Sheet1

Unit ParametersOrdering InformationAcoustical Data
Tag NameSmall Fan CoilBase Unit42VBD03CRCY5AYKHOctave band Center Freq, Hz1252505001k2k4k8kdBA
Unit Model42VBD03CRCY5AYKH42VBD03: Vertical Cabinet Fan Coil Unit 300 FCM Cooling 115-1-60 (PSC Std)Sound Power Data
Unit Type42VB Vertical Cabinet1-in. leveling legs setRadiated Sound Power, dB5963575547433860
Unit Size300 CFMHex fasteners on both cabinet doorsDischarge Sound Power, dBNANANANANANANANA
Fan SpeedHighDrains on Coil, 4-Pipe
Motor/DrivePSC Motor(2) Union Fittings, Cooling Coil
1-Row Heating Coil - in addition to standard coil - for a 4 pipe system. 3/1 split coil.
Coil Parameters20 Non-fused Service Switch
Ball valve with Memory Stop, Return Line, Cooling Coil
System Type4-Pipe Heating and CoolingCircuit Setter, Return Line, Cooling Coil
Cooling CoilCold Fluid CoolingBall valve with Memory stop, Supply Line, Cooling Coil
Cooling Coil Rows3 RowsStrainer and Blowdown, Supply Line, Cooling Coil
Coil HandRight Hand3-way Motorized Actuator, 25 psi, Supply Line, Cooling Coil
Hydronic Coil Test Pressure350 psig Coil Test Pressure(2) Union Fittings, Heating Coil
Heating CoilHot Fluid HeatingBall Valve with Memory Stop, Return Line, Heating Coil
Heating Coil Rows1 rowCircuit Setter, Return Line, Heating Coil
Coil wrappingNoneBall Valve, Supply Line, Heating Coil
Strainer and Blowdown, Supply Line, Heating Coil
3-way Motorized Actuator, 25 psi, Supply Line, Heating Coil
Dimensions24" Stanless Steel braided hose with threaded fittings, Supply Line, Heating Coil
24" Stainless Steel braided hose with threaded fittings, Return Line, Cooling Coil
Unit Length9 inches24" Stainless Steel braided hose with threaded fittings, Supply Line, Cooling Coil
Unit Width41 inches24" Stainless Steel braided hose with threaded fittings, Return Line, Heating Coil
Unit Height25 inchesUnit-Mtd 3-speed 24V controls by others
Shipping Weight68 pounds1/2 inch (5GPM Maximum)

Electrical Note: Not all valve components are rated for the selected Hydronic Coil Test Pressure. Refer to the valve component cut sheets in the Product Library for help.

Motor Voltage115-1-60 (PSC Std) V-Ph-Hz
Motor FLA0.83
Unit MCA1.04
MFS15

Cooling Data Heating Data

Coil TypeCold fluid coolingCoil TypeHot fluid heating
Coil Rows3 rowsCoil Rows1 row
Fluid TypeFresh waterFluid TypeFresh water
Total Capacity7,162 BTU/hrSensible Capacity10,949 BTU/hr
Sensible Capacity5,273 BTU/hrEntering Air Temp60 F
Entering Air Dry Bulb Temp80 FLeaving Air Temp103.2 F
Entering Air Wet Bulb Temp67 FFluid Flow Rate101 gpm
Leaving Air Dry Bulb Temp59.2 FFluid Entering Temp180 F
Leaving Air Wet Bulb Temp57.2 FFluid Leaving Temp160 F
Fluid Flow Rate1.4 gpmFluid Pressure Drop.9 - ft wg
Fluid Pressure Drop5.4 ft wg
Fluid Entering Temp45 F
Fluid Leaving Temp55 F

Unit Performance

Actual Airflow230 CFM
Altitude0 ft
External Static Pressure.1 in wg
Voltage115-1-60 (PSC Std) V-Ph-Hz

Additional Factory Provided and Field Installed (Valve Assembly for CW and HW)

Coil ConnectionsOpposite endSupply isolation valves: 1/2 in. Ball Valve with Memory Stop (supply)
Unit ArrangementFront Return/Top supplyReturn isolation valves: 1/2 in. Ball Valve with Memory Stop (return)
FiltersStd 1 in. Throwaway24 in. Stainless steel braided hose (supply)
Cabinet ColorsArctic White (std)24 in. Stainless steel braided hose (return)
Drain PansStandard drain pan1/2 in. Circuit setter in Return Line with Pressure Ports (CW and HW)
Coil HandRight hand1/2 in. Strainer Y type with blowdown (CW and HW)
Control Access Doors1-in leveling legs setTwo union fittings at coil 1/2 inch
AAV/DrainsHex fasteners on both cabinet doors1/2 inch three-way motorized valve, 2 position, piped normally closed, wired, with one installed belled stub of tubing for field
Control PackagesManual air vents and drainsHeating same as Cooling: Heaing valve package contains the same valve components as the cooling valve package
SwitchesUnit-mtd 3-speed 24V controls by others
20A Non-fused Service Switch
InsulationStd, fiberglass insulation
PackagingUnits shipped on treated wood pallet
Mounting TypeFloor mount
Cabinet ConstructionStandard cabinet construction
Coil Tube0.016 Inch wall thickness (Std)