ATTACHMENT 2 ELECTRICAL DRAWINGS.pdf

PDF 3 MB Posted

Attached to
Power Infrastructure and Solar System Upgrades, Mauna Loa Observatory Federal contract opportunity
Solicitation number
1305M324R0042
Issued by
Department of Commerce National Oceanic and Atmospheric Administration

About this file

This document is a solicitation (Solicitation Number: 1305M324R0042) for the Power Infrastructure and Solar System Upgrade Project at the Mauna Loa Atmospheric Baseline Observatory (MLO) site in Hawaii. The solicitation is issued by the Department of Commerce National Oceanic and Atmospheric Administration (NOAA) and requires offerors to provide all supervision, tools, materials, labor, and services necessary for the completion of the work.

The key details include a deadline of 10:00 AM Mountain Time on April 29, 2024 for submitting questions, and the solicitation is requesting proposals for upgrades to the power infrastructure and solar systems at the MLO site. The scope of work includes, but is not limited to, the installation of new electrical switchgear, panels, wiring, and a new ground-mounted utility approved junction box. Offerors are required to review the entirety of the solicitation, which includes drawings and specifications, and to visit the site to verify all dimensions and site conditions prior to submitting a bid.

View the file

Other files for this federal contract opportunity

Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

APPLICABLE CODES

HAWAII STATE BUILDING CODE AND

AMMEDMENTS TO THE IBC 2018

ELECTRIC CODE NEC 2017

PLUMBING CODE UPC 2018

MECHANICAL CODE IMC 2018

BARRIER FREE CODE ANSI 117.1-2009

FIRE PROTECTION CODE IFC 2018

HVAC&R STANDARD ASHRAE 90.1-2013

ENERGY CODE IECC 2018

FUEL GAS CODE IFGC 2018

CHAPTER 11 OF IBC/2018

C O

P Y

R I G

H T

D

J

A

R C

H I T

E C

T U

R E

L

L C

U

N A

U T

H O

R I Z

E

R

P

R O

D U

C T

I O

N

O

R

O

T H

S

O

F

T

H I

A

W I N

G

R

I C

T L

Y

P

R O

H I B

I T

E D

H ad d o n fi e ld

-B e rl in R d

Su it e

V o o rh e e s, N J

-8

-2 w w w .d j-a rc h .c om

DRAWING TITLE:

PROJECT NO. 201203

DRAWN BY: KMK

CHECKED BY: DEJ

SCALE: AS NOTED

ISSUE FOR:

BID 07/30/21

P R

O P O

SE

D

A L T

E R

A T

IO

N

S F

O R

M A

U N

A L

O A

O B

SE

R

V A

T O

R Y

C A

M P U

S

-2

M

A U

N A

L O

A A

C C

E

SS

R O

A D

W A

IM

E A

H

I

P

R

E

L

I

M

I

N

A

R

Y

N

R

C

O

N

S

T

R

U

C

T

I

O

N

A0.0

COVER SHEET

KEY PLAN

LOCATION MAP

ARCHITECT:

DJ ARCHITECTURE, LLC

1010 HADDONFIELD-BERLIN ROAD, SUITE 405

VOORHEES, NJ 08043

CONTACT: DAN JOST, RA

PH: 856-809-2791

EMAIL: DJOST@DJ-ARCH.COM

PROJECT TEAM

T.O. CONC.

EL. 0'-0"

SYMBOLS LEGEND

COLUMN LINE

A

AX.X

AX.X

FINISH

SF-##

P?

RM NAME

##/A#.#

T.O. CONC

EL. 0'-0"

ELEVATION/DWG. OR

BLDG. SECTION/DWG.

OR WALL

SECTION/DWG.

DETAIL/DWG.

FINISH TYPE

STOREFRONT TYPE

PARTITION TYPE

ROOM NAME/NUMBER

DOOR NUMBER

WINDOW TYPE

INTERIOR ELEVATION

SPOT ELEVATION

DATUM ELEVATION

REVISION - ADDENDUM

REVISION -

CONSTRUCTION

BULLETIN

C.J. CONTROL JOINT

CLG. CEILING

CLKG. CAULKING

CLR. CLEAR

C.O. CASED OPENING

COL. COLUMN

CONC. CONCRETE

CONN. CONNECTION

CONST. CONSTRUCTION

CONT. CONTINUOUS

CORR. CORRIDOR

CTSK. COUNTERSUNK

CNTR. COUNTER

C.T. CERAMIC TILE

CTR. CENTER

DBL. DOUBLE

DEPT. DEPARTMENT

D.F. DRINKING FOUNTAIN

DET. DETAIL

DIA. DIAMETER

DIM. DIMENSION

DISP. DISPENSER

DN. DOWN

HDWE HARDWARE

H.M. HOLLOW METAL

HORIZ. HORIZONTAL

HR. HOUR

I.D. INSIDE DIMENSION

INSUL. INSULATION

INT. INTERIOR

O.A. OVERALL

OBS. OBSCURE

O.C. ON CENTER

O.D. OUTSIDE DIMENSION

OPNG. OPENING

OPP.

OPPOSITE

PRCST. PRE-CAST

PL. PLATE

P.LAM. PLASTIC LAMINATE

PLAS. PLASTER

PLYWD. PLYWOOD

HDWD HARDWOOD

D.O. DOOR OPENING

DR. DOOR

DWR. DRAWER

DS. DOWNSPOUT

DWG. DRAWING

E. EAST

E.J. EXPANSION JOINT

EL. ELEVATION

ELEC. ELECTRICAL

EMER. EMERGENCY

ENCL. ENCLOSURE

EQ. EQUAL

EQPT. EQUIPMENT

E.W.C. ELECTRIC WATER COOLER

EXIST. EXISTING

EXPO. EXPOSED

EXP. EXPANSION

EXT. EXTERIOR

F.D. FLOOR DRAIN

FDN. FOUNDATION

F.E. FIRE EXTINGUISHER

F.E.C. FIRE EXTINGUISHER CABINET

FIN. FINISH

FIXT. FIXTURE

FL. FLOOR

FLASH. FLASHING

FLUOR. FLUORESCENT

F.O.C. FACE OF CONCRETE

F.O.F. FACE OF FINISH

F.O.S. FACE OF STUDS

FT. FOOT OR FEET

FTG. FOOTING

FURR. FURRING

GALV. GALVANIZED

GL. GLASS

GR. GRADE

GYP. GYPSUM

GYP.BD. GYPSUM WALLBOARD

H.B. HOSE BIBB

H.C. HOLLOW CORE

PR. PAIR

PSF POUNDS PER SQUARE FOOT

Q.T. QUARRY TILE

R. RISER

RAD. RADIUS

R.D. ROOF DRAIN

REF. REFERENCE

REFR. REFRIGERATOR

REINF REINFORCED

REQD REQUIRED

RESIL. RESILIENT

RM. ROOM

R.O. ROUGH OPENING

RWC RAINWATER CONDUCTOR

S. SOUTH

S.C. SOLID CORE

SCHED. SCHEDULED

SHT. SHEET

S.J. SAWCUT JOINT

SIM. SIMILAR

SPEC. SPECIFICATION

SPECD. SPECIFIED (SECTION)

S.ST. STAINLESS STEEL

STD. STANDARD

STL. STEEL

STOR. STORAGE

STRUC. STRUCTURAL

SUSP. SUSPENDED

T.C. TOP OF CURB

TEL. TELEPHONE

T&G TONGUE AND GROOVE

THK. THICK

T.O. TOP OF

T.P. TOP OF PAVEMENT

TV TELEVISION

T.W. TOP OF WALL

TYP. TYPICAL

UNF. UNFINISHED

U.O.N. UNLESS OTHERWISE NOTED

UR. URINAL

VCT VINYL COMPOSITION TILE

VERT. VERTICAL

VEST. VESTIBULE

W. WEST

W/ WITH

WD WOOD

WITHOUTW/O

WATERPROOFWP

WAINSCOTWSCT.

WT. WEIGHT

EA. EACH

CMU CONCRETE MASONRY UNIT

D DEPTH

H.D. HEAVY DUTY

HEIGHTHGT.

PSI POUNDS PER SQUARE INCH

RET. RETAINING

TS TUBE STEEL

FIRE-RETARDANT TREATEDFR.TR.

INSULATING GLASSI.G.

PR.TR. PRESSURE TREATED

T.G. TEMPERED GLASS

U.G. UNDERGROUND

HSS HOLLOW STEEL SECTION

P.O.C. POINT OF CONNECTION

EXT. INSUL. & FINISH SYSTEME.I.F.S.

O.H.

OVERHANG

R.T.U. HVAC UNIT

P.S.F.F. PREFAB. STRUC. STL. FABR.

FABR. FABRICATOR/ FABRICATED

FURRING CHANNELF.C.

F.O.M. FACE OF MASONRY

WIDTHWDT.

VENT THRU ROOF

VERIFY IN FIELDV.I.F.

V.T.R.

THR. THRESHOLD

SF STOREFRONT

SECTIONSECT.

INFORMATIONINFO.

PLUMBINGPLMB.

QUARTERQTR.

RND. ROUND

FACE OF (XX)F.O.(XX)

GA. GAUGE

PARTITIONPRTN.

TEMPERED INSULATING GLASST.I.G.

VINYL WALL COVERINGVWC

PT. POINT

PTD. PAINTED

S.F. SQUARE FEET

CER. CERAMIC

C.I. CAST IRON

C.G. CORNER GUARD

NO. NUMBER

NOM. NOMINAL

N.T.S. NOT TO SCALE

COLD FORMEDC.F.

ARCH. DRAWING ABBREVIATIONS

& AND

L ANGLE

@ AT

L

CENTERLINE

# POUND or NUMBER

ACCES. ACCESSIBLE

AL. ALUMINUM

APPROX. APPROXIMATE

ARCH. ARCHITECTURAL

ASPH. ASPHALT

BD. BOARD

BITUM. BITUMINOUS

BLDG. BUILDING

BLK. BLOCK

BM. BEAM

B.O. BOTTOM OF

CAB. CABINET

CEM. CEMENT

JAN. JANITOR

JT. JOINT

KIT. KITCHEN

LAM. LAMINATE

LAV. LAVATORY

LLH LONG LEG HORIZONTAL

MAX. MAXIMUM

MECH. MECHANICAL

MEMB. MEMBRANE

MET. METAL

MFR. MANUFACTURER

MIN. MIMIMUM

MISC. MISCELLANEOUS

M.O. MASONRY OPENING

M.R. MOISTURE RESISTANT

MTD. MOUNTED

N. NORTH

N.I.C. NOT IN CONTRACT

C

B.C. BACK OF CURB

L. LENGTH

MED. MEDIUM

MASONRYMAS.

BRG.

BTWN.

BEARING

BETWEEN

ADJ. ADJUSTABLE

A.F.F. ABOVE FINISH FLOOR

ACOUSTICAL CEILING TILEACT.

