Attachment_2_Pine_Knot_Maps.pdf
PDF 4 MB Posted
- Attached to
- Fire Alarm Inspection; Pine Knot JCC, KY. Federal contract opportunity
- Solicitation number
- 1282A724Q0004
- Issued by
- Department of Agriculture Forest Service
About this file
This document summarizes the details of a federal solicitation for fire alarm inspection services at the Pine Knot Job Corps Center located in Pine Knot, Kentucky. The solicitation was issued by the Department of Agriculture Forest Service under number 1282A724Q0004. The solicitation seeks inspection services for the fire alarm system at the Pine Knot JCC campus. The document provides an overview of the campus layout including various buildings and structures. Relevant buildings are identified along with their current uses such as administration, housing, dining, vocational training, and recreation facilities. The campus map and floor plans attached to the document provide additional location details.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment_3_Wage_Determination_2015-4695.pdf | ||
| Sol_1282A724Q0004.pdf | ||
| Attachment_4_Previous_Fire_Inspection_Report.pdf | ||
| Attachment_1_Statement_of_Work.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
300/310
345/346
STAFF HOUSING
R o u t e
J
O
B
C
R
P
S
R
A
D
STAFF
APARTMENTS
ABANDONED
SEWAGE
PUMPS
0 125 250 500 Feet
Existing Site Plan
Pine Knot Civilian Conservation Center
Pine Knot, Kentucky
BUILDINGS
46 - FORMER STORAGE (VACANT)
77 - TRAILER (VACANT)
100-00- ADMINISTRATION BUIL
200-00- WELL
210-10- COUNSE
220-SAFETY/CRT/COMPUTER TECH/IT
230-30- VACANT TRADE BUIL
240-40- WELDING/CENTER MAINTEN
250-50- CARPENTRY
260-60- VOCATION/WPO/
270-70- WELDING PROJECTS/TRADE MATERIAL STO
300/310- SUPPLY WAREHOUSE/FIRE CACHE
320-20- AUTO MECHANICS
360-60- FLAMMABLE STO
400-00- STUDENT ACTIVITY CE
410 HUMPHREY DORMITORY (FEMALE)
420-20- KING HALL DORM (M
430-30- PERKINS DORM (M
440-40- WASHINGTON DORM (M
450-50- LAU
500-00- ACADEMIC EDUCA
510 -DINING HALL
520-20- CULINARY
530-30- FORESTRY CONSERVATION/FIREFIGH
600-00- GYMNASIUM/RECREATION
STRUCTURES
50A-CARPENTER SHOP GAZEBO
80 - STORAGE SHED
90 - STORAGE
105-05- GAZE
115-15- GUARD S
216 - GAZEBO
225-25- GAZE
235-35- MAINTENANCE STORAGE
245-45- GAZE
255-55- CARPENTRY
305-05- GAZE
315-15- STORAGE SH
316-16- STORAGE SH
325-25- POLE BUILDING STO
335-35- GAZE
345/346- STOR GARAGE 1/
POLE BLDG STOR 1
355-55- FLEET VEHICLE KEY S
365-65- FUEL PUMPS (ABANDO
401-01- GAZE
405-05- GAZE
406-06- GAZEB
445-45- GAZEB
455-55- GAZEB
456-56- RESIDENT STO
STORAGE
RECREATION
MEDICAL/DENTAL
EDUCATION
DORMITORY
CAFETERIA
ADMINISTRATION
FUNCTION LEGEND
VACANT
5 April 2023
505-05- GAZEB
508-08- CONTAIN
515-15- DINING PAVI
517-17- STORAGE SH
521-21- GAZEB
525-STORAGE GARAGE
535-35- POLE BUILDING STORA
601-01- AMPHITHE
602-02- PAVI
603-03- STORAGE SH
605-05- GAZEB
611-11- RECREATION STORA
612-12- RECREATION STORA
613-13- RECREATION STORA
614-14- CONTAINER 2- FUEL STO
615-15- RECREATION STORA
625-25- DUG O
626-26- DUG O
Building Descriptions and Structures PINE KNOT Civilian Conservation Center
BUILDING 100 - ADMINISTRATION BUILDING
COMPUTER
PROGRAM CLERKCENTER
DIRECTOR
ADMINISTRATIVE
OFFICER
MAIL ROOM
SUPPORT
SERVICES
SUPERVISOR
CONFERENCE
ROOM
ELEC
W
M
K I T
C H
E N
DN
DN
RECEPTION
DATA RACK
PULL-DOWN
STAIR TO
ATTIC BELOW
ATTIC FLOOR
ABOVE
CONFERENCE
ROOM
OFFICE
OFFICE
BUILDING 100
ADMINISTRATION BUILDING
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
ADMINISTRATION
Building Descriptions Date: 03/06/2023Center : Pine Knot (00320) Page: 12 of 128
Building: 0100 - ADMINISTRATION BUILDING
There is a 12 gallon electric hot water heater, American Water Heater, model# E61-12U-125SVComments:
PVC None None
Electric Water Cooler Hose Bibb Lavatory Sink Water Closet (Tank)
Gas (Natural)
None None ABC Type Fire Extinguisher
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Split Direct Expansion (Air
Cooled)
Single Duct
Fan Coil
Refrigerant
Refrigerant
Electric
Electric
Mechanical
Mechanical
None
None
Entire Building
Electronic Equipment
Room
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
The outside units are a Lenox model HS14-651-9P and Tempstar model N4A360AKC400 (mfg date April 2014)
The outside unit is a Liebert model PFH027A-PL7. This system heats and cools the computer room.
