Attachment 2 - Repair Waterfront Phase II Drawings.pdf

PDF 23 MB Posted

Attached to
Repair Waterfront – Phase 2 at USCG Station Portsmouth Harbor (New Castle, New Hampshire)
Solicitation number
70Z0G126BSNNE8241
Issued by

About this file

This document is a set of civil engineering design drawings and specifications for the U.S. Coast Guard Station Portsmouth Harbor in New Castle, New Hampshire, addressing waterfront repair and restoration work identified as Phase 2.

The project encompasses four primary repair areas: (1) bulkheads and quay walls requiring chinking, repointing, void repair, and concrete closure walls at the north and south locations; (2) rip-rap revetment restoration involving stone placement, bedding layers, and geotextile installation across approximately 380 cubic yards; (3) wave screen/floating dock repairs including pile recoating with coal-tar epoxy, cleat replacement, and galvanic anode installation; and (4) a new timber floating dock replacement with expanded polystyrene float modules designed for 40 PSF uniform live load and 8-inch minimum freeboard. The base bid scope totals approximately 14 individual line items with quantities ranging from 8 each (pile coatings and anodes) to 700 cubic yards (interim stone berm). Two bid options are available: Option 1 provides 150 cubic yards of additional revetment extension at the west end of the quay wall (RPUID 816511), and Option 2 offers installation of eight HDPE pile sleeves for protection (RPUID 50109). Work restrictions limit loading within 15 feet of the existing north quay wall to 100 PSF uniform live load, with vehicles and cranes prohibited. The project specifications reference 2018 International Building Code, AISC Steel Construction Manual 15th Edition, 2024 American Wood Council NDS, Unified Facilities Criteria 4-152-01 and 4-152-07, and OSHA 29 CFR 1910. Design by Lloyd-Collins JV (Bellaire, Texas) and USCG Civil Engineering Unit Providence; drawings issued for bidding November 2025.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RE

PA

IR

W

AT

ER

FR

ON

T

- P

HA

SE

CG

S

TA

P

OR

TS

M

OU

TH

H

AR

BO

R

NE

W

C

AS

TL

E

NH

GE

NE

RA

L

CO

VE

R

SH

EE

T

BULKHEADS, RIP-RAP

WAVE SCREEN, AND

FLOATING DOCK

G-001

P1

P1

2G

1.

dw g

US

CG

C

IV

IL

E

NG

IN

EE

RI

NG

U

NI

T

PR

OV

ID

EN

CE

KI

LV

ER

T

ST

, S

UI

TE

W

AR

W

IC

K, R I 0

DA

VI

D J.

AR

PI

N, P

.E

Z.

JE

NK

IN

S J.

DE

L

TU

FO

M .S

CH

M

ID

D.

O 'C

ON

NO

R

MICHAEL P. CAROSOTTO, P.E.

MICHAEL P. CAROSOTTO, P.E.

DAVID C. DILL

LL

OY

D

CO

LL

IN

S

JV

BE

LL

AI

RE

, T

EX

AS

(8

) 4

-4

LC

JV

-1

IS

SU

ED

F

OR

B

ID

DI

NG

NO

V

U.S. COAST GUARD

CIVIL ENGINEERING

DE

SI

GN

ED

B Y:

DE

SC

RI

PT

IO

N

M

AR

K

ED

IT

ED

B Y:

DA

TE

CH

EC

KE

D

BY

DR

AW

N

BY

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

TECHNICAL DIRECTOR

BRANCH CHIEF

APPROVING OFFICIAL DATE

SH

EE

T

OF

US

CG

P

RO

JE

CT

N

UM

BE

R

US

CG

F

IL

EN

AM

E

A/ E

CO

M

PA

NY

CO

NS

UL

TI

NG

A

/E

US

CG

P

RO

JE

CT

M

AN

AG

ER

A/

E

PR

OJ

EC

T

NO

SHEET ID

M

EA

SU

RE

M

EN

T

BA

R:

1"

HA

LF

S

IZ

E

1/ 2"

US

CG

D

RA

W

IN

G

SE

RI

ES

N

UM

BE

R

U.S. COAST GUARD

CIVIL ENGINEERING UNIT

PROVIDENCE

VICINITY MAP

SCALE: NTS

LOCATION MAP

SCALE: NTS

CG STA PORTSMOUTH HARBOR

NEW CASTLE, ROCKINGHAM COUNTY, NEW HAMPSHIRE

16654142 REPAIR WATERFRONT - PHASE 2

BULKHEADS, RIP-RAP, WAVE SCREEN,

AND FLOATING DOCK - BOATHOUSE

EXCEL

LE

N C E

I N E N G I N E E R I N G

U . S . C O A S T G U

A R

D

CIVIL

ENGINEERING UNIT

PROVIDENCE

SUMMARY OF WORK (BASE BID)

RPUID ITEM QUANTITY (APPROX.)

816511 CHINK AND REPOINT NORTH QUAY WALL 200 LF

816511 PROVIDE CLOSURE WALL AT EAST END OF NORTH QUAY WALL 20 LF

816511, 9383 REPAIR CONCRETE DUMPSTER SLAB AND PAVEMENT 620 SF

816511, 810801 REPLACE NORTH QUAY WALL FENCE 220 LF

816511 REPAIR VOIDS IN SOUTH QUAY WALL 10 CY

816511 REPAIR SINKHOLE BEHIND SOUTH QUAY WALL 60 CY

816511 REPAIR EAST END OF SOUTH QUAY WALL WITH INTERIM STONE BERM 700 CY

857029 RESTORE RIP-RAP REVETMENT 380 CY

857029, 9383 REPAIR PAVING IN WEST PARKING LOT 560 SF

857029, 810801 REPLACE REVETMENT FENCE 180 LF

50109 RECOAT WAVE SCREEN PILES 8 EA

50109 REPLACE WAVE SCREEN CLEAT 1 EA

50109 INSTALL ANODES ON WAVE SCREEN PILES 8 EA

848538 INSTALL TIMBER FLOAT 550 SF

THIS TABLE IS NOT AN EXHAUSTIVE LIST OF ALL SCOPE ITEMS, ESPECIALLY INCIDENTAL WORK, AND IS INTENDED TO BE A GENERAL SUMMARY ONLY. REFER TO THE DRAWINGS CONTAINED HEREIN AND THE PROJECT SPECIFICATIONS

FOR ADDITIONAL INFORMATION AND DETAILS ON THE FULL PROJECT SCOPE OF WORK.

SUMMARY OF WORK (BID OPTIONS)

RPUID ITEM QUANTITY

(APPROX.)

816511 BID OPTION 1: PROVIDE REVETMENT EXTENSION AT

WEST END OF QUAY WALL 150 CY

50109 BID OPTION 2: INSTALL HDPE PILE SLEEVES 8 EA

THIS TABLE IS NOT AN EXHAUSTIVE LIST OF ALL SCOPE ITEMS, ESPECIALLY INCIDENTAL WORK, AND IS INTENDED TO BE A GENERAL SUMMARY ONLY. REFER TO THE DRAWINGS CONTAINED

HEREIN AND THE PROJECT SPECIFICATIONS FOR ADDITIONAL INFORMATION AND DETAILS ON

THE FULL PROJECT SCOPE OF WORK.

DRAWING INDEX

SHEET ID SHEET # SHEET TITLE

G-001 1 COVER SHEET

G-002 2 ABBREVIATIONS

G-003 3 GENERAL NOTES

G-101 4 WORK PLAN

G-901 5 EXISTING CONDITIONS PHOTOS

C-001 6 EXISTING CONDITIONS NOTES

C-101 7 EXISTING SITE PLAN

C-102 8 QUAY WALL REPAIR PLAN

C-301 9 NORTH RIP-RAP REPAIR SECTIONS

C-302 10 QUAY WALL REPAIR SECTIONS

C-501 11 SOUTH QUAY WALL REPAIR DETAILS

C-502 12 MISCELLANEOUS SITE REPAIR DETAILS - 1

C-503 13 MISCELLANEOUS SITE REPAIR DETAILS - 2

S-101 14 WAVE SCREEN REPAIR PLAN

S-102 15 FLOATING DOCK REPLACEMENT

S-501 16 WAVE SCREEN DETAILS

PROJECT INFORMATION

RE

PA

IR

W

AT

ER

FR

ON

T

- P

HA

SE

CG

S

TA

P

OR

TS

M

OU

TH

H

AR

BO

R

NE

W

C

AS

TL

E

NH

GE

NE

RA

L

AB

BR

EV

IA

TI

ON

S

BULKHEADS, RIP-RAP,

WAVE SCREEN, AND

FLOATING DOCK

G-002

P1

P1

2G

2.

dw g

US

CG

C

IV

IL

E

NG

IN

EE

RI

NG

U

NI

T

PR

OV

ID

EN

CE

KI

LV

ER

T

ST

, S

UI

TE

W

AR

W

IC

K, R I 0

DA

VI

D J.

AR

PI

N, P

.E

Z.

JE

NK

IN

S J.

DE

L

TU

FO

M .S

CH

M

ID

D.

O 'C

ON

NO

R

LL

OY

D-

CO

LL

IN

S

JV

BE

LL

AI

RE

, T

EX

AS

(8

) 4

-4

LC

JV

-1

IS

SU

ED

F

OR

B

ID

DI

NG

NO

V

US COAST GUARD

CIVIL ENGINEERING

DE

SI

GN

ED

B Y:

DE

SC

RI

PT

IO

N

M

AR

K

ED

IT

ED

B Y:

DA

TE

CH

EC

KE

D

BY

DR

AW

N

BY

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

US

CG

D

RA

W

IN

G

SE

RI

ES

N

UM

BE

R

SH

EE

T

OF

US

CG

P

RO

JE

CT

N

UM

BE

R

US

CG

F

IL

EN

AM

E

A/ E

CO

M

PA

NY

CO

NS

UL

TI

NG

A

/E

US

CG

P

RO

JE

CT

M

AN

AG

ER

A/

E

PR

OJ

EC

T

NO

SHEET ID

M

EA

SU

RE

M

EN

T

BA

R:

1"

HA

LF

S

IZ

E

1/ 2"

TIDAL DATA

MLLW NAVD88

USCG ANNOTATION SYMBOLS LEGEND

GRID IDENTIFIER

W.L. AT '##

FLOW

KEYNOTE SYMBOL

SPOT ELEVATION INDICATOR FLOW ARROW

WATER LEVEL IDENTIFIER

X/#

COMMON ABBREVIATIONS

ABBR TERM

ABAND. ABANDONED

& AND

AASHTO AMERICAN ASSOCIATION

OF STATE HIGHWAY AND

TRANSPORTATION

OFFICIALS

L ANGLE

℄ CENTER LINE

DIA. DIAMETER

# NUMBER

⅊ PLATE

BLDG BUILDING

CMP CORRUGATED METAL

PIPE

C.P. CONTROL POINT

CONC. CONCRETE

COND. CONDUIT

CSTO CONFIGURATION

STANDARD TECHNICAL

ORDER

DIP DUCTILE IRON PIPE

DWG DRAWING

EA EACH

EL ELEVATION

ELEC ELECTRICAL

EOI END OF GEOPHYSICAL

INVESTIGATION

EP EDGE OF PAVEMENT

ES ELECTRIC SWITCH

EXST EXISTING

FT FEET

GOVT GOVERNMENT

GRAN. GRANITE

HDG HOT DIP GALVANIZED

HDPE HIGH DENSITY

POLYETHYLENE

HS SIGNIFICANT WAVE

HEIGHT

LB POUND

LF LINEAR FEET

MAX MAXIMUM

MIN MINIMUM

MISC MISCELLANEOUS

MLW MEAN LOW WATER

MLLW MEAN LOWER LOW

WATER

MHW MEAN HIGH WATER

MHHW MEAN HIGHER HIGH

WATER

NAVD NORTH AMERICAN

VERTICAL DATUM

NHDOT NEW HAMPSHIRE

DEPARTMENT OF

TRANSPORTATION

NFPA NATIONAL FIRE

PROTECTION AGENCY

NIC NOT IN CONTRACT

NTS NOT TO SCALE

NOAA NATIONAL OCEANIC AND

ATMOSPHERIC

ADMINISTRATION

OC ON CENTER

PSF POUNDS PER SQ. FT.

PT PRESSURE TREATED

PVC POLY-VINYL CHLORIDE

QA QUALITY ASSURANCE

QC QUALITY CONTROL

RCP REINFORCED

CONCRETE PIPE

REV REVISION

SBL SINGLE BLUE LINE

SF SQUARE FEET

SHT SHEET

SQ SQUARE

SS STAINLESS STEEL

SWL SINGLE WHITE LINE

SYL SINGLE YELLOW LINE

TH THRESHOLD ELEVATION

TMB TIMBER EDGE/CURB

TYP TYPICAL

UNO UNLESS NOTED

OTHERWISE;

UTIL UTILITY

W WITH

W/O WITHOUT

WWTD WASTE WATER

TREATMENT

DEPARTMENT

XS EXTRA STRONG

(X) INVERT I.D.

CONNECTION UNKNOWN

USCG DETACHMENTS

ABBR TERM

CEU CIVIL ENGINEERING UNIT

CEUP CEU PROVIDENCE

CG COAST GUARD

STA U.S. COAST GUARD

STATION

USCG UNITED STATES COAST

GUARD

USCG PERSONNEL

ABBR TERM

CO; COMMANDING OFFICER

OIC OFFICER IN CHARGE

KO CONTRACTING OFFICER

COR CONTRACTING OFFICER

DOR DESIGNER OF RECORD

DPM DESIGN PROJECT

MANAGER

APPLICABLE CODES

2018 INTERNATIONAL BUILDING CODE

AMERICAN INSTITUTE OF STEEL CONSTRUCTION: STEEL CONSTRUCTION MANUAL 15TH EDITION

(AISC)

2024 AMERICAN WOOD COUNCIL NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION

(NDS)

AMERICAN INSTITUTE OF TIMBER CONSTRUCTION, TIMBER CONSTRUCTION MANUAL, 6TH EDITION

(TCM)

UNIFIED FACILITIES CRITERIA (UFC)

4-152-01 PIERS AND WHARVES (2024)

4-152-07 SMALL CRAFT BERTHING FACILITIES (2012)

3-301-01 STRUCTURAL ENGINEERING (2023)

29 CFR 1910 OCCUPATIONAL SAFETY AND HEALTH (OSHA)

FACILITY/ASSET NAME:

FACILITY/ASSET # (RPUID):

CONSTRUCTION TYPE:

FACILITY GENERAL INFORMATION

BULKHEADS - NORTH QUAYWALL

816511

DRY STACKED GRANITE BLOCKS

FACILITY/ASSET NAME:

FACILITY/ASSET # (RPUID):

BULKHEADS - SOUTH QUAYWALL

816511

FACILITY/ASSET NAME:

FACILITY/ASSET # (RPUID):

CONSTRUCTION TYPE:

RIP-RAP

857029

ANGULAR STONE

STRUCTURE LENGTH:

FACILITY/ASSET NAME:

FACILITY/ASSET # (RPUID):

CONSTRUCTION TYPE:

WAVE SCREEN

50109

CONCRETE FLOATING DOCK

EXPOSURE CATEGORY: D

WAVE HEIGHT: 3 FT.

UNIFORM LIVE LOAD: 40 PSF

STRUCTURE LENGTH: 180 FT

STRUCTURE HEIGHT: 15-18 FT

CONSTRUCTION TYPE: DRY STACKED GRANITE BLOCKS

STRUCTURE LENGTH: 340 FT

STRUCTURE HEIGHT: 15 FT

280 FT

100 YEAR FLOOD RECURRENCE FLOOD WAVE ZONE (VE ZONE)

100 YEAR RECURRENCE FLOOD ZONE (AE ZONE)

HIGHEST OBSERVED WATER LEVEL (01/02/2010)

MEAN HIGHER HIGH WATER (MHHW)

MEAN HIGH WATER (MHW)

NORTH AMERICAN VERTICAL DATUM (NAVD) 1988

NATIONAL GEODETIC VERTICAL DATUM (NGVD) 1929

MEAN LOW WATER (MLW)

MEAN LOWER LOW WATER (MLLW)

LOWEST OBSERVED WATER LEVEL (02/02/2018)

REFERENCE:

NOAA TIDAL STATION #8423998, FORT POINT, NEWCASTLE, NH

FEMA FLOOD MAP 33015C0279F

19.95' 15.00' 16.95' 11.00' 12.78' 7.82' 9.85' 4.89' 8.95' 4.00' 4.95' 0.00' 4.19' -0.77' 0.33' -4.63' 0.00' -4.96' -2.71' -7.66'

USCG DRAWING VIEW SYMBOLS LEGEND

NORTH

PLAN

TRUE N

X# TITLE

SCALE: X=1'-0"

XX###

X#

X#

X#

X#

X#

XX###

X#

XX###

0 1" 2"1/2"

XX###

X#

X#

XX###

X#

XX###

REVISION #

DRAWING VIEW TITLES REVISION CLOUDS AND DELTAS

GRAPHIC SCALES NORTH ARROWS

DRAWING VIEW INDICATOR EXTERIOR ELEVATION INDICATOR

ENLARGED DETAIL INDICATORS INTERIOR ELEVATION INDICATOR

SECTIONAL VIEW INDICATOR

REV CLOUD

PLAN NORTH

TRUE NORTH

ELEVATION

NUMBER/ID

ELEVATION

DRAWING

SHEET

DRAWING

SHEET

NUMBER/ID

DRAWING

VIEW

NUMBER/ID

DRAWING

VIEW

NUMBER/ID

DRAWING

VIEW

TITLE

DRAWING

SCALE

CONCRETE (PLAN AND/OR SECTION)

DEMOLITION AND REMOVALS (PLAN AND/OR SECTION)

BEDROCK/LEDGE (SECTION)

SOIL/FILL (PLAN AND/OR SECTION)

GROUT (SECTION)

STONE RIPRAP (PLAN AND/OR SECTION)

(UNLESS NOTED OTHERWISE)

MATERIALS IN PLAN & SECTIONS

LOAD RESTRICTED AREA (PLAN)

GRANULAR BACKFILL OR GRAVEL SUBBASE (SECTION)

DE

SI

GN

ED

B Y:

DE

SC

RI

PT

IO

N

M

AR

K

ED

IT

ED

B Y:

DA

TE

CH

EC

KE

D

BY

DR

AW

N

BY

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

US

CG

D

RA

W

IN

G

NU

M

BE

R

SH

EE

T

OF

US

CG

P

RO

JE

CT

N

UM

BE

R

US

CG

F

IL

EN

AM

E

A/ E

CO

M

PA

NY

CO

NS

UL

TI

NG

A

/E

US

CG

P

RO

JE

CT

M

AN

AG

ER

A/

E

PR

OJ

EC

T

NO

SHEET ID

M

EA

SU

RE

M

EN

T

BA

R:

1"

HA

LF

S

IZ

E

1/ 2"

GENERAL WATERFRONT REPAIR NOTES:

RE

PA

IR

W

AT

ER

FR

ON

T

- P

HA

SE

CG

S

TA

P

OR

TS

M

OU

TH

H

AR

BO

R

NE

W

C

AS

TL

E

NH

GE

NE

RA

L

GE

NE

RA

L

NO

TE

S

BULKHEADS, RIP-RAP

WAVE SCREEN, AND

FLOATING DOCK

G-003

P1

P1

2G

3.

dw g

US

CG

C

IV

IL

E

NG

IN

EE

RI

NG

U

NI

T

PR

OV

ID

EN

CE

KI

LV

ER

T

ST

, S

UI

TE

W

AR

W

IC

K, R I 0

DA

VI

D J.

AR

PI

N, P

.E

Z.

JE

NK

IN

S J.

DE

L

TU

FO

M .S

CH

M

ID

D.

O 'C

ON

NO

R

LL

OY

D-

CO

LL

IN

S

JV

BE

LL

AI

RE

, T

EX

AS

(8

) 4

-4

LC

JV

-1

IS

SU

ED

F

OR

B

ID

DI

NG

NO

V

US COAST GUARD

CIVIL ENGINEERING

1. THESE DRAWINGS FORM A PART OF THE SPECIFICATIONS. REFER TO THE TECHNICAL SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

2. ALL DIMENSIONS, ELEVATIONS AND CONDITIONS SHALL BE VERIFIED IN THE FIELD. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER BEFORE ORDERING MATERIALS AND PROCEEDING WITH THE AFFECTED PART OF THE WORK.

3. THE CONTRACTOR IS ADVISED THAT THE DRAWINGS AND SPECIFICATIONS FORM A PART OF THE CONTRACT DOCUMENTS. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL KEEP A COPY OF THE DRAWINGS AND

SPECIFICATIONS ONSITE AT ALL TIMES DURING THE PROJECT.

4. ELEVATIONS ARE IN FEET BASED ON NORTH AMERICAN VERTICAL DATUM OF 1988 (NAVD88), UNLESS NOTED OTHERWISE.

5. EXISTING CONDITIONS ARE INTENDED TO PROVIDE GENERAL OVERVIEW OF STRUCTURES BUT DO NOT INCLUDE ALL APPURTENANCES AND CONDITIONS. ALL DIMENSIONS AND DETAILS OF THE EXISTING CONSTRUCTION SHALL BE CHECKED AND VERIFIED IN THE FIELD BY THE CONTRACTOR PRIOR TO COMMENCING CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER BEFORE ORDERING MATERIALS AND PROCEEDING WITH THE AFFECTED PART OF THE WORK.

6. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE ALL WORK WITH THE CONTRACTING OFFICER'S REPRESENTATIVE ON A DAILY

BASIS.

7. THE EXACT SIZE & LOCATION OF ALL EXISTING UTILITIES IMPACTED BY THE WORK SHALL BE FIELD VERIFIED BY THE CONTRACTOR PRIOR TO START OF CONSTRUCTION. CONTRACTOR SHALL TAKE CARE TO PROTECT ALL UTILITIES IN THE WORK AREA AND ALL CONSTRUCTION SHALL

BE COORDINATED WITH THE CONTRACTING OFFICER'S REPRESENTATIVE.

8. METHODS OF DEMOLITION, CONSTRUCTION, AND ERECTION ARE THE CONTRACTOR'S RESPONSIBILITY UNLESS OTHERWISE SPECIFIED.

9. THE CONTRACTOR SHALL PROVIDE AND MAINTAIN ENVIRONMENTAL CONTROLS AS REQUIRED BY FEDERAL, STATE AND MUNICIPAL REGULATIONS AND PERMITS. ENVIRONMENTAL CONTROLS SHALL INCLUDE BUT NOT BE LIMITED TO TURBIDITY, PH, AND DUST.

10. THE CONTRACTOR SHALL FOLLOW ALL APPLICABLE FEDERAL, STATE AND MUNICIPAL REGULATIONS, INCLUDING THE FEDERAL DEPARTMENT OF LABOR, SAFETY, OCCUPATIONAL SAFETY, HEALTH ACT, U.S. ARMY CORPS OF ENGINEERS, STATE/LOCAL WETLANDS CONTROL, AND

PERMITS.

11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY ADDITIONAL COST OF REINSPECTION OR RETEST WHEN PRIOR REJECTION MAKES

REINSPECTION OR RETEST NECESSARY.

12. THE CONTRACTOR IS RESPONSIBLE FOR ALL DAMAGE DONE TO STRUCTURES AND VESSELS OR INJURIES TO THE PUBLIC AND FACILITY

PERSONNEL AS A RESULT OF PERFORMING THE WORK.

UTILITY NOTES

1. CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PROTECT AND SUPPORT EXISTING UTILITIES WITHIN THE AREA OF WORK. ANY

DAMAGE INCURRED SHALL BE REPAIRED IMMEDIATELY TO THE SATISFACTION OF THE CONTRACTING OFFICER'S REPRESENTATIVE, AT THE

CONTRACTORS EXPENSE.

2. ALL UTILITIES WITHIN THE LIMITS OF THE WORK SHALL BE EITHER PROTECTED AND SUPPORTED DURING CONSTRUCTION, OR DISCONNECTED AND REINSTALLED, AS REQUIRED TO COMPLETE THE SCOPE REPAIR WORK. ANY UTILITY COMPONENTS WITHIN THE LIMITS OF WORK THAT ARE DAMAGED DURING CONSTRUCTION, OR NOT SUITABLE FOR REINSTALLATION AS A RESULT OF THE WORK, SHALL BE

REPLACED IN-KIND AT NO ADDITIONAL COST TO THE GOVERNMENT.

4. ALL INCIDENTAL ELECTRICAL WORK REQUIRED TO COMPLETE THE REPAIRS SHALL BE COMPLETED IN ACCORDANCE WITH THE NFPA 70:

NATIONAL ELECTRIC CODE.

5. OUTAGES SHALL BE LIMITED TO THE EXTENT PRACTICAL TO MINIMIZE INTERRUPTIONS TO STATION OPERATIONS. DURING WORK WITHIN THE LIMITS OF THE FUEL SYSTEM, THE FUEL SYSTEM SHALL BE TURNED OFF AND DISCONNECTED AS REQUIRED TO COMPLETE THE WORK, BUT NO LONGER THAN 3 WEEKS. DURING THIS TIME, THE CG WILL BE UTILIZING A LOCAL MARINA FOR REFUELING. IF FUEL OUTAGES LAST LONGER THAN 3 WEEKS, THE CONTRACTOR SHALL PROVIDE TEMPORARY ON-SITE FUEL SERVICE FOR THE VESSELS AT NO ADDITIONAL

COST TO THE GOVERNMENT.

6. NOTIFY THE COR AND THE STATION A MINIMUM OF 5 WORKING DAYS IN ADVANCE OF ANY OUTAGES. ALL OUTAGES, INCLUDING DISCONNECTION OF THE FUEL SERVICES, SHALL BE APPROVED BY THE CONTRACTING OFFICER AND COORDINATED WITH THE COR AND THE

STATION.

MARINE COATING NOTES

1. MARINE COATING FOR RECOATING THE EXISTING GUIDE PILES SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH SPECIFICATION

SECTION 09 97 13.26.

2. COATING SHALL BE BLACK, COMPOSED OF A TWO-PART COAL-TAR EPOXY, OR APPROVED EQUAL, APPLIED TO A MINIMUM 16 MIL

THICKNESS (DRY FILM).

3. COATING SHALL BE APPLIED IN STRICT CONFORMANCE TO APPLICABLE ENVIRONMENTAL PERMITS AND REGULATIONS AND THE UNITED

STATES COAST GUARD'S ENVIRONMENTAL POLICIES AND STANDARDS.

4. IF BID OPTION ITEM 2 IS AWARDED, THE CONTRACTOR SHALL ENSURE THAT THE COATING HAS SUFFICIENTLY CURED AND IS ADEQUATELY

PROTECTED DURING INSTALLATION OF THE PILE SLEEVES.

REVETMENT NOTES

1. THE CONTRACTOR SHALL PROVIDE AND SET NEW BEDDING AND RIPRAP STONES FOR THE RESTORATION OF THE REVETMENT WITHIN THE

CONSTRUCTION LIMITS AS SHOWN ON THE DRAWINGS. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL REGULATORY

REQUIREMENTS WITHIN THE LIMITS SPECIFIED HEREIN AND INDICATED BY THE DRAWINGS.

2. THE RIPRAP STONES SHALL BE PLACED AND NOT DUMPED. THE RIPRAP SHALL BE GRADED AND PLACED INTO POSITION BY EQUIPMENT IN ORDER TO INTERLOCK WITH ADJOINING UNITS WITH MAXIMUM CONTACT POINTS. EACH STONE SHALL BE ADEQUATELY KEYED INTO PROPER

SEATING TO ENSURE A TIGHT FIT, AND THE STABILITY OF THE SLOPE IS MAINTAINED.

3. AT THE NORTH REVETMENT, THE CONTRACTOR SHALL MAY USE EXISTING STONES PRESENT IN THE AREA TO REGRADE THE EXISTING AREA TO ESTABLISH THE SUBSURFACE GRADES PRIOR TO PLACEMENT OF THE BEDDING LAYER. EXISTING STONES MAY BE USED AS THE TOE STONE, PROVIDED THAT THEY ARE OF THE REQUIRED SIZE AND SET TO ESTABLISH THE TOE OF THE RESTORED SLOPE AREA.

4. THE INTENT OF THE BEDDING LAYER AND RIPRAP SLOPE SHOWN IS TO IMPROVE PROTECTION AND STABILIZATION OF THE ERODED SHORELINE AREA, LOCATED ABOVE MEAN HIGH WATER. THE EXISTING SLOPE IN THIS AREA SHALL BE EXCAVATED AND PREPARED TO SET THE TOE STONES, BEDDING LAYER, AND RESTORED SLOPE PROTECTION AS SHOWN ON THE DRAWINGS. IN THE EVENT THAT LEDGE OUTCROPPINGS ARE PRESENT THAT INTERFERE WITH THE PROPOSED BEDDING AND RIPRAP LAYERS SHOWN, THE BEDDING LAYER THICKNESS MAY BE REDUCED, OR TERMINATED IN THE AREA OF INTERFERENCES, TO FACILITATE CONSTRUCTION AND MAINTAIN A CONSISTENT REVETMENT FACE. IF THE BEDDING LAYER IS TERMINATED AT THESE AREAS, THE GEOTEXTILE LAYERS FOR THE SURROUNDING BEDDING SHALL BE TURNED BACK A MINIMUM 18 INCHES TO PREVENT LOSS OF BEDDING MATERIAL.

5. RIPRAP REVETMENT STONES FOR THE NORTH REVETMENT SHALL CONFORM TO NHDOT TABLE 583-1 CLASS III GRADATION. RIPRAP REVETMENT STONES FOR THE SOUTH REVETMENT SHALL CONFORM TO NHDOT TABLE 583-1 CLASS VII GRADATION.

6. BEDDING STONE FOR THE NORTH REVETMENT SHALL CONFORM TO NHDOT #357 STONE, TABLE 703.1.

7. BEDDING STONE FOR THE SOUTH REVETMENT SHALL CONFORM TO NHDOT SECTION 585.2.1 3, CLASS C STONE.

8. THE CONTRACTOR SHALL PLACE TOE STONES, FOLLOWED BY BEDDING STONE, AND RIPRAP STONE.

9. REFER TO SPECIFICATION SECTION 35 31 19.40 FOR ADDITIONAL REQUIREMENTS.

CATHODIC PROTECTION NOTES

1. GALVANIC ANODES FOR THE PILES SHALL BE ALUMINUM ANODES PROVIDED AND INSTALLED IN ACCORDANCE WITH PROJECT

SPECIFICATION SECTION 26 42 13.

2. ANODE SHALL BE A MINIMUM 120-LB ANODE., MEETING THE FOLLOWING CHEMICAL COMPOSITION, AND WITH DIMENSIONS AS SHOWN ON

THE CONTRACT DRAWINGS:

A. ZINC (Zn) 2.80 - 6.50% B. INDIUM (In) 0.01 - 0.02% C. SILICON (Si) 0.08 - 0.20% D. COPPER (Cu) 0.006% (MAX) E. IRON (Fe) 0.120% (MAX)

F. ALUMINUM REMAINDER

3. ANODE CORE SHALL BE A FLAT-BAR TYPE AS SHOWN ON THE DRAWINGS.

GEOTEXTILE NOTES

1. GEOTEXTILE FOR SOIL SEPARATION IN AREAS OF EXCAVATION, SINKHOLE REPAIRS, AND GENERAL CIVIL SITE WORK SHALL BE A CLASS 2

NON-WOVEN GEOTEXTILE IN ACCORDANCE WITH AASHTO M288, SUITABLE FOR SOIL SEPARATION AND SUBSURFACE DRAINAGE USES.

2. GEOTEXTILE FOR RIPRAP REVETMENT LAYERS IN AREAS OF EXCAVATION SHALL BE A CLASS 2 WOVEN GEOTEXTILE IN ACCORDANCE WITH

AASHTO M288, SUITABLE FOR RIPRAP REVETMENT AND SLOPE STABILIZATION USES.

3. JOINTS SHALL BE LAPPED A MINIMUM OF 12 INCHES FOR SOIL SEPARATION, AND MINIMUM OF 36 INCHES FOR REVETMENT LAYERS.

TERMINATIONS SHALL BE TURNED BACK A MINIMUM OF 18 INCHES TO PREVENT LOSS OF CONTAINED OR SEPARATED MATERIAL.

4. REFER TO SPECIFICATION SECTION 31 05 19.13 FOR ADDITIONAL REQUIREMENTS.

DEMOLITION AND EXCAVATION NOTES:

1. WHERE COMPONENTS ARE CALLED OUT ON THESE DRAWINGS AS "REPLACE", "REMOVE AND REPLACE", OR SIMILAR VERBIAGE, CONTRACTOR SHALL REMOVE AND DISPOSE OF EXISTING COMPONENTS, AND FURNISH AND INSTALL NEW COMPONENTS. WHERE COMPONENTS ARE CALLED OUT ON THESE DRAWINGS AS "REMOVE AND SALVAGE" OR SIMILAR VERBIAGE, CONTRACTOR SHALL REMOVE, STORE AND PROTECTS ITEMS AS NECESSARY, AND REINSTALL THE EXISTING COMPONENTS.

2. CONTRACTOR SHALL REMOVE ALL ITEMS IDENTIFIED FOR REMOVAL OR DEMOLITION IN THIS DRAWING SET AS REQUIRED TO COMPLETE THE REPAIRS. FOR ITEMS TO BE REMOVED AND REINSTALLED, THE CONTRACTOR MAY ELECT TO LEAVE THE SITE FEATURES IN PLACE DURING REPAIRS, PROVIDED THAT THE FEATURES ARE SHORED AS NECESSARY, PROTECTED FROM DAMAGE, AND REMAIN UNDISTURBED THROUGHOUT THE PROJECT. ITEMS THAT ARE DAMAGED OR DISTURBED, SHALL BE REPLACED IN-KIND OR AS INDICATED IN THE DRAWINGS, TO THE SATISFACTION OF THE CONTRACTING OFFICER AND AT NO ADDITIONAL COST TO THE GOVERNMENT.

3. ALL MATERIAL REMOVED/DEMOLISHED AND NOT SALVAGED AND/OR REINSTALLED SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE DISPOSED OF OFF-SITE. REMOVED MATERIAL SHALL BE DISPOSED OF IN ACCORDANCE WITH ALL LOCAL, STATE AND

FEDERAL LAWS.

4. THE CONTRACTOR SHALL PROVIDE CONTROL MEASURES AS REQUIRED BY ENVIRONMENTAL REGULATIONS AND AS REQUIRED TO PREVENT DEBRIS CONTAMINANTS (SOLID, LIQUID OR DISSOLVED) FROM ENTERING THE WATER. UNDERWATER INSPECTIONS MAY BE CONDUCTED BY THE CONTRACTING OFFICER TO ENSURE THE CONTRACTOR HAS REMOVED ALL DEMOLITION AND CONSTRUCTION DEBRIS FROM THE

MUDLINE.

5. CONTRACTOR SHALL PREVENT THE SPREAD OF DUST AND DEBRIS AND AVOID THE CREATION OF A NUISANCE OR HAZARD IN THE SURROUNDING AREA. DO NOT USE WATER IF IT RESULTS IN HAZARDOUS OR OBJECTIONABLE CONDITIONS SUCH AS, BUT NOT LIMITED TO, FLOODING OR POLLUTION.

6. CONTRACTOR SHALL VERIFY AND VALIDATE THAT ALL MATERIALS REMOVED FROM THE SITE ARE CONTAMINANT FREE PRIOR TO DISPOSING OR RECYCLING OF ANY MATERIAL; APPROPRIATE REGULATORY TESTING SHALL CONFIRM THAT MATERIALS ARE FREE OF CONTAMINANTS.

7. WHERE PEDESTRIAN/CG PERSONNEL AND DRIVER SAFETY IS ENDANGERED IN THE AREA OF REMOVAL OR EXCAVATION WORK, USE TRAFFIC BARRICADES. ANCHOR BARRICADES IN A MANNER TO PREVENT DISPLACEMENT BY WIND. NOTIFY FACILITY PERSONNEL PRIOR TO

BEGINNING SUCH WORK.

8. CONTRACTOR SHALL IMPLEMENT METHODS TO SEAL ENDS OF EXCAVATIONS IN ORDER TO MINIMIZE WATER INFILTRATION AND MIGRATION OF FINES FROM ADJACENT AREAS INTO THE EXCAVATION. AREAS THAT BECOME DESTABILIZED AND/OR LOSS OF FILL CREATED FROM THE EXCAVATIONS SHALL BE REPAIRED TO THE SATISFACTION OF THE CONTRACTING OFFICER AT NO ADDITIONAL COST TO THE GOVERNMENT.

9. THE CONTRACTOR IS ADVISED THAT DEWATERING MAY BE REQUIRED TO COMPLETE THE WORK. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING NECESSARY DEWATERING PERMITS FOR DISCHARGING INTO THE SURFACE WATERS, OR COORDINATING WITH THE CITY OF PORTSMOUTH WWTP FOR DISCHARGING INTO THE PUBLICLY OWNED TREATMENT WORKS (POTW). IT IS ANTICIPATED THAT DISCHARGE METERING, WATER SAMPLING, AND SETTLEMENT OF SUSPENDED SOLIDS WILL BE REQUIRED PRIOR TO DISCHARGING INTO SURFACE WATERS OR POTW. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL CONSTRUCTION-RELATED PERMITS, INCLUDING DEWATERING

PERMITS.

10. THE CONTRACTOR SHALL OBTAIN A PERMIT FROM THE TOWN OF NEW CASTLE FIRE DEPARTMENT FOR WELDING OR TORCH CUTTING WORK PERFORMED AT THE SITE. CONTRACTOR SHALL ALSO OBTAIN A BURN PERMIT FROM STA EPO PRIOR TO WELDING OR TORCH CUTTING.

11. REFER TO SPECIFICATION SECTION 02 41 00 DEMOLITION AND DECONSTRUCTION FOR ADDITIONAL DEMOLITION REQUIREMENTS. REFER TO SPECIFICATION SECTION 31 23 00.00 FOR ADDITIONAL EXCAVATION AND EARTHWORK REQUIREMENTS.

CONCRETE NOTES:

1. CAST-IN-PLACE CONCRETE SHALL APPLY TO FENCE POST FOOTINGS, SOUTH QUAY WALL VOID REPAIR, CLOSURE WALL AT EAST END OF

NORTH QUAY WALL, AND OTHER INCIDENTAL SITE WORK.

2. ALL CONCRETE CONSTRUCTION AND DETAILING SHALL CONFORM TO THE LATEST EDITION OF ACI 318.

3. CONCRETE SHALL HAVE A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 5,000 PSI IN ACCORDANCE WITH THE SPECIFICATIONS. THE CONCRETE FOR THE SOUTH QUAY WALL VOID REPAIR SHALL BE A MARINE-GRADE CONCRETE, INCLUDING A CORROSION INHIBITOR.

4. MAINTAIN 3" CLEAR COVER TO ALL REINFORCING STEEL, UNLESS OTHERWISE NOTED.

5. EXPOSED CONCRETE EDGES SHALL HAVE A 3/4" CHAMFER, UNLESS OTHERWISE INDICATED.

6. CONCRETE SURFACES SHALL BE COVERED AND MOIST CURED FOR A PERIOD OF NOT LESS THAN SEVEN (7) FULL DAYS AFTER CONCRETE

PLACEMENTS.

7. ALL WELDED WIRE REINFORCING SHALL BE IN ACCORDANCE WITH ASTM A1064. ALL REINFORCING BARS SHALL BE IN ACCORDANCE WITH ASTM A615, GRADE 60. REINFORCING BARS FOR THE SOUTH QUAY WALL VOID REPAIR SHALL BE HOT-DIP GALVANIZED IN ACCORDANCE

WITH ASTM A767.

8. ALL REINFORCING SHALL BE FULLY SUPPORTED ON APPROVED PLASTIC CHAIRS AND/OR COATED STEEL.

9. REFER TO SECTION 03 30 00 CAST-IN-PLACE CONCRETE FOR ADDITIONAL REQUIREMENTS.

STRUCTURAL STEEL NOTES:

1. ALL STRUCTURAL STEEL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE AISC STEEL CONSTRUCTION

MANUAL.

2. ALL STRUCTURAL STEEL SHAPES SHALL BE ASTM A572, GRADE 50. ALL STEEL PLATES SHALL BE ASTM A36. ALL STEEL PLATES AND SHAPES, SHALL BE HDG, UNLESS NOTED OTHERWISE.

3. STEEL PIPE SHALL BE ASTM A53 GRADE B. ALL PIPE SHALL BE HDG, UNLESS NOTED OTHERWISE.

4. ALL ABOVE WATER WELDING SHALL BE IN ACCORDANCE WITH SPECIFICATION SECTION 05 12 00 AND THE STRUCTURAL WELDING CODE D1.1 OF THE AMERICAN WELDING SOCIETY (AWS). ELECTRODES SHALL BE E7OXX LOW HYDROGEN IN ACCORDANCE WITH AWS SPECIFICATIONS.

UNDERWATER WELDING SHALL BE IN ACCORDANCE WITH AWS CODE D3.6.

5. ALL BOLTS, THREADED RODS, NUTS AND WASHERS SHALL BE HOT-DIP GALVANIZED, UNLESS NOTED OTHERWISE, IN ACCORDANCE WITH

ASTM A153, OR F2329, AS APPLICABLE.

6. STAINLESS STEEL BOLTS AND THREADED ROD SHALL BE TYPE 316/316L.

7. ALL DISSIMILAR METALS SHALL BE SEPARATED BY PLASTIC SEPARATION SHEETS OR BUSHINGS NOT LESS THAN 1/16 INCH THICK. THE SEPARATION SHEETS SHALL BE NYLATRON-GS, PLASTIC SHEET CONFORMING TO MILITARY SPECIFICATION MIL-P-15035 OR OTHER SUITABLE

MATERIAL TO LIMIT GALVANIC CORROSION.

8. REFER TO SPECIFICATION SECTION 05 12 00 FOR ADDITIONAL STRUCTURAL REQUIREMENTS, SECTION 32 31 13, AND CSTO REFERENCE

DOCUMENT INCLUDED IN SPECIFICATIONS FOR STEEL SECURITY FENCING REQUIREMENTS.

9. ALL REPLACEMENT FENCING SHALL BE USCG CSTO-COMPLIANT 7-FT HIGH CHAINLINK FENCE WITH A 1-FT TOPGUARD (8-FT TOTAL FENCE

HEIGHT). SEE CSTO REFERENCE DOCUMENT INCLUDED IN PROJECT SPECIFICATIONS.

TIMBER FLOATING DOCK NOTES:

1. THE FLOATING DOCKS SHALL BE CONSTRUCTED OF TIMBER, WITH FLOAT MODULES CONSISTING OF EXPANDED POLYSTYRENE BILLETS ENCAPSULATED IN AN HDPE SHELL. ALL DOCKS SHALL BE DESIGNED FOR THE MARINE SALTWATER ENVIRONMENT.

2. FLOATING DOCK SHALL BE CONSTRUCTED FOR A UNIFORM LIVE LOAD OF 40-PSF, MAINTAINING A MINIMUM FREEBOARD OF 8 INCHES UNDER DEAD AND LIVE LOAD CONDITIONS. DOCKS SHALL HAVE A MINIMUM FREEBOARD OF 18-22 INCHES UNDER DEAD LOAD CONDITIONS, INCLUDING ALL PERMANENT DOCK COMPONENTS AND GANGWAY. DOCKS SHALL NOT HAVE MORE THAN A 5 DEGREE LIST AFTER

COMPLETED INSTALLATION.

3. ADDITIONAL FLOATATION SHALL BE USED FOR FLOATING DOCK UNDER GANGWAY LANDING TO PROVIDE LEVEL FLOATATION UNDER

GANGWAY DEAD LOAD.

4. FLOATING DOCK WILL BE EXPOSED TO WIND AND WAVES DURING ERECTION AND WHILE IN SERVICE, AND CONTRACTOR SHALL ANALYZE, DESIGN AND CONSTRUCT ACCORDINGLY. CONTRACTOR SHALL PROVIDE BRACKETED CONNECTIONS AND HARDWARE TO ACCOMMODATE DESIGN LOADS AND FREEBOARD REQUIREMENTS AS OUTLINED ABOVE, AND TO WITHSTAND ENVIRONMENTAL WAVE AND VESSEL WAKE ACTION NORMAL TO THE SITE. THE FOLLOWING IS MINIMUM DESIGN CRITERIA THAT SHALL BE USED FOR THE DOCK SYSTEM:

4.a. UNIFORM LIVE LOAD: 40 PSF 4.b. CURRENT VELOCITY: 0.5 FPS 4.c. SIGNIFICANT WAVE HEIGHT (HS): 2.0 FT 4.d. WAVE PERIOD: 3 SECONDS 4.e. VESSEL IMPACT: 1000 FT-LB AT 10 DEGREES FROM LONGITUDINAL AXIS 4.f. WIND LOAD: 22 PSF ON MOORED VESSEL PROFILES AND EXPOSED FLOAT AREAS.

4.g. MOORED VESSEL: (2) 47-FT MOTOR-LIFE BOAT, ONE LOCATED ON EACH SIDE OF DOCK.

5. PILE GUIDE ASSEMBLIES SHALL BE ROLLER-TYPE, CONSTRUCTED OF HDG HOLLOW STRUCTURAL STEEL OR HDG STEEL ANGLES WITH A

MINIMUM STEEL THICKNESS OF 3/8-INCH.

6. CLEATS SHALL BE 15-INCH HOT-DIPPED GALVANIZED CAST STEEL AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS, USING THRU-BOLTED CONNECTIONS. MOORING HARDWARE AND MOORING HARDWARE CONNECTIONS SHALL BE

DESIGNED FOR A 3,500 LB LINE LOAD.

7. REFER TO SPECIFICATION SECTION 35 51 13.00 FOR ADDITIONAL REQUIREMENTS.WORK RESTRICTIONS:

1. THE CONTRACTOR IS ADVISED THAT LOADING WITHIN 15 FEET OF THE EXISTING NORTH QUAY WALL FACE IS LIMITED TO 100 PSF UNIFORM

LIVE LOAD. VEHICLES, CRANES, OR OTHER LOAD HANDLING EQUIPMENT IS PROHIBITED IN THIS AREA. REFER TO SEE SHEET G-101 AND THE

PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS AND RESTRICTIONS.

SULLIVAN LANE

EXISTING STONE REVETMENT

MHW (EL. 4.0')

STA PORTSMOUTH HARBOR

PISCATAQUA RIVER

BULKHEADS - NORTH QUAY WALL (RPUID 816511) (SHEET C-102, C-301)

- CHINK AND REPOINT QUAY WALL

- REMOVE AND REPLACE EXISTING FENCE (RPUID 810801)

- REPAIR SINKHOLES IN DUMPSTER PAD AREA (RPUID 9383)

- PROVIDE EAST CLOSURE WALL IN DUMPSTER PAD AREA

RIP-RAP (RPUID 857029) (SHEET C-102, C-301)

- RESTORE RIP-RAP REVETMENT

- REMOVE AND REPLACE EXISTING FENCE (RPUID 810801)

- REPAIR SINKHOLES IN WEST PARKING LOT (RPUID 9383)

BULKHEADS - SOUTH QUAY WALL (RPUID 816511) (SHEET C-102, C-302)

- REPAIR VOID IN FACE OF QUAY WALL

- REPAIR SINKHOLE BEHIND QUAY WALL

- PROVIDE REVETMENT EXTENSION AT WEST END OF QUAY WALL (BID OPTION 1)

WAVE SCREEN/FLOAT DOCK (RPUID 50109) (SHEET S-101)

- RECOAT GUIDE PILES FROM MLW TO TOP OF PILES

- REPLACE BROKEN CLEAT

- INSTALL GALVANIC ANODES

- INSTALL HDPE PILE SLEEVES (BID OPTION 2)

BULKHEAD - SOUTH QUAY WALL (RPUID 816511) (SHEET C-102, C-302)

- REPAIR EAST WALL WITH INTERIM STONE BERM

FORT CONSTITUTION

EXISTING STATION ENTRANCE GATE EQUIPMENT SHED

EXISTING BOATHOUSE

HAZARDOUS WASTE STORAGE

EXISTING GABION MATTRESS

LOADING WITHIN 15 FEET OF QUAY WALL

IS LIMITED TO 100 PSF UNIFORM LIVE

LOAD. VEHICLES, CRANES, OR OTHER

LOAD HANDLING EQUIPMENT IS

PROHIBITED IN THIS AREA. (SEE NOTE 2)

FLOATING DOCK - BOATHOUSE (RPUID 848538) (SHEET S-102)

- INSTALL NEW TIMBER FLOAT

ENG BLDG

SAR BLDG

UNH BLDG

MULTI MISSION

BLDG

SHED

OLD OIL HOUSE

KEEPER'S QUARTERS

0+

0+20 0+40 0+60 0+80 1+00 1+20 1+40 1+60 1+80 1+98

0+00 0+20 0+40 0+60 0+80 1+00 1+20 1+40 1+60 1+80 2+00 2+20

2+40 2+60 2+80 3+00 3+20 3+40 3+60 3+80 4+004+12

DE

SI

GN

ED

B Y:

DE

SC

RI

PT

IO

N

M

AR

K

ED

IT

ED

B Y:

DA

TE

CH

EC

KE

D

BY

DR

AW

N

BY

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

SH

EE

T

OF

US

CG

P

RO

JE

CT

N

UM

BE

R

US

CG

F

IL

EN

AM

E

A/ E

CO

M

PA

NY

CO

NS

UL

TI

NG

A

/E

US

CG

P

RO

JE

CT

M

AN

AG

ER

A/

E

PR

OJ

EC

T

NO

SHEET ID

M

EA

SU

RE

M

EN

T

BA

R:

1"

HA

LF

S

IZ

E

1/ 2"

US

CG

D

RA

W

IN

G

SE

RI

ES

N

UM

BE

R

RE

PA

IR

W

AT

ER

FR

ON

T

- P

HA

SE

CG

S

TA

P

OR

TS

M

OU

TH

H

AR

BO

R

NE

W

C

AS

TL

E

NH

GE

NE

RA

L W

OR

K

PL

AN

BULKHEADS, RIP-RAP,

WAVE SCREEN, AND

FLOATING DOCK

G-101

P1

P1

2G

1.

dw g

US

CG

C

IV

IL

E

NG

IN

EE

RI

NG

U

NI

T

PR

OV

ID

EN

CE

KI

LV

ER

T

ST

, S

UI

TE

W

AR

W

IC

K, R I 0

DA

VI

D J.

AR

PI

N, P

.E

Z.

JE

NK

IN

S J.

DE

L

TU

FO

M .S

CH

M

ID

D.

O 'C

ON

NO

R

LL

OY

D-

CO

LL

IN

S

JV

BE

LL

AI

RE

, T

EX

AS

(8

) 4

-4

LC

JV

-1

IS

SU

ED

F

OR

B

ID

DI

NG

NO

V

US COAST GUARD

CIVIL ENGINEERING

F1 G-901

F3 G-901

F3 G-901

F5 G-901

F7 G-901

D1 G-901

D3 G-901

D5 G-901

D7 G-901

B1 G-901

B3 G-901

B5 G-901

B7 G-901

A1 G-901A3

G-901

A5 G-901 A7

G-901

NOTES

1. CONTRACTOR SHALL COORDINATE STATION ACCESS AND PARKING WITH THE

COR AND OIC. SEE SPECIFICATION SECTION 01 14 00 ADDITIONAL REQUIREMENTS.

2. AREA OF LOAD RESTRICTIONS SHOWN HAS INTERMITTENT AREAS OF

SUBSIDENCE AND SINKHOLES THROUGHOUT. CONTRACTOR SHALL EXERCISE

EXTREME CAUTION WHEN USING THIS AREA WHILE PERFORMING THE WORK.

X# G-901

LEGEND

PHOTO IDENTIFIER (ARROW INDICATES DIRECTION TAKEN)

LOAD RESTRICTED AREA

APPROXIMATE AREA OF WORK

WORK PLAN

AutoCAD SHX Text

SBL

AutoCAD SHX Text

TMB

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SYL

AutoCAD SHX Text

SYL

AutoCAD SHX Text

TMB

AutoCAD SHX Text

AutoCAD SHX Text 30'

AutoCAD SHX Text 60'

AutoCAD SHX Text

PLAN

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

SCALE: 1"=30'

OVERALL OF NORTH QUAYWALL, LOOKING SOUTHEASTF1 NTS

TYPICAL GAPS BETWEEN BLOCKS IN NORTH QUAYWALLF3 NTS

SHIFTED AND DISPLACED BLOCKS IN NORTH QUAYWALLF5 NTS

ROTATION AND BULGING ALONG TOP OF NORTH QUAYWALLF7 NTS

OVERALL OF NORTH REVETMENTD1 NTS

FAILED SOUTH QUAYWALL, LOOKING EASTA1 NTS

DUMPSTER PAD AREA TO BE REPAIREDB1 NTS

EAST CLOSURE WALL REPAIR AREA AT DUMPSTER PADB3 NTS

LOSS OF STONES AND CONCRETE IN SOUTH QUAYWALLB7 NTS

FAILED SOUTH QUAYWALL, LOOKING WESTA3 NTS

CORROSION AND COATING LOSS ON WAVE ATTENUATOR PILESA5 NTS

UNPROTECTED SHORELINE TO WEST OF SOUTH QUAYWALLB5 NTS

GABION MATTRESS REPAIR AT NORTHWEST REVETMENTD3 NTS

TEMPORARY REPAIRS AT NORTH REVETMENTD5 NTS

FORMER BOATHOUSE FLOATING DOCK LOCATIOND7 NTS

BROKEN CLEAT ON WAVE ATTENUATORA7 NTS

RE

PA

IR

W

AT

ER

FR

ON

T

- P

HA

SE

CG

S

TA

P

OR

TS

M

OU

TH

H

AR

BO

R

NE

W

C

AS

TL

E

NH

GE

NE

RA

L

EX

IS

TI

NG

C

ON

DI

TI

ON

S

PH

OT

OS

BULKHEADS, RIP-RAP,

WAVE SCREEN, AND

FLOATING DOCK

G-901

P1

P1

2G

1.

dw g

US

CG

, C

EU

P

RO

VI

DE

NC

E

KI

LV

ER

T

ST

, S

UI

TE

W

AR

W

IC

K, R

I 0

DA

VI

D J.

AR

PI

N, P

.E

Z.

JE

NK

IN

S J.

DE

L

TU

FO

M .S

CH

M

ID

D.

O 'C

ON

NO

R

LL

OY

D-

CO

LL

IN

S

JV

BE

LL

AI

RE

, T

EX

AS

(8

) 4

-4

LC

JV

-1

IS

SU

ED

F

OR

B

ID

DI

NG

NO

V

US COAST GUARD

CIVIL ENGINEERING

DE

SI

GN

ED

B Y:

DE

SC

RI

PT

IO

N

M

AR

K

ED

IT

ED

B Y:

DA

TE

CH

EC

KE

D

BY

DR

AW

N

BY

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

SH

EE

T

OF

US

CG

P

RO

JE

CT

N

UM

BE

R

US

CG

F

IL

EN

AM

E

A/ E

CO

M

PA

NY

CO

NS

UL

TI

NG

A

/E

US

CG

P

RO

JE

CT

M

AN

AG

ER

A/

E

PR

OJ

EC

T

NO

SHEET ID

M

EA

SU

RE

M

EN

T

BA

R:

1"

HA

LF

S

IZ

E

1/ 2"

US

CG

D

RA

W

IN

G

SE

RI

ES

N

UM

BE

R

SOLICITATION NO.: CONTRACT NO.:

EXISTING QUAYWALL TO BE

CHINKED AND REPOINTED

EXISTING

QUAYWALL GAPS TO

BE CHINKED (TYP)

EXISTING QUAYWALL

GAPS TO BE CHINKED

(TYP)

EXISTING REVETMENT TO BE

STABILIZED WITH RIPRAP

EXISTING GABION

MATTRESSES TO

REMAIN

EXISTING NORTH REVETMENT

TO BE STABILIZED WITH RIPRAP

EXISTING REVETMENT TO BE

STABILIZED WITH RIPRAP AREA OF TIMBER FLOATING

DOCK REPLACEMENT

VOID BELOW DUMPSTER

PAD TO BE REPAIRED

AREA OF RIPRAP STABILIZATION

AT WEST END OF SOUTH

QUAYWALL (BID OPTION ITEM 1)

VOID/MISSING STONES IN SOUTH

QUAYWALL TO BE REPAIRED

AREA OF FAILED SOUTH

QUAYWALL TO BE REPLACED

WITH INTERIM RIPRAP BERM

AREA OF MISSING STONES TO

BE RESET AT SOUTH QUAYWALL

EXISTING FLOATING WAVE

ATTENUATOR GUIDE PILES TO BE

RECOATED (BASE BID) AND

PROTECTED WITH HDPE SLEEVES (BID

OPTION ITEM 2)(TYP)

BROKEN CLEAT TO BE REPLACED ON

EXISTING FLOATING WAVE

ATTENUATOR

AREA OF FAILED SOUTH

QUAYWALL TO BE REPLACED

WITH INTERIM RIPRAP BERM

EXISTING FENCE TO BE

REPLACED (TYP)

OHW

S

D

G

W

X

E

C

U

FM

1. REFERENCE: USCG STATION PORTSMOUTH HARBOR NEWCASTLE, NH

2. FIELD SURVEY PERFORMED BY J.H.H. & S.N.F. (SURVEYING AND MAPPING, LLC) DURING

MARCH, 2025 USING A TOTAL STATION AND A SURVEY GRADE GPS WITH A DATA

COLLECTOR AND A DIGITAL LEVEL. TRAVERSE ADJUSTMENT BASED ON LEAST SQUARE

ANALYSIS.

3. TERRESTRIAL LIDAR SURVEY PERFORMED BY M.J.C. (SURVEYING AND MAPPING, LLC) ON

MARCH 10, 2025 USING A LEICA HDS SCANNER. REGISTRATION ADJUSTMENT BASED ON

LEAST SQUARE ANALYSIS.

4. HORIZONTAL DATUM BASED ON NAD83(2011) NEW HAMPSHIRE STATE PLANE COORDINATE

ZONE (2800) DERIVED FROM REDUNDANT GPS OBSERVATIONS UTILIZING THE KEYNET GPS

VRS NETWORK.

5. VERTICAL DATUM IS BASED ON NAVD88 PER DIFFERENTIAL LEVELS FROM DISK

CONSTITUTION 147 RM 1 (PUBLISHED NAVD88 ELEVATION = 14.69'). THIS DISK WAS ALSO

USED AS CONTROL POINT #3 SHOWN HEREON.

6. HIGHEST OBSERVABLE TIDE LINE IDENTIFIED BY LUKE HURLEY, CWS#232 ON MARCH 1,

2025.

7. PROPER FIELD PROCEDURES WERE FOLLOWED IN ORDER TO GENERATE CONTOURS AT 1'

INTERVALS. ANY MODIFICATION OF THIS INTERVAL WILL DIMINISH THE INTEGRITY OF THE

DATA, AND DOUCET SURVEY WILL NOT BE RESPONSIBLE FOR ANY SUCH ALTERATION

PERFORMED BY THE USER.

8. THE ACCURACY OF MEASURED UTILITY INVERTS AND PIPE SIZES/TYPES IS SUBJECT TO

NUMEROUS FIELD CONDITIONS, INCLUDING; THE ABILITY TO MAKE VISUAL OBSERVATIONS,

DIRECT ACCESS TO THE VARIOUS ELEMENTS, MANHOLE CONFIGURATION, ETC.

9. UNDERGROUND UTILITIES SHOWN HEREON ARE THE RESULT OF A QUALITY LEVEL B

UTILITY DESIGNATION COMPLETED BY DOUCET SURVEY DURING MARCH 2025 AND FROM

DATA OBTAINED FROM RECORD MAPS & DRAWINGS. DOUCET'S UTILITY DESIGNATION WAS

COMPLETED IN ACCORDANCE WITH THE STANDARD PROCEDURES SET FORTH IN ASCE

38-22 AND CONSISTENT WITH APPROPRIATE QUALITY LEVELS. DRAIN & SANITARY SEWER

WERE VISUALLY ALIGNED AND MAPPED AT QUALITY LEVEL C UNLESS OTHERWISE SHOWN.

ALL ABOVEGROUND STRUCTURES, SURFACE FEATURES AND THE LOCATION OF THE MARK

OUT ARE THE RESULT OF AN INSTRUMENT SURVEY COMPLETED BY DOUCET UNLESS

OTHERWISE NOTED. THERE MAY BE OTHER UNDERGROUND UTILITIES, THE EXISTENCE OF

WHICH ARE NOT KNOWN OR CERTIFIED BY THE UNDERSIGNED. DIG-SAFE AND THE

APPROPRIATE AUTHORITIES MUST BE NOTIFIED PRIOR TO CONDUCTING TEST BORINGS,

EXCAVATION OR CONSTRUCTION ACTIVITIES.

10. QUALITY LEVEL D (QLD) RECORD UTILITY INFORMATION IS BASED ON USCG BASE PLAN

DRAWING P1805UPOR AND UTILITY RECORDS MADE AVAILABLE BY COLLINS ENGINEERS,

INC.. THE UTILITY INFORMATION IS ONLY INTENDED TO BE USED TO HELP FACILITATE A

GRAPHIC REPRESENTATION AND DO NOT REPRESENT SURVEY LOCATIONS.

11. APPROXIMATE ABUTTER LINES AS SHOWN HEREON ARE BASED ON NH GRANIT GIS DATA

AND ARE IN THEIR ORIGINAL LOCATION.

DE

SI

GN

ED

B Y:

DE

SC

RI

PT

IO

N

M

AR

K

ED

IT

ED

B Y:

DA

TE

CH

EC

KE

D

BY

DR

AW

N

BY

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

SH

EE

T

OF

US

CG

P

RO

JE

CT

N

UM

BE

R

US

CG

F

IL

EN

AM

E

A/ E

CO

M

PA

NY

CO

NS

UL

TI

NG

A

/E

US

CG

P

RO

JE

CT

M

AN

AG

ER

A/

E

PR

OJ

EC

T

NO

SHEET ID

M

EA

SU

RE

M

EN

T

BA

R:

1"

HA

LF

S

IZ

E

1/ 2"

US

CG

D

RA

W

IN

G

SE

RI

ES

N

UM

BE

R

EXISTING CONDITIONS LEGEND

S-QLD

W-QLD

E-QLD

UTILITY LINES QUALITY LEVEL 'D' (SEE NOTE 10)

U-QLD

FM-QLD

FO

AB

DOUCET

SURVEY A Company

102 Kent Place, Newmarket, NH 03857 (603) 659-6560 Offices in Bedford & Keene, NH and Kennebunk, ME

Locations Nationwide | http://www.sam.biz

DOUCET

SURVEY A Company

RE

PA

IR

W

AT

ER

FR

ON

T

- P

HA

SE

CG

S

TA

P

OR

TS

M

OU

TH

H

AR

BO

R

NE

W

C

AS

TL

E

NH

CI

VI

L

EX

IS

TI

NG

C

ON

DI

TI

ON

S

NO

TE

S

BULKHEADS, RIP-RAP,

WAVE SCREEN, AND

FLOATING DOCK

C-001

P1

P1

2C

1.

dw g

US

CG

C

IV

IL

E

NG

IN

EE

RI

NG

U

NI

T

PR

OV

ID

EN

CE

KI

LV

ER

T

ST

, S

UI

TE

W

AR

W

IC

K, R I 0

DA

VI

D J.

AR

PI

N, P

.E

Z.

JE

NK

IN

S J.

DE

L

TU

FO

M .S

CH

M

ID

D.

O 'C

ON

NO

R

LL

OY

D-

CO

LL

IN

S

JV

BE

LL

AI

RE

, T

EX

AS

(8

) 4

-4

LC

JV

-1

IS

SU

ED

F

OR

B

ID

DI

NG

NO

V

US COAST GUARD

CIVIL ENGINEERING

APPROXIMATE ABUTTERS LINE (NOTE 11)

MAJOR CONTOUR LINE

MINOR CONTOUR LINE

RETAINING WALL

CHAIN LINK FENCE

CONSTRUCTION FENCE

GUARDRAIL

OVERHEAD WIRE

DRAIN LINE

SEWER LINE (SEE NOTE 9)

SEWER FORCEMAIN LINE (SEE NOTE 9)

WATER LINE (SEE NOTE 9)

GAS LINE (SEE NOTE 9)

ELECTRIC LINE (SEE NOTE 9)

FUEL OIL LINE (SEE NOTE 9)

CABLE/INTERNET LINE (SEE NOTE 9)

ABANDONED SEWER LINE (SEE NOTE 9)

UNIDENTIFIED UNDERGROUND UTILITY (SEE NOTE 9)

UNIDENTIFIED ABOVEGROUND CONDUIT

HIGHEST OBSERVABLE TIDE (SEE NOTE 6)

CONCRETE

RIP RAP

CRUSHED STONE

BRICK

PILE

LEDGE OUTCROP

SINKHOLE

SNOWBANK

SPOT GRADE

DISK FOUND

DISK SET

UTILITY POLE & GUY WIRE

UTILITY POLE STUMP

LIGHT POLE W/ARM

CATCH BASIN

SEWER MANHOLE

WATER SHUTOFF VALVE

GAS REGULATOR VALVE

HAND HOLE

PAD MOUNTED TRANSFORMER

ELECTRIC BOX

ELECTRIC MANHOLE

ELECTRIC METER

TELEPHONE MANHOLE

CABLE BOX

UNIDENTIFIED UTILITY BOX

AIR CONDITIONER

VENT PIPE

SIGN (TWO POSTS)

SQUARE POST

WOODEN POST

BOLLARD

JERSEY BARRIER

MONITORING WELL LOCATION

CAPSTAN

ABANDONED

CORRUGATED METAL PIPE

CONTROL POINT

CONCRETE

CONDUIT

DUCTILE IRON PIPE

END OF GEOPHYSICAL INVESTIGATION

EDGE OF PAVEMENT

ELECTRIC SWITCH

FINISHED FLOOR ELEVATION

GRANITE

REINFORCED CONCRETE PIPE

SINGLE WHITE LINE

SINGLE YELLOW LINE

SINGLE BLUE LINE

THRESHOLD ELEVATION

TIMBER EDGE / CURB

TYPICAL

INVERT I.D. CONNECTION UNKNOWN

ELECTRIC LINE

SEWER LINE

SEWER FORCEMAIN LINE

WATER LINE

UNIDENTIFIED UNDERGROUND UTILITY

EXISTING CONDITIONS NOTES

AutoCAD SHX Text

GR

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

AutoCAD SHX Text

CONC.

AutoCAD SHX Text

AutoCAD SHX Text

HH

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SYL

AutoCAD SHX Text

EP

AutoCAD SHX Text

ES

AutoCAD SHX Text

FF

AutoCAD SHX Text

TH

AutoCAD SHX Text

GRAN.

AutoCAD SHX Text 100.0

AutoCAD SHX Text

TMB

AutoCAD SHX Text

DIP

AutoCAD SHX Text

RCP

AutoCAD SHX Text (X)

AutoCAD SHX Text

EOI

AutoCAD SHX Text

CMP

AutoCAD SHX Text

EM

AutoCAD SHX Text

COND.

AutoCAD SHX Text C.P.

AutoCAD SHX Text

VP

AutoCAD SHX Text

MW

AutoCAD SHX Text

SBL

ABAND.

FORT CONSTITUTION

SULLIVAN LANE

PISCATAQUA RIVER

ATLANTIC OCEAN

DE

SI

GN

ED

B Y:

DE

SC

RI

PT

IO

N

M

AR

K

ED

IT

ED

B Y:

DA

TE

CH

EC

KE

D

BY

DR

AW

N

BY

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

SH

EE

T

OF

US

CG

P

RO

JE

CT

N

UM

BE

R

US

CG

F

IL

EN

AM

E

A/ E

CO

M

PA

NY

CO

NS

UL

TI

NG

A

/E

US

CG

P

RO

JE

CT

M

AN

AG

ER

A/

E

PR

OJ

EC

T

NO

SHEET ID

M

EA

SU

RE

M

EN

T

BA

R:

1"

HA

LF

S

IZ

E

1/ 2"

US

CG

D

RA

W

IN

G

SE

RI

ES

N

UM

BE

R

RE

PA

IR

W

AT

ER

FR

ON

T

- P

HA

SE

CG

S

TA

P

OR

TS

M

OU

TH

H

AR

BO

R

NE

W

C

AS

TL

E

NH

CI

VI

L

EX

IS

TI

NG

S

IT

E

PL

AN

BULKHEADS, RIP-RAP,

WAVE SCREEN, AND

FLOATING DOCK

C-101

P1

P1

2C

1.

dw g

US

CG

C

IV

IL

E

NG

IN

EE

RI

NG

U

NI

T

PR

OV

ID

EN

CE

KI

LV

ER

T

ST

, S

UI

TE

W

AR

W

IC

K, R I 0

DA

VI

D J.

AR

PI

N, P

.E

Z.

JE

NK

IN

S J.

DE

L

TU

FO

M .S

CH

M

ID

D.

O 'C

ON

NO

R

LL

OY

D-

CO

LL

IN

S

JV

BE

LL

AI

RE

, T

EX

AS

(8

) 4

-4

LC

JV

-1

DO

UC

ET

S

UR

VE

Y

NE

W M

AR

KE

T, N

H

IS

SU

ED

F

OR

B

ID

DI

NG

NO

V

US COAST GUARD

CIVIL ENGINEERING

EXISTING SITE PLAN

NOTE:

1. SEE SHEET C-001 FOR EXISTING SITE PLAN NOTES AND SYMBOLS.

AutoCAD SHX Text

STORAGE CONTAINER

AutoCAD SHX Text

HORSESHOE PIT

AutoCAD SHX Text

GRAN. QUAY WALL (TYP.)

AutoCAD SHX Text

CONC. BLOCK QUAY WALL

AutoCAD SHX Text

GRAN. BLOCK WALL

AutoCAD SHX Text

STONE PILE (TYP.)

AutoCAD SHX Text

FUEL TANK

AutoCAD SHX Text

TBM 8965A MAG NAIL SET IN LEDGE OUTCROP ELEV.=14.17'

AutoCAD SHX Text

ANTENNA

AutoCAD SHX Text

COND. (TYP.)

AutoCAD SHX Text

STORAGE CONTAINER

AutoCAD SHX Text

FUEL TANK

AutoCAD SHX Text

SWING GATE (TYP.)

AutoCAD SHX Text

SLIDING GATE (TYP.)

AutoCAD SHX Text

DUMPSTERS

AutoCAD SHX Text

CONC. BLOCK RET. WALL

AutoCAD SHX Text

PROPANE TANK

AutoCAD SHX Text

ELECTRIC PANEL

AutoCAD SHX Text

PIPE (TYP.)

AutoCAD SHX Text

UTILITY BOX

AutoCAD SHX Text

SECURITY CAMERA POST

AutoCAD SHX Text

WATER UTILITY CABINET

AutoCAD SHX Text

SBL

AutoCAD SHX Text

GATE CONTROL BOX

AutoCAD SHX Text

STONE & BRICK WALL

AutoCAD SHX Text

STONE & BRICK WALL

AutoCAD SHX Text

~HELICOPTER PAD~

AutoCAD SHX Text

FUEL TANKS

AutoCAD SHX Text

DECK

AutoCAD SHX Text

GANGWAY

AutoCAD SHX Text

COLLAPSED QUAY WALL

AutoCAD SHX Text

GANGWAY

AutoCAD SHX Text

TH=12.8'

AutoCAD SHX Text

GANGWAY

AutoCAD SHX Text

DOCK

AutoCAD SHX Text

BOATHOUSE

AutoCAD SHX Text

WALKWAY

AutoCAD SHX Text

GRAN. BLOCK WALL

AutoCAD SHX Text

ENGINEERING BUILDING

AutoCAD SHX Text

SAR BUILDING

AutoCAD SHX Text

UNH BUILDING

AutoCAD SHX Text

KEEPER'S QUARTERS

AutoCAD SHX Text

OLD OIL HOUSE

AutoCAD SHX Text

SHED

AutoCAD SHX Text

MULTI MISSION BUILDING

AutoCAD SHX Text

AUX SHED

AutoCAD SHX Text

BUILDING OVERHANG

AutoCAD SHX Text

QUAY WALL FOOTING

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text

STEPS

AutoCAD SHX Text

RAMP

AutoCAD SHX Text

RAMP

AutoCAD SHX Text

GATE CALL BOX

AutoCAD SHX Text

LUMBER PILE

AutoCAD SHX Text

~ROCKY SHORELINE~

AutoCAD SHX Text

~ROCKY SHORELINE~

AutoCAD SHX Text

EP

AutoCAD SHX Text

EP

AutoCAD SHX Text

EP

AutoCAD SHX Text

EP

AutoCAD SHX Text

EP

AutoCAD SHX Text

EP

AutoCAD SHX Text

~PAVED PARKING~

AutoCAD SHX Text

~PAVED PARKING~

AutoCAD SHX Text

EP

AutoCAD SHX Text

EP

AutoCAD SHX Text

EP

AutoCAD SHX Text

EP

AutoCAD SHX Text

EP

AutoCAD SHX Text

TMB

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SWL

AutoCAD SHX Text

SYL

AutoCAD SHX Text

SYL

AutoCAD SHX Text

~PAVED DRIVE~

AutoCAD SHX Text (A)

AutoCAD SHX Text CB 2467 RIM ELEV.=9.6' SUMP ELEV.=5.4' (2468) 12" RCP INV.=5.6' (A) 12" CMP INV.=5.4'

AutoCAD SHX Text

SMH 1949 RIM ELEV.=13.4' ABANDONED STRUCTURE & LINES

AutoCAD SHX Text

TAX MAP 19, LOT 2-2

AutoCAD SHX Text

TAX MAP 19, LOT 2

AutoCAD SHX Text

TAX MAP 19, LOT 3

AutoCAD SHX Text

(2)ES

AutoCAD SHX Text

(2)ES

AutoCAD SHX Text

ACCESS HATCH (TYP.)

AutoCAD SHX Text

ABAND.

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

ABAND.

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

ABAND.

AutoCAD SHX Text

ABAND.

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

EOI

AutoCAD SHX Text

TMB

AutoCAD SHX Text

EOI

AutoCAD SHX Text

VOLLEYBALL COURT

AutoCAD SHX Text

FF=10.7' (ARCHED DOORWAY IN FORTRESS WALL)

AutoCAD SHX Text

UPPER EDGE OF RIP-RAP

AutoCAD SHX Text

EQUIPMENT SHED

AutoCAD SHX Text

HAZARDOUS WASTE STORAGE

AutoCAD SHX Text

AutoCAD SHX Text 30'

AutoCAD SHX Text 60'

AutoCAD SHX Text

PLAN

AutoCAD SHX Text

NORTH

SCALE: 1"=30'

35'

0+

0+20 0+40 0+60 0+80 1+00 1+20 1+40 1+60 1+80 1+98

REMOVE AND REPLACE EXISTING FENCE

ALONG NORTH REVETMENT (APPROX. 180 LF)

MHW (EL. 4.0')

CHINK AND REPOINT FACE OF STONE QUAY

WALL (APPROX. 200 LF OF WALL)

REPAIR EXISTING REVETMENT (APPROX.

250 CY OF CLASS III REVETMENT STONE)

(APPROX. 130 CY OF BEDDING STONE)

EXISTING ELECTRICAL

EQUIPMENT PADS

EXISTING SIDEWALK

EXISTING GABIONS TO REMAIN

EXISTING FUEL TANK

ENG BLDG

SAR BLDG

PROVIDE CONCRETE CLOSURE WALL

AND REPAIR SINKHOLES/ VOIDS IN

DUMPSTER PAD AREA

REMOVE AND REPLACE PAVEMENT AT EDGE

OF PARKING LOT TO REPAIR SINKHOLES. SEE

TYPICAL PAVING DETAIL A8 ON SHEET C-502.

ASSUME UP TO 2 CY OF SUPPLEMENTAL FILL

WILL BE REQUIRED BELOW BASE COURSE.

16'

REMOVE AND REPLACE EXISTING FENCE

ALONG NORTH QUAY WALL APPROX. 220 LF)

0+00 0+20 0+40 0+60 0+80 1+00 1+20 1+40 1+60 1+63

REMOVE EXISTING LOOSE BLOCKS AND

PROVIDE CLASS VII RIPRAP TO CREATE

INTERIM BERM FROM STA 2+30 TO STA 3+40

(APPROX. 700 CY)FILL MISSING BOTTOM COURSE

OF WALL WITH REINFORCED

CONCRETE (APPROX. 10 CY)

BID OPTION 1: PROVIDE ADDITIONAL

CLASS VII RIPRAP REVETMENT ALONG

UNPROTECTED SLOPE. LIMITS SHOWN

ARE APPROXIMATE. REVETMENT TO

EXTEND WEST UNTIL TOP OF

REVETMENT (AT EL. +15.0') MEETS

EXISTING GRADE (APPROX. 150 CY)

RESET APPROX. 2 DISPLACED WALL

BLOCKS AT STA 2+40 (APPROX.10 LF)

EXCAVATE AND BACKFILL SINKHOLES

BEHIND QUAYWALL (APPROX. 60 CY)

BOTTOM TWO COURSES OF EXISTING BLOCK

WALL TO REMAIN IN PLACE AND DOWELED INTO

UNDERLYING HARDPAN/LEDGE

REMOVE EXISTING REMNANT BLOCKS FROM FAILED

WALL (TYP, APPROX. 50 BLOCKS) AND USE WHERE

DESIGNATED FOR REUSE AS SHOWN. PLACE

SURPLUS BLOCKS IN DESIGNATED REMNANT

STONE STOCKPILE AREA.

53'-0"±

(SEE NOTE 3)

16'-5"±

(SEE NOTE 3)

20'

REMNANT STONE

STOCK PILE

REUSE EXISTING STONE

BLOCKS TO FORM STEPPED

SIDE SLOPE CONTAINMENT

FOR BERM (TYP)

0+00 0+20 0+40 0+60 0+80 1+00 1+20 1+40 1+60 1+80 2+00 2+20

2+40 2+60 2+80 3+00 3+20 3+40 3+60 3+80 4+00 4+12

DE

SI

GN

ED

B Y:

DE

SC

RI

PT

IO

N

M

AR

K

ED

IT

ED

B Y:

DA

TE

CH

EC

KE

D

BY

DR

AW

N

BY

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

SH

EE

T

OF

US

CG

P

RO

JE

CT

N

UM

BE

R

US

CG

F

IL

EN

AM

E

A/ E

CO

M

PA

NY

CO

NS

UL

TI

NG

A

/E

US

CG

P

RO

JE

CT

M

AN

AG

ER

A/

E

PR

OJ

EC

T

NO

SHEET ID

M

EA

SU

RE

M

EN

T

BA

R:

1"

HA

LF

S

IZ

E

1/ 2"

US

CG

D

RA

W

IN

G

SE

RI

ES

N

UM

BE

R

RE

PA

IR

W

AT

ER

FR

ON

T

- P

HA

SE

CG

S

TA

P

OR

TS

M

OU

TH

H

AR

BO

R

NE

W

C

AS

TL

E

NH

CI

VI

L

QU

AY

W

AL

L

RE

PA

IR

P

LA

N

BULKHEADS

AND RIP-RAP

C-102

P1

P1

2C

2.

dw g

US

CG

C

IV

IL

E

NG

IN

EE

RI

NG

U

NI

T

PR

OV

ID

EN

CE

KI

LV

ER

T

ST

, S

UI

TE

W

AR

W

IC

K, R I 0

DA

VI

D J.

AR

PI

N, P

.E

Z.

JE

NK

IN

S J.

DE

L

TU

FO

M .S

CH

M

ID

D.

O 'C

ON

NO

R

LL

OY

D-

CO

LL

IN

S

JV

BE

LL

AI

RE

, T

EX

AS

(8

) 4

-4

LC

JV

-1

IS

SU

ED

F

OR

B

ID

DI

NG

NO

V

US COAST GUARD

CIVIL ENGINEERING

NORTH QUAY WALL REPAIR

SOUTH QUAY WALL REPAIR

NOTES

1. THE EXISTING ELECTRICAL AND TELECOMMUNICATION UTILITIES LOCATED WITHIN THE LIMITS OF WORK SHALL BE TEMPORARILY SUPPORTED AND PROTECTED DURING THE WORK, OR REMOVED, SALVAGED, AND REINSTALLED. UTILITIES THAT ARE DAMAGED AS A RESULT OF THE WORK SHALL BE REPLACED BY THE

CONTRACTOR, AT NO ADDITIONAL COST TO THE GOVERNMENT.

2. REFER TO THE UTILITY NOTES ON SHEET G-002 AND THE PROJECT SPECIFICATIONS FOR UTILITY AND FUEL

LINE OUTAGE REQUIREMENTS.

3. THE EXCAVATION LIMITS SHOWN ARE APPROXIMATE. THE ACTUAL LIMITS OF EXCAVATION WILL BE BASED ON THE MEANS AND METHODS OF CONSTRUCTION DETERMINED BY THE CONTRACTOR, AS NECESSARY TO PERFORM THE SINKHOLE REPAIRS TO THE MINIMUM LIMITS REQUIRED, AND MAINTAIN A SAFE EXCAVATION

AND STABLE SLOPE.

