Attachment 2 - JCI 3030 hon-ba-fire-jci-6880.pdf
PDF 1007 KB Posted
- Attached to
- DESIGN-BUILD (DB) BARRACKS INITIATIVE (PACKAGE #1), MARINE CORPS AIR STATION (MCAS) CHERRY POINT, NC
- Solicitation number
- ML26-85
About this file
This is a product data sheet for the IFC-3030 Intelligent Addressable Fire Alarm System, manufactured by Johnson Controls. The document describes a fire alarm control panel designed for medium- to large-scale facilities, featuring modular design with one to ten Signaling Line Circuits (SLCs) supporting up to 3,180 intelligent addressable devices. The system includes a large 640-character liquid crystal display (LCD) for presenting vital fire situation information to operators and supports optional single- or multichannel voice, firefighters' telephone, LED/LCD/PC-based graphic annunciators, and advanced detection products.
The IFC-3030 features FlashScan intelligent protocol technology that polls 318 devices per loop in less than two seconds and activates up to 159 outputs in under five seconds. Key capabilities include AWACS advanced warning algorithms for smoke detection with drift compensation and maintenance alerts, nine sensitivity levels for alarm detection, and self-optimizing pre-alarm functionality. The system supports field programming through autoprogram features, keypad program editing while maintaining fire protection, and VeriFire Tools offline programming software. Additional system specifications include up to 96 programmable input/output panel circuits, 4,000-event history file capacity, network options supporting IFC-640, IFC-3030, and JNCA network annunciators, and compatibility with various power supplies, system modules, audio options, and intelligent detection devices. The panel is UL-listed, FM-approved, and designed to comply with UL Standards 864 and 1076 and NFPA 72 requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 1 - Company Information.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JCI-6880 • 06/24/04 — Page 1 of 8
General
The IFC-3030 is an intelligent Fire Alarm Control Panel de-signed for medium- to large-scale facilities. Fire emergency detection and evacuation are extremely critical to life safety, and the IFC-3030 is ideally suited for these applications.
The IFC-3030 is ideal for virtually any application because it fea-tures a modular design that is configured per project require-ments. With one to ten Signaling Line Circuits (SLCs), the IFC- 3030 supports up to 3,180 intelligent addressable devices.
Information is critical to fire evacuation personnel, and the IFC-3030’s large 640-character Liquid Crystal Display (LCD) presents vital information to operators concerning a fire situ-ation, fire progression, and evacuation details.
A host of other options are available, including single- or multichannel voice; firefighters telephone; LED, LCD, or PC-based graphic annunciators; fire or integration networking;
advanced detection products for challenging environments, and many additional options.
Features
• One to ten isolated intelligent Signaling Line Circuits (SLC) Style 4, 6 or 7.
• Up to 159 detectors (any mix of ion, photo, laser photo, thermal, or multi-sensor) and 159 modules (N.O. manual stations, two-wire smoke, notification, or relay) per SLC.
318 devices per loop/3180 per FACP or network node.
• Large 640-character LCD backlit display (16 lines x 40 char-acters) or display-less (a node on a network).
• Network option – supports IFC-640, IFC-3030, JNCA net-work annunciator, or IFW network control station.
• UniNet® compatible.
• Built-in Alarm, Trouble, Security, and Supervisory relays.
• Up to 96 input or output panel circuits per FACP or net-work node; circuits configurable online.
• VeriFire™ Tools online/offline program option.
• Application code is saved in Flash memory, eliminating the need to change EPROMs.
• Built-in Degraded Mode option. In the event of a CPU fail-ure, the system is capable of general alarm if a fire condi-tion is present.
• Weekly Occupancy Schedules allow changing sensitivity by time of day and day of week.
• Optional universal 2040-point DACT.
• EIA-485 annunciators, including custom graphics.
• Printer interface (80-column and 40-column printers).
• History file with 4000-event capacity in nonvolatile memory, plus separate 1000-event alarm-only file.
• Advanced history filters allow sorting by event, time, date, or address.
• Alarm Verification selection per point, with tally.
• Autoprogramming and Walk Test reports.
• Positive Alarm Sequence (PAS) Presignal.
• Silence inhibit and Auto Silence timer options.
• March time and temporal signals supported on panel circuits.
• Field-programmable on panel or on PC, with VeriFire™
Tools program, also check, compare.
• Non-alarm points for lower priority functions.
• Remote ACK/Signal Silence/System Reset/Drill via moni-tor modules.
• Powerful Boolean logic equations — 1000!
• Supports SCS Series smoke control system in both HVAC or FSCS modes.
IFC-3030
Intelligent Addressable
Fire Alarm System
June 24, 2004 JCI-6880
AWACS™, HARSH™, NOTI•FIRE•NET™, VeriFire™ are trade-marks, and FlashScan®, ONYX®, UniNet®, and VIEW® are reg-istered trademarks of NOTIFIER. Acclimate™ is a trademark of System Sensor. Microsoft® and Windows® are registered trade-marks of the Microsoft Corporation. LEXAN® is a registered trade-mark of GE Plastics, a subsidiary of General Electric Company.
j6
0p h1
.jp g
IFC-3030 shown in CAB-C4 backbox with 640-character display
S1570
7165-0554:149 7170-0554:150
California State Fire Marshal
CS118 Vol. 25/ S635 Vol. 46
MEA
345-02-E
Vol. II
Made in the U.S.A.
This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact your Johnson Controls Field Support Center.
507 East Michigan Street, Milwaukee, WI 53202
Page 2 of 8 — JCI-6880 • 06/24/04
Sample System Options j6880blk.wmf
• EIA-232 printer port.
• EIA-485 annunciator port.
• 640-character display features:
� Backlit, 640-character display.
� Program keypad: full QWERTY keypad.
� Up to nine users, each with a password and selectable access levels.
� 10 LED indicators: Power; Fire Alarm; Pre-Alarm; Se-curity; Supervisory; System Trouble; Other Event; Sig-nals Silenced; Point Disabled; CPU Failure.
� Membrane Switch Controls: Acknowledge; Signal Si-lence; Drill; System Reset; Lamp Test.
� LCD Display: 640 characters (16 x 40) with long-life LED backlight.
• FlashScan® intelligent features:
� Poll 318 devices on each loop in less than two seconds.
� Activate up to 159 outputs in less than five seconds.
� Multicolor LEDs blink device address during Walk Test.
� Fully digital, high-precision protocol (U.S. Patent
5,539,389).
� Manual sensitivity adjustment — nine levels.
� Pre-alarm AWACS™ — nine levels.
� Sensitivity windows:
Ion – 0.5 to 2.5%/foot obscuration.
Photo – 0.5 to 2.35%/foot obscuration.
Laser (VIEW®) – 0.02 to 2.0%/foot obscuration.
Acclimate™ – 0.5 to 4.0%/foot obscuration.
HARSH™ – 0.5 to 2.35%/foot obscuration.
� Drift compensation (U.S. Patent 5,764,142).
� Multi-detector algorithm involves nearby detectors in alarm decision (U.S. Patent 5,627,515).
� Automatic detector sensitivity testing.
� Maintenance alert (two levels).
� Self-optimizing pre-alarm.
� Programmable activation of sounder/relay bases dur-ing alarm or pre-alarm.
� Read Status displays the level of detector cleanliness.
• VIEW® Very Intelligent Early Warning smoke detection technology:
� Revolutionary spot laser design.
� Advanced AWACS™ algorithms differentiate between smoke and non-smoke signals (U.S. Patent 5,831,524).
� Addressable operation pinpoints the fire location.
� No moving parts to fail or filters to change.
� Early warning performance comparable to the best as-piration systems at a fraction of the lifetime cost.
• Acclimate™ low-profile intelligent multi-sensor:
� Detector automatically adjusts sensitivity levels with-out operator intervention or programming. Sensitivity increases with heat.
� Microprocessor-based technology; combination photo and thermal technology.
� Low-temperature signal at 40°F ± 5°F (4.44°C ± 2.77°C).
• RFX Wireless Interface System:
� Allows protection in areas where the use of wire is un-economical or unpractical.
� Allows communication with wireless smoke detectors and wireless monitor modules; each RFX unit and de-tector is assigned an address.
� Requires 24 VDC from SLC or system auxiliary power.
• HARSH™ Hostile-Area Smoke Head:
� Provides early warning of smoke detection in environment where traditional smoke detectors are not practical.
� The detector's filters remove particulates down to 30 microns in size.
� Intake fan draws air into photo chamber, while airborne particles and water mist are removed.
� Requires auxiliary 24 VDC from system or remote power supply.
JCI-6880 • 06/24/04 — Page 3 of 8
Autoprogram Confirmation screen (SLCs) 6880prog.wmf
• Releasing features:
� Ten independent hazards.
� Sophisticated cross-zone (three options).
� Delay timer and Discharge timers (adjustable).
� Abort (four options).
• Voice and telephone features:
� Solid state message generation.
� Hard-wired voice control module options.
� Firefighter telephone option.
� 30- to 120-watt high-efficiency amplifiers (AA Series).
� Backup tone generator and amplifier option.
� Multichannel voice transponder (XPIQ).
FlashScan® Exclusive New
World-Leading Detector Protocol
At the heart of the IFC-3030 is a set of detection devices and device protocol — FlashScan® (U.S. Patent 5,539,389).
FlashScan® is an all-digital protocol that gives superior pre-cision and high noise immunity.
As well as giving quick identification of an active input de-vice, this new protocol can also activate many output devices in a fraction of the time required by competitive protocols.
This high speed also allows the IFC-3030 to have the largest device per loop capacity in the industry — 318 points — yet every input and output device is sampled in less than two seconds. The microprocessor-based FlashScan® detectors have bicolor LEDs that can be coded to provide diagnostic information, such as device address during Walk Test.
AWACS™ Advanced Warning
Addressable Combustion Sensing
AWACS™ is a set of software algorithms that provide the IFC-3030 with industry-leading smoke detection capability.
These complex algorithms require many calculations on each reading of each detector, and are made possible by the very high-speed microcomputer used by the IFC-3030.
Drift Compensation and Smoothing. Drift com-pensation allows the detector to retain its original ability to detect actual smoke, and resist false alarms, even as dirt ac-cumulates. It reduces maintenance requirements by allow-ing the system to automatically perform the periodic sensitiv-ity measurements required by NFPA Code 72. Smoothing filters are also provided by software to remove transient noise signals, usually caused by electrical interference.
Maintenance Warnings. When the drift compensa-tion performed for a detector reaches a certain level, the per-formance of the detector may be compromised, and special warnings are given. There are three warning levels: (1) Low Chamber value, usually indicative of a hardware problem in the detector; (2) Maintenance Alert, indica-tive of dust accumulation that is near but below the allowed limit; (3) Maintenance Urgent, indicative of dust accumulation above the allowed limit.
Sensitivity Adjust. Nine sensitivity levels are provided for alarm detection.
These levels can be set manually, or can change automatically between day and night. Nine levels of pre-alarm sensitivity can also be selected, based on predeter-mined levels of alarm. Pre-alarm operation can be latching or self-restoring, and can be used to activate special control func-tions.
Self-Optimizing Pre-Alarm. Each detector may be set for “Self-Optimizing” pre-alarm. In this special mode, the detector “learns” its normal environment, measuring the peak analog readings over a long period of time, and setting the pre-alarm level just above these normal peaks.
Cooperating Multi-Detector Sensing. A patented feature of AWACS™ is the ability of a smoke sensor to con-sider readings from nearby sensors in making alarm or pre-alarm decisions. Without statistical sacrifice in the ability to resist false alarms, it allows a sensor to increase its sensitiv-ity to actual smoke by a factor of almost two to one.
Field Programming Options
Autoprogram is a timesaving feature of the IFC-3030. It is a special software routine that allows the IFC-3030 to “learn” what devices are physically connected and automati-cally load them in the program with default values for all parameters. Requiring less than one minute to run, this rou-tine allows the user to have almost immediate fire protection in a new installation, even if only a portion of the detectors are installed.
Keypad Program Edit. The IFC-3030 has the exclu-sive feature of program creation and editing capability from the front panel keypad, while continuing to provide fire protection. The architecture of the IFC-3030 software is such that each point entry carries its own program, including control-by-event links to other points. This allows the pro-gram to be entered with independent per-point segments, while the IFC-3030 simultaneously monitors other (already installed) points for alarm conditions.
VeriFire™ Tools is an offline programming and test utility that can greatly reduce installation programming time, and increase confidence in the site-specific software. It is Windows® based and provides technologically advanced capabilities to aid the installer. The installer may create the entire program for the IFC-3030 in the comfort of the office, test it, store a backup file, then bring it to the site and download from a laptop into the panel.
Page 4 of 8 — JCI-6880 • 06/24/04
Network
Diagram bo rd .w m f
JCPU-3030, shown without keyboard/display
The control panel electronics are contained on one printed circuit board (PCB) that holds the central processing unit (JCPU-3030). The JCPU-3030 can be purchased with or without keypad and display; connections are identical on both versions. Dia-gram shows location of connections, switches, jumpers, and LEDs on the circuit board.
j6880cnf.wmf
JCI-6880 • 06/24/04 — Page 5 of 8
Placement of Equipment in Chassis and Cabinet
The following guidelines outline the IFC-3030’s flexible sys-tem design.
Rows: The first row of equipment in the cabinet mounts in chassis CHS-M3. Mount the second, third, or fourth rows of equipment in chassis CHS-4MB (see IFC-3030 Installation Manual regarding panel output modules) or CHS-4L (for voice components, see Voice Alarm System Manual).
