M|P Project # 0110.20.001 SET NO. _______

PROJECT MANUAL

MAHG21-1108

REPLACE SANITARY

LINES DINING

FACILITIES

LIVE OAK DINING

BUILDING 2001 – KAFB

Vectrus

505 E. Street | Bldg. 2001 | Biloxi | Mississippi 39534

REV 0 – Issued For Construction August 14, 2020

Machado|Patano, PLLC M|P Design Group, PLLC

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

024200 - 1 Selective Demolition with KAFB Supplement

SECTION 024200

SELECTIVE DEMOLITION WITH KAFB SUPPLEMENT

PART 1 GENERAL

1.01 SUMMARY

A. Section Includes: Demolition and removal of selected portions of building or structure.

1.02 DEFINITIONS

A. Remove: Detach items from existing construction and legally dispose of them off-site unless indicated to be removed and salvaged or removed and reinstalled.

B. Remove and Reinstall: Detach items from existing construction, prepare for reuse, and reinstall where indicated.

C. Existing to Remain: Existing items of construction that are not to be permanently removed and that are not otherwise indicated to be removed, removed and salvaged, or removed and reinstalled.

D. Preinstallation Meetings E. Predemolition Conference: Conduct conference at Project site.

1.03 INFORMATIONAL SUBMITTALS

A. For refrigerant- VECTRUS Technicians will remove and store all refrigerant.

B. Predemolition Photographs or Video: Submit before Work begins.

1.04 CLOSEOUT SUBMITTALS

A. Landfill Records: Indicate receipt and acceptance of hazardous wastes by a landfill facility licensed to accept hazardous wastes.

1.05 FIELD CONDITIONS

A. Conditions existing at time of inspection for bidding purpose will be maintained by The Government as far as practical.

1. Before selective demolition, The Government will remove the following items:

a. All loose furniture from spaces included on scope of work.

B. Notify The Government Contracting Officer and VECTRUS Construction Manager of discrepancies between existing conditions and Drawings before proceeding with selective demolition.

C. Hazardous Materials: It is not expected that hazardous materials will be encountered in the Work.

1. If suspected hazardous materials are encountered, do not disturb; immediately notify The

Government Contracting Officer and VECTRUS Construction Manager.

2. Follow requirements as stated within the Statement of Work.

D. Storage or sale of removed items or materials on-site is not permitted.

E. Utility Service: Maintain existing utilities indicated to remain in service and protect them against damage during selective demolition operations. Maintain fire-protection facilities in service during selective demolition operations.

PART 2 PRODUCTS

2.01 PEFORMANCE REQUIREMENTS

A. Regulatory Requirements: Comply with governing EPA notification regulations before beginning selective demolition. Comply with hauling and disposal regulations of authorities having jurisdiction.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

024200 - 2 Selective Demolition with KAFB Supplement

B. Standards: Comply with ANSI/ASSE A10.6 and NFPA 241.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that utilities have been disconnected and capped before starting selective demolition operations.

B. Survey existing conditions and correlate with requirements indicated to determine extent of selective demolition required.

C. When unanticipated mechanical, electrical, or structural elements that conflict with intended function or design are encountered, investigate and measure the nature and extent of conflict.

Promptly submit a written report to contracting officer.

3.02 UTILITY SERVICES AND MECHANICAL/ELECTRICAL SYSTEMS

A. Existing Services/Systems to Remain: Maintain services/systems indicated to remain and protect them against damage.

1. Comply with requirements for existing services/systems interruptions specified Statement of work attached.

B. Existing Services/Systems to Be Removed, Relocated, or Abandoned: Locate, identify, disconnect, and seal or cap off indicated utility services and mechanical/electrical systems serving areas to be selectively demolished.

1. Arrange to shut off indicated utilities with utility companies and contracting officer per statement of work attached.

2. If services/systems are required to be removed, relocated, or abandoned, provide temporary services/systems that bypass area of selective demolition and that maintain continuity of services/systems to other parts of building.

3. Disconnect, demolish, and remove fire-suppression systems, plumbing, and HVAC systems, equipment, and components indicated to be removed.

a. Piping to Be Removed: Remove portion of piping indicated to be removed and cap or plug remaining piping with same or compatible piping material.

b. Piping to Be Abandoned in Place: Drain piping and cap or plug piping with same or compatible piping material.

c. Equipment to Be Removed: Disconnect and cap services and remove equipment.

d. Equipment to Be Removed and Reinstalled: Disconnect and cap services and remove, clean, and store equipment; when appropriate, reinstall, reconnect, and make equipment operational.

e. Equipment to Be Removed and Salvaged: Disconnect and cap services and remove equipment and deliver to The Government.

f. Ducts to Be Removed: Remove portion of ducts indicated to be removed and plug remaining ducts with same or compatible ductwork material.

g. Ducts to Be Abandoned in Place: Cap or plug ducts with same or compatible ductwork material.

C. Refrigerant: Remove refrigerant from mechanical equipment to be selectively demolished according to 40 CFR 82 and regulations of authorities having jurisdiction and contracting officer per statement of work attached.

3.03 PREPARATION

A. Temporary Shoring: Provide and maintain shoring, bracing, and structural supports as required to preserve stability and prevent movement, settlement, or collapse of construction and finishes to remain, and to prevent unexpected or uncontrolled movement or collapse of construction being demolished.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

024200 - 3 Selective Demolition with KAFB Supplement

3.04 SELECTIVE DEMOLITION, GENERAL

A. General: Demolish and remove existing construction only to the extent required by new construction and as indicated. Use methods required to complete the Work within limitations of governing regulations and as follows:

1. Neatly cut openings and holes plumb, square, and true to dimensions required. Use cutting methods least likely to damage construction to remain or adjoining construction.

Use hand tools or small power tools designed for sawing or grinding, not hammering and chopping, to minimize disturbance of adjacent surfaces. Temporarily cover openings to remain.

