Attachment_2_-_Smith_River_BPS_Working_Drawings.pdf
PDF 13 MB Posted
- Solicitation number
- 0000040888
- Issued by
- Del Norte County, California
About this file
Smith River Border Station - HVAC Split System Working Drawings
This is a set of working drawings prepared by GHD Inc. for the State of California Department of General Services (DGS), Division of the State Architect (DSA), for the Smith River Border Station HVAC Split System project located at 17200 US 101, Smith River, California 95567. The project involves the installation of a ductless split HVAC system to replace existing furnace and associated equipment. The scope includes demolition of existing furnace, return and supply registers, and flex ductwork; installation of four ductless fan coil units (FC-101, FC-102, FC-103, and FC-201) with associated refrigerant piping and condensate drain systems; installation of supply fan filter boxes with MERV-13 filters; and installation of new electrical distribution panel and disconnect switches. The project includes modifications to both the floor level and a 438-square-foot mezzanine area. DGS Project Number 13984 references work order M29562 with an expiration date of June 30, 2027. Project Manager Anthony Brown and mechanical engineer Terry Wong are identified as responsible parties. The drawings were prepared as of February 2, 2026, and reviewed by DSA on April 14, 2026.
The working drawings establish detailed design specifications and installation requirements, including thermostat mounting heights of 48 inches above finished floor and ductless fan coil mounting at 80 inches above finished floor to the unit's bottom. Electrical work requires compliance with the latest California Electrical Code and includes a 200-ampere, 240-volt, single-phase meter main panel with branch circuit panel replacement and dedicated disconnect switches for equipment. The documents specify that all existing equipment and piping dimensions and locations must be verified in the field prior to demolition and construction, with all discrepancies reported immediately to the engineer. Refrigerant piping uses 3/8-inch suction lines and 1/4-inch liquid lines, and condensate drains consist of 5/8-inch copper pipe routed to the nearest lavatory fixture or daylighted outdoors six inches above finished grade. The project requires coordination with the owner regarding shutdown of existing systems and adherence to manufacturer's installation instructions for all equipment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 26-0094_IFB_Public_Works.pdf | ||
| 26-0094_COST_PROPOSAL.xlsx | XLSX spreadsheet | |
| Attachment_4_-_SR_BPS_Project_Manual__Specifications_.pdf | ||
| Non-Collusion.pdf | ||
| Labor_Code_Certifications.pdf | ||
| Attachment_3_-_SR_BPS_Working_Drawings_-_As-built_Excerpts.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TEST MARK (For DSA Use Only) Prior to adding document to the Session the Plan Reviewer shall place this test mark off the top edge of the first sheet and change status to "INCORPORATE".
If Back-check menu does not show or the color does not change to green, the Plan Reviewer shall fix the back-check menu. For guidance on how to fix the back-check menu, refer to PR 18-06, Appendix D, Checklist D2.
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
01-122926
04/14/2026
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
01-122926
M001
MECHANICAL LEGEND,
ABBREVIATIONS AND
GENERAL NOTES
AS NOTED
02-02-2026
13984
CONSULTANT:
117 PARK PLACE
POINT RICHMOND
CALIFORNIA 94801
(510) 236-7435 www.intres.com
IR PROJECT #2017-050-06
STAMP:
ABCDEFGHIJKLMNOPQRSTU
ABCDEFGHIJKLMNOPQRSTU
Issue No.
Date Description
Project
Supervisor Designed Drawn Checked
File Date Vault File Number
Sheet Title
DGS Project # Work Order
Reference North Sheet Scale
Sheet Number
X
Project Manager: Anthony Brown 916 879-1021 Voice
Anthony.brown@ dgs.ca.gov
707 Third Street, 3rd Floor
Design Services Section
Facility Management Division State of California
West Sacramento, California 95605
Department of General Services
GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 W www.ghd.com
SMITH RIVER
BORDER
STATION - HVAC
SPLIT SYSTEM
17200 US 101
SMITH RIVER, CALIFORNIA 95567
DGS PROJ #13984
M29562 6/30/27
No.
Exp.
RE
G I
S T
ER
ED PRO F E S S I ON A L ENGI NEER
S TA T E O F C A L I F O R N I A
T E R R Y W O NG
M E C H A N I C A L
GENERAL MECHANICAL NOTESABBREVIATIONS
FD
FSD
M
DUCT SECTION, SUPPLY AIR UP
DUCT SECTION, RETURN AIR UP
DUCT SECTION, EXHAUST AIR UP
DUCT SECTION, SUPPLY AIR DN
DUCT SECTION, RETURN AIR DN
DUCT SECTION, EXHAUST AIR DN
FLEXIBLE DUCT
FIRE AND SMOKE DAMPER
FIRE DAMPER
DIRECTION OF FLOW
MANUAL VOLUME DAMPER
WALL SUPPLY OUTLET, RETURN GRILLE
CEILING DIFFUSER
CEILING RETURN
CEILING EXHAUST
DUCT SMOKE DETECTOR
THERMOSTAT
REMOTE SENSOR
MOTORIZED ACTUATOR
S
AV
FOS
CWS
SYMBOL
FUEL OIL (SUPPLY)
FUEL OIL (RETURN)
CHILLED WATER SUPPLY
CHILLED WATER RETURN
HEATING HOT WATER SUPPLY
HEATING HOT WATER RETURN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
REFRIGERANT LIQUID
REFRIGERANT SUCTION
AUTOMATIC AIR VENT
BLOW OFF STRAINER
FILTER AND STRAINER LINE
PRESSURE GAGE
PRESSURE GAGE AND COCK
PRESSURE REDUCING VALVE
RELIEF OR SAFETY VALVE
STRAINER
TEMPERATURE GAGE
PUMP (PLAN)
PUMP (SCHEMATIC)
EXPANSION LOOP
CAP
CONCENTRIC REDUCER
UNION
THREE-WAY MANUAL VALVE
BALL VALVE
BUTTERFLY VALVE
DIAPHRAGM VALVE
GATE VALVE
GLOBE VALVE
CHECK VALVE
POINT OF CONNECTION
FLEXIBLE CONNECTOR
THERMOMETER
PETE'S PLUG
AIR TERMINAL IDENTIFICATION
AIR TERMINAL MARK
AIRFLOW, CFM
NOTE:
ARROWS INDICATE DIRECTION OF AIRFLOW
NO ARROWS INDICATE 4-WAY AIRFLOW
AIR TERMINAL NECK SIZE (IF SHOWN)
KEYNOTE
ROOM NAME AND ROOM NUMBER
DETAIL INDICATOR SECTION INDICATOR
MECHANICAL EQUIPMENT
DESIGNATION
(SEE SCHEDULE)
DETAIL NUMBER
SHEET NUMBER ON WHICH DETAIL
APPEARS
SECTION LETTER
SHEET NUMBER ON WHICH SECTION
APPEARS
SHEET ANNOTATION
CARBON DIOXIDE SENSOR
DESCRIPTION
FOR
CWR
HHWS
HHWR
CS
CR
RL
RS
P
A AMPERES, AREA
ABS ACRYLONITRILE-BUTADIENE
-STYRENE
AD AREA DRAIN
AFF ABOVE FINISHED FLOOR
AG ABOVE GRADE
APPROX APPROXIMATE
AS AIR SEPARATOR
AVG AVERAGE
BD BALANCE DAMPER
BDD BACK DRAFT DAMPER
BFP BACK FLOW PREVENTER
BG BELOW GRADE
BHP BRAKE HORSEPOWER
BOD BOTTOM OF DUCT
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT
PER HOUR
C CELSIUS
℄ CENTERLINE
CCW COUNTER CLOCKWISE
CD CEILING DIFFUSER,
CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWP CHILLED WATER PUMP
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CI CAST IRON
CMPR COMPRESSOR
CONT CONTINUED
CT COOLING TOWER
CU COPPER
CU FT CUBIC FEET
CU IN CUBIC INCHES
CW COLD WATER, CLOCKWISE
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN,
CWS CONDENSER WATER SUPPLY
CWV COMBINATION WASTE & VENT
D DEPTH
DB DECIBEL, DRY BULB
DEG DEGREE(S)
DIA DIAMETER
DN DOWN
DPT DIFFERENTIAL PRESSURE
TRANSMITTER
DS DOWN SPOUT
DWG DRAWING
(E) EXISTING
EA EACH
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EFF EFFICIENCY
EG EXHAUST GRILLE
ELEV ELEVATION
ENT ENTERING
ESP EXTERNAL STATIC PRESSURE
F FLOW
FACP FIRE ALARM CONTROL PANEL
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN, FIRE DAMPER
FDC FIRE DEPARTMENT
CONNECTION
FM FLOW METER
FP FIRE PROTECTION
FPI FINS PER INCH
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOW SWITCH
FSD FIRE/SMOKE DAMPER
FSP FIRE SPRINKLER
FT FOOT, FEET
G GAS
GA GAUGE
GALV GALVANIZED
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPS GALLONS PER SECOND
HD HEAD
HG MERCURY
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HP HORSEPOWER
HR HOSE REEL, HOUR
HT HEIGHT
HVAC HEATING, VENTILATION
& CONDITIONING
HW HOT WATER
HWR HOT WATER RETURN
HZ FREQUENCY
ID INSIDE DIAMETER
INVERT INVERT ELEVATION
IW INDIRECT WASTE
KW KILOWATTS
KWH KILOWATTS PER HOUR
L LENGTH
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LF LINEAR FEET
LPG LIQUID PETROLEUM GAS
LTG LIGHTING
LVG LEAVING
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH 1,000 BTUH
MCC MOTOR CONTROL CENTER
MD MOTORIZED DAMPER
MFR MANUFACTURER
MIN MINIMUM, MINUTE
MTD MOUNTED
MUA MAKE UP AIR
(N) NEW
NC NORMALLY CLOSED, NOISE CRITERIA
NIC NOT IN CONTRACT
NO NORMALLY OPEN, NUMBER
NTS NOT TO SCALE
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER
ORD OVERFLOW ROOF DRAIN
PB POLYBUTYLENE
PE POLYETHYLENE
PPM PARTS PER MILLION
POC POINT OF CONNECTION
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH,
ABSOLUTE
PSIG POUNDS PER SQUARE INCH, GAGE
PVC POLYVINYL CHLORIDE
RA RETURN AIR
RD ROOF DRAIN
REQ REQUIRED
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
RPS REVOLUTIONS PER SECOND
SAD SEE ARCHITECTURAL DRAWINGS
STD STANDARD
SOV SHUT OFF VALVE
SD SUPPLY DIFFUSER, STORM DRAIN
SS SANITARY SEWER, STAINLESS STEEL
TD TEMPERATURE DIFFERENTIAL
TEMP TEMPERATURE
TOD TOP OF DUCT
TP TOTAL STATIC PRESSURE
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VENT, VOLT
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
VP VELOCITY PRESSURE
VTR VENT THROUGH ROOF
W WIDTH
W/ WITH
WB WET BULB
WG WATER GAGE
W/O WITHOUT
WRG WALL RETURN GRILLE
WSR WALL SUPPLY REGISTER
WH WATER HEATER
WHA WATER HAMMER ARRESTOR
XFMR TRANSFORMER
YR YEAR
Z ZONE
HVAC PIPING
MECHANICAL SYMBOLS LEGEND
1. THESE DRAWINGS ARE BASED UPON AVAILABLE DOCUMENTS, WHICH MAY NOT ACCURATELY
PORTRAY AS-BUILT CONDITIONS. EXISTING EQUIPMENT AND PIPING SIZES, LOCATIONS, AND
DIMENSIONS SHALL BE VERIFIED IN THE FIELD PRIOR TO DEMOLITION AND CONSTRUCTION.
