ATTACHMENT 2 ELECTRICAL DRAWINGS.pdf
PDF 3 MB Posted
- Attached to
- Power Infrastructure and Solar System Upgrades, Mauna Loa Observatory Federal contract opportunity
- Solicitation number
- 1305M324R0042
About this file
This document is a solicitation (Solicitation Number: 1305M324R0042) for the Power Infrastructure and Solar System Upgrade Project at the Mauna Loa Atmospheric Baseline Observatory (MLO) site in Hawaii. The solicitation is issued by the Department of Commerce National Oceanic and Atmospheric Administration (NOAA) and requires offerors to provide all supervision, tools, materials, labor, and services necessary for the completion of the work.
The key details include a deadline of 10:00 AM Mountain Time on April 29, 2024 for submitting questions, and the solicitation is requesting proposals for upgrades to the power infrastructure and solar systems at the MLO site. The scope of work includes, but is not limited to, the installation of new electrical switchgear, panels, wiring, and a new ground-mounted utility approved junction box. Offerors are required to review the entirety of the solicitation, which includes drawings and specifications, and to visit the site to verify all dimensions and site conditions prior to submitting a bid.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 1305M324R00420004 SF30.pdf | ||
| 1305M324R0042 Solicitation Questions and Answers.pdf | ||
| ATTACHMENT 2 - Geotechnical Reconnaissance Report.pdf | ||
| ATTACHMENT 8 - MLO Site Pictures.zip | ZIP file | |
| ATTACHMENT 6 - MLO Electrical Grounding Survey.pdf | ||
| ATTACHMENT 7 - Aerial Photography Existing Buildings.pdf | ||
| 1305M324R00420003 SF30.pdf | ||
| 1305M324R00420002 SF30.pdf | ||
| 1305M324R00420001 SF30.pdf | ||
| ATTACHMENT 4 BANNED CONSTRUCTION MATERIALS LIST.pdf | ||
| 1305M324R0042 SF1442.pdf | ||
| ATTACHMENT 3 POSSIBLE POWER AND NETWORK TRENCH ROUTES.pdf | ||
| ATTACHMENT 5 CONSTRUCTION WAGE RATE REQUIREMENTS HI20240001.pdf | ||
| ATTACHMENT 1 STATEMENT OF WORK.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPLICABLE CODES
HAWAII STATE BUILDING CODE AND
AMMEDMENTS TO THE IBC 2018
ELECTRIC CODE NEC 2017
PLUMBING CODE UPC 2018
MECHANICAL CODE IMC 2018
BARRIER FREE CODE ANSI 117.1-2009
FIRE PROTECTION CODE IFC 2018
HVAC&R STANDARD ASHRAE 90.1-2013
ENERGY CODE IECC 2018
FUEL GAS CODE IFGC 2018
CHAPTER 11 OF IBC/2018
C O
P Y
R I G
H T
D
J
A
R C
H I T
E C
T U
R E
L
L C
U
N A
U T
H O
R I Z
E
R
P
R O
D U
C T
I O
N
O
R
O
T H
S
O
F
T
H I
A
W I N
G
R
I C
T L
Y
P
R O
H I B
I T
E D
H ad d o n fi e ld
-B e rl in R d
Su it e
V o o rh e e s, N J
-8
-2 w w w .d j-a rc h .c om
DRAWING TITLE:
PROJECT NO. 201203
DRAWN BY: KMK
CHECKED BY: DEJ
SCALE: AS NOTED
ISSUE FOR:
BID 07/30/21
P R
O P O
SE
D
A L T
E R
A T
IO
N
S F
O R
M A
U N
A L
O A
O B
SE
R
V A
T O
R Y
C A
M P U
S
-2
M
A U
N A
L O
A A
C C
E
SS
R O
A D
W A
IM
E A
H
I
P
R
E
L
I
M
I
N
A
R
Y
N
R
C
O
N
S
T
R
U
C
T
I
O
N
A0.0
COVER SHEET
KEY PLAN
LOCATION MAP
ARCHITECT:
DJ ARCHITECTURE, LLC
1010 HADDONFIELD-BERLIN ROAD, SUITE 405
VOORHEES, NJ 08043
CONTACT: DAN JOST, RA
PH: 856-809-2791
EMAIL: DJOST@DJ-ARCH.COM
PROJECT TEAM
T.O. CONC.
EL. 0'-0"
SYMBOLS LEGEND
COLUMN LINE
A
AX.X
AX.X
FINISH
SF-##
P?
RM NAME
##/A#.#
T.O. CONC
EL. 0'-0"
ELEVATION/DWG. OR
BLDG. SECTION/DWG.
OR WALL
SECTION/DWG.
DETAIL/DWG.
FINISH TYPE
STOREFRONT TYPE
PARTITION TYPE
ROOM NAME/NUMBER
DOOR NUMBER
WINDOW TYPE
INTERIOR ELEVATION
SPOT ELEVATION
DATUM ELEVATION
REVISION - ADDENDUM
REVISION -
CONSTRUCTION
BULLETIN
C.J. CONTROL JOINT
CLG. CEILING
CLKG. CAULKING
CLR. CLEAR
C.O. CASED OPENING
COL. COLUMN
CONC. CONCRETE
CONN. CONNECTION
CONST. CONSTRUCTION
CONT. CONTINUOUS
CORR. CORRIDOR
CTSK. COUNTERSUNK
CNTR. COUNTER
C.T. CERAMIC TILE
CTR. CENTER
DBL. DOUBLE
DEPT. DEPARTMENT
D.F. DRINKING FOUNTAIN
DET. DETAIL
DIA. DIAMETER
DIM. DIMENSION
DISP. DISPENSER
DN. DOWN
HDWE HARDWARE
H.M. HOLLOW METAL
HORIZ. HORIZONTAL
HR. HOUR
I.D. INSIDE DIMENSION
INSUL. INSULATION
INT. INTERIOR
O.A. OVERALL
OBS. OBSCURE
O.C. ON CENTER
O.D. OUTSIDE DIMENSION
OPNG. OPENING
OPP.
OPPOSITE
PRCST. PRE-CAST
PL. PLATE
P.LAM. PLASTIC LAMINATE
PLAS. PLASTER
PLYWD. PLYWOOD
HDWD HARDWOOD
D.O. DOOR OPENING
DR. DOOR
DWR. DRAWER
DS. DOWNSPOUT
DWG. DRAWING
E. EAST
E.J. EXPANSION JOINT
EL. ELEVATION
ELEC. ELECTRICAL
EMER. EMERGENCY
ENCL. ENCLOSURE
EQ. EQUAL
EQPT. EQUIPMENT
E.W.C. ELECTRIC WATER COOLER
EXIST. EXISTING
EXPO. EXPOSED
EXP. EXPANSION
EXT. EXTERIOR
F.D. FLOOR DRAIN
FDN. FOUNDATION
F.E. FIRE EXTINGUISHER
F.E.C. FIRE EXTINGUISHER CABINET
FIN. FINISH
FIXT. FIXTURE
FL. FLOOR
FLASH. FLASHING
FLUOR. FLUORESCENT
F.O.C. FACE OF CONCRETE
F.O.F. FACE OF FINISH
F.O.S. FACE OF STUDS
FT. FOOT OR FEET
FTG. FOOTING
FURR. FURRING
GALV. GALVANIZED
GL. GLASS
GR. GRADE
GYP. GYPSUM
GYP.BD. GYPSUM WALLBOARD
H.B. HOSE BIBB
H.C. HOLLOW CORE
PR. PAIR
PSF POUNDS PER SQUARE FOOT
Q.T. QUARRY TILE
R. RISER
RAD. RADIUS
R.D. ROOF DRAIN
REF. REFERENCE
REFR. REFRIGERATOR
REINF REINFORCED
REQD REQUIRED
RESIL. RESILIENT
RM. ROOM
R.O. ROUGH OPENING
RWC RAINWATER CONDUCTOR
S. SOUTH
S.C. SOLID CORE
SCHED. SCHEDULED
SHT. SHEET
S.J. SAWCUT JOINT
SIM. SIMILAR
SPEC. SPECIFICATION
SPECD. SPECIFIED (SECTION)
S.ST. STAINLESS STEEL
STD. STANDARD
STL. STEEL
STOR. STORAGE
STRUC. STRUCTURAL
SUSP. SUSPENDED
T.C. TOP OF CURB
TEL. TELEPHONE
T&G TONGUE AND GROOVE
THK. THICK
T.O. TOP OF
T.P. TOP OF PAVEMENT
TV TELEVISION
T.W. TOP OF WALL
TYP. TYPICAL
UNF. UNFINISHED
U.O.N. UNLESS OTHERWISE NOTED
UR. URINAL
VCT VINYL COMPOSITION TILE
VERT. VERTICAL
VEST. VESTIBULE
W. WEST
W/ WITH
WD WOOD
WITHOUTW/O
WATERPROOFWP
WAINSCOTWSCT.
WT. WEIGHT
EA. EACH
CMU CONCRETE MASONRY UNIT
D DEPTH
H.D. HEAVY DUTY
HEIGHTHGT.
PSI POUNDS PER SQUARE INCH
RET. RETAINING
TS TUBE STEEL
FIRE-RETARDANT TREATEDFR.TR.
INSULATING GLASSI.G.
PR.TR. PRESSURE TREATED
T.G. TEMPERED GLASS
U.G. UNDERGROUND
HSS HOLLOW STEEL SECTION
P.O.C. POINT OF CONNECTION
EXT. INSUL. & FINISH SYSTEME.I.F.S.
O.H.
OVERHANG
R.T.U. HVAC UNIT
P.S.F.F. PREFAB. STRUC. STL. FABR.
FABR. FABRICATOR/ FABRICATED
FURRING CHANNELF.C.
F.O.M. FACE OF MASONRY
WIDTHWDT.
VENT THRU ROOF
VERIFY IN FIELDV.I.F.
V.T.R.
THR. THRESHOLD
SF STOREFRONT
SECTIONSECT.
INFORMATIONINFO.
PLUMBINGPLMB.
QUARTERQTR.
RND. ROUND
FACE OF (XX)F.O.(XX)
GA. GAUGE
PARTITIONPRTN.
TEMPERED INSULATING GLASST.I.G.
VINYL WALL COVERINGVWC
PT. POINT
PTD. PAINTED
S.F. SQUARE FEET
CER. CERAMIC
C.I. CAST IRON
C.G. CORNER GUARD
NO. NUMBER
NOM. NOMINAL
N.T.S. NOT TO SCALE
COLD FORMEDC.F.
ARCH. DRAWING ABBREVIATIONS
& AND
L ANGLE
@ AT
L
CENTERLINE
# POUND or NUMBER
ACCES. ACCESSIBLE
AL. ALUMINUM
APPROX. APPROXIMATE
ARCH. ARCHITECTURAL
ASPH. ASPHALT
BD. BOARD
BITUM. BITUMINOUS
BLDG. BUILDING
BLK. BLOCK
BM. BEAM
B.O. BOTTOM OF
CAB. CABINET
CEM. CEMENT
JAN. JANITOR
JT. JOINT
KIT. KITCHEN
LAM. LAMINATE
LAV. LAVATORY
LLH LONG LEG HORIZONTAL
MAX. MAXIMUM
MECH. MECHANICAL
MEMB. MEMBRANE
MET. METAL
MFR. MANUFACTURER
MIN. MIMIMUM
MISC. MISCELLANEOUS
M.O. MASONRY OPENING
M.R. MOISTURE RESISTANT
MTD. MOUNTED
N. NORTH
N.I.C. NOT IN CONTRACT
C
B.C. BACK OF CURB
L. LENGTH
MED. MEDIUM
MASONRYMAS.
BRG.
BTWN.
BEARING
BETWEEN
ADJ. ADJUSTABLE
A.F.F. ABOVE FINISH FLOOR
ACOUSTICAL CEILING TILEACT.
BUILT-UP ROOFINGBUR MOUNTINGMTG.
LLV LONG LEG VERTICAL
LT. LIGHT
MAUNA LOA
OBSERVATORY
AREA OF
WORK
PROPOSED ALTERATIONS FOR:
MAUNA LOA OBSERVATORY
NOAA OBSERVATORY
44-2441 MAUNA LOA ACCESS ROAD
WAIMEA, HI 96743
BUILDING CODE DATA
ELECTRICAL ENGINEER:
SCHOOLEY ELECTRIC
1812 GARDEN AVENUE
CHERRY HILL, NJ 08003
CONTACT: JOE SCHOOLEY, PE
PH: 856-424-7900
CELL: 856-261-4859
EMAIL: EMAIL@SCHOOLEYELECTRIC.COM
OWNER:
U.S. DEPARTMENT OF COMMERCE/NOAA
WESTERN ACQUISITION DIVISION
325 BROADWAY, SOU6
BOULDER, CO 80305
CONTACT: BRIAN VASEL
PHONE: 303-497-6655
EMAIL: BRIAN.VASEL@NOAA.GOV
GENERAL NOTES
FE
FIRE EXTINGUISHER,
SURFACE MOUNTED,
LOCATIONS TO BE
DETERMINED IN FIELD W/
OWNER IN ACCORDANCE
W/ NFPA REGULATIONS
AutoCAD SHX Text SCOPE OF WORK: THESE DRAWINGS INDICATE GENERAL SCOPE OF WORK AND : THESE DRAWINGS INDICATE GENERAL SCOPE OF WORK AND DESIGN INTENT FOR THE PROJECT. THIS DRAWING SET IS INTENDED FOR BIDDING ONLY AND NOT FOR CONSTRUCTION. THE CONTRACTOR SHALL VISIT THE SITE, REVIEW CONSTRUCTION CONDITIONS AND, PRIOR TO SUBMITTING A FINAL BID, SHALL VERIFY ALL DIMENSIONS SHOWN ON THE DRAWINGS, ALL SITE CONDITIONS, AND ALL REQUIREMENTS FOR THE PROJECT. THE INTENTION OF THESE DRAWINGS IS TO PROVIDE FOR WORK COMPLETE IN EVERY DETAIL EVEN THOUGH EVERY ITEM INVOLVED MAY NOT BE SHOWN OR MENTIONED IN PARTICULAR. VARIATIONS OR AMBIGUITIES BETWEEN THESE DRAWINGS AND ACTUAL SITE CONDITIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND OWNER IN WRITING AND SHALL BE RESOLVED AND DOCUMENTED BY THE CONTRACTOR IN WRITING. THE CONTRACTOR SHALL PROVIDE ALL SUPERVISION, TOOLS, MATERIAL, LABOR, SERVICES, TRANSPORTATION, ETC. NECESSARY FOR COMPLETION OF THE WORK INTENDED TO BE SHOWN AND/OR DESCRIBED.
AutoCAD SHX Text PERMITS: THE CONTRACTOR SHALL SECURE AND PAY FOR THE BUILDING PERMIT AND : THE CONTRACTOR SHALL SECURE AND PAY FOR THE BUILDING PERMIT AND FOR ALL OTHER PERMITS AND GOVERNMENTAL FEES, LICENSES AND INSPECTIONS NECESSARY FOR THE PROPER EXECUTION OF THE WORK.
AutoCAD SHX Text MATERIALS AND GUARANTEE: ALL MATERIALS AND EQUIPMENT FURNISHED FOR THE : ALL MATERIALS AND EQUIPMENT FURNISHED FOR THE PROJECT SHALL BE NEW, UNLESS OTHERWISE SPECIFIED, AND ALL WORK SHALL BE OF GOOD QUALITY AND FREE FROM FAULTS AND DEFECTS. ALL WORK SHALL BE GUARANTEED FOR ONE (1) FULL YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION. ALL MANUFACTURER'S WARRANTIES SHALL BE IN EXCESS OF THE CONTRACTOR'S GUARANTEE.
AutoCAD SHX Text MEANS AND METHODS: THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR : THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, AND PRODUCTION PROCEDURES REQUIRED FOR THE PROPER AND SAFE EXECUTION AND COMPLETION OF THE WORK AND FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY PRECAUTIONS, PROCEDURES AND PROBLEMS IN CONNECTION WITH THE WORK.
AutoCAD SHX Text CHANGES IN THE WORK: THE ARCHITECT IS NOT RESPONSIBLE FOR SITE INSPECTIONS, : THE ARCHITECT IS NOT RESPONSIBLE FOR SITE INSPECTIONS, GENERAL OBSERVATIONS AND/OR DEVIATIONS FROM THE CONSTRUCTION DOCUMENTS. NO DEVIATIONS FROM THE WORK SHOWN OR REASONABLY IMPLIED SHALL BE UNDERTAKEN WITHOUT CONSENT FROM THE ARCHITECT.
AutoCAD SHX Text 6.
AutoCAD SHX Text 5.
AutoCAD SHX Text 4.
AutoCAD SHX Text 3.
AutoCAD SHX Text American National Standards Institute (ANSI) American Society for Testing and Materials (ASTM) American Concrete Institute (ACI) American Society of Civil Engineers (ASCE) American Institute of Steel Construction (AISC) American Welding Society (AWS) Factory Mutual System (FM) Institute of Electrical & Electronics (IEEE) National Association of Architectural Metal Manufacturers (NAAMM) National Concrete Masonry Association (NCMA) National Fire Protection Association (NFPA) Steel Deck Institute (SDI) Steel Joist Institute (SJI) U.S. Department of Commerce - National Bureau of Standards (DOC) Underwriters Laboratories (UL) Local codes, state laws and all other governing authorities
AutoCAD SHX Text REFERENCE STANDARDS: ALL EQUIPMENT, TESTS, MATERIALS, AND DETAILS OF : ALL EQUIPMENT, TESTS, MATERIALS, AND DETAILS OF INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS AND LATEST REVISIONS OF THE FOLLOWING APPLICABLE STANDARDS:
AutoCAD SHX Text 2.
AutoCAD SHX Text 1.
AutoCAD SHX Text
CURRENT ISSUE DRAWINGS
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DRAWING TITLE
AutoCAD SHX Text
CURRENT ISSUE
AutoCAD SHX Text
DATE ISSUED
AutoCAD SHX Text A0.0
AutoCAD SHX Text
COVER SHEET, CODE DATA
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A0.1
AutoCAD SHX Text
SITE PLAN
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A1.1
AutoCAD SHX Text
KEELING BUILDING ADDITION DEMOLITION PLAN
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A1.2
AutoCAD SHX Text
KEELING BUILDING ADDITION FLOOR PLAN
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A1.3
AutoCAD SHX Text
KEELING BUILDING ADDITION FLOOR FINISH AND POWER PLANS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A1.4
AutoCAD SHX Text
KEELING BUILDING ADDITION REFLECTED CEILING PLAN
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A1.5
AutoCAD SHX Text
KEELING BUILDING ADDITION ROOF PLAN, ROOF FRAMING PLAN
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A1.6
AutoCAD SHX Text
KEELING BUILDING ADDITION SCHEDULES AND DETAILS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A1.7
AutoCAD SHX Text
KEELING BUILDING ADDITION EXTERIOR ELEVATIONS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A1.8
AutoCAD SHX Text
KEELING BUILDING ADDITION SECTIONS AND DETAILS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A1.9
AutoCAD SHX Text
KEELING BUILDING MILLWORK DETAILS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A2.2
AutoCAD SHX Text
TOWER BUILDING FLOOR PLAN
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A2.4
AutoCAD SHX Text
TOWER BUILDING REFLECTED CEILING AND POWER PLANS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A2.5
AutoCAD SHX Text
TOWER BUILDING ROOF PLAN, ROOF FRAMING PLAN
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A2.6
AutoCAD SHX Text
TOWER BUILDING SCHEDULES AND DETAILS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A2.7
AutoCAD SHX Text
TOWER BUILDING EXTERIOR ELEVATIONS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A2.8
AutoCAD SHX Text
TOWER BUILDING SECTIONS AND DETAILS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A3.2
AutoCAD SHX Text
GARAGE/CARPORT FLOOR PLAN
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A3.4
AutoCAD SHX Text
GARAGE/CARPORT REFLECTED CEILING AND POWER PLANS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A3.5
AutoCAD SHX Text
GARAGE/CARPORT ROOF PLAN, ROOF FRAMING PLAN
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A3.6
AutoCAD SHX Text
GARAGE/CARPORT SCHEDULES AND DETAILS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A3.7
AutoCAD SHX Text
GARAGE/CARPORT EXTERIOR ELEVATIONS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text A3.8
AutoCAD SHX Text
GARAGE/CARPORT SECTIONS AND DETAILS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text M1.0
AutoCAD SHX Text
MECHANICAL FLOOR PLANS AND NOTES
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text M2.0
AutoCAD SHX Text
MECHANICAL SCHEDULE AND NOTES
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text E0.0
AutoCAD SHX Text
ELECTRICAL KEY PLAN AND GENERAL NOTES
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text E1.1
AutoCAD SHX Text
KEELING ELECTRICAL POWER AND LIGHTING PLANS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text E2.1
AutoCAD SHX Text
TOWER ELECTRICAL POWER AND LIGHTING PLANS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
AutoCAD SHX Text E3.1
AutoCAD SHX Text
GARAGE/CARPORT ELECTRICAL POWER AND LIGHTING PLANS
AutoCAD SHX Text
BID
AutoCAD SHX Text 07/30/21
A0.1
A0.1
A0.1
A0.1
C O
P Y
R I G
H
J
A
R C
H I T
E C
T U
R E
L
L C
N A
U T
H O
R I Z
P
R O
D U
C T
I O
N
O
R
O
T H
T
H
A
W I N
G
R
I C
T L
Y
P
R O
H I B
I T
E D
H ad d o n fi e ld
-B e rl in R d
Su it e
V o o rh e e s, N J
-8
-2 w w w .d j-a rc h .c om
DRAWING TITLE:
PROJECT NO. 201203
DRAWN BY: KMK
CHECKED BY: DEJ
SCALE: AS NOTED
ISSUE FOR:
BID 07/30/21
P R
O P O
SE
D
A L T
E R
A T
IO
N
S F
O R
M A
U N
A L
O A
O B
SE
R
V A
T O
R Y
C A
M P U
S -2
M
A U
N A
L O
A A
C C
E
SS
R O
A D
W A
IM
E A
H
I
P
R
E
L
I
M
I
N
A
R
Y
N
R
C
O
N
S
T
R
U
C
T
I
O
N
A0.1
SITE PLAN
1"=30'
SITE DEMO PLAN
1"=30'
PROPOSED SITE PLAN
1/4" = 1'-0"
CHIN BUILDING PAD EXPANSION
1/2" = 1'-0"
CHIN BUILDING PAD EXPANSION DETAIL
1/2" = 1'-0"
CHIN BUILDING EXISTING PAD DETAIL
AutoCAD SHX Text
ASIAA COMPLEX
AutoCAD SHX Text
GONG
AutoCAD SHX Text
NDACC BULDING
AutoCAD SHX Text
ASIAA COMPLEX
AutoCAD SHX Text
GONG
AutoCAD SHX Text
NDACC BULDING
AutoCAD SHX Text WALKWAY NOTE: HEAVY HEAVY DUTY GRIP STRUT WALKWAY PANELS, 10GA GALVANIZED STEEL, 36" WIDE, PART #H-85010-W BY METALS, INC.
AutoCAD SHX Text
CABLE TRAY NOTE: 12" WIDE BY 5 1/4" DEEP ALUMINUM CABLE LADDER TRAY
AutoCAD SHX Text NOTE: SITE PLANS ARE DIAGRAMMATIC IN NATURE AND ARE ONLY INTENDED TO SHOW APPROXIMATE LOCATIONS OF BUILDING AND NEW WORK
AutoCAD SHX Text
SIM.
AutoCAD SHX Text EXISTING BUILDING NOTES: - SEAL AND PAINT EXISTING SEAL AND PAINT EXISTING EXTERIOR TO MATCH KEELING BUILDING. - PROVIDE EXHAUST FAN ON SWITCH.PROVIDE EXHAUST FAN ON SWITCH.
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
GRADE
GRADE
1. ALL WORK PERFORMED SHALL COMPLY WITH THE PROVISIONS OF THE DRAWINGS AND SHALL SATISFY ALL APPLICABLE CODES, ORDINANCES, AND REGULATIONS OF ALL GOVERNING
BODIES INVOLVED INCLUDING THE LATEST VERSION OF THE NATIONAL ELECTRIC CODE.
2. ALL WORK DETAILED ON THESE ELECTRICAL DRAWINGS SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR UNLESS OTHERWISE INDICATED. THE ELECTRICAL
CONTRACTOR IS RESPONSIBLE FOR ALL WORK MATERIAL AND LABOR TO SATISFY A COMPLETE AND WORKING SYSTEM WHETHER IMPLIED OR SPECIFIED.
3. ALL DRAWINGS SHALL BE REVIEWED BY THE ELECTRICAL CONTRACTOR TO BECOME FAMILIAR WITH THE REQUIREMENTS OF THE PROJECT. THE ELECTRICAL CONTRACTOR IS REQUIRED
TO ALERT THE PROFESSIONAL ENGINEER OF ANY DISCREPANCIES ON THE DRAWINGS IMMEDIATELY. THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH
THE SCOPE OF WORK.
5. ALL WIRING AND CONDUIT SIZING SHALL BE IN COMPLIANCE WITH ARTICLE 310 AND APPENDIX C OF THE LATEST VERSION OF THE NATIONAL ELECTRIC CODE.
6. STANDARDS OF THE FOLLOWING ORGANIZATIONS ARE APPLICABLE: ILLUMINATING ENGINEERING SOCIETY (IES), AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), INSTITUTE OF
ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE), INSULATED CABLE ENGINEERS ASSOCIATION (ICEA), NATIONAL ELECTRICAL CODE (NEC), NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION (NEMA), NATIONAL ELECTRICAL SAFETY CODE (NESC), NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), UNDERWRITER'S LABORATORIES (UL), OCCUPATIONAL SAFETY
AND HEALTH ACT (OSHA)
7. ALL WORK SHALL COMPLY WITH ALL REGULATIONS AND BE SUBJECT TO INSPECTION AND APPROVAL OF AUTHORITIES HAVING JURISDICTION.
8. THE ELECTRICAL CONTRACTOR IS REQUIRED TO OBTAIN AND PAY FOR ALL NECESSARY ELECTRICAL PERMITS AND FEES.
9. THE ELECTRICAL CONTRACTOR IS REQUIRED TO CHECK ALL EQUIPMENT DIMENSIONS PRIOR TO PURCHASE OF ANY EQUIPMENT. IF THERE IS A DISCREPANCY BETWEEN THESE DRAWINGS
AND THE EQUIPMENT TO BE PURCHASED, THE ELECTRICAL CONTRACTOR SHALL NOTIFY THE PROFESSIONAL ENGINEER IMMEDIATELY AND NOT PURCHASE EQUIPMENT UNTIL RESOLVED.
10. ALL MATERIAL AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS' INSTRUCTIONS. THIS INCLUDES THE USE OF CALIBRATED TORQUE WRENCHES
AND SCREWDRIVERS TO TIGHTEN ALL TERMINALS, LUGS, AND BUS JOINTS.
11. ALL WORK SHALL COMPLY WITH STARTUP PROCEDURES AS DEFINED BY CONSTRUCTION MANAGER AND OWNER. ANY SHUTDOWNS TO ELECTRICAL SYSTEMS SHALL BE COORDINATED
WITH OWNER AND CONSTRUCTION MANAGER.
12. ALL ELECTRICAL WORK SHALL BE ARRANGED IN A NEAT, WELL-ORGANIZED MANNER. THE ELECTRICAL CONTRACTOR SHALL APPLY, INSTALL, CONNECT, ERECT, USE, CLEAN, ADJUST, AND
CONDITION ALL MATERIALS AND ALL EQUIPMENT AS RECOMMENDED BY THE MANUFACTURERS IN PUBLISHED LITERATURE.
13. ANY OPENINGS MADE THROUGH MASONRY AND CONCRETE BY CORE DRILLING SHALL BE PERFORMED IN AGREED LOCATIONS WITH THE OWNER OR BUILDING SUPERVISOR. ALL
OPENINGS SHALL BE RESTORED TO THEIR ORIGINAL CONDITION TO MATCH REMAINING SURROUNDING MATERIALS.
14. THE ELECTRICAL CONTRACTOR SHALL ARRANGE FOR THE COORDINATION OF ALL TRADES AND THE PROCUREMENT OF ALL INSPECTION CERTIFICATES AND FEES FOR THE COMPLETE
ELECTRICAL INSTALLATION. INSPECTIONS ARE REQUIRED ON ALL WORK AND NO WORK SHALL BE CLOSED UNTIL INSPECTED AND APPROVED.
15. NO CONDUIT SHALL BE SMALLER THAN ¾" ELECTRICAL TRADE SIZE. HOME RUN CIRCUITS MORE THAN 100' FROM THE PANEL BOARD SHALL BE MADE WITH THE NEXT LARGER SIZE
AS REQUIRED TO LIMIT VOLTAGE DROP TO 2% MAXIMUM. VOLTAGE DROP CALCULATIONS MUST BE PERFORMED BY THE ELECTRICAL CONTRACTOR AND SUBMITTED TO PROFESSIONAL
ENGINEER IF REQUESTED.
16. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A TYPED DIRECTORY OF EQUIPMENT THAT EACH CIRCUIT CONTROLS.
17. THE ELECTRICAL CONTRACTOR SHALL CONFIRM EXACT LOCATIONS OF ALL NEW EQUIPMENT SELECTED WITH THE OWNER OR BUILDING SUPERVISOR. REQUIRED NEC CLEARANCES
SHALL BE MET. BEFORE ORDERING ANY MATERIAL OR DOING ANY WORK, THE ELECTRICAL CONTRACTOR SHALL CHECK AND VERIFY ALL MEASUREMENTS.
18. CONTRACT DRAWINGS SHALL BE KEPT ON THE JOB SITE FROM THE BEGINNING OF THE WORK UNTIL PROJECT COMPLETION.
19. THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE MANUFACTURER'S OPERATION MANUALS WITH DETAILED OPERATING INSTRUCTIONS FOR EACH PIECE OF EQUIPMENT FURNISHED
ON THE JOB. THE ELECTRICAL CONTRACTOR SHALL PROVIDE MAINTENANCE INSTRUCTIONS FOR EACH PIECE OF EQUIPMENT PROVIDED ON THE JOB.
20. THE ELECTRICAL CONTRACTOR SHALL REMOVE ALL RUBBISH ACCUMULATED AND CAUSED BY SUBCONTRACTORS AND EMPLOYEES OF THE ELECTRICAL CONTRACTOR.
21. ELECTRICAL SHUTDOWNS REQUIRED FOR DISCONNECTING EXISTING ELECTRICAL ITEMS AND THE CONNECTION OF NEW ELECTRICAL ITEMS MUST BE COORDINATED WITH THE
OWNER FOR SCHEDULING PURPOSES. A METHOD OF PROCEDURE SHALL BE SUBMITTED TO PROFESSIONAL ENGINEER PRIOR TO SCHEDULING ANY SHUTDOWNS.
22. ALL CONDUCTORS SHALL BE COPPER THHN/THWN CONDUCTORS IN RACEWAY UNLESS OTHERWISE NOTED.
23. NON-METALLIC CONDUIT SHALL BE USED ON UNDERGROUND FEEDS ONLY.
24. THE ELECTRICAL CONTRACTOR SHALL FOLLOW PROPER GROUNDING TECHNIQUES PER ARTICLE 250 OF THE LATEST VERSION OF THE NATIONAL ELECTRIC CODE.
25. ALL EQUIPMENT SHALL BE RATED FOR PROPER ENVIRONMENTAL CONDITIONS. ALL OUTDOOR EQUIPMENT SHALL BE RATED NEMA3R FOR WEATHERPROOF LOCATIONS.
26. ON COMPLETION OF THE WORK, THE ENTIRE WIRING SYSTEM SHALL BE ENTIRELY FREE FROM GROUNDS, SHORT CIRCUITS, OPENS, OVERLOADS AND IMPROPER VOLTAGES. THE
ELECTRICAL CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND TESTING EQUIPMENT NECESSARY TO CONDUCT THE REQUIRED TESTS AND SUBMIT A WRITTEN RECORD OF
THE TESTS PERFORMED TO THE OWNER/BUILDING SUPERVISOR.
27. ALL EQUIPMENT AND SYSTEMS SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP FOR ONE (1) YEAR FROM DATE OF ACCEPTANCE. UPON WRITTEN
NOTICE, AND AT NO EXPENSE TO THE OWNER, THE ELECTRICAL CONTRACTOR SHALL PROMPTLY REPAIR ALL DEFECTIVE MATERIALS.
28. ALL PANELS, CONTACTORS, CIRCUIT BREAKERS, SAFETY SWITCHES AND SIMILAR ITEMS SHALL BE IDENTIFIED BY NAME, FUNCTION, AND/OR CONTROL. THE ELECTRICAL
CONTRACTOR SHALL PROVIDE NEATLY TYPED SCHEDULES OUTLINING CIRCUIT CONTROL FOR ALL PANELBOARDS.
29. THE ELECTRICAL CONTRACTOR SHALL PROVIDE IDENTIFICATION ON THE INSIDE OF BOXES WITH BLANK COVERS WHERE APPLICABLE.
30. IN GENERAL, THE ELECTRICAL CONTRACTOR SHALL ARRANGE WORK SO THAT NO ACCESS PANELS WILL BE REQUIRED. JUNCTION BOXES AND SIMILAR EQUIPMENT THAT REQUIRE
ACCESS SHALL BE LOCATED ABOVE REMOVABLE TILE CEILING OR IN UNFINISHED SPACES.
31. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ADEQUATE PROTECTION AGAINST DAMAGE TO ALL MATERIAL AND EQUIPMENT DURING SHIPPING AND STORAGE AT THE SITE. ALL
STORED EQUIPMENT SHALL BE COVERED TO AVOID DUST AND MOISTURE. AFTER EQUIPMENT IS INSTALLED, THE ELECTRICAL CONTRACTOR SHALL COVER ALL OPENINGS TO
PREVENT ENTRANCE OF WATER AND OTHER MATERIALS. ALL CONDUIT OPENINGS SHALL BE CLOSED WITH TEMPORARY METAL OR PLASTIC CAPS, INCLUDING THOSE TERMINATED
IN ELECTRICAL EQUIPMENT.
32. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE OWNER SO AS NOT TO INTERFERE WITH THE NORMAL FUNCTION OF THE BUILDING.
33. ALL ELECTRICAL PENETRATIONS THROUGH FIRE RATED WALL OR PARTITIONS SHALL BE FIRESTOPPED USING APPROVED METHODS TO MAINTAIN THE FIRE RATING PER THE LATEST
VERSION OF THE NATIONAL ELECTRIC CODE.
34. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND UL APPROVED.
35. THE ELECTRICAL CONTRACTOR SHALL SUBMIT A LIST OF EQUIPMENT AND MATERIALS TO BE USED, LISTING EACH ITEM SEPARATELY, AND INDICATING THE NAME OF THE
MANUFACTURER, SOURCE OF MATERIAL, OR SUBCONTRACTOR.
36. THE ELECTRICAL CONTRACTOR IS REQUIRED TO SUBMIT EQUIPMENT CUT-SHEETS AND SHOP DRAWINGS AND OBTAIN APPROVAL BEFORE PURCHASE AND/OR INSTALLATION OF
MATERIALS. APPROVAL WILL BE GIVEN ONLY TO INDICATE GENERAL COMPLIANCE WITH CONTRACT REQUIREMENTS. THE ELECTRICAL CONTRACTOR SHALL CHECK ALL DRAWINGS
AND SPECIFICATIONS FOR COMPLIANCE BEFORE SUBMISSION.
37. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL LUG SIZES OF EQUIPMENT WITH WIRE SIZES USED AND OR SPECIFIED.
38. FASTENING SHALL BE PERFORMED BY THE ELECTRICAL CONTRACTOR AS FOLLOWS:
A. IN HOLLOW MASONRY OR DRYWALL CONSTRUCTION SHALL BE PERFORMED WITH TOGGLE BOLTS
B. IN STRUCTURAL IRON MACHINE BOLTS SHALL BE UTILIZED
C. IN WOOD OR OTHER FIBROUS MATERIALS, LAG SCREW OR BOLTS SHALL BE UTILIZED
D. IN SOLID MASONRY, METALLIC EXPANSION SHIELDS AND MACHINE BOLTS SHALL BE UTILIZED
E. IN POURED CONCRETE, CONCRETE BOX INSERTS WITH ADDITIONAL REINFORCING STEEL INSTALLED WHERE DIRECTED SHALL BE USED.
F. GROUPS OF EQUIPMENT AND DEVICES SHALL BE SUPPORTED ON RACKS AND FRAMES CONSTRUCTED OF POWER-STRUT OR SIMILAR STRUCTURAL MEMBERS.
39. ALL CONDUITS SHALL BE RIGIDLY AND FIRMLY INSTALLED BY MALLEABLE OR WROUGHT STEEL HANGERS OF STANDARD DESIGN, PIPE CLAMPS, OR FABRICATED STEEL SUPPORTS
OF APPROVED DESIGN.
40. USE ONLY U.L. APPROVED RACEWAYS, WITH U.L. LABEL AND MANUFACTURERS NAME CLEARLY IDENTIFIED. THE MINIMUM SIZE CONDUIT SHALL BE 3/4".
41. RIGID STEEL CONDUIT (HEAVYWALL) SHALL BE GALVANIZED. CONDUIT FITTINGS SHALL BE CAST, MALLEABLE IRON, SMOOTH FINISH, FULL THREADED HUBS (IMC ACCEPTABLE).
42. ELECTRICAL METALLIC TUBING (EMT) (THINWALL) SHALL BE GALVANIZED. EMT FITTINGS SHALL BE SET SCREW TYPE.
43. WIREWAYS AND TROUGHS SHALL BE GALVANIZED STEEL, PROPERLY SIZED, WITH SCREWED COVERS. THE ELECTRICAL CONTRACTOR SHALL PROVIDE INTERIOR PARTITIONS
WHERE REQUIRED OR INDICATED.
44. FLEXIBLE CONDUIT SHALL BE STEEL, GALVANIZED AND U.L. APPROVED FOR GROUNDING. THE ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE GROUND WIRE.
45. LIQUID-TIGHT CONDUIT SHALL BE PVC JACKETED FLEXIBLE STEEL TYPE.
46. UNDERGROUND RACEWAYS SHALL BE PLASTIC (PVC) MINIMUM TYPE I, SUITABLE FOR ENCASEMENT IN CONCRETE. PROVIDE CONDUIT TO DUCT FITTINGS WHERE CHANGE OR
RACEWAY OCCURS.
47. THROUGH-WALL OUTLET BOXES SHALL NOT BE PERMITTED.
48. SLIP JOINT FITTINGS SHALL BE USED FOR CONDUITS PASSING THROUGH STRUCTURAL EXPANSION JOINTS. FITTINGS SHALL BE U.L. APPROVED FOR GROUNDING.
49. JUNCTION AND PULL BOXES, WHERE REQUIRED, SHALL BE CODE GAUGE GALVANIZED SHEET STEEL, WITH SCREWED COVERS, SIZED AS REQUIRED BY CODE. RECESSED
BOXES IN FINISHED AREAS WILL NOT BE ACCEPTED UNLESS SPECIFICALLY NOTED ON DRAWINGS.
50. RACEWAY INSTALLATIONS SHALL BE MECHANICALLY SECURED FOR A CONTINUOUS EFFECTIVE GROUND.
51. RIGID STEEL CONDUIT SHALL BE USED WHERE EXPOSED TO MOISTURE, BELOW GRADE OR IN FLOOR FILLS, FOR EXPOSED RUNS OUTDOORS AND IN OTHER WET LOCATIONS, INCLUDING WEATHER PROTECTED AREAS.
52. THINWALL TUBING (EMT) MAY BE USED FOR EXPOSED AND CONCEALED WIRING IN DRY LOCATIONS, NOT SPECIFICALLY MENTIONED ABOVE.
53. WIRING IN CONCRETE SLABS (ON GRADE), WHERE EXPOSED TO MOISTURE OR BELOW GRADE SHALL BE INSTALLED IN GALVANIZED STEEL CONDUIT. PVC RACEWAYS MAY BE
INSTALLED UNDER SLAB ON GRADE. THE ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE GROUND CABLE IN ALL PVC RACEWAYS.
54. LIQUID-TIGHT FLEXIBLE CONDUIT SHALL BE USED FOR FINAL CONNECTIONS TO EQUIPMENT, MOTORS, AND SIMILAR EQUIPMENT IN WET/DAMP AREAS.
55. THE ELECTRICAL CONTRACTOR SHALL INSTALL EXPOSED CONDUIT IN A NEAT SYMMETRICAL MANNER. CONDUITS SHALL FOLLOW BUILDING LINES, SECURELY SUPPORTED
FROM THE BUILDING STRUCTURE ON 10 FOOT INTERVALS BY CONDUIT STRAPS OR PIPE HANGERS ON SUPPORTING ASSEMBLIES AND SUPPORTED WITHIN 3 FEET OF OUTLET BOX
OR FITTING.
56. THE ELECTRICAL CONTRACTOR SHALL RUN EXPOSED CONDUIT IN UNFINISHED SPACES AFTER DUCTWORK AND PIPING HAVE BEEN INSTALLED, AND PROVIDE SUSPENSION
MATERIALS AS REQUIRED. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED OFFSETS, BENDS, BOXES AND FITTINGS AS REQUIRED.
57. THE ELECTRICAL CONTRACTOR SHALL NOT PIERCE STRUCTURAL MEMBERS WITHOUT PERMISSION.
58. WHERE CONDUIT PASSES THROUGH EXTERIOR WALLS, FLOOR OR ROOF, THE ELECTRICAL CONTRACTORS SHALL INSTALL APPROPRIATE FITTINGS AND MATERIALS TO MAKE
OPENINGS WATERTIGHT.
59. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A NYLON LINE PULL LINE IN ALL EMPTY CONDUITS.
60. THE ELECTRICAL CONTRACTOR SHALL MAKE PANELBOARD CONNECTIONS SO THAT CIRCUIT PROTECTORS ARE IN LOGICAL OPERATING SEQUENCE, AND SO THAT LOADS ARE
BALANCED ACROSS ALL PHASES.
61. WHERE CONDUIT ENTERS BUILDING FROM BELOW GRADE, THE ELECTRICAL CONTRACTOR SHALL SEAL END OF RACEWAY WITH APPROVED WATERPROOFING COMPOUND AFTER
WIRES HAVE BEEN INSTALLED.
62. THE ELECTRICAL CONTRACTOR SHALL SUPPORT CONDUCTORS IN VERTICAL RACEWAYS IN ACCORDANCE WITH THE LATEST VERSION OF THE NATIONAL ELECTRIC CODE.
63. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL WIRING, CONNECTIONS AND DEVICES, ETC. NECESSARY TO COMPLY WITH THE GROUNDING REQUIREMENTS OF THE LATEST
VERSION OF THE NATIONAL ELECTRIC CODE AND AS SHOWN ON THE DRAWINGS. EXCEPT WHERE SPECIFICALLY INDICATED OTHERWISE, ALL EXPOSED NON-CURRENT CARRYING
METALLIC PARTS OF ELECTRICAL EQUIPMENT, RACEWAY SYSTEMS, GROUNDING CONDUCTORS OF NON-METALLIC COVERED CABLE AND NEUTRAL CONDUCTORS OF THE WIRING
SYSTEM, SHALL BE GROUNDED.
64. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL SERVICE EQUIPMENT HAS BEEN APPROVED BY THE LOCAL UTILITY COMPANY BEFORE PURCHASE OF SUCH EQUIPMENT.
THIS INCLUDES VERIFYING THAT THE AIC RATINGS OF ALL DISTRIBUTION EQUIPMENT ARE ACCEPTABLE. THE ELECTRICAL CONTRACTOR SHALL SUBMIT AIC CALCULATIONS IF
REQUESTED BY PROFESSIONAL ENGINEER.
GENERAL ELECTRICAL NOTES
KEELING
BUILDING
ADDITION
EXISTING
KEELING
BUILDING
EXISTING
BUTLER
BUILDING
NEW TOWER
SCIENCE BUILDING
NEW GARAGE
BUILDING
EXISTING 300KVA
PAD MOUNTED
UTILITY
TRANSFORMER
EXISTING 50KVA MAT MOUNTED
UTILITY TRANSFORMER TO BE REMOVED
(REFER TO "PROJECT SCOPE NOTE J"
FOR MORE DETAILS)
EXISTING
TANK
RELOCATED
CHIN BUILDING
EXISTING
DOBSON DOME
EXISTING NDACC BUILDING
NEW UTILITY APPROVED GROUND MOUNTED JUNCTION BOX
(REFER TO "PROJECT SCOPE NOTE J" FOR MORE DETAILS)
EC-01 (REFER TO "PROJECT SCOPE NOTE J" FOR MORE DETAILS)
NEW 400A 120/208V 1Ø
SWITCH BOARD
"SWB-TS" LOCATION
EC-03
EC-04
EXISTING
300KVA
TRANSFORMER
120/208V 3Ø
EXISTING 120/208V
3Ø METER PANEL
(SOUTH EXTERIOR
WALL OF BUTLER
BUILDING)
70A3P
M
400A3P
M
EXISTING
PANEL "MLSO"
100A3P 100A3P
EXISTING DISTRIBUTION PANEL 400A MLO 120/208V 3Ø
100A3P 100A3P 100A3P 50A3P 100A3P 50A3P 50A2P 60A3P 60A3P 100A3P
EXISTING 70A
120/208V 3Ø
PUMP
ROOM
PANEL
EXISTING 100A
120/208V 3Ø
KEELING
BUILDING
PANEL "K"
EXISTING 70A
120/208V 3Ø
MLO WEST
PANEL
(CAMERA BUILDING)
EXISTING 100A
120/208V 3Ø
ACE
BUILDING
PANEL
EXISTING 100A
120/208V 3Ø
BUTLER
BUILDING
PANEL
EXISTING 50A
120/208V 3Ø
DOBSON
DOME
PANEL
EXISTING 100A
120/208V 3Ø
LIDAR
BUILDING
PANEL
EXISTING 100A
120/208V 3Ø
SOLAR
VARIABILITY
BUILDING PANEL
EXISTING 50A
120/208V 1Ø
SOLAR
DOME
PANEL
NEW 60A
120/208V 3Ø
TOWER SCIENCE
BUILDING
PANEL "TB"
NEW 60A
120/208V 3Ø
GARAGE
BUILDING
PANEL "G"
NEW 100A
120/208V 3Ø
KEELING
BUILDING
ADDITION
PANEL "KA"
50A2P 100A2P
EXISTING SPECIAL PROJECTS DISTRIBUTION PANEL 400A MLO 120/240 1Ø
100A2P 100A2P 60A2P
EXISTING
SCHNELL
BUILDING
EXISTING
UCHIDA
BUILDING
EXISTING
MLO EAST
PANEL
(MICROWAVE)
EXISTING
GONG
EXISTING
NIST LUNAR
BUILDING
NEW GROUND MOUNT
UTILITY APPROVED
JUNCTION BOX
TO BE LOCATED
AT EXISTING 50KVA
MAT MOUNTED
TRANSFORMER
100A2P
M
400A2P
M
EXISTING
HAWAII TELCOM
PANEL
EC-01
(REFER TO
"PROJECT SCOPE
NOTE J" FOR
MORE DETAILS)
EC-02 EC-02 EC-05EXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTING
EXISTING EXISTING EXISTING EXISTING EXISTING
EXISTING EXISTING
EXISTING 120/240V 1Ø
METER PANEL
SERVING
HAWAII TELECOM &
NE CLUSTER
(SPECIAL PROJECTS)
EXISTING
EXISTING
EXISTING
EC-03
NEW 400A
120/208V 3Ø
NEMA3R
SWITCHBOARD
EXTERIOR OF
TOWER SCIENCE
BUILDING
PANEL "SWB-TS"
5 5 5 5 5 5 5 5 5 5 5 5
NEW 60A
120/208V 1Ø
CHIN
BUILDING
PANEL "CB"
EC-04
ELECTRICAL CONDUIT SCHEDULE
PVC = UNDERGROUND/OUTDOOR, EMT= INTERIOR ABOVE GRADE
CONDUIT I.D. CONDUIT SIZE/TYPE CONDUIT WIRE SIZE & GROUND
EC-01 4" PVC
(4) 500kcmil THHN/THWN CU, (1) 1/0 THHN/THWN CU GROUND
EC-02 2" PVC
(4) #6 THHN/THWN CU, (1) #8 THHN/THWN CU GROUND
EC-03 4" PVC
(4) 500kcmil THHN/THWN CU, (1) 1/0 THHN/THWN CU GROUND
EC-04 2" PVC
(3) #6 THHN/THWN CU, (1) #8 THHN/THWN CU GROUND
EC-05 2" PVC
(4) #3 THHN/THWN CU, (1) #8 THHN/THWN CU GROUND
EC-06 3/4" EMT
(3) #8 THHN/THWN CU, (1) #10 THHN/THWN CU GROUND
REFER TO "PROJECT
SCOPE NOTE J" FOR
MORE DETAILS
E.C. SHALL INSTALL NEW CONDUIT/WIRE (EC-01) FROM EXISTING 300KVA UTILITY TRANSFORMER TO NEW UTILITY
APPROVED JUNCTION BOX LOCATED AT EXISTING UTILITY POLE/SERVICE. ALL UNDERGROUND CONDUITS SHALL HAVE
MINIMUM 24" COVER. REFER TO "PROJECT SCOPE NOTE J" ON THIS SHEET FOR FURTHER DETAILS.
E.C. SHALL INSTALL NEW UTILITY APPROVED JUNCTION BOX AND INTERCEPT EXISTING SECONDARY CONDUIT/WIRE AT
EXISTING UTILITY TRANSFORMER. E.C. SHALL JUNCTION NEW EC-01 CONDUIT/WIRE FROM EXISTING 300KVA
TRANSFORMER WITH EXISTING SECONDAY CONDUIT/WIRE IN NEW JUNCTION BOX. ALL UNDERGROUND CONDUITS SHALL
HAVE MINIMUM 24" COVER. REFER TO "PROJECT SCOPE NOTE J" ON THIS SHEET FOR FURTHER DETAILS.
THIS WORK WILL RESULT IN NEW VOLTAGE CHARACTERISTICS 120/208V 1Ø AT EXISTING 120/240V 1Ø ELECTRICAL
DISTRIBUTION AND EQUIPMENT. E.C. IS RESPONSIBLE FOR PROPER OPERATION OF ALL EXISTING EQUIPMENT NOW
POWERED BY 208V RATHER THAN 240V. E.C. SHALL ALSO UPDATE ALL IDENTIFICATION AND LABELING AT ALL EQUIPMENT
FROM 240V TO 208V.
E.C. SHALL PROVIDE NEW CONDUIT/WIRE FROM EXISTING METER ENCLOSURE TO NEW 400A NEMA3R SWITCHBOARD
"SWB-TS" EQUIPMENT. UNDERGROUND CONDUITS SHALL HAVE MINUMUM 24" COVER. E.C. SHALL NOT MAKE ANY
CONNECTIONS UNTIL EXISTING BUTLER BUILDING ELECTRICAL DISTRIBUTION HAS BEEN DISCONNECTED.
E.C. SHALL EXTEND/JUNCTION/REWORK ALL EXISTING LOAD WIRING FROM EXISTING 400A 120/208V 3Ø PANELBOARD IN
EXISTING BUTLER BUILDING TO NEW 400A NEMA3R SWITCHBOARD "SWB-TS" EQUIPMENT AT EXTERIOR OF NEW TOWER
SCIENCE BUILDING PER PLANS. ALL CONDUITS FROM BUTLER BUILDING TO NEW "SWB-TS" SHALL BE UNDERGROUND WITH
MINIMUM 24" COVER. E.C. SHALL NOT MAKE ANY CONNECTIONS UNTIL EXISTING BUTLER BUILDING ELECTRICAL
DISTRIBUTION HAS BEEN DISCONNECTED.
A. THE PURPOSE OF THESE DRAWINGS IS TO PROVIDE SCOPE DESCRIPTION FOR BUDGET PRICING. THESE DRAWINGS ARE NOT INTENDED FOR CONSTRUCTION.
B. THE MAUNA LOA SITE IS UNIQUE IN TERRAIN, ALTITUDE AND UTILITY INFRASTRUCTURE. THE CONTRACTORS BIDDING ON THIS SCOPE SHALL BE AWARE OF THE COMPLEXITIES FOR
CONSTRUCTION THIS SITE.
C. A "SITE-WIDE" GROUNDING SYSTEM NEEDS TO BE INSTALLED FOR PROPER ELECTRICAL SYSTEM PERFORMANCE AND PERSONNEL SAFETY. THESE DRAWINGS DO NOT SHOW DETAILS
RELATIVE TO THE "SITE-WIDE" GROUNDING SYSTEM. THE INTENTION IS FOR EACH BUILDING'S ELECTRICAL SERVICE GROUNDING TO BE CONNECTED VIA NEW 3/0 COPPER WIRE INSTALLED IN
1 1/4" PVC CONDUIT TO THE NEW TOWER FOUNDATION. THE TOWER FOUNDATION SHALL BE UTILIZED FOR THE "SITE-WIDE" GROUNDING SYSTEM COMMON GROUND POINT.
D. E.C. SHALL UTILIZE WELDED TABS, COMMERCIAL GROUND BUSSING, CHEMICAL ENHANCEMENT IN ESTABLISHING THE SITE-WIDE GROUNDING SYSTEM.
E. AFTER CONSTRUCTION IS COMPLETE, THE E.C. SHALL TEST AND DOCUMENT THE GROUNDING SYSTEM PERFORMANCE
F. ALL GROUNDING CONNECTIONS SHALL BE PERFORMED WITH EXOTHERMICALLY WELDED CABLE CONNECTIONS THAT ARE LABELED AND LISTED
G. ALL TIE-INS INTO EXISTING GROUND SYSTEM AT EACH BUILDING’S ELECTRICAL SERVICE LOCATION SHALL BE 4/0 STRANDED COPPER
H. INSTALL SITE-WIDE UFER GROUNDING SCHEME AT ALL NEW CONCRETE INSTALLATIONS ON THE PROJECT INCLUDING BUILDING FOUNDATIONS, WALKWAYS, ETC. AND CONNECT 3/0 COPPER
WIRE TO "SITE-WIDE" GROUNDING SCHEME. CONCRETE REBAR CONNECTIONS SHALL BE EXPOSED AND ELECTRICALLY CONNECTED TO EACH BUILDING ELECTRICAL SERVICES.
I. THE E.C. SHALL INSPECT, TEST AND REPLACE AS NEEDED THE FOLLOWING ELECTRICAL SYSTEM COMPONENTS:
I.1. BONDING CONNECTIONS NEED TO BE INSPECTED AND RE-INSTALLED AS REQUIRED
I.2. SURGE PROTECTORS SHALL BE CATALOGED BY LOCATION AND NAMEPLATE DATA. EXISTING DEVICES THAT ARE NO LONGER PROVIDING PROTECTION SHALL BE REPLACED WITH
EQUIVALENT DEVICE/PROTECTION
I.3. ALL CONVENIENCE OUTLETS (PARTICULARLY OUTDOOR) SHOULD BE REPLACE WITH GFCI / AFCI PER CODE.
I.4. ALL EXISTING CONDUITS AND WIRING LAYING ON THE SURFACE OF THE GROUND ARE NOT CODE COMPLIANT OR SAFE. THESE CONDUITS SHALL BE RE-INSTALLED BELOW GRADE TO
MEET NATIONAL ELECTRIC CODE.
J. THE REMOVAL OF THE EXISTING 50KVA UTILITY TRANSFORMER AND REPLACEMENT WITH JUNCTION BOX SHALL BE QUOTED AS AN ADD/ALT. THE E.C. SHALL CONTACT THE LOCAL UTILITY
AND CONFIRM PROPER SCOPE FOR REMOVAL OF 50KVA TRANSFORMER, FENCING & PRIMARY CABLING AND THE PURCHASE/INSTALLATION OF THE JUNCTION BOX. THE BASE PROPOSAL
SHALL INCLUDE THE FOLLOWING:
J.1. E.C. SHALL CONTACT LOCAL UTILITY FOR REQUIREMENTS/SCOPE THAT IS NOT SPECIFICALLY LISTED HERE.
J.2. E.C SHALL REMOVE/REPLACE AND EXTEND PERIMETER FENCING AREA AROUND EXISTING UTILITY MAT TRANSFORMER / UTILITY POLE TO MEET UTILITY AND OSHA CLEARANCE
REQUIREMENTS. NEW FENCING SHALL BE PROPERLY GROUNDED PER UTILITY DIRECTION AND NATIONAL ELECTRICAL CODE REQUIREMENTS.
J.3. E.C. SHALL PROPERLY PROTECT ALL PRIMARY AND SECONDARY WIRING BY INSTALLING IN PVC CONDUITS WITH PROPER CLEARANCES AND COVER.
K. ALL EQUIPMENT AND PARTS SUPPLIED SHALL BE LISTED AND LABELED AND ACCEPTABLE TO THE AHJ & LOCAL UTILITY AS WELL AS SUBMITTED ON AND APPROVED BY THE CONTRACTING
AGENCY.
L. ALL WORK SHALL COMPLY WITH ALL RELEVANT LOCAL, STATE, FEDERAL AND UTILITY REQUIREMENTS.
M. AS BUILT DOCUMENTATION SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR AT THE COMPLETION OF THE PROJECT.
PROJECT SPECIFIC NOTES
UTILITY/SOURCE
NEUTRAL FROM UTILITY / SOURCE
G
EACH BUILDING'S
MAIN SERVICE
N
(1) 3/0 COPPER TO METAL
WATER PIPE PER NEC
250.52(A)(1)
(IF AVAILABLE)
GROUNDING IN ACCORDANCE WITH ARTICLE 250 OF THE
CURRENT NATIONAL ELECTRIC CODE.
IF AVAILABLE ON THE PREMISES ITEMS 250.52(A)(1) THROUGH
(A)(6) SHALL BE BONDED TOGETHER TO FORM THE
GROUNDING ELECTRODE SYSTEM
250.52(A)(1) METAL UNDERGROUND WATER PIPE
250.52(A)(2) METAL FRAME OF THE BUILDING OR STRUCTURE
250.52(A)(3) CONCRETE-ENCASED ELECTRODE
250.52(A)(4) GROUND RING
250.52(A)(5) ROD AND PIPE ELECTRODES
250.52(A)(6) PLATE ELECTRODES
250.52(A)(7) OTHER LOCAL METAL UNDERGROUND SYSTEMS
GROUND PER NEC 250.24 (C) (1)
OR MANUFACTURER'S
EQUIVALENT BONDING MEANS
(1) 3/0 COPPER
A "SITE-WIDE"
GROUNDING SYSTEM
COMMON GROUNDING
POINT AT NEW TOWER
FOUNDATION
GROUND FROM UTILITY / SOURCE
ELECTRICAL
KEY PLAN &
GENERAL NOTES
E0.0
E0.0
PARTIAL SITE ELECTRICAL PLAN
SCALE: NONE
DRAWING:
PROJECT NO. 201203
DRAWN BY: SV/JV
CHECKED BY: JPS
SCALE: AS NOTED
ISSUE FOR:
O Contracting & Engineering
PHONE EMAIL FAX
(856) 424 7900 EMAIL@SCHOOLEYELECTRIC.COM (856) 424 0272
1812 Garden Avenue PO BOX 3125 Cherry Hill, NJ 08034
SCH CITYOLE CELE R
D A
N
IE
L E
JO
ST
R
A N
J A
I0
R E G
IS
T
E R
E D
A R
C H
IT
E C
T
H ad d o n fi e ld
-B e rl in R d
Su it e
V o o rh e e s, N J
-8
-2 w w w .d j-a rc h .c om
P R
O P O
SE
D
A L T
E R
A T
IO
N
S F
O R
M
A U
N A
L O
A O
B
SE
R V
A T
O R
Y N
O A
A O
B
SR
V A
T O
R Y
-2
M
A U
N A
L O
A A
C C
E
SS
R O
A D
W A
IM
E A
H
I
BID 07/30/21
P
R
E
L
I
M
I
N
A
R
Y
N
R
C
O
N
S
T
R
U
C
T
I
O
N
E0.0
ELECTRICAL ONE-LINE
SCALE: NONE
E0.0
ELECTRICAL KEY-NOTES
SCALE: NONE
E0.0
ELECTRICAL SERVICE GROUNDING DETAIL
SCALE: NONE
4A
E0.0
ELECTRICAL CONDUIT SCHEDULE
SCALE: NONE
TOILET ROOM
KITCHENETTE
OFFICE
IT CLOSET
STORAGE
TOILET ROOM
SCIENCE
OUTREACH AREA
CORRIDOR
K-40,42
40A/208V/1Ø
(EV CHARGING STATION)
KA-12
36" AFF
36" AFF
36"
AFF
36"
AFF
KA-12 KA-14 KA-14 KA-14
KA-14
36"
AFF
KA-10
KA-10
KA-10
KA-10
KA-18
R
K A
K A
A
F F
G
F I
K A
K A
KA-2
KA-2
48"AFF
GFI
KA-4
48"AFF
GFI
KA-4
KA-2
NEW PANEL "KA"
60A 3Ø 120/208V
KA-16
F
KA-16
F
KA-1,3
40A/208V/1Ø
(EV CHARGING STATION)
EXISTING PANEL "K"
100A 120/208V 3Ø
G F
I
EC-06
EC-06
KA-4
KA-8
20A/120V/1Ø
KA-6
20A/120V/1Ø
KA-4
KA-11,13
20A/208V/1Ø
KA-15,17
50A/208V/1Ø
KA-19
20A/120V/1Ø
GFI/WP
KA-24
GFI/WP
KA-24
K A
A
F F
G
F I
A
F F
G
F I
OPTIONAL CABINET
OVEN, 20A/120V
K-8
K-10
K-18
MERCURY
PLATFORM
KA-24
GFI/WP
KA-4
KA-5,7,9
15A/208V/3Ø
RELOCATE HAWAII
TELECOM EQUIPMENT
RELOCATED HAWAII
TELECOM EQUIPMENT
E.C. SHALL PROVIDE NEW 40A2P CIRCUIT FROM EXITING PANEL "K" TO POWER NEW EV CAR CHARGER.
EXISTING ELECTRICAL PANEL "K" SHALL REMAIN. EXISTING COUNTER/SINK SHALL BE RELOCATED BY OTHERS.
TOILET ROOM
KITCHENETTE
OFFICE
MECHANICAL
STORAGE
TOILET ROOM
CORRIDOR
SCIENCE
OUTREACH AREA
KA-23
KA-27
SOS
S O
S
S3OS
S3OS
KA-25
KA-25
SOS
SOS
OS
OS
KA-25
KA-25
KA-25
SYMBOL
LIGHT FIXTURE SCHEDULE
DESCRIPTIONNO.
EXISTING TO REMAIN
LINEAR SUSPENDED LED EQUAL TO NEO-RAY
DEFINE GEN-2-4" SUSPENDED PENDENT DIRECT, 3000K
LINEAR SURFACE MTD. LED EQUAL TO NEO-RAY
DEFINE GEN-2-4" SUSPENDED SURFACE DIRECT, 3000K
LINEAR LED EQUAL TO METALUX LW LED WRAP
4 FEET SURFACE MOUNTED, 4000K
LINEAR LED EQUAL TO METALUX LW LED WRAP
4 FEET CHAIN HUNG, 4000K
LINEAR LED EQUAL TO FAIL-SAFE VRVT3
4 FEET, SURFACE MOUNTED, 3500K
A
B
C
D
E
F
EXIT LIGHT CO. ELSM-G-RM
ARCHITECTURAL RECESSED-MOUNTED LED EDGE-LIT
EXIT SIGN W/ BATTERY BACKUP
DUAL LITE ZR SERIES REMOTE HEAD
10-65W MATCHING EMERGENCY PACK
DUAL LITE LZ SERIES
LZ SERIES INDOOR EMERGENCY LIGHTING UNIT
DUAL LITE ZR SERIES WEATHERPROOF REMOTE HEADS
10-65W MATCHING EMERGENCY PACK
MECHANICAL
106A
SOS
KA-9
MECHANICAL
106A
KA-2
SYMBOL
SYMBOL LEGEND
DUPLEX RECEPTACLE R = REFRIGERATOR
GFI = GROUND FAULT INTERRUPTER F = IN-FLOOR
DESCRIPTION
DATA PORT LOCATION
ELECTRICAL PANEL
CEILING OCCUPANCY SENSOR
E.C. SHALL PROVIDE OVERRIDE SWITCH
3-WAY OCCUPANCY SENSOR - WALL MOUNT
SINGLE POLE OCCUPANCY SENSOR - WALL MOUNT
SOS
S3OS
OS
EXHAUST FAN - SEE MECHANICAL EQUIPMENT
DETAILS
ELECTRIC HEATER - SEE MECHANICAL EQUIPMENT
DETAILS
QUAD RECEPTACLE
SUPPLY FAN - SEE MECHANICAL EQUIPMENT
DETAILS
ELECTRIC DUCT HEATER - SEE MECHANICAL
EQUIPMENT DETAILS
CB-6
CB-4
CB-8
CB-2
NEW PANEL "CB"
60A 1Ø 120/208V
DD
D
SOS
CB-1
CB-5,7
20A/208V/1Ø
CB-3
NEW 100A 120/208V 3Ø PANEL "KA"
PANEL DESCRIPTION: 120/208V 3Ø, 100A MAIN BREAKER ONLY
CB SIZE CIRCUIT DESCRIPTION CIRCUIT DESCRIPTION SIZE CB
40A
NEW
EV CHARGING STATION
CORRIDOR/I.T. RECEPTACLES 20A 2
3 TOILET GFI RECEPTS/EF-1'S/SF-1 20A 4
15A
EDH-1
ELECTRIC DUCT HEATER
EH-1 TOILET RM 20A 6
7 EH-1 TOILET RM 20A 8
9 OFFICE 108 LEFT RECEPTACLES 20A 10
20A
EH-4
ELECTRIC HEATER
OFFICE 108 REAR RECEPTACLES 20A 12
13 OFFICE 108 REAR/RIGHT RECEPTS 20A 14
20A
EH-3
ELECTRIC HEATER
OFFICE 108 CENTER FLOOR RECS 20A 16
17 KITCHENETTE REFRIGERATOR 20A 18
19 20A KITCENETTE EF-2 EXHAUST FAN KITCHENETTE COUNTER RECEPS 20A 20
21 20A SPARE WATER COOLER RECEPTACLE 20A 22
23 20A OFFICE LIGHTING EXTERIOR RECEPTACLES 20A 24
25 20A TOILET/MECH./CORR. LIGHTING OPTIONAL CABINET OVEN 20A 26
27 20A OFFICE CEILING FAN
SUB-PANEL "CB"
CHIN BUILDING
60A
29 20A SPARE 30
31 20A SPARE SPARE 20A 32
33 20A SPARE SPARE 20A 34
35 20A SPARE SPARE 20A 36
37 20A SPARE SPARE 20A 38
39 20A SPARE SPARE 20A 40
41 20A SPARE SPARE 20A 42
NEW 60A 120/208V 1Ø PANEL "CB"
PANEL DESCRIPTION: 120/208V 1Ø, 60A MAIN CIRCUIT BREAKER
CB SIZE CIRCUIT DESCRIPTION CIRCUIT DESCRIPTION SIZE CB
1 20A BUILDING LIGHTING QUAD RECEPTACLE 20A 2
3 20A EF-1 EXHAUST FAN QUAD RECEPTACLE 20A 4
20A
EH-4
ELECTRIC HEATER
QUAD RECEPTACLE 20A 6
7 QUAD RECEPTACLE 20A 8
9 20A SPARE SPARE 20A 10
11 20A SPARE SPARE 20A 12
13 20A SPARE SPARE 20A 14
15 20A SPARE SPARE 20A 16
17 20A SPARE SPARE 20A 18
E1.1
ELECTRICAL POWER PLAN - KEELING BUILDING
SCALE: 1/4"=1'-0"
NEW ELECTRICAL
POWER & LIGHTING
PLANS
E1.1
E1.1
ELECTRICAL SYMBOL LEGEND
SCALE: NONE
DRAWING:
PROJECT NO. 201203
DRAWN BY: SV/JV
CHECKED BY: JPS
SCALE: AS NOTED
ISSUE FOR:
O Contracting & Engineering
PHONE EMAIL FAX
(856) 424 7900 EMAIL@SCHOOLEYELECTRIC.COM (856) 424 0272
1812 Garden Avenue PO BOX 3125 Cherry Hill, NJ 08034
SCH CITYOLE CELE R
D A
N
IE
L E
JO
ST
R
A N
J A
I0
R E G
IS
T
E R
E D
A R
C H
IT
E C
T
H ad d o n fi e ld
-B e rl in R d
Su it e
V o o rh e e s, N J
-8
-2 w w w .d j-a rc h .c om
P R
O P O
SE
D
A L T
E R
A T
IO
N
S F
O R
M
A U
N A
L O
A O
B
SE
R V
A T
O R
Y N
O A
A O
B
SR
V A
T O
R Y
-2
M
A U
N A
L O
A A
C C
E
SS
R O
A D
W A
IM
E A
H
I
BID 07/30/21
P
R
E
L
I
M
I
N
A
R
Y
N
R
C
O
N
S
T
R
U
C
T
I
O
N
E1.1
ELECTRICAL KEY-NOTES
SCALE: NONE
E1.1
ELECTRICAL LIGHTING PLAN - KEELING BUILDING
SCALE: 1/4"=1'-0" 7
E1.1
LIGHTING FIXTURE SCHEDULE
SCALE: NONE
EXISTING LIGHTING, CIRCUITRY &
CONTROL SHALL REMAIN
E1.1
ELECTRICAL POWER & LIGHTING PLANS MEZZANINE - KEELING BUILDING
SCALE: 1/4"=1'-0"
EXISTING LIGHTING, CIRCUITRY &
CONTROL SHALL REMAIN
E1.1
ELECTRICAL PLAN - CHIN BUILDING
SCALE: 1/4"=1'-0"
E1.1
ELECTRICAL PANEL SCHEDULES
SCALE: NONE
AutoCAD SHX Text
REF.
AutoCAD SHX Text
30" HIGH TOP WORK SURFACE
AutoCAD SHX Text
STAIRS UP
AutoCAD SHX Text
EH
AutoCAD SHX Text
AutoCAD SHX Text
EH
AutoCAD SHX Text
AutoCAD SHX Text
EH
AutoCAD SHX Text
AutoCAD SHX Text
EF
AutoCAD SHX Text
AutoCAD SHX Text
EF
AutoCAD SHX Text
AutoCAD SHX Text
EH
AutoCAD SHX Text
AutoCAD SHX Text
EF
AutoCAD SHX Text
AutoCAD SHX Text
EDH
AutoCAD SHX Text
AutoCAD SHX Text
SP
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
GYP. BD. CEILING
AutoCAD SHX Text D
AutoCAD SHX Text
EF
AutoCAD SHX Text
AutoCAD SHX Text
EH
AutoCAD SHX Text
AutoCAD SHX Text
SF
AutoCAD SHX Text
AutoCAD SHX Text
EDH
AutoCAD SHX Text
AutoCAD SHX Text
EH
AutoCAD SHX Text
AutoCAD SHX Text
EF
NOAA SCIENCE
NON-NOAA SCIENCE
FLEX SCIENCE
TB-4
TB-4
TB-4
TB-4
TB-4
TB-4
TB-2
TB-2
TB-2
TB-2
TB-2
TB-2
36" AFF
36" AFF
36" AFF
TB-6
TB-6
TB-6
TB-6
TB-6
36" AFF
36" AFF
36" AFF
TB-10
TB-10
TB-10
TB-10
TB-10
TB-10
36" AFF
36" AFF
36" AFF36" AFF
TB-8
TB-8
TB-8
TB-8
TB-8
TB-8
36" AFF
TB-12
TB-12
TB-12
TB-12
TB-12
TB-12
36" AFF
TB-4
36" AFF
NEW PANEL "TB"
60A 3Ø 120/208V
TB-6
36" AFF 36" AFF 36" AFF
TB-2
TB-2
TB-6
TB-6
TB-10
TB-10
TB-12TB-8TB-2
36" AFF
36" AFF
36" AFF
36" AFF
36" AFF
36" AFF
NEW 400A 120/208V 3Ø
SWITCHBOARD "SWB-TS"
TB-1,3
30A/208V/1Ø
TB-5,7
30A/208V/1Ø
TB-9,11
30A/208V/1Ø
TB-13
20A/120V/1Ø
TB-15,17,19
TB-13
NOAA SCIENCE
NON-NOAA SCIENCE
FLEX SCIENCE
OS OS OS
TB-14 TB-14 TB-14
SYMBOL
LIGHT FIXTURE SCHEDULE
DESCRIPTIONNO.
EXISTING TO REMAIN
LINEAR SUSPENDED LED EQUAL TO NEO-RAY
DEFINE GEN-2-4" SUSPENDED PENDENT DIRECT, 3000K
LINEAR SURFACE MTD. LED EQUAL TO NEO-RAY
DEFINE GEN-2-4" SUSPENDED SURFACE DIRECT, 3000K
LINEAR LED EQUAL TO METALUX LW LED WRAP
4 FEET SURFACE MOUNTED, 4000K
LINEAR LED EQUAL TO METALUX LW LED WRAP
4 FEET CHAIN HUNG, 4000K
LINEAR LED EQUAL TO FAIL-SAFE VRVT3
4 FEET, SURFACE MOUNTED, 3500K
A
B
C
D
E
F
EXIT LIGHT CO. ELSM-G-RM
ARCHITECTURAL RECESSED-MOUNTED LED EDGE-LIT
EXIT SIGN W/ BATTERY BACKUP
DUAL LITE ZR SERIES REMOTE HEAD
10-65W MATCHING EMERGENCY PACK
DUAL LITE LZ SERIES
LZ SERIES INDOOR EMERGENCY LIGHTING UNIT
DUAL LITE ZR SERIES WEATHERPROOF REMOTE HEADS
10-65W MATCHING EMERGENCY PACK
SYMBOL
SYMBOL LEGEND
DUPLEX RECEPTACLE R = REFRIGERATOR
GFI = GROUND FAULT INTERRUPTER F = IN-FLOOR
DESCRIPTION
DATA PORT LOCATION
ELECTRICAL PANEL
CEILING OCCUPANCY SENSOR
E.C. SHALL PROVIDE OVERRIDE SWITCH
3-WAY OCCUPANCY SENSOR - WALL MOUNT
SINGLE POLE OCCUPANCY SENSOR - WALL MOUNT
SOS
S3OS
OS
EXHAUST FAN - SEE MECHANICAL EQUIPMENT
DETAILS
ELECTRIC HEATER - SEE MECHANICAL EQUIPMENT
DETAILS
QUAD RECEPTACLE
SUPPLY FAN - SEE MECHANICAL EQUIPMENT
DETAILS
ELECTRIC DUCT HEATER - SEE MECHANICAL
EQUIPMENT DETAILS
NEW 60A 120/208V 3Ø PANEL "TB"
PANEL DESCRIPTION: 120/208V 3Ø, 60A MAIN CIRCUIT BREAKER
CB SIZE CIRCUIT DESCRIPTION CIRCUIT DESCRIPTION SIZE CB
30A
EH-2
NOAA SCIENCE 102
NOAA SCIENCE 102 RECEPTS 20A 2
3 NOAA SCIENCE 102 RECEPTS 20A 4
30A
EH-2
FLEX SCIENCE 101
FLEX SCIENCE 101 RECEPTS 20A 6
7 FLEX SCIENCE 101 RECEPTS 20A 8
30A
EH-2
NON NOAA SCIENCE 100
NON NOAA SCIENCE 100 RECEPTS 20A 10
11 NON NOAA SCIENCE 100 RECEPTS 20A 12
13 20A EF-3 EXHAUST & SF-2 SUPPLY FANS SCIENCE RMS 100-102 LIGHTING 20A 14
30A
EDH-2
ELECTRIC DUCT HEATER
SPARE 20A 16
17 SPARE 20A 18
19 SPARE 20A 20
21 20A SPARE SPARE 20A 22
23 20A SPARE SPARE 20A 24
25 20A SPARE SPARE 20A 26
27 20A SPARE SPARE 20A 28
29 20A SPARE SPARE 20A 30
31 20A SPARE SPARE 20A 32
33 20A SPARE SPARE 20A 34
35 20A SPARE SPARE 20A 36
37 20A SPARE SPARE 20A 38
39 20A SPARE SPARE 20A 40
41 20A SPARE SPARE 20A 42
NEW 400A 120/208V 3Ø SWITCHBOARD "SWB-TS"
PANEL DESCRIPTION: 120/208V 3Ø, 400A MAIN CIRCUIT BREAKER
CB SIZE CIRCUIT DESCRIPTION CIRCUIT DESCRIPTION SIZE CB
100A
FUTURE PUMP
ROOM FEED
FUTURE SOLAR VARIABILITY
BUILDING PANEL FEED
50A
3 4
5 6
100A
FUTURE KEELING
PANEL "K" FEED
FUTURE SOLAR DOME
PANEL FEED
50A
9 10
11 12
100A
FUTURE ACE BUILDING
WEST PANEL FEED
FUTURE TOWER SCIENCE
BUILDING PANEL FEED
60A
15 16
17 18
100A
FUTURE ACE BUILDING
PANEL FEED
FUTURE KNEELING ADDITION
BUILDING PANEL FEED
60A
21 22
23 24
100A
FUTURE BUTLER
BUILDING PANEL FEED
FUTURE SOLAR VARIABILITY
BUILDING PANEL FEED
60A
27 28
29 30
100A
FUTURE LIDAR
BUILDING PANEL FEED
SPACE TBD
33 34
35 36
50A
FUTURE DOBSON DOME
PANEL FEED
SPACE TBD
39 40
41 42
TBD SPACE SPACE TBD
45 46
47 48
TBD SPACE SPACE TBD
51 52
53 54
E2.1
ELECTRICAL POWER PLAN - TOWER BUILDING
SCALE: 1/4"=1'-0"
NEW ELECTRICAL
POWER & LIGHTING
PLANS
E2.1
E2.1
ELECTRICAL SYMBOL LEGEND
SCALE: NONE
DRAWING:
PROJECT NO. 201203
DRAWN BY: SV/JV
CHECKED BY: JPS
SCALE: AS NOTED
ISSUE FOR:
O Contracting & Engineering
PHONE EMAIL FAX
(856) 424 7900 EMAIL@SCHOOLEYELECTRIC.COM (856) 424 0272
1812 Garden Avenue PO BOX 3125 Cherry Hill, NJ 08034
SCH CITYOLE CELE R
D A
N
IE
L E
JO
ST
R
A N
J A
I0
R E G
IS
T
E R
E D
A R
C H
IT
E C
T
H ad d o n fi e ld
-B e rl in R d
Su it e
V o o rh e e s, N J
-8
-2 w w w .d j-a rc h .c om
P R
O P O
SE
D
A L T
E R
A T
IO
N
S F
O R
M
A U
N A
L O
A O
B
SE
R V
A T
O R
Y N
O A
A O
B
SR
V A
T O
R Y
-2
M
A U
N A
L O
A A
C C
E
SS
R O
A D
W A
IM
E A
H
I
BID 07/30/21
P
R
E
L
I
M
I
N
A
R
Y
N
R
C
O
N
S
T
R
U
C
T
I
O
N
E2.1
ELECTRICAL LIGHTING PLAN - TOWER BUILDING
SCALE: 1/4"=1'-0"
E2.1
LIGHTING FIXTURE SCHEDULE
SCALE: NONE
E2.1
ELECTRICAL PANEL SCHEDULES
SCALE: NONE
AutoCAD SHX Text
EH
AutoCAD SHX Text
AutoCAD SHX Text
EH
AutoCAD SHX Text
AutoCAD SHX Text
EH
AutoCAD SHX Text
AutoCAD SHX Text
EF
AutoCAD SHX Text
AutoCAD SHX Text
EDH
AutoCAD SHX Text
AutoCAD SHX Text
SF
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text
EF
AutoCAD SHX Text
AutoCAD SHX Text
EH
AutoCAD SHX Text
AutoCAD SHX Text
SF
AutoCAD SHX Text
AutoCAD SHX Text
EDH
GARAGE AREA
CAR PORT
WORKSHOP
G-3
G-3
G-3
G-3
G-9
G-7
G-5
NEW PANEL "G"
60A 3Ø 120/208V
G-1
G-1
G-1
G-13
GFI/WP
G-13
GFI/WP
48" AFF
48" AFF
48" AFF
48" AFF
G-9
G-2,4
40A/208V/1Ø
(EV CHARGING STATION)
EC-06
G-6,8
30A/208V/1Ø
G-10,12
30A/208V/1Ø
G-14
20A/120V/1Ø
G-16
20A/120V/1Ø
G-13
GFI/WP
G-15,17,19
G-14
GARAGE AREA
CAR PORT
WORKSHOP
OS
OS
OS
G-11
G-11
G-11
SYMBOL
SYMBOL LEGEND
DUPLEX RECEPTACLE R = REFRIGERATOR
GFI = GROUND FAULT INTERRUPTER F = IN-FLOOR
DESCRIPTION
DATA PORT LOCATION
ELECTRICAL PANEL
CEILING OCCUPANCY SENSOR
E.C. SHALL PROVIDE OVERRIDE SWITCH
3-WAY OCCUPANCY SENSOR - WALL MOUNT
SINGLE POLE OCCUPANCY SENSOR - WALL MOUNT
SOS
S3OS
OS
EXHAUST FAN - SEE MECHANICAL EQUIPMENT
DETAILS
ELECTRIC HEATER - SEE MECHANICAL EQUIPMENT
DETAILS
QUAD RECEPTACLE
SUPPLY FAN - SEE MECHANICAL EQUIPMENT
DETAILS
ELECTRIC DUCT HEATER - SEE MECHANICAL
EQUIPMENT DETAILS
SYMBOL
LIGHT FIXTURE SCHEDULE
DESCRIPTIONNO.
EXISTING TO REMAIN
LINEAR SUSPENDED LED EQUAL TO NEO-RAY
DEFINE GEN-2-4" SUSPENDED PENDENT DIRECT, 3000K
LINEAR SURFACE MTD. LED EQUAL TO NEO-RAY
DEFINE GEN-2-4" SUSPENDED SURFACE DIRECT, 3000K
LINEAR LED EQUAL TO METALUX LW LED WRAP
4 FEET SURFACE MOUNTED, 4000K
LINEAR LED EQUAL TO METALUX LW LED WRAP
4 FEET CHAIN HUNG, 4000K
LINEAR LED EQUAL TO FAIL-SAFE VRVT3
4 FEET, SURFACE MOUNTED, 3500K
A
B
C
D
E
F
EXIT LIGHT CO. ELSM-G-RM
ARCHITECTURAL RECESSED-MOUNTED LED EDGE-LIT
EXIT SIGN W/ BATTERY BACKUP
DUAL LITE ZR SERIES REMOTE HEAD
10-65W MATCHING EMERGENCY PACK
DUAL LITE LZ SERIES
LZ SERIES INDOOR EMERGENCY LIGHTING UNIT
DUAL LITE ZR SERIES WEATHERPROOF REMOTE HEADS
10-65W MATCHING EMERGENCY PACK
NEW 60A 120/208V 3Ø PANEL "G"
PANEL DESCRIPTION: 120/208V 3Ø, 60A MAIN CIRCUIT BREAKER
CB SIZE CIRCUIT DESCRIPTION CIRCUIT DESCRIPTION SIZE CB
1 20A GARAGE AREA 101 RECEPTS
NEW
EV CHARGING STATION
40A
3 20A WORKSHOP 102 COUNTER RECS 4
5 20A DRILL PRESS RECEPTACLE
EH-2
GARAGE AREA 101
30A
7 20A BAND SAW RECPTACLE 8
9 20A WORKSHOP 102 RECEPTACLES
EH-2
WORKSHOP 102
30A
11 20A LIGHTING 12
13 20A CAR PORT/OUTDOOR GFI RECS
EF-4 GARAGE, SF-3 WORKSHOP
20A 14
15A
EDH-3
ELECTRIC DUCT HEATER
GARAGE OVERHEAD DOOR 20A 16
17 SPARE 20A 18
19 SPARE 20A 20
21 20A SPARE SPARE 20A 22
23 20A SPARE SPARE 20A 24
25 20A SPARE SPARE 20A 26
27 20A SPARE SPARE 20A 28
29 20A SPARE SPARE 20A 30
31 20A SPARE SPARE 20A 32
33 20A SPARE SPARE 20A 34
35 20A SPARE SPARE 20A 36
37 20A SPARE SPARE 20A 38
39 20A SPARE SPARE 20A 40
41 20A SPARE SPARE 20A 42
E3.1
ELECTRICAL POWER PLAN - GARAGE BUILDING
SCALE: 1/4"=1'-0"
NEW ELECTRICAL
POWER & LIGHTING
PLANS
E3.1
DRAWING:
PROJECT NO. 201203
DRAWN BY: SV/JV
CHECKED BY: JPS
SCALE: AS NOTED
ISSUE FOR:
O Contracting & Engineering
PHONE EMAIL FAX
(856) 424 7900 EMAIL@SCHOOLEYELECTRIC.COM (856) 424 0272
1812 Garden Avenue PO BOX 3125 Cherry Hill, NJ 08034
SCH CITYOLE CELE R
D A
N
IE
L E
JO
ST
R
A N
J A
I0
R E G
IS
T
E R
E D
A R
C H
IT
E C
T
H ad d o n fi e ld
-B e rl in R d
Su it e
V o o rh e e s, N J
-8
-2 w w w .d j-a rc h .c om
P R
O P O
SE
D
A L T
E R
A T
IO
N
S F
O R
M
A U
N A
L O
A O
B
SE
R V
A T
O R
Y N
O…