BUILT-UP ROOFINGBUR MOUNTINGMTG.

LLV LONG LEG VERTICAL

LT. LIGHT

MAUNA LOA

OBSERVATORY

AREA OF

WORK

PROPOSED ALTERATIONS FOR:

MAUNA LOA OBSERVATORY

NOAA OBSERVATORY

44-2441 MAUNA LOA ACCESS ROAD

WAIMEA, HI 96743

BUILDING CODE DATA

ELECTRICAL ENGINEER:

SCHOOLEY ELECTRIC

1812 GARDEN AVENUE

CHERRY HILL, NJ 08003

CONTACT: JOE SCHOOLEY, PE

PH: 856-424-7900

CELL: 856-261-4859

EMAIL: EMAIL@SCHOOLEYELECTRIC.COM

OWNER:

U.S. DEPARTMENT OF COMMERCE/NOAA

WESTERN ACQUISITION DIVISION

325 BROADWAY, SOU6

BOULDER, CO 80305

CONTACT: BRIAN VASEL

PHONE: 303-497-6655

EMAIL: BRIAN.VASEL@NOAA.GOV

GENERAL NOTES

FE

FIRE EXTINGUISHER,

SURFACE MOUNTED,

LOCATIONS TO BE

DETERMINED IN FIELD W/

OWNER IN ACCORDANCE

W/ NFPA REGULATIONS

AutoCAD SHX Text SCOPE OF WORK: THESE DRAWINGS INDICATE GENERAL SCOPE OF WORK AND : THESE DRAWINGS INDICATE GENERAL SCOPE OF WORK AND DESIGN INTENT FOR THE PROJECT. THIS DRAWING SET IS INTENDED FOR BIDDING ONLY AND NOT FOR CONSTRUCTION. THE CONTRACTOR SHALL VISIT THE SITE, REVIEW CONSTRUCTION CONDITIONS AND, PRIOR TO SUBMITTING A FINAL BID, SHALL VERIFY ALL DIMENSIONS SHOWN ON THE DRAWINGS, ALL SITE CONDITIONS, AND ALL REQUIREMENTS FOR THE PROJECT. THE INTENTION OF THESE DRAWINGS IS TO PROVIDE FOR WORK COMPLETE IN EVERY DETAIL EVEN THOUGH EVERY ITEM INVOLVED MAY NOT BE SHOWN OR MENTIONED IN PARTICULAR. VARIATIONS OR AMBIGUITIES BETWEEN THESE DRAWINGS AND ACTUAL SITE CONDITIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND OWNER IN WRITING AND SHALL BE RESOLVED AND DOCUMENTED BY THE CONTRACTOR IN WRITING. THE CONTRACTOR SHALL PROVIDE ALL SUPERVISION, TOOLS, MATERIAL, LABOR, SERVICES, TRANSPORTATION, ETC. NECESSARY FOR COMPLETION OF THE WORK INTENDED TO BE SHOWN AND/OR DESCRIBED.

AutoCAD SHX Text PERMITS: THE CONTRACTOR SHALL SECURE AND PAY FOR THE BUILDING PERMIT AND : THE CONTRACTOR SHALL SECURE AND PAY FOR THE BUILDING PERMIT AND FOR ALL OTHER PERMITS AND GOVERNMENTAL FEES, LICENSES AND INSPECTIONS NECESSARY FOR THE PROPER EXECUTION OF THE WORK.

AutoCAD SHX Text MATERIALS AND GUARANTEE: ALL MATERIALS AND EQUIPMENT FURNISHED FOR THE : ALL MATERIALS AND EQUIPMENT FURNISHED FOR THE PROJECT SHALL BE NEW, UNLESS OTHERWISE SPECIFIED, AND ALL WORK SHALL BE OF GOOD QUALITY AND FREE FROM FAULTS AND DEFECTS. ALL WORK SHALL BE GUARANTEED FOR ONE (1) FULL YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION. ALL MANUFACTURER'S WARRANTIES SHALL BE IN EXCESS OF THE CONTRACTOR'S GUARANTEE.

AutoCAD SHX Text MEANS AND METHODS: THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR : THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, AND PRODUCTION PROCEDURES REQUIRED FOR THE PROPER AND SAFE EXECUTION AND COMPLETION OF THE WORK AND FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY PRECAUTIONS, PROCEDURES AND PROBLEMS IN CONNECTION WITH THE WORK.

AutoCAD SHX Text CHANGES IN THE WORK: THE ARCHITECT IS NOT RESPONSIBLE FOR SITE INSPECTIONS, : THE ARCHITECT IS NOT RESPONSIBLE FOR SITE INSPECTIONS, GENERAL OBSERVATIONS AND/OR DEVIATIONS FROM THE CONSTRUCTION DOCUMENTS. NO DEVIATIONS FROM THE WORK SHOWN OR REASONABLY IMPLIED SHALL BE UNDERTAKEN WITHOUT CONSENT FROM THE ARCHITECT.

AutoCAD SHX Text 6.

AutoCAD SHX Text 5.

AutoCAD SHX Text 4.

AutoCAD SHX Text 3.

AutoCAD SHX Text American National Standards Institute (ANSI) American Society for Testing and Materials (ASTM) American Concrete Institute (ACI) American Society of Civil Engineers (ASCE) American Institute of Steel Construction (AISC) American Welding Society (AWS) Factory Mutual System (FM) Institute of Electrical & Electronics (IEEE) National Association of Architectural Metal Manufacturers (NAAMM) National Concrete Masonry Association (NCMA) National Fire Protection Association (NFPA) Steel Deck Institute (SDI) Steel Joist Institute (SJI) U.S. Department of Commerce - National Bureau of Standards (DOC) Underwriters Laboratories (UL) Local codes, state laws and all other governing authorities

AutoCAD SHX Text REFERENCE STANDARDS: ALL EQUIPMENT, TESTS, MATERIALS, AND DETAILS OF : ALL EQUIPMENT, TESTS, MATERIALS, AND DETAILS OF INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS AND LATEST REVISIONS OF THE FOLLOWING APPLICABLE STANDARDS:

AutoCAD SHX Text 2.

AutoCAD SHX Text 1.

AutoCAD SHX Text

CURRENT ISSUE DRAWINGS

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

DRAWING TITLE

AutoCAD SHX Text

CURRENT ISSUE

AutoCAD SHX Text

DATE ISSUED

AutoCAD SHX Text A0.0

AutoCAD SHX Text

COVER SHEET, CODE DATA

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A0.1

AutoCAD SHX Text

SITE PLAN

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A1.1

AutoCAD SHX Text

KEELING BUILDING ADDITION DEMOLITION PLAN

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A1.2

AutoCAD SHX Text

KEELING BUILDING ADDITION FLOOR PLAN

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A1.3

AutoCAD SHX Text

KEELING BUILDING ADDITION FLOOR FINISH AND POWER PLANS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A1.4

AutoCAD SHX Text

KEELING BUILDING ADDITION REFLECTED CEILING PLAN

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A1.5

AutoCAD SHX Text

KEELING BUILDING ADDITION ROOF PLAN, ROOF FRAMING PLAN

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A1.6

AutoCAD SHX Text

KEELING BUILDING ADDITION SCHEDULES AND DETAILS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A1.7

AutoCAD SHX Text

KEELING BUILDING ADDITION EXTERIOR ELEVATIONS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A1.8

AutoCAD SHX Text

KEELING BUILDING ADDITION SECTIONS AND DETAILS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A1.9

AutoCAD SHX Text

KEELING BUILDING MILLWORK DETAILS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A2.2

AutoCAD SHX Text

TOWER BUILDING FLOOR PLAN

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A2.4

AutoCAD SHX Text

TOWER BUILDING REFLECTED CEILING AND POWER PLANS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A2.5

AutoCAD SHX Text

TOWER BUILDING ROOF PLAN, ROOF FRAMING PLAN

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A2.6

AutoCAD SHX Text

TOWER BUILDING SCHEDULES AND DETAILS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A2.7

AutoCAD SHX Text

TOWER BUILDING EXTERIOR ELEVATIONS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A2.8

AutoCAD SHX Text

TOWER BUILDING SECTIONS AND DETAILS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A3.2

AutoCAD SHX Text

GARAGE/CARPORT FLOOR PLAN

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A3.4

AutoCAD SHX Text

GARAGE/CARPORT REFLECTED CEILING AND POWER PLANS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A3.5

AutoCAD SHX Text

GARAGE/CARPORT ROOF PLAN, ROOF FRAMING PLAN

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A3.6

AutoCAD SHX Text

GARAGE/CARPORT SCHEDULES AND DETAILS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A3.7

AutoCAD SHX Text

GARAGE/CARPORT EXTERIOR ELEVATIONS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text A3.8

AutoCAD SHX Text

GARAGE/CARPORT SECTIONS AND DETAILS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text M1.0

AutoCAD SHX Text

MECHANICAL FLOOR PLANS AND NOTES

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text M2.0

AutoCAD SHX Text

MECHANICAL SCHEDULE AND NOTES

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text E0.0

AutoCAD SHX Text

ELECTRICAL KEY PLAN AND GENERAL NOTES

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text E1.1

AutoCAD SHX Text

KEELING ELECTRICAL POWER AND LIGHTING PLANS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text E2.1

AutoCAD SHX Text

TOWER ELECTRICAL POWER AND LIGHTING PLANS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

AutoCAD SHX Text E3.1

AutoCAD SHX Text

GARAGE/CARPORT ELECTRICAL POWER AND LIGHTING PLANS

AutoCAD SHX Text

BID

AutoCAD SHX Text 07/30/21

A0.1

A0.1

A0.1

A0.1

C O

P Y

R I G

H

J

A

R C

H I T

E C

T U

R E

L

L C

N A

U T

H O

R I Z

P

R O

D U

C T

I O

N

O

R

O

T H

T

H

A

W I N

G

R

I C

T L

Y

P

R O

H I B

I T

E D

H ad d o n fi e ld

-B e rl in R d

Su it e

V o o rh e e s, N J

-8

-2 w w w .d j-a rc h .c om

DRAWING TITLE:

PROJECT NO. 201203

DRAWN BY: KMK

CHECKED BY: DEJ

SCALE: AS NOTED

ISSUE FOR:

BID 07/30/21

P R

O P O

SE

D

A L T

E R

A T

IO

N

S F

O R

M A

U N

A L

O A

O B

SE

R

V A

T O

R Y

C A

M P U

S -2

M

A U

N A

L O

A A

C C

E

SS

R O

A D

W A

IM

E A

H

I

P

R

E

L

I

M

I

N

A

R

Y

N

R

C

O

N

S

T

R

U

C

T

I

O

N

A0.1

SITE PLAN

1"=30'

SITE DEMO PLAN

1"=30'

PROPOSED SITE PLAN

1/4" = 1'-0"

CHIN BUILDING PAD EXPANSION

1/2" = 1'-0"

CHIN BUILDING PAD EXPANSION DETAIL

1/2" = 1'-0"

CHIN BUILDING EXISTING PAD DETAIL

AutoCAD SHX Text

ASIAA COMPLEX

AutoCAD SHX Text

GONG

AutoCAD SHX Text

NDACC BULDING

AutoCAD SHX Text

ASIAA COMPLEX

AutoCAD SHX Text

GONG

AutoCAD SHX Text

NDACC BULDING

AutoCAD SHX Text WALKWAY NOTE: HEAVY HEAVY DUTY GRIP STRUT WALKWAY PANELS, 10GA GALVANIZED STEEL, 36" WIDE, PART #H-85010-W BY METALS, INC.

