This document is Attachment 2 of a federal solicitation containing Salient Characteristics for Mobile Dehumidification Carts designed for multiple USCG airframes under contract number 70Z03826QE0000052.

The dehumidification units must be mobile carts capable of producing 300 cubic feet per minute (CFM) of processed air to reduce relative humidity within aircraft to 30-40% RH within one hour and maintain this level for a minimum of eight hours daily. Each unit shall automatically regulate supplied air regardless of ambient conditions and feature electric reactivation capability with a closed-loop system. The maximum noise level is 85 decibels at zero feet during operation. The cart dimensions must not exceed 72 inches (H) x 33 inches (W) x 72 inches (L) to pass through industrial personnel doors, and shall include parking brakes, solid nonmetallic tires, anti-vibration barriers, and secure wiring with neoprene-gasketed access panels. Power requirements are dual standards: 208-240VAC/3ph/60Hz or 440-480VAC/3ph/60Hz at 60 amps maximum, with standard 50-foot SOOW power cables (expandable to 100 feet). All electrical components must be mounted above 18 inches from floor level for NFPA Class I, Division 2 compliance and carry UL or ETL certification. Standard 8-inch process air inlet and outlet connections are required with optional 4-inch reducers available. The cart shall be painted white polyurethane per MIL-PRF-85285 with tropical rust proofing suitable for coastal/high-humidity environments, include a 100-foot grounding reel, identification markings, and an identification plate containing manufacturer information, model number, serial number, and contract number. Units must dock and undock from aircraft within five minutes and withstand commercial transportation without damage.

View the file

Other files for this federal contract opportunity

Other files attached to Dehumidification Carts for Multiple USCG Airframes, newest first.
File Type Posted
Amend 2 --Attachment 1 - Schedule of Supplies.xlsx XLSX spreadsheet
Amend 2 -- Attachment 3 - 26QE0000052 - 8-20-26.pdf PDF
Amend 1 --Attachment 1 - Schedule of Supplies.xlsx XLSX spreadsheet
Amend 1 -- Attachment 3 - Terms and Conditions 26QE0000052.docx DOCX document
Attachment 1 - Schedule of Supplies.xlsx XLSX spreadsheet
Attachment 3 26QE52 Terms and Conditions.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 2

Salient Characteristics

Dehumidification Carts for Multiple USCG Airframes

70Z03826QE0000052

▪ Mobile Dehumidification (DH) unit.

o 300 cubic feet per minute (CFM) of processed DH air.

o Reduces relative humidity (RH) within the aircraft to a target zone (30-40% RH) within one (1) hour.

o Once docked to an aircraft, unit automatically regulates (30-40%) supplied RH air to the aircraft regardless of ambient temperature and humidity.

o Achieve 30-40% RH for a minimum of eight (8) hours per day.

▪ Test ports for process airflow.

o Electric reactivation of dehumidifier.

o Closed loop system.

o Doors and access panels gasketed with neoprene.

▪ Maximum of 85 decibels (db) @ 0 feet while operating.

▪ Unit mounted on mobile roll-around pushcart.

o Maximum dimensions: 72 inches (H) x 33 inches (W) x 72 inches (L)

▪ Dimensions of cart and mounted components are designed to enter through industrial personnel doors of the hangars.

o Parking brake(s).

o Enclosure for duct and adapter storage while not in use.

o Power Cord hangar for storage when not in use or for movement.

o Pushcart handle or handrail for manual movement.

o Solid, Nonmetallic and non-pneumatic tires.

o Anti vibration barrier between removable basket and mounts to avoid chaffing.

o Secure and route wiring to avoid chaffing, abrasion and heat sources direct and indirectly.

▪ DH unit and pushcart constructed and/or rated for an indoor environment / use.

▪ All electrical components and connections mounted above 18” from floor level for use in NFPA Class I, Div. 2 environments.

o National Fire Protection Association (NFPA), NFPA 70 National Electrical Code; Chapter 5. Special Occupancies;

Article 513; Aircraft Hangars and NFPA 505, Fire Safety Standard for Powered Industrial Trucks; Including Type

Designations, Areas of Use, Conversions, Maintenance, and Operations, Chapter 4. Hazardous (Classified)

Locations.).

o UL or ETL listed and approved electrical equipment.

▪ Power requirement: two (2) standards;

o 1.) 208-240vac/3ph/60hz and 2.) 440-480vac/3ph/60hz, 60 amps maximum.

o Power cord: Standard: 50 feet (SOOW) power cable (bare end; no plug).

▪ S = Service

▪ O = Oil-Resistant Conductors

▪ O = Oil-Resistant Jacket

▪ W = Water-Resistant o Option to increase to 100 feet (SOOW) power cable (as identified by specific location needs).

o CG will provide the power cord plug for each unit once delivered to destination.

▪ Standard 8” process air inlet and outlet (for most CG aircraft applications).

▪ Optional reducer from standard 8” inlet / outlet to 4” hoses (for use with existing hose and aircraft adapter setup (4” for small helicopter)).

▪ Aircraft hoses and aircraft interface adapters (AIA) will be procured and supplied by CG unit at final delivery destination.

Attachment 2

Salient Characteristics

Dehumidification Carts for Multiple USCG Airframes

70Z03826QE0000052

▪ Dock and undock to the aircraft in five (5) or less minutes (this requirement is already achieved through the pre-existing and established aircraft interface adapters (AIA) used with each CG aircraft).

▪ Cart Painted white polyurethane coating 17925, mil-prf-85285.

o Controls and components do not require additional coatings. Standard commercial practices and coatings are acceptable.

▪ Coatings.

o The cart shall be primed and painted using standard commercial practices using commercially available coatings and shall conform to coating manufacturer’s guidelines.

o The finish shall show no evidence of uneven application, curtains, runs, snags, orange peel, lack of adhesion, or other defects.

▪ Tropical rust proofing.

o This should be considered a premium rust proofing package usually consisting of an additional coating. The cart shall be treated with a corrosion preventative compound. These units will used in tropical/coastal environments and experience high humidity and salt spray. Areas such as those listed below, usually exhibit high levels of corrosion and should be considered for additional coatings:

▪ Exterior

▪ Seams

▪ Welds

▪ Hidden recessed areas

▪ Locations where dissimilar metals come in contact

▪ Grounding reel with 100 feet of 3/32 inch cable with mounted alligator or hand grip clip.

▪ Transportability.

o Units capable of being transported by commercial trailers, trains, and marine vessels, and must be capable of withstanding the impact forces encountered in shipment, without damage, or permanent deformation.

▪ Identification markings.

o Instruction, warning, and caution plates describing any special or important procedure to be followed in assembling, operating, loading and servicing. Securely attached by screws, bolts, or rivets in conspicuous locations.

▪ Identification plate. An identification plate made of corrosion resistant material permanently installed shall contain the following information:

o NOMENCLATURE:

o MANUFACTURER’S PART NUMBER:

o MANUFACTURERS MODEL NUMBER:

o MANUFACTURER’S SERIAL NUMBER:

o MANUFACTURER’S NAME:

o MANUFACTURER’S CAGE CODE:

o MANUFACTURERS’ ADDRESS:

o MANUFACTURER’S SERVICE PHONE NUMBER:

o DATE OF MANUFACTURE:

o CONTRACT NUMBER: