Attachment 2 - Program Guide PG-18-15 - East Orange Design.pdf
PDF 599 KB Posted
- Attached to
- C1DA--Design Parking Garage (VA-21-00008299)
- Solicitation number
- 36C77621R0038
About this file
This is a presolicitation notice for an architect-engineering services contract to design a parking garage at the East Orange, New Jersey VA Medical Center. The Veterans Health Administration seeks to award a firm-fixed price contract for design and construction period services with an anticipated period of performance of 365 days from notice to award. The project budget is between $10-20 million. This is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses. Interested firms must submit Standard Form 330 statements of qualifications by February 16, 2021 including experience designing parking garages and similar projects, professional qualifications, past performance on government contracts, and knowledge of the project locality. A two-phase evaluation process will select a shortlist of at least three firms for discussions, then identify the highest rated firm to receive the solicitation for negotiations.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 3 - Design Schedule.pdf | ||
| Attachment 4 - Past Performance Questionnaire.docx | DOCX document | |
| Attachment 1 - Final SOW - East Orange - Parking Structure.pdf | ||
| 36C77621R0038.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Construct Parking Garage for NJHCS Project No. 561-240 VANJHCS, East Orange Campus East Orange, NJ 07018
Program Guide, PG-18-15, Volume C TIL Baseline: Nov 2008 VHA NJHCS Modification: October 2020
Department of Veterans Affairs
VA Medical Center Projects
A/E Submission Instructions for Minor and NRM Construction Program:
• Schematics
• Design Development
• Construction Documents
Program Guide, PG-18-15, Volume C Page i TIL Baseline: May 2006 VHA NJHCS Modification: October 2020
Department of Veterans Affairs Washington, DC 20420
FOREWORD
This document states the minimum requirements for each submission in the production of VA Schematics, Design Development, and Construction Documents for Minor and NRM Construction Program for Medical Center Projects. It will give VA reviewers and the A/E a clear understanding of what is required of the A/E at each stage of design.
This document does not relieve the A/E firms of their professional responsibility to produce a correct, complete, and fully coordinated set of construction documents.
Lloyd H. Siegel William W. Graham Director, Facilities Quality Office (Acting) Director, Engineering Management and Field Support Office
Program Guide, PG-18-15, Volume C Page ii
A/E SUBMISSION INSTRUCTIONS FOR
MINOR AND NRM CONSTRUCTION PROGRAM
MEDICAL CENTER PROJECTS
Table-of-Contents
I. GENERAL
A. INTRODUCTION
B. A/E RESPONSIBILITIES
C. SUBMISSION POLICY
D. QUALITY ASSURANCE/QUALITY CONTROL
E. ADDITIONAL SERVICES
F. CRITICAL PATH METHOD
II. SUBMISSIONS
A. SITE DEVELOPMENT
B. ARCHITECTURAL
C. FIRE PROTECTION
D. INTERIOR DESIGN
E. STRUCTURAL
F. PLUMBING
G. SANITARY
H. HVAC
I. ELECTRICAL
J. EQUIPMENT
K. STEAM GENERATION
L. STEAM DISTRIBUTION (OUTSIDE)
M. SOLID WASTE DISPOSAL SYSTEM (INCLUDING INCINERATION)
N. AUTOMATIC TRANSPORT
O. ASBESTOS ABATEMENT
P. SPACE PLANNING
Q. CRITICAL PATH METHOD (CPM)
Program Guide, PG-18-15, Volume C Page iii
Table of Contents (Cont.)
R. ESTIMATING
S. SPECIFICATIONS
T. FINAL BID DOCUMENTS
III. DISTRIBUTION OF A/E MATERIAL
A. SYMBOL IDENTIFICATION OF CONTRACT DRAWINGS
B. GENERAL NOTES
Program Guide, PG-18-15, Volume C 1
A/E SUBMISSION INSTRUCTIONS FOR
MINOR AND NRM CONSTRUCTION PROGRAM
MEDICAL CENTER PROJECTS
I. GENERAL
A. INTRODUCTION
1. This document contains information and minimal submission requirements for contract documents specified in the A/E contract.
2. The Department of Veterans Affairs (VA) may contract with an
Architect/Engineer (A/E) for any portion of a design: Schematics, Design Development, Construction Documents, or a combination of these.
a. For projects where the VA is contracting for Schematics Documents only, Schematics and Design Development Documents only, or Schematics, Design Development, and Construction Documents, the VA will provide the Design Program (if available), Facility Development Plans (if available), and VA design standards to accompany the Scope of Work for the project.
b. For projects where the VA is contracting for Design Development and
Construction Documents only, the VA will provide the Schematics Plans and VA design standards to accompany the Scope of Work for the project.
c. For projects where the VA is contracting for Construction Documents only, the VA will provide the Design Development Plans and VA design standards to accompany the Scope of Work for the project.
3. Coordinate all activities with the VA Medical Center (VAMC). Hold informal meetings (upon mutual consent of the VA and the A/E) at the VAMC to discuss the design and related issues. Continue to expand contacts by telephone, rough sketch studies and other means of communication with the purpose of finalizing a general design approach to be followed.
4. Final approved Schematic documents shall be the basis for the development of the Design Development phase. Likewise, final approved Design Development documents shall be the basis for the development of the Construction Documents phase. The VAMC must approve any changes from each set of documents before the A/E proceeds to the next phase.
Program Guide, PG-18-15, Volume C 2
5. VA will review all submittals for functional and aesthetic relationships.
However, no further functional decisions are anticipated after the Design Development phase.
6. Provide a design narrative/analysis for each technical discipline (e.g., architectural, mechanical, fire protection, etc.) which describes the intent of each discipline with schematic and/or design development submission.
7. Provide computations and sizing calculations for electrical, mechanical (HVAC, plumbing, and steam), sanitary, structural and fire protection designs.
For computerized calculations, submit complete and clear documentation of computer programs, interpretation of input/output, and description of program procedures.
8. Provide individually packaged drawings for each submission to each unit specified in the "Distribution of A/E Materials" section.
9. Submit a complete set of final approved drawings incorporating all revisions, within 30 days after completion of the Schematics and Design Development stages.
10. At each review stage, the VA’s technical reviewer, a value-engineering consultant, or a construction manager will perform a value engineering review.
11. Submit final drawings (Bid Documents) in CD disks to be used with the AutoCAD version at the VAMC. Submit instructions on the use of the disks along with a complete listing of all layers that are used.
B. A/E RESPONSIBILITIES:
1. Contract documents shall meet or exceed the requirements of this document.
2. The A/E is responsible for producing a complete set of drawings, design narrative/analysis, calculations, sample boards, and specifications in accordance with professional standard practices and VA criteria. Each A/E discipline shall receive a copy of their respective VA design manuals, standard details, construction standards, and VA National CAD Standard Application Guide. The AE is responsible for obtaining the NCS.
3. A/E shall conduct coordination meetings between A/E technical disciplines before submitting material for each VA review and provide minutes of the meetings to VAMC.
4. A/E shall adhere to the approved Memorandum of Agreement (MOA).
Program Guide, PG-18-15, Volume C 3
5. A/E shall provide a checklist of all submittals, certifications, tests, and inspections required per drawing and specification section.
6. In addition, the A/E shall conduct interim fire protection installation inspections and witness final fire protection equipment testing.
7. As part of the Construction Documents and Bid Documents submissions, the A/E shall provide a “End of Construction Deliverables” list of information, products or services that are owed to the Government during the project closeout phase. This list shall also provide a reference to the drawings and specifications (if any) where these deliverables are identified. Deliverables include:
a) Spare parts
b) Training
c) Operation & maintenance manuals
d) Extended warranties
e) Other ‘end of construction’ deliverables
C. SUBMISSION POLICY:
1. There is a Schematic submission, a Design Development (DD**) submission, and a Construction Document (CD***) submission indicated in this guide. The VAMC may alter the submission requirements depending upon the complexity of the project by adding or deleting certain reviews. Where additional reviews might be required, the VAMC will issue, at their discretion, a detailed “Statement of Task” or supplemental instructions to the A/E, which would be provided at the time of solicitation for a fee proposal.
2. At each submission, the A/E shall date all material and present the designs on VA standard size drawings that are appropriately labeled, "SCHEMATIC SUBMISSION", “DESIGN DEVELOPMENT SUBMISSION”, OR
“CONSTRUCTION DOCUMENT SUBMISSION”, in large block letters above or beside the VA standard drawing title block. In each submission, the A/E shall incorporate the corrections, adjustments, and changes made by VA at the previous review.
3. Schematic Design (SD) 35% The Consultant shall assess existing systems for adequacy and incorporate Medical Center comments for their improvement. Consultant shall conduct field investigation as necessary to confirm routing of existing utilities and constructability of the concepts. The goal of the schematic design is to obtain Medical Center approval of a basis of design for the project and finalize, or “freeze” critical design parameters as defined in Part II of this document.
Program Guide, PG-18-15, Volume C 4
Schematic Design shall be considered fully complete when it aligns with the requirements listed in Part II of this document.
4. Design Development (DD) 65%
The Consultant shall use the fully complete Schematic Design documents and add detailed design information. The detailed designs contain the mechanical, electrical, plumbing, structural, and architectural details which typically identify design elements such as material types and location of windows and doors.
Design Development shall be considered fully complete when it aligns with the requirements listed in Part II of this document.
5. Construction Documents (CD) 95%
The Consultant shall use the fully complete Design Development documents and add construction details such as specifications, details, and materials.
Construction Documentation shall be considered fully complete when it aligns with the requirements listed in Part II of this document.
6. Bid Documents (BD) 100%
a) The Consultant shall use the fully complete Construction Documents and make any final changes required. These Document shall be stamped and signed by the registered architect and /or engineer and shall serve as the bid documents for the construction phase.
7. Submissions shall be delivered in hard copy and “soft copy” (i.e.
electronic). Electronic submissions shall meet the following requirements:
a) Drawings:
File Type Schematics DD CD BD Record
Portable Document Format (*.PDF) ✓ ✓ ✓ ✓ ✓
AutoCAD (*.DWG, *.DXF) ✓ ✓ ✓
1) Portable Document Format (*.PDF) drawings received as part of the Bid Documents submission shall be stamped and certified by a Registered Architect, Licensed Professional Engineer, or Licensed Surveyor as appropriate.
b) Specifications:
File Type Schematics DD CD BD Record
Microsoft Word (*.DOCX) ✓ ✓ ✓ ✓
Portable Document Format (*.PDF) ✓ ✓
1) Microsoft Word (*.DOCX) specifications shall be edited using Microsoft Word
Track Changes feature, shall be submitted as individual files, and shall use the same formatting throughout.
Program Guide, PG-18-15, Volume C 5
2) Portable Document Format (*.PDF) specifications shall be generated from the Microsoft Word files with Track Changes display set on “Final” or “No Markup”, shall be submitted as individual files, and shall be submitted as a single combined PDF document that is fully bookmarked and hyperlinked.
c) Schedules (Design and Construction):
File Type Schematics DD CD BD Record
Microsoft Project (*.MPP) ✓ ✓ ✓ ✓
Portable Document Format (*.PDF) ✓ ✓ ✓ ✓
1) The Design Schedule shall be provided as part of the Fee Proposal.
Once the Fee Proposal is accepted and a Notice of Award is issued, the proposed schedule shall be baselined. All future design schedule updates provided as part of the contract process shall be provided using
Microsoft Projects tracking features with the critical path displayed. The project’s design schedule shall not be re-baselined without approval by the COR.
2) The Construction Schedule shall be provided as part of the different design submissions to project estimated construction duration and document the key dependencies between any identified phases.
d) Submittal Log
File Type Schematics DD CD BD Record
Microsoft Excel (*.XLSX) ✓ ✓ ✓
Portable Document Format (*.PDF) ✓ ✓ ✓
e) All other unspecified design documents must be provided in in a
Microsoft Office compatible format (*.DOC, *.DOCX, *.PPT, *.PPTX, *.XLS, *.XLSX) or Portable Document Format (*.PDF).
D. QUALITY ASSURANCE/QUALITY CONTROL (QA/QC):
In an effort to reduce construction change orders due to design errors and omissions, the Office of Facilities Management has initiated a Quality Assurance/Quality Control program. The A/E shall develop, execute, and demonstrate that the project plans and specifications have gone through a rigorous review and coordination effort. The requirements are as follows:
Program Guide, PG-18-15, Volume C 6
1. Fee Proposal: Provide an outline of the actions that your firm will take during the design process along with an associated fee.
2. Two Weeks after Receipt of the Notice To Award: Submit a detailed QA/QC Plan describing each step that will be taken during the development of the various phases of design. Each step should have an appropriate space where a senior member of the firm can initial and date when the action has been completed.
3. Submissions (35%, 65%, 95%, 100%): Submit the completed QA/QC Plan along with the latest marked-up documents (plans, specifications, etc.)
necessary to ensure that a thorough review and coordination have been completed.
E. ADDITIONAL SERVICES:
If additional services (i.e. surveys, soil borings, asbestos surveys, water flow testing, or lead surveys), are necessary to be performed by consultants, submit criteria for the work to be performed to the VAMC Contracting Officer as soon as possible. Upon approval of the criteria, submit proposals and qualifications of at least three firms being considered for the work in accordance with the contract procedures (CP1) of the contract, together with a proposal from the recommended firm and a brief justification for its selection, for VA approval. A/E should submit survey information for the Schematic Review.
F. CRITICAL PATH METHOD PHASING MEETINGS
A. If required and prior to submission of Schematic material, the A/E shall meet with the VAMC’s Project Manager to discuss and outline phasing requirements for the project. These phasing requirements shall describe the general sequence of the project work, estimated project duration, and what
Government constraints will exist that will influence the Contractor's approach to the construction project. The A/E shall be responsible for recording the phasing requirements.
B. Submit a phasing narrative and phasing plans (on reduced size plans) within two weeks after each phasing meeting to the VAMC Project Manager. VA will review these submission(s) and return comments to the A/E within two weeks of receipt. The A/E will then use this information in preparing their schematic, design development, and construction document submissions.
Program Guide, PG-18-15, Volume C 7
II. SUBMISSIONS
A. SITE DEVELOPMENT: Submit the following:
Site Development: Schematics* DD** CD***
Narrative ✓
Analysis of site ✓
Circulation study ✓
Phasing analysis ✓
Parking analysis ✓
Development concept showing proposed buildings and structures
Landscape drawings with plant groupings
Topographic, utility, and landscape survey
Demolition plan ✓ ✓ ✓
Layout plan showing location of:
• Building and structures ✓ ✓ ✓
• Roads ✓ ✓ ✓
• Fire Access ✓ ✓
• Parking ✓ ✓ ✓
• Accessible spaces ✓ ✓
• Van spaces ✓ ✓
• Mechanical and electrical equipment on grade
• Future expansion ✓
• Off-site roads ✓ ✓ ✓
• Off-site utilities ✓ ✓ ✓
• Service area(s) ✓ ✓
• Entrances and exits ✓ ✓
• Walks ✓ ✓
• Inlets ✓ ✓
• Contractor's staging area ✓ ✓
• Vertical and horizontal road alignment
• Paving joint patterns ✓ ✓
Grading plan showing:
• Existing contours ✓ ✓
• Proposed contours ✓ ✓
Program Guide, PG-18-15, Volume C 8
Site Development: Schematics* DD** CD***
• Spot elevations at structure corners, entrances, equipment pads, etc.
• First floor elevations ✓ ✓
• Rim and invert elevations on storm drainage fixtures
• Erosion and sediment control ✓ ✓
Rock excavation (quantity) ✓ ✓
Planting plan showing:
• List of plant material ✓ ✓ ✓
• Limits of irrigation ✓ ✓ ✓
Site details ✓ ✓
Landscape details ✓ ✓
Signage plan and schedule ✓ ✓
Specifications ✓ ✓
* Submit site and landscape plans at an appropriate scale to show all work involved.
** Submit site and landscape plans at same scale as topographic/utility survey incorporating all of the revisions required by comments from schematics.
*** Submit fully dimensioned, complete, and coordinated site and landscape plans incorporating all revisions required by comments from the design development phase.
Program Guide, PG-18-15, Volume C 9
B. ARCHITECTURAL: Submit or show the following:
Architectural: Schematics* DD** CD***
Location of:
• Rooms1 ✓ ✓ ✓
• Doors2 ✓ ✓ ✓
• Corridor(s)3 ✓ ✓ ✓
• Basic column grid/sizes ✓ ✓ ✓
• Expansion and seismic joints ✓ ✓ ✓
• Electrical closets ✓ ✓ ✓
• Equipment rooms ✓ ✓ ✓
• Signal and telephone closets ✓ ✓ ✓
• Mechanical shafts and space ✓ ✓ ✓
• Stair(s) ✓ ✓
• Ramp(s) ✓ ✓
• Elevator(s) ✓ ✓ ✓
• Automatic Conveyances ✓ ✓ ✓
Floor Plans/Drawings:
• All floors (new and renovated) ✓ ✓ ✓
• Penthouse ✓ ✓ ✓
• Roof plan ✓ ✓ ✓
• Pipe basement ✓ ✓ ✓
• Pipe tunnel ✓ ✓
• Reflected ceiling4 ✓ ✓
• Equipment floor plans 1:50 (1/4 inch) scale5
• Demolition plans6 ✓ ✓
Room names and numbers7 ✓ ✓
Program net/designed net ✓ ✓ ✓
Exterior dimensions/total building gross area
Size and shape of all departmental functions and services9
Exterior building elevations10 ✓ ✓ ✓
Finish floor elevations11 ✓ ✓ ✓
Door locations, sizes, and swings ✓ ✓
Wall thickness and chase walls ✓ ✓
Handrail location/dimensions ✓ ✓
Fixed equipment ✓ ✓
Equipment elevations and details ✓
Plumbing fixtures ✓ ✓
Program Guide, PG-18-15, Volume C 10
Architectural: Schematics* DD** CD***
Wheelchair accessible facilities ✓ ✓
Wall sections12 ✓ ✓
Building sections13 ✓ ✓
Finish grades at corners, entrances, exits, platforms and ramps
Fire and smoke rated partitions14 ✓ ✓ ✓
Lead-lined and radio-frequency-shielded partitions14
Fire extinguisher cabinets14 ✓ ✓
Spray-on fire proofing (see fire protection)
Construction details15 ✓ ✓
Drafting symbols, abbreviations, and general notes
Door, window, and louver schedules ✓
Interior details, elevations, sections ✓
Finish schedule16 ✓ ✓
Graphics and signage17 ✓
Color rendering ✓
Specifications ✓ ✓
Lead abatement18 ✓
Lead abatement specification19 ✓
* Submit, as a minimum, a single line layout for at a scale not less than 1:100 (1/8 inch). A scale of 1:200 (1/16 inch) is acceptable for architectural floor layout if an entire floor cannot be shown on one sheet. Submit a complete double line layout of areas of critical importance, at a scale of 1:50
(1/4 inch) including equipment.
** Submit minimum 1:100 (1/8 inch) scale floor plans, new and renovated, incorporating all of the revisions required by comments from schematics.
*** Submit fully dimensioned, complete, and coordinated 1:100 (1/8 inch) scale floor plans, incorporating all revisions required by comments from the design development phase.
