This is an architectural drawing package for a fire suppression water tank repair project at Richmond National Battlefield Park located at 8761 Battlefield Park Road, Richmond, Virginia 23231. The project, issued for review on 11/20/2025, is managed by the United States Department of the Interior and focuses on repairs to the fire suppression water tank at the Fort Harrison Unit of Richmond National Battlefield Park.
The drawings specify comprehensive repair and maintenance requirements for a 24-inch diameter shell tank with a normal full level elevation of 110.97 feet. Key work items include providing inspection and identifying any deficiencies before work begins, ensuring all work adheres to NFPA Standard 22 (2023) for water tanks for private fire protection, performing required tests to verify water tank functionality and NFPA 22 compliance, cleaning the tank interior and installing a passive cathodic protection system, and clearing dirt and debris from the foundation per NFPA 22:2023 Section 12.2.1.2. Additional requirements include installing lightning protection per NFPA 780 Section 4.4, and cleaning and lubricating the liquid level indicator per NFPA 22:2023 Section 14.1.8. The tank features 24-inch diameter shell manholes, a 24-inch by 30-inch access hatch with screened roof vent, handrail with ladder and locking security cover, fill and relief pipes, 6-inch freeboard, an 18-foot 6-inch minimum oiled sand cushion foundation, and safety signage for confined space entry and fall protection requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment_3_-_Wage_Determination__VA20260007.pdf | ||
| Sol_140P4226R0031.pdf | ||
| Attachment_5_-_Certifications_From_Section_K.docx | DOCX document | |
| Attachment_6_-_Limitations_on_Subcontracting_compliance_worksheet.xlsx | XLSX spreadsheet | |
| Attachment_4_-__Technical_Capability_Submittals.docx | DOCX document | |
| Attachment_1_-__RICH_FS_Tank_SPECS.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RICHMOND NATIONAL BATTLEFIELD PARK
REPAIR TO THE FIRE SUPPRESSION WATER TANK
FIRE SUPPRESSION
SHEET
COVER SHEET & DRAWING LIST
TITLE OF SHEET
FP-01 FLOOR PLAN2
SUB SHEET
CS
LOCATION ADDRESS CITY, STATE, ZIP CODE HISTORIC MARKER COPY PLUS CODE
FT HARRISON V.C. 8761 BATTLEFIELD PARK RD RICHMOND, VA 23231 37° 25' 41.5" N, 77° 22' 23.4" W CJHH+73 Richmond, Virginia
PROJECT LOCATION:
18'-6"±
2" MIN. OILED
SAND CUSHION
24"x30" ACCESS HATCH
SCREENED ROOF VENT
HANDRAIL
LADDER WITH LOCKING
SECURITY COVER
6" MIN.
24" DIAMETER
SHELL MANHOLE
SHELL MANHOLE
24" DIAMETER
FILL AND RELIEF PIPES
6"Ø OVERFLOW PIPE
24"x30" ACCESS HATCH
AROUND ACCESS HATCH
HANDRAIL
TANK PLAN
SCALE: 1/4" = 1'-0"
TANK DIAMETER + 18'-0"
24" DIAMETER
SHELL MANHOLES
2"Ø DRAIN PIPE
SPLASH BLOCK
36"
10"
REBAR
6" FREEBOARD
SLAB ELEV 92.80
ELEV = 110.97
NORMAL FULL LEVEL
WATER LEVEL INDICATOR
CONTROL PANEL FOR HEATER
CLEAR DIRT AND
DEBRIS 6" FROM TOP
OF TANK FOUNDATION.
SEAL FOUNDATION
WITH CONCRETE
SEALANT.
PROVIDE LIGHTNING
PROTECTION
PROVIDE VALVE AND SCREEN TO
DRAIN PIPE. PROVIDE SPLASH
PAD TO DIRECT WATER AWAY
FROM THE TANK.
POST SIGN STATING
"CONFINED SPACE ENTRY"
AT MANHOLES (TYP).
CLEAN AND LUBRICATE
MOVING PARTS OF THE
LIQUID LEVEL INDICATOR.
INSTALL CABLE LADDER
SAFETY CLIMB DEVICE AND
A CABLE TYPE LADDER
SAFETY CLIMB DEVICE
POST "FALL PROTECTION
REQUIRE" SIGN
POST "CONFINED SPACE
ENTRY" SIGN
INSTALL A PASSIVE
CATHODIC PROTECTION
SYSTEM IN INTERIOR OF
TANK
CLEAN INTERIOR OF TANK
1 TANK ELEVATION
SCALE: 1/4" = 1'-0"
FORT HARRISON UNIT
RICHMOND NATIONAL BATTLEFIELD PARK
FIRE SUPPRESSION RESERVOIR
FP-01
GENERAL NOTES
1. PROVIDE INSPECTION OF THE TANK AND IDENTIFY ANY DEFICIENCIES TO THE NPS BEFORE BEGINNING WORK.
2. ENSURE ALL WORK ADHERES TO NFPA STANDARD 22, 2023: STANDARD FOR WATER TANKS FOR PRIVATE FIRE PROTECTION.
3. PERFORM REQUIRED TESTS TO ENSURE THE WATER TANK IS FUNCTIONAL AND COMPLIANT WITH NFPA 22.
4. CLEAN INTERIOR OF TANK AND INSTALL A PASSIVE CATHODIC PROTECTION SYSTEM IN THE TANK INTERIOR.
5. CLEAN DIRT AND DEBRIS FROM FOUNDATION PER NFPA-22 2023, SECTION 12.2.1.2
6. PROVIDE LIGHTNING PROTECTION PER NFPA 780, SECTION 4.4.
7. CLEAN AND LUBRICATE LIQUID LEVEL INDICATOR IN COMPLIANCE WITH NFPA 22 2023, SECTION 14.1.8.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
AutoCAD SHX Text 256092
AutoCAD SHX Text
AutoCAD SHX Text
ELS
AutoCAD SHX Text
ELS
AutoCAD SHX Text
HACE
AutoCAD SHX Text
NOV 2025
AutoCAD SHX Text
| 01 COVER SHEET RICH (2) |
| FP-01 |
| FP-00 |
File details come from the government source that posted it. Updated .