NOTIFY THE ENGINEER IMMEDIATELY OF ALL DISCREPANCIES AFFECTING THE REMOVAL OF
EXISTING EQUIPMENT AND PIPING, AND THE INSTALLATION OF NEW EQUIPMENT AND PIPING.
2. INSTALL PIPING AND DUCTWORK TO BEST SUIT FIELD CONDITIONS AND COORDINATE WITH THE
INSTALLATION WORK OF OTHER TRADES. THESE DRAWINGS ARE DIAGRAMMATIC, DO NOT SCALE
TO DETERMINE EXACT LOCATION OF PIPING.
3. PROTECT ALL EXISTING EQUIPMENT THAT IS TO REMAIN. VERIFY WITH OWNER WHAT SYSTEMS
WILL REMAIN OPERATIONAL THROUGHOUT CONSTRUCTION. NOTIFY THE OWNER PRIOR TO
SHUTTING DOWN ANCILLARY SYSTEMS OR EQUIPMENT.
4. REPAIR AND/OR REPLACE ALL EXISTING UTILITIES, STRUCTURAL ELEMENTS, EQUIPMENT, PIPING, CONDUIT, DUCTWORK, ETC. THAT IS DAMAGED OR BECOMES INOPERABLE AS A RESULT OF THIS
WORK.
5. COORDINATE MODIFICATIONS TO EXISTING SYSTEMS WITH OWNER TO MINIMIZE SHUTDOWN TIME
OF BUILDING SYSTEMS.
6. FOR ALL MECHANICAL SYSTEMS CONTROLS, PROVIDE CONDUIT AND WIRING IN ACCORDANCE
WITH DIVISION 26 SPECIFICATIONS AND MANUFACTURER'S REQUIREMENTS.
7. ALL SANITARY AND SANITARY VENT PIPING SHALL SLOPE AT 14" PER 12" UNLESS OTHERWISE
NOTED.
SYMBOLDESCRIPTION
DD
T
CO2
12x12 SD-1
WH
X-501
A X-301
MECH ROOM
RCR RCR DBR
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
01-122926 http://www.ghd.com/
FD
A
B
C
D
E
1 2 3 4 5
WOMEN
MEN
INSPECTION
BAYS
STORAGE
GENERATOR
OFFICE
A
B
C
D
E
1 2 3 4 5
438 SF
MEZZANINE
M101
FLOOR AND
MEZZANINE PLANS
SMITH RIVER, CALIFORNIA 95567
AS NOTED
02-02-2026
13984
CONSULTANT:
117 PARK PLACE
POINT RICHMOND
CALIFORNIA 94801
(510) 236-7435 www.intres.com
IR PROJECT #2017-050-06
STAMP:
ABCDEFGHIJKLMNOPQRSTU
ABCDEFGHIJKLMNOPQRSTU
Issue No.
Date Description
Project
Supervisor Designed Drawn Checked
File Date Vault File Number
Sheet Title
DGS Project # Work Order
Reference North Sheet Scale
Sheet Number
X
Project Manager: Anthony Brown 916 879-1021 Voice
Anthony.brown@ dgs.ca.gov
707 Third Street, 3rd Floor
Design Services Section
Facility Management Division State of California
West Sacramento, California 95605
Department of General Services
GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 W www.ghd.com
SMITH RIVER
BORDER
STATION - HVAC
SPLIT SYSTEM
17200 US 101
SMITH RIVER, CALIFORNIA 95567
DGS PROJ #13984
M29562 6/30/27
No.
Exp.
