Attachment (2) Enclosure (1) through (12) for Manifold Drawing.pdf

PDF 393 KB Posted

Attached to
Hose Connection and Fire Hose Manifold (SRF-JRMC) Yokosuka, Japan
Solicitation number
N6264926QB082
Issued by

About this file

This file contains engineering drawings for an X99 Fire Hose Manifold assembly used in naval applications. The manifold is available in two configurations: Type-A and Type-B, with detailed technical specifications for manufacturing and assembly.

The X99 Fire Hose Manifold comprises multiple components including main pipes, branch pipes A and B, adapters, cap plates, legs (A and B), and rubber bumpers (SUGATSUNE 200-140-452 or equivalent). The main pipe is constructed from copper-nickel tubing (Cu-Ni 90-10 C7060 or 70-30 C7150) with 3-inch nominal pipe size, while branch pipes are 2.5-inch and 2.125-inch NPS respectively. The adapter features 2.5-inch-7.5 NH threads in accordance with NFPA 1963. All components require red paint finish except internal surfaces and threads, sharp edge breaking, and engraving with manufacturing month, year, and serial number. Manufacturing requirements include penetrant testing per JIS Z 2343 and hydrostatic testing at 216-220 psig for 30 minutes using clean fresh water. Welding specifications require Gas Tungsten Arc Welding with specific preheat (60°F minimum), interpass (150°F maximum), filler metal (MIL-EN/RN67 or equivalent), and shielding gas (Argon) parameters. Socket welding procedures for adapters and branched pipes are detailed in separate drawings with precise joint preparation tolerances and 45-degree beveling requirements. Post-weld heat treatment is not permitted.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LEG A (2EA)

See DWG# C951KKFY18009-7

RUBBER BUMPER (4EA)

SUGATSUNE 200-140-452 or equivalent

ADAPTER

See DWG# C951KKFY18009-6

BRANCH PIPE B

See DWG# C951KKFY18009-5

TYP

MAIN PIPE

See DWG# C951KKFY18009-3

BRANCH PIPE A (2EA)

See DWG# C951KKFY18009-4

CAP PLATE (2EA)

See DWG# C951KKFY18009-9

Engraving;

Manufacturing month, year, serial No.

Enclosure (1)

X99 FIRE HOSE MANIFOLD, Type-A

Approved by - date

Designed by - date

Scale

DWG No.

REV

C951 Kimura - 6-Aug-2018

3rd angle projection

DATE REVISOR MODIFIED PORTIONSREV.

1:4

C951KKFY18009-1

Title

Unit

INCH

NOTES

1. Break all sharp edges and corners.

2. Paint in red except inside and threads.

3. Refer to DWG#

C951KKFY18009-10

through -12 for welding.

4. Perform penetrant testing in accordance with JIS Z 2343.

5. Perform hydrostatic test. Test pressure: 216 - 220 psig, Duration: 30 min, Test fluid: clean fresh water

C241 Oosaki - 31-Aug-2018

RUBBER BUMPER (4EA)

SUGATSUNE 200-140-452 or equivalent

TYP

MAIN PIPE

See DWG# C951KKFY18009-3

BRANCH PIPE B

See DWG# C951KKFY18009-5

ADAPTER

See DWG# C951KKFY18009-6

BRANCH PIPE A (2EA)

See DWG# C951KKFY18009-4

LEG B (2EA)

See DWG# C951KKFY18009-8

CAP PLATE (2EA)

See DWG# C951KKFY18009-9

Engraving;

Manufacturing month, year, serial No.

Enclosure (2)

X99 FIRE HOSE MANIFOLD, Type-B

Approved by - date

Designed by - date

Scale

DWG No.

REV

C951 Kimura - 6-Aug-2018

3rd angle projection

DATE REVISOR MODIFIED PORTIONSREV.

1:4

C951KKFY18009-2

Title

Unit

INCH

NOTES

1. Break all sharp edges and corners.

2. Paint in red except inside and threads.

3. Refer to DWG#

C951KKFY18009-10

through -12 for welding.

4. Perform penetrant testing in accordance with JIS Z 2343.

5. Perform hydrostatic test. Test pressure: 216 - 220 psig, Duration: 30 min, Test fluid: clean fresh water

14"

∅2

2-∅2

8"

TUBE, METALLIC, 3" NPS

Mat'l: Cu-Ni 90-10 (C7060) or 70-30 (C7150)

O.D.: 3.50 ±0.01"

WALL: 0.16" to 0.22"

4710-01-422-9584 or eq.

60°

60°

Enclosure (3)

NOTES

1. Unless otherwise specified, allowable tolerance shall be JIS B 0405 CLASS C.

2. Unless otherwise specified, finish all over.

3. Break all sharp edges and corners.

FIRE HOSE MANIFOLD, MAIN PIPE

Approved by - date

Designed by - date

Scale

DWG No.

REV

C951 Kimura - 6-Aug-2018

3rd angle projection

DATE REVISOR MODIFIED PORTIONSREV.

1/2

C951KKFY18009-3

Title

Unit

INCH

R1

3"

TUBE, METALLIC, 2-1/2" NPS

Mat'l: Cu-Ni 90-10 (C7060) or 70-30 (C7150)

O.D.: 2.875 ±0.008"

WALL: 0.187 ±0.018"

P/N: 710200.450 (Mfr: W&O) or eq.

2.5"-11 NPT

Coutinuously beveled.

Process (1) Process (2)

45°

45°

Enclosure (4)

NOTES

1. Unless otherwise specified, allowable tolerance shall be JIS B 0405 CLASS C.

2. Unless otherwise specified, finish all over.

3. Break all sharp edges and corners.

Approved by - date

Designed by - date

Scale

DWG No.

REV

C951 Kimura - 6-Aug-2018

3rd angle projection

DATE REVISOR MODIFIED PORTIONSREV.

1/2

C951KKFY18009-4

Title

Unit

INCH

R1

TUBE,METALLIC

Mat'l: Cu-Ni 90-10 (C7060) or 70-30 (C7150)

O.D.: 2.875 ±0.008"

WALL: 0.187 ±0.018"

P/N: 710200.450 (Mfr: W&O) or eq.

Process (1) Process (2)

Coutinuously beveled.

45°

45°

C

Enclosure (5)

NOTES

1. Unless otherwise specified, allowable tolerance shall be JIS B 0405 CLASS C.

2. Unless otherwise specified, finish all over.

3. Break all sharp edges and corners.

Approved by - date

Designed by - date

Scale

DWG No.

REV

C951 Kimura - 6-Aug-2018

3rd angle projection

DATE REVISOR MODIFIED PORTIONSREV.

1/2

C951KKFY18009-5

Title

Unit

INCH

1"

35°

C

"-7

NH

2.92"

+0.011"

-0.014"

C

R

C

∅3

"∅3

∅4

R

Center of ∅1/4" endmill

R

DETAIL OF ROCKER LUG

SCALE: 1/1

(∅3

∅2.47"

Enclosure (6)

NOTES

1. Material: Cu-Ni 90-10 (C7060) or 70-30 (C7150)

2. Unless otherwise specified, allowable tolerance shall be JIS B 0405 CLASS C.

3. Unless otherwise specified, finish all over.

4. 2.5"-7.5 NH threads shall be provided in accordance with NFPA 1963.

5. Break all sharp edges and corners.

FIRE HOSE MANIFOLD, ADAPTER

Approved by - date

Designed by - date

Scale

DWG No.

REV

C951 Kimura - 23-Aug-2018

3rd angle projection

DATE REVISOR MODIFIED PORTIONSREV.

1/2

C951KKFY18009-6

Title

Unit

INCH

11"

5"

2"

4-R

5"

5"

10"

1"

2-∅

" HOLE

" THK

R1

Enclosure (7)

NOTES

1. Material: Cu-Ni 90-10 (C7060) or 70-30 (C7150)

2. Unless otherwise specified, allowable tolerance shall be JIS B 0405 CLASS C.

3. Break all sharp edges and corners.

FIRE HOSE MANIFOLD, LEG A

Approved by - date

Designed by - date

Scale

DWG No.

REV

C951 Kimura - 6-Aug-2018

3rd angle projection

DATE REVISOR MODIFIED PORTIONSREV.

1/2

C951KKFY18009-7

Title

Unit

INCH

1"

30°

3"

R

5"

4-R

1"

2-∅

" HOLE

3"

3"

" THK

R1

Enclosure (8)

NOTES

1. Material: Cu-Ni 90-10 (C7060) or 70-30 (C7150)

2. Unless otherwise specified, allowable tolerance shall be JIS B 0405 CLASS C.

3. Break all sharp edges and corners.

FIRE HOSE MANIFOLD, LEG B

Approved by - date

Designed by - date

Scale

DWG No.

REV

C951 Kimura - 6-Aug-2018

3rd angle projection

DATE REVISOR MODIFIED PORTIONSREV.

1/2

C951KKFY18009-8

Title

Unit

∅3

60°

Enclosure (9)

NOTES

1. Material: Cu-Ni 90-10 (C7060) or 70-30 (C7150)

2. Unless otherwise specified, allowable tolerance shall be JIS B 0405 CLASS C.

3. Break all sharp edges and corners.

FIRE HOSE MANIFOLD, CAP PLATE

Approved by - date

Designed by - date

Scale

DWG No.

REV

C951 Kimura - 6-Aug-2018

3rd angle projection

DATE REVISOR MODIFIED PORTIONSREV.

1/2

C951KKFY18009-9

Title

Unit

2-1/2" PIPE

" to

0.19" x 0.33" (MIN)

ADAPTER

Enclosure (10)

FIRE HOSE MANIFOLD, WLD ADAPTER

Approved by - date

Designed by - date

Scale

DWG No.

REV

C951 Kimura - 6-Aug-2018

3rd angle projection

DATE REVISOR MODIFIED PORTIONSREV.

1/1

C951KKFY18009-10

Title

Unit

INCH

Notes

1. Socket welding between Adapter and Pipe shall be in accordance with this drawing.

2. Welding Process: Gas Tungsten Arc Welding

3. Preheat: 60°F (Min)

4. Interpass: 150°F (Max)

5. Filler Metal Type: MIL-EN/RN67 or equivalent

6. Torch Shielding Gas Type: Argon

7. Shielding Gas Flow Rate: 15 - 30 cubic feet/min

8. Diameter of Tungsten Electrode: 3/32" (Max)

9. Torch Cup Size: 5/16" (Min)

10. Post Weld Heat Treatment shall not be allowed.

References

1. NAVSHIPREPFACPI 074-5A

2. MIL-STD-22D P-14

3. JIS Z 3420

0 to

0.1"

45°

2-1/2" PIPE

3" PIPE

Enclosure (11)

Approved by - date

Designed by - date

Scale

DWG No.

REV

C951 Kimura - 6-Aug-2018

3rd angle projection

DATE REVISOR MODIFIED PORTIONSREV.

1/1

C951KKFY18009-11

Title

Unit

INCH

Notes

1. Welding for branched pipes shall be in accordance with this drawing.

2. Welding Process: Gas Tungsten Arc Welding

3. Preheat: 60°F (Min)

4. Interpass: 150°F (Max)

5. Filler Metal Type: MIL-EN/RN67 or equivalent

6. Torch Shielding Gas Type: Argon

7. Shielding Gas Flow Rate: 15 - 30 cubic feet/min

8. Diameter of Tungsten Electrode: 3/32" (Max)

9. Torch Cup Size: 5/16" (Min)

10. Post Weld Heat Treatment shall not be allowed.

References

1. NAVSHIPREPFACPI 074-5A

2. MIL-STD-22D P-62

0 to

60° MIN

CAP PLATE

3" PIPE

Enclosure (12)

Approved by - date

Designed by - date

Scale

DWG No.

REV

C951 Kimura - 6-Aug-2018

3rd angle projection

DATE REVISOR MODIFIED PORTIONSREV.

1/1

C951KKFY18009-12

Title

Unit

INCH

Notes

1. Welding between Pipe and Cap Plate shall be in accordance with this drawing.

2. Welding Process: Gas Tungsten Arc Welding

3. Inside purging is required.

4. Preheat: 60°F (Min)

5. Interpass: 150°F (Max)

6. Filler Metal Type: MIL-EN/RN67 or equivalent

7. Torch Shielding/Purging Gas Type: Argon

8. Shielding Gas Flow Rate: 15 - 30 cubic feet/min

9. Diameter of Tungsten Electrode: 3/32" (Max)

10. Torch Cup Size: 5/16" (Min)

11. Post Weld Heat Treatment shall not be allowed.

References

1. NAVSHIPREPFACPI 074-5A

2. MIL-STD-22D P-2

File details come from the government source that posted it. Updated .