MAP KEY
LOCATION DESCRIPTION
RICHARDSON VISITORS GATE
ARCTIC VALLEY GATE GLENN HWY SOUTHBOUND EXIT
ELMENDORF VISITORS GATE
654 6TH STREET: FIRE STATION 4
8517 20TH STREET: SECURITY FORCES
CLEAN FILL LANDFILL SITE
CONCRETE LANDFILL SITE
BUILDING 55294 AND 55298
JOINT BASE ELMENDORF-RICHARDSON
673RD CIVIL ENGINEER SQUADRON
KEY PLAN
NOT FOR CONSTRUCTION
A B C D E F G H I
SHEET
REFERENCE
NUMBER
AF PROJECT NUMBER:
AEC FILE NAME:
DRAWING SCALE:
PLOT SCALE:
SYMBOL DATE DESCRIPTION
REVISIONS
JOINT BASE ELMENDORF-RICHARDSON, AK
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJ. ENG.
LOCATION
DRAWINGS
1:1
AF CONTRACT NUMBER:
INV. NUMBER:
DATE APPR
DATE:
DATE:
DATE:
DATE:
DRAWING NO:
U.S. AIR FORCE
02 JUN 2022
06/02/2022
06/02/2022
N
Repair Replace Overhead Doors ASP B55294, 55298
HJZH 22-1033
ANSI
D
AND
EXHIBIT
C-1
SCHEDULE OF DRAWINGS
SHEET NUMBER SHEET TITLE
C-1 COVER SHEET
C-2 LOCATION MAP
3-8 FACILITY EXHIBIT DRAWINGS
6-13 LPS EXHIBIT DRAWINGS
1. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS.
2. AT NO TIME WILL THE CONTRACTORS WORK, STORAGE OF MATERIALS, PARKING OF VEHICLES OR OTHER ACTIVITIES BE ALLOWED TO INTERFERE WITH THE WORK ACTIVITIES OF GOVERNMENT PERSONNEL OR TO DAMAGE GOVERNMENT OR PRIVATE PROPERTY.
3. THE CONTRACTOR SHALL AT ALL TIMES KEEP THE WORK AREA FREE FROM ACCUMULATION OF WASTE MATERIALS. DEBRIS SHALL BE REMOVED ON A DAILY
BASIS.
4. ALL WELDING AND / OR THE USE OF FLAME PRODUCING DEVICES SHALL BE CLEARED THROUGH THE FIRE DEPARTMENT.
5. ALL CONSTRUCTION PERMITS, FEES AND COORDINATION OF ANCILLARY ITEMS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
6. THE WORK OF THIS CONTRACT SHALL COMPLY WITH APPLICABLE FEDERAL, STATE AND LOCAL CODES OR STANDARDS, INCLUDING BUT NOT LIMITED TO:
ENVIRONMENTAL PROTECTION AGENCY, NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE, NATIONAL FIRE PROTECTION ASSOCIATION, OSHA
STANDARDS, FIRE CODES, INTERNATIONAL BUILDING CODE.
PROJECT NOTES:
COVER SHEET
PROJECT LOCATION
LOCATION 1
LOCATION 2
BLDG 55300
A B C D E F G H I
SHEET
REFERENCE
NUMBER
AF PROJECT NUMBER:
AEC FILE NAME:
DRAWING SCALE:
PLOT SCALE:
SYMBOL DATE DESCRIPTION
REVISIONS
JOINT BASE ELMENDORF-RICHARDSON, AK
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJ. ENG.
LOCATION
DRAWINGS
1:1
AF CONTRACT NUMBER:
INV. NUMBER:
DATE APPR
DATE:
DATE:
DATE:
DATE:
DRAWING NO:
U.S. AIR FORCE
02 JUN 2022
06/02/2022
06/02/2022
N
Repair Replace Overhead Doors ASP B55294, 55298
HJZH 22-1033
ANSI
D
AND
EXHIBIT
AERIAL MAP
C-2
LADUE DR
BLDG 55294
BLDG 55298
EXHIBIT DRAWING
PRO
L P I TECTIONLI
G
HT
N ING
ITSNI
T U TE
MEM BER
Lowell Hart
CHECKED BY:
REVISED DATE:
SCALE:
SHEET:
DATE:
DRAWN BY:
DWG. NO.
