Sheet1
| Unit Parameters | Ordering Information | Acoustical Data | ||||||||||
| Tag Name | Small Fan Coil | Base Unit | 42VBD03CRCY5AYKH | Octave band Center Freq, Hz | 125 | 250 | 500 | 1k | 2k | 4k | 8k | dBA |
| Unit Model | 42VBD03CRCY5AYKH | 42VBD03: Vertical Cabinet Fan Coil Unit 300 FCM Cooling 115-1-60 (PSC Std) | Sound Power Data | |||||||||
| Unit Type | 42VB Vertical Cabinet | 1-in. leveling legs set | Radiated Sound Power, dB | 59 | 63 | 57 | 55 | 47 | 43 | 38 | 60 | |
| Unit Size | 300 CFM | Hex fasteners on both cabinet doors | Discharge Sound Power, dB | NA | NA | NA | NA | NA | NA | NA | NA | |
| Fan Speed | High | Drains on Coil, 4-Pipe | ||||||||||
| Motor/Drive | PSC Motor | (2) Union Fittings, Cooling Coil | ||||||||||
| 1-Row Heating Coil - in addition to standard coil - for a 4 pipe system. 3/1 split coil. | ||||||||||||
| Coil Parameters | 20 Non-fused Service Switch | |||||||||||
| Ball valve with Memory Stop, Return Line, Cooling Coil | ||||||||||||
| System Type | 4-Pipe Heating and Cooling | Circuit Setter, Return Line, Cooling Coil | ||||||||||
| Cooling Coil | Cold Fluid Cooling | Ball valve with Memory stop, Supply Line, Cooling Coil | ||||||||||
| Cooling Coil Rows | 3 Rows | Strainer and Blowdown, Supply Line, Cooling Coil | ||||||||||
| Coil Hand | Right Hand | 3-way Motorized Actuator, 25 psi, Supply Line, Cooling Coil | ||||||||||
| Hydronic Coil Test Pressure | 350 psig Coil Test Pressure | (2) Union Fittings, Heating Coil | ||||||||||
| Heating Coil | Hot Fluid Heating | Ball Valve with Memory Stop, Return Line, Heating Coil | ||||||||||
| Heating Coil Rows | 1 row | Circuit Setter, Return Line, Heating Coil | ||||||||||
| Coil wrapping | None | Ball Valve, Supply Line, Heating Coil | ||||||||||
| Strainer and Blowdown, Supply Line, Heating Coil | ||||||||||||
| 3-way Motorized Actuator, 25 psi, Supply Line, Heating Coil | ||||||||||||
| Dimensions | 24" Stanless Steel braided hose with threaded fittings, Supply Line, Heating Coil | |||||||||||
| 24" Stainless Steel braided hose with threaded fittings, Return Line, Cooling Coil | ||||||||||||
| Unit Length | 9 inches | 24" Stainless Steel braided hose with threaded fittings, Supply Line, Cooling Coil | ||||||||||
| Unit Width | 41 inches | 24" Stainless Steel braided hose with threaded fittings, Return Line, Heating Coil | ||||||||||
| Unit Height | 25 inches | Unit-Mtd 3-speed 24V controls by others | ||||||||||
| Shipping Weight | 68 pounds | 1/2 inch (5GPM Maximum) |
Electrical Note: Not all valve components are rated for the selected Hydronic Coil Test Pressure. Refer to the valve component cut sheets in the Product Library for help.
| Motor Voltage | 115-1-60 (PSC Std) V-Ph-Hz |
| Motor FLA | 0.83 |
| Unit MCA | 1.04 |
| MFS | 15 |
Cooling Data Heating Data
| Coil Type | Cold fluid cooling | Coil Type | Hot fluid heating |
| Coil Rows | 3 rows | Coil Rows | 1 row |
| Fluid Type | Fresh water | Fluid Type | Fresh water |
| Total Capacity | 7,162 BTU/hr | Sensible Capacity | 10,949 BTU/hr |
| Sensible Capacity | 5,273 BTU/hr | Entering Air Temp | 60 F |
| Entering Air Dry Bulb Temp | 80 F | Leaving Air Temp | 103.2 F |
| Entering Air Wet Bulb Temp | 67 F | Fluid Flow Rate | 101 gpm |
| Leaving Air Dry Bulb Temp | 59.2 F | Fluid Entering Temp | 180 F |
| Leaving Air Wet Bulb Temp | 57.2 F | Fluid Leaving Temp | 160 F |
| Fluid Flow Rate | 1.4 gpm | Fluid Pressure Drop | .9 - ft wg |
| Fluid Pressure Drop | 5.4 ft wg | ||
| Fluid Entering Temp | 45 F | ||
| Fluid Leaving Temp | 55 F |
Unit Performance
| Actual Airflow | 230 CFM |
| Altitude | 0 ft |
| External Static Pressure | .1 in wg |
| Voltage | 115-1-60 (PSC Std) V-Ph-Hz |
Additional Factory Provided and Field Installed (Valve Assembly for CW and HW)
| Coil Connections | Opposite end | Supply isolation valves: 1/2 in. Ball Valve with Memory Stop (supply) |
| Unit Arrangement | Front Return/Top supply | Return isolation valves: 1/2 in. Ball Valve with Memory Stop (return) |
| Filters | Std 1 in. Throwaway | 24 in. Stainless steel braided hose (supply) |
| Cabinet Colors | Arctic White (std) | 24 in. Stainless steel braided hose (return) |
| Drain Pans | Standard drain pan | 1/2 in. Circuit setter in Return Line with Pressure Ports (CW and HW) |
| Coil Hand | Right hand | 1/2 in. Strainer Y type with blowdown (CW and HW) |
| Control Access Doors | 1-in leveling legs set | Two union fittings at coil 1/2 inch |
| AAV/Drains | Hex fasteners on both cabinet doors | 1/2 inch three-way motorized valve, 2 position, piped normally closed, wired, with one installed belled stub of tubing for field |
| Control Packages | Manual air vents and drains | Heating same as Cooling: Heaing valve package contains the same valve components as the cooling valve package |
| Switches | Unit-mtd 3-speed 24V controls by others | |
| 20A Non-fused Service Switch | ||
| Insulation | Std, fiberglass insulation | |
| Packaging | Units shipped on treated wood pallet | |
| Mounting Type | Floor mount | |
| Cabinet Construction | Standard cabinet construction | |
| Coil Tube | 0.016 Inch wall thickness (Std) |