Wiring: When designing the cabinet layout, consider sepa-ration of power-limited and non-power-limited wiring as dis-cussed in the IFC-3030 Installation Manual.
Positions: A chassis offers four basic side-by-side posi-tions for components; the number of modules that can be mounted in each position depends on the chassis model and the size of the individual module. There are a variety of stand-offs and hardware items available for different combinations and configurations of components.
It is critical that all mounting holes of the IFC-3030 are secured with a screw or standoff to ensure continuity of Earth Ground.
Layers: The JCPU-3030 mounts in chassis CHS-M3 in the top row of the cabinet. The JCPU-3030 and its optional dis-play occupy the left half of the chassis (positions 1 and 2). If JNCA is used, it may be door-mounted in front of a displayless JCPU-3030ND. The right half (positions 3 and 4) of CHS-M3 can hold up to four layers of equipment including annuncia-tors, panel output modules, and option boards. The BMP-1 Blank Module Plate covers unused positions and also pro-vides a location to door-mount some option boards. Second, third, and fourth tiers of equipment use any chassis compat-ible with CAB-4 Series backboxes, such as the CHS-4MB.
Some equipment, such as the JNCA and annunciators, can be door-mounted; refer to equipment documentation for details.
Expansion: Loop Control Module LCM-320 adds SLC loops to the IFC-3030; the Loop Expander Module LEM-320 expands an LCM-320;
adding another loop. The IFC-3030 supports up to five LCMs and up to five LEMs. Other option boards include the NCM-W, NCM-F, and the TM-4. Panel modules include CRM-
4RK, DCM-4RK, ICM-4RK, IZE-A, IZM-8RK,
VCM-4RK, and their respective expanders.
j6
0c hs
.w m f
Agency Listings and Approvals
See the first page of this data sheet for listing agencies and file numbers. These listings and approvals apply to the basic IFC-3030 control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
The IFC-3030 complies with UL Standards 864 (Fire) and 1076 (Burglary). It is designed to meet NFPA 72 Local, Auxiliary, Remote Station, Proprietary, and Emergency Voice/Alarm Fire System Requirements.
Specifications
• Primary input power, AMPS-24: 120 VAC, 50/60 Hz, 3.0 amps. AMPS-24E: 220/240 VAC, 50/60 Hz, 1.5 Amps.
• Total output 24 V power: 4.5 A in alarm.*
• General purpose power: 1.0 A.
• Battery charger range: 25 AH – 200 AH. Use separate cabi-net for batteries over 25 AH.
• Float Rate: 27.6 V.
• Temperature and humidity ranges: This system meets NFPA requirements for operation at 0°C to 49°C (32°F to 120°F);
and at a relative humidity (noncondensing) of 85% at 30°C (86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C (89.6°F ± 1.1°F) per ULC. However, the useful life of the system’s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and hu-midity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15°C to 27°C (60°F to 80°F).
*Note: The power supply has a total of 4.5 Amps of available power.
System Capacity
• Intelligent Signaling Line Circuits ........ 1 expandable to 10
• Intelligent detectors ......................................... 159 per loop
• Addressable monitor/control modules ............ 159 per loop
• Programmable input and output panel circuits
• Programmable software zones ........................... over 2000
• ACS annunciators per JCPU-3030 ....................32 address x 64 or 96* points *Note: The JCPU-3030 can support up to 96 annunciator address points per ACM-24AT/-48A.
Page 6 of 8 — JCI-6880 • 06/24/04
IFW-W: Intelligent Fire Workstation (network control station), Wire. UL-Listed graphics PC with mouse, 17" color flat-screen LCD monitor. Order as necessary for network systems. Each IFW consumes one of 103 network addresses. See IFW tech-nical bulletin.
IFW-F: Intelligent Fire Workstation (network control station), Fiber. UL-Listed graphics PC with mouse, 17" color flat-screen LCD monitor. Order as necessary for network systems. Each IFW consumes one of 103 network addresses. See IFW tech-nical bulletin.
Power Supplies
AMPS-24(E): One required for each IFC-3030. Address-able power supply and battery charger with two 24 VDC out-puts. Addressable by any FlashScan® or CLIP mode FACP.
Charges 25 to 200 AH batteries. Occupies up to four addresses on an SLC, depending on configuration. Primary input power for panel; AMPS-24: 110-120 VAC, 50/60 Hz, 4.5 A maximum.
AMPS-24E: 220/240 VAC, 50/60 Hz, 2.25 A maximum. See AMPS-24 technical bulletin.