AutoCAD SHX Text

CABLE TRAY NOTE: 12" WIDE BY 5 1/4" DEEP ALUMINUM CABLE LADDER TRAY

AutoCAD SHX Text NOTE: SITE PLANS ARE DIAGRAMMATIC IN NATURE AND ARE ONLY INTENDED TO SHOW APPROXIMATE LOCATIONS OF BUILDING AND NEW WORK

AutoCAD SHX Text

SIM.

AutoCAD SHX Text EXISTING BUILDING NOTES: - SEAL AND PAINT EXISTING SEAL AND PAINT EXISTING EXTERIOR TO MATCH KEELING BUILDING. - PROVIDE EXHAUST FAN ON SWITCH.PROVIDE EXHAUST FAN ON SWITCH.

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

GRADE

GRADE

1. ALL WORK PERFORMED SHALL COMPLY WITH THE PROVISIONS OF THE DRAWINGS AND SHALL SATISFY ALL APPLICABLE CODES, ORDINANCES, AND REGULATIONS OF ALL GOVERNING

BODIES INVOLVED INCLUDING THE LATEST VERSION OF THE NATIONAL ELECTRIC CODE.

2. ALL WORK DETAILED ON THESE ELECTRICAL DRAWINGS SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR UNLESS OTHERWISE INDICATED. THE ELECTRICAL

CONTRACTOR IS RESPONSIBLE FOR ALL WORK MATERIAL AND LABOR TO SATISFY A COMPLETE AND WORKING SYSTEM WHETHER IMPLIED OR SPECIFIED.

3. ALL DRAWINGS SHALL BE REVIEWED BY THE ELECTRICAL CONTRACTOR TO BECOME FAMILIAR WITH THE REQUIREMENTS OF THE PROJECT. THE ELECTRICAL CONTRACTOR IS REQUIRED

TO ALERT THE PROFESSIONAL ENGINEER OF ANY DISCREPANCIES ON THE DRAWINGS IMMEDIATELY. THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH

THE SCOPE OF WORK.

5. ALL WIRING AND CONDUIT SIZING SHALL BE IN COMPLIANCE WITH ARTICLE 310 AND APPENDIX C OF THE LATEST VERSION OF THE NATIONAL ELECTRIC CODE.

6. STANDARDS OF THE FOLLOWING ORGANIZATIONS ARE APPLICABLE: ILLUMINATING ENGINEERING SOCIETY (IES), AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), INSTITUTE OF

ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE), INSULATED CABLE ENGINEERS ASSOCIATION (ICEA), NATIONAL ELECTRICAL CODE (NEC), NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION (NEMA), NATIONAL ELECTRICAL SAFETY CODE (NESC), NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), UNDERWRITER'S LABORATORIES (UL), OCCUPATIONAL SAFETY

AND HEALTH ACT (OSHA)

7. ALL WORK SHALL COMPLY WITH ALL REGULATIONS AND BE SUBJECT TO INSPECTION AND APPROVAL OF AUTHORITIES HAVING JURISDICTION.

8. THE ELECTRICAL CONTRACTOR IS REQUIRED TO OBTAIN AND PAY FOR ALL NECESSARY ELECTRICAL PERMITS AND FEES.

9. THE ELECTRICAL CONTRACTOR IS REQUIRED TO CHECK ALL EQUIPMENT DIMENSIONS PRIOR TO PURCHASE OF ANY EQUIPMENT. IF THERE IS A DISCREPANCY BETWEEN THESE DRAWINGS

AND THE EQUIPMENT TO BE PURCHASED, THE ELECTRICAL CONTRACTOR SHALL NOTIFY THE PROFESSIONAL ENGINEER IMMEDIATELY AND NOT PURCHASE EQUIPMENT UNTIL RESOLVED.

10. ALL MATERIAL AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS' INSTRUCTIONS. THIS INCLUDES THE USE OF CALIBRATED TORQUE WRENCHES

AND SCREWDRIVERS TO TIGHTEN ALL TERMINALS, LUGS, AND BUS JOINTS.

11. ALL WORK SHALL COMPLY WITH STARTUP PROCEDURES AS DEFINED BY CONSTRUCTION MANAGER AND OWNER. ANY SHUTDOWNS TO ELECTRICAL SYSTEMS SHALL BE COORDINATED

WITH OWNER AND CONSTRUCTION MANAGER.

12. ALL ELECTRICAL WORK SHALL BE ARRANGED IN A NEAT, WELL-ORGANIZED MANNER. THE ELECTRICAL CONTRACTOR SHALL APPLY, INSTALL, CONNECT, ERECT, USE, CLEAN, ADJUST, AND

CONDITION ALL MATERIALS AND ALL EQUIPMENT AS RECOMMENDED BY THE MANUFACTURERS IN PUBLISHED LITERATURE.

13. ANY OPENINGS MADE THROUGH MASONRY AND CONCRETE BY CORE DRILLING SHALL BE PERFORMED IN AGREED LOCATIONS WITH THE OWNER OR BUILDING SUPERVISOR. ALL

OPENINGS SHALL BE RESTORED TO THEIR ORIGINAL CONDITION TO MATCH REMAINING SURROUNDING MATERIALS.

14. THE ELECTRICAL CONTRACTOR SHALL ARRANGE FOR THE COORDINATION OF ALL TRADES AND THE PROCUREMENT OF ALL INSPECTION CERTIFICATES AND FEES FOR THE COMPLETE

ELECTRICAL INSTALLATION. INSPECTIONS ARE REQUIRED ON ALL WORK AND NO WORK SHALL BE CLOSED UNTIL INSPECTED AND APPROVED.

15. NO CONDUIT SHALL BE SMALLER THAN ¾" ELECTRICAL TRADE SIZE. HOME RUN CIRCUITS MORE THAN 100' FROM THE PANEL BOARD SHALL BE MADE WITH THE NEXT LARGER SIZE

AS REQUIRED TO LIMIT VOLTAGE DROP TO 2% MAXIMUM. VOLTAGE DROP CALCULATIONS MUST BE PERFORMED BY THE ELECTRICAL CONTRACTOR AND SUBMITTED TO PROFESSIONAL

ENGINEER IF REQUESTED.

16. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A TYPED DIRECTORY OF EQUIPMENT THAT EACH CIRCUIT CONTROLS.

17. THE ELECTRICAL CONTRACTOR SHALL CONFIRM EXACT LOCATIONS OF ALL NEW EQUIPMENT SELECTED WITH THE OWNER OR BUILDING SUPERVISOR. REQUIRED NEC CLEARANCES

SHALL BE MET. BEFORE ORDERING ANY MATERIAL OR DOING ANY WORK, THE ELECTRICAL CONTRACTOR SHALL CHECK AND VERIFY ALL MEASUREMENTS.

18. CONTRACT DRAWINGS SHALL BE KEPT ON THE JOB SITE FROM THE BEGINNING OF THE WORK UNTIL PROJECT COMPLETION.

19. THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE MANUFACTURER'S OPERATION MANUALS WITH DETAILED OPERATING INSTRUCTIONS FOR EACH PIECE OF EQUIPMENT FURNISHED

ON THE JOB. THE ELECTRICAL CONTRACTOR SHALL PROVIDE MAINTENANCE INSTRUCTIONS FOR EACH PIECE OF EQUIPMENT PROVIDED ON THE JOB.

20. THE ELECTRICAL CONTRACTOR SHALL REMOVE ALL RUBBISH ACCUMULATED AND CAUSED BY SUBCONTRACTORS AND EMPLOYEES OF THE ELECTRICAL CONTRACTOR.

21. ELECTRICAL SHUTDOWNS REQUIRED FOR DISCONNECTING EXISTING ELECTRICAL ITEMS AND THE CONNECTION OF NEW ELECTRICAL ITEMS MUST BE COORDINATED WITH THE

OWNER FOR SCHEDULING PURPOSES. A METHOD OF PROCEDURE SHALL BE SUBMITTED TO PROFESSIONAL ENGINEER PRIOR TO SCHEDULING ANY SHUTDOWNS.

22. ALL CONDUCTORS SHALL BE COPPER THHN/THWN CONDUCTORS IN RACEWAY UNLESS OTHERWISE NOTED.

23. NON-METALLIC CONDUIT SHALL BE USED ON UNDERGROUND FEEDS ONLY.

24. THE ELECTRICAL CONTRACTOR SHALL FOLLOW PROPER GROUNDING TECHNIQUES PER ARTICLE 250 OF THE LATEST VERSION OF THE NATIONAL ELECTRIC CODE.

25. ALL EQUIPMENT SHALL BE RATED FOR PROPER ENVIRONMENTAL CONDITIONS. ALL OUTDOOR EQUIPMENT SHALL BE RATED NEMA3R FOR WEATHERPROOF LOCATIONS.

26. ON COMPLETION OF THE WORK, THE ENTIRE WIRING SYSTEM SHALL BE ENTIRELY FREE FROM GROUNDS, SHORT CIRCUITS, OPENS, OVERLOADS AND IMPROPER VOLTAGES. THE

ELECTRICAL CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND TESTING EQUIPMENT NECESSARY TO CONDUCT THE REQUIRED TESTS AND SUBMIT A WRITTEN RECORD OF

THE TESTS PERFORMED TO THE OWNER/BUILDING SUPERVISOR.

27. ALL EQUIPMENT AND SYSTEMS SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP FOR ONE (1) YEAR FROM DATE OF ACCEPTANCE. UPON WRITTEN

NOTICE, AND AT NO EXPENSE TO THE OWNER, THE ELECTRICAL CONTRACTOR SHALL PROMPTLY REPAIR ALL DEFECTIVE MATERIALS.

28. ALL PANELS, CONTACTORS, CIRCUIT BREAKERS, SAFETY SWITCHES AND SIMILAR ITEMS SHALL BE IDENTIFIED BY NAME, FUNCTION, AND/OR CONTROL. THE ELECTRICAL

CONTRACTOR SHALL PROVIDE NEATLY TYPED SCHEDULES OUTLINING CIRCUIT CONTROL FOR ALL PANELBOARDS.

29. THE ELECTRICAL CONTRACTOR SHALL PROVIDE IDENTIFICATION ON THE INSIDE OF BOXES WITH BLANK COVERS WHERE APPLICABLE.

30. IN GENERAL, THE ELECTRICAL CONTRACTOR SHALL ARRANGE WORK SO THAT NO ACCESS PANELS WILL BE REQUIRED. JUNCTION BOXES AND SIMILAR EQUIPMENT THAT REQUIRE

ACCESS SHALL BE LOCATED ABOVE REMOVABLE TILE CEILING OR IN UNFINISHED SPACES.

31. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ADEQUATE PROTECTION AGAINST DAMAGE TO ALL MATERIAL AND EQUIPMENT DURING SHIPPING AND STORAGE AT THE SITE. ALL

STORED EQUIPMENT SHALL BE COVERED TO AVOID DUST AND MOISTURE. AFTER EQUIPMENT IS INSTALLED, THE ELECTRICAL CONTRACTOR SHALL COVER ALL OPENINGS TO

PREVENT ENTRANCE OF WATER AND OTHER MATERIALS. ALL CONDUIT OPENINGS SHALL BE CLOSED WITH TEMPORARY METAL OR PLASTIC CAPS, INCLUDING THOSE TERMINATED

IN ELECTRICAL EQUIPMENT.

32. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE OWNER SO AS NOT TO INTERFERE WITH THE NORMAL FUNCTION OF THE BUILDING.

33. ALL ELECTRICAL PENETRATIONS THROUGH FIRE RATED WALL OR PARTITIONS SHALL BE FIRESTOPPED USING APPROVED METHODS TO MAINTAIN THE FIRE RATING PER THE LATEST

VERSION OF THE NATIONAL ELECTRIC CODE.

34. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND UL APPROVED.

35. THE ELECTRICAL CONTRACTOR SHALL SUBMIT A LIST OF EQUIPMENT AND MATERIALS TO BE USED, LISTING EACH ITEM SEPARATELY, AND INDICATING THE NAME OF THE

MANUFACTURER, SOURCE OF MATERIAL, OR SUBCONTRACTOR.

36. THE ELECTRICAL CONTRACTOR IS REQUIRED TO SUBMIT EQUIPMENT CUT-SHEETS AND SHOP DRAWINGS AND OBTAIN APPROVAL BEFORE PURCHASE AND/OR INSTALLATION OF

MATERIALS. APPROVAL WILL BE GIVEN ONLY TO INDICATE GENERAL COMPLIANCE WITH CONTRACT REQUIREMENTS. THE ELECTRICAL CONTRACTOR SHALL CHECK ALL DRAWINGS

AND SPECIFICATIONS FOR COMPLIANCE BEFORE SUBMISSION.

37. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL LUG SIZES OF EQUIPMENT WITH WIRE SIZES USED AND OR SPECIFIED.

38. FASTENING SHALL BE PERFORMED BY THE ELECTRICAL CONTRACTOR AS FOLLOWS:

A. IN HOLLOW MASONRY OR DRYWALL CONSTRUCTION SHALL BE PERFORMED WITH TOGGLE BOLTS

B. IN STRUCTURAL IRON MACHINE BOLTS SHALL BE UTILIZED

C. IN WOOD OR OTHER FIBROUS MATERIALS, LAG SCREW OR BOLTS SHALL BE UTILIZED

D. IN SOLID MASONRY, METALLIC EXPANSION SHIELDS AND MACHINE BOLTS SHALL BE UTILIZED

E. IN POURED CONCRETE, CONCRETE BOX INSERTS WITH ADDITIONAL REINFORCING STEEL INSTALLED WHERE DIRECTED SHALL BE USED.

F. GROUPS OF EQUIPMENT AND DEVICES SHALL BE SUPPORTED ON RACKS AND FRAMES CONSTRUCTED OF POWER-STRUT OR SIMILAR STRUCTURAL MEMBERS.

39. ALL CONDUITS SHALL BE RIGIDLY AND FIRMLY INSTALLED BY MALLEABLE OR WROUGHT STEEL HANGERS OF STANDARD DESIGN, PIPE CLAMPS, OR FABRICATED STEEL SUPPORTS

OF APPROVED DESIGN.

40. USE ONLY U.L. APPROVED RACEWAYS, WITH U.L. LABEL AND MANUFACTURERS NAME CLEARLY IDENTIFIED. THE MINIMUM SIZE CONDUIT SHALL BE 3/4".

41. RIGID STEEL CONDUIT (HEAVYWALL) SHALL BE GALVANIZED. CONDUIT FITTINGS SHALL BE CAST, MALLEABLE IRON, SMOOTH FINISH, FULL THREADED HUBS (IMC ACCEPTABLE).

42. ELECTRICAL METALLIC TUBING (EMT) (THINWALL) SHALL BE GALVANIZED. EMT FITTINGS SHALL BE SET SCREW TYPE.

43. WIREWAYS AND TROUGHS SHALL BE GALVANIZED STEEL, PROPERLY SIZED, WITH SCREWED COVERS. THE ELECTRICAL CONTRACTOR SHALL PROVIDE INTERIOR PARTITIONS

WHERE REQUIRED OR INDICATED.

44. FLEXIBLE CONDUIT SHALL BE STEEL, GALVANIZED AND U.L. APPROVED FOR GROUNDING. THE ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE GROUND WIRE.

45. LIQUID-TIGHT CONDUIT SHALL BE PVC JACKETED FLEXIBLE STEEL TYPE.

46. UNDERGROUND RACEWAYS SHALL BE PLASTIC (PVC) MINIMUM TYPE I, SUITABLE FOR ENCASEMENT IN CONCRETE. PROVIDE CONDUIT TO DUCT FITTINGS WHERE CHANGE OR

RACEWAY OCCURS.

47. THROUGH-WALL OUTLET BOXES SHALL NOT BE PERMITTED.

48. SLIP JOINT FITTINGS SHALL BE USED FOR CONDUITS PASSING THROUGH STRUCTURAL EXPANSION JOINTS. FITTINGS SHALL BE U.L. APPROVED FOR GROUNDING.

49. JUNCTION AND PULL BOXES, WHERE REQUIRED, SHALL BE CODE GAUGE GALVANIZED SHEET STEEL, WITH SCREWED COVERS, SIZED AS REQUIRED BY CODE. RECESSED

BOXES IN FINISHED AREAS WILL NOT BE ACCEPTED UNLESS SPECIFICALLY NOTED ON DRAWINGS.

50. RACEWAY INSTALLATIONS SHALL BE MECHANICALLY SECURED FOR A CONTINUOUS EFFECTIVE GROUND.

51. RIGID STEEL CONDUIT SHALL BE USED WHERE EXPOSED TO MOISTURE, BELOW GRADE OR IN FLOOR FILLS, FOR EXPOSED RUNS OUTDOORS AND IN OTHER WET LOCATIONS, INCLUDING WEATHER PROTECTED AREAS.

52. THINWALL TUBING (EMT) MAY BE USED FOR EXPOSED AND CONCEALED WIRING IN DRY LOCATIONS, NOT SPECIFICALLY MENTIONED ABOVE.

53. WIRING IN CONCRETE SLABS (ON GRADE), WHERE EXPOSED TO MOISTURE OR BELOW GRADE SHALL BE INSTALLED IN GALVANIZED STEEL CONDUIT. PVC RACEWAYS MAY BE

INSTALLED UNDER SLAB ON GRADE. THE ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE GROUND CABLE IN ALL PVC RACEWAYS.

54. LIQUID-TIGHT FLEXIBLE CONDUIT SHALL BE USED FOR FINAL CONNECTIONS TO EQUIPMENT, MOTORS, AND SIMILAR EQUIPMENT IN WET/DAMP AREAS.

55. THE ELECTRICAL CONTRACTOR SHALL INSTALL EXPOSED CONDUIT IN A NEAT SYMMETRICAL MANNER. CONDUITS SHALL FOLLOW BUILDING LINES, SECURELY SUPPORTED

FROM THE BUILDING STRUCTURE ON 10 FOOT INTERVALS BY CONDUIT STRAPS OR PIPE HANGERS ON SUPPORTING ASSEMBLIES AND SUPPORTED WITHIN 3 FEET OF OUTLET BOX

OR FITTING.

56. THE ELECTRICAL CONTRACTOR SHALL RUN EXPOSED CONDUIT IN UNFINISHED SPACES AFTER DUCTWORK AND PIPING HAVE BEEN INSTALLED, AND PROVIDE SUSPENSION

MATERIALS AS REQUIRED. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED OFFSETS, BENDS, BOXES AND FITTINGS AS REQUIRED.

57. THE ELECTRICAL CONTRACTOR SHALL NOT PIERCE STRUCTURAL MEMBERS WITHOUT PERMISSION.

58. WHERE CONDUIT PASSES THROUGH EXTERIOR WALLS, FLOOR OR ROOF, THE ELECTRICAL CONTRACTORS SHALL INSTALL APPROPRIATE FITTINGS AND MATERIALS TO MAKE

OPENINGS WATERTIGHT.

59. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A NYLON LINE PULL LINE IN ALL EMPTY CONDUITS.

60. THE ELECTRICAL CONTRACTOR SHALL MAKE PANELBOARD CONNECTIONS SO THAT CIRCUIT PROTECTORS ARE IN LOGICAL OPERATING SEQUENCE, AND SO THAT LOADS ARE

BALANCED ACROSS ALL PHASES.

61. WHERE CONDUIT ENTERS BUILDING FROM BELOW GRADE, THE ELECTRICAL CONTRACTOR SHALL SEAL END OF RACEWAY WITH APPROVED WATERPROOFING COMPOUND AFTER

WIRES HAVE BEEN INSTALLED.

62. THE ELECTRICAL CONTRACTOR SHALL SUPPORT CONDUCTORS IN VERTICAL RACEWAYS IN ACCORDANCE WITH THE LATEST VERSION OF THE NATIONAL ELECTRIC CODE.

63. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL WIRING, CONNECTIONS AND DEVICES, ETC. NECESSARY TO COMPLY WITH THE GROUNDING REQUIREMENTS OF THE LATEST

VERSION OF THE NATIONAL ELECTRIC CODE AND AS SHOWN ON THE DRAWINGS. EXCEPT WHERE SPECIFICALLY INDICATED OTHERWISE, ALL EXPOSED NON-CURRENT CARRYING

METALLIC PARTS OF ELECTRICAL EQUIPMENT, RACEWAY SYSTEMS, GROUNDING CONDUCTORS OF NON-METALLIC COVERED CABLE AND NEUTRAL CONDUCTORS OF THE WIRING

SYSTEM, SHALL BE GROUNDED.

64. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL SERVICE EQUIPMENT HAS BEEN APPROVED BY THE LOCAL UTILITY COMPANY BEFORE PURCHASE OF SUCH EQUIPMENT.