2. Cut or drill from the exposed or finished side into concealed surfaces to avoid marring existing finished surfaces.

3. Do not use cutting torches until work area is cleared of flammable materials. At concealed spaces, such as duct and pipe interiors, verify condition and contents of hidden space before starting flame-cutting operations. Maintain fire watch and portable fire-suppression devices during flame-cutting operations.

4. Locate selective demolition equipment and remove debris and materials so as not to impose excessive loads on supporting walls, floors, or framing.

5. Dispose of demolished items and materials promptly.

B. Removed and Reinstalled Items:

1. Clean and repair items to functional condition adequate for intended reuse.

2. Pack or crate items after cleaning and repairing. Identify contents of containers.

3. Protect items from damage during transport and storage.

4. Reinstall items in locations indicated. Comply with installation requirements for new materials and equipment. Provide connections, supports, and miscellaneous materials necessary to make item functional for use indicated.

C. Existing Items to Remain: Protect construction indicated to remain against damage and soiling during selective demolition. When permitted by Contracting Officer construction manager, items may be removed to a suitable, protected storage location during selective demolition and cleaned and reinstalled in their original locations after selective demolition operations are complete.

3.05 DISPOSAL OF DEMOLISHED MATERIALS

A. General: Except for items or materials indicated to be recycled, reused, salvaged, reinstalled, or otherwise indicated to remain The Government's property, remove demolished materials from Project site and legally dispose of them in an EPA-approved landfill.

1. Do not allow demolished materials to accumulate on-site.

2. Remove and transport debris in a manner that will prevent spillage on adjacent surfaces and areas.

3. Remove debris from elevated portions of building by chute, hoist, or other device that will convey debris to grade level in a controlled descent.

4. Comply with requirements specified in Statement of Work attached.

B. Burning: Do not burn demolished materials.

C. Disposal: Transport demolished materials off The Government's property and legally dispose of them.

3.06 CLEANING

A. Clean adjacent structures and improvements of dust, dirt, and debris caused by selective demolition operations. Return adjacent areas to condition existing before selective demolition operations began.

END OF SECTION

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

030516 - 1 Underslab Vapor Barrier

SECTION 030516

UNDERSLAB VAPOR BARRIER

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Sheet vapor barrier under concrete slabs on grade.

1.02 RELATED REQUIREMENTS

A. Section 033000 - Cast-in-Place Concrete: Preparation of subgrade, granular fill, placement of concrete.

1.03 REFERENCE STANDARDS

A. ASTM E1643 - Standard Practice for Selection, Design, Installation and Inspection of Water

Vapor Retarders Used in Contact with Earth or Granular Fill Under Concrete Slabs 2018a.

B. ASTM E1745 - Standard Specification for Plastic Water Vapor Retarders Used in Contact with

Soil or Granular Fill under Concrete Slabs 2017.

1.04 SUBMITTALS

A. See the Statement of Work for submittal procedures.

B. Product Data: Submit manufacturers' data on manufactured products.

C. Samples: Submit samples of underslab vapor barrier to be used.

D. Manufacturer's Installation Instructions: Indicate installation procedures and interface required with adjacent construction.

PART 2 PRODUCTS

2.01 MATERIALS

A. Underslab Vapor Barrier:

1. Water Vapor Permeance: Not more than 0.010 perms, maximum.

2. Complying with ASTM E1745 Class A.

3. Thickness: 15 mils.

4. Basis of Design:

a. Stego Industries LLC; Stego Wrap Vapor Barrier (15-mil):

www.stegoindustries.com/#sle.

b. Tex-Trude; XTreme Vapor Barrier (15 mil): www.textrude.com

c. Raven Industries; Vaporblock VB15 (15 mil blue); www.ravenind.com.

d. Insulation Solutions; Viper II (15 mil blue); insulationsolutions.com.

e. Husky / Poly-America; Yellow Guard Vapor Barrier (15 mil): www.yellowguard.com

f. Or Equal.

B. Accessory Products: Vapor barrier manufacturer's recommended tape, adhesive, mastic, etc., for sealing seams and penetrations in vapor barrier.

1. Seam Tape:

a. Water Vapor Transmission Rate: ASTM E 96, 0.3 perms or lower

b. Stego Industries LLC; Stego Tape

c. Or Equal.

2. Vapor Proofing Mastic:

a. Water Vapor Transmission Rate: ASTM E 96, 0.3 perms or lower

b. Stego Industries LLC; Stego Mastic

c. Or Equal.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

030516 - 2 Underslab Vapor Barrier

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that surface over which vapor barrier is to be installed is complete and ready before proceeding with installation of vapor barrier.

3.02 INSTALLATION

A. Install vapor barrier in accordance with manufacturer's instructions and ASTM E1643.

B. Install vapor barrier under interior slabs on grade; lap sheet over footings and seal to foundation walls.

C. Unroll vapor barrier with the longest dimension parallel with the direction of the pour.

D. Lap joints minimum 6 inches and seal with manufacturer's approved tape.

E. Seal joints, seams and penetrations watertight with manufacturer's recommended products and follow manufacturer's written instructions.

F. No penetration of vapor barrier is allowed except for reinforcing steel and permanent utilities.

G. Repair damaged vapor retarder before covering with other materials. Repair damaged areasby cutting patches of vapor retarder, overlapping dmaged area 6 inches minimum and taping all four sides with tape.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

032000 - 1 CONCRETE REINFORCEMENT

SECTION 032000

CONCRETE REINFORCEMENT

PART 1 - GENERAL

1.01 RELATED SECTIONS

A. Section 03 30 00 – Cast-in-Place Concrete.

1.02 REFERENCES

A. ACI 117 – Standard Specifications for Tolerances for Concrete Construction and Materials.

B. ACI 301 – Standard Specifications for Structural Concrete.

C. ACI 315 – Details and Detailing of Concrete Reinforcement.

D. ACI 318 – Building Code Requirements for Structural Concrete.

E. ASTM A185 – Standard Specification for Steel Welded Wire Reinforcement, Plain, for Concrete

Reinforcement.

F. ASTM A615 – Standard Specification for Deformed and Plain Billet-Steel Bars for Concrete

Reinforcement.

G. ASTM A706 – Standard Specification for Low-Alloy Steel Deformed and Plain Bars for

Concrete Reinforcement.

H. AWS D1.4 – Structural Weld Code - Reinforcing Steel.

I. AWS D12.1 – Recommended Practices for Welding Reinforcing Steel Metal Inserts, and

Connections in Reinforced Concrete Construction.

J. CRSI – Manual of Standard Practice.

1.03 SUBMITTALS

A. See the Statement of Work for submittal procedures.

B. Indicate size, spacing, location and quantities of reinforcing steel and wire fabric, bending and cutting schedules, splice lengths, stirrup spacing, supporting and spacing devices. Detail reinforcing steel in accordance with ACI 315 and CRSI Standards.

C. Written description of reinforcement without adequate sections, elevations, and details is not acceptable.

D. Reproduction of Structural Drawings for shop drawings is not permitted. Electronic drawing files will not be provided to the Contractor.

E. Submit manufacturer's data for tension and compression splicers.

1.04 STORAGE AND PROTECTING

A. Store reinforcing steel above ground so that it remains clean. Maintain steel surfaces free from materials and coatings that might impair bond.

PART 2 - PRODUCTS

2.01 MATERIALS

2.02 DEFORMED REINFORCING STEEL: ASTM A615, REFER TO STRUCTURAL DRAWINGS FOR

GRADE (GRADE 60 MINIMUM).

A. Welded Steel Wire Fabric: ASTM A185.

2.03 ACCESSORY MATERIALS

A. Annealed Steel Tie Wire: 16.5 gauge minimum.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

032000 - 2 CONCRETE REINFORCEMENT

B. Bar Supports: Plastic-tipped steel Class I bar supports conforming to CRSI Specifications.

Concrete brick may be used to support reinforcement to obtain proper clearance from earth.

PART 3 - EXECUTION

3.01 FABRICATION

A. Fabricate reinforcing steel in accordance with ACI 318 and CRSI standards.

B. Bend bars cold. Do not heat or flame cut bars. No field bending of bars partially embedded in concrete is permitted, unless specifically approved Structural Engineer and checked by Testing and Inspection Agency for cracks.

C. Weld only as indicated. Perform welding in accordance with AWS D1.4 and AWS D12.1.

D. Tag reinforcing steel for easy identification.

3.02 INSTALLATION

A. Before placing concrete, clean reinforcement of foreign particles and coatings.

B. Place, support, and secure reinforcement against displacement in accordance with ACI 318 and CRSI standards. Do not deviate from alignment or measurement.

C. Place concrete beam reinforcement support parallel to main reinforcement.

D. Locate welded wire reinforcement in the top third of slabs. Overlap mesh one lap plus two inches at side and end joints.

E. Furnish and install dowels or mechanical splices at intersections of walls, columns and piers to permit continuous reinforcement or development lengths at such intersections.

F. Maintain cover and tolerances in accordance with ACI and CRSI Specifications, unless indicated otherwise on Structural Drawings.

3.03 DOWELS IN EXISTING CONCRETE

A. Install dowels and dowel adhesive in accordance with manufacturer’s recommendations.

B. Minimum embedment length into the existing concrete shall be 12 bar diameters, unless noted otherwise.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

033000 - 1 CAST-IN-PLACE CONCRETE

SECTION 033000

CAST-IN-PLACE CONCRETE

PART 1 - GENERAL

1.01 RELATED SECTIONS

A. Section 03 20 00 – Concrete Reinforcement.

1.02 REFERENCES

A. ACI 117 – Standard Specifications for Tolerances for Concrete Construction and Materials.

B. ACI 214 – Recommended Practice for Evaluation of Strength Test Results of Concrete.

C. ACI 301 – Specifications for Structural Concrete.

D. ACI 302.1 – Guide for Concrete Floor and Slab Construction.

E. ACI 304 – Recommended Practice for Measuring, Mixing, Transporting and Placing Concrete.

F. ACI 305 – Hot Weather Concreting.

G. ACI 306 – Cold Weather Concreting.

H. ACI 308 – Guide to Concrete Curing.

I. ACI 309 – Recommended Practice for Consolidation of Concrete.

J. ACI 318 – Building Code Requirements for Reinforced Concrete.

K. ASTM C31 – Standard Practice for Making and Curing Concrete Test Specimens in the Field.

L. ASTM C33 – Standard Specification for Concrete Aggregates.

M. ASTM C39 – Standard Test Method for Compressive Strength of Cylindrical Concrete

Specimens.

N. ASTM C94 – Standard Specification for Ready-Mixed Concrete.

O. ASTM C138 – Standard Test Method for Density (Unit Weight), Yield, and Air Content

(Gravimetric) of Concrete.

P. ASTM C143 – Standard Test Method for Slump of Hydraulic-Cement Concrete.

Q. ASTM C150 – Standard Specification for Portland Cement.

R. ASTM C172 – Standard Practice for Sampling Freshly Mixed Concrete.

S. ASTM C173 – Standard Test Method for Air Content of Freshly Mixed Concrete by the

Volumetric Method.

T. ASTM C230 – Standard Specification for Flow Table for Use in Tests of Hydraulic Cement.

U. ASTM C260 – Standard Specification for Air-Entraining Admixtures for Concrete.

V. ASTM C309 – Standard Specification for Liquid Membrane-Forming Compounds for Curing

Concrete.

W. ASTM C494 – Standard Specification for Chemical Admixtures for Concrete.

X. ASTM C618 – Standard Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in Concrete.

Y. ASTM E1155 – Standard Test Method for Determining FF Floor Flatness and FL Floor

Levelness Numbers.

