3 June 2021

Page 1 of 2 10 June 2021

Technical Requirements Document

The 16th Electronic Warfare Squadron (EWS/EWX) Advanced Programs (AP) test laboratory has a vital requirement for the following product to satisfy the mission. Laboratory testing of the defensive systems during Area of Responsibility (AOR) mission data file development enables the process to test, analyze, correct/improve and re-test in a long term organic environment.

The cost saving to the Air Force in organic laboratory testing is significant when compared and contrasted against a traveling to contractor facilities to build a mission data file and test at 16 EWS, Eglin AFB AP laboratory.

Equipment under test must remain at a specific cooling temperature and flow rates. Indoor air-cooled chiller/heater system with advanced temperature control technology allows full proportional cooling from 0% to 100% load conditions. With available temperature stabilities of ±0.05°C for critical applications, even with high cooling power requirements up to 70kW.

PAO Chiller Specifications

Fluid Setpoint Range +10°C to +27°C

Temperature Stability ± 0.5°C

Net Cooling Capacities

(*Ratings on 60 Hz with standard pump) 10 kW at 15°C Ambient up to +25°C

Nominal Heating Capacity 10 kW

Recirculating Flow/Pressure 7 Gpm at 140 PSI Adjustable

Stainless Steel Reservoir 10 gallons (Vented)

Recirculating Fluid PAO

Recirculating Supply / Return Fittings 3/4” Stainless Steel FNPT

Heat Rejection to Ambient 71,500 BTU/hr Maximum

Condenser Air Flow 4,200 CFM, Directed Outward

Electrical Service 208/230 VAC, 60Hz, 3 phase, 80 amp service

Dimensions 72” H x 47” W x 42” D

Weight 1,220 lbs. dry weight approx.

Warranty 12 Months, Parts and Labor

Patents: #4,742,689, #4,959,972, #4,934,155

Refrigeration 6 Hp hermetically sealed scroll compressor, R-507 refrigerant, Dual fan condenser

Fluid Distribution Flow Control Panel Description

Recirculating Flow/Pressure

(provided by external chiller system) 7 Gpm at 140 PSI Adjustable

Recirculating Fluid PAO

Recirculating Supply / Return Fittings 3/4” Stainless Steel FNPT

3 June 2021

Page 2 of 2 10 June 2021

Flow Path 1 .79 - 1 Gpm

Flow Path 2 .78 - 1 Gpm

Flow Path 3 .84 - 1 Gpm

Flow Path 4 .24 - .5 Gpm

Flow Path 5 .3 - .5 Gpm

Flow Path 6 .456 - 1.5 Gpm

Flow Path 7 Up to 1.5 Gpm

Dimensions 70” H x 56” W x 30” D

Weight 450 lbs. dry weight approx.

Must provide the specific cooling requirements for units under test. The strict power requirements and small form factor chiller must meet current location lab setup/availability to the 16th EWS. It will also allow the 16 EWS to run tests without damage to the damage to Line Replaceable Units.

Delivery within 24 weeks ARO.

** The government reserves the right to refuse final acceptance until all discrepancies have been resolved to the satisfaction of the government. **