Comments:
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Area Served
Control System
Heat Distribution
Fresh Air Intake
Piping System
4. Distribution System
Page: 13 of 128
Building: 0100 - ADMINISTRATION BUILDING
Comments: Electrical service of 120/240V to the building is provided from a pole-mounted utility-owned transformer (25KVA) bank, located at the west side of the building, via a 350A pole-mounted main circuit breaker.
From this circuit breaker the electrical service is routed to the building via underground cable and terminated in the 400A main distribution panelboard with 350A main circuit breaker (MCB). The utility submeter for this building is mounted at the utility pole.
FIRE ALARM
Comments: The fire alarm control panel is a Notifier SGL 404. This panel is located in the kitchen electrical closet.
Comments: The Center's main incoming communication systems (telephone and internet) are located in the computer room of this building. The public address system is not connected and therefore is not operational.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None None TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
High Intensity Discharge (HID) Comments: Building-mounted light fixtures are controlled by astronomical time clock, located in the electrical closet.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Storage Rooms
Toilets
Conference Rooms
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Distribution Panel 120/240V, 1-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
Number of Deficiencies = 1
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
Type Location N/A N/A
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required No
Number of Deficiencies = 1
BUILDING 200 - WELLNESS
EXAM 1
CMHC
CLOSET
COPYBATH 2
MEDICAL
STORAGE
BREAK ROOM
KITCHEN
TEAP
JAN
STORAGE
WAIT
RECEPTION
EXAM 2
EXAM 3
OFFICE
BATH 1
MECH
T
FEMALE
WARD
DN
MALE WARD
TLT
T
T
T
BUILDING 200
WELLNESS
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
MEDICAL/DENTAL
Page: 17 of 128
Building: 0200 - WELLNESS
Domestic hot water is provided by a Richmond model TES85-18-G 80 gallon electric water heater.Comments:
Cast Iron None None
Electric Water Cooler Lavatory Shower/Bathtub Sink Water Closet (Flush Valve)
Gas (Natural)
Wet None ABC Type Fire Extinguisher
Comments: There is a sprinkler system in the attic of the building where the mechanical equipment is located.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
The three outside condensing units are Trane model TTB042D.Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Area Served
Control System
Heat Distribution
Fresh Air Intake
Piping System
Page: 18 of 128
Building: 0200 - WELLNESS
Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the north side of the building, via a 400A pole-mounted disconnect switch, that feeds the building service entrance equipment. From this main disconnect switch the electrical service is routed to the building via underground cable and terminates in the electrical trough which feeds one 400 A main panelboard with 400 A main circuit breaker and one 200 A disconnect switch.
FIRE ALARM
Comments: The fire alarm control panel is a Simplex 4007. This panel is located in the lobby.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control Panel Flow Switch Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
High Intensity Discharge (HID) Comments: Building-mounted lighting are controlled by astronomical time clock located in the electrical room.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Medical/Dental
Storage Rooms
Reception
Corridors & Stairs
Wards (Patient)
Toilets
Housing Lounge
Equipment Rooms (Elec/Mech)
Area Recommended Recorded Light Type
Selected Lighting w/ Battery Battery Backup
Main Distribution Panel 120/208V, 1-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
LIGHTING
BUILDING 220 - SAFETY/CRT/COMPUTER TECH/IT
ORIENTATION
STAFF OFFICE
TOILET TOILET
IT
COMPUTER
SERVICE
TECHNOLOGY
UPUP
FIRST FLOOR
OFFICE
OFFICE
UP
STO.
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
NON-ACADEMIC
VOCATION/THEORY
BUILDING 220
SAFETY/CRT/COMPUTER
TECH/IT
CTR OFFICE
CTR COMPUTER
ROOM
STORAGE
DN DN
ROOF
SECOND FLOOR
DN
STORAGE
COMPUTER SERVICE
TECH ((CTR)
STORAGE
CTR OFFICE
T
SAFETY OFFICE
BUILDING 220
SAFETY/CRT/COMPUTER
TECH/IT
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
NON-ACADEMIC
ADMINISTRATION
Page: 28 of 128
Building: 0220 - SAFETY/CRT/COMPUTER TECH/IT
None None ABC Type Fire Extinguisher
Comments: Electrical service of 120/240V to the building is provided from a pole-mounted utility-owned transformer bank, located at the north side of the building, via a 600A pole-mounted main distribution panel. From this distribution panelboard the electrical service is routed to the building via underground cable and terminates in the two 225A panelboard with 225A main circuit breaker (MCB0, and two 150A main lugs only panelboards.
FIRE ALARM
Comments: The fire alarm control panel is a Simplex 4007. This panel is located in the first-floor instructor office.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
High Intensity Discharge (HID) Comments: The exterior building-mounted light fixtures are controlled by a photocell.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Classrooms
Offices
Storage Rooms
Vocational
Toilets
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Distribution Panel 120/240V, 1-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
Type Location N/A N/A
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required
Number of Deficiencies = 0
BUILDING 230 - VACANT TRADE BUILDING
TEMPORARY
STORAGE
TOILET
BUILDING 230
VACANT TRADE BUILDNG
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
VACANT
Page: 33 of 128
Building: 0230 - VACANT TRADE BUILDING
None None ABC Type Fire Extinguisher
Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the east side of the building, via a 400A pole-mounted main disconnect switch that feeds the building service entrance equipment. From this disconnect switch the electrical service is routed to the building via underground cable and terminates in the 200A main panelboard with 200A main circuit breaker. Building service entrance equipment consists of one 400A main panelboard with 400A main circuit breaker (MCB), and one 200A panelboard with 200A main circuit breaker (MCB), FIRE ALARM
Comments: The fire alarm control panel is a Simplex 4001. This panel is located in the masonry shop area.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
Incandescent Comments: The exterior building-mounted light fixtures are controlled by a photocell.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Classrooms
Offices
Storage Rooms
Toilets
Vocational
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Panelboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
Type Location N/A N/A
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required No
BUILDING 240 - WELDING/CENTER MAINTENANCE
FIRST FLOOR
MEZZANINE
STORAGE
OFFICE
MAITENANCE
SHOP
FLAMMABLE &
PAINT
STORAGE
TOOL
STORAGE
WELDING
SHOP
GRINDING
SHOP
OXYGEN/
ACETYLENE
STORAGE
TOILET
OFFICE
CLASSROOM
STORAGE
STORAGE
STORAGE
T
WELDING/CENTER
MAINTENANCE
BUILDING 240
60 Feet15 300
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
VOCATION/THEORY
STORAGE/SUPPORT
Page: 38 of 128
Building: 0240 - WELDING/CENTER MAINTENANCE
Domestic hot water is provided by a US/Craftmaster model E1F50RD045V 50-gallon electric water heater.
Comments:
Cast Iron None None
Electric Water Cooler Fixed Emergency Eyewash Hose Bibb Lavatory Multi-Compartment Sink Urinal Water Closet (Tank)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: Electrical service of 120/240V to the building is provided from a pole-mounted utility-owned transformer bank, located at the east side of the building, via a 1,200A pole-mounted main disconnect switch that feeds the building service entrance equipment. From this disconnect switch the electrical service is routed to the building via underground cable and terminates in the 1,200A main distribution panelboard with 1,200A main circuit breaker. Building electrical equipment consists of one 1,200A main distribution panelboard (MDP) with 1,200A main circuit breaker (MCB), one 400A panelboard with 400A main circuit breaker (MCB), two 225A panelboards with 225A MCB, and two 200A panelboards with 200A MCB.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Incandescent Comments: The exterior building-mounted light fixtures are controlled by a photocell.
Main Panelboard 120/240V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Page: 39 of 128
Building: 0240 - WELDING/CENTER MAINTENANCE
FIRE ALARM
Comments: The fire alarm control panel is a Fire-Lite MS4424B. This panel is located in the paint shop area.
Comments: The building is connected to the LAN.