1. SUBMITTALS: Submit according to the requirements in the Statement of Work.

2. Submit three copies of the concrete mix designs to contracting officer. Include the following:

3. Documentation of mix design proportions complying with ACI 318, Chapter 5.

4. Type and quantities of materials including admixtures

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

033000 - 2 CAST-IN-PLACE CONCRETE

5. Slump

6. Air content

7. Water/cement ratio

8. Fresh unit weight

9. Aggregates sieve analysis

10. Design compressive strength

11. Location of placement in structure

12. Method of placement

13. Method of curing

14. Seven-day and 28-day compressive strengths

a. Mix design submittals not conforming to the above will be rejected.

1.03 QUALITY ASSURANCE

A. The ready-mixed concrete plant shall be certified for conformance with the requirements of the National Ready Mix Concrete Association.

PART 2 - PRODUCTS

2.01 CONCRETE MIX DESIGN

A. Normal Weight Concrete for foundations:

1. Compressive Strength, when tested in accordance with ASTM C39/C39M at 28 days:

3,500 pounds per square inch minimum.

2. Fly Ash Content: Not allowable.

3. Cement Content: Minimum 520 lb per cubic yard.

4. Water-Cement Ratio: Maximum 50 percent by weight.

5. Total Air Content for foundation concrete: 4 percent, determined in accordance with

ASTM C173/C173M.

6. Maximum Slump: 4 inches +/- 1”.

7. Maximum Aggregate Size: 1.5 inch.

2.02 MATERIALS

A. Materials designated by specific manufacturer's trade names are approved, subject to compliance with the quality and performance indicated by the manufacturer. Instructions and recommendations, published by the manufacturer of such materials are included in and are a part of these Specifications.

2.03 CEMENT

A. Cement: Type I Portland cement complying with ASTM C150, unless noted otherwise. Use one brand only.

2.04 AGGREGATE

A. Fine Aggregate: Fine aggregate complying with ASTM C33.

B. Coarse Aggregate: Gravel or crushed stone complying with ASTM C33 for normal weight concrete. Size coarse aggregate in accordance with ACI 318.

C. Polished Concrete Aggregate: Aggregate shall be a limestone aggregate and not a river rock.

2.05 WATER

A. Water: Potable water free of deleterious substances complying with ACI 318.

2.06 AIR ENTRAINING AGENT

A. Air Entraining Agent: Air entraining agent complying with ASTM C260.

2.07 WATER REDUCER

A. Water Reducer: Water reducing agent complying with ASTM C494.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

033000 - 3 CAST-IN-PLACE CONCRETE

2.08 MID-RANGE/HIGH-RANGE WATER REDUCER

A. Mid-range/High-range Water Reducer: Mid-range and high-range water reducers (plasticizers) complying with ASTM C494.

2.09 CHLORIDE

A. Chlorides: Chlorides of any form shall not be used in concrete.

2.10 CURING COMPOUND

A. Curing Compound: A water-based, “odorless,” acrylic curing compound with a minimum solid content of 20 percent may be used at the Contractor's option complying with ASTM C309.

2.11 ACCELERATORS

A. Accelerators: Non-chloride accelerators complying with ASTM C494.

2.12 RETARDERS

A. Retarders: Retarders complying with ASTM C494.

PART 3 - EXECUTION

3.01 GENERAL

A. Prepare place of deposit, mix, convey, and place in accordance with ACI 301 and ACI 304.

B. Wet forms before placing concrete.

1. Deposit concrete as near as practical to final position.

2. Do no flowing of concrete with vibrators.

3. Place slabs in accordance with ACI 302.

4. Place and finish concrete members to comply with tolerances in ACI 117.

5. Do not use aluminum equipment in placing and finishing concrete.

3.02 SLABS-ON-GRADE

A. Place concrete for slabs-on-grade on properly prepared granular subbase with vapor barrier.

1. Place thickened slabs for partitions integral with floor slabs.

3.03 MID-RANGE / HIGH-RANGE WATER REDUCERS

A. Mid-range or high-range water reducers are to be added at dosage recommended by the manufacturer. The slump of the concrete shall be one to four inches at the time the water reducers are added. Do not permit fresh concrete containing superplasticizers to come in contact with fresh concrete not containing superplasticizers.

3.04 ADDITION OF WATER AT JOB SITE

A. Water may be added at the jobsite if neither the maximum permissible water/cement ratio nor the maximum slump is exceeded. All concrete delivery trucks will have actual batch weight tickets available that clearly indicate the quantity of water that may be added at the jobsite that will not exceed the maximum water/cement ratio.

3.05 TIME LIMIT

A. Deposit concrete within one and one-half hours after batching.

3.06 VIBRATION

A. Consolidate concrete in accordance with ACI 301 and ACI 309.

3.07 CURING

A. Begin curing procedures immediately following the commencement of the finishing operation.

B. Cure concrete in accordance with ACI 308. Keep the concrete surface moist.

C. If an acrylic curing compound is used, apply in accordance with manufacturer's recommendations to surfaces of concrete not protected for five days by formwork. Do not use

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

033000 - 4 CAST-IN-PLACE CONCRETE

curing compound in areas to receive material that does not adhere to concrete cured with a curing compound unless the curing compound is water-soluble.

3.08 WEATHER PROVISIONS

A. Perform cold weather concreting in accordance with ACI 306.

B. Perform hot weather concreting in accordance with ACI 305.

C. Protect concrete from drying and excessive temperature for the first seven days.

D. Protect fresh concrete from wind.

3.09 CONTRACTION JOINTS

A. Provide contraction joints in slabs-on-grade to match existing concrete joints.

3.10 CUTTING CONCRETE

A. Obtain Contracting Officer's written approval prior to cutting concrete for installation of other work.

3.11 PATCHWORK AND REPAIRS

A. Notify Contracting Officer of any defective areas in concrete to be patched or repaired. Repair and patch defective areas with non-shrink grout. Cut out defective areas over 2 inches in diameter to solid concrete but not less than a depth of one inch. Make edges of cuts perpendicular to the concrete surface.

3.12 CONCRETE FINISHES

A. Finish Concrete in accordance with ACI 301.

B. All slabs, including roof slabs, shall be troweled finish, unless noted otherwise.

C. Finish slabs to the following flatness and levelness tolerances:

1. FF25/FL20 minimum overall for composite of all measured values and FF17/FL12 minimum for any individual floor section.

