALLATION

Mounting Nut yticapaC ebuT .aiD tuohtiW niarD htiW niarD

A B

"½1 )mm83( rh/sbl82 )h/gK31( rh/sbl75 )h/gK62(

"52.3 )mm58(

"15.1 )mm04(

"2 )mm05( rh/sbl75 )h/gK62( rh/sbl58 )h/gK93(

"00.5 )mm031(

"30.2 )mm05(

3.25" (85 mm)

OM-697

Table 10-1: Water Seal Minimum Height*

* Height required to overcome humidifier internal pressure.

Figure 10-1: Multiple Tube with Condensate Wasted to Floor Drain

Dispersion Tube

Duct

Dispersion Tube

VAPORSTREAM®

VLC or VLDI Humidifier

1-½" (38 mm) Dia. Vapor Hose or Hard Tubing*

Water Seal (5" (125 mm) approx.)

6" (150 mm) Min.

Floor Drain*

Condensate Drain Tube by Others** (3/4" (20 mm) minimum)

*Refer to local codes for drain pipe sizing requirements.

OM-696

½" (50 mm) O.D. Condensate Drain Tube

Figure 10-2: Multiple Tube with Condensate Return to Humidifier

Dispersion Tube

Dispersion Tube Duct

Water Seal (5" (125 mm) approx.)

½" (13 mm) Air Vent

6" (150 mm) Min.

1-½" (38 mm) Dia. Vapor Hose or Hard Tubing *

Condensate Drain Tube by Others, 3/4" (20 mm) Minimum

Refer to Water Seal Height, Table 10-1

VAPORSTREAM VLC

or VLDI Humidifier

¾" (20 mm) Condensate Return Connection (on face plate)

½" (50 mm) O.D. Condensate Drain Tube

Air Gap

DISPERSION TUBE INSTALLATION

reifidimuH rH/sbL h/gK thgieH )sehcnI( thgieH )mm(

WK84otpU 831-5 26-2 21 503 otWK94

WK46

381-931 38-36 51 083 otWK56

WK001

722-481 301-48 81 064

OPTIONAL WEATHER COVER

A weatherproof enclosure is available, as an option, for the VAPORSTREAM® VLC. This weather cover is avail-able in either galvanized or stainless steel and comes in four sizes, designed to fit over a 3, 6, 9, or 12 heater VLC (see figure 12-2 for dimensional data on the four sizes).

The weather cover encloses the VLC to protect it from wind and water, and is ETL listed to conform to UL standard 988. The weather cover is fully assembled at the DRI-STEEM factory and is available with a remotely mounted controller.

Instructions for Installation (See Page 12, Figures 12-1 and 12-2):

1. Remove the weather cover top and panels C and D to access the water and electrical connections. A 7/16" socket wrench is required.

2. Connect water supply and drain piping (panel C).

3. Terminate main power to unit (panel D).

4. Check the hose cuff(s) and hose clamp(s) for loose-ness created during shipment.

5. Re-attach the weather cover top and panels C and D which were removed in step #1.

6. Check that all bolts are securely fastened.

7. Connect steam dispersion device(s) to the outlet(s) on the humidifier.

8. Verify that a good seal is maintained after making the connections.

NOTES:

The bottom of the weather cover is open to accomodate piping and electrical connections. These connections must be run in watertight plastic conduit due to the outdoor environment.

Other modifications may need to be made by the installer including:

• freeze protection on all water piping

• insulation of hard piping between humidifier and dispersion device

Maintenance:

Periodic maintenance of the weather cover itself is recommended in order to insure it's continued wind/water proof state.

1. Periodically check the condition of the gasket(s).

Replace as needed or on an annual basis.

2. Annually check for loose bolts or connections.

3. Annually check the hose cuff(s) for signs of wear.

Replace as needed or on an annual basis.