RE
G I
S T
ER
ED PRO F E S S I ON A L E NGI NEER
STA T E O F C A L I F O R N I A
T E R R Y W O N G
M E C H A N I C A L
1/4" = 1'-0"2 MEZZANINE PLAN
1/4" = 1'-0"1 FLOOR PLAN
FC
FC
FC
FC
HP
(E) FURNACE
HP
(E) GENERATOR
(E) LPG STORAGE TANKS
TFC-101
TFC-102
TFC-103
T FC-201
(E) SUPPLY REGISTER
TO REMAIN
(E) RETURN REGISTER
(E) 1/2" GAS LINE
L
8"Ø
8" Ø
SHEET GENERAL NOTES
1. MOUNT THERMOSTATS 48" ABOVE FINISHED FLOOR TO TOP OF THERMOSTAT.
2. MOUNT DUCTLESS FAN COILS 80" ABOVE FINISHED FLOOR TO BOTTOM OF UNIT.
SHEET KEYNOTES
1. DEMOLISH EXISTING FURNACE AND ASSOCIATED APPURTENANCES. DISCONNECT GAS
LINE AND CAP. CAP THE BOTTOM OF FLUE, FLUE TO REMAIN ABANDONED IN PLACE.
2. DEMOLISH EXISTING RETURN REGISTER AND PATCH OPENING INTO SPACE. MATCH PAINT
WITH EXISTING.
3. DEMOLISH EXISTING FLEX DUCT AND ASSOCIATED APPURTENANCES.
4. DEMOLISH EXISTING SUPPLY REGISTER AND PATCH OPENING INTO SPACE. MATCH PAINT
WITH EXISTING.
5. PROVIDE FAN FILTER BOX WITH 24" x 12" x 2" MERV-13 FILTER. REFER TO SUPPLY FAN
SCHEDULE ON SHEET M-601 FOR FILTER BOX SIZING. PROVIDE FLEXIBLE CONNECTION
BETWEEN FAN AND DUCTWORK.
6. 12" W x 10" H LOUVER OPENING. PROVIDE STAINLESS STEEL INSECT SCREEN.
7. ROUTE 5/8" CONDENSATE DRAIN TO NEAREST LAVATORY FIXTURE TAILPIECE. PROVIDE
LAVATORY TAILPIECE W/ CONDENSATE DRAIN CONNECTION.
8. DAYLIGHT 5/8" DWV COPPER CONDENSATE DRAIN OUTDOORS, TERMINATE 6" ABOVE
FINISHED GRADE.
(E) 6"Ø FLEX DUCT
SF
REUSE EXISTING FLEX DUCT
(E) 1/2" GAS LINE
(E) 1/2" GAS LINE
(E) 1/2" GAS LINE
CONTINUED ON 2, M101
(E) SUPPLY REGISTER
TO REMAIN
(E) SUPPLY REGISTER
TO REMAIN
RCR RCR DBR
5/8" CONDENSATE DRAIN
3/8" SUCTION
1/4" LIQUID
3/8" SUCTION
1/4" LIQUID
3/8" SUCTION
1/4" LIQUID
3/8" SUCTION
1/4" LIQUID
5/8" CONDENSATE DRAIN
3/8" SUCTION
1/4" LIQUID TO FC-103
3/8" SUCTION
1/4" LIQUID TO FC-101 & FC-102
3/8" SUCTION
1/4" LIQUID TO FC-201
5/8" CONDENSATE DRAIN FROM HP-1
5/8" CONDENSATE DRAIN FROM HP-2 8
5/8" CONDENSATE DRAIN.
ROUTE THROUGH ATTIC
SPACE
5/8" CONDENSATE DRAIN.
ROUTE THROUGH ATTIC
SPACE
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
01-122926
ALIGN VERTICAL LEGS OF WALL
BRACKETS W/ (E) STUDS
(N) x4 BLOCKING BETWEEN (E) STUDS
(E) STUDS @ 16" OC. VERIFY IN FIELD
(5 MIN) 3" LAG SCREWS, 1/4" DIA MIN, UPSIZE AS
NEEDED TO FIT EQUIPMENT MOUNTING HOLES
(3) 3" LAG SCREWS PER LEG, 1/4"
DIA MIN, UPSIZE AS NEEDED TO
FIT EQUIPMENT MOUNTING HOLES
EMBED
SCREWS PER PROFILE
(E) STUD WALL
BLOCKING PER PROFILE
PROFILE ELEVATION
MIN 3"
MAX 30"
MIN 10.5"
MAX 16"
M601
MECHANICAL DETAILS
AND SCHEDULES
RCR RCR DBR
AS NOTED
02-02-2026
13984
CONSULTANT:
117 PARK PLACE
POINT RICHMOND
CALIFORNIA 94801
(510) 236-7435 www.intres.com
IR PROJECT #2017-050-06
STAMP:
ABCDEFGHIJKLMNOPQRSTU
ABCDEFGHIJKLMNOPQRSTU
Issue No.
Date Description
Project
Supervisor Designed Drawn Checked
File Date Vault File Number
Sheet Title
DGS Project # Work Order
Reference North Sheet Scale
Sheet Number
X
Project Manager: Anthony Brown 916 879-1021 Voice
Anthony.brown@ dgs.ca.gov
707 Third Street, 3rd Floor
Design Services Section
Facility Management Division State of California
West Sacramento, California 95605
Department of General Services
GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 W www.ghd.com
SMITH RIVER
BORDER
STATION - HVAC
SPLIT SYSTEM
17200 US 101
SMITH RIVER, CALIFORNIA 95567
DGS PROJ #13984
M29562 6/30/27
No.
Exp.
RE
G I
S T
ER
ED PRO F E S S I ON A L E NGI NEER
STA T E O F C A L I F O R N I A
T E R R Y W O N G
M E C H A N I C A L
1 WALL BRACKET ANCHORAGE
NTS
HANGER BRACKET
3/8"Ø ASTM A36 GALVANIZED
THREADED ROD W/ NUT AND
WASHER AT EACH SIDE OF
ATTACHMENT TO EQUIPMENT
AND ATTACHMENT TO UNISTRUT,
TYP.
DUCT
MECHANICAL
EQUIPMENT AS
SHOWN ON PLANS
3" x 3" x 12" W/(1) 1/2" DIA THRU BOLT OR 12" DIA x
3-1/2" LAG BOLT, TYP.
" M
AX
2 SUSPENDED FAN DETAIL
NTS
FINISHED WALL
WALL MOUNTED DUCTLESS
AIR HANDLING UNIT AND
INSTALLATION PLATE
#10 SCREWS
(TYP. 2) AT EACH
WALL STUD
BLOCKING AS REQUIRED
WITH #10 SCREWS (TYP. 2)
AT EACH WALL STUD.
WALL STUD.
3 DUCTLESS FAN COIL MOUNTING
NTS
NOTE: REFER TO MANUFACTURERS INSTRUCTIONS FOR
INSTALLATION. MOUNT UNIT 80" ABOVE FINISHED FLOOR TO
BOTTOM OF UNIT.
A35, FRAMING CLIP W/#8 FHWS AT
EACH SIDE, TOP & BOTTOM, TYP.
NOTE: REFER TO MFR INSTRUCTIONS FOR MOUNTING
CONDENSING UNIT TO BRACKET.
2" P-TRAP
GROUND JOINT CONNECTION
5/8" CONDENSATE
DRAIN CONNECTION
FINISHED WALL
2" FEMALE NPT OUTLET
WALL ESCUTEON
4 TAILPIECE CONDENSATE DRAIN CONNECTION DETAIL
NOT TO SCALE
BACK-UP
MATERIAL
WATERPROOF
SEALANT
WALL
PIPE SLEEVE
PIPE
INSULATION WHERE REQUIRED
ESCUTCHEON PLATE
(WHERE EXPOSED)ANCHOR
EXTERIOR INTERIOR
5 PIPE THRU EXTERIOR WALL DETAIL
NOT TO SCALE
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
01-122926
M701
MECHANICAL
TITLE 24
AS NOTED
02-02-2026
13984
CONSULTANT:
117 PARK PLACE
POINT RICHMOND
CALIFORNIA 94801
(510) 236-7435 www.intres.com
IR PROJECT #2017-050-06
STAMP:
ABCDEFGHIJKLMNOPQRSTU
ABCDEFGHIJKLMNOPQRSTU
Issue No.
Date Description
Project
Supervisor Designed Drawn Checked
File Date Vault File Number
Sheet Title
DGS Project # Work Order
Reference North Sheet Scale
Sheet Number
X
Project Manager: Anthony Brown 916 879-1021 Voice
Anthony.brown@ dgs.ca.gov
707 Third Street, 3rd Floor
Design Services Section
Facility Management Division State of California
West Sacramento, California 95605
Department of General Services
GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 W www.ghd.com
SMITH RIVER
BORDER
STATION - HVAC
SPLIT SYSTEM
17200 US 101
SMITH RIVER, CALIFORNIA 95567
DGS PROJ #13984
M29562 6/30/27
No.
Exp.
RE
G I
S T
ER
ED PRO F E S S I ON A L ENGI NEER
STA T E O F C A L I F O R N I A
T E R R Y W O NG
M E C H A N I C A L
RCR RCR DBR
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
01-122926
EDGE OF ELECTRICAL BOX BOLT
HOLES TO ALIGN WITH STUDS
PROFILE ELEVATION
EMBED
(4) 3" LAG SCREWS, 1/4" Ø MIN,
UPSIZE AS NEEDED TO FIT
EQUIPMENT MOUNTING HOLES
1'-3"2 1/2"2" 4'-
4" 2"
2 1/2"
SCREWS PER PROFILE
(E) STUD @ 16" OC,
VERIFY IN FIELD
(E) STUD WALL
EMBED
(2) 3" LAG SCREWS, 1/4" Ø MIN,
UPSIZE AS NEEDED TO FIT
EQUIPMENT MOUNTING HOLES
EDGE OF DISCONNECT BOX
(N) x4 BLOCKING
BETWEEN (E) STUDS
(E) STUD @ 16" OC,
VERIFY IN FIELD
SCREWS PER PROFILE
(E) STUD WALL
PROFILE ELEVATION
6"2"
1 3 /4" 2"
BLOCKING PER PROFILE
E001
ELECTRICAL LEGEND,
ABBREVIATIONS AND
GENERAL NOTES
17200 US 101
SMITH RIVER, CALIFORNIA 95567
DGS PROJ #13984
RK RK EAO
AS NOTED
02-02-2026
13984
CONSULTANT:
117 PARK PLACE
POINT RICHMOND
CALIFORNIA 94801
(510) 236-7435 www.intres.com
IR PROJECT #2017-050-06
STAMP:
ABCDEFGHIJKLMNOPQRSTU
ABCDEFGHIJKLMNOPQRSTU
Issue No.
Date Description
Project
Supervisor Designed Drawn Checked
File Date Vault File Number
Sheet Title
DGS Project # Work Order
Reference North Sheet Scale
Sheet Number
X
Project Manager: Anthony Brown 916 879-1021 Voice
Anthony.brown@ dgs.ca.gov
707 Third Street, 3rd Floor
Design Services Section
Facility Management Division State of California
West Sacramento, California 95605
Department of General Services
GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 W www.ghd.com
SMITH RIVER
BORDER
STATION - HVAC
SPLIT SYSTEM
17200 US 101
SMITH RIVER, CALIFORNIA 95567
DGS PROJ #13984
ANNOTATION
CONDUIT
MAIN SWITCHBOARD
DISTRIBUTION PANEL BOARD
COMBINATION METER/MAIN SERVICE PANEL
BRANCH CIRCUIT PANEL BOARD, SURFACE OR FLUSH MOUNTED
LIGHTING CONTROL PANEL
SIGNAL TERMINAL CABINET OR CONTROL PANEL
SURFACE OR FLUSH MOUNTED
SIGNAL TERMINAL BACKBOARD
CONCRETE UNDERGROUND HAND HOLE
(NUMBER DENOTES CHRISTY SIZE)
TRANSFORMER
EQUIPMENT
OR
OR
N30
OR
OR
DENOTES HEIGHT IN INCHES
AFF (INTERIOR) AFG (EXTERIOR)
GENERAL ELECTRICAL NOTESELECTRICAL SYMBOLS LEGEND
KEYNOTE
RACEWAY, FEEDER OR CIRCUIT DESIGNATION (SEE SCHEDULE)
LIGHTING FIXTURE TYPE DESIGNATION
(SEE SCHEDULE)
DETAIL INDICATOR SECTION INDICATOR
MECHANICAL EQUIPMENT DESIGNATION
(SEE SCHEDULE)
DUPLEX RECEPTACLE, 20A 125V 2P 3W, GROUNDING TYPE,
MOUNTING HEIGHT: +18" AFF UON
DUPLEX RECEPTACLE - EMERGENCY POWER
SPECIAL PURPOSE RECEPTACLE AS DESIGNATED
SEE 'SPECIAL SYMBOLS' ON EACH SHEET
JUNCTION BOX, CODE SIZED UON
DISCONNECT SWITCH - FUSED WHERE APPLICABLE
MOTOR STARTER, COMBINATION WITH DISCONNECT SWITCH
MOTOR STARTER OR CONTROLLER
MOTOR CONNECTION
POWER POLE: P=POWER, T=TELEPHONE, D=DATA, C=COMBINATION
GROUND ROD
GUY WIRE AND ANCHOR
CONDUIT INSTALLED ABOVE GRADE
CONDUIT INSTALLED UNDERGROUND OR UNDER SLAB
CONDUIT STUB-OUT WITH CAP
FLEXIBLE CONDUIT WHIP TO LIGHT FIXTURE OR EQUIPMENT
DENOTES TYPE
DENOTES WATTS
POWER
#10
CONDUIT HOME RUN TO DESIGNATED PANEL, TERMINAL, OR CONTROL CABINET
EXAMPLES:
NOTE FOR CONDUIT: THE TIC MARKS INDICATE THE QUANTITY OF #12 AWG WIRES
OR, IF INDICATED, THE QUANTITY OF OTHER SIZE WIRE OR CABLES.
SEE THE SINGLE LINE DIAGRAM FOR FEEDER SIZES.
EXAMPLES: = (3) #12 = (2) #10
L1-4
INDICATES
BRANCH PANEL
INDICATES CIRCUIT
BREAKER I.D.
COMMA INDICATES MULTIPLE
SINGLE POLE CIRCUITS
L1-6,8 L1-10/12
SLASH INDICATES
MULTI-POLE CIRCUIT
= (1) TYPE F1 CABLE. SEE CABLE SCHEDULE.
DETAIL NUMBER
SHEET NUMBER ON
WHICH DETAIL APPEARS
SECTION LETTER
SHEET NUMBER ON WHICH
SECTION APPEARS
OR
OR
OBJECT LINES
NEW OBJECTS
(HEAVY CONTINUOUS LINES, UNDERGROUND CONDUIT
HEAVY DASHED LINES)
EXISTING OBJECTS TO REMAIN. MAY INCLUDE NEW CIRCUITING ETC.
(FINE CONTINUOUS LINES, UNDERGROUND CONDUIT
FINE DASHED LINES)
EXISTING OBJECTS TO BE DEMOLISHED
(EXTRA FINE DASHED LINES, SCREENED)
ABBREVIATIONS
(D) DEMOLISH
(E) EXISTING
(F) FUTURE
(N) NEW
A AMPERES
AC ALTERNATING CURRENT
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPS INTERRUPTING CAPACITY
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BAT BATTERY
BFG BELOW FINISH GRADE
CATV CABLE TELEVISION
C CONDUIT
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CO CONDUIT ONLY
CPT CONTROL POWER TRANSFORMER
CT CURRENT TRANSFORMER
CU COPPER
DC DIRECT CURRENT
EF EXHAUST FAN
EGU ENGINE GENERATOR UNIT
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENT ELECTRICAL NON-METALLIC TUBING
EP EXPLOSION PROOF
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FU FUSE
GND GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GFR GROUND FAULT RELAY
HID HIGH INTENSITY DISCHARGE
HOA "HAND-OFF-AUTO" SWITCH
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HVAC HEATING, VENTILATION &
AIR-CONDITIONING
IG ISOLATED GROUND
JB JUNCTION BOX
KAIC KILO-AMPS INTERRUPTING CAPACITY
KV KILOVOLT
KVA KILOVOLT-AMP
KW KILOWATT
KWH KILOWATT-HOUR
LPG LIQUID PROPANE GAS
LPS LOW PRESSURE SODIUM
LV LOW VOLTAGE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTOR
MFR MANUFACTURER
MH METAL HALIDE
MLO MAIN LUGS ONLY
MV MEDIUM VOLTAGE
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NTS NOT TO SCALE
PA PUBLIC ADDRESS
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
PB PULL BOX, ELECTRICAL
RECPT RECEPTACLE, OUTLET
RGS RIGID GALVANIZED STEEL (CONDUIT)
RVSS REDUCED VOLTAGE SOFT START
RTU REMOTE TERMINAL UNIT
TV TELEVISION MONITOR (SET)
TVSS TRANS. VOLT. SURGE SUPPRESSOR
UF UNDER FLOOR
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
VA VOLT-AMP
VFD VARIABLE FREQUENCY DRIVE
WP WEATHERPROOF
WPI WEATHERPROOF IN USE
XFMR TRANSFORMER
1. ALL WORK SHALL CONFORM TO THE LATEST ADOPTED VERSION OF THE CALIFORNIA
ELECTRICAL CODE (CEC).
2. THE CONTRACTOR SHALL MAINTAIN ALL EQUIPMENT IN A SAFE AND RESPONSIBLE MANNER.
KEEP DEAD FRONT EQUIPMENT IN PLACE WHILE EQUIPMENT IS ENERGIZED. CONDUCT ALL
CONSTRUCTION OPERATIONS IN A SAFE MANNER FOR EMPLOYEES AS WELL AS OTHER WORK
PERSONS OR ANYONE VISITING THE JOB SITE. PROVIDE BARRIERS, FLAGS, TAPE, ETC. AS
REQUIRED TO MAINTAIN SAFETY.
3. PRIOR TO COMMENCING WORK ON EXISTING SYSTEMS OR WHERE EXISTING SYSTEMS REQUIRE
TEMPORARY SHUT DOWNS, COORDINATE WITH OWNERS REPRESENTATIVE. WHERE
DISCONNECTING, MODIFYING OR WORKING ON EXISTING EQUIPMENT OR SYSTEMS, PROVIDE A
WRITTEN METHOD OF PROCEDURE OUTLINING DATES, TIMES, DURATION AND DESCRIPTION OF
PROPOSED WORK FOR APPROVAL PRIOR TO COMMENCING WORK . WORK ON EXISTING
EQUIPMENT SHALL NOT COMMENCE UNTIL WRITTEN AUTHORIZATION IS GIVEN BY THE OWNERS
REPRESENTATIVE.
4. ALL EQUIPMENT SHALL BE LISTED AND LABELED PER RECOGNIZED ELECTRICAL TESTING
LABORATORY AND INSTALLED PER THE LISTING REQUIREMENTS AND THE MANUFACTURERS
INSTRUCTIONS.
5. ALL EQUIPMENT SHALL BE GROUNDED PER THE REQUIREMENTS OF CEC ARTICLE 250.
EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED IN ALL POWER SYSTEM
RACEWAYS.
6. CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL DIMENSIONS PRIOR TO
CONSTRUCTION.
7. ALL WORK ON OR AROUND UTILITY EQUIPMENT AND FEEDERS SHALL BE COORDINATED WITH
THAT UTILITY. ALL WORK ON UTILITY EQUIPMENT SHALL BE TO UTILITY STANDARDS AND
REQUIREMENTS.OR
J
J
J
T
A
WH
E-501
A E-301
F1
P
M
J J
+48"
1 PANEL BOARD ANCHORAGE NOT TO SCALE
2 DISCONNECT SWITCH ANCHORAGE NOT TO SCALE
EAO
E25957RE
G I
S T
ER
ED PRO F E S S I ON A L ENG I NEER
S T A T E O F C A L I F O R N I A
E L E C T R I C A L
RE
B E
C C A O . K EA T I NG
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
01-122926
A
B
C
D
E
1 2 3 4 5
WOMEN
MEN
INSPECTION
BAYS
STORAGE
GENERATOR
OFFICE
A
B
C
D
E
1 2 3 4 5
438 SF
MEZZANINE
E101
ELECTRICAL SITE
PLAN
17200 US 101
SMITH RIVER, CALIFORNIA 95567
DGS PROJ #13984
RK RK EAO
AS NOTED
02-02-2026
13984
CONSULTANT:
117 PARK PLACE
POINT RICHMOND
CALIFORNIA 94801
(510) 236-7435 www.intres.com
IR PROJECT #2017-050-06
STAMP:
ABCDEFGHIJKLMNOPQRSTU
ABCDEFGHIJKLMNOPQRSTU
Issue No.
Date Description
Project
Supervisor Designed Drawn Checked
File Date Vault File Number
Sheet Title
DGS Project # Work Order
Reference North Sheet Scale
Sheet Number
X
Project Manager: Anthony Brown 916 879-1021 Voice
Anthony.brown@ dgs.ca.gov
707 Third Street, 3rd Floor
Design Services Section
Facility Management Division State of California
West Sacramento, California 95605
Department of General Services
GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 W www.ghd.com
SMITH RIVER
BORDER
STATION - HVAC
SPLIT SYSTEM
17200 US 101
SMITH RIVER, CALIFORNIA 95567
DGS PROJ #13984
SHEET GENERAL NOTES
1. TYPICAL POWER CIRCUITS CONSIST OF (2) #12 AWG, #12 GND IN 3/4" RGS
CONDUIT.
2. COORDINATE EXACT LOCATION OF ELECTRICAL EQUIPMENT WITH
ARCHITECT AND MECHANICAL EQUIPMENT.
SHEET KEYNOTES
1. DISCONNECT AND REMOVE (E) BRANCH CIRCUIT PANEL, PRESERVE CIRCUITS AND
PREPARE TO RECONNECT TO (N) PANEL. PROVIDE BRANCH CIRCUIT PANEL WITH
FEATURES AS SHOWN ON PANEL SCHEDULE. PROVIDE CIRCUIT BREAKERS FOR (E)
LOADS TO MATCH ORIGINAL CIRCUIT BREAKER RATINGS. RECONNECT (E) LOADS TO (N)
PANEL.
2. PROVIDE DISCONNECT SWITCH AND POWER CIRCUIT TO INDICATED EQUIPMENT.
PANEL A 1
FC
FC
FC
FC
HP
SF
(E) FURNACE
HP
(E) GENERATOR
(PROTECT IN PLACE)
(E) LPG STORAGE TANKS
(PROTECT IN PLACE)
(E) METER MAIN SERVICE
ENTRANCE PANEL "MP"
(PROTECT IN PLACE)
1 ELECTRICAL FLOOR PLAN
SCALE: 1/4" = 1'-0"
2 MEZZANINE ELECTRICAL PLAN
SCALE: 1/4" = 1'-0"
PANEL-A, CKT-22
PANEL "MP"
PANEL "MP"
TO HP-1
TO HP-2
(E) RECEPTACLE TO REMAIN
(E) RECEPTACLE TO REMAIN
(E) RECEPTACLE TO REMAIN
(E) RECEPTACLE TO REMAIN
(E) RECEPTACLE TO REMAIN
(E) RECEPTACLE TO REMAIN
EAO
TO HP-1
TO HP-1
E25957RE
G I
ST
ER
ED PRO F E S S I ON A L ENGI NEER
S TA T E O F C A L I F O R N I A
E L E C T R I C A L
RE
B E
C C A O . K E A T I NG
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
01-122926
E601
ELECTRICAL SINGLE
LINE DIAGRAM AND
SCHEDULES
17200 US 101
SMITH RIVER, CALIFORNIA 95567
DGS PROJ #13984
AS NOTED
02-02-2026
13984
CONSULTANT:
117 PARK PLACE
POINT RICHMOND
CALIFORNIA 94801
(510) 236-7435 www.intres.com
IR PROJECT #2017-050-06
STAMP:
ABCDEFGHIJKLMNOPQRSTU
ABCDEFGHIJKLMNOPQRSTU
Issue No.
Date Description
Project
Supervisor Designed Drawn Checked
File Date Vault File Number
Sheet Title
DGS Project # Work Order
Reference North Sheet Scale
Sheet Number
X
Project Manager: Anthony Brown 916 879-1021 Voice
Anthony.brown@ dgs.ca.gov
707 Third Street, 3rd Floor
Design Services Section
Facility Management Division State of California
West Sacramento, California 95605
Department of General Services
GHD Inc.
2235 Mercury Way Suite 150 Santa Rosa California 95407 USA T 1 707 523 1010 W www.ghd.com
SMITH RIVER
BORDER
STATION - HVAC
SPLIT SYSTEM
17200 US 101
SMITH RIVER, CALIFORNIA 95567
DGS PROJ #13984
200A 2P
M
(E) METER MAIN PANEL "MP"
240V 1PH
200A
METER NUMBER: 96 471 553
N G
125A
2P PANEL
A
25A 2P
20A 2P
HP-1
HP-2
SHEET KEYNOTES
1.
SHEET KEYNOTES
1. PROVIDE CIRCUIT BREAKER WITH RATINGS AS INDICATED IN (E) PANEL.
2. REPLACE (E) BRANCH CIRCUIT PANEL WITH (N) PANEL. PROVIDE BRANCH CIRCUIT
PANEL WITH FEATURES AS SHOWN ON PANEL SCHEDULE.
GENERAL NOTES
1. REFER TO SITE PLAN FOR EQUIPMENT LOCATIONS.
1 SINGLE LINE DIAGRAM
SCALE: NONE
2 ELECTRICAL SCHEDULES
SCALE: NONE
70A 2P
GENERATOR
G
(E) ATS
(E) GENERATOR 16KW
TO UTILITY
(3) #10 AWG, #10 GND IN 3/4" C
VD: 2.84%
(3) #10 AWG, #10 GND IN 3/4" C
VD: 0.94%
FEEDERS TO REMAIN
3 MECHANICAL CONNECTION SCHEDULE
SCALE: NONE
E25957RE
G I
S T
ER
ED PRO F E S S I ON A L E NGI NEER
S TA T E O F C A L I F O R N I A
E L E C T R I C A L
RE
B E
C C A O . K E A T I NG
RK RK EAOEAO
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
01-122926
File details come from the government source that posted it. Updated .