C-502 A1

C-501 A1

C-501 A6

D1 C-503

AutoCAD SHX Text

SBL

AutoCAD SHX Text

WOOD PILING (TYP. OF AREA)

AutoCAD SHX Text

MULTI-MISSION BLDG

AutoCAD SHX Text C-302

AutoCAD SHX Text E1

AutoCAD SHX Text C-302

AutoCAD SHX Text E5

AutoCAD SHX Text

AutoCAD SHX Text 10'

AutoCAD SHX Text 20'

AutoCAD SHX Text 40'

AutoCAD SHX Text

PLAN

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

SCALE: 1"=20'

AutoCAD SHX Text

AutoCAD SHX Text 10'

AutoCAD SHX Text 20'

AutoCAD SHX Text 40'

AutoCAD SHX Text

PLAN

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

SCALE: 1"=20'

AutoCAD SHX Text C-301

AutoCAD SHX Text E5

AutoCAD SHX Text C-301

AutoCAD SHX Text A5

AutoCAD SHX Text C-301

AutoCAD SHX Text E1

AutoCAD SHX Text C-302

AutoCAD SHX Text A1

AutoCAD SHX Text C-302

AutoCAD SHX Text A5

AutoCAD SHX Text C-301

A1

0.

2.56%

2.99%

2.95% 5.12%

-7.47%

-5.12%

5.12% -11.75%

-694.05%

-557.45%

-44.66%

-53.33%

-25.75%

-29.21%

-45.04%

GEOTEXTILE FILTER FABRIC

(BELOW SUPPLEMENTAL RIP RAP)

EXISTING REVETMENT TO

REMAIN (BELOW MHW)

EXISTING ROCKFILLED

GABION BASKET TO REMAIN

EXISTING GRADE

EXISTING FENCE TO BE REMOVED

AND REPLACED WITH 8-FT HIGH

CHAIN LINK FENCE

MHW = 4.0'

MLW = -4.6'

ELECTRIC AND CABLE UTILITIES TO

REMAIN AND TO BE PROTECTED

DURING CONSTRUCTION, LOCATION

IS APPROXIMATE (SEE NOTE 2)

TOP OF REVETMENT EL. =11.0'

2' THICK CLASS III REVETMENT

SLOPE

APPROXIMATE EXISTING

SLOPE. EXCAVATE AS

NEEDED TO PLACE NEW

REVETMENT

0.

2.43% 2.38%

2.32% 3.04% 3.58% -0.72% 0.74% 0.43% -0.43%

-67.49%

-49.86%

-49.72%

-18.15%

-33.67%

-29.21%

-45.04%

-30.50%

0.

2.43% 2.38%

2.32% 3.04% 3.58% -0.72% 0.74% 0.43% -0.43%

-67.49%

-49.86%

-49.72%

-18.15%

-33.67%

-29.21%

-45.04%

-30.50%

REVETMENT TOE EL. =7.0'

GEOTEXTILE FILTER FABRIC (BELOW BEDDING

LAYER, IN BETWEEN TOP AND BOTTOM

LAYERS, WRAPPING UP TOE STONE, MIN. 18")

3.5' DIA (MIN) TOE

STONE

1' THICK BEDDING LAYER

1V:2H (MIN) 2' THICK CLASS

III REVETMENT SLOPE

EXISTING REVETMENT TO

REMAIN (BELOW MHW)

EXISTING GRADE EXISTING FENCE TO BE

REMOVED AND REPLACED WITH

8-FT HIGH CHAIN LINK FENCE

MHW = 4.0'

MLW = -4.6'

ELECTRIC AND CABLE

UTILITIES TO REMAIN AND TO

BE PROTECTED DURING

CONSTRUCTION, LOCATION IS

APPROXIMATE (SEE NOTE 2) TOP OF REVETMENT EL. =13.0'

APPROXIMATE EXISTING

SLOPE. EXCAVATE AS

NEEDED TO PLACE NEW

REVETMENT

EXTEND GEOTEXTILE TO GRADE

0.

4.99%

1.85% -2.36% -1.29%

4.76%

5.68% -16.28%13.09%8.11% 6.76% 6.73%

-6.73%

-9.49%

-34.86%

-35.36%-28.72%-58.88%-24.47%

-24.63%

-37.95%

-46.71%

-47.69%

-28.01%

0.

EXISTING FENCE TO BE

REMOVED AND REPLACED WITH

8-FT HIGH CHAIN LINK FENCE

EXISTING GRADE

GEOTEXTILE FILTER FABRIC (BELOW BEDDING

LAYER, IN BETWEEN TOP AND BOTTOM LAYERS,

WRAPPING UP TOE STONE, MIN. 18")

EXISTING REVETMENT

TO REMAIN (BELOW MHW)

3.5' DIA (MIN) TOE STONE

1V:2H (MIN) 2' THICK CLASS III

REVETMENT SLOPE2'-6"±

2 (MIN)

REVETMENT TOE EL. =7.0'

MHW = 4.0'

MLW = -4.6'

ELECTRIC AND CABLE UTILITIES TO

REMAIN AND TO BE PROTECTED

DURING CONSTRUCTION, LOCATION IS

APPROXIMATE (SEE NOTE 2)

1' THICK BEDDING LAYER

TOP OF REVETMENT EL. =13.0'

4.99%

1.85% -2.36% -1.29%

4.76%

5.68% -16.28%13.09%8.11% 6.76% 6.73%

-6.73%

-9.49%

-34.86%

-35.36%-28.72%-58.88%-24.47%

-24.63%

-37.95%

-46.71%

-47.69%

-28.01%

APPROXIMATE EXISTING SLOPE.

EXCAVATE AS NEEDED TO PLACE

NEW REVETMENT

REMOVE AND REPLACE

PAVEMENT TO REPAIR SINKHOLE

IN PARKING AREA (SEE NOTE 4)

EXTEND GEOTEXTILE TO GRADE

-9 .9

-8 .2

0.

1.60% 2.14% 5.72%

5.49%

-9.92%

9.92%

8.85%

-45.57%

-44.90%

-28.13%

-8.72%

-6.03%

-49.01%

-44.04%

-28.61%

-9 .9

-8 .2

0.

1.60% 2.14% 5.72%

5.49%

-9.92%

9.92%

8.85%

-45.57%

-44.90%

-28.13%

-8.72%

-6.03%

-49.01%

-44.04%

-28.61%

2'-6"±

EXISTING FENCE TO BE

REMOVED AND REPLACED WITH

8-FT HIGH CHAIN LINK FENCE

GEOTEXTILE FILTER FABRIC (BELOW BEDDING LAYER,

IN BETWEEN TOP AND BOTTOM LAYERS, WRAPPING

UP BACK OF TOE STONE, MIN. 18")

3.5' DIA (MIN) TOE

STONE

1' THICK BEDDING LAYER

1V:2H (MIN) 2' THICK

CLASS III REVETMENT

SLOPE

EXISTING REVETMENT TO

REMAIN (BELOW MHW)

EXISTING GRADE REVETMENT TOE EL. =7.0'

2 (MIN)

MHW = 4.0'

MLW = -4.6'

ELECTRIC AND CABLE UTILITIES TO

REMAIN AND TO BE PROTECTED

DURING CONSTRUCTION, LOCATION IS

APPROXIMATE (SEE NOTE 2)

TOP OF REVETMENT EL. =13.0'

APPROXIMATE EXISTING SLOPE.

EXCAVATE AS NEEDED TO PLACE

NEW REVETMENT

EXTEND GEOTEXTILE TO GRADE

DE

SI

GN

ED

B Y:

DE

SC

RI

PT

IO

N

M

AR

K

ED

IT

ED

B Y:

DA

TE

CH

EC

KE

D

BY

DR

AW

N

BY

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

SH

EE

T

OF

US

CG

P

RO

JE

CT

N

UM

BE

R

US

CG

F

IL

EN

AM

E

A/ E

CO

M

PA

NY

CO

NS

UL

TI

NG

A

/E

US

CG

P

RO

JE

CT

M

AN

AG

ER

A/

E

PR

OJ

EC

T

NO

SHEET ID

M

EA

SU

RE

M

EN

T

BA

R:

1"

HA

LF

S

IZ

E

1/ 2"

US

CG

D

RA

W

IN

G

SE

RI

ES

N

UM

BE

R

RE

PA

IR

W

AT

ER

FR

ON

T

- P

HA

SE

CG

S

TA

P

OR

TS

M

OU

TH

H

AR

BO

R

NE

W

C

AS

TL

E

NH

CI

VI

L

NO

RT

H

RI

P-

RA

P

RE

PA

IR

S

EC

TI

ON

S

BULKHEADS

AND RIP-RAP

C-301

P1

P1

2C

1.

dw g

US

CG

C

IV

IL

E

NG

IN

EE

RI

NG

U

NI

T

PR

OV

ID

EN

CE

KI

LV

ER

T

ST

, S

UI

TE

W

AR

W

IC

K, R I 0

DA

VI

D J.

AR

PI

N, P

.E

Z.

JE

NK

IN

S J.

DE

L

TU

FO

M .S

CH

M

ID

D.

O 'C

ON

NO

R

LL

OY

D-

CO

LL

IN

S

JV

BE

LL

AI

RE

, T

EX

AS

(8

) 4

-4

LC

JV

-1

IS

SU

ED

F

OR

B

ID

DI

NG

NO

V

US COAST GUARD

CIVIL ENGINEERING

RIP-RAP SECTION - STA 0+34E1

RIP-RAP SECTION - STA 0+85A1

RIP-RAP SECTION - STA 0+47E5

RIP-RAP SECTION - STA 1+29A5

NOTES

1. THE INTENT OF THE BEDDING LAYER AND RIPRAP SLOPE SHOWN IS TO IMPROVE PROTECTION AND STABILIZATION OF THE ERODED SHORELINE AREA, LOCATED ABOVE MEAN HIGH WATER. THE EXISTING SLOPE IN THIS AREA SHALL BE EXCAVATED AND PREPARED TO SET THE TOE STONES, BEDDING LAYER, AND RESTORED SLOPE PROTECTION AS SHOWN ON THE DRAWINGS. IN THE EVENT THAT LEDGE OUTCROPPINGS ARE PRESENT THAT INTERFERE WITH THE PROPOSED BEDDING AND RIPRAP LAYERS SHOWN, THE BEDDING LAYER THICKNESS MAY BE REDUCED, OR TERMINATED IN THE AREA OF INTERFERENCES, TO FACILITATE CONSTRUCTION AND MAINTAIN A CONSISTENT REVETMENT FACE. IF THE BEDDING LAYER IS TERMINATED AT THESE AREAS, THE GEOTEXTILE LAYERS FOR THE SURROUNDING BEDDING SHALL BE TURNED BACK A MINIMUM 18 INCHES TO PREVENT LOSS OF BEDDING MATERIAL.

2. THE EXISTING ELECTRICAL AND TELECOMMUNICATION UTILITIES LOCATED WITHIN THE LIMITS OF WORK SHALL BE TEMPORARILY SUPPORTED AND PROTECTED DURING THE WORK, OR REMOVED, SALVAGED, AND REINSTALLED. UTILITIES THAT ARE DAMAGED AS A RESULT OF THE WORK SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL COST TO THE GOVERNMENT.

3. EXISTING GRADE LINE IS SHOWN FOR REFERENCE. CONTRACTOR SHALL REMOVE EXISTING REVETMENT STONE, RUBBLE, VEGETATION, AND SOIL WITHIN THE LIMITS OF THE NEW REVETMENT AS NECESSARY TO COMPLETE THE WORK. EXISTING STONE MEETING THE GRADATION REQUIREMENTS MAY BE USED TO SUPPLEMENT THE NEW REVETMENT STONE. EXISTING STONES ALREADY ESTABLISHED IN THE INTENDED TOE STONE LOCATION, AND MEETING THE TOE STONE SIZE REQUIREMENTS, MAY REMAIN IN PLACE.

4. REMOVE EXISTING PAVEMENT AND EXISTING BASE COURSE IN THE LIMITS OF SINKHOLE REPAIRS TO A MINIMUM TOTAL DEPTH OF 10" BELOW TOP OF FINISH PAVEMENT.