EVALUATION:
AZ-2017-0220
JLH
20TH FEBRUARY 2017
AS SHOWN
ORIGINAL SIZE: 30" X 42"NO. DATE DESCRIPTION OF REVISION BY
Project Name and Location
Materials By:
Preferred Lightning Protection
2100 East First Street Maryville, MO 64468
Phone: 866-299-7406 or 660-562-2771
Fax: 660-582-2603 U.L. Listing E236181
L.P.I. Manufacturing Member
Design and Installation by:
CONDUCTOR BEND SHALL NOT FORM A SHARPER ANGLE THAN 90 DEGREES OR HAVE A RADIUS LESS THAN 8
INCHES.
ISOLATED METAL BODIES THAT SHOW NO CONDUCTANCE TO GROUND SHALL NOT REQUIRE BONDING. A
GROUNDED METAL BODY WITHIN THE SIX FOOT RULE SHALL BE BONDED TO THE SYSTEM.
AIR TERMINAL SHALL BE PLACED AT THE LOCATIONS INDICATED, NOT MORE THAN 2'-0" FROM THE ENDS OF RIDGES, OUTSIDE CORNERS, OR OUTSIDE EDGES OF MAIN ROOFS AND MUST EXTEND A MINIMUM OF 10"
ABOVE OBJECT TO BE PROTECTED.
MIDROOF AIR TERMINALS SHALL BE SPACED AT 50'-0" O.C. MAXIMUM SPACING.
JOB CONDITIONS MAY DICTATE VARIATIONS IN AIR TERMINAL, CONDUCTORS AND GROUND ROD LOCATIONS.
CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD PATH FREE FROM "U" AND "V" POCKETS. ANY
RISE IN HORIZONTAL CONDUCTOR SHALL NOT EXCEED 8 INCHES.
CABLE MAY RISE UPWARDS AT A RATE OF 3" OF RISE PER 1'-0" RUN MAXIMUM.
COPPER LIGHTNING PROTECTION MATERIALS SHALL NOT BE PLACED ON ALUMINUM, GALVANIZED STEEL, GALVALUME SURFACES OR ANY OTHER DISSIMILAR METAL SURFACES, PAINTED OR NOT, NOR SHALL
ALUMINUM MATERIALS BE PLACED ON COPPER SURFACES.
FOR THE SAKE OF CLARITY WE HAVE NOT CALLED OUT EACH INDIVIDUAL ITEM OF LIGHTNING PROTECTION MATERIALS ON THE ROOF PLAN. WE HAVE SHOWN TYPICAL DETAILS AND HAVE CALLED OUT EACH OF THESE
DETAILS ON THE ROOF PLAN, ONLY IN SCATTERED LOCATIONS.
ALL STRUCTURAL STEEL, REBAR, FRAMING & MISCELLANEOUS STEEL SHALL BE MADE ELECTRICALLY CONTINUOUS THROUGH CONSTRUCTION (NOT THE RESPONSIBILITY OF THE LIGHTNING PROTECTION
CONTRACTOR).
ELECTRIC, TELEPHONE AND ANTENNA SYSTEM GROUNDS SHALL BE CONNECTED WITH MAIN SIZE CONDUCTOR
TO ONE LIGHTNING PROTECTION GROUND OR METAL WATER PIPE.
A LIGHTNING ARRESTOR, PROTECTOR, OR ANTENNA-DISCHARGE UNIT MUST BE INSTALLED ON EACH ELECTRIC AND TELEPHONE SERVICE ENTRANCE AND RADIO AND TELEVISION ANTENNA LEAD IN. (TO BE PROVIDED BY
ELECTRICAL CONTRACTOR.)
ALL ADHESIVE FIXTURES SHALL BE SET WITH AN ADHESIVE COMPOUND COMPATIBLE WITH THE ROOFING
MATERIAL. ADHESIVES SHALL BE APPROVED IN ADVANCE BY THE ROOFING CONTRACTOR.
BOND ALL METAL PIPES SUCH AS WATER, GAS, FIRE, STORM, SEWER WHICH ENTER THE STRUCTURE TO THE
NEAREST DOWNLEAD, GROUND ROD OR COUNTERPOISE.
CABLE WILL BE FASTENED EVERY 3'-0" O.C. MAXIMUM SPACING.
PERIMETER AND RIDGE AIR TERMINALS 10" TO 23" WILL BE SPACED UP TO 20' MAXIMUM. AIR TERMINALS 24" AND
OVER WILL BE SPACED 25' MAXIMUM.
CONNECTIONS TO GROUND AND/OR COUNTERPOISE SHALL BE MADE AT A POINT NOT LESS THAN 1'-0" BELOW
GRADE, AND 2'-0" AWAY FROM FOUNDATION WALL.
LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED IN A NEAT, PROFESSIONAL MANNER.
ON EXTERIOR WALLS OF BLOCK OR BRICK, DOWNLEAD CABLES SHALL BE ANCHORED IN THE BLOCK OR BRICK, NOT IN MORTAR.
NOTE: ALL ROOF AREAS ILLUSTRATED ON THESE SUBMITTAL DRAWINGS WHICH HAVE NOT BEEN
PROVIDED WITH LIGHTNING PROTECTION COMPONENTS ARE PROTECTED FROM HIGHER ROOFS OR
STRUCTURES. THESE AREAS FALL WITHIN A "ZONE OF PROTECTION" AS ESTABLISHED BY THE
CURRENT EDITION OF THE STANDARD FOR PROTECTION AGAINST LIGHTNING "ANSI/NFPA 780" AND
THE INSTALLATION REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS AS PROVIDED BY
STANDARD 96A OF UNDERWRITERS' LABORATORIES.
NOTE: INSTALLING CONTRACTOR TO FIELD VERIFY ACTUAL TYPES, LOCATIONS, NUMBERS OF
ROOFTOP OBSTRUCTION LIGHTS, AREAWAY LIGHTS, AND ANY SIMILAR LIGHTING FIXTURES WHICH
MAY PROJECT ABOVE BUILDING ROOF EDGES OR PARAPET WALLS AND ALSO ALL MECHANICAL
EQUIPMENT SUCH AS EXHAUST FANS, FLUES, COOLING TOWERS, CHILLERS, CONDENSING UNITS, ROOFTOP AIR HANDLING UNITS, ETC. AND PROTECT BY CORRECT APPLICATION SHOWN IN DETAIL
"F" UNLESS ITEMS OF EQUIPMENT ARE UNDER ZONE OF PROTECTION BY ADJACENT HIGHER
PROTECTED ROOF LEVELS.
NOTE: THIS LIGHTNING PROTECTION LAYOUT DRAWING IS BASED UPON THE MOST CURRENT
CONTRACT DRAWINGS AND INFORMATION AVAILABLE. THE ACTUAL SYSTEM LAYOUT, CHOICE OF AIR
TERMINAL/CABLE MOUNTING AND ROUTING METHODS, THRU-ROOF AND DOWNLEAD/GROUNDING
LOCATIONS, BONDING REQUIREMENTS, ETC., MAY VARY ACCORDING TO THE FINAL DESIGN OF THE BUILDING. LIGHTNING PROTECTION INSTALLER MUST FIELD VERIFY THE ACTUAL CONDITIONS OF THE
BUILDING(S) TO DETERMINE THE PROTECTION LEVEL NEEDED AND MAKE ANY ADJUSTMENTS,
UPWARD OR DOWNWARD, AS REQUIRED FOR U.L. 96-96A COMPLIANCE AND CERTIFICATION.
NOTE: INSTALLING CONTRACTOR SHALL, PER GENERAL NOTE #2 AND DETAILS "G" AND "H", FIELD VERIFY ACTUAL TYPES AND LOCATIONS OF ROOF LOCATED METAL BODIES SUCH AS SUNSHADES, LADDERS, ROOF HATCHES, SMOKE HATCHES, SCUPPERS, ROOF DRAINS, CAMERAS, WINDOW
WASHING TIEBACKS, PHOTO CELLS, SOIL VENT PIPES, ETC., WHICH MAY REQUIRE BONDING. BOND IF WITHIN 6'-0" OF A LIGHTNING PROTECTION CONDUCTOR OR IF WITHIN 6'-0" OF AN ITEM WHICH HAS ALREADY BEEN BONDED BY THE 6' RULE. UTILIZE THE PROPER APPLICATION OF PLATE, CLAMP, LUG, ETC., TO THE SURFACE/SHAPE OF THE OBJECT TO BE BONDED.
NOTE: ALUMINUM LIGHTNING PROTECTION MATERIALS ARE REQUIRED TO BE UTILIZED ON ALL
BUILDING ROOF LEVELS FOR METALS COMPATIBILITY WITH GALVANIZED STEEL, GALVALUME AND
ALUMINUM SHEET METAL COPINGS, GRAVEL STOPS, ROOF AND WALL PANELS, FLASHINGS AND
EQUIPMENT HOUSINGS, ETC. THE ALUMINUM LIGHTNING PROTECTION MATERIALS AS BID AND
ILLUSTRATED ON THESE SHOP DRAWINGS ARE REQUIRED FOR UL 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATIONS AND TO MAINTAIN THE INTEGRITY OF ROOFING SHEET METAL MATERIALS
AGAINST DAMAGE AND POTENTIAL ROOF SYSTEM FAILURES.
LIGHTNING PROTECTION AND GROUNDING SYSTEM
Phone: 623.845.1094 Fax: 623.845.1093 Website: www.hart-assoc.com
HART & ASSOCIATES INC.
3803 NORTH 36TH AVENUE
PHOENIX, ARIZONA 85019
TEST WELL LOCATION
LP 100
NOTE: THE DESIGN & DETAILS SHOWN WILL MEET THE REQUIREMENTS OF
UNDERWRITERS LABORATORY STANDARD 96A, NATIONAL FIRE PROTECTION ASSOCIATION CODE 780
& THE LIGHTNING PROTECTION INSTITUTE STANDARD 175 FOR LIGHTNING PROTECTION SYSTEMS.
LHH
REPAIR AMMO AREA LIGHTNING PROTECTION
JBER, ALASKA
PROJECT NUMBER: HJZH161046
Master Installer # 1443
U.L. Listing E104704
EST. 1965
BUILDING NO. 55294
#A54 ALUMINUM LIGHTNING PROTECTION
CONDUCTOR
DOWNLEAD LOCATION 1” PVC CONDUIT
UL LISTED/RATED SCHEDULE 80
3/4” X 10’ COPPER CLAD GROUND ROD LOCATION
5/8” X 24” ALUMINUM AIR TERMINAL AND
ALUMINUM BASE
2/0 BARE COPPER GROUND RING/COUNTERPOISE
GROUNDING SYSTEM
LO
A
D
IN
G D
O
CK
LO
A
D
IN
G D
O
CK
LO
A
D
IN
G D
O
CK
65’-4” 10’-00”
’-8
LP300
TYP
V
LP300
TYP
A
LP300
TYP
H
LIGHTNING PROTECTION SYSTEM BASIS OF
DESIGN:
STANDARD: 2014 NFPA 780
STRIKING DISTANCE: 100'
GROUND RING: APPROX. 385’ of 2/0 BARE COPPER CLASS 2
NUMBER OF DOWN CONDUCTORS: 4
AIR TERMINALS: 1/2"X24" COPPER. 3 TOTAL
G
HT
N ING
ITSNI
T U TE
MEM BER
Lowell Hart
CHECKED BY:
REVISED DATE:
SCALE:
SHEET:
DATE:
DRAWN BY:
DWG. NO.
EVALUATION:
AZ-2017-0220
JLH
20TH FEBRUARY 2017
AS SHOWN
ORIGINAL SIZE: 30" X 42"NO. DATE DESCRIPTION OF REVISION BY
Project Name and Location
Materials By:
Preferred Lightning Protection
2100 East First Street Maryville, MO 64468
Phone: 866-299-7406 or 660-562-2771
Fax: 660-582-2603 U.L. Listing E236181
L.P.I. Manufacturing Member
Design and Installation by:
CONDUCTOR BEND SHALL NOT FORM A SHARPER ANGLE THAN 90 DEGREES OR HAVE A RADIUS LESS THAN 8
INCHES.