2. Slabs to receive wood flooring: FF45/FL30 minimum overall for composite of all measured values and FF30/FL20 minimum for any individual floor section.

3. Contracting Officer representattive will identify which sections of slabs are to be tested for flatness and levelness.

a. FL values are applicable only if testing is performed within 72 hours of concrete placement, before tensioning of tendons, and before removal of formwork.

b. FF values are applicable to all types of slab construction and are not subject to any time constraints.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

093000 - 1 Tiling

SECTION 093000

TILING

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Tile for floor applications.

B. Trim and accessories for a complete installation.

1.02 RELATED REQUIREMENTS

1.03 REFERENCE STANDARDS

A. ANSI A108.11 - American National Standard Specifications for Interior Installation of Cementitious Backer Units 2018.

B. ANSI A118.5 - American National Standard Specifications for Chemical Resistant Furan Mortars and Grouts for Tile Installation 1999 (Reaffirmed 2016).

C. ANSI A118.12 - American National Standard Specifications for Crack Isolation Membranes for Thin-Set Ceramic Tile and Dimension Stone Installation 2014.

D. ANSI A137.1 - American National Standard Specifications for Ceramic Tile 2019.

E. ASTM F710 - Standard Practice for Preparing Concrete Floors to Receive Resilient Flooring

2019, with Editorial Revision (2020).

F. ASTM F1869 - Standard Test Method for Measuring Moisture Vapor Emission Rate of Concrete

Subfloor Using Anhydrous Calcium Chloride 2016a.

G. TCNA (HB) - Handbook for Ceramic, Glass, and Stone Tile Installation 2019.

1.04 SUBMITTALS

A. See the Statement of Work for submittal procedures.

B. Product Data: Provide manufacturers' data sheets on tile, mortar, grout, and accessories.

Include instructions for using grouts and adhesives.

C. Shop Drawings: Indicate tile layout, patterns, color arrangement, perimeter conditions, junctions with dissimilar materials, control and expansion joints, thresholds, ceramic accessories, and setting details.

D. Samples: provide two samples in actual size of each tile specified.

E. Maintenance Data: Include recommended cleaning methods, cleaning materials, and stain removal methods.

F. Maintenance Materials: Furnish the following for Owner's use in maintenance of project.

1. See the Statement of Work for additional provisions.

2. Extra Tile: 5 percent of each size, color, and surface finish combination, but not less than one box of each type.

1.05 MOCK-UP

A. Construct tile mock-up where indicated on drawings, incorporating all components specified for the location.

1. Approved mock-up may remain as part of the Work.

1.06 DELIVERY, STORAGE, AND HANDLING

A. Protect adhesives from freezing or overheating in accordance with manufacturer's instructions.

1. Deliver packaged materials and store in original containers with seals unbroken and labels intact until time of use, in accordance with manufacturer's instructions. All cartons must be from the same Lot.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

093000 - 2 Tiling

1.07 FIELD CONDITIONS

A. Do not install solvent-based products in an unventilated environment.

B. Maintain ambient and substrate temperature of 50 degrees F during installation of mortar materials.

PART 2 PRODUCTS

2.01 TILE

A. Manufacturers: match existing tile type, color and shape.

1. Or Equal

B. Quarry Tile, Type QT and QTB: ANSI A137.1, standard grade.

1. Provide as floor tile and wall base in locations where existing tile have been demolished.

2. Size: 6 by 6 inch, nominal on floor tile.

3. Thickness: 1/2 inch, nominal.

4. Edges: Square.

5. Surface Finish: Unglazed.

6. Color(s): match existing.

7. Trim Units: Matching cove base shapes in sizes coordinated with field tile.

8. Products:

a. match existing tile.

2.02 TRIM AND ACCESSORIES

A. Trim/Termination Strips: Satin natural anodized extruded aluminum, style and dimensions to suit application, indicated below, or if not indicated to suit application, for setting using tile mortar or adhesive.

1. Floor transitions must be ADA compliant.

2. Applications:

a. Open cut or unfinished edges (end or top) of wall tile equal to Schluter QUADEC.

b. Tile to Tile Outside corners equal to Schluter QUADEC.

c. Tile to carpet transitions equal to Schluter SCHIENE.

d. Tile to VCT transitions equal to Schluter RENO-U

e. Wall corners, outside and inside where tile abuts another material besides tile equal to Schluter QUADEC.

f. Tile to concrete transitions equal to Schluter Reno-Ramp/-K.

g. In other locations as indicated on Drawings.

h. Provide in heights to suit application.

3. Manufacturers:

a. Schluter-Systems: www.schluter.com/#sle.

b. Or Equal .

2.03 SETTING MATERIALS

A. Manufacturers:

1. LATICRETE International, Inc: www.laticrete.com.

2. Merkrete, by Parex USA, Inc: www.merkrete.com.

3. ProSpec, an Oldcastle brand: www.prospec.com.

4. Or Equal.

B. Latex-Portland Cement Mortar Bond Coat: ANSI A118.4.

C. Mortar Bed Materials: Pre-packaged mix of Portland cement, sand, latex additive, and water.

1. Products:

a. LATICRETE International, Inc; LATICRETE 3701 Fortified Mortar Bed:

www.laticrete.com/#sle.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

093000 - 3 Tiling

b. Merkrete, by Parex USA, Inc; Merkrete Underlay C: www.merkrete.com/#sle.

c. Proflex Products, Inc; MSI - Mud Set Installation: www.proflex.us/#sle.

d. Or Equal .

2.04 GROUTS

A. Manufacturers:

1. LATICRETE International, Inc: www.laticrete.com/#sle.

2. Or Equal .

B. Furan Grout: ANSI A118.5 chemical resistant furan resin grout.

1. Applications: use in all areas receiving quarry tile.

2. Color(s): As selected by Contracting Officer from manufacturer's full line matching existing .

3. Products:

a. LATICRETE International, Inc; LATICRETE SPECTRALOCK 2000 IG:

www.laticrete.com/#sle.

b. or Equal.

2.05 ACCESSORY MATERIALS

A. Concrete Floor Slab Crack Isolation Membrane: Material complying with ANSI A118.12; not intended as waterproofing.

1. Thickness: 20 mils, maximum.

2. Crack Resistance: No failure at 1/16 inch gap, minimum.

3. Products:

a. LATICRETE International, Inc; LATICRETE Blue 92 Anti-Fracture Membrane:

www.laticrete.com/#sle.

b. Merkrete, by Parex USA, Inc; Merkrete Fracture Guard: www.merkrete.com/#sle.

c. Or Equal.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that wall surfaces are smooth and flat within the tolerances specified for that type of work, are dust-free, and are ready to receive tile.

B. Verify that sub-floor surfaces are dust-free and free of substances that could impair bonding of setting materials to sub-floor surfaces.

C. Verify that concrete sub-floor surfaces are ready for tile installation by testing for moisture emission rate and alkalinity; obtain instructions if test results are not within the following limits:

1. Moisture Emission Rate: Not greater than 3 lb per 1000 sq ft per 24 hours, test in accordance with ASTM F1869.

2. Alkalinity (pH): Verify pH range of 5 to 9, test in accordance with ASTM F710.

3.02 PREPARATION

A. Protect surrounding work from damage.

B. Vacuum clean surfaces and damp clean.

C. Seal substrate surface cracks with filler. Level existing substrate surfaces to acceptable flatness tolerances.

D. Install backer board in accordance with ANSI A108.11 and board manufacturer's instructions.

Tape joints and corners, cover with skim coat of setting material to a feather edge.

3.03 INSTALLATION - GENERAL

A. Install tile, thresholds, and stair treads and grout in accordance with applicable requirements of ANSI A108.1a through ANSI A108.13, manufacturer's instructions, and TCNA (HB)

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

093000 - 4 Tiling recommendations.

B. Lay tile to pattern indicated. Do not interrupt tile pattern through openings.

C. Extend tile work into recesses and under or behind equipment and fixtures, to form a complete covering without interruptions, except as otherwise shown. Terminate work neatly at obstructions, edges and corners without disrupting pattern or joint alignments.

D. Cut and fit tile to penetrations through tile, leaving sealant joint space. Form corners and bases neatly. Align floor joints.

E. Place tile joints uniform in width, subject to variance in tolerance allowed in tile size. Make grout joints without voids, cracks, excess mortar or excess grout, or too little grout.

F. Form internal angles square and external angles square.

G. Perform cutting and drilling of tile without marring visible surfaces. Carefully grind cut edges of tile abutting trim, finish or built up items for straight aligned joints. Fit tile closely to electrical outlets, piping, fixtures and other penetrations, so that plates, collars or covers overlap tile.

H. Install tile base without wall tile using dry set or latex portland cement.

I. Jointing Pattern: Unless indicated otherwise, lay tile in grid pattern. Layout tile work and center tile fields in both directions in each space or on each wall area. Adjust to minimize tile cutting and slithers of tile. Provide uniform joint widths.

J. Install expansion joints where tile work abuts restraining surfaces such as perimeter walls, columns, etc. Install directly over joints in structural floor including construction joints or cold joints. Set compressible back up strip when mortar is placed or utilize removable wood strips to provide space for back up after mortar has cured. Install sealant after tile work and grout are dry. Follow sealant manufacturer's recommendations.

K. Install non-ceramic trim in accordance with manufacturer's instructions.

L. Sound tile after setting. Replace hollow sounding units.

M. Keep control and expansion joints free of mortar, grout, and adhesive.

N. Prior to grouting, allow installation to completely cure; minimum of 48 hours.

O. Grout tile joints unless otherwise indicated.

P. At changes in plane and tile-to-tile control joints, use tile sealant instead of grout, with either bond breaker tape or backer rod as appropriate to prevent three-sided bonding.

3.04 INSTALLATION - FLOORS - THIN-SET METHODS

A. Over interior concrete substrates, install in accordance with TCNA (HB) Method F113, dry-set or latex-Portland cement bond coat, with standard grout, unless otherwise indicated.

1. Where epoxy bond coat and grout are indicated, install in accordance with TCNA (HB)

Method F131.

2. Where furan bond coat and grout are indicated, install in accordance with TCNA (HB)

Method F133.

B. Install tile-to-tile floor movement joints in accordance with TCNA (HB) Method EJ171F.

3.05 INSTALLATION - FLOORS - MORTAR BED METHODS

A. Over interior concrete substrates, install in accordance with TCNA (HB) Method F112, bonded, unless otherwise indicated.

1. Where epoxy bond coat and grout are indicated, install in accordance with TCNA (HB)

Method F132, bonded.

2. Where epoxy or furan grout is indicated, but not epoxy or furan bond coat, install in accordance with TCNA (HB) Method F114, with cleavage membrane.

B. Cleavage Membrane: Lap edges and ends.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

093000 - 5 Tiling

C. Mortar Bed Thickness: 1 1/2" inch, unless otherwise indicated on Drawings.

3.06 CLEANING

A. Clean tile and grout surfaces per manufacturers requirements for each specific product.

B. Clean all tile surfaces so they are free of foreign matter.

C. Leave tile work clean and free of non-uniform joints, cracked, chipped, broken, unbonded, or otherwise defective tile work.

3.07 PROTECTION

A. Do not permit traffic over finished floor surface for seven days after installation.

B. Protect wall tile surfaces to prevent damage for duration of construction.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

220517 - 1 Sleeves and Sleeve Seals for Plumbing Piping

SECTION 220517

SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Pipe sleeves.

B. Manufactured sleeve-seal systems.

1.02 REFERENCE STANDARDS

A. ASTM C592 - Standard Specification for Mineral Fiber Blanket Insulation and Blanket-Type

Pipe Insulation (Metal-Mesh Covered) (Industrial Type) 2016.

B. ASTM E814 - Standard Test Method for Fire Tests of Penetration Firestop Systems 2013a

(Reapproved 2017).

1.03 SUBMITTALS

A. See the Statement of Work for submittal procedures.

B. Shop Drawings: Indicate pipe materials used, jointing methods, supports, floor and wall penetration seals. Indicate installation, layout, weights, mounting and support details, and piping connections.

1.04 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacturing the Products specified in this section with minimum three years documented experience.

B. Installer Qualifications: Company specializing in performing work of the type specified this section.

1. Minimum three years experience.

C. Clean equipment, pipes, valves, and fittings of grease, metal cuttings, and sludge that may have accumulated from the installation and testing of the system.

1.05 DELIVERY, STORAGE, AND HANDLING

A. Deliver and store sleeve and sleeve seals in shipping containers, with labeling in place.

B. Provide temporary protective coating on cast iron and steel sleeves if shipped loose.

1.06 WARRANTY

A. See the Statement of Work for additional warranty requirements.

B. Correct defective Work within a five year period after Date of Substantial Completion.

PART 2 PRODUCTS

2.01 PIPE SLEEVES

A. Manufacturers:

1. Flexicraft Industries: www.flexicraft.com/#sle.

2. Or Equal .

B. Vertical Piping:

1. Sleeve Length: 1 inch above finished floor.

2. Provide sealant for watertight joint.

3. Blocked Out Floor Openings: Provide 1-1/2 inch angle set in silicon adhesive around opening.

4. Drilled Penetrations: Provide 1-1/2 inch angle ring or square set in silicone adhesive around penetration.

C. Plastic or Sheet Metal: Pipe passing through interior walls, partitions, and floors, unless steel or brass sleeves are specified below.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

220517 - 2 Sleeves and Sleeve Seals for Plumbing Piping

D. Clearances:

1. Provide allowance for insulated piping.

2. Wall, Floor, Floor, Partitions, and Beam Flanges: 1 inch greater than external; pipe diameter.

3. All Rated Openings: Caulked tight with fire stopping material complying with ASTM E814 to prevent the spread of fire, smoke, and gases.

2.02 MANUFACTURED SLEEVE-SEAL SYSTEMS

A. Manufacturers:

1. Flexicraft Industries; PipeSeal: www.flexicraft.com/#sle.

2. Or Equal .

B. Modular/Mechanical Seal:

1. Synthetic rubber interlocking links continuously fill annular space between pipe and wall/casing opening.

2. Provide watertight seal between pipe and wall/casing opening.

3. Elastomer element size and material in accordance with manufacturer's recommendations.

4. Glass reinforced plastic pressure end plates.

PART 3 EXECUTION

3.01 PREPARATION

A. Ream pipe and tube ends. Remove burrs. Bevel plain end ferrous pipe.

B. Remove scale and foreign material, from inside and outside, before assembly.

3.02 INSTALLATION

A. Route piping in orderly manner, plumb and parallel to building structure. Maintain gradient.

B. Install piping to conserve building space, to not interfere with use of space and other work.

C. Install piping and pipe sleeves to allow for expansion and contraction without stressing pipe, joints, or connected equipment.

D. Inserts:

1. Provide inserts for placement in concrete formwork.

2. Provide inserts for suspending hangers from reinforced concrete slabs and sides of reinforced concrete beams.

3. Where concrete slabs form finished ceiling, locate inserts flush with slab surface.

4. Where inserts are omitted, drill through concrete slab from below and provide through-bolt with recessed square steel plate and nut recessed into and grouted flush with slab.

E. Structural Considerations:

1. Do not penetrate building structural members unless indicated.

F. Provide sleeves when penetrating footings, floors, walls, and partitions. Seal pipe including sleeve penetrations to achieve fire resistance equivalent to fire separation required.

1. Underground Piping: Caulk pipe sleeve watertight with lead and oakum or mechanically expandable chloroprene inserts with bitumen sealed metal components.

2. Aboveground Piping:

a. Pack solid using mineral fiber complying with ASTM C592.

b. Fill space with an elastomer caulk to a depth of 0.50 inch where penetrations occur between conditioned and unconditioned spaces.

3. All Rated Openings: Caulk tight with fire stopping material complying with ASTM E814 to prevent the spread of fire, smoke, and gases.

4. Caulk exterior wall sleeves watertight with lead and oakum or mechanically expandable chloroprene inserts with mastic-sealed components.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

220517 - 3 Sleeves and Sleeve Seals for Plumbing Piping

G. Manufactured Sleeve-Seal Systems:

1. Install manufactured sleeve-seal systems in sleeves located in grade slabs and exterior concrete walls at piping entrances into building.

2. Provide sealing elements of the size, quantity, and type required for the piping and sleeve inner diameter or penetration diameter.

3. Locate piping in center of sleeve or penetration.

4. Install field assembled sleeve-seal system components in annular space between sleeve and piping.

5. Tighten bolting for a water-tight seal.

6. Install in accordance with manufacturer's recommendations.

H. When installing more than one piping system material, ensure system components are compatible and joined to ensure the integrity of the system. Provide necessary joining fittings.

Ensure flanges, union, and couplings for servicing are consistently provided.

3.03 CLEANING

A. Upon completion of work, clean all parts of the installation.

B. Clean equipment, pipes, valves, and fittings of grease, metal cuttings, and sludge that may have accumulated from the installation and testing of the system.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

220529 - 1 Hangers and Supports for Plumbing Piping and Equipment

SECTION 220529

HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Support and attachment components for equipment, piping, and other plumbing work.

1.02 REFERENCE STANDARDS

A. ASTM A123/A123M - Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products 2017.

B. ASTM A153/A153M - Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware 2016a.

C. ASTM B633 - Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel 2019.

D. MFMA-4 - Metal Framing Standards Publication 2004.

E. MSS SP-58 - Pipe Hangers and Supports - Materials, Design, Manufacture, Selection, Application, and Installation 2018.

