This document is a Baseline Asbestos Assessment Survey for Building 500 at the Lake Baldwin Orlando VA Medical Center, conducted by Thunderbird-HRP JV, LLC in October 2024. The comprehensive survey identified multiple areas containing asbestos-containing materials (ACM), primarily on the first floor, including flooring materials, mastics, and duct insulation. Specifically, the assessment found approximately 5,028 square feet of mastic containing asbestos (5% Chrysotile) associated with vinyl floor tiles, and an additional 600 square feet of mosaic vinyl floor sheeting with asbestos in its backing.
The survey recommends that prior to any disturbance activities, confirmed and assumed ACM should be abated or provided with appropriate response actions. The report suggests treating any unsampled suspect materials as potentially containing asbestos until proven otherwise. Additionally, the survey recommends submitting a notification to the Florida Department of Environmental Protection at least 10 days before renovation/demolition, in accordance with state and federal regulations. The assessment was conducted following Veterans Health Administration (VHA) Directive 7714 and complies with OSHA and EPA asbestos management regulations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Baseline Asbestos Assessment Survey
Project Location: Building 500 – Main Clinic Lake Baldwin Orlando VA Medical Center 5201 Raymond Street, Orlando, FL 32083
Prepared for:
Rohan McKenzie and Robert Edwards Contracting Offcr. and Contracting Spc.
Department of Veterans Affairs Network Contracting Office 8 (NCO 8) Orlando VA Healthcare System 13800 Veterans Way, Orlando FL 32827
Prepared by:
Thunderbird-HRP JV, LLC 2500 S. Old Highway 94, Ste. 202 St. Charles, MO 63303
February 26, 2025
Baseline Asbestos Assessment Survey Orlando VA Medical Center: BLD 500 i
TABLE OF CONTENTS
EXECUTIVE SUMMARY ........................................................................................................... II
1. INTRODUCTION
1.1. Purpose
1.2. Scope of Services
1.3. Project Limitations
2. ASBESTOS BULK SAMPLING
2.1. Sampling Methodology
2.2. Non-Suspect Material(s)
3. SITE PROVIDED INFORMATION
3.1. Previous Assessment Activities
4. FINDINGS AND CONCLUSIONS
5. RECOMMENDATIONS
6. SIGNATURE PAGE
7. REFERENCES
TABLES
Table 1 Suspect ACM Sampling Information
FIGURES
Figure 1 1st Floor Sampling Locations Figure 2 2nd Floor Sampling Locations Figure 3 3rd Floor Sampling Locations Figure 4 4th Floor Sampling Locations Figure 5 Mezzanine Sampling Locations
APPENDICES
Appendix A Laboratory Analytical Reports Appendix B Photograph Log of Homogenous Areas Appendix C Asbestos Inspector Licenses ii
EXECUTIVE SUMMARY
Baseline Asbestos Assessment Survey
Assessment Location: Lake Baldwin Orlando VA Medical Center: Building 500 – Main Clinic, located at
13800 Veterans Way, Orlando, Florida, 32083 (referred to herein as “the Site”)
Purpose of Assessment: The Veterans Health Administration (VHA) Directive 7714 (Asbestos
Management Program), dated April 6, 2017, calls for a survey following requirements of the Asbestos
Hazard Emergency Response Act (AHERA), known as a baseline survey. The purpose of the baseline survey is to identify, quantify, and sample suspect asbestos containing material (ACM) throughout the building. The survey was conducted in accordance with the Occupational Safety and Health
Administration (OSHA) and the Environmental Protection Agency (EPA) regulations. Non-suspect materials, which are defined as materials that are not expected to contain asbestos, were not sampled or analyzed as part of this survey.
Assessment Activities: The baseline survey for Building 500 was conducted on October 24th through
October 28th, 2024, by Thunderbird-HRP JV, LLC (Thunderbird-HRP) accredited asbestos inspectors. The survey included collecting representative samples of suspect asbestos-containing materials (ACMs), assessing their condition, and quantifying the materials and hazards present throughout the building.
Samples were submitted to Arrowhead Technologies, LLC, in Clearwater, Florida, a National Voluntary
Laboratory Accreditation Program accredited laboratory (NVLAP code 200703-0), for analysis of asbestos content by the Polarized Light Microscopy (PLM) method. A summary of suspect materials included in the asbestos survey, with those reported to be ACM (if applicable) indicated in bold, is included in Table 1.
Key Findings
As detailed in Table 1, the following is provided as a summary of materials containing asbestos:
The 1st floor of Building 500 contains multiple flooring materials and mastics reported to contain asbestos and are identified as ACM. Specifically, HA-34, HA-38, HA-54, HA-56, HA-106 and HA-144 have mastic containing asbestos (approximately 5,028 square feet) with the associated vinyl floor tile containing no asbestos. HA-55 is a mosaic pattern LinoleumTM-type vinyl floor sheeting containing asbestos in the backing (approximately 600 square feet). Refer to Table 1 and Figure 1 for detailed sample descriptions and ACM locations.
The previous Asbestos Survey report conducted by OHC Environmental Engineering, dated
September 29, 2014 identified asbestos in Red Duct Mastic and Sink Undercoating in addition iii to the flooring materials and mastics identified in this report. The Red Duct Mastic and Sink
Undercoating on the first floor should be assumed positive.
Recommendations
Recommendations resulting from the Baseline Asbestos Assessment Survey include the following:
Prior to disturbance activities, any confirmed and/or assumed ACM should be abated or provided with appropriate response actions. These materials are summarized above and within
Section 4.0 of this report.
Additionally, any other suspect material not included in this report should be treated as ACM, and should not be disturbed until sampled, tested, and proven otherwise.
1. INTRODUCTION
Thunderbird-HRP was retained by the Orlando VA Healthcare System to conduct a baseline asbestos assessment survey for the Lake Baldwin Orlando VA Medical Center, Building 500 – Main Clinic, located at 5201 Raymond Street, Orlando, FL 32083 (hereinafter referred to as “the Site”). This included inspecting suspect flooring, wall, ceiling, duct and piping systems located in all areas of Building 500 (crawl space, Mezzanine, and Floors 1 – 4). The specific locations included in the survey are detailed in Section 2.0.
1.1. Purpose
The Veterans Health Administration (VHA) Directive 7714 (Asbestos Management Program), dated April
6, 2017, calls for a survey following requirements of the Asbestos Hazard Emergency Response Act
(AHERA), known as a baseline survey. The purpose of the baseline survey is to identify, quantify, and sample suspect asbestos containing material (ACM) throughout the building. The survey was conducted in accordance with the Occupational Safety and Health Administration (OSHA) and the Environmental
Protection Agency (EPA) regulations. Non-suspect materials, which are defined as materials that are not expected to contain asbestos, were not sampled or analyzed as part of this survey.
1.2. Scope of Services
This baseline asbestos assessment survey was performed using general procedures and protocols appearing in EPA 40 CFR, part 763 (AHERA Protocols), and included the following general components: (1)
Site walkthrough; (2) Identification, classification, and bulk sample collection of suspect ACM; and (3) interpretation of laboratory analytical results. The scope of services provided by Thunderbird-HRP included the following tasks:
Review of applicable regulatory standards on asbestos and pre-demolition/renovation requirements;
Coordination with a NVLAP accredited laboratory for bulk sample analysis;
Walkthrough of all areas of interest with the Site representatives and review the scope of the project;
Identification, classification, quantification, delineation, and bulk sample collection of suspect ACM which is present within the building; and
Interpretation of laboratory PLM analytical reports.
No significant scope-of-work additions or modifications other than those noted below.
1.3. Project Limitations
The following areas were not inspected due to inaccessibility, or at the request of the site contact:
Roof / Roofing materials, Building Exterior
CT Scan Addition – Under Construction
Beneath concrete floors , D
Behind or inside concrete, masonry, cementitious, rigid, or CMU Walls or Parapets or CMU walls and cavities (loose fill insulation)
Confined Wall and floor utility chases, pipe chases and/or tunnels, inside/behind walls and wall cavities, pipe/utility trenches, etc vinyl/metal windows/casings (caulking & glazing)
Mirror Glue (in Restrooms)
Room 1720, 266 & 272, Clean Rooms – Above the ceiling and under the vinyl tile was not inspected.
If any additional materials other than those sampled and reported in this survey are identified within the building, they should be treated as asbestos-containing until proven otherwise via sampling and analysis in accordance with applicable regulations.
2. ASBESTOS BULK SAMPLING
The baseline survey for Building 500 was conducted on October 24th through October 28th, 2024, by
Thunderbird-HRP accredited asbestos inspectors. The survey included collecting representative samples of suspect asbestos-containing materials (ACMs), assessing their condition, and quantifying the materials and hazards present throughout the building.
2.1. Sampling Methodology
Thunderbird-HRP personnel systematically inspected the Site building as described above, and specified by the Site representatives. During the survey, Thunderbird-HRP classified each suspect ACM as one (1) of three (3) types:
Surfacing Materials - ACM sprayed or troweled on surfaces (walls, ceilings, structural members) for acoustical, decorative, or fireproofing purposes.
Thermal System Insulation (TSI) - Insulation used to inhibit heat transfer or prevent condensation on pipes, boilers, tanks, ducts, and various other components of hot and cold-water systems and heating, ventilation, and air conditioning (HVAC) systems. This includes pipe lagging, pipe wrap;
block, batt, and blanket insulation; cements and “muds”; and a variety of other products such as gaskets and ropes; or, Miscellaneous Material – Other, largely non-friable products and materials such as flooring, floor tile, ceiling tile, roofing felt, concrete pipe, outdoor siding, and fabrics.
Thunderbird-HRP inspectors touched all suspect materials to determine the extent to which the material, when dry, may be crumbled, pulverized, or reduced to powder by hand. During the survey, suspect materials identified by the inspector were also evaluated for overall condition, and each suspect material was assigned a condition of significantly damaged, damaged, or good overall condition for the locations the materials were observed. As defined by the US EPA under Asbestos Hazard Emergency Response Act
(AHERA), a material is significantly damaged if ten percent (10%) or greater of the material is evenly deteriorated, crumbling, hanging, or if the material contains over 25% localized damage. A damaged material is one that has less than 10% evenly distributed damage or less than 25% localized damage. A material in good condition is a material with no visible damage or deterioration or showing only very limited damage or deterioration.
Each suspect ACM was also classified into a homogeneous sampling area (HA). An HA is an area which is uniform in texture and appearance, was likely installed during the same period, and is unlikely to consist of more than one type or formulation of material. Thunderbird-HRP inspectors collected samples of each material from each HA, with multiple samples of a single material collected as appropriate. Samples were not collected from materials that were readily identifiable as non-asbestos containing (i.e., wood, fiberglass, foam, rubber, paper wraps, etc.) or previously confirmed to be asbestos containing (if applicable).
To avoid disturbing the material any more than necessary and to minimize any unnecessary release of potential asbestos fibers during collection, Thunderbird-HRP’s inspectors performed bulk sampling of suspect ACM in accordance with generally accepted procedures outlined in the US EPA document
"Guidance for Controlling Asbestos-Containing Materials in Buildings" (EPA-560/5-85-024, June 1985).
Each sample was collected using wet methods and placed in clean, sealable plastic bags and labeled with a unique sample identification number.
Bulk samples were submitted to Arrowhead Technologies, LLC, in Clearwater, Florida, a National Voluntary
Laboratory Accreditation Program accredited laboratory (NVLAP code 200703-0), for analysis of asbestos content by the Polarized Light Microscopy (PLM) method.
2.2. Non-Suspect Material(s)
Non-suspect materials, which are defined as materials that are not expected to contain asbestos, were not sampled or analyzed. Non-suspect materials typically include general building materials (e.g., glass, metals, brick, fiberglass, concrete, wood, cinderblock, and rubber). Please note that if a suspect material is later identified on-site and is not among those materials identified in this report, that material must be assumed to be asbestos containing until sampled and proven otherwise. Refer to Table 1 for Suspect ACM
Sampling Information.
3. SITE PROVIDED INFORMATION
During this assessment, Site contacts provided Thunderbird-HRP with access to individual areas of the building.
3.1. Previous Assessment Activities
Site contacts provided Thunderbird-HRP with the following ACM survey:
ASBESTOS NESHAP SURVEY, Orlando Veterans Administration Medical Center, Building 500, 5201
Raymond Street, Orlando, Florida conducted by OHC Environmental Engineering, dated
September 29, 2014
4. FINDINGS AND CONCLUSIONS
The 1st floor of Building 500 contains multiple flooring materials and mastics reported to contain asbestos and are identified as ACM. Specifically, HA-34, HA-38, HA-54, HA-56, HA-106 and HA-144 have mastic containing asbestos (approximately 5,028 square feet) with the associated vinyl floor tile containing no asbestos. HA-55 is a mosaic pattern vinyl floor sheeting containing asbestos in the backing (approximately 600 square feet). Refer to Table 1 and Figure 1 for detailed sample descriptions and ACM locations.
The previous Asbestos Survey report conducted by OHC Environmental Engineering, dated
September 29, 2014, identified asbestos in Red Duct Mastic and Sink Undercoatings in addition to the flooring materials and mastics identified in this report. The Red Duct Mastic and Sink
Undercoatings on the first floor should be assumed positive.
Figures depicting sample locations are provided in Figure 1 (1st Floor), Figure 2 (2nd Floor), Figure 3 (3rd
Floor), Figure 4 (4th Floor) and Figure 5 (Mezzanine). The complete asbestos laboratory analytical reports are provided in Appendix A. A photograph log depicting each homogeneous sampling area is provided in
Appendix B, and Thunderbird/HRP inspector’s license documentation is provided in Appendix C.
5. RECOMMENDATIONS
Based on the findings of the baseline asbestos assessment survey documented in this report, Thunderbird-
HRP recommend the following:
Prior to disturbance activities, any confirmed and/or assumed ACM should be abated or provided with appropriate response actions. These materials are summarized above and within Section 4.0 of this report.
Additionally, any other suspect material not included in this report should be treated as ACM, and should not be disturbed until sampled, tested, and proven otherwise.
In accordance with Federal and State of Florida rules, Thunderbird-HRP recommends that a notification and a copy of this report be submitted to the Florida Department of Environmental
Protection (FDEP) at least 10 days prior to the onset date of renovation/demolition. The FDEP prefers that the notification be delivered via email at the following web link:
o http://www.fldepportal.com/go/submit-registration/
Correspondence or questions may be addressed by the FDEP’s Central District office o Asbestos Program Director
Florida Department of Environmental Protection
Central District
3319 Maguire Boulevard
Suite No. 232
Orlando, Florida 32803 p: 407.897.4100
6. SIGNATURE PAGE
Thunderbird-HRP, with over 40 years of combined experience in environmental consulting, certifies that the baseline asbestos assessment survey documented in this report has been completed in accordance with the NESHAP and AHERA current regulations and requirements.
EPA
Accredited
Expiration.
Date
Signature Date
Survey Conducted and Report Written by:
Mr. Adam Marenholz
25-5606- 106-277914 1/3/26
2/26/25
Survey Conducted and Report Written by:
Mr. William Swain
25-5606- 106-503921 1/3/26
Survey Conducted and Report Written by:
Mr. Richard Cwiklowski, P.E.
Senior Project Manager
STC-
20240202-
003751ABIR
2/2/25
Signature Date
Report Reviewed by:
Mr. John Stump, PG, LAC Primary Qualifying Agent HRP Associates, Inc.
Asbestos Business Organization ZA473
Report Issued by:
Darby W. Hittle, L.E.P Thunderbird Environmental LLC.
President/Owner
Rick.Cwiklowski Placed Image
7. REFERENCES
Code of Federal Regulations Title 40, Chapter 1, Subpart C, Part 61, Subpart M (https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-61/subpart-M).
United States Environmental Protection Agency, Asbestos and School Buildings (https://www.epa.gov/asbestos/asbestos-and-school-buildings).
VHA Directive 7714, Asbestos Management Program, Department of Veterans Affairs, April 6, 2017.
TABLE(S)
Baseline Asbestos Assessment Survey Orlando VA Medical Center: BLD 500
Table 1 of 9
TABLE 1: SUSPECT ACM SAMPLING INFORMATION (BUILDING 500)
HA #* Sample IDs Material Description Material Locations
Sample Locations Type, Condition Friable (Y/N)
Approx.
Quantity
ACM
(Y/N)
Asbestos Type
HA-1 HA-1- A,B,C,D,E White mastic (on duct insulation) 1st, 2nd, and
4th Floor
A – Room 403 (Group Room #1) B – Room 418 (office room) C – Room 440 (Server Room) D – Room 1807 E – Room 219
Misc., Good N _ N ND
HA-2 HA-2-A, B, C Yellow mastic (located beneath 12” x 12” Grey carpet)
4th Floor A – Room 403 (Group Room #1) B – Room 418 (office room) C – Room 442 (Teamwork Zone)
Misc., Good N
N ND
HA-3 HA-3-A, B, C, D 2’ x 2’ white lay-in ceiling tile 4th Floor
A – Room 403 (Group Room #1) B – Room 418 (office room) C – Room 424 (Restroom) D – Room 440 (Server Room)
Misc., Good N
N ND
HA-4 HA-4-A, B Grey mastic (on duct) 4th Floor A – Room 424 (Restroom) B – Room 457 (Restroom)
Misc., Good N
N ND
HA-5 HA-5-A, B, C
White drywall
4th Floor A – Room 424 (Restroom) B – Room 433 (Breakroom) C – Room 457 (Restroom)
Misc. Cat. 2, Good
Y
_ N ND
white joint compound N ND
HA-6 HA-6-A, B, C
Grey cove base
4th Floor A – Room 433 (Breakroom) B – Room 440 (Server Room) C – Room 467 (Storage Room)
Misc., Good N
_ N ND
Tan mastic N ND
HA-7 HA-7-A, B, C
2’ x 4’ tan vinyl tile w/ grey streaks
4th Floor A – Room 433 (Breakroom) B – Room 467 (Storage Room) C – Checkout Area (409)
Misc., Good N
_ N ND
Grey mastic N ND
HA-8 HA-8-A,B,C,D,F
Red mastic (located on piping in plenum space / walls) 1st, 3rd & 4th
Floor
A – Public Corridor (408) B – Room 333 (IT Room) C – Room 333 (IT Room) D – Room 1807 (Stairwell) F – Room 1121 (Utility Closet)
Misc., Good N
_ N ND
HA-9 HA-9-A,B,C
White drywall
3rd Floor A – Room 305 (Group Room #2B) B – Room 303 (Group Room #1B) C – Room 314 (Restroom)
Misc. Cat. 2, Good
Y
_ N ND
White joint compound N ND
HA-10 HA-10-A,B,C White mastic (on duct insulation) 3rd Floor A – Room 305 (Group Room #2B) B – Room 303 (Group Room #1B) C – Room 314 (Restroom)
Misc., Good N
N ND
HA-11 HA-11-A,B,C
Yellow mastic
(located beneath 12” x 12” blue carpet) 3rd Floor A – Room 305 (Group Room #2B) B – Room 303 (Group Room #1B) C – Room 339 (Office 44)
Misc., Good N
N ND
Baseline Asbestos Assessment Survey Orlando VA Medical Center: BLD 500
Table 2 of 9
HA #* Sample IDs Material Description Material Locations Sample Locations
Type, Condition
Friable (Y/N)
Approx.
Quantity
ACM
(Y/N) Asbestos Type
HA-12 HA-12-A,B,C 2’ x 2’ white in-lay ceiling tile 3rd Floor A – Room 305 (Group Room #2B) B – Rm 303 (Group Room #1B) C – Room 314 (Restroom)
Misc., Good Y
N ND
HA-13 HA-13-A,B,C Grey mastic on duct 3rd Floor A – Room 314 (restroom) B – Room 330 (Restroom) C – Room 306 (Restroom)
Misc., Good N
N ND
HA-14 HA-14-A,B,C,D Pinkish red fire caulk 3rd and 1st
Floor
A – Room 333 (IT Room) B – Room 333 (IT Room) C – Room 333 (IT Room) D – Room 1715 (Prep Area)
Misc., Good N
HA-15 HA-15-A Green mastic (located around PVC piping) 3rd Floor A – Room 333 (IT Room) Misc., Good N _ N ND
HA-16 HA-16-A,B,C
Grey cove base
3rd Floor A – Room 331 (Breakroom) B – Room 339 (Office 44) C – Room 375 (Mail Room)
Misc., Good N
_ N ND
Tan mastic N ND
HA-17 HA-17-A,B
2’ x 2’ tan, grey streaked vinyl floor tile
3rd Floor A – Room 331 (Breakroom) B – Room 375 (Mailroom)
Misc., Good N
_ N ND
grey mastic N ND
HA-18 HA-18-A Off-white mastic on air duct insulation Mezzanine A – mezzanine air duct insulation Misc., Good N _ N ND
HA-19 HA-19-A,B,C White mastic Mezzanine A,B,C – mezzanine air duct insulation Misc., Good N _ N ND
HA-20 HA-20-A,B,C Grey mastic Mezzanine A,B,C – mezzanine air duct insulation Misc., Good N _ N ND
HA-21 HA-21-A,B,C Dark grey mastic Mezzanine A,B,C – located on corner of air handling Unit 11 Misc., Good N
N ND
HA-22 HA-22-A,B Red mastic Mezzanine A,B – located around PVC piping through floor
Misc., Good N
N ND
HA-23 HA-23-A
White drywall
Mezzanine A – mezzanine western wall Misc. Cat. 2, Good Y
_ N ND
White joint compound N ND
HA-24 HA-24-A,B,C White mastic on air duct insulation 1st Floor (VBA) A – Room 1215 (Office 3) B – Room 1015 (Office 16) C – Room 1017 (File Room)
Misc., Good N
N ND
HA-25 HA-25-A,B,C 2’ x 2’ white, smooth in-lay ceiling tile 1st Floor (VBA) A – Room 1215 (Office 3) B – Room 1015 (Office 16) C – Room 1017 (File Room)
Misc., Good N
N ND
HA-26 HA-26-A,B,C
Clear mastic
(Located beneath grey/cracked blue carpet and black rubber backing)
1st Floor (VBA) A – Room 1215 (Office 3) B – Room 1015 (Office 16) C – Room 1032 (Conference Room)
Misc., Good N
Baseline Asbestos Assessment Survey Orlando VA Medical Center: BLD 500
Table 3 of 9
HA #* Sample IDs Material Description Material Locations Sample Locations
Type, Condition
Friable (Y/N)
Approx.
Quantity
ACM
(Y/N) Asbestos Type
HA-27 HA-27-A,B,C
Off-white drywall
1st Floor (VBA) A – Room 1215 (Office 3) B – Room 1015 (Office 16) C – Room 1017 (File Room)
Misc. Cat. 2, Good Y
_ N ND
White joint compound N ND
HA-28 HA-28-A,B,C
Grey cove base
1st Floor (VBA) A – Room 1215 (Office 3) B – Room 1015 (Office 16) C – Room 1017 (File Room)
Misc., Good N
_ N ND
Clear / grey mastic N ND
HA-29 HA-29-A,B,C,D Red fire caulk 1st Floor (VBA) A,B,C – Room 1017 (File Room; on wall above plenum space) D – Hallway outside Room 1600A
Misc., Good N
N ND
HA-30 HA-30-A,B,C
3’ x 3’ grey splotched vinyl floor tile
1st Floor (VBA) A – Room 1017 (File Room) B,C – Room 1056 (Breakroom)
Misc., Good N
_ N ND
Red mastic N ND
HA-31 HA-31-A,B,C
Brown laminate plank flooring
1st Floor (VBA) A – Room 1048 (Copier Area) B – Room 1044C (Office Cubicle) C – Corridor 1002 (by swing doors)
Misc., Good N
_ N ND
Red mastic N ND
HA-32 HA-32-A,B,C Clear mastic (under dark grey carpet with purple cracks design)
1st Floor (VBA) A – Room 1044B (Office Cubicle) B – Room 1044C (Office Cubicle) C – Room 1044E (Office Cubicle)
Misc., Good N _ N ND
HA-33 HA-33-A,B,C,D 2’ x 2’ white fissured ceiling tile 1st Floor (Store)
A – Room 1815 (Storage Room) B – Room 1815A (Storage Room) C – Room 1815A (Storage Room) D – Room 1516A
Misc., Good Y _ N ND
HA-34 HA-34-A,B,C,D,E
12” x 12” white w/ grey marble vinyl floor tile
1st Floor
A – Room 1815 (Storage Room) B – Room 1815 (Storage Room) C – Room 1815 (Storage Room) D – Room 1127 (Exam Room) E – Room 1123B
Misc., Good N 2,000 SF
N ND
Black mastic Y 5% Chrysotile
HA-35 HA-35-A,B,C,D
White drywall
1st Floor A,B,C – Room 1815A (Storage Room) D – Hallway outside Room 1600A
Misc. Cat. 2, Good Y _
N ND
White joint compound N ND
HA-36 HA-36-A,B,C Red fire caulk 1st Floor (Store)
A – Room 1815 (Storage Room) B – Room 1815 (Storage Room) C – Room 1815A (Storage Room)
Misc., Good N _ N ND
HA-37 HA-37-A,B,C
12” x 12” white vinyl floor tile 1st Floor
(Store) A,B,C – Room 1815A (Storage Room) Misc., Good N _
N ND
Yellow mastic N ND
HA-38 HA-38-A,B,C
12” x 12” white vinyl floor tile (beneath HA-37)
1st Floor A,B – Room 1815A (Storage Room) C – Room 1516A Misc., Good N 2,000 SF black mastic Y 5% Chrysotile
Baseline Asbestos Assessment Survey Orlando VA Medical Center: BLD 500
Table 4 of 9
HA #* Sample IDs Material Description Material Locations Sample Locations
Type, Condition
Friable (Y/N)
Approx.
Quantity
ACM
(Y/N) Asbestos Type
HA-39 HA-39-A,B,C
Grey cove base 1st Floor
(Store)
A – Room 1815A (Storage Room) B – Room 1815A (Storage Room) C – Room 1815 (Storage Room)
Misc., Good N _
N ND
Tan mastic N ND
HA-40 HA-40-A,B,C
Brown “wood” plank laminate flooring 1st Floor
(Store) A,B,C – Room 1708 (Store) Misc., Good N _
N ND
Yellow/black mastic N ND
HA-41 HA-41-A,B,C,D 2’ x 2’ white smooth in-lay ceiling tile 1st Floor A,B,C – Room 1711C (Dining Room) D – Hallway outside Room 1600A Misc., Good Y _ N ND
HA-42 HA-42-A,B,C
Beige cove base 1st Floor
(Dining Room) A,B,C – Room 1711C (Dining Room) Misc., Good N _ N ND
Yellow mastic
HA-43 HA-43-A,B,C,D,E,F White mastic on duct insulation 1st Floor
A,B,C – Room 1711C (Dining Room) D – Storage Room (Pharmacy) E – Room 1340C F – Room 142 (IT Room)
Misc., Good N _ N ND
HA-44 HA-44-A,B,C,D,E,F
White drywall
1st Floor
A,B,C – Room 1711C (Dining Room) D – Room 1340C E – Room 1801B F – Room 1704
Misc. Cat. 2, Good Y _ N ND
White joint compound
HA-45 HA-45-A,B,C Grey mastic on duct 1st Floor
(Dining Room) A,B,C – Mechanical Room within Dining Room (1711C)
Misc., Good N _ N ND
HA-46 HA-46-A,B,C,D,E 2’ x 2’ white fissured ceiling tile 1st Floor
(Dining Room)
A,B,C – Room 1711C (Dining Room) D – Room 1801B E – Room 1704
Misc., Good N _ N ND
HA-47 HA-47-A,B,C 2’ x 2’ white vinyl ceiling tile 1st Floor A – Room 1728 B – Room 1807 (Stairwell) C – Room 1817 (Storage)
Misc., Good N _ N ND
HA-48 HA-48-A Tan mastic on duct insulation 1st Floor A – Room 1728 Misc., Good N _ N ND
HA-49 HA-49-A,B,C,D,E,F
White drywall
1st Floor
A – Room 1728 B – Room 1827 C – Room 1827 D – Room 1715 (Prep Area) E – Room 1715 (Beverages Area) F – Room 1309J
Misc. Cat. 2, Good
Y _
N ND
White/grey joint compound N ND
HA-50 HA-50-A
12” x 12” white vinyl floor tile
1st Floor A – Room 1728
Misc., Good N _
Yellow mastic N ND
Baseline Asbestos Assessment Survey Orlando VA Medical Center: BLD 500
Table 5 of 9
HA #* Sample IDs Material Description Material Locations
Sample Locations Type, Condition Friable (Y/N)
Approx.