B. NOTES:
1. Use lines between spaces to indicate the centerline of the partition (for schematics only).
2. Indicate doors with a slash mark.
Program Guide, PG-18-15, Volume C 11
3. Along the corridor, the line shall represent the corridor side of the partition.
4. Indicate ceiling mounted equipment, lighting fixtures, air diffusers, registers, tracks, and other significant elements.
5. Identify all equipment for each room. Indicate and coordinate all equipment with the Equipment Guide List (Program Guide 7610) and Activated Equipment
List. Use VA standard symbols and notation to distinguish between contractor-furnished and installed (CC), VA-furnished contractor-installed (VC), VA-furnished and installed (VV), VA-furnished with construction funds [VC(CF) and VV(CF)], and relocated (R) equipment. Equipment floor plans are not required for the offices, consultation rooms, classrooms, conference rooms, and waiting rooms within the above departments. Draw equipment details which are necessary for major decisions, though complete detailing is not required for this submittal.
6. Indicate existing finish schedule and notes on plan.
7. Label as required for schematic drawings. Coordinate new room numbering with medical center.
8. Use the same names on drawings as those used in the space program.
Provide area figures in fractional form, e.g., 400/390. Indicate space provided, but not called for in the space program, as: -/390.
9. Label each service or activity listed in the Project Scope Data of the Design Program and indicate boundaries with a distinctive line. Include the activity code number (see Handbook 7610).
10. If the project requires exterior work, show all facades indicating massing, proposed fenestration and the building relationship to adjacent structures and the finish grade. Show all significant building materials, including their colors, any proposed roof top mechanical equipment, architectural screens, skylights, and stacks on the elevation drawings. If building is designed for future expansion (vertical and/or horizontal), delineate elevations with and without the future expansion. If project is an addition, show elevations of the existing building in sufficient detail to illustrate the relationship between the new and existing in terms of scale, material, and detail.
11. Define the relationship of the finish ground floor to finish grade at major entrances and docks.
12. Indicate construction including fire resistance rating, building materials and systems, and proposed sill and head heights of openings. Indicate both new and renovated areas on form provided by VA.
Program Guide, PG-18-15, Volume C 12
13. Define building configuration. Draw sections at the same scale as floor plans, normally 1:100 (1/8 inch). If the building abuts an existing structure, indicate in the section how the new floor elevations align with existing.
14. Identify psychiatric areas where special considerations are required to ensure the safety of patients (e.g. hard ceilings, safety glazing, etc.).
15. Indicate new building components and systems, such as window design, roofing system, special entryways, building "skin", and any special architectural elements for the project. Complete detailing of miscellaneous items is not required for this submission.
16. Indicate all building systems, materials, and future expansion, if applicable.
17. Submit a drawing for all which is part of the construction contract.
18. Provide square meters (feet) of lead paint and x-ray shielding to be removed.
19. Format provided in SPECIFICATIONS. If there is no VA master specification, develop contract specification that is in compliance with regulations of the Environmental Protection Agency.
Program Guide, PG-18-15, Volume C 13
C. FIRE PROTECTION: Submit the following:
Fire Protection: Schematics* DD** CD***
Fire protection narrative:1
• Fire and smoke separation ✓
• Fire sprinkler/standpipe system ✓
• Size of fire pumps ✓
• Water supply available/max.
demand
• Water flow testing results ✓
• Fire alarm systems2 ✓
Existing to be modernized ✓
Base loop system for interface of new construction
• Kitchen extinguishing systems ✓
• Size of air handling unit ✓
• Exit paths from each zone ✓
• Distances to stairs ✓
• Occupancy of each area ✓
• Exit calculations for each floor ✓
• Smoke control features ✓
Floor Plans/Drawings:3 & 4
• Sprinkler zones ✓
• Fire alarm zones ✓
• Smoke zones ✓
• Building water supply ✓
• Interior sprinkler supply lines ✓
• Standpipes ✓
• Fire extinguisher cabinets ✓ ✓ ✓
• Fireproofing of structural members ✓
• Sprinkler/standpipe riser supply piping
• Termination of sprinkler main and inspector test drains
• Sprinkler alarm valves ✓ ✓
• Waterflow and tamper switches ✓ ✓
• Sprinkler system fire department connections
• Sprinkler design hazards per
NFPA 13
• Exit signs and emergency lighting ✓ ✓
Program Guide, PG-18-15, Volume C 14
• Occupied areas not protected by automatic sprinklers
Calculations ✓ ✓ ✓
Estimated capacities for proposed air handling units in cubic meters (cubic feet) per minute
Location of:
• Fire alarm system ✓ ✓
• Annunciator panels ✓ ✓
• Pull stations ✓ ✓
• Flow switches ✓ ✓
• Audio-visual devices ✓ ✓
• Smoke detectors ✓ ✓
• Duct smoke detectors ✓ ✓
• Smoke dampers ✓ ✓
• Fire dampers ✓ ✓
• Fire alarm risers5 ✓ ✓
• Exit signs ✓ ✓
• Emergency lighting ✓ ✓
• Fire sprinklers ✓ ✓
• Standpipes ✓ ✓
• Fire hydrants ✓ ✓
• Fire pumps ✓ ✓
• Post indicator valves ✓ ✓
• Sectional valves ✓ ✓
• Fire extinguisher cabinets ✓ ✓
• Electromagnetic door hold open devices
Wall sections indicating fire resistive ratings
Staff sleeping rooms ✓ ✓
Excavation plan signage ✓ ✓
Door and window schedule with fire rating or fire rated glazing
Zoning of each fire alarm initiating device
Details:
• Fire pump system (capacity and pressure)
Program Guide, PG-18-15, Volume C 15
• Elevation and isometric view of fire pump
• Stairwell sign ✓
• Annunciator panel ✓
Interconnection of fire alarm system with:
• Smoke dampers ✓
• Air handlers ✓
• Elevator controls ✓
• Kitchen fire extinguishing and fire pump system
• HVAC system with smoke duct detectors
Single line riser diagram for fire alarm system
Height/configuration of storage racks and shelving
Specifications ✓
1:100 (1/8 inch). Submit a complete double line layout of areas of critical importance, at a scale of 1:50 (1/4 inch) including equipment.
** Submit minimum 1:100 (1/8 inch) scale floor plans, new and renovated, incorporating all of the revisions required by comments from schematics.
*** Submit fully dimensioned, complete, and coordinated 1:100 (1/8 inch)
Program Guide, PG-18-15, Volume C 16
C. NOTES:
1. Indicate NFPA 220 and UBC fire resistive rating of the building, NFPA 101 occupancy type, and fire protection code analysis to access compliance with
NFPA 101.