BB-100: Battery and power supply backbox. The BB-100 mounts the AMPS-24(E) power supply (when the main power supply does not mount in the main cabinet). It also mounts up to two PS/BAT-121000 100-AH batteries. 30" (76.20 cm) wide x 25" (63.50 cm) high x 7.5" (19.05 cm) deep; depth includes door.
BB-200: Battery and power supply backbox. The BB-200 mounts the AMPS-24(E) power supply (when the main power supply does not mount in the main cabinet). It also mounts up to four PS/BAT-121000 100-AH batteries. 30" (76.20 cm) wide x 36" (91.44 cm) high x 7.5" (19.05 cm) deep; depth includes door.
NFS-LBB: Battery Box (required for batteries over 25 AH).
Dimensions: Box: 24" (610 mm) wide x 14" (356 mm) high x 7.75" (197 mm) deep. Door: 24.125" (613 mm) wide x 14.25" (362 mm) high; door adds 0.0625" (approx. 1.6 mm) to depth.
APS-6R: Auxiliary Power Supply (expander). Provides up to
6.0 amperes of regulated power for compatible Notification ap-pliance circuits. Includes battery input and transfer relay, and overcurrent protection. Mounts on one of four positions on a CHS-4L or CHS-4 chassis.
ACPS-2406: six-amp addressable charger power supply.
See ACPS-2406 technical bulletin.
FCPS-24: The FCPS-24 is a remote six-amp (four-amp con-tinuous) repeater/power supply.
FCPS-24S6/-24S8: Remote six-amp and eight-amp power supplies with battery charger. See FCPS-24S6/-24S8 techni-cal bulletin.
BAT Series: IFC-3030 utilizes two 12 volt, 12 to 55 AH batteries.
PS Series: IFC-3030 utilizes two 12 volt, 25 to 200 AH batteries.
System Modules
The IFC-3030 includes the ability to communicate with up to twelve conventional modules each with up to eight circuits. Any mix of initiating, notification, relay, speaker, or telephone may be used. Choose any combination of up to eight input (IZM/ IZE) or output modules: ICM/ICE, CRM/CRE, DCM or VCM/ VCE. Panel modules mount on either: the two far-right posi-tions of the CHS-M3 (next to the primary display); or on any of the four positions on the CHS-4N chassis (CHS-4MN kit re-quired). NOTES: 1) These modules/expanders are NOT to be used for releasing applications. 2) For additional infor-mation on these panel circuit modules and expanders, see Panel Circuit Modules technical bulletin.
CHS-4MB: Expansion Chassis. Mounts up to four modules.
Includes CHS-4N, MP-1B (Module Dress Panel), and Expander Ribbon Cable.
IZM-8RK and IZE-A: The IZM-8RK includes eight Class B (Style B) Initiating Zones (Initiating Device Circuits) that can be selected for Class A/B with the addition of an IZE-A ex-pander module. Each IZM/IZE zone can be programmed for a
PRODUCT LINE INFORMATION
• Configuration Guidelines
• Network Options
• Power Supplies
• System Modules
• Audio Options
• Compatible Devices, EIA-232 Ports
• Compatible Devices, EIA-485 Ports
• Compatible Intelligent Devices
• Other Options
Configuration Guidelines
Stand-alone and network systems require a main display. On single-CPU systems (one IFC-3030), the display option is the JCPU-3030D. On network systems (two or more IFC-3030s and/or IFC-640s), at least one JNCA or IFW annunciation de-vice is required. Options listed as follows:
JCPU-3030D: IFC-3030 Primary Display. JCPU-3030D ships with keypad/display installed; includes 640-character backlit LCD display, QWERTY programming and control key-pad. JCPU-3030 is a central processing unit and requires an AMPS-24(E) power supply.
JCPU-3030ND: JCPU-3030 without display.
JVeriFire-TCD: VeriFire™ Tools CD-ROM. Contains pro-gramming software for the IFC-3030, IFC-640, JNCA, and XPIQ. Includes local panel connection cable. Programming PC requires a serial port connection. See VeriFire™ Tools tech-nical bulletin.
LCM-320: Loop Control Module. Adds SLCs to 3030; 3030 supports up to 5 LCM-320s and 5 LEM-320s. See LCM/LEM- 320 technical bulletin.
LEM-320: Loop Expander Module. Expands each LCM used on the 3030. See LCM/LEM-320 technical bulletin.
CHS-M3: Mounting chassis for JCPU-3030. One required for each JCPU-3030D/3030ND.