THIS INCLUDES VERIFYING THAT THE AIC RATINGS OF ALL DISTRIBUTION EQUIPMENT ARE ACCEPTABLE. THE ELECTRICAL CONTRACTOR SHALL SUBMIT AIC CALCULATIONS IF

REQUESTED BY PROFESSIONAL ENGINEER.

GENERAL ELECTRICAL NOTES

KEELING

BUILDING

ADDITION

EXISTING

KEELING

BUILDING

EXISTING

BUTLER

BUILDING

NEW TOWER

SCIENCE BUILDING

NEW GARAGE

BUILDING

EXISTING 300KVA

PAD MOUNTED

UTILITY

TRANSFORMER

EXISTING 50KVA MAT MOUNTED

UTILITY TRANSFORMER TO BE REMOVED

(REFER TO "PROJECT SCOPE NOTE J"

FOR MORE DETAILS)

EXISTING

TANK

RELOCATED

CHIN BUILDING

EXISTING

DOBSON DOME

EXISTING NDACC BUILDING

NEW UTILITY APPROVED GROUND MOUNTED JUNCTION BOX

(REFER TO "PROJECT SCOPE NOTE J" FOR MORE DETAILS)

EC-01 (REFER TO "PROJECT SCOPE NOTE J" FOR MORE DETAILS)

NEW 400A 120/208V 1Ø

SWITCH BOARD

"SWB-TS" LOCATION

EC-03

EC-04

EXISTING

300KVA

TRANSFORMER

120/208V 3Ø

EXISTING 120/208V

3Ø METER PANEL

(SOUTH EXTERIOR

WALL OF BUTLER

BUILDING)

70A3P

M

400A3P

M

EXISTING

PANEL "MLSO"

100A3P 100A3P

EXISTING DISTRIBUTION PANEL 400A MLO 120/208V 3Ø

100A3P 100A3P 100A3P 50A3P 100A3P 50A3P 50A2P 60A3P 60A3P 100A3P

EXISTING 70A

120/208V 3Ø

PUMP

ROOM

PANEL

EXISTING 100A

120/208V 3Ø

KEELING

BUILDING

PANEL "K"

EXISTING 70A

120/208V 3Ø

MLO WEST

PANEL

(CAMERA BUILDING)

EXISTING 100A

120/208V 3Ø

ACE

BUILDING

PANEL

EXISTING 100A

120/208V 3Ø

BUTLER

BUILDING

PANEL

EXISTING 50A

120/208V 3Ø

DOBSON

DOME

PANEL

EXISTING 100A

120/208V 3Ø

LIDAR

BUILDING

PANEL

EXISTING 100A

120/208V 3Ø

SOLAR

VARIABILITY

BUILDING PANEL

EXISTING 50A

120/208V 1Ø

SOLAR

DOME

PANEL

NEW 60A

120/208V 3Ø

TOWER SCIENCE

BUILDING

PANEL "TB"

NEW 60A

120/208V 3Ø

GARAGE

BUILDING

PANEL "G"

NEW 100A

120/208V 3Ø

KEELING

BUILDING

ADDITION

PANEL "KA"

50A2P 100A2P

EXISTING SPECIAL PROJECTS DISTRIBUTION PANEL 400A MLO 120/240 1Ø

100A2P 100A2P 60A2P

EXISTING

SCHNELL

BUILDING

EXISTING

UCHIDA

BUILDING

EXISTING

MLO EAST

PANEL

(MICROWAVE)

EXISTING

GONG

EXISTING

NIST LUNAR

BUILDING

NEW GROUND MOUNT

UTILITY APPROVED

JUNCTION BOX

TO BE LOCATED

AT EXISTING 50KVA

MAT MOUNTED

TRANSFORMER

100A2P

M

400A2P

M

EXISTING

HAWAII TELCOM

PANEL

EC-01

(REFER TO

"PROJECT SCOPE

NOTE J" FOR

MORE DETAILS)

EC-02 EC-02 EC-05EXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTING

EXISTING EXISTING EXISTING EXISTING EXISTING

EXISTING EXISTING

EXISTING 120/240V 1Ø

METER PANEL

SERVING

HAWAII TELECOM &

NE CLUSTER

(SPECIAL PROJECTS)

EXISTING

EXISTING

EXISTING

EC-03

NEW 400A

120/208V 3Ø

NEMA3R

SWITCHBOARD

EXTERIOR OF

TOWER SCIENCE

BUILDING

PANEL "SWB-TS"

5 5 5 5 5 5 5 5 5 5 5 5

NEW 60A

120/208V 1Ø

CHIN

BUILDING

PANEL "CB"

EC-04

ELECTRICAL CONDUIT SCHEDULE

PVC = UNDERGROUND/OUTDOOR, EMT= INTERIOR ABOVE GRADE

CONDUIT I.D. CONDUIT SIZE/TYPE CONDUIT WIRE SIZE & GROUND

EC-01 4" PVC

(4) 500kcmil THHN/THWN CU, (1) 1/0 THHN/THWN CU GROUND

EC-02 2" PVC

(4) #6 THHN/THWN CU, (1) #8 THHN/THWN CU GROUND

EC-03 4" PVC

(4) 500kcmil THHN/THWN CU, (1) 1/0 THHN/THWN CU GROUND

EC-04 2" PVC

(3) #6 THHN/THWN CU, (1) #8 THHN/THWN CU GROUND

EC-05 2" PVC

(4) #3 THHN/THWN CU, (1) #8 THHN/THWN CU GROUND

EC-06 3/4" EMT

(3) #8 THHN/THWN CU, (1) #10 THHN/THWN CU GROUND

REFER TO "PROJECT

SCOPE NOTE J" FOR

MORE DETAILS

E.C. SHALL INSTALL NEW CONDUIT/WIRE (EC-01) FROM EXISTING 300KVA UTILITY TRANSFORMER TO NEW UTILITY

APPROVED JUNCTION BOX LOCATED AT EXISTING UTILITY POLE/SERVICE. ALL UNDERGROUND CONDUITS SHALL HAVE

MINIMUM 24" COVER. REFER TO "PROJECT SCOPE NOTE J" ON THIS SHEET FOR FURTHER DETAILS.

E.C. SHALL INSTALL NEW UTILITY APPROVED JUNCTION BOX AND INTERCEPT EXISTING SECONDARY CONDUIT/WIRE AT

EXISTING UTILITY TRANSFORMER. E.C. SHALL JUNCTION NEW EC-01 CONDUIT/WIRE FROM EXISTING 300KVA

TRANSFORMER WITH EXISTING SECONDAY CONDUIT/WIRE IN NEW JUNCTION BOX. ALL UNDERGROUND CONDUITS SHALL

HAVE MINIMUM 24" COVER. REFER TO "PROJECT SCOPE NOTE J" ON THIS SHEET FOR FURTHER DETAILS.

THIS WORK WILL RESULT IN NEW VOLTAGE CHARACTERISTICS 120/208V 1Ø AT EXISTING 120/240V 1Ø ELECTRICAL

DISTRIBUTION AND EQUIPMENT. E.C. IS RESPONSIBLE FOR PROPER OPERATION OF ALL EXISTING EQUIPMENT NOW

POWERED BY 208V RATHER THAN 240V. E.C. SHALL ALSO UPDATE ALL IDENTIFICATION AND LABELING AT ALL EQUIPMENT

FROM 240V TO 208V.

E.C. SHALL PROVIDE NEW CONDUIT/WIRE FROM EXISTING METER ENCLOSURE TO NEW 400A NEMA3R SWITCHBOARD

"SWB-TS" EQUIPMENT. UNDERGROUND CONDUITS SHALL HAVE MINUMUM 24" COVER. E.C. SHALL NOT MAKE ANY

CONNECTIONS UNTIL EXISTING BUTLER BUILDING ELECTRICAL DISTRIBUTION HAS BEEN DISCONNECTED.

E.C. SHALL EXTEND/JUNCTION/REWORK ALL EXISTING LOAD WIRING FROM EXISTING 400A 120/208V 3Ø PANELBOARD IN

EXISTING BUTLER BUILDING TO NEW 400A NEMA3R SWITCHBOARD "SWB-TS" EQUIPMENT AT EXTERIOR OF NEW TOWER

SCIENCE BUILDING PER PLANS. ALL CONDUITS FROM BUTLER BUILDING TO NEW "SWB-TS" SHALL BE UNDERGROUND WITH

MINIMUM 24" COVER. E.C. SHALL NOT MAKE ANY CONNECTIONS UNTIL EXISTING BUTLER BUILDING ELECTRICAL

DISTRIBUTION HAS BEEN DISCONNECTED.

A. THE PURPOSE OF THESE DRAWINGS IS TO PROVIDE SCOPE DESCRIPTION FOR BUDGET PRICING. THESE DRAWINGS ARE NOT INTENDED FOR CONSTRUCTION.

B. THE MAUNA LOA SITE IS UNIQUE IN TERRAIN, ALTITUDE AND UTILITY INFRASTRUCTURE. THE CONTRACTORS BIDDING ON THIS SCOPE SHALL BE AWARE OF THE COMPLEXITIES FOR

CONSTRUCTION THIS SITE.

C. A "SITE-WIDE" GROUNDING SYSTEM NEEDS TO BE INSTALLED FOR PROPER ELECTRICAL SYSTEM PERFORMANCE AND PERSONNEL SAFETY. THESE DRAWINGS DO NOT SHOW DETAILS

RELATIVE TO THE "SITE-WIDE" GROUNDING SYSTEM. THE INTENTION IS FOR EACH BUILDING'S ELECTRICAL SERVICE GROUNDING TO BE CONNECTED VIA NEW 3/0 COPPER WIRE INSTALLED IN

1 1/4" PVC CONDUIT TO THE NEW TOWER FOUNDATION. THE TOWER FOUNDATION SHALL BE UTILIZED FOR THE "SITE-WIDE" GROUNDING SYSTEM COMMON GROUND POINT.

D. E.C. SHALL UTILIZE WELDED TABS, COMMERCIAL GROUND BUSSING, CHEMICAL ENHANCEMENT IN ESTABLISHING THE SITE-WIDE GROUNDING SYSTEM.

E. AFTER CONSTRUCTION IS COMPLETE, THE E.C. SHALL TEST AND DOCUMENT THE GROUNDING SYSTEM PERFORMANCE

F. ALL GROUNDING CONNECTIONS SHALL BE PERFORMED WITH EXOTHERMICALLY WELDED CABLE CONNECTIONS THAT ARE LABELED AND LISTED

G. ALL TIE-INS INTO EXISTING GROUND SYSTEM AT EACH BUILDING’S ELECTRICAL SERVICE LOCATION SHALL BE 4/0 STRANDED COPPER

H. INSTALL SITE-WIDE UFER GROUNDING SCHEME AT ALL NEW CONCRETE INSTALLATIONS ON THE PROJECT INCLUDING BUILDING FOUNDATIONS, WALKWAYS, ETC. AND CONNECT 3/0 COPPER

WIRE TO "SITE-WIDE" GROUNDING SCHEME. CONCRETE REBAR CONNECTIONS SHALL BE EXPOSED AND ELECTRICALLY CONNECTED TO EACH BUILDING ELECTRICAL SERVICES.

I. THE E.C. SHALL INSPECT, TEST AND REPLACE AS NEEDED THE FOLLOWING ELECTRICAL SYSTEM COMPONENTS:

I.1. BONDING CONNECTIONS NEED TO BE INSPECTED AND RE-INSTALLED AS REQUIRED

I.2. SURGE PROTECTORS SHALL BE CATALOGED BY LOCATION AND NAMEPLATE DATA. EXISTING DEVICES THAT ARE NO LONGER PROVIDING PROTECTION SHALL BE REPLACED WITH

EQUIVALENT DEVICE/PROTECTION

I.3. ALL CONVENIENCE OUTLETS (PARTICULARLY OUTDOOR) SHOULD BE REPLACE WITH GFCI / AFCI PER CODE.

I.4. ALL EXISTING CONDUITS AND WIRING LAYING ON THE SURFACE OF THE GROUND ARE NOT CODE COMPLIANT OR SAFE. THESE CONDUITS SHALL BE RE-INSTALLED BELOW GRADE TO

MEET NATIONAL ELECTRIC CODE.

J. THE REMOVAL OF THE EXISTING 50KVA UTILITY TRANSFORMER AND REPLACEMENT WITH JUNCTION BOX SHALL BE QUOTED AS AN ADD/ALT. THE E.C. SHALL CONTACT THE LOCAL UTILITY

AND CONFIRM PROPER SCOPE FOR REMOVAL OF 50KVA TRANSFORMER, FENCING & PRIMARY CABLING AND THE PURCHASE/INSTALLATION OF THE JUNCTION BOX. THE BASE PROPOSAL

SHALL INCLUDE THE FOLLOWING:

J.1. E.C. SHALL CONTACT LOCAL UTILITY FOR REQUIREMENTS/SCOPE THAT IS NOT SPECIFICALLY LISTED HERE.

J.2. E.C SHALL REMOVE/REPLACE AND EXTEND PERIMETER FENCING AREA AROUND EXISTING UTILITY MAT TRANSFORMER / UTILITY POLE TO MEET UTILITY AND OSHA CLEARANCE

REQUIREMENTS. NEW FENCING SHALL BE PROPERLY GROUNDED PER UTILITY DIRECTION AND NATIONAL ELECTRICAL CODE REQUIREMENTS.

J.3. E.C. SHALL PROPERLY PROTECT ALL PRIMARY AND SECONDARY WIRING BY INSTALLING IN PVC CONDUITS WITH PROPER CLEARANCES AND COVER.

K. ALL EQUIPMENT AND PARTS SUPPLIED SHALL BE LISTED AND LABELED AND ACCEPTABLE TO THE AHJ & LOCAL UTILITY AS WELL AS SUBMITTED ON AND APPROVED BY THE CONTRACTING

AGENCY.

L. ALL WORK SHALL COMPLY WITH ALL RELEVANT LOCAL, STATE, FEDERAL AND UTILITY REQUIREMENTS.

M. AS BUILT DOCUMENTATION SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR AT THE COMPLETION OF THE PROJECT.

PROJECT SPECIFIC NOTES

UTILITY/SOURCE

NEUTRAL FROM UTILITY / SOURCE

G

EACH BUILDING'S

MAIN SERVICE

N

(1) 3/0 COPPER TO METAL

WATER PIPE PER NEC

250.52(A)(1)

(IF AVAILABLE)

GROUNDING IN ACCORDANCE WITH ARTICLE 250 OF THE

CURRENT NATIONAL ELECTRIC CODE.

IF AVAILABLE ON THE PREMISES ITEMS 250.52(A)(1) THROUGH

(A)(6) SHALL BE BONDED TOGETHER TO FORM THE

GROUNDING ELECTRODE SYSTEM

250.52(A)(1) METAL UNDERGROUND WATER PIPE

250.52(A)(2) METAL FRAME OF THE BUILDING OR STRUCTURE

250.52(A)(3) CONCRETE-ENCASED ELECTRODE

250.52(A)(4) GROUND RING

250.52(A)(5) ROD AND PIPE ELECTRODES

250.52(A)(6) PLATE ELECTRODES

250.52(A)(7) OTHER LOCAL METAL UNDERGROUND SYSTEMS

GROUND PER NEC 250.24 (C) (1)

OR MANUFACTURER'S

EQUIVALENT BONDING MEANS

(1) 3/0 COPPER

A "SITE-WIDE"

GROUNDING SYSTEM

COMMON GROUNDING

POINT AT NEW TOWER

FOUNDATION

GROUND FROM UTILITY / SOURCE

ELECTRICAL

KEY PLAN &

GENERAL NOTES

E0.0

E0.0

PARTIAL SITE ELECTRICAL PLAN

SCALE: NONE

DRAWING:

PROJECT NO. 201203

DRAWN BY: SV/JV

CHECKED BY: JPS

SCALE: AS NOTED

ISSUE FOR:

O Contracting & Engineering

PHONE EMAIL FAX

(856) 424 7900 EMAIL@SCHOOLEYELECTRIC.COM (856) 424 0272

1812 Garden Avenue PO BOX 3125 Cherry Hill, NJ 08034

SCH CITYOLE CELE R

D A

N

IE

L E

JO

ST

R

A N

J A

I0

R E G

IS

T

E R

E D

A R

C H

IT

E C

T

H ad d o n fi e ld

-B e rl in R d

Su it e

V o o rh e e s, N J

-8

-2 w w w .d j-a rc h .c om

P R

O P O

SE

D

A L T

E R

A T

IO

N

S F

O R

M

A U

N A

L O

A O

B

SE

R V

A T

O R

Y N

O A

A O

B

SR

V A

T O

R Y

-2

M

A U

N A

L O

A A

C C

E

SS

R O

A D

W A

IM

E A

H

I

BID 07/30/21

P

R

E

L

I

M

I

N

A

R

Y

N

R

C

O

N

S

T

R

U

C

T

I

O

N

E0.0

ELECTRICAL ONE-LINE

SCALE: NONE

E0.0

ELECTRICAL KEY-NOTES

SCALE: NONE

E0.0

ELECTRICAL SERVICE GROUNDING DETAIL

SCALE: NONE

4A

E0.0

ELECTRICAL CONDUIT SCHEDULE

SCALE: NONE

TOILET ROOM

KITCHENETTE

OFFICE

IT CLOSET

STORAGE

TOILET ROOM

SCIENCE

OUTREACH AREA

CORRIDOR

K-40,42

40A/208V/1Ø

(EV CHARGING STATION)

KA-12

36" AFF

36" AFF

36"

AFF

36"

AFF

KA-12 KA-14 KA-14 KA-14

KA-14

36"

AFF

KA-10

KA-10

KA-10

KA-10

KA-18

R

K A

K A

A

F F

G

F I

K A

K A

KA-2

KA-2

48"AFF

GFI

KA-4

48"AFF

GFI

KA-4

KA-2

NEW PANEL "KA"

60A 3Ø 120/208V

KA-16

F

KA-16

F

KA-1,3

40A/208V/1Ø

(EV CHARGING STATION)

EXISTING PANEL "K"

100A 120/208V 3Ø

G F

I

EC-06

EC-06

KA-4

KA-8

20A/120V/1Ø

KA-6

20A/120V/1Ø

KA-4

KA-11,13

20A/208V/1Ø

KA-15,17

50A/208V/1Ø

KA-19

20A/120V/1Ø

GFI/WP

KA-24

GFI/WP

KA-24

K A

A

F F

G

F I

A

F F

G

F I

OPTIONAL CABINET

OVEN, 20A/120V

K-8

K-10

K-18

MERCURY

PLATFORM

KA-24

GFI/WP

KA-4

KA-5,7,9

15A/208V/3Ø

RELOCATE HAWAII

TELECOM EQUIPMENT

RELOCATED HAWAII

TELECOM EQUIPMENT

E.C. SHALL PROVIDE NEW 40A2P CIRCUIT FROM EXITING PANEL "K" TO POWER NEW EV CAR CHARGER.

EXISTING ELECTRICAL PANEL "K" SHALL REMAIN. EXISTING COUNTER/SINK SHALL BE RELOCATED BY OTHERS.

TOILET ROOM

KITCHENETTE

OFFICE

MECHANICAL

STORAGE

TOILET ROOM

CORRIDOR

SCIENCE

OUTREACH AREA

KA-23

KA-27

SOS

S O

S

S3OS

S3OS

KA-25

KA-25

SOS

SOS

OS

OS

KA-25

KA-25

KA-25

SYMBOL

LIGHT FIXTURE SCHEDULE

DESCRIPTIONNO.

EXISTING TO REMAIN

LINEAR SUSPENDED LED EQUAL TO NEO-RAY

DEFINE GEN-2-4" SUSPENDED PENDENT DIRECT, 3000K

LINEAR SURFACE MTD. LED EQUAL TO NEO-RAY

DEFINE GEN-2-4" SUSPENDED SURFACE DIRECT, 3000K

LINEAR LED EQUAL TO METALUX LW LED WRAP

4 FEET SURFACE MOUNTED, 4000K

LINEAR LED EQUAL TO METALUX LW LED WRAP

4 FEET CHAIN HUNG, 4000K

LINEAR LED EQUAL TO FAIL-SAFE VRVT3

4 FEET, SURFACE MOUNTED, 3500K

A

B

C

D

E

F

EXIT LIGHT CO. ELSM-G-RM

ARCHITECTURAL RECESSED-MOUNTED LED EDGE-LIT

EXIT SIGN W/ BATTERY BACKUP

DUAL LITE ZR SERIES REMOTE HEAD

10-65W MATCHING EMERGENCY PACK

DUAL LITE LZ SERIES

LZ SERIES INDOOR EMERGENCY LIGHTING UNIT

DUAL LITE ZR SERIES WEATHERPROOF REMOTE HEADS

10-65W MATCHING EMERGENCY PACK

MECHANICAL

106A

SOS

KA-9

MECHANICAL

106A

KA-2

SYMBOL

SYMBOL LEGEND

DUPLEX RECEPTACLE R = REFRIGERATOR

GFI = GROUND FAULT INTERRUPTER F = IN-FLOOR

DESCRIPTION

DATA PORT LOCATION

ELECTRICAL PANEL

CEILING OCCUPANCY SENSOR

E.C. SHALL PROVIDE OVERRIDE SWITCH

3-WAY OCCUPANCY SENSOR - WALL MOUNT

SINGLE POLE OCCUPANCY SENSOR - WALL MOUNT

SOS

S3OS

OS

EXHAUST FAN - SEE MECHANICAL EQUIPMENT

DETAILS

ELECTRIC HEATER - SEE MECHANICAL EQUIPMENT

DETAILS

QUAD RECEPTACLE

SUPPLY FAN - SEE MECHANICAL EQUIPMENT

DETAILS

ELECTRIC DUCT HEATER - SEE MECHANICAL

EQUIPMENT DETAILS

CB-6

CB-4

CB-8

CB-2

NEW PANEL "CB"

60A 1Ø 120/208V

DD

D

SOS

CB-1

CB-5,7

20A/208V/1Ø

CB-3

NEW 100A 120/208V 3Ø PANEL "KA"

PANEL DESCRIPTION: 120/208V 3Ø, 100A MAIN BREAKER ONLY

CB SIZE CIRCUIT DESCRIPTION CIRCUIT DESCRIPTION SIZE CB

40A

NEW

EV CHARGING STATION

CORRIDOR/I.T. RECEPTACLES 20A 2

3 TOILET GFI RECEPTS/EF-1'S/SF-1 20A 4

15A

EDH-1

ELECTRIC DUCT HEATER

EH-1 TOILET RM 20A 6

7 EH-1 TOILET RM 20A 8

9 OFFICE 108 LEFT RECEPTACLES 20A 10

20A

EH-4

ELECTRIC HEATER

OFFICE 108 REAR RECEPTACLES 20A 12

13 OFFICE 108 REAR/RIGHT RECEPTS 20A 14

20A

EH-3

ELECTRIC HEATER

OFFICE 108 CENTER FLOOR RECS 20A 16

17 KITCHENETTE REFRIGERATOR 20A 18

19 20A KITCENETTE EF-2 EXHAUST FAN KITCHENETTE COUNTER RECEPS 20A 20

21 20A SPARE WATER COOLER RECEPTACLE 20A 22

23 20A OFFICE LIGHTING EXTERIOR RECEPTACLES 20A 24

25 20A TOILET/MECH./CORR. LIGHTING OPTIONAL CABINET OVEN 20A 26

27 20A OFFICE CEILING FAN

SUB-PANEL "CB"

CHIN BUILDING

60A

29 20A SPARE 30

31 20A SPARE SPARE 20A 32

33 20A SPARE SPARE 20A 34

35 20A SPARE SPARE 20A 36

37 20A SPARE SPARE 20A 38

39 20A SPARE SPARE 20A 40

41 20A SPARE SPARE 20A 42

NEW 60A 120/208V 1Ø PANEL "CB"

PANEL DESCRIPTION: 120/208V 1Ø, 60A MAIN CIRCUIT BREAKER

CB SIZE CIRCUIT DESCRIPTION CIRCUIT DESCRIPTION SIZE CB

1 20A BUILDING LIGHTING QUAD RECEPTACLE 20A 2

3 20A EF-1 EXHAUST FAN QUAD RECEPTACLE 20A 4

20A

EH-4

ELECTRIC HEATER

QUAD RECEPTACLE 20A 6

7 QUAD RECEPTACLE 20A 8

9 20A SPARE SPARE 20A 10

11 20A SPARE SPARE 20A 12

13 20A SPARE SPARE 20A 14

15 20A SPARE SPARE 20A 16

17 20A SPARE SPARE 20A 18

E1.1

ELECTRICAL POWER PLAN - KEELING BUILDING

SCALE: 1/4"=1'-0"

NEW ELECTRICAL

POWER & LIGHTING

PLANS

E1.1

E1.1

ELECTRICAL SYMBOL LEGEND

SCALE: NONE

DRAWING:

PROJECT NO. 201203

DRAWN BY: SV/JV

CHECKED BY: JPS

SCALE: AS NOTED

ISSUE FOR:

O Contracting & Engineering

PHONE EMAIL FAX

(856) 424 7900 EMAIL@SCHOOLEYELECTRIC.COM (856) 424 0272

1812 Garden Avenue PO BOX 3125 Cherry Hill, NJ 08034

SCH CITYOLE CELE R

D A

N

IE

L E

JO

ST

R

A N

J A

I0

R E G

IS

T

E R

E D

A R

C H

IT

E C

T

H ad d o n fi e ld

-B e rl in R d

Su it e

V o o rh e e s, N J

-8

-2 w w w .d j-a rc h .c om

P R

O P O

SE

D

A L T

E R

A T

IO

N

S F

O R

M

A U

N A

L O

A O

B

SE

R V

A T

O R

Y N

O A

A O

B

SR

V A

T O

R Y

-2

M

A U

N A

L O

A A

C C

E

SS

R O

A D

W A

IM

E A

H

I

BID 07/30/21

P

R

E

L

I

M

I

N

A

R

Y

N

R

C

O

N

S

T

R

U

C

T

I

O

N

E1.1

ELECTRICAL KEY-NOTES

SCALE: NONE

E1.1

ELECTRICAL LIGHTING PLAN - KEELING BUILDING

SCALE: 1/4"=1'-0" 7

E1.1

LIGHTING FIXTURE SCHEDULE

SCALE: NONE

EXISTING LIGHTING, CIRCUITRY &

CONTROL SHALL REMAIN

E1.1

ELECTRICAL POWER & LIGHTING PLANS MEZZANINE - KEELING BUILDING

SCALE: 1/4"=1'-0"

EXISTING LIGHTING, CIRCUITRY &

CONTROL SHALL REMAIN

E1.1

ELECTRICAL PLAN - CHIN BUILDING

SCALE: 1/4"=1'-0"

E1.1

ELECTRICAL PANEL SCHEDULES

SCALE: NONE

AutoCAD SHX Text

REF.

AutoCAD SHX Text

30" HIGH TOP WORK SURFACE

AutoCAD SHX Text

STAIRS UP

AutoCAD SHX Text

EH

AutoCAD SHX Text

AutoCAD SHX Text

EH

AutoCAD SHX Text

AutoCAD SHX Text

EH

AutoCAD SHX Text

AutoCAD SHX Text

EF

AutoCAD SHX Text

AutoCAD SHX Text

EF

AutoCAD SHX Text

AutoCAD SHX Text

EH

AutoCAD SHX Text

AutoCAD SHX Text

EF

AutoCAD SHX Text

AutoCAD SHX Text

EDH

AutoCAD SHX Text

AutoCAD SHX Text

SP

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text

GYP. BD. CEILING

AutoCAD SHX Text D

AutoCAD SHX Text

EF

AutoCAD SHX Text

AutoCAD SHX Text

EH

AutoCAD SHX Text

AutoCAD SHX Text

SF

AutoCAD SHX Text

AutoCAD SHX Text

EDH

AutoCAD SHX Text

AutoCAD SHX Text

EH

AutoCAD SHX Text

AutoCAD SHX Text

EF

NOAA SCIENCE

NON-NOAA SCIENCE

FLEX SCIENCE

TB-4

TB-4

TB-4

TB-4

TB-4

TB-4

TB-2

TB-2

TB-2

TB-2

TB-2

TB-2

36" AFF

36" AFF

36" AFF

TB-6

TB-6

TB-6

TB-6

TB-6

36" AFF

36" AFF

36" AFF

TB-10

TB-10

TB-10

TB-10

TB-10

TB-10

36" AFF

36" AFF

36" AFF36" AFF

TB-8

TB-8

TB-8

TB-8

TB-8

TB-8

36" AFF

TB-12

TB-12

TB-12

TB-12

TB-12

TB-12

36" AFF

TB-4

36" AFF

NEW PANEL "TB"

60A 3Ø 120/208V

TB-6

36" AFF 36" AFF 36" AFF

TB-2

TB-2

TB-6

TB-6

TB-10

TB-10

TB-12TB-8TB-2

36" AFF

36" AFF

36" AFF

36" AFF

36" AFF

36" AFF

NEW 400A 120/208V 3Ø

SWITCHBOARD "SWB-TS"

TB-1,3

30A/208V/1Ø

TB-5,7

30A/208V/1Ø

TB-9,11

30A/208V/1Ø

TB-13

20A/120V/1Ø

TB-15,17,19

TB-13

NOAA SCIENCE

NON-NOAA SCIENCE

FLEX SCIENCE

OS OS OS

TB-14 TB-14 TB-14

SYMBOL

LIGHT FIXTURE SCHEDULE

DESCRIPTIONNO.

EXISTING TO REMAIN

LINEAR SUSPENDED LED EQUAL TO NEO-RAY

DEFINE GEN-2-4" SUSPENDED PENDENT DIRECT, 3000K

LINEAR SURFACE MTD. LED EQUAL TO NEO-RAY

DEFINE GEN-2-4" SUSPENDED SURFACE DIRECT, 3000K

LINEAR LED EQUAL TO METALUX LW LED WRAP

4 FEET SURFACE MOUNTED, 4000K

LINEAR LED EQUAL TO METALUX LW LED WRAP

4 FEET CHAIN HUNG, 4000K

LINEAR LED EQUAL TO FAIL-SAFE VRVT3

4 FEET, SURFACE MOUNTED, 3500K

A

B

C

D

E

F

EXIT LIGHT CO. ELSM-G-RM

ARCHITECTURAL RECESSED-MOUNTED LED EDGE-LIT

EXIT SIGN W/ BATTERY BACKUP

DUAL LITE ZR SERIES REMOTE HEAD

10-65W MATCHING EMERGENCY PACK

DUAL LITE LZ SERIES

LZ SERIES INDOOR EMERGENCY LIGHTING UNIT

DUAL LITE ZR SERIES WEATHERPROOF REMOTE HEADS

10-65W MATCHING EMERGENCY PACK

SYMBOL

SYMBOL LEGEND

DUPLEX RECEPTACLE R = REFRIGERATOR

GFI = GROUND FAULT INTERRUPTER F = IN-FLOOR

DESCRIPTION

DATA PORT LOCATION

ELECTRICAL PANEL

CEILING OCCUPANCY SENSOR

E.C. SHALL PROVIDE OVERRIDE SWITCH

3-WAY OCCUPANCY SENSOR - WALL MOUNT

SINGLE POLE OCCUPANCY SENSOR - WALL MOUNT

SOS

S3OS

OS

EXHAUST FAN - SEE MECHANICAL EQUIPMENT

DETAILS

ELECTRIC HEATER - SEE MECHANICAL EQUIPMENT

DETAILS

QUAD RECEPTACLE

SUPPLY FAN - SEE MECHANICAL EQUIPMENT

DETAILS

ELECTRIC DUCT HEATER - SEE MECHANICAL

EQUIPMENT DETAILS

NEW 60A 120/208V 3Ø PANEL "TB"

PANEL DESCRIPTION: 120/208V 3Ø, 60A MAIN CIRCUIT BREAKER

CB SIZE CIRCUIT DESCRIPTION CIRCUIT DESCRIPTION SIZE CB

30A

EH-2

NOAA SCIENCE 102

NOAA SCIENCE 102 RECEPTS 20A 2

3 NOAA SCIENCE 102 RECEPTS 20A 4

30A

EH-2

FLEX SCIENCE 101

FLEX SCIENCE 101 RECEPTS 20A 6

7 FLEX SCIENCE 101 RECEPTS 20A 8

30A

EH-2

NON NOAA SCIENCE 100

NON NOAA SCIENCE 100 RECEPTS 20A 10

11 NON NOAA SCIENCE 100 RECEPTS 20A 12

13 20A EF-3 EXHAUST & SF-2 SUPPLY FANS SCIENCE RMS 100-102 LIGHTING 20A 14

30A

EDH-2

ELECTRIC DUCT HEATER

SPARE 20A 16

17 SPARE 20A 18

19 SPARE 20A 20

21 20A SPARE SPARE 20A 22

23 20A SPARE SPARE 20A 24

25 20A SPARE SPARE 20A 26

27 20A SPARE SPARE 20A 28

29 20A SPARE SPARE 20A 30

31 20A SPARE SPARE 20A 32

33 20A SPARE SPARE 20A 34

35 20A SPARE SPARE 20A 36

37 20A SPARE SPARE 20A 38

39 20A SPARE SPARE 20A 40

41 20A SPARE SPARE 20A 42

NEW 400A 120/208V 3Ø SWITCHBOARD "SWB-TS"

PANEL DESCRIPTION: 120/208V 3Ø, 400A MAIN CIRCUIT BREAKER

CB SIZE CIRCUIT DESCRIPTION CIRCUIT DESCRIPTION SIZE CB

100A

FUTURE PUMP

ROOM FEED

FUTURE SOLAR VARIABILITY

BUILDING PANEL FEED

50A

3 4

5 6

100A

FUTURE KEELING

PANEL "K" FEED

FUTURE SOLAR DOME

PANEL FEED

50A

9 10

11 12

100A

FUTURE ACE BUILDING

WEST PANEL FEED

FUTURE TOWER SCIENCE

BUILDING PANEL FEED

60A

15 16

17 18

100A

FUTURE ACE BUILDING

PANEL FEED

FUTURE KNEELING ADDITION

BUILDING PANEL FEED

60A

21 22

23 24

100A

FUTURE BUTLER

BUILDING PANEL FEED

FUTURE SOLAR VARIABILITY

BUILDING PANEL FEED

60A

27 28

29 30

100A

FUTURE LIDAR

BUILDING PANEL FEED

SPACE TBD

33 34

35 36

50A

FUTURE DOBSON DOME

PANEL FEED

SPACE TBD

39 40

41 42

TBD SPACE SPACE TBD

45 46

47 48

TBD SPACE SPACE TBD

51 52

53 54

E2.1

ELECTRICAL POWER PLAN - TOWER BUILDING

SCALE: 1/4"=1'-0"

NEW ELECTRICAL

POWER & LIGHTING

PLANS

E2.1

E2.1

ELECTRICAL SYMBOL LEGEND

SCALE: NONE

DRAWING:

PROJECT NO. 201203

DRAWN BY: SV/JV

CHECKED BY: JPS

SCALE: AS NOTED

ISSUE FOR:

O Contracting & Engineering

PHONE EMAIL FAX

(856) 424 7900 EMAIL@SCHOOLEYELECTRIC.COM (856) 424 0272

1812 Garden Avenue PO BOX 3125 Cherry Hill, NJ 08034

SCH CITYOLE CELE R

D A

N

IE

L E

JO

ST

R

A N

J A

I0

R E G

IS

T

E R

E D

A R

C H

IT

E C

T

H ad d o n fi e ld

-B e rl in R d

Su it e

V o o rh e e s, N J

-8

-2 w w w .d j-a rc h .c om

P R

O P O

SE

D

A L T

E R

A T

IO

N

S F

O R

M

A U

N A

L O

A O

B

SE

R V

A T

O R

Y N

O A

A O

B

SR

V A

T O

R Y

-2

M

A U

N A

L O

A A

C C

E

SS

R O

A D

W A

IM

E A

H

I

BID 07/30/21

P

R

E

L

I

M

I

N

A

R

Y

N

R

C

O

N

S

T

R

U

C

T

I

O

N

E2.1

ELECTRICAL LIGHTING PLAN - TOWER BUILDING

SCALE: 1/4"=1'-0"

E2.1

LIGHTING FIXTURE SCHEDULE

SCALE: NONE

E2.1

ELECTRICAL PANEL SCHEDULES

SCALE: NONE

AutoCAD SHX Text

EH

AutoCAD SHX Text

AutoCAD SHX Text

EH

AutoCAD SHX Text

AutoCAD SHX Text

EH

AutoCAD SHX Text

AutoCAD SHX Text

EF

AutoCAD SHX Text

AutoCAD SHX Text

EDH

AutoCAD SHX Text

AutoCAD SHX Text

SF

AutoCAD SHX Text

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text

EF

AutoCAD SHX Text

AutoCAD SHX Text

EH

AutoCAD SHX Text

AutoCAD SHX Text

SF

AutoCAD SHX Text

AutoCAD SHX Text

EDH

GARAGE AREA

CAR PORT

WORKSHOP

G-3

G-3

G-3

G-3

G-9

G-7

G-5

NEW PANEL "G"

60A 3Ø 120/208V

G-1

G-1

G-1

G-13

GFI/WP

G-13

GFI/WP

48" AFF

48" AFF

48" AFF

48" AFF

G-9

G-2,4

40A/208V/1Ø

(EV CHARGING STATION)

EC-06

G-6,8

30A/208V/1Ø

G-10,12

30A/208V/1Ø

G-14

20A/120V/1Ø

G-16

20A/120V/1Ø

G-13

GFI/WP

G-15,17,19

G-14

GARAGE AREA

CAR PORT

WORKSHOP

OS

OS

OS

G-11

G-11

G-11

SYMBOL

SYMBOL LEGEND

DUPLEX RECEPTACLE R = REFRIGERATOR

GFI = GROUND FAULT INTERRUPTER F = IN-FLOOR

DESCRIPTION

DATA PORT LOCATION

ELECTRICAL PANEL

CEILING OCCUPANCY SENSOR

E.C. SHALL PROVIDE OVERRIDE SWITCH

3-WAY OCCUPANCY SENSOR - WALL MOUNT

SINGLE POLE OCCUPANCY SENSOR - WALL MOUNT

SOS

S3OS

OS

EXHAUST FAN - SEE MECHANICAL EQUIPMENT

DETAILS

ELECTRIC HEATER - SEE MECHANICAL EQUIPMENT

DETAILS

QUAD RECEPTACLE

SUPPLY FAN - SEE MECHANICAL EQUIPMENT

DETAILS

ELECTRIC DUCT HEATER - SEE MECHANICAL

EQUIPMENT DETAILS

SYMBOL

LIGHT FIXTURE SCHEDULE

DESCRIPTIONNO.

EXISTING TO REMAIN

LINEAR SUSPENDED LED EQUAL TO NEO-RAY

DEFINE GEN-2-4" SUSPENDED PENDENT DIRECT, 3000K

LINEAR SURFACE MTD. LED EQUAL TO NEO-RAY

DEFINE GEN-2-4" SUSPENDED SURFACE DIRECT, 3000K

LINEAR LED EQUAL TO METALUX LW LED WRAP

4 FEET SURFACE MOUNTED, 4000K

LINEAR LED EQUAL TO METALUX LW LED WRAP

4 FEET CHAIN HUNG, 4000K

LINEAR LED EQUAL TO FAIL-SAFE VRVT3

4 FEET, SURFACE MOUNTED, 3500K

A

B

C

D

E

F

EXIT LIGHT CO. ELSM-G-RM

ARCHITECTURAL RECESSED-MOUNTED LED EDGE-LIT

EXIT SIGN W/ BATTERY BACKUP

DUAL LITE ZR SERIES REMOTE HEAD

10-65W MATCHING EMERGENCY PACK

DUAL LITE LZ SERIES

LZ SERIES INDOOR EMERGENCY LIGHTING UNIT

DUAL LITE ZR SERIES WEATHERPROOF REMOTE HEADS

10-65W MATCHING EMERGENCY PACK

NEW 60A 120/208V 3Ø PANEL "G"

PANEL DESCRIPTION: 120/208V 3Ø, 60A MAIN CIRCUIT BREAKER

CB SIZE CIRCUIT DESCRIPTION CIRCUIT DESCRIPTION SIZE CB

1 20A GARAGE AREA 101 RECEPTS

NEW

EV CHARGING STATION

40A

3 20A WORKSHOP 102 COUNTER RECS 4

5 20A DRILL PRESS RECEPTACLE

EH-2

GARAGE AREA 101

30A

7 20A BAND SAW RECPTACLE 8

9 20A WORKSHOP 102 RECEPTACLES

EH-2

WORKSHOP 102

30A

11 20A LIGHTING 12

13 20A CAR PORT/OUTDOOR GFI RECS

EF-4 GARAGE, SF-3 WORKSHOP

20A 14

15A

EDH-3

ELECTRIC DUCT HEATER

GARAGE OVERHEAD DOOR 20A 16

17 SPARE 20A 18

19 SPARE 20A 20

21 20A SPARE SPARE 20A 22

23 20A SPARE SPARE 20A 24

25 20A SPARE SPARE 20A 26

27 20A SPARE SPARE 20A 28

29 20A SPARE SPARE 20A 30

31 20A SPARE SPARE 20A 32

33 20A SPARE SPARE 20A 34

35 20A SPARE SPARE 20A 36

37 20A SPARE SPARE 20A 38

39 20A SPARE SPARE 20A 40

41 20A SPARE SPARE 20A 42

E3.1

ELECTRICAL POWER PLAN - GARAGE BUILDING

SCALE: 1/4"=1'-0"

NEW ELECTRICAL

POWER & LIGHTING

PLANS

E3.1

DRAWING:

PROJECT NO. 201203

DRAWN BY: SV/JV

CHECKED BY: JPS

SCALE: AS NOTED

ISSUE FOR:

O Contracting & Engineering

PHONE EMAIL FAX

(856) 424 7900 EMAIL@SCHOOLEYELECTRIC.COM (856) 424 0272

1812 Garden Avenue PO BOX 3125 Cherry Hill, NJ 08034

SCH CITYOLE CELE R

D A

N

IE

L E

JO

ST

R

A N

J A

I0

R E G

IS

T

E R

E D

A R

C H

IT

E C

T

H ad d o n fi e ld

-B e rl in R d

Su it e

V o o rh e e s, N J

-8

-2 w w w .d j-a rc h .c om

P R

O P O

SE

D

A L T

E R

A T

IO

N

S F

O R

M

A U

N A

L O

A O

B

SE

R V

A T

O R

Y N

O…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .