Attachment 2 - Fire Suppression - Site Visit Quesitons and Answers.pdf
PDF 90 KB Posted
- Attached to
- Fire Suppression Support Services Maintenance & Repair Federal contract opportunity
- Solicitation number
- W91CRB-23-R-0019
About this file
This document contains questions and answers from a site visit for a federal fire suppression system maintenance and repair contract opportunity. The fire suppression system at the site includes a 20,000 gallon water tank, pumps controlled by a variable frequency drive for pressure control, and heat trace and a heater to prevent freezing. While there is freeze protection at some locations, other lines only drain down to prevent freezing. An inventory of fire suppression systems and their locations exists but there is no cross-trip between the fire alarm and suppression systems. The related solicitation is for fire suppression support services maintenance and repair services for the Department of the Army Materiel Command Army Contracting Command at Aberdeen Proving Ground.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Solicitation Exhibit A - Fire Suppression Support Services LOE.xlsx | XLSX spreadsheet | |
| W91CRB-23-R-0019 - Fire Suppression Support Services - RFP.pdf | ||
| Attachment 1 - QASP_Fire_Suppression.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Suppression - Questions and Answers from the Site Visit on 19 October 2023
Question: Is there any freeze protection in place for fire suppression system?
Answer: No, only freeze protection at AA5 is to drain the lines.
Answer: PI Pumphouse has a heater in it and there is heat trace on the water lines from the holding tank to the pump house
Question: Is the water pump variable speed?
Answer: No
The electric motor connected to the pump is controlled by a variable drive unit, this is how we control pressure. It is a variable frequency drive. There is a set of digital manuals that go with the pump setups and a few hard copies, if needed.
Question: What is the size of the water tank?
Answer: 20,000 gallons
Question: Is there an inventory of systems and their locations?
Answer: Yes
Question: Is there a cross trip between the fire suppression system and the fire alarm system?
Answer: No