DP-DISP: Dress panel for top row in cabinet with JCPU- 3030D installed.
BMP-1: Blank module for unused module positions.
Sample system: Four-loop IFC-3030 with display: JCPU-3030D, DP-DISP, two BMP-1s, CHS-M3, two LCM-320s, two LEM-320s, AMPS-24, SBB-A4, JDR-A4, BP-4, BB-100, and batteries.
Network Options
JNCA: Network Control Annunciator, 640 characters. An al-ternate primary display for JCPU-3030 can be provided by the JNCA or the IFW. Using JNCA as primary display enables non- English languages. When used on single JCPU-3030 systems, the JNCA is the Primary Display for the panel and connects directly to the JCPU-3030. On network systems (two or more JCPU-3030s), one network display (either JNCA or IFW) is required for every system. On network systems, the JNCA con-nects (and requires) an NCM network communications mod-ule. Mounts in a row of FACP node or in two annunciator po-sitions. Mounting options include the DP-DISP, ADP-4B, or in an annunciator box, such as the JABS-2D. In CAB-4 top-row applications, a DP-DISP and two BMP-1 blank modules are required for mounting. See JNCA technical bulletin.
NCM-W: Network Communications Module, Wire. Order one NCM per network node (JCPU-3030 or JNCA). See NCM tech-nical bulletin.
NCM-F: Network Communications Module, Fiber. Order one NCM per network node (JCPU-3030 or JNCA). See NCM tech-nical bulletin.
RPT-W: repeater board; wire connection.
RPT-F: repeater board; fiber connection.
RPT-WF: repeater board; allows a change in media type between wire and fiber.
JCI-6880 • 06/24/04 — Page 7 of 8 variety of initiating devices functions including: dry contact input, two-wire smoke detection, flow, tamper, non-fire, and many others. The IZM-8RK (with optional IZE-A) mounts in one of four possible positions on the CHS-4N mounting chassis. IZE-A Initiating Zone Expander; when used with IZM-8RK, provides eight Style D (Class A) alarm initiating circuits.
ICM-4RK: Notification Appliance Circuit Module, provides four Style Y (Class B) or Style Z (Class A) alarm Notification Appliance Circuits. Maximum signaling current is 3.0 amps per circuit or 6.0 amps per module, subject to power supply limita-tions (includes auxiliary power harness, ELRs and slide-in la-bels). Includes ON/OFF controls and ON/OFF LEDs.
ICE-4: Notification Appliance Circuit Expander, expands ICM-4 to provide a total of eight Style Y or Style Z alarm Notification Appliance Circuits. Circuit ratings are same as ICM-4. Note:
maximum of one per ICM-4RK. May also be used to add four Notification Appliance Circuits to VCM-4.
CRM-4RK: Control Relay Module, four Form-C relay con-tacts, rated at 5.0 A, 120 VAC or 28 VDC (resistive) per circuit.
Includes manual ON/OFF controls and LEDs.
CRE-4: Control Relay Expander, expands CRM-4 to provide a total of eight Form-C relay contacts. Note: maximum of one per CRM-4RK. May also be connected to add four relays to ICM-4 or VCM-4.
VCM-4RK: Voice Control Module provides four Style Y (25 and 70 VRMS) and Style Z (25 VRMS only) speaker circuits, eight manual select switches and indicators, slide-in labels, and plug-in terminal blocks. Move jumper to convert to tele-phone circuits with remote ring signal and local call-in flash.
May be expanded to eight circuits with VCE-4, ICE-4, or CRE-4.
VCE-4: Voice Control Expander adds four circuits to VCM-4.
Note: VCM-4/ VCE-4 combination must be eight speaker or eight phone circuits.
DCM-4RK: Dual Channel Module provides four Class B (Style Y, 25 and 70 VRMS) or Class A (Style Z, 25 VRMS only) speaker circuits plus four channel A/B select relays. Not ex-pandable.
ARM-4: Auxiliary Relay Module, four Form-C relays controlled by a relay module (CRM-4 or CRE-4). N.O. contacts rated 20 amps; N.C. contacts rated 10 amps at 125 VAC and 30 VDC.
Note: maximum of one for each CRM-4 or CRE-4.
Audio Options
JVCC-1B: Voice Control Center. Provides a variety of user-selectable tones on a single channel. Up to two different tones or messages may be selected on a single channel. Also pro-vides optional digital voice message capability and on-site pro-grammable voice messages. Includes Audio Message Gen-erator (AMG-1) microphone, cables, dress panels, and instruc-tions.
JVTCC-1B: Voice/Telephone Control Center. Provides all that the JVCC-1(B) provides plus two-way Fire Fighters Tele-phone (FFT-7) capability.
JTCC-1B: Telephone Control Center. Provides a stand-alone two-way Fire Fighters telephone (FFT-7S). Includes cables, dress panel and instructions.
AMG-E: Audio Message Generator (without microphone). Or-der in addition to JVCC-1(B) or JVTCC-1(B) if two-channel sys-tem is required.
FFT-7/FFT-7S: Fire Fighters Telephone control with mas-ter handset.
FTM-1: Firephone Control Module connects a remote firefighter telephone to a centralized telephone console. Reports status to panel. Wiring to jacks and handsets is supervised.
RM-1/RM-1SA: Remote microphone assemblies, mount on ADP-4 (RM-1) dress panel or CAB-RM/-RMR (RM-1SA) stand-alone cabinets.
AA-30: Audio Amplifier, 30 watts. Switch-mode power. In-cludes amplifier and audio input supervision, backup input, and automatic switchover, power supply, cables.
AA-120/AA-100: Audio Amplifier provides up to 120 watts of 25 VRMS audio power. The amplifier contains an integral chassis for mounting to a CAB-B4, -C4, or -D4 backbox (con-sumes one row). Switch-mode power. Includes audio input and amplified output supervision, backup input, and automatic switchover to backup tone. Order the AA-100 for 70.7 VRMS systems and 100 watts of power.
VROM-(n): Factory-programmed message for installation in AMG-1. Provides up to 24 seconds of evacuation message on nonvolatile memory chip. Choose one of many standard mes-sages available. Up to two of these messages may be installed in one AMG. Includes VROM, instructions for installation and operation, and written text of message.
VRAM-1: Field-programmed memory to be installed in AMG-1. Provides up to 24 seconds of field-programmable evacuation message on nonvolatile memory chip. Message is programmed from microphone or cassette tape. Up to two of these nonvolatile memory chips may be installed in one AMG.
Includes VRAM and instructions for installation and operation.
XP Series: The XP Series Transponder provides conven-tional monitor and control points (CLIP mode only).
XPIQ: The XPIQ quad intelligent voice transponder for dis-tributed multichannel voice evacuation systems, an integrated audio amplification and distribution subsystem controlled by FACP. Capable of playing up to four simultaneous messages.
Accepts up to four 25-watt amplifiers.
Compatible Devices, EIA-232 Ports
JPRN-5: 80-column printer. See JPRN-5 technical bulletin.
JPRN-6: 80-column printer. See JPRN-6 technical bulletin.
VS4095/S2: Printer, 40-column, 24 V. Order from Keltron, Inc.
Compatible Devices, EIA-485 Ports
ACS Series: Annunciator Control Modules ACM-16AT, AEM-16AT, ACM-32A, and AEM-32A.
ACM-24AT: ACS Series annunciator for IFC-640 and IFC- 3030 – up to 96 points of annunciation with Alarm or Active LED, Trouble LED, and switch per circuit. Active/Alarm LEDs can be programmed (by powered-up switch selection) by point to be red, green, or yellow; the Trouble LED is always yellow.
See ACS Series Annunciator technical bulletin.
AEM-24AT: Same LED and switch capabilities as ACM- 24AT, expands the ACM-24AT to 48, 72, or 96 points. See ACS Series Annunciator technical bulletin.
ACM-48A: ACS Series annunciator for IFC-640 and IFC- 3030 – up to 96 points of annunciation with Alarm or Active LED per circuit. Active/Alarm LEDs can be programmed (by powered-up switch selection) in groups of 24 to be red, green, or yellow. Expandable to 96 points with one AEM-48A. See ACS Series Annunciator technical bulletin.
AEM-48A: Same LED capabilities as ACM-48A, expands the ACM-48A to 96 points. See ACS Series Annunciator technical bulletin.
ACM-8R: Remote Relay Module with eight Form-C contacts.
Can be located up to 6,000 ft. (1828.8 m) from panel on four wires.
LCD-80: Liquid Crystal Display annunciator, 80-characters backlit. Use in ACS mode only. See LCD-80 technical bulletin.
LCD-160: Liquid Crystal Display annunciator, 160-character backlit. Can store character sets for multiple languages. Sup-ports Canadian requirements.
LDM Series: Lamp Driver Modules LDM-32, LDM-E32, and
LDM-R32.
RFX: Wireless interface system. See RFX technical bulletin.
RPT-485 Series: Repeats EIA-485 over twisted pair or converts to fiber-optic medium; repeater, isolator and/or fiber-optic modem.
SCS Series: Smoke control station; eight (expandable to
16) circuits.
Page 8 of 8 — JCI-6880 • 06/24/04
TM-4: Transmitter Module. Includes three reverse-polarity cir-cuits and one municipal box circuit. Mounts in panel module position (as in single-address mode applications) or in CHS- M3 position. See TM-4 technical bulletin.
UDACT: Universal Digital Alarm Communicator Transmitter, 636 channel.
UZC-256: Programmable Universal Zone Coder provides positive non-interfering successive zone coding. Microproces-sor-controlled, field-programmable from IBM®-compatible PCs (requires optional programming kit).
Compatible Intelligent Devices
1951J: Low-profile FlashScan® ionization detector, will re-place 1351J.
1351J: Low-profile FlashScan® ionization detector.
2951J: Low-profile FlashScan® photoelectric detector, will replace 2351J.
2351J: Low-profile FlashScan® photoelectric detector.
2951TJ: Low-profile FlashScan® photoelectric detector with 135°F (57°C) thermal, will replace 2351TJ.
2351TJ: Low-profile FlashScan® photoelectric detector with 135°F (57°C) thermal.
5951J: FlashScan® thermal detector 135°F (57°C), will re-place 5351J.
5351J: FlashScan® thermal detector 135°F (57°C).
5951RJ: FlashScan® thermal detector 135°F (57°C) with rate-of-rise, will replace 5351RJ.
5351RJ: FlashScan® thermal detector 135°F (57°C) with rate-of-rise.
5951HJ: FlashScan® 190°F (88°C) high-temperature ther-mal detector.
DH300P: FlashScan® photo duct detector with housing.
DH300PL: Low-flow FlashScan® photo duct detector with housing, will replace DH300P.
DH300RP: FlashScan® photo duct detector with relay and housing.
DH300RPL: Low-flow FlashScan® photo duct detector with relay and housing, will replace DH300RP.
2951TMJ: FlashScan Acclimate™ low-profile multisensor detector, will replace 2351TMJ.
2351TMJ: Acclimate™ low-profile multisensor detector.
FTX-P2J: FlashScan® HARSH™ Hostile Area Smoke Head.
FTX-P1J: HARSH™ Hostile Area Smoke Head, CLIP only.
7351LJ: FlashScan® VIEW® laser photo detector.
7251J: Low-profile VIEW® laser photo detector, CLIP only.
B224RB: Low-profile relay base.
B224BI: Isolator base for low-profile detectors.
B210LPJ: Low-profile base. Standard U.S. style.
B501J: European-style, 4" (10.16 cm) base.
B710HD: Base for FTX-P2J HARSH™ detector above.
M300MJ: FlashScan® monitor module.
M300DJ: FlashScan® dual monitor module.
M302MJ: FlashScan® two-wire detector monitor module.
M301MJ: FlashScan® miniature monitor module.
M300CJ: FlashScan® NAC control module.
M300RJ: FlashScan® relay module.
M300SMJ: FlashScan® pull station monitor module.
JBG-12LX: Manual fire alarm station, addressable.
M500XJ: Isolator module.
XP Series: Transponders, provide conventional monitor and control points (CLIP mode only).
XP5-M: FlashScan® transponder, five monitor points.
XP5-C: FlashScan® transponder, five control points or Form-C relays.
XP6-C: Six-supervised control module; monitors wiring to de-vices that require external power supply to operate.
XP6-MA: Six-zone module for interface between intelligent alarm system and a two-wire conventional detection zone.
XP6-R: Six (Form-C)-relay control module.
XP10-M: Ten-input monitor module; interface between a con-trol panel and normally-open contact devices.
XPIQ: Intelligent quad transponder.
Other Options
DPI-232: Direct Panel Interface, specialized modem for ex-tending serial data links to remotely located FACPs and/or peripherals.
CHS-4N: Chassis for mounting up to four APS-6Rs.
CHS-4L: Low-profile four-position Chassis. Mounts two AA-30 amplifiers or one AMG-E and one AA-30.
DP-1B: Blank Dress panel. Provides dead-front panel for un-used tiers or to cover AA-30, AA-120, or AMG-E.
CAB-4 Series: The CAB-4 Series cabinets are fabricated from 16-gauge steel with unique full-front LEXAN®, reverse-silk-screened for durability. The cabinet assembly consists of two basic parts: a Backbox (SBB-_4), and a Locking Door (JDR- _4) that may hinge right or left. Cabinets are available in four sizes, “A” through “D”, with one to four tiers. A trim ring option is available for semi-flush mounting.
Other options as listed in previous sections. Technical bulletins are available for many of these products.