Audible Alarm Control Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None None TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
T8 - Fluorescent
T8 - Fluorescent
T12 - Fluorescent
T12 - Fluorescent
High Intensity Discharge (HID)
Incandescent
T12 - Fluorescent
Offices
Classrooms
Storage Rooms
Vocational
Vocational
Vocational
Toilets
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Emergency Exit
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Make Up air systems are deteriorated, and there is no exhaust system for the Welding Shop.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoNo
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Poor Electrical: Fair
Type Location N/A N/A
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
BUILDING 250 - CARPENTRY SHOP
CARPENTRY SHOP
DUST COLLECTOR
OFFICE
CARPENTRY
CLASS
TOILET
STORAGE
TOILET
STORAGE
STORAGE
STORAGE
BUILDING 250
CARPENTRY SHOP
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
Page: 44 of 128
Building: 0250 - CARPENTRY SHOP
Two electric water heaters are 10 gallon each Richmond model 6EP10-1.Comments:
Cast Iron None None
Electric Water Cooler Fixed Emergency Eyewash Hose Bibb Lavatory Sink Water Closet (Tank)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: Electrical services of 120/208V, 1-phase and 3-phase to the building are provided from a pole-mounted utility-owned transformer bank located at the northeast side of the building via overhead cable to one 200A, 3-pole main circuit breaker (MCB), one 200A, 2-pole main circuit breaker, and one 100A, 120/208V, 1-phase panelboard with 100A main circuit breaker (MCB) located in the carpentry shop.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Incandescent Comments: The exterior building-mounted light fixtures are controlled by a photocell.
Main Circuit Breaker 120/240V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 3
Page: 45 of 128
Building: 0250 - CARPENTRY SHOP
FIRE ALARM
Comments: The fire alarm control panel is a Siemens FS-250 located in the carpentry shop.
Comments: The building is connected to the LAN. The public address system is not connected and therefore is not operational.
Audible Alarm Control Panel Duct Smoke Detector Heat Detector Manual Pull Station Visual Alarm
Connected to Main System None None TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
T8 - Fluorescent
T12 - Fluorescent
T12 - Fluorescent
High Intensity Discharge (HID)
T12 - Fluorescent
Classrooms
Offices
Storage Rooms
Vocational
Toilets
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Emergency Exit
Number of Deficiencies = 2
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Two electrical panels are more than forty years old, deteriorated, overloaded and undersized for the existing loads.
There is no heat in the Shop area.
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoNo
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Fair Electrical: Poor
Type Location N/A N/A
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
BUILDING 260 - VOCATION/WPO/AWPO
OFFICE
ASSIST. WPO
CONFERENCE
WPO/CONFERERRNCE ROOM
TOILET
W
M
CLOSET
OFFICE
COPY ROOM
OFFICE
BUILDING 260
VOCATION/WPO/AWPO
20 Feet100 5
PINE KNOT CIVILIAN CONSERVATION
CENTER
STORAGE SUPPORT
Page: 49 of 128
Building: 0260 - VOCATION/WPO/AWPO
There is a 30 gallon electric water heater, Richmond model 6K30-2.Comments:
Cast-Iron None None
Electric Water Cooler Lavatory Sink Urinal Water Closet (Tank)
Gas (Natural)
None None ABC Type Fire Extinguisher
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Single Duct None Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Cooling is provided by the same units that provide heating. The model numbers are given under heating.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Area Served
Control System
Heat Distribution
Fresh Air Intake
Piping System
Page: 50 of 128
Building: 0260 - VOCATION/WPO/AWPO
Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank located at the northwest side of the building via underground cable and terminates in the 200A main branch panelboard with 200A main circuit breaker (MCB).
FIRE ALARM
Comments: The fire alarm control panel is by Simplex 4007. This panel is located in the maintenance office.
Comments: The building is connected to the LAN. The public address system is not connected and therefore is not operational.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None None None
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
Incandescent Comments: The exterior building-mounted light fixtures are controlled by a photocell.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Storage Rooms
Conference Rooms
Toilets
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Branch Panel 120/208V, 1-Phase, 3 Wire Branch Panel Only Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
Electric Water Gas No NoNo
BUILDING UTILITY METERING
Type Location N/A N/A
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required
BUILDING 300/0310 - SUPPLY WAREHOUSE/FIRE CACHE
WAREHOUSE
FIRE FIGHTING/
URBAN FORESTRY
OFFICE
LOADING
DOCK
T
DN
DN
FIRE FIGHTING/
URBAN FORESTRY
STORAGE
OFFICE
SUPPLIES
CLOTHES
STORAGE
MVD
BUILDING 300/310
SUPPLY WAREHOUSE/FIRE CACHE
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
VOCATION/THEORY
Page: 59 of 128
Building: 0300/0310 - SUPPLY WAREHOUSE/FIRE CACHE
There is a 10 gallon electric hot water heater, Richmond model 6EP-1.Comments:
Cast Iron None None
Electric Water Cooler Lavatory Water Closet (Tank)
Comments: Richmond 6EP10-1, 10 Gallon electric water heater
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the north side of the building, via a 200A pole-mounted circuit breaker that feeds the building service entrance equipment. From this disconnect switch the electrical service is routed to the building via underground cable and terminated in the 200A main panelboard with 200A main circuit breaker (MCB).