Quantity
ACM
(Y/N)
Asbestos Type
HA-51 HA-51-A,B,C
Black cove base
1st Floor A – Room 1728 B – Room 1720C (Women’s Locker) C – Room 1827
Misc., Good N _
N ND
Clear/tan mastic N ND
HA-52 HA-52-A,B,C,D,E 2’ x 2’ white fissured (older) ceiling tile 1st Floor
(Dining Room)
A – Room 1727 B,C – Room 1827 D – Room 1715 (Prep Area) E – Room 1309J
Misc., Good Y
HA-53 HA-53-A
Tan cove base
1st Floor A – Room 1727 Misc., Good N _
N ND
Yellow mastic N ND
HA-54 HA-54-A,B,C
Yellow mastic (located beneath 2’ x 2’ green carpet – black backing)
1st Floor A – Room 1727 B – Room 1720C (Women’s Locker) C – Room 1827
Misc., Good N 800 SF
N ND
12” x 12” white vinyl floor tile N ND Black mastic Y 3% Chrysotile
HA-55 HA-55-A,B,C,D
HA-55-A,B only: yellow mastic (located beneath 12” x 12” green carpet – black backing)
1st Floor A,B – Room 1727A C – 1720CA (Restroom) D – Room 1118
Misc., Good N 600 SF
N ND
Mosaic white/tan vinyl floor sheeting Y 30% Chrysotile Yellow mastic N ND
HA-56 HA-56-A
Yellow mastic (located beneath green carpet)
1st Floor A – Room 1727B Misc., Good N 120 SF
N ND
12” x 12” grey vinyl floor tile N ND Brown mastic Y 5% Chrysotile
HA-57 HA-57-A,B,C
Light brown faux wood linoleum planking
1st Floor A – 1721 Loading Dock Hallway B – 1721 Loading Dock Hallway C – 1721 Hallway (outside Canteen)
Misc., Good N _
N ND
Yellow mastic N ND
HA-58 HA-58-A,B
Dark grey cove base
1st Floor A – Room 1712 (Canteen Office) B – Room 1715B
Misc., Good N _
N ND
Tan mastic N ND
HA-59 HA-59-A,B,C
12” x 12” white vinyl tile (located under HA-60)
1st Floor A – Room 1712 (Canteen Office) B – Room 1715B C – Room 1715A
Misc., Good N _
N ND
Yellow mastic N ND Grey levelling compound N ND
HA-60 HA-60-A,B,C
12” x 12” grey streaked linoleum tile
1st Floor A – Room 1712 (Canteen Office) B – Room 1621 (Admin Office) Misc., Good N _
N ND
Clear / yellow mastic N ND
HA-61 HA-61-A,B,C
Black, tall cove base
1st Floor A – Room 1715 (Chef Area) B – Room 1715C C – Room 1715M
Misc., Good N _
N ND
Yellow mastic N ND
HA-62 HA-62-A 2’ x 4’ grey splotched linoleum tile 1st Floor A – Room 1715B Misc., Good N _ N ND
HA-63 HA-63-A,B,C
Tan cove base
1st Floor A – Room 1715B B – Room 1715B C – Room 1715B
Misc., Good N _
White mastic N ND
Baseline Asbestos Assessment Survey Orlando VA Medical Center: BLD 500
Table 6 of 9
HA #* Sample IDs Material Description Material Locations
Sample Locations Type, Condition
Friable (Y/N)
Approx.
Quantity
ACM
(Y/N)
Asbestos Type
HA-64 HA-64-A,B,C Tan mastic under wall vinyl sheeting 1st Floor A,B,C – Room 1715 (Paper Goods Storage) Misc., Good N _ N ND
HA-65 HA-65-A,B
12” x 12” white vinyl floor tile (thin)
1st Floor A,B – Room 1715R Misc., Good N _
N ND
Grey mastic N ND
HA-66 HA-66-A,B,C
White drywall
1st Floor A – Room 1602 (Classroom) B – Room 1612A (Copy Room) C – Room 1621
Misc. Cat. 2, Good
N _
N ND
white joint compound N ND
HA-67 HA-67-A,B,C
Grey cove base (tall)
1st Floor A – Room 1601 B – Room 1620 (Board Room) C – Room 1611
Misc., Good N _
N ND
Yellow mastic N ND
HA-68 HA-68-A
White leveling compound (located beneath red/blue carpet) 1st Floor A – Room 1621A (Copy Room) Misc., Good N _ N ND
HA-69 HA-69-A Yellow mastic (located beneath red/blue carpet) 1st Floor A – Room 1621A (Copy Room) Misc., Good N _ N ND
HA-70 HA-70-A,B,C,D,E,F Yellow mastic (located beneath 2’ x 2’ blue and white lined carpet)
1st Floor
A – Room1622 (VAM Room) B – Room 1620 (Board Room) C – Room 1617 (Offices) D – Room 1801B E – Room 1704 F – Room 1703
Misc., Good N _ N ND
HA-71 HA-71-A,B,C
Grey cove base (short)
1st Floor A – Room 1607C B – Room 1704 C – Room 1704
Misc., Good N _
N ND
Tan mastic N ND
HA-72 HA-72-A,B,C
Tan cove base
1st Floor A – Room 1616 B – Room 1607 C – Room 1607
Misc., Good N _
N ND
Yellow mastic N ND
HA-73 HA-73-A
Brown plank linoleum flooring
1st Floor A – Room 1607C (HAS Supervisor) Misc., Good N _ N ND Yellow mastic
HA-74 HA-74-A
2’ x 4’ off-white vinyl tile
1st Floor A – Room 1611 (Office) Misc., Good N _
N ND
Yellow mastic N ND
HA-75 HA-75-A,B,C 2’ x 2’ white in-lay ceiling tile 1st Floor A – Room 1802 (interview Room) B – Room 1806 C – Room 1807
Misc., Good N _ N ND
HA-76 HA-76-A,B,C,D
White drywall
1st Floor
A – Room 1802 B – Room 1806 C – Room 1807 D – Pharmacy Storage Room
Misc. Cat. 2, Good Y _
White joint compound N ND
Baseline Asbestos Assessment Survey Orlando VA Medical Center: BLD 500
Table 7 of 9
HA #* Sample IDs Material Description Material Locations
Sample Locations Type, Condition Friable (Y/N)
Approx.
Quantity
ACM
(Y/N)
Asbestos Type
HA-77 HA-77-A,B,C
2’ x 2’ grey streaked vinyl floor tile
1st Floor A – Room 1802 B – Room 1806 C – Room 1810 (Kitchen Fridge)
Misc., Good N _
N ND
Yellow mastic N ND
HA-78 HA-78-A,B,C
Grey cove base (tall)
1st Floor A – Room 1802 B – Room 1806 C – Room 1807 (Stairwell)
Misc., Good N _
N ND
Tan mastic N ND
HA-79 HA-79-A,B,C
Grey mastic (located under grey carpet with orange lines)
1st Floor A – Room 1807 (Comm. Field Staff) B – Room 1812A C – Room 1814A
Misc., Good N _
N ND
Grey leveling compound N ND
HA-80 HA-80-A,B,C
Light grey linoleum floor sheeting
1st Floor A – Room 1807 (Stairwell) B – Room 1807 (Stairwell) C – Room 112
Misc., Good N _
N ND
Yellow mastic N ND
HA-81 HA-81-A,B,C
3’ x 3’ white with black swirled vinyl floor tile
1st Floor A – Room 1817/1824 (MSD Storage) B – Room 1817/1824 (MSD Storage) C – Room 1126 (Emerg. Treatment)
Misc., Good N _
N ND
Yellow mastic N ND
HA-82 HA-82-A,B,C,D
Greyish/pink cove base
1st Floor A – Room 117 (Lounge) B – Room 118 (Restroom) C – Room 120
Misc., Good N _
N ND
Yellow mastic N ND
HA-83 HA-83-A,B,C
12” X 12” white, grey speckled vinyl floor tile
1st Floor A – Room 117 B – Room 118 C – Area outside Pharmacy Workroom
Misc., Good N _
N ND
Yellow mastic N ND
HA-84 HA-84-A,B,C
Brown vinyl plank flooring 1st and 2nd
Floor
A – Room 120 B – Room 120 C – Room 260
Misc., Good N _
N ND
Clear/yellow mastic N ND
HA-85 HA-85-A
2’ x 2’ tan, white brushed vinyl tile 1st Floor
(Pharmacy) A – Pharmacy Storage Room Misc., Good N _
N ND
Yellow mastic N ND
HA-86 HA-86-A
Clear mastic (located beneath grey and tan carpet) 1st Floor
(Pharmacy) A – Pharmacy Workroom Misc., Good N _ N ND
HA-100 HA-100-A,B,C,D
Vinyl blue, white, and black floor sheeting
1st Floor A,B – Room 1340C (Physical Therapy) C,D – Room 1213D
Misc., Good N _
N ND
Pinkish red mastic N ND
HA-101 HA-101-A,B,C,D
Tan with grey textured floor coating
1st Floor
A – Room 1213J B – Room 1213F C – Room 1214C D – Room 1430
Misc., Good N _ N
ND
Tan Mastic ND
Baseline Asbestos Assessment Survey Orlando VA Medical Center: BLD 500
Table 8 of 9
HA #* Sample IDs Material Description Material Locations
Sample Locations Type, Condition Friable (Y/N)
Approx.
Quantity
ACM
(Y/N)
Asbestos Type
HA-102 HA-102-A,B,C
Teal carpet mastic (located beneath grey/white carpet with black backing) 1st Floor A,B – Room 1214 C – Room 1304B Misc., Good N _ N ND
HA-103 HA-103-A,B,C,D
12” x 12” white speckled vinyl floor tile
1st Floor
A – Room 1309E B – Room 1309D C – Room 1309H D – Room 1113 (Kitchen)
Misc., Good N _
N ND
Yellow mastic N ND
HA-104 HA-104-A,B,C
Blue cove base
1st Floor A,B,C – Room 1309D Misc., Good N _
N ND
Yellow mastic N ND
HA-105 HA-105-A,B Black dental lab countertop 1st Floor A,B – Room 1306C (Dental Lab) Misc., Good N _ N ND
HA-106 HA-106-A,B,C
12” x 12” older white vinyl floor tile
1st Floor A,B,C – Room 1306 (HVAC Closet) Misc., Good N 8 SF
N ND
Black mastic Y 5% Chrysotile
HA-107 HA-107-A
Black cove base
1st Floor A – Room 1306 Misc., Good N _
N ND
Brown mastic N ND
HA-108 HA-108-A,B,C
1’ X 2’ grey streaked vinyl floor tile
1st Floor A – Room 1604 B – Room 1604A C – Room 1604C
Misc., Good N _
N ND
Greyish/yellow mastic N ND
HA-109 HA-109-A,B,C 2’ x 2’ white acoustic ceiling tile 1st Floor A,B,C – Room 1604 Misc., Good N _ N ND
HA-110 HA-110-A,B,C
3’ x 4’ grey brushed vinyl floor tile
1st Floor A,B,C – Room 1606 (Police Locker Room)
Misc., Good N _
N ND
Yellow mastic N ND
HA-111 HA-111-A,B,C,D
Blue vinyl floor sheeting (grey stencils)
1st Floor A,B,C – Room 1121 (Reception) D – Room 1459
Misc., Good N _
N ND
Grey mastic N ND
HA-112 HA-112-A,B
Grey laminate flooring
1st Floor A,B – Room 1097 (Xray Room) Misc., Good N _ N ND Yellow mastic
HA-113 HA-113-A,B,C
White laminate flooring
1st Floor A – Room 1097 (Xray Room) B – Room 1100 C – Room 1097
Misc., Good N _ N ND Yellow mastic
HA-114 HA-114-A,B
12” x 12” dark grey vinyl floor tile
1st Floor A,B – Room 1100 Misc., Good N _
N ND
Yellow mastic N ND
HA-115 HA-115-A,B,C
0.5’ x 2.5’ grey vinyl plank flooring
1st Floor A,B,C – Room 1076 (Radiology Reception)
Misc., Good N _
N ND
Orange mastic N ND
HA-116 HA-116-A,B,C
Brown/grey vinyl floor sheeting
1st Floor A,B – Room 125 C – Hallway outside Room 121
Misc., Good N _
N ND
Green/yellow mastic N ND
HA-117 HA-117-A,B,C
Grey speckled vinyl sheeting
2nd Floor A – Room 229L B – Room 229M C – Room 228
Misc., Good N _
Grey mastic N ND
Baseline Asbestos Assessment Survey Orlando VA Medical Center: BLD 500
Table 9 of 9
HA #* Sample IDs Material Description Material Locations
Sample Locations Type, Condition Friable (Y/N)
Approx.
Quantity
ACM
(Y/N)
Asbestos Type
HA-118 HA-118-A,B,C
2’ x 2’ tan streaked vinyl floor tile
2nd Floor A – Room 203C B – Room 205 C – Room 201
Misc., Good N _
N ND
Yellow/grey mastic N ND
HA-119 HA-119-A,B,C 2’ x 4’ white ceiling tile 2nd Floor A,B,C – Room 219 Misc., Good Y _ N ND
HA-120 HA-120-A,B,C
White drywall
2nd Floor A – Room 219 B – Room 205 C – Hallway outside Room 217
Misc. Cat. 2, Good N _
N ND
White joint compound N ND
HA-121 HA-121-A,B,C
Off-white streaked vinyl floor sheeting
2nd Floor A – Room 210 B – Room 209A C – Room 217
Misc., Good N _ N ND Grey mastic
Grey leveling compound Yellow mastic
HA-127 HA-127-A Black epoxy flooring 1st Floor A – Room 1510 Misc., Good N _ N ND
HA-128 HA-128-A,B,C
Yellow carpet mastic (located beneath grey camo and grey carpets) 1st Floor
A – Room 1495 (Office) B – Room 1460 C – Room 1453
Misc., Good N _ N ND
HA-129 HA-129-A,B,C 2’ x 2’ white ceiling tile 1st Floor A – Room 1438 B – Room 1451 C – Corridor E105
Misc., Good Y _ N ND
HA-142 HA-142-A,B,C Grey fireproofing Spray-Applied Crawl Space A,B,C – crawl space on ceiling Surfacing, Good N _ N ND
HA-143 HA-143-A,B,C Tan mastic on piping Crawl Space A,B,C – crawl space on piping Misc., Good N _ N ND
HA-144 HA-144-A,B,C
White carpet mastic (beneath grey, white carpet)
1st Floor A,B,C – Room 1703A Misc., Good N 100 SF
N ND
12” x 12” white, grey speckled floor tile N ND Black/yellow mastic Y 2% Chrysotile
Homogeneous sampling areas identified in this table are based on information observed at the site. Material locations and total quantities for each suspect material were estimated at the discretion of the survey inspector(s) based on only observations during the survey. These should not be construed with total locations/quantities for the site building. Quantities and locations of underlying materials such as mastics should also be confirmed at the time of abatement due to difficulty with field confirmation as estimates are based on only those locations sampled during the inspection.
*Homogeneous areas 87-99, 122-126, and 130-141 are not included in this report as they pertain to other buildings on-site.
Bold: Signifies asbestos detected >1% ND: No Asbestos Content Detected
FIGURES
OVERALL FLOOR PLAN - BUILDING 500 - FLOOR: 01
SCALE: 3/128"=1'-0"
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD FD FD FD
FD
FD
FD
FD
FD
FD
FD
FD
DRAW
DRAW
DRAW
DRAW
DRAW
PHLEBOLOMY
SUP CLOSET
M TLT
W TLT
M TLT
W TLT
STAFF TLT
CLEAN
STAFF
LACACTION
ROOM
PROCESSING
SUPPLY CLOSET
STAFF
ENTRY/EXIT
SPECIMAN
PROCESS
FRONT DESK/
SPEC LOG-IN
LC
KR
LO
C
KE
R
S
DRAW
BARIC DRAW
TLT M
TLT W
BREAK ROOM
RECLINED DRAW
DRAW
VOLUNTEER INFO
CENTER
FR
ID
G E
LO
C
KE
R
S
ERG International
1999/XC
ERG International
ERG International
TV
TV
1208 ERG International
362P ERG International
ERG International
1208 ERG International
ERG International
COR2460 ERG International
COR2460 ERG International
DN
REF.
DN
BREAKROOM
OPEN OFFICE
INTERVIEW 1812A
INTERVIEW
1802A
INTERVIEW
1802 IT
PROGRAM
SUPERVISOR
PROGRAM
SUPERVISOR
OUTREACH
STORAGE
1814E
UNISEX
ELEC
1802E
ELEC
1802D
WORK AREA
1807A WORK AREA
1814A
NE LOADING
DOCK
WAITING
1800A
RECEPTION
STAFF ENTRY
1807B
STAFF ENTRY
1807C
CLOSET
1814C
UNISEX
COMMUNITY/FIELD
STAFF
COMMUNITY/FIELD
STAFF
1814G
PROGRAM
SUPERVISOR
SUPPLY
PROGRAM
MANAGER
UNDER CONSTRUCTION
HA-83-C
HA-86-A
HA-76-D,
HA-43-D
HA-80-C
HA-84-B
HA-83-A
HA-82-A,
HA-84-D
HA-128-C
HA-29-B
HA-127-A HA-67-A,
HA-74-A
HA-70-C
HA-37-D,
HA-38-C,
HA-33-D
100-ABC
108-C
HA-71-A
HA-68-A,
HA-69-A
HA-24-A
HA-25-A
HA-26-A
HA-27-A
HA-28-A
HA-28-C
HA-24-C
HA-25-C
HA-27-C
HA-29-ABC
HA-24-B
HA-25-B
HA-26-B
HA-27-B
HA-28-B
HA-30-A
HA-30-B
HA-30-C
HA-31-A
HA-32-A
HA-32-B
HA-32-C
HA-31-B HA-31-C
HA-115-A
HA-115-B
HA-115-C
HA-128-B
HA-128-A
HA-129-A HA-116-B
HA-116-A
HA-116-C
HA-34-F
109-ABC
HA-35-D
HA-44-D
HA-29-B HA-109-A
HA-108-A HA-67-A
HA-66-A
HA-70-A
HA-66-C
HA-70-B
HA-67-B
HA-41-A
HA-42-B
HA-45-A,B,C
HA-41-B
HA-43-C
HA-49-A,B,C
HA-44-F
HA-46-F
HA-70-E
HA-42-A
HA-46-A
HA-59-A
HA-52D
HA-49-E
HA-14-D
HA-40-C
HA-70-D
HA-46-D
HA-40-A
HA-48-B
HA-75-A
HA-76-A
HA-77-A
HA-78-A HA-75-B
HA-76-B
HA-77-B
HA-78-B
HA-79-A
HA-1-D
HA-75-C
HA-76-C
HA-78-C
HA-80-A
HA-47-B
HA-80-B
HA-8-D
HA-79-B
HA-77-C
HA-81-A
HA-81-B
HA-79-C
HA-47-C
HA-54-C
HA-51-C
HA-49-B
HA-52-B
HA-52-C
HA-49-C
HA-50-C
HA-52-A
HA-48-A
HA-49-A
HA-57-A
HA-55-C HA-55-A
HA-56-A
HA-54-B
HA-51-B
HA-57-A,B
HA-65-A,B
HA-61-C
HA-64-B
HA-63-A,B,C
HA-59-C
HA-58-BHA-61-A
HA-58-A
HA-49-D
HA-60-A
HA-111-C
HA-111-A
HA-111-B
HA-34-E
HA-55-D
HA-113-C
HA-113-A
HA-112-A
HA-112-B
HA-113-B
HA-81-C
HA-34-D
HA-103-D
HA-114-A,B
HA-102-C
HA-102-C
C.T.-41(HA)
HA-102-B
HA-100-C
HA-43-E
HA-44-D
HA-52-E
HA-49-F
HA-100-C,D
HA-100-A
HA-100-B
HA-101-A
HA-107-A
HA-106-A,B,C
HA-105-A,B
HA-101-B
HA-103-C
HA-103-A
HA-104-A
HA-103-B
HA-104-B
HA-104-C
Veterans Health Administration
Drawing Title Project Title
Location
Date Checked Drawn
Building Number Project Number
Drawing Number
Drawing #
U.S. DEPARTMENT OF VETERANS AFFAIRS
ORLANDO VA HEALTH CARE SYSTEMS
FACILITIES & ENGINEERING SERVICE BOB 1 of 5
BUILDING 500
02/26/2025
ASBESTOS SAMPLE LOCATIONS
BASELINE ASBESTOS SURVEY
FLOOR 01
36C24824D0112
LAKE BALDWIN BUILDING 500, MAIN CLINIC
VHAORLLuna-D Rectangle
HA-84-C
HA-119-A,B,C
HA-120-A
HA-1-E
HA-118-B
HA-117-B
HA-117-A
HA-118-A
HA-117-CHA-118-C
HA-120-B
HA-121-CHA-121-A
HA-121-B
Veterans Health Administration
Drawing Title Project Title
Location
Date Checked Drawn
Building Number Project Number
Drawing Number
Drawing #
U.S. DEPARTMENT OF VETERANS AFFAIRS
ORLANDO VA HEALTH CARE SYSTEMS
FACILITIES & ENGINEERING SERVICE BOB 2 of 5
BUILDING 500
02/26/2025
BUILDING 500- FLOOR 2
SCALE 1/32" = 1'-0"
ASBESTOS SAMPLE LOCATIONS
BASELINE ASBESTOS SURVEY
FLOOR 02
36C24824D0112
LAKE BALDWIN BUILDING 500, MAIN CLINIC
2 2 2
2 2 2
2 2 2
2 2 2
2 2 2
2 2 2
2 2 2
2 2 2
CHECK-IN
GROUP ROOM
#2A
JAN
BREAKROOM
WORK AREA
REST
REST
REST
ELECT
STG
343 STORAGE
DATA
ELECT
REST
REST
MED TREATM
STORAGE
TRIAGE
OFFICE 26
OFFICE 27
OFFICE 28
OFFICE 29
OFFICE 30
OFFICE 31
GROUP ROOM
#1A
OFFICE 32
OFFICE 33
OFFICE 34
OFFICE 35
OFFICE 36
OFFICE 25
OFFICE 24
OFFICE 23
OFFICE 22
OFFICE 21
OFFICE 20
OFFICE 13
OFFICE 14
OFFICE 15
OFFICE 16
OFFICE 17
OFFICE 18
OFFICE 19
OFFICE 12
OFFICE 11
OFFICE 10
OFFICE 9
OFFICE 8
OFFICE 7
OFFICE 6
OFFICE 5
OFFICE 4
OFFICE 3
OFFICE 2
OFFICE 1
RESTROOM
WAITING
OVERFLOW
WAITING
CHECK-OUT
STG
OFFICE 37
OFFICE 38
OFFICE 40
OFFICE 39
OFFICE 41
OFFICE 42
OFFICE 43
OFFICE 44
OFFICE 45
OFFICE 46
OFFICE 48
OFFICE 47
OFFICE 49
OFFICE 50
SHAFT
SHAFT
SHAFT
SHAFT
SHAFT
SHAFT
82 180
180 82
FE
FE
FE
GROUP ROOM
#2B
GROUP ROOM
#1B
HA-11-A
HA-10-A
HA-9-A
HA-12-A HA-13-C
HA-16-C
HA-17-B
HA-9-B
HA-10-B
HA-12-B
HA-11-B
HA-13-A
HA-10-C
HA-9-C
HA-12-C
HA-16-B HA-11-C
HA-16-A
HA-17-A
HA-13-B
HA-14-A,B,C HA-8-B,C
HA-15-A
RED MASTIC ON
DUCTS UNDER
INSULATION
Veterans Health Administration
Drawing Title Project Title
Location
Date Checked Drawn
Building Number Project Number
Drawing Number
Drawing #
U.S. DEPARTMENT OF VETERANS AFFAIRS
ORLANDO VA HEALTH CARE SYSTEMS
FACILITIES & ENGINEERING SERVICE BOB 3 of 5
BUILDING 500
02/26/2025
BUILDING 500- FLOOR 3
SCALE 1/16" = 1'-0"
ASBESTOS SAMPLE LOCATIONS
BASELINE ASBESTOS SURVEY
FLOOR 03
2 2 2
2 2 2
2 2 2
2 2 2
2 2 2
2 2 2
2 2 2
2 2 2
WAITING #1
WAITING #2
CHECK-IN
407 CHECK-OUT
NURSE TRIAGE
JAN
OFFICE 1
OFFICE 2
OFFICE 3
OFFICE 4
OFFICE 5
OFFICE 6
OFFICE 1
OFFICE 2
OFFICE 3
OFFICE 4
OFFICE 5
BREAKROOM
WORK AREA
REST
OFFICE 6
NEUROP
RECORDS
POD
REST
INTERV ROOM 2
INTERV ROOM 1
EDU/ADM POD
REST
ELEC
STG
444 STORAGE
DATA
ELEC
OFFICE 15
REST 468
OFFICE 14
OFFICE 13
OFFICE 12
REST
VOC REHAB OFF
INTERV ROOM 3
POD
REST
OBS REST
OFFICE 1
OFFICE 2
OFFICE 3
OFFICE 4
OFFICE 5
OFFICE 6
OFFICE 7
OFFICE 8
OFFICE 9
OFFICE 10
OFFICE 11
STORAGE
SUB-WAITING
GROUP ROOM #1
TEAMWORK
ZONE VOC
REHAB
TEAMWORK
ZONE EXTRA
STG
PTSD OPEN
WORK AREA
OFFICE 7
OFFICE 8
GROUP ROOM #2
VESTIBULE
Public Cooridor
Restricted Cooridor
SHAFT
SHAFT
SHAFT
SHAFT
SHAFT
SHAFT
60 180
180 60
MTD = 160'-11" CCPPTT == x6'-3x'-"3"
MAX DEAD END = 24'-8" MTD = 160'-11" CPT = 63'-3"
MAX DEAD END = 24'-8"
FE
FE
FE
HA-5-B
HA-7-A
HA-6-A
HA-6-C
HA-7-B
HA-6-B
HA-5-CHA-4-BHA-8-A
HA-2-C
HA-1-C
HA-3-D
HA-4-A
HA-5-A
HA-3-C
HA-2-B
HA-1-B
HA-3-B
HA-1-A
HA-3-A
HA-2-A
HA-7-C
Veterans Health Administration
Drawing Title Project Title
Location
Date Checked Drawn
Building Number Project Number
Drawing Number
Drawing #
U.S. DEPARTMENT OF VETERANS AFFAIRS
ORLANDO VA HEALTH CARE SYSTEMS
FACILITIES & ENGINEERING SERVICE BOB
ASBESTOS SAMPLE LOCATIONS
BASELINE ASBESTOS SURVEY
FLOOR 04
BUILDING 500
02/26/2025
BUILDING 500- FLOOR 4
SCALE 1/16" = 1'-0"
HA-20-C
HA-20-A,B
HA-19-A,C
HA-18-A
HA-23-A
HA-19-B
HA-22-A
HA-22-B
HA-21-A,B,C
Veterans Health Administration
Drawing Title Project Title
Location
Date Checked Drawn
Building Number Project Number
Drawing Number
Drawing #
U.S. DEPARTMENT OF VETERANS AFFAIRS
ORLANDO VA HEALTH CARE SYSTEMS
FACILITIES & ENGINEERING SERVICE BOB 5 of 5
BUILDING 500
01/17/2025
BUILDING 500- MEZZANINE
SCALE 1/16" = 1'-0"
ASBESTOS SAMPLE LOCATIONS
BASELINE ASBESTOS SURVEY
FLOOR MEZZANINE
APPENDIX A
LABORATORY ANALYTICAL REPORTS
Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
Rick.Cwiklowski Line
APPENDIX B
PHOTO LOG OF HOMOGENEOUS AREAS
Site Address: Orlando VA Building 500 - 5201 Raymond St, Orlando, FL Photographed: October 26, 2024
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-1: Off-white mastic on duct HA-2: Carpet mastic
HA-3: Ceiling tile (smooth and recessed) HA-4: Grey duct mastic
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-5: White joint compound and drywall HA-6: Short grey cove base with yellow adhesive
HA-7: Vinyl tile adhesive HA-8: Red caulking
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-9: White joint compound and drywall HA-10: Off white duct mastic
HA-11: Yellow/green carpet mastic HA-12: 2x2 white ceiling tile (smooth)
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-13: Grey mastic on duct HA-14: Pink fire caulking
HA-15: Grey mastic on PVC HA-16: Grey cove base and tan mastic
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-17: 2x2 tan vinyl flooring and grey mastic HA-18: Off white mastic on duct insulation
HA-19: White mastic on duct insulation HA-20: Grey mastic on duct insulation
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-21: Dark grey mastic on air handling unit
HA-22: Red mastic
HA-23: Off-white joint compound and drywall HA-24: White mastic on duct insulation
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-25: 2X2 white ceiling tile HA-26: Clear/grey mastic on carpet backing
HA-27: Off-white joint compound and drywall HA-28: Grey cove base with clear mastic
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-29: Red mastic HA-30: 3X3 grey vinyl floor tile with red mastic
HA-31: Vinyl tile and mastic HA-32: Clear mastic on carpet backing
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-33: 2x2 ceiling tile (fissured) HA-34: 12x12 white vinyl floor tile with black mastic
HA-35: White drywall with white joint compound HA-36: Red mastic
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-37: 12x12 white floor tile with yellow
HA-38: 12x12 white vinyl floor tile with black
HA-39: Grey cove base with tan mastic HA-40: Laminate wood planking (brown) with black and yellow mastic
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-41: 2x2 white ceiling tile (smooth) HA-42: Beige cove base with yellow mastic
HA-43: White mastic on duct insulation HA-44: White drywall with white joint compound
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-45: Grey mastic on duct HA-46: 2x2 white ceiling tile (fissured)
HA-47: 2x2 white vinyl ceiling tile HA-48: Tan mastic on duct insulation
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-49: White drywall with white joint
HA-50: 12x12 white vinyl floor with yellow
HA-51: Black cove base with clear and tan mastic HA-52: 2x2 white ceiling tile (fissured)
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-53: Tan cove base with yellow mastic HA-54: Yellow mastic on 12x12 tile with black mastic beneath
HA-55: Yellow mastic on white linoleum sheeting, yellow mastic beneath
HA-56: 12x12 grey vinyl floor tile with brown mastic and yellow mastic
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-57: Light brown linoleum plank flooring with yellow mastic HA-58: Dark grey cove base with tan mastic
HA-59: 12x12 white vinyl tile, yellow mastic and grey leveling compound HA-60 1x1 linoleum grey tile with clear/yellow
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-61: Black tall cove base with yellow mastic HA-62: 2x4 grey spotted linoleum tile
HA-63: Tan cove base with white mastic HA-64: Tan mastic under vinyl white sheeting
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-65: 12x12 white vinyl floor tile HA-66: White drywall with joint compound
HA-67: Tall grey cove base with yellow mastic HA-68: Red/blue carpet with yellow mastic
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-69: Red/blue carpet with yellow adhesive HA-70: 2x2 blue/white carpet with yellow
HA-71: Grey short cove base with tan mastic HA-72: Tan cove base with yellow mastic
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-73: Brown plant linoleum flooring with yellow mastic HA-74: 2x4 off white vinyl floor tile with yellow
HA-75: 2x2 white inlay ceiling tile HA-76: White drywall and plaster
M:\Data\T\THUJV - THUNDERBIRD-HRP JV, LLC\ORLANDO VA HEALTHCARE SYSTEMS, LAKE BALDWIN OPC\THU2015BA - VA Orlando OPC\Photos\Photograph Log - Building 500 - Missing 4.docx
HA-77: 2x2 grey floor tile with yellow mastic HA-78: Tall grey cove base with tan mastic
HA-79: Grey/orange lined carpet with grey leveling compound and mastic HA-80: Light grey linoleum floor with yellow