4. Annually check the cover for any signs of corrosion or degradation. Repair as needed.

Figure 11-1: VLC Weather Cover

WEATHER COVER DIMENSIONS

Figure 12-1: Weather Cover Exploded View

Table 12-1: 3, 6, 9, and 12 Heater Overall Dimensions of Weather Cover

Panel A

Top Panel

Panel D

Panel C

OM-906A

Panel B

Figure 12-2: Weather Cover Dimensions

OM-904

Panel Identification Label

B ETL Certification Label

A

C

Product Identification Label

D

:2-21erugiF retteLtuollaC noitpircseDtuollaC eerhT sehcni( eerhT )mm( xiS sehcni( xiS )mm( eniN )sehcni( eniN )mm( evlewT )sehcni( evlewT )mm(

A thgieH ¾05 0921 ¾05 0921 ¾05 0921 ¾05 0921

B htgneL ½32 006 23 518 04 5101 ½74 5021

C htdiW 52 536 ½32 006 ½32 006 ½32 006

D mottobmorfecnatsiD ¾7 002 ¾7 002 ¾7 002 ¾7 002

RAPID-SORB® ASSEMBLY AND INSTALLATION

Instructions for Horizontal Duct

1. Unpack shipment and verify receipt of all RAPID-SORB components with packing list. Report any shortages to the DRI-STEEM factory immediately.

2. Provide necessary access in and around duct work.

3. Locate 1" x 1½" (25 mm x 38 mm) stainless steel channel inside the duct. Hang the channel from the top of the duct, centered between duct side walls, with the two mounting holes provided.

4. If hose cuffs are used, slide cuffs over the open end of each tube. Install a pair of hose clamps on each tube.

5. Note direction of air flow within duct, then arrange each dispersion tube so steam will discharge perpendicular to the air flow. Use the hex bolts provided to attach tubes to overhead 1" x 1½" (25 mm x 38 mm) channel. Do not secure. If the header is outside the duct (see figure 13-2), punch-out necessary clearance holes in the base of the duct to slide dispersion tubes up from bottom.

6. For a Header Inside the Duct (See figure 13-1.):

Punch or cut out necessary clearance holes for RAPID-SORB header. Slide header into the duct, position header and slide the dispersion tube hose cuffs or slip couplings over the header dispersion tube nipples.

Position the header so vertical dispersion tubes are perpendicular to duct and pitch the header to condensate drain. Secure header to the mounting bracket. Use escutcheon plates to secure header where it enters the duct.

Check that the dispersion tubes discharge steam perpen-dicular to the air flow. Secure tubes to the overhead channel. Secure the channel to the duct. Position hose cuffs or slip couplings over tube and header tube nipples, and secure with clamps.

For a Header Outside the Duct (See figure 13-2.):

Position header under dispersion tubes, then slide hose cuffs or slip couplings over header dispersion tube nipples.

Position the header so dispersion tubes are perpendicular to duct and pitch the header to condensate drain. Secure dispersion tubes in place with the tube escutcheon plates provided.

Check the position of the tubes for steam release perpen-dicular to the air flow. Secure tubes to the overhead channel, and secure channel to the duct. With header pitched to condensate drain, slip hose cuffs or slip couplings over tube nipples and secure with clamps.

7. Connect a condensate drain to the header, provide the water trap as shown, and run to open drain, sized accord-ing to local codes.

8. Attach the header steam supply connector to main header using the hose cuff and clamps provided, but do not secure.

9. Route the necessary number of vapor hoses or pipes from the humidifier tank, position connector to accept the hoses or pipes and secure.

Note: Refer to page 15 for vapor hose information on routing and for alternate vapor hose installation methods.

Figure 13-1: RAPID-SORB Unit Header Inside Duct

Top of Duct or Casing

OM-102

Condensate Drain, 3/4" NPT

3/4" (20 mm) Copper

Air Gap

*Open Drain

Pitch 1/8" per foot (10 mm/m) minimum

Hose Cuff and Clamps

VAPORSTREAM® Model VLC Humidifier

Orificed Tubelets

A

A

Dispersion Tube

3/8-16 x ½" Hex Head Bolt

1" x 1-1/2" (25 mm x 38 mm) S.S.T.Channel (by DRI-STEEM)

Duct

Escutcheon Plate

Figure 13-2: RAPID-SORB Unit Header Under Duct

Slip Coupling or Hose Cuff

View A-A

* Refer to local codes for drain pipe size requirements.

OM-101

Dispersion Tube

Orificed Tubelets

Slip Coupling or Hose Cuff

Optional Companion Flange or Threaded Connection for Hard Piping

Header Condensate Drain,3/4" NPT

3/4" (20 mm)Copper Air Gap

*Open Drain

5" (125 mm) Min.