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Incandescent Comments: The exterior building-mounted light fixtures are controlled by a photocell.
Main Panelboard 120/240V, 3-Phase, 4 Wire Panelboard Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Page: 60 of 128
Building: 0300/0310 - SUPPLY WAREHOUSE/FIRE CACHE
FIRE ALARM
Comments: The fire alarm control panel is a Honeywell 6700 located in the warehouse area.
Comments: The building is connected to the LAN.
Audible Alarm Control Panel Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None None None
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
T12 - Fluorescent
T12 - Fluorescent
T8 - Fluorescent
T12 - Fluorescent
Offices
Storage/Warehouse-Active
Classrooms
Toilets
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 1
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoNo
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location N/A N/A
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments
BUILDING 320 - AUTO MECHANICS SHOP
TOILET TOILET
AUTO MECHANICS
SHOP
AUTO MECHANICS
CLASSROOM
OFFICE
TOOL ROOM
CLASSROOM
RECYCLING
STORAGE
STORAGE
BUILDING 320
AUTO MECHANICS SHOP
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
Page: 64 of 128
Building: 0320 - AUTO MECHANICS SHOP
Domestic hot water is provided by a Richmond Perfect 30-gallon water heater.Comments:
Comments:
Cast Iron Outdoor None
A grease and oil interceptor is installed outside the building, on the northeast corner adjacent to the sewage lift station.
Electric Water Cooler Fixed Emergency Eyewash Sink Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the southeast side of the building, via two circuit breakers, one 225A pole-mounted circuit breaker and one 225A wall-mounted circuit breaker that feeds the building service entrance equipment. Building service entrance equipment consists of two 225A main panelboards with 225A main circuit breakers.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID) Comments: The exterior building-mounted light fixtures are controlled by a photocell.
Main Panelboard 120/208V, 1-Phase, 3 Wire Panelboard Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 2
Page: 65 of 128
Building: 0320 - AUTO MECHANICS SHOP
FIRE ALARM
Comments: The fire alarm control panel is a Siemens FS-250. This panel is located in the office.
Comments: The building is connected to the LAN.
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None None TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
High Intensity Discharge (HID)
T8 - Fluorescent
Classrooms
Offices
Storage Rooms
Vocational
Toilets
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Emergency Exit
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoNo
BUILDING UTILITY METERING
Structure: Good Exterior: Fair Interior: Good Mechanical: Good Electrical: Good
Type Location N/A N/A
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments
BUILDING 400 - STUDENT ACTIVITY CENTER
W M
T
JAN
NIGHT
SHIFT
MAIL ROOM
RESIDENTIAL
MANAGER
RESIDENTIAL
SUPERVISOR
STORAGE
CSO
LOUNGE
STORAGESTUDENT
GOV.ASSOC.
OFFICE
CANTEEN
RAMP
DN
FIREPLACE
DEPUTY
CENTER
DIRECTOR
MEDICATION
ROOM
BUILDING 400
STUDENT ACTIVITIES
CENTER
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
ADMINISTRATION
RECREATION
HOUSING
MEDICAL/DENTAL
Page: 72 of 128
Building: 0400 - STUDENT ACTIVITY CENTER
Domestic hot water is provided by a 20-gallon electric water heater.Comments:
PVC None None
Electric Water Cooler Lavatory Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Copper Copper Electric Building Water Softener No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
The furnaces are provided with evaporator coils matched to Lennox outdoor air cooled condensing units. One is a model HS26-060-2P and one is a model HS26-048-2P.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Area Served
Control System
Heat Distribution
Fresh Air Intake
Piping
Page: 73 of 128
Building: 0400 - STUDENT ACTIVITY CENTER
Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the south side of the building, via a 400A pole-mounted disconnect switch. From this distribution panelboard the electrical service is routed to the building via underground cable and terminates in the 400A panelboard with 300A main circuit breaker (MCB).
FIRE ALARM
Comments: The fire alarm control panel is a Simplex 4007. This panel is located in the residential manager's office.
Comments: The building is connected to the LAN.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None None None
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
Incandescent Comments: The exterior building-mounted light fixtures are controlled by a photocell.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
High Intensity Discharge (HID)
Offices
Corridors & Stairs
Storage Rooms
Lounges
Study Room
Area Recommended Recorded Light Type
None Battery Backup
Main Branch Panel 120/208V, 1-Phase, 3 Wire Branch Panel Only Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
Type Location N/A N/A
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required No
BUILDING 410 - HUMPHREY DORMITORY (FEMALE)
DORM ROOMS
(TYPICAL)
DORM ROOMS
(TYPICAL)
TOILET/SHOWERS
TOILET/SHOWERS
M E
C H
DORM ROOMS
(TYPICAL)
DORM ROOMS
(TYPICAL)
R.A.
LOUNGE
STORAGE
J
STORAGE
J
STORAGE
DN
STORAGE
BUILDING 410
HUMPHREY DORMITORY
(FEMALE)
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
STUDENT HOUSING
Page: 77 of 128
Building: 0410 - HUMPHREY DORMITORY (FEMALE)
There are two 120 gallon hot water heaters. One is a Rheemglass model EGS18-120G and the other is a Richmond Perfect model TES120-36G.
Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Shower Shower/Bathtub Sink Water Closet (Flush Valve)
None
Wet None ABC Type Fire Extinguisher
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
There are two outside heat pump units. One unit is a Trane model TWA060C300A and the other unit is a Maytag model DT5BD-060K.
Comments:
Number of Deficiencies = 1
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
Number of Deficiencies = 1FIRE PROTECTION
3. Air Conditioning
Area Served
Control System
Heat Distribution
Fresh Air Intake
Piping System
Page: 78 of 128
Building: 0410 - HUMPHREY DORMITORY (FEMALE)
Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the east side of the building, via a 400A pole-mounted main circuit breaker. From this circuit breaker the electrical service is routed to the building via underground cable and terminates in the 400A main panelboard with 400A main circuit breaker (MCB). The service equipment is located in the electrical/mechanical room.
FIRE ALARM
Comments: The fire alarm control panel is a Siemens FS-250. This panel is located in the RA office.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Flow Switch Heat Detector Manual Pull Station Smoke Detector Tamper Switch Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
Light Emitting Diode (LED) Comments: The exterior building-mounted light fixtures are controlled by a time clock.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Sleeping Rooms
Offices
Storage Rooms
Equipment Rooms (Elec/Mech)
Shower
Laundry Room
Housing Lounge
Corridors & Stairs
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Panelboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 1
Type Location None None
There is no gas in this building.
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required
BUILDING 420 - KING HALL DORMITORY (MALE)
MECH/ELEC
LOWER LEVEL
UP
UP
T T
OFFICE
IT
OFFICE
OFFICE
OFFICE
OFFICE
BUILDING 420
KING HALL DORMITORY
(MALE)
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
ADMINISTRATION
RECREATION
DORM ROOMS
(TYPICAL)
DORM ROOMS
(TYPICAL)
TOILET/SHOWERS
TOILET/SHOWERS
MECH
DORM ROOMS
(TYPICAL)
DORM ROOMS
(TYPICAL)
R.A. OFFICE
LOUNGE
RAMP
RAMP
STORAGE
FIRST FLOOR
JAN
JAN
DN
DN
DN
DN
BUILDING 420
KING HALL DORMITORY
(MALE)
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
Page: 82 of 128
Building: 0420 - KING HALL DORMITORY (MALE)
There are two 120 gallon each electric hot water heaters. One is a Rheem model EGS18-120-G and the other is a Bradford White model MII120-18-3SF-39.
Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Service Sink Shower Urinal Water Closet (Flush Valve)
None
None None ABC Type Fire Extinguisher
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Three split system heat pumps serve the dorm. The three outdoor units for the dorm are as follows:
Rudd-Rheem model RP1424AJINA (mfg 2/2017), Tempstar model N4H3609HB400 (mfg 2/2011) and International Comfort Products model R2H360GHR4.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Area Served
Control System
Heat Distribution
Fresh Air Intake
Piping System
Page: 83 of 128
Building: 0420 - KING HALL DORMITORY (MALE)
Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the northwest side of the building, via a 600A pole-mounted main circuit breaker. From this circuit breaker the electrical service is routed to the building via underground cable and terminated in the 600A main panelboard with 600A main circuit breaker (MCB). The service equipment is located in the electrical/mechanical room.
FIRE ALARM
Comments: The fire alarm control panel is a Simplex 4007. This panel is located in the RA office.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
Light Emitting Diode (LED) Comments: Building-mounted lighting is controlled by an astronomical time clock located in the electrical/mechanical room.
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T12 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
Sleeping Rooms
Offices
Storage Rooms
Housing Lounge
Corridors & Stairs
Shower
Equipment Rooms (Elec/Mech)
Toilets
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Panelboard 120/240V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
Type Location None None
There is no gas in this building.
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required
BUILDING 430 - PERKINS DORMITORY (MALE)
DORM ROOM
(TYPICAL)
DORM ROOM
(TYPICAL)
STORAGE
LOUNGE
DORM ROOM (TYPICAL)
DORM ROOM (TYPICAL)
M E
C H
R.A. OFFICE
RAMP RAMP
JAN
JAN
RAMP
R A
M P
STORAGE
DN
DN
DN
STORAGE
DN
UNDER
CONSTRUCTION
UNDER
CONSTRUCTION
BUILDING 430
PERKINS DORMITORY
(MALE)
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
Page: 87 of 128
Building: 0430 - PERKINS DORMITORY (MALE)
Domestic hot water is provided by two Bradford White model MII120-183SF39 120 gallon electric water heaters.
Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Shower Sink Urinal Water Closet (Flush Valve)
None
None None ABC Type Fire Extinguisher
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Outdoor units are Trane model 2TWA0060A3000AB, and Goodman CPLJ48-1B plus International Comfort Product model X12147111, mfg date April 2012.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Number of Deficiencies = 1FIRE PROTECTION
3. Air Conditioning
Area Served
Control System
Heat Distribution
Fresh Air Intake
Piping
Page: 88 of 128
Building: 0430 - PERKINS DORMITORY (MALE)
Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the west side of the building, via a 600A pole-mounted main circuit breaker. From this circuit breaker the electrical service is routed to the building via underground cable and terminated in the 600A main panelboard with 600A main circuit breaker (MCB). The service equipment is located in the electrical/mechanical room.
FIRE ALARM
Comments: The fire alarm control panel is a Simplex 4007. This panel is located in the RA office.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
High Intensity Discharge (HID) Comments: The exterior building-mounted light fixtures are controlled by a photocell.
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Sleeping Rooms
Offices
Storage Rooms
Housing Lounge
Corridors & Stairs
Shower
Toilets
Equipment Rooms (Elec/Mech)
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Panelboard 120/240V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
Type Location None None
There is no gas in this building.
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required No
BUILDING 440 - WASHINGTON DORMITORY (MALE)
LOUNGE
R.A. OFFICE
DORM ROOM
(TYPICAL)
STORAGE
DORM ROOM
(TYPICAL)
DORM ROOM
(TYPICAL)
TOILET/SHOWERS
MECH
DORM ROOM
(TYPICAL)
STORAGE
STORAGE
STORAGE
JAN
JAN
DN
DN
STORAGE
BUILDING 440
WASHINGTON DORM (MALE)
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
Page: 92 of 128
Building: 0440 - WASHINGTON DORMITORY (MALE)
Domestic hot water is provided by two 120 gallon electric water heaters. One water heater is a Bradford White model MII120-18-35F-39 and the other is a Richmond Perfect model ES-TES120- 18G.
Comments:
Cast Iron None None
Electric Water Cooler Hose Bibb Lavatory Service Sink Shower Urinal Water Closet (Flush Valve)
None
None None ABC Type Fire Extinguisher
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Heat Pump (Air
Source)
Single Duct Refrigerant Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Cooling is provided by three split system heat pumps, data for which is provided under heating.Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Area Served
Control System
Heat Distribution
Fresh Air Intake
Piping System
Page: 93 of 128
Building: 0440 - WASHINGTON DORMITORY (MALE)
Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the west side of the building, via a 600A pole-mounted main circuit breaker. From this circuit breaker the electrical service is routed to the building via underground cable and terminates in the 600A main panelboard with 600A main lugs only (MLO). The service equipment is located in the electrical/mechanical room.
FIRE ALARM
Comments: The fire alarm control panel is a Simplex 4007. This panel is located in the RA office.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
Light Emitting Diode (LED) Comments: The exterior building-mounted light fixtures are controlled by a time clock.
T8 - Fluorescent
Incandescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Sleeping Rooms
Storage Rooms
Offices
Housing Lounge
Corridors & Stairs
Shower
Laundry Room
Equipment Rooms (Elec/Mech)
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Panelboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 1
Type Location None None
There is no gas in this building.
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required
BUILDING 450 - LAUNDRY
MECH
LAUNDRY
MECH.
TOILET
JAN/
STORAGE
COMMERCIAL
WASHER &
DRYER
BUILDING 450
LAUNDRY
20 Feet100 5
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
Page: 97 of 128
Building: 0450 - LAUNDRY
Hot water is provided by two 100 gallon each Bradford White model EF100T250E3NA2 gas-fired water heaters.
Comments:
Comments:
Cast Iron None None
There is an external lint trap installed on the sewer outside the building.
Electric Water Cooler Hose Bibb Lavatory Sink Water Closet (Tank)
Gas (Natural)
None None ABC Type Fire Extinguisher
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
None None None None Natural None None
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Area Served
Control System
Heat Distribution
Fresh Air Intake
Piping
4. Distribution System Number of Deficiencies = 1
Page: 98 of 128
Building: 0450 - LAUNDRY
Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the north side of the building, via a 600A pole-mounted disconnect switch. From this disconnect switch the electrical service is routed to the building via underground cable and terminates in the 400A main panelboard with 400A main circuit breaker (MCB).
FIRE ALARM
Comments: The fire alarm control panel is a Fire-Lite Alarms- MS 2. This panel is located in the storage room. There are some smoke detectors which are battery operated.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
None Closed Circuit TV None TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
High Intensity Discharge (HID) Comments: The exterior building-mounted light fixtures are controlled by a photocell.
T8 - Fluorescent
T8 - Fluorescent
T12 - Fluorescent
Laundry Room
Toilets
Equipment Rooms (Elec/Mech)
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Panelboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
Electric Water Gas No NoNo
BUILDING UTILITY METERING
Type Location N/A N/A
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required No
BUILDING 500 - ACADEMIC EDUCATION
FIRST FLOOR
MECH
M
W
STUDENT STORAGE
COPY
CLASSROOM
UPUP
MECH
CPP/
TABE
OFFICE
OFFICE
CLASSROOM
OFFICE
CPP/
TABE
BUILDING 500
ACADEMIC EDUCATION
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
ACADEMIC
NON-ACADEMIC
SECOND FLOOR
COMPUTER
LAB
CLASSROOM
STAFF
LOUNGE
M W
CUSTODIAL
ROOM AND
STAFF TOILET
JAN
STORAGE/
MEDS
PRINCIPAL
COPY ROOM
STORAGE
LIBRARY
LANGUAGE
ARTS
CLASSROOM
DN DN DN
CLASSROOM
CLASSROOM
BUILDING 500
ACADEMIC EDUCATION
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
ACADEMIC
Page: 103 of 128
Building: 0500 - ACADEMIC EDUCATION
Hot water is provided by a 30 gallon electric water heater.Comments:
Cast Iron Outdoor None
Electric Water Cooler Lavatory Service Sink Urinal Water Closet (Flush Valve)
None
None None ABC Type Fire Extinguisher
Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the south side of the building, via a 600A pole-mounted main disconnect switch. From this disconnect switch the electrical service is routed to the building via underground cable and terminated in the trough. Building service entrance equipment consists of two 225A main panelboards with 225A main circuit breaker (MCB), and one 400A 3-pole disconnect switch. The service equipment is located in the electrical/mechanical room.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID) Comments: The exterior building-mounted light fixtures are controlled by a photocell.
Main Panelboards 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Page: 104 of 128
Building: 0500 - ACADEMIC EDUCATION
FIRE ALARM
Comments: The fire alarm control panel is a Simplex 4001. This panel is located in the educational office on the second floor.
Comments: The public address system is not connected and therefore not operational.
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None None TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
Incandescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Storage Rooms
Offices
Classrooms
Toilets
Equipment Rooms (Elec/Mech)
Housing Lounge
Corridors & Stairs
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Emergency Exit
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Exterior doors, frames and sidelights are damaged.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No N/ANo
BUILDING UTILITY METERING
Structure: Good Exterior: Fair Interior: Good Mechanical: Good Electrical: Good
Type Location N/A N/A
CARBON MONOXIDE DETECTION
Detection Required No
BUILDING 510 - DINING HALL
DINING
SERVING
JAN
M
W
MECH
TRASH CANS
FREEZERS
DRY FOOD
STORAGE
OFFICE
CULINARY ARTS
DISHWASHING
KITCHEN
FREEZER
STORAGE
DN
LOADING
DOCK
DN
PANTRY/
STORAGE
BUILDING 510
DINING HALL
40 Feet200 10
PINE KNOT CIVILIAN CONSERVATION
CENTER
PINE KNOT, KENTUCKY
FOOD SERVICE
Page: 109 of 128
Building: 0510 - DINING HALL
Domestic hot water is provided by two 100 gallon Bradford White model D100T1993M gas-fired water heaters.
Comments:
Cast Iron Outdoor None
Electric Water Cooler Hose Bibb Lavatory Multi-Compartment Sink Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet Chemical
Comments: Electrical service of 120/208V to the building is provided from a pad-mounted utility-owned transformer, located at the west side of the building, via underground cable and terminated in the 1,600A main distribution panelboard (MDP) with 1,600A main circuit breaker (MCB). The service equipment is located in the electrical/mechanical room.
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID) Comments: The exterior building-mounted light fixtures are controlled by a photocell.
Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Wat…
This is the start of the file's text. The full file is on GovTribe.