2. Determine type, features, age, reliability, compliance with present day codes, capacity, zoning, supervision, control panel and power supplies, initiating devices and circuits, and auxiliary functions for existing fire alarm system. Indicate manufacturer, model number, voltage, and wiring style of existing alarm systems and devices. Provide recommendations for the proposed fire alarm work.
3. Provide information to meet JCAHO requirements; e.g. location of all fire rated barriers, smoke barriers, exit signs, fire extinguishers, manual pull stations, smoke detectors, and sprinkler flow switches. Show all interim life safety measures such as temporary systems Fire Alarm, Sprinkler, and Smoke.
4. At DD Submission, add room names, room numbers, door locations and swings, smoke and fire rated partitions, sprinkler/standpipe risers to floor plans.
Identify psychiatric areas on drawings so areas for institutional type heads are identified. Add location of all valves (post indicator, sectional) and backflow preventer if provided.
5. Show new equipment and/or the necessary changes involved if modification to the existing system is required. Include any recommendations where certain requirements of VA criteria might be waived, in order to allow the existing equipment to be reused.
Program Guide, PG-18-15, Volume C 17
D. INTERIOR DESIGN: Submit the following:
Interior Design: Schematics* DD** CD***
Written interior design concept1 ✓
Illustrate overall design solution2 ✓
Material and finish samples ✓
Sketches ✓
Design solution for interior spaces:
• Perspectives ✓ ✓
• Plans ✓ ✓
• Details ✓ ✓
• Elevations ✓ ✓
• Sections ✓ ✓
• Wayfinding ✓ ✓
• Floor patterns ✓ ✓
• Wall patterns ✓ ✓
• Lighting ✓ ✓
• Signage ✓ ✓
• Handrails ✓ ✓
• Bumper guards ✓ ✓
Specification section 09050 ✓ ✓
Finish schedule ✓ ✓
Exterior colors and materials ✓ ✓
Sample boards for interior and exterior materials, products, and finishes
Edited carpet and wallcovering specifications
Keyed Finnish plans ✓
Interior design details, elevations, and sections importance, at a scale of 1:50 (1/4 inch) including equipment.
Program Guide, PG-18-15, Volume C 18
D. NOTES:
1. Provide a document of data collected in interior design programming.
Include collection and analysis of data from the VAMC project coordinator and interior designer. Data includes, but is not limited to the following: existing interior and exterior design and materials, light, safety, patient profile, customer’s “vision” or desired image, public vs. private spaces, complete signage package, goals of customer, relationship to existing facilities, future expansion/renovation plans, regional influences, etc.
2. Discuss and illustrate the overall design solution for the primary areas of the project using marked-up floor plans, loose sketches, and material and finish samples. Use broad categories of materials, finishes, color palettes, patterns, textures, and scales. Separately group all major neutral background materials and finishes that will be used and discuss how they will be integrated with all other materials and finishes on the project. Include all primary and secondary corridors, typical patient and toilet rooms, lobbies, atriums, eating spaces, chapels, waiting rooms, and exam rooms. Show the relationship among departments and functions, and between public and private spaces.
Program Guide, PG-18-15, Volume C 19
E. STRUCTURAL: Submit the following:
Structural: Schematics* DD** CD***
Three alternative structural systems for typical bays1
Supporting calculations2 ✓ ✓ ✓
Cost estimates for each system3 ✓
Recommend preferred system ✓
Column locations ✓
Shear load resisting elements4 ✓
Boring location plan5 ✓
Structural plans6 ✓ ✓
Sections ✓ ✓
Details ✓ ✓
Size/location of:
• Columns ✓ ✓
• Beams ✓ ✓
Lateral load resisting elements ✓ ✓
Load bearing walls ✓ ✓
Slabs ✓ ✓
Foundations ✓ ✓
Elevations ✓
Schedules ✓
General notes ✓
Boring logs ✓
Subsurface investigation report ✓
Estimated quantity of rock ✓
Specifications ✓
* Submit, as a minimum, a single line layout for at a scale not less than 1:100 (1/8 inch). Submit a complete double line layout of areas of critical importance, at a scale of 1:50 (1/4 inch) including equipment.
Program Guide, PG-18-15, Volume C 20
E. NOTES:
1. When only one structural system is possible due to other project requirements, include an explanatory statement and submit only that structural system.
2. Include vertical and lateral load design for CD submission.
3. Include foundation and fireproofing.
4. Indicate existing utilities and structures within, adjacent, or contiguous to the new construction.
5. Upon approval of the subsurface investigation criteria, submit qualifications of at least three consultants being considered for the work together with the proposal of the consultant recommended as most qualified.
6. If there is only a CD submission, provide a Structural Engineering Analysis Submission within six weeks from the Notice of Award including sketches, calculations, and cost estimates of three alternative structural systems for typical bays, boring location plan for subsurface investigation, and consultant qualifications. For vertical expansion projects, analyze existing structure for structural feasibility.
Program Guide, PG-18-15, Volume C 21
F. PLUMBING: Submit the following:
Plumbing: Schematics* DD** CD***
Narrative:
• Existing plumbing systems to be used and necessary modifications
• New plumbing systems ✓ ✓ ✓
• New or modified water treatment ✓ ✓ ✓
Floor Plans/Drawings:
• Room names ✓ ✓ ✓
• Identify
Existing plumbing fixtures w/VA numbering system
New plumbing fixtures w/VA numbering system
Existing equipment ✓ ✓ ✓
New equipment ✓ ✓ ✓
New medical gas outlets ✓ ✓
New laboratory gas outlets ✓ ✓
Plumbing piping ✓ ✓ ✓
• Size of pipe ✓ ✓
• Equipment schedule ✓ ✓
• Fire & smoke partitions ✓ ✓ ✓
• Demolition plans ✓ ✓
• Riser diagrams ✓
• Legend, notes, and details ✓
Location and size of sprinkler riser, standpipes, and fire pumps (see fire protection)
Location of emergency eyewash and shower equipment
Calculations (equipment & piping) ✓ ✓
List of Required Contract
Specifications
Contract Specifications ✓
Program Guide, PG-18-15, Volume C 22
F. PLUMBING (cont.):
1:100 (1/8 inch).
incorporating all of the revisions required by comments from schematics phase.
design development phase. Submit a complete double line layout of areas of critical importance, at a scale of 1:50 (1/4 inch).