6" (150 mm) Min.

Nut and Bolt

Duct or Casing

1" x 1-1/2" (25 mm x 38 mm) S.S.T. Channel (by DRI-STEEM)

Pitch 1/8" per foot (10 mm/m) minimum

Mounting Channel

Mounting Nut

5" (125 mm) Min.

6" (150

mm) Min.

Figure 14-1: Plan View

Steam Supply

1/8" per foot (10mm/m) pitch minimum

Drain

RAPID-SORB® ASSEMBLY AND INSTALLATION

Vertical Duct Installation Install the RAPID-SORB with dispersion tubes and header pitched to condensate drain as shown in figures 14-1,14-2, and 14-3.

See "Instructions for Horizontal Duct" for additional information on page 13, as applicable.

Figure 14-2: Elevation View Tube without Drain

Figure 14-3: Elevation View Tube with Drain Table 14-1*: Maximum Steam Carrying Capacity in Lbs/Hr and Kg/Hr

6" (150 mm) Min.

5" (125 mm) Min.

Recommended 2" per foot (165 mm/m) pitch

Airflow

* Based on total pressure drop in piping/hose of 5" (12.65 mm) W.C.

** For developed length add 50% to measured length for pipe fittings.

Note: To minimize lossof humidifier capacity and efficiency, it is recommended that tubing/piping be installed.

1/4" NPT

Open Drain

3/4" NPT

Coupling

Condensate Drain

Piping by others

Recommended 1/8" per foot (10 mm/m) pitch minimum

Airflow

5" (125 mm)Min.

6" (150

mm) Min.

5" (125

mm) Min.

Vapor Hose Copper or Stainless Steel Tubing and

Schedule 40 Steel Pipe

Hose I.D. Developed Length of 10’ (3.0 Meters)**

Tube or Pipe Size

Base on Developed Length of 20’ (6 Meters)**

11/2" (38 mm) 150 lbs/hr 68 kg 11/2" (38 mm) 150 lbs/hr 68 kg/h

2" (50 mm) 250 lbs/hr 115 kg 2" (50 mm) 220 lbs/hr 100 kg/h

3" (75 mm) 450 lbs/hr 205 kg/h

4" (100 mm) 750 lbs/hr 340 kg/h

5" (125 mm) 1400 lbs/hr 635 kg/h

6" (150 mm) 2300 lbs/hr 1043 kg/h

Figure 15-1: Piping method recommended when obstruction prevents dispersion tube from being continuously pitched back to humidifier:

Drain Piping A drain line should be extended from the skimmer connection to a sanitary waste or suitable drain. If non-metallic pipe or hose is used, it must be capable of withstanding temperatures up to 212°F (100° C).

To prevent steam from escaping out the drain line, a water seal must be provided in the drain line of sufficient height to contain the pressure developed within the humidifier and steam dispersion system. To determine the proper height of the water seal, see table 16-1.

Make-up Water Piping When non-metallic water piping is used, it must be rated to withstand 212°F (100° C) or greater temperature. If not, the final three feet (one meter) connected to the humidifier should be metallic and should not be insulated.

As part of the fill valve assembly, the needle valve restricts the rush of cold water entering the evaporating chamber during the fill cycle. Cold water could drop the chamber water temperature and collapse the steam. If the rumbling sound occurs during the fill cycle, adjust the needle valve to decrease the water fill rate.

The VAPORSTREAM® Model VLC has a one-inch (25

mm) internal “air gap”. However, local codes may require a vacuum breaker.

PIPING METHODS

Figure 15-2: Piping method recommended when humidifier must be mounted higher than the duct:

* Refer to local codes for drain pipe size requirements.

2" Per Foot (165 mm/m) Pitch

5" (125 mm) Min.

Funnel or Floor Drain*

OM-699

Optional SST Tubing Tee

OM-698 Funnel or Floor Drain*

Obstruction

¾" (20 mm) Tubing 5" (125 mm) Min.

4" (100

mm) Min.

PIPING DIAGRAMS: STEAM, WATER AND DRAIN

Alternate Water Seal and Drain Valve Piping (by installer) Used when water seal must be elevated above flow line of drain connection (humidifier near floor)

Standard Unit (Non-DI/RO Water)

Note: Drain piping material must be suitable for 212°F (100°C) water.

DI/RO Water Unit

Table 16-1: Water Seal Height (H) Recommendations

Note: If piping to dispersion tube is over 20 feet (6 meters) increase water seal height by 15%.

OM-633

¾" (20 mm) SST Drain Valve

H

Float Operated Water Make-up Valve

Overflow - ¾" (20 mm)

¼" (6 mm) NPT Water Supply, 25 psi minimum, (172 kPa)

Drain and Water Seal Piping - ¾" (20 mm) (by installer)

Air Gap

Open Drain *Float Operated Low-Water Cut-off

Heaters

OM-634

Heaters H

Clean-out Tray

Clean-out Plate

Three Probe Level Control and Low-Water Cut-off Drain

Connection Open Drain*

Air Gap

Drain and Water Seal Piping - ¾" (20 mm) (by installer)

Manual or Optional Electric Drain Valve

Water Supply Line (25 psi minimum) Water Skim/Overflow Outlet - ¾" (20 mm)

Needle Valve

Solenoid Water Make-up Valve

* Refer to local codes for drain pipe sizing and maximum temperature requirements.

OM-635

Solenoid Water Make-up Valve

Needle Valve

Water Skim/ Overflow Outlet

Water Supply Line, 25 psi minimum, (172 kPa)

Note: Flow Line of Water Seal cannot be above Flow Line of Skimmer Outlet

Air Gap

Open Drain*

Manual or Optional Electric Drain Valve Drain Connection

Clean-out Plate reifidimuH rH/sbL h/gK thgieH )sehcnI( thgieH )mm(

WK84otpU 831-5 26-2 21 503 otWK94

WK46

381-931 38-36 51 083 otWK56

WK001

722-481 301-48 81 064

Field installed for clean-out

START-UP PROCEDURE

Introduction After the system has been properly installed and con-nected to both electrical and water supplies, it may then be started.

Start-up and Checkout Procedures Mounting Check mounting to see that unit is level and securely supported before filling with water.

Piping Verify that all piping connections have been completed as recommended and that water pressure is available.

Electrical Verify that all wiring connections have been made in accordance with all governing codes and the enclosed VAPORSTREAM® VLC wiring diagram.

Caution: Only qualified electrical personnel should perform start-up procedure.

Control System For start-up instructions, see the operations and mainte-nance manual for your humidifier control system.

OPERATION

For operating instructions, see the VAPOR-LOGIC®

Installation Instructions and Maintenance Operations Manual.

Caution: Overtightening cover will cause leaks.

All cover knobs are turned down at the factory until the bottom of the knob makes contact with the flange, then one half turn further. If more compression is required, turn all knobs a half turn more. Do not turn knobs more than a half turn before identifying that a leak still exists.

RECOMMENDED MAINTENANCE

VAPORSTREAM® Model VLC Only Using softened water will significantly reduce mineral build-up in the humidifier. When softened water is not available, the VAPORSTREAM VLC is designed to deal with water hardness in one of two ways depending on the degree of hardness. For light to moderate hardness, up to 10 grains per gallon ( 170 mg/l), using the surface water skim time feature with annual cleaning is recommended.

For high mineral content water, above 10 grains per gallon (170 mg/l), a periodic drain and flush through the motor-ized drain valve, in addition to the surface water skim time feature, is recommended. The frequency of cleaning will depend on water condition and evaporation load.

The humidifier should be inspected for leaks at least annually. Also, the current draw of the heaters should be checked and all safety devices in the control circuit should be cycled on and off to verify that they are functioning.

Caution: When performing maintenance on the VAPORSTREAM Model VLC, always set control module switch to "STBY” position, place main disconnect in “OFF” position, and close manual water shut-off valve.

Seasonally or as Required

1. Cleaning Tank - Slide the clean-out tray out and dispose of any loose scale that has collected in the tray.

This should be done before the build-up reaches the underside of the heating elements.