1.03 ADMINISTRATIVE REQUIREMENTS

A. Coordination:

1. Coordinate sizes and arrangement of supports and bases with the actual equipment and components to be installed.

2. Coordinate the work with other trades to provide additional framing and materials required for installation.

3. Coordinate compatibility of support and attachment components with mounting surfaces at the installed locations.

4. Coordinate the arrangement of supports with ductwork, piping, equipment and other potential conflicts installed under other sections or by others.

5. Notify contracting officer of any conflicts with or deviations from Contract Documents.

Obtain direction before proceeding with work.

B. Sequencing:

1. Do not install products on or provide attachment to concrete surfaces until concrete has fully cured.

1.04 SUBMITTALS

A. See the Statement of Work for submittal procedures.

B. Product Data: Provide manufacturer's standard catalog pages and data sheets for metal channel (strut) framing systems and post-installed concrete and masonry anchors .

C. Shop Drawings: Include details for fabricated hangers and supports .

1.05 QUALITY ASSURANCE

A. Comply with applicable building code.

PART 2 PRODUCTS

2.01 SUPPORT AND ATTACHMENT COMPONENTS

A. General Requirements:

1. Comply with MSS SP-58.

2. Provide all required hangers, supports, anchors, fasteners, fittings, accessories, and hardware as necessary for the complete installation of plumbing work.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

220529 - 2 Hangers and Supports for Plumbing Piping and Equipment

3. Provide products listed, classified, and labeled as suitable for the purpose intended, where applicable.

4. Where support and attachment component types and sizes are not indicated, select in accordance with manufacturer's application criteria as required for the load to be supported . Include consideration for vibration, equipment operation, and shock loads where applicable.

5. Do not use wire, chain, perforated pipe strap, or wood for permanent supports unless specifically indicated or permitted.

6. Steel Components: Use corrosion resistant materials suitable for the environment where installed.

a. Indoor Dry Locations: Use zinc-plated steel or approved equivalent unless otherwise indicated.

b. Zinc-Plated Steel: Electroplated in accordance with ASTM B633.

c. Galvanized Steel: Hot-dip galvanized after fabrication in accordance with ASTM

A123/A123M or ASTM A153/A153M.

B. Metal Channel (Strut) Framing Systems:

1. Manufacturers:

a. Cooper B-Line, a division of Eaton Corporation : www.cooperindustries.com/#sle.

b. Thomas & Betts Corporation : www.tnb.com/#sle.

c. Unistrut, a brand of Atkore International Inc : www.unistrut.com/#sle.

d. Source Limitations: Furnish channels (struts) and associated fittings, accessories, and hardware produced by a single manufacturer.

2. Provide factory-fabricated continuous-slot metal channel (strut) and associated fittings, accessories, and hardware required for field-assembly of supports.

3. Comply with MFMA-4.

4. Channel Material:

a. Indoor Dry Locations: Use painted steel, zinc-plated steel, or galvanized steel.

5. Minimum Channel Thickness: Steel sheet, 12 gage, 0.1046 inch.

6. Minimum Channel Dimensions: 1-5/8 inch width by 13/16 inch height.

C. Hanger Rods: Threaded zinc-plated steel unless otherwise indicated.

1. Minimum Size, Unless Otherwise Indicated or Required:

a. Equipment Supports: 1/2 inch diameter.

b. Piping up to 1 inch (27 mm) nominal: 1/4 inch diameter.

c. Piping larger than 1 inch (27 mm) nominal: 3/8 inch diameter.

d. Trapeze Support for Multiple Pipes: 3/8 inch diameter.

D. Anchors and Fasteners:

1. Manufacturers - Mechanical Anchors:

a. Hilti, Inc : www.us.hilti.com/#sle.

b. ITW Red Head, a division of Illinois Tool Works, Inc : www.itwredhead.com/#sle.

c. Powers Fasteners, Inc : www.powers.com/#sle.

d. Simpson Strong-Tie Company Inc : www.strongtie.com/#sle.

e. Or Equal .

2. Manufacturers - Powder-Actuated Fastening Systems:

a. Hilti, Inc : www.us.hilti.com/#sle.

b. ITW Ramset, a division of Illinois Tool Works, Inc : www.ramset.com/#sle.

c. Powers Fasteners, Inc : www.powers.com/#sle.

d. Simpson Strong-Tie Company Inc : www.strongtie.com/#sle.

e. Or Equal .

3. Unless otherwise indicated and where not otherwise restricted, use the anchor and fastener types indicated for the specified applications.

4. Concrete: Use preset concrete inserts, expansion anchors, or screw anchors.

Friday, August 14, 2020 REV 0: Issued For Construction

0110.20.001 / MAHG211108

Replace Sanitary Lines Live Oak Dining

220529 - 3 Hangers and Supports for Plumbing Piping and Equipment

5. Solid or Grout-Filled Masonry: Use expansion anchors or screw anchors.

6. Hollow Masonry: Use toggle bolts.

7. Hollow Stud Walls: Use toggle bolts.

8. Steel: Use beam clamps, machine bolts, or welded threaded studs.

9. Plastic and lead anchors are not permitted.

10. Powder-actuated fasteners are not permitted.

11. Hammer-driven anchors and fasteners are not permitted.

12. Preset Concrete Inserts: Continuous metal channel (strut) and spot inserts specifically designed to be cast in concrete ceilings, walls, and floors.

a. Comply with MFMA-4.

b. Channel Material: Use galvanized steel.

c. Minimum Channel Thickness: Steel sheet, 12 gage, 0.1046 inch minimum base metal thickness.

d. Manufacturer: Same as manufacturer of metal channel (strut) framing system or

Equal.

13. Post-Installed Concrete and Masonry Anchors: Evaluated and recognized by ICC

Evaluation Service, LLC (ICC-ES) for compliance with applicable building code.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that field measurements are as indicated.

B. Verify that mounting surfaces are ready to receive support and attachment components.

C. Verify that conditions are satisfactory for…