Attachment_1_Statement_of_Work.pdf
PDF 338 KB Posted
- Attached to
- Fire Alarm Inspection; Pine Knot JCC, KY. Federal contract opportunity
- Solicitation number
- 1282A724Q0004
- Issued by
- Department of Agriculture Forest Service
About this file
This statement of work outlines requirements for inspection and testing services of fire alarm and suppression systems at the Pine Knot Job Corps Center in Kentucky. The contractor will be responsible for inspecting and testing fire alarm systems in 28 buildings following the tasks defined in Appendix A on an annual basis. Deliverables will include inspection reports for each system tested within 14 days of inspection, due by December 30 each year. The contractor must have qualified personnel and will use government furnished utilities while providing their own tools and test equipment. The contractor must comply with all applicable safety and regulatory requirements and coordinate access and work hours with the center. Travel will be at the contractor's expense. The contracting officer's representative is William Knaack and inquiries can be directed to Eric Asper.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment_3_Wage_Determination_2015-4695.pdf | ||
| Sol_1282A724Q0004.pdf | ||
| Attachment_2_Pine_Knot_Maps.pdf | ||
| Attachment_4_Previous_Fire_Inspection_Report.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK
FOR
INSPECTION AND TESTING OF FIRE
ALARM & FIRE SUPPRESSION SYSTEMS
Pine Knot Job Corps
Job Corps National Office November 2023
TABLE OF CONTENTS
1. BACKGROUND 2
1.1. DESCRIPTION OF SERVICES 2
2. GOVERNMENT FURNISHED PROPERTY AND SERVICES 4
2.1. UTILITIES 4
2.2. SECURITY, FIRE AND MEDICAL SERVICES 4
3. GENERAL INFORMATION 4
3.1. DAMAGES TO GOVERNMENT BUILDINGS, EQUIPMENT OR VEGETATION 4
3.2. PERMITS, LICENSES AND CERTIFICATIONS (RESERVED) 4
3.3. HOURS OF OPERATION 4
3.4. RECOGNIZED HOLIDAYS 4
3.5. TRAFFIC LAWS 5
3.6. WEAPONS, FIREARMS, AND AMMUNITION 5
3.7. GOVERNMENT INTERFACE 5
3.8. SAFETY 5
3.9. WORKMANSHIP 5
3.10. TOOLS 5
3.11. TEST EQUIPMENT 5
3.12. SANITARY FACILITIES 5
3.13. PERSONNEL 5
4. LIST OF APPENDICES: 6
APPENDIX A - FIRE DETECTION AND ALARM SYSTEM IT TASKS 7
APPENDIX B - BUILDINGS REQUIRING FIRE ALARM TESTING AND INSPECTION 8
3 `
PERFORMANCE WORK STATEMENT
1. BACKGROUND
Job Corps Centers serve students, and thus require life safety systems to be operational at all times to ensure safety of building occupants in the event of an emergency. This effort will provide all personnel, labor, equipment, tools, materials, instruments, meters, gauges, test equipment, transportation, supervision, and other items and services necessary to perform inspection and testing (IT) for the Fire Alarm Systems (FA) & Fire Suppression Systems (FS) for the Pine Knot Job Corps Center located in Pine Knot, Kentucky. A table showing buildings requiring FA and FS services is included in the attached sheet titled Appendix F.
1.1. DESCRIPTION OF SERVICES
1.1.1. LOCATION OF SERVICES
This project is located at the Pine Knot Job Corps Center campus located in Pine Knot Kentucky. The address is 132 Job Corps Road Pine Knot Kentucky 42635. Driving directions can be obtained by calling the Center at 606-354- 4232.
1.1.2. TASK 1: SCHEDULED FIRE ALARM AND MASS NOTIFICATION SYSTEM TESTING
Buildings have fire alarm systems that are in service. The Contractor shall inspect each system and test it in accordance with the attached inspection schedule in Appendix A for Fire Alarm. Guidance on the tasks in Appendix A can be found in NFPA 70B, latest edition (Recommended Practice for Electrical Equipment Maintenance). Fire alarm system descriptions and locations are as follows:
BUILDING SYSTEM
100(2) – Administration Notifier SGL-404
250(8) - Carpentry Siemens FS-250
260(9) – Vocation Bidg Simplex 4007ES
240(10) – Welding/Maintenance Fire-Lite MS4424B
230(11) - Masonry Simplex 4001
600(14) - Gym
300/310(33) – Warehouse
520(54) – Culinary Arts
Simplex 4007ES
Honeywell Silent Knight 6700
Honeywell Silent Knight 6700
510(55) Dining Hall Fire-Lite MS5UD
410(56 - Humphrey Hall Fire-Lite ES-50X
420(57) – King Hall Simplex 4007ES
430(59) – Perkins Hall Simples 4007ES
440(60) – Washington Hall Simplex 4007ES
500(65) - Education Simplex 4001
4 `
220(66) – Safety/CTR/CT Simplex 4007ES
450(67) - Laundry Fire-Lite MS-2
320(68) - Automotive Siemens FS-220
530(74) – Urban Forestry
200(75) – Wellness
400(76) – Student Activity Center
Simplex 4007ES
1.1.3. SUBMITTALS/DELIVERABLES
Contractor shall provide a separate inspection report for each system tested/inspected. Furnish reports in both hard format to the Center and electronic PDF format to the CO. Each report will include the following at a minimum:
• Job Corps Center Name
• Building Number and Name
• Item Description
• Location
• Inspection and Testing Performed in accordance with Appendices
• Indication of Pass/Fail
• Recommendations for repair in case of failed test
• Indication of System Normal, Warning or Caution Condition
• Date of Inspection
• Name of Inspector
• Signature of Inspector
Inspection reports are due within fourteen (14) days of the system inspection.
Inspection reports are a yearly requirement. Inspection reports are due by December 30th of each year. This will begin with the first inspection report due by December 30, 2023.
2. GOVERNMENT FURNISHED PROPERTY AND SERVICES
2.1 UTILITIES
Use of Government existing facilities will be permitted without metering and without payment of use charges, as long as facilities are cleaned and maintained in an acceptable condition. At Substantial Completion, restore these facilities to condition existing before initial use. The following are available for use by the Contractor: water, and electrical power services. The following are not available: telephone service. The Contractor is expected to provide whatever phone service he deems necessary for the duration of the project.
2.2 FIRE SERVICES
Municipal or volunteer fire protection services are not available at this site.
3. GENERAL INFORMATION
3.1 DAMAGES TO GOVERNMENT BUILDINGS, EQUIPMENT OR VEGETATION
5 `
Damages to Government buildings, equipment, or vegetation are addressed in FAR clause 52.237-2 – Protection of Government Buildings, Equipment, and Vegetation. The Contractor shall use reasonable care to avoid damaging existing buildings, equipment, and vegetation on the Government installation. If the Contractor's failure to use reasonable care causes damage to any of this property, the Contractor shall replace or repair the damage at no expense to the Government as the Contracting Officer directs. If the Contractor fails or refuses to make such repair or replacement, the Contractor shall be liable for the cost, which may be deducted from the contract price.
3.2 PERMITS, LICENSES AND CERTIFICATIONS (RESERVED)
3.3 HOURS OF OPERATION
The Contractor shall perform services during normal duty hours which are 0800-1630 Monday through Friday, excluding Federal Holidays. The Contractor may work weekends and holidays if approved in advance at his convenience. Work required outside of the standard work hours shall be coordinated with the Center.
3.4 RECOGNIZED HOLIDAYS
The Contractor is not required to provide service on federal holidays, except in emergency situations. The holidays are as follows:
New Year’s Day - 1 January Martin Luther King Day - 3rd Monday in January Washington’s Birthday - 3rd Monday in February Memorial Day - last Monday in May Juneteenth – 19 June Independence Day - 4 July Labor Day - 1st Monday in September Columbus Day - 2nd Monday in October Veteran’s Day - 11 November Thanksgiving Day - 4th Thursday in November Christmas Day - 25 December
If a holiday fall on Saturday, the preceding Friday will be the observed holiday. If the holiday falls on Sunday, the following Monday will be the observed holiday. If a holiday falls on a scheduled service day, the Contractor will be responsible for rescheduling services for the first day post the holiday observance.
3.5 TRAFFIC LAWS
The Contractor and its employees shall comply with all site traffic regulations.
3.6 WEAPONS, FIREARMS, AND AMMUNITION
Contractor employees are prohibited from possessing weapons, firearms, or ammunition, on themselves or within their Contractor-owned or privately owned vehicle while on the Center.
3.7 GOVERNMENT INTERFACE
Do not unduly interfere with regularly scheduled Government operational activities in the performance of contract requirements. In the event a Government supervisor so requests, temporarily cease work in the area and report the instructions, to include name of the Government person involved, to the CO immediately by the most expedient means. Notify the CO verbally of disputes with customers or other base Contractors and follow-up in writing.
3.8 SAFETY
The Contractor shall comply with all applicable Occupational Safety and Health Administration (OSHA) standards, federal, state, and local laws, regulations, and requirements regarding worker safety while performing
6 ` work at the Center. Compliance shall also include following industry standards concerning worker safety and personal protective equipment. The Contractor shall comply with all safety and health requirements necessary for the protection of personnel, facilities and equipment.
3.8.1 WRITTEN SAFETY PROGRAM
Maintain a written Safety Program, as required by OSHA and make said plan available for review by the Government upon request by the Contracting Officer.
3.9 WORKMANSHIP
All work shall be performed by qualified, experienced Contractor personnel.
3.10 TOOLS
All tools shall be furnished by the Contractor.
3.11 TEST EQUIPMENT
The Contractor shall furnish his own test equipment.
3.12 SANITARY FACILITIES
The Contractor's workmen may use existing sanitary facilities, subject to the regulations governing their use by Government personnel in the buildings in which the work is being accomplished.
3.13 PERSONNEL
Contractor personnel shall present a neat appearance. Contractor personnel shall be easily recognizable while on the installation in conjunction with this contract.
The government is authorized to restrict the employment under the contract of any Contractor employee or prospective Contractor employee, who is identified as a potential threat to the health, safety, security, general well- being, or operational mission of the installation and its population.
4. LIST OF APPENDICES:
• APPENDIX A - FIRE DETECTION AND ALARM SYSTEM ITEM TASKS
• APPENDIX B - BUILDINGS REQUIRING FIRE ALARM TESTING AND INSPECTION
7 `
APPENDIX A - FIRE DETECTION AND ALARM SYSTEM INSPECTION AND TESTING
TASKS
Frequency Component Tasks
Monthly
1. Control Panels and Annunciator Equipment (unmonitored only)
• Reserved
Annual
1. Control Panel and Annunciator Equipment (monitored)
1. Test to verify proper receipt of alarm, supervisory, and trouble signals (inputs) and operation of notification appliances and auxiliary functions (outputs).
2. Verify that all lamps and LEDs are illuminated.
3. Load test backup batteries (when provided).
2. Initiating Devices:
a. Manual Fire Alarm
Stations
1. Verify station is accessible (visual).
b. Radiant Energy Detectors (Optical Detectors)
• Reserved
. Gas Detectors • Reserved
3. Notification Appliances and
Voice Communication (telephone, speakers, horns, and strobe lights)
1. Test to verify operability.
4. Digital Alarm Transmitters and Receivers
1. Test to verify operability.
APPENDIX B - BUILDINGS REQUIRING FIRE ALARM TESTING AND INSPECTION
Building 100(2) 250(8) 260(9) 240(10) 230(11) 600(14) 300/310(33) 520(54) 510(55) 410(56) 420(57) 430(59) 440(60) 500(65) 220(66) 450(67) 320(68) Services Fire Alarm System Annual Tasks x
X
Building 530(74) 200(75) 400(76) Services Fire Alarm System Annual Tasks
TRAVEL
• All travel shall be included in the firm fixed priced CLINs. All travel shall be in accordance with Federal Travel Regulations. Current Federal Travel Regulations may be obtained from the following website: https://www.gsa.gov. Any deemed necessary ODCs should be factored into the fully burdened FFP.
GOVERNMENT POINT OF CONTACT
• The government point of contact is Eric Todd Asper, Eric.Asper@usda.gov and Contracting Officer’s representative for this contract will be William Knaack, william.knaack@usda.gov.
NON PERSONAL SERVICES STATEMENT
• The Contractor’s employees performing services as described shall be controlled, directed and supervised at all times by the
Contractor. Contractor management will ensure that the employees properly comply with the performance work standards outlined in the Statement of Work. The work set forth may not be interpreted or implemented in any manner that results in the Contractor creating or modifying Federal Policy. The Government will control access to the facilities and will perform the inspections and acceptance of the completed work. The term Contractor as applied herein includes Sub Contractors and Tradespeople.
END OF PINE KNOT JOB CORPS FIRE SAFETY INSPECTION AND TESTING STATEMENT
OF WORK
mailto:Eric.Asper@usda.gov mailto:william.knaack@usda.gov
| 1. BACKGROUND 2 |
| 2. GOVERNMENT FURNISHED PROPERTY AND SERVICES 4 |
| 3. GENERAL INFORMATION 4 |
| 4. LIST OF APPENDICES: 6 APPENDIX A - FIRE DETECTION AND ALARM SYSTEM IT TASKS 7 |
| APPENDIX B - BUILDINGS REQUIRING FIRE ALARM TESTING AND INSPECTION 8 |
| 1.1. DESCRIPTION OF SERVICES |
| 2.1 UTILITIES |
| Use of Government existing facilities will be permitted without metering and without payment of use charges, as long as facilities are cleaned and maintained in an acceptable condition. At Substantial Completion, restore these facilities to condition ... |
| 2.2 FIRE SERVICES |
| 3.1 DAMAGES TO GOVERNMENT BUILDINGS, EQUIPMENT OR VEGETATION |
| 3.4 RECOGNIZED HOLIDAYS |
| 3.5 TRAFFIC LAWS |
| 3.6 WEAPONS, FIREARMS, AND AMMUNITION |
| 3.7 GOVERNMENT INTERFACE |
| 3.8 SAFETY |
| 3.8.1 WRITTEN SAFETY PROGRAM |
| 3.9 WORKMANSHIP |
| 3.10 TOOLS |
| 3.11 TEST EQUIPMENT |
| 3.12 SANITARY FACILITIES |
| 3.13 PERSONNEL |
File details come from the government source that posted it. Updated .