Program Guide, PG-18-15, Volume C 23
G. SANITARY: Submit the following:
Sanitary: Schematics* DD** CD***
Narrative:
• Existing sanitary systems:
underground water, sanitary sewers, storm sewers, & fuel gas with sources, disposal methods, storage pressures, condition, etc.
• New sanitary systems ✓ ✓ ✓
• Provide water analysis & expected yield if well required
• Circulation study to assess emergency vehicle access
Install test well, if well is required. ✓
Utility Plans/Drawings showing existing and new sanitary systems:
• Size of pipes ✓ ✓ ✓
• Invert elevations of sewers ✓ ✓ ✓
• Locate/size
Pumps ✓ ✓ ✓
Storage facilities ✓ ✓ ✓
Treatment equipment ✓ ✓ ✓
Fire hydrants ✓ ✓
Sectional and post indicator valves
Backflow preventer ✓ ✓
• Areas of new irrigation system ✓
• New irrigation system ✓
• Profiles of sanitary & storm sewers ✓
• Demolition Plans ✓ ✓
• Legend, notes, and details ✓
Point of connection to sprinkler system ✓ ✓ ✓
Calculations ✓ ✓
List of specifications ✓
Contract Specifications ✓
Program Guide, PG-18-15, Volume C 24
G. SANITARY (cont.):
* Submit utility drawings at same scale as provided for Site Development drawings.
** Submit utility drawings at same scale as provided for Site Development drawings, incorporating all of the revisions required by comments from the schematics phase.
*** Submit utility drawings at same scale as provided for Site Development drawings, incorporating all of the revisions required by comments from the design development phase. Submit legend, notes, and details at a scale not less than 1:100 (1/8 inch).
Program Guide, PG-18-15, Volume C 25
H. HVAC: Submit the following:
HVAC: Schematics* DD** CD***
Description of HVAC systems ✓
Equipment for each functional space ✓
Life cycle cost analysis1 ✓
Tentative location/sizes:
• Mechanical equipment room ✓
• Principal vertical shafts ✓
Block layout of equipment ✓
Louvers:2
• Outside air ✓ ✓ ✓
• Exhaust air ✓ ✓ ✓
• Relief air ✓ ✓ ✓
Engineering calculations3 ✓ ✓ ✓
Selection of HVAC equipment ✓ ✓
Catalog cuts of equipment ✓ ✓
Room by room heating and cooling loads
Zone by zone heating & cooling loads ✓ ✓
Building block heating & cooling loads ✓ ✓
Tabulation of steam consumption ✓ ✓
Psychometric chart for air handling unit ✓ ✓
Coil entering and leaving conditions ✓ ✓
Fan motor heat gains ✓ ✓
Consumption of humidification loads ✓ ✓
Sound/acoustic analysis ✓ ✓
Room-by-room air balance charts4 ✓ ✓
Chilled water plant:5
• Quantity and type of chillers ✓ ✓
• Capacity in tons of refrigeration ✓ ✓
• Electrical equipment ✓ ✓
Heating system:
• Total heating load ✓ ✓
• Domestic hot water load ✓ ✓
• Humidification load ✓ ✓
• Equipment steam demand ✓ ✓
• Zoning of heating system ✓ ✓
Program Guide, PG-18-15, Volume C 26
HVAC floor plan:6
• Main supply, return and exhaust ductwork
• Volume dampers ✓ ✓
• Fire and smoke partitions ✓ ✓
• Fire and smoke dampers ✓ ✓
• Smoke detectors ✓ ✓
• Automatic control dampers ✓ ✓
• Air quantities for each room ✓ ✓
• Air inlets/outlets ✓ ✓
• Rises and drops in ductwork ✓ ✓
• Expansion loops ✓ ✓
• Anchors ✓ ✓
• Vales ✓ ✓
• Drip assemblies ✓ ✓
• Balancing fittings ✓ ✓
Interconnection of HVAC equipment with fire protection equipment (see fire protection)
Plan/section of mechanical equipment rooms
Schematic flow and riser diagrams7 ✓ ✓
Schematic control diagrams8 ✓ ✓
HVAC demolition drawings ✓ ✓
Phasing plan ✓ ✓
Equipment schedule ✓ ✓
Seismic bracing ✓ ✓
VA symbols and abbreviation ✓ ✓
Selection of
• Pumps ✓
• Fans ✓
Sizing and selection of
• Expansion tanks ✓
• Steam to hot water convertor ✓
• Heat exchangers
Sound analysis ✓
Complete selection data ✓
Outside chilled water and condenser water distribution9
Standard detail drawings ✓
Program Guide, PG-18-15, Volume C 27
Automatic temperature control drawings10
HVAC specifications ✓
H. NOTES:
1. Provide specific design recommendations and full back-up data. Include the heating and cooling capacities of each functional area and the block cooling and heating loads for each new and/or existing building.
2. The locations of these louvers must not allow short circuiting of air from emergency generator exhaust or truck waiting and loading dock areas into air intake etc. Consider factors affecting louver location such as visibility, historical considerations, wind direction, nuisance and health hazard odors (from emergency generator or truck exhausts).
3. Include room-by-room, peak zone-by-zone, and building block heating and cooling loads. Provide a tabulation of steam consumption based on data from all sources. Show correlation between each HVAC zone boundary and architectural floor area correlation between the architectural room numbers and abbreviated/coded room numbers used with computer input data sheets.
4. Show supply, return, exhaust, make-up, and transfer quantities with intended pressure relationships, i.e. positive, negative, or zero with respect to adjoining spaces.
5. Provide pertinent data on accessories such as pumps and cooling tower etc.
Show the extent of the outside chilled water and condenser water piping. Clearly show how the piping will be laid in tunnels, trenches, or by direct burial.
6. Show ceiling clearances, at locations where ducts cross each other, by providing 1:50 (1/4 inch) scale local sections. Show all ductwork, and piping 150
Program Guide, PG-18-15, Volume C 28 mm (6 inch) and larger in double line. Show separate floor plans for air distribution and piping unless waived by VA. Show clearances required for access and maintenance with coil and tube pull.
7. Show typical air handling systems and all hydronic systems with existing capacities and new estimated loads. Verify actual operating conditions and capacities of HVAC systems prior to design.
8. Show control devices, such as, thermostats, humidistats, flow control valves, dampers, freezestats, operating and high limit sensors for all air systems and fluids, smoke dampers, duct detectors etc. Provide a written description of the sequence of operation on the floor plans. Detail the scope of work involved with the Central Engineering Center (ECC) and address if enough spare capacity is available or a new ECC is required. Show a point schedule for analog/digital input/output to be included in ECC.