2. Cleaning Probes - Disconnect the plug and cable assembly and unscrew the probe holder from the VAPORSTREAM VLC unit. The scale will easily flake off from the sensing portion. The sensing portion, bottom 3/8" (10 mm), of the probe should be brushed clean with stainless steel wool.

3. Cleaning Skim Overflow Port - Loosen deposits with a long tool, such as a screwdriver. Proper skimmer drainage should be verified by a weekly visual inspection.

Water should drain from skimmer drain pipe after each fill cycle. (For cleaning piping, disconnect and flush out. If mineral deposits have restricted the flow, replace piping.)

Summer Maintenance After the humidification season, a complete inspection and cleaning of the heaters, probe control, skimmer port, and water chamber is recommended. After cleaning, the unit should remain empty until humidification is required.

Adjusting the Surface Skim Bleed-Off Quantity The skim time determines the quantity of water skimmed with each fill cycle. The skim time is field adjustable using the VAPOR-LOGIC® keypad.

Each time the VAPORSTREAM VLC refills, it fills to an elevation near the lip of the skim overflow fitting. A portion of the refill water then flows to drain carrying the minerals floating on the water with it. This reduces the mineral concentration, thereby reducing the frequency of cleaning needed.

The heated water that flows to drain is a cost of operation. Cleaning the humidifier is also an operational cost. Therefore, it is recommended that the user observe and adjust the skimming quantity. By doing so, a balance between minimizing mineral build-up and conserving hot water can be achieved.

VAPORSTREAM Model VLDI Only The humidifier should be inspected for leaks at least annually. Also, the current draw of the heaters should be checked and all safety devices in the control cabinet should be cycled on and off to verify that they are func-tioning.

Make-up Water Piping Use cold or hot makeup water. If the water pressure is above 60 psi (410 kPa) and/or water hammer would be objectionable, a pressure reducing valve or shock arrester should be installed. Even though the VAPORSTREAM VLC has an internal 1" (25 mm) air gap, some local codes may require a vacuum breaker.

Caution: Minimum water supply pressure is 25 psi (172 kPa).

Cleaning Evaporating Chamber As long as mineral-free water is used in the VAPORSTREAM VLDI, no cleaning or flushing of the evaporating chamber should be necessary.

For trouble-shooting instructions, see the VAPOR-LOGIC®

Installation Instructions and Maintenance Operations Manual.

TROUBLE-SHOOTING GUIDE

REPLACEMENT PARTS

VAPORSTREAM® Model VLC Humidifier

TAB - Specify humidifier model and serial numbers when ordering.

Notes:

1. For dispersion tube(s) specify type

(L-tube, straight tube, RAPID-SORB®, etc) humidifier model and serial numbers.

2. Parts not itemized are typical hardware stock items.

OM-907

No. Description Part No.

1 Tank 167700-TAB

2 Cover, One Heater 167710-TAB

2 Cover, Three Heater 167715-TAB

2 Cover, Six Heater 167720-TAB

2 Cover, Nine Heater 167725-TAB

2 Cover, Twelve Heater 167730-TAB

3 Cover, Heater Louvered 167740-TAB

4 Knob, T-Handled Utility 700725

5 Heater 409600-TAB

6 Gasket, Cover 160691-TAB

7 Clean-Out Plate 165472

8 Gasket, Clean-Out Plate 308225

9 Switch Door Interlock 408475

10 Thermal Cut-Out 409560-001

11 Valve, ¾" Ball (Manual Drain) 505011

12 Valve, ¾" Electric (Auto Drain) 505400-001

13 Probe Plug 406050-004

14 Probe Housing 308500

15 Probe Assembly 406015

16 Gasket, Probe 309750-004

17 Strainer, ¼" Sediment 300050

18 Valve, ¼" Needle 505070-001

19 Fill Valve, ¼" Solenoid 505084

20 Clean-Out Tray 167770-TAB

VAPORSTREAM Model VLDI Humidifier

OM-908

No. Description Part No.

1 Tank 167700-TAB

2 Cover, One Heater 167710-TAB

2 Cover, Three Heater 167715-TAB

2 Cover, Six Heater 167720-TAB

2 Cover, Nine Heater 167725-TAB

2 Cover, Twelve Heater 167730-TAB

3 Cover, Heater Louvered 167740-TAB

4 Knob, T-Handled Utility 700725

5 Heater 409600-TAB

6 Gasket, Cover 160691-TAB

7 Clean-Out Plate 165472

8 Gasket, Clean-Out Plate 308225

9 Switch Door Interlock 408475

10 Thermal Cut-Out 409560-001

11 Valve, ¾" Ball (Manual Drain) 505000-001

12 Float Valve Assembly 505210

13 DI Housing 167780

14 Gasket, Low Water Tube 160698

15 Low Water Tube 167785

16 Low Water Cut-Out Switch 408420-001

TAB - Specify humidifier model and serial numbers when ordering.

Notes:

1. For dispersion tube(s) specify type (L-tube, straight tube, RAPID-SORB®, etc) humidifier model and serial numbers.

2. Parts not itemized are typical hardware stock items.

REPLACEMENT PARTS

DATE

INSPECTED PERSONNEL OBSERVATION ACTION PERFORMED

MAINTENANCE SERVICE RECORD

DATE

INSPECTED PERSONNEL OBSERVATION ACTION PERFORMED

MAINTENANCE SERVICE RECORD

TWO-YEAR LIMITED WARRANTY

DRI-STEEM Humidifier Company (“DRI-STEEM”) warrants to the original user that its products will be free from defects in materials and workmanship for a period of two (2) years after installation or twenty-seven (27) months from the date DRI-STEEM ships such product, whichever date is the earlier.

If any DRI-STEEM product is found to be defective in material or workmanship during the applicable warranty period, DRI-STEEM’s entire liability, and the purchaser’s sole and exclusive remedy, shall be the repair or replacement of the defective product, or the refund of the purchase price, at DRI-STEEM’s election. DRI-STEEM shall not be liable for any costs or expenses, whether direct or indirect, associated with the installation, removal or re-installation of any defective product.

DRI-STEEM’s limited warranty shall not be effective or actionable unless there is compliance with all installa-tion and operating instructions furnished by DRI-STEEM, or if the products have been modified or altered without the written consent of DRI-STEEM, or if such products have been subject to accident, misuse, mishandling, tampering, negligence or improper maintenance. Any warranty claim must be submitted to DRI-STEEM in writing within the stated warranty period.

DRI-STEEM’s limited warranty is made in lieu of, and DRI-STEEM disclaims all other warranties, whether express or implied, including but not limited to any IMPLIED WARRANTY OF MERCHANTABILITY, ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, any implied warranty arising out of a course of dealing or of performance, custom or usage of trade.

DRI-STEEM SHALL NOT, UNDER ANY CIRCUMSTANCES BE LIABLE FOR ANY DIRECT, INDIRECT,

INCIDENTAL, SPECIAL OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, LOSS OF

PROFITS, REVENUE OR BUSINESS) OR DAMAGE OR INJURY TO PERSONS OR PROPERTY IN ANY

WAY RELATED TO THE MANUFACTURE OR THE USE OF ITS PRODUCTS. The exclusion applies regardless of whether such damages are sought based on breach of warranty, breach of contract, negligence, strict liability in tort, or any other legal theory, even if DRI-STEEM has notice of the possibility of such damages.

By purchasing DRI-STEEM’s products, the purchaser agrees to the terms and conditions of this limited warranty.

Form No. VLCOM-0300 Copyright © 2000 DRI-STEEM Humidifier Company Printed in U.S.A.

Continuous product improvement is a policy of DRI-STEEM Humidifier Company therefore, product features and specifications are subject to change without notice.

DRI-STEEM, RAPID-SORB, STS, LTS, VAPOR-LOGIC and VAPOR-LOGIC2 are Registered Trademarks of the DRI-STEEM Humidifier Company.

TEFLON is a Registered Trademark of Dupont.

14949 Technology Drive • Eden Prairie, MN 55344 Phone: (952) 949-2415 • 800-328-4447 • Fax: (952) 949-2933 E-Mail: sales@dristeem.com • Web: www.dristeem.com Europe Office:

Bell Place, Bell Lane • Syresham, Brackley • NN13 5HP, U.K.

Phone: +44 1280 850122 • Fax: +44 1280 850124 E-Mail: 106277.1443@compuserve.com

File details come from the government source that posted it. Updated .