9. Show pipe sizes and insulation with plans, profile, sections, details, and all accessories, such as, anchors, expansion loops/joints, valves, manholes, capped and flanged connections, interface between the new and existing work (if any).
Clearly indicate interferences (if any) with the existing utilities and/or landscape elements on outside piping layout drawings. Show rerouting any utilities, cuttings of roads, pavements, trees, etc., and the extent of new and demolition work.
Outside utility drawings shall be based on the study of the latest site drawings, discussions with engineering personnel, and actual site inspection of the existing utility.
10. Show all duct detectors, control valves/dampers static pressure sensors, differential pressure control assemblies, etc., whose actual physical location is critical for the intended sequence of operation on floor plans.
Program Guide, PG-18-15, Volume C 29
I. ELECTRICAL: Submit the following:
Electrical: Schematics* DD** CD***
Narratives:
• Design1 ✓
• Life cycle analysis for electrical systems
Location and size of:
• Electrical equipment2 ✓
• Electric closets3 ✓
• Telephone closets3 ✓
• Signal closets3 ✓
• Electrical distribution equipment
Drawings showing:
• Electrical plot plan of existing and proposed underground power (including manholes)
• Telephone systems ✓ ✓ ✓
• Signal inter-building systems ✓ ✓ ✓
• Proposed electrical system4 ✓ ✓ ✓
• Electric symbols ✓ ✓ ✓
• Lighting fixture schedule ✓ ✓ ✓
• Emergency Life Safety Equipment
(see fire protection)
• Symbols, note, abbreviations ✓ ✓
List of specialty areas ✓
Method of short-circuit calculations ✓
Method of voltage drop and demand calculations
Utility company correspondence ✓
Utility company requirements ✓ ✓
Load calculations for normal & emergency use
Drawings:
• Lighting layouts ✓ ✓
• Power layouts ✓ ✓
• Signal layouts ✓ ✓
• Specialty area layouts ✓ ✓
• Demolition plans ✓ ✓
Riser diagrams ✓ ✓
Branch circuit wiring (typ.) ✓ ✓
Program Guide, PG-18-15, Volume C 30
Electrical: Schematics* DD** CD***
Location and size of:
• Primary distribution switchgear/switchboard
• Engine-generator sets ✓ ✓
• Substation/padmounted transformer ✓ ✓
• Manholes ✓ ✓
Location of smoke dampers and duct smoke detectors
Interconnection of electrical control equipment with HVAC equipment
Smoke partitions and fire alarm zones ✓ ✓ ✓
Fire alarm and signal riser diagrams
Calculations for emergency generator(s)
Phasing scheme ✓ ✓
Electrical details ✓ importance, at a scale of 1:50 (1/4 inch) including equipment.
** Submit minimum 1:100 (1/8 inch) scale floor plans, new and renovated, incorporating all of the revisions required by comments from schematics.
*** Submit fully dimensioned, complete, and coordinated 1:100 (1/8 inch)
Program Guide, PG-18-15, Volume C 31
I. NOTES:
1. Include basic assumptions, points of interconnection, impact of new construction to existing electrical distribution system, current demand loading
(high voltage switchgear and primary feeder), and projected load of new construction. Propose various feasible electrical systems for project and provide advantages/disadvantages.
2. Include means and clearances for installation, maintenance, and removal/replacement of equipment.
3. Electrical, signal and telephone closets must stack vertically.
4. Include high voltage and low voltage switchgear, transformers and low voltage main and/or distribution panels, branch panels and methods of feeding 277/480 volt and 120/208 volt normal and emergency panels.
J. EQUIPMENT: Submit the following:
Equipment: Schematics* DD** CD***
Equipment (on architectural drawing) ✓ ✓ ✓
Activation Equipment List (Excel format) importance, at a scale of 1:50 (1/4 inch) including equipment.
** Submit minimum 1:100 (1/8 inch) scale floor plans, new and renovated, incorporating all of the revisions required by comments from schematics.
*** Submit fully dimensioned, complete, and coordinated 1:100 (1/8 inch)
Program Guide, PG-18-15, Volume C 32
K. STEAM GENERATION: Submit the following:
Steam Generation: Schematics* DD** CD***
Report on new and existing steam loads1
Life-cycle cost analysis of steam supply alternatives
Analysis of alternate plant locations ✓
Life-cycle cost analysis for alternative types of equipment
Life-cycle cost analysis for heat recovery alternatives
Data on emissions regulations ✓
Data on methods of compliance ✓
Selection of major equipment ✓
Plot plan with new and existing plant locations
Fuel related storage and handling facilities
Alternate plan view layouts of new and existing plant
Plot plan of steam generating facility2 ✓ ✓
Catalog cuts on equipment from two manufacturers
Plans/sections/locations of:
• Equipment ✓ ✓
• Major piping ✓ ✓
• Pipe supports ✓ ✓
Demolition ✓ ✓
Schematic flow diagrams of all piping systems
Calculations:
• Equipment sizing ✓ ✓ ✓
• Major piping systems ✓ ✓
• Steam load ✓ ✓
• Control and regulating valve ✓ ✓
• Flowmeter systems ✓ ✓
• Steam trap ✓ ✓
• Heating and ventilating system ✓ ✓
• Steam piping ✓ ✓
Schedules ✓ ✓
Equipment lists ✓ ✓
Program Guide, PG-18-15, Volume C 33
Steam Generation: Schematics* DD** CD***
Verification of emission regulations ✓ ✓
List of standards and details ✓ importance, at a scale of 1:50 (1/4 inch) including equipment.
** Submit minimum 1:100 (1/8 inch) scale floor plans, new and renovated, incorporating all of the revisions required by comments from schematics.
*** Submit fully dimensioned, complete, and coordinated 1:100 (1/8 inch) scale floor plans, incorporating all revisions required by comments from the
K. NOTES:
1. Include maximum and minimum summer and winter demands and total annual production. Provide break-down of new steam loads into categories of end use such as building heating, humidification, reheat, domestic hot water, sterilization, line losses, kitchen, and laundry.
2. Show boilers, pumps, heat recovery devices, tanks, and emission control devices.
Program Guide, PG-18-15, Volume C 34
L. STEAM DISTRIBUTION (OUTSIDE): Submit the following:
Steam Distribution (Outside): Schematics* DD** CD***
Estimate steam and condensate loads ✓ ✓ ✓
Life-cycle cost analysis of steam distribution system
Calculations of pipe sizing ✓ ✓ ✓
Steam distribution plot plan ✓ ✓ ✓
Existing underground utilities
Soil conditions report ✓ ✓ ✓
Performance requirements for steam traps
Calculate pipe stress ✓ ✓
Select expansion facilities for piping ✓ ✓
Location of:
• Manholes ✓ ✓
• Pipe expansion devices ✓ ✓
Profile drawings including existing utilities
Plan views/sections/dimensions for major piping, pipe layout and pipe supports of:
• Manholes ✓ ✓
• Trenches ✓ ✓
• Tunnels ✓ ✓
Demolition Plans ✓ ✓
* Submit outside steam generation plans at an appropriate scale to show all work involved.
** Submit outside steam generation plans at same scale as topographic/utility survey incorporating all of the revisions required by comments from schematics.
*** Submit fully dimensioned, complete, and coordinated outside steam generation plans incorporating all revisions required by comments from the
Program Guide, PG-18-15, Volume C 35
M. SOLID WASTE DISPOSAL SYSTEM INCLUDING INCINERATION:
Submit the following:
Solid Waste Disposal System Including
Incineration:
Schematics* DD** CD***
Incineration report including:
1. amount and type of waste (new & existing)
2. emissions regulations and types of emissions controls required
3. life-cycle cost analysis on alternatives for waste disposal
4. calculations of equipment sizing and description of types of equipment
5. viable alternatives for waste disposal
Evaluation of capability of existing incinerator
Complete description of existing processing system
Tests to determine remaining service life and capacity of system
Plot plan with new plant location and location of existing plant
Plan view layout of new system or existing system showing new equipment location
Load calculations on amount and types of waste
Plot plan with location of new processing system
Plans/sections showing locations of:
• Equipment
• Major piping ✓ ✓
Demolition ✓ ✓
Catalog cuts (2 min.) of equipment selections
Emissions control devices ✓ ✓
Schedules ✓ ✓
Equipment lists ✓ ✓
List of standards to be furnished later ✓ ✓
Program Guide, PG-18-15, Volume C 36
Solid Waste Disposal System Including Incineration:
Schematics* DD** CD***
List of special details to be furnished later
Verification of applicable emissions regulations affecting design or operation
*** Submit fully dimensioned, complete, and coordinated 1:100 (1/8 inch)
Program Guide, PG-18-15, Volume C 37
N. AUTOMATIC TRANSPORT: Submit the following:
Automatic Transport: Schematics* DD* CD*
Automatic transport systems (ATS):
• Narrative w/ recommended improvements for exiting system
• Traffic study including existing and proposed ATS w/ alternate methods of distribution
Changes to existing systems (arch. dwgs.)
Hoistway (arch. dwg.) ✓ ✓
Machine room vents (arch. dwg.) ✓ ✓
Type of ventilation (mech. dwg.) ✓ ✓
Electrical requirements (elect. dwg.) ✓ ✓
Drawings:1, 2, & 3
• Automatic Transport Systems ✓ ✓
• Elevators ✓ ✓
• Dumbwaiters ✓ ✓
• Other ATS systems ✓ ✓
Sizes/dimensions/details:
• Hoistway enclosures ✓ ✓
• Pits ✓ ✓
• Pit ladders ✓ ✓
• Machine area ladder and railings ✓ ✓
• Entrances ✓ ✓
• Machine rooms ✓ ✓
Locations/dimensions:
• Elevator cars ✓ ✓
• Entrances ✓ ✓
• Counterweights ✓ ✓
• Trap doors ✓ ✓
Location of hoistway vents ✓ ✓
Location of steel hoisting beams ✓ ✓
Size of machine beams ✓ ✓
Size of end reactions ✓ ✓
Location/detail of machine beam pockets
Rail loadings ✓ ✓
Hydraulic elevator piston pit loads ✓ ✓
Program Guide, PG-18-15, Volume C 38
Automatic Transport: Schematics* DD* CD*
Details
• Hoistway entrances for elevators ✓ ✓
• Carlifts ✓ ✓
• Dumbwaiters ✓ ✓
• Trash chutes ✓ ✓
• Linen chutes ✓ ✓
• ETVS ✓ ✓
Elevator machine room equipment layout
Interface with automatic recall and shutdown (see fire protection)
N. NOTES:
1. Include tracking, piping, battery charging areas, blower rooms, queuing areas, cart holding areas, cart washer, central control area, and floor or wall recessed transport control units. Indicate architectural features in areas to be utilized for these systems. Indicate on architectural drawings all the major equipment located in machine rooms, secondary levels, pits, and the areas pertaining to ATS, AGVS and ETVS.
2. Indicate changes required on the architectural drawings where existing transport systems are retained and modified to serve new and existing areas.
3. Provide all electrical criteria (per basic electrical notes and Automatic Transport Design Manual) on electrical drawings.
Program Guide, PG-18-15, Volume C 39
O. ASBESTOS ABATEMENT: Submit the following:
Asbestos Abatement: Schematics* DD** CD***
Asbestos abatement report including:
1. Summary results of building records
2. Summary results of station personnel interview
3. determination of materials known to contain asbestos
4. visual inspection of building to determine location and condition of asbestos
5. sample strategy on the extent of asbestos present
Name and location of qualified laboratory for sample analysis
Asbestos abatement drawing ✓
Major Decontamination Areas showing:
1. Limits of sealing off the location
2. Quantities of asbestos material
3. Arrangements for auxiliary rooms
4. Engineering of negative air systems
5. Path of asbestos to loading platform
6. Location and connection to required utilities
Minor Decontamination Areas showing:
1. location, type, and length of pipe element to be abated by "Glove and Bag" approach
2. Other abatement features
Summary of:1
• Square meter (feet) of floor space for abatement
• Total linear and square meter (feet) of asbestos to be abated
• Total cost of abatement2 ✓ ✓
Program Guide, PG-18-15, Volume C 40
Asbestos Abatement: Schematics* DD** CD***
Asbestos abatement drawings including:
1. restoration of impacted building sub-systems
2. integrated phasing on execution of abatement
1:100 (1/8 inch. Submit a complete double line layout of areas of critical
** Submit minimum 1:100 (1/8 inch) scale f loor plans, new and renovated, *** Submit fully dimensioned, complete, and coordinated 1:100 (1/8 inch)
O. NOTES:
1. Provide a copy of the summary to the construction cost estimator for inclusion as a separate bid item in the project estimate.
2. Include any cost for decontamination of equipment and fixtures.
Program Guide, PG-18-15, Volume C 41
P. SPACE PLANNING
Schematics DD CD
Space-Accounting Summary Table ✓1 ✓2 ✓3
P. NOTES:
1. Provide a tabular table with columns entitled Departmental Function, H-7610
Req…