ISOLATED METAL BODIES THAT SHOW NO CONDUCTANCE TO GROUND SHALL NOT REQUIRE BONDING. A
GROUNDED METAL BODY WITHIN THE SIX FOOT RULE SHALL BE BONDED TO THE SYSTEM.
AIR TERMINAL SHALL BE PLACED AT THE LOCATIONS INDICATED, NOT MORE THAN 2'-0" FROM THE ENDS OF RIDGES, OUTSIDE CORNERS, OR OUTSIDE EDGES OF MAIN ROOFS AND MUST EXTEND A MINIMUM OF 10"
ABOVE OBJECT TO BE PROTECTED.
MIDROOF AIR TERMINALS SHALL BE SPACED AT 50'-0" O.C. MAXIMUM SPACING.
JOB CONDITIONS MAY DICTATE VARIATIONS IN AIR TERMINAL, CONDUCTORS AND GROUND ROD LOCATIONS.
CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD PATH FREE FROM "U" AND "V" POCKETS. ANY
RISE IN HORIZONTAL CONDUCTOR SHALL NOT EXCEED 8 INCHES.
CABLE MAY RISE UPWARDS AT A RATE OF 3" OF RISE PER 1'-0" RUN MAXIMUM.
COPPER LIGHTNING PROTECTION MATERIALS SHALL NOT BE PLACED ON ALUMINUM, GALVANIZED STEEL, GALVALUME SURFACES OR ANY OTHER DISSIMILAR METAL SURFACES, PAINTED OR NOT, NOR SHALL
ALUMINUM MATERIALS BE PLACED ON COPPER SURFACES.
FOR THE SAKE OF CLARITY WE HAVE NOT CALLED OUT EACH INDIVIDUAL ITEM OF LIGHTNING PROTECTION MATERIALS ON THE ROOF PLAN. WE HAVE SHOWN TYPICAL DETAILS AND HAVE CALLED OUT EACH OF THESE
DETAILS ON THE ROOF PLAN, ONLY IN SCATTERED LOCATIONS.
ALL STRUCTURAL STEEL, REBAR, FRAMING & MISCELLANEOUS STEEL SHALL BE MADE ELECTRICALLY CONTINUOUS THROUGH CONSTRUCTION (NOT THE RESPONSIBILITY OF THE LIGHTNING PROTECTION
CONTRACTOR).
ELECTRIC, TELEPHONE AND ANTENNA SYSTEM GROUNDS SHALL BE CONNECTED WITH MAIN SIZE CONDUCTOR
TO ONE LIGHTNING PROTECTION GROUND OR METAL WATER PIPE.
A LIGHTNING ARRESTOR, PROTECTOR, OR ANTENNA-DISCHARGE UNIT MUST BE INSTALLED ON EACH ELECTRIC AND TELEPHONE SERVICE ENTRANCE AND RADIO AND TELEVISION ANTENNA LEAD IN. (TO BE PROVIDED BY
ELECTRICAL CONTRACTOR.)
ALL ADHESIVE FIXTURES SHALL BE SET WITH AN ADHESIVE COMPOUND COMPATIBLE WITH THE ROOFING
MATERIAL. ADHESIVES SHALL BE APPROVED IN ADVANCE BY THE ROOFING CONTRACTOR.
BOND ALL METAL PIPES SUCH AS WATER, GAS, FIRE, STORM, SEWER WHICH ENTER THE STRUCTURE TO THE
NEAREST DOWNLEAD, GROUND ROD OR COUNTERPOISE.
CABLE WILL BE FASTENED EVERY 3'-0" O.C. MAXIMUM SPACING.
PERIMETER AND RIDGE AIR TERMINALS 10" TO 23" WILL BE SPACED UP TO 20' MAXIMUM. AIR TERMINALS 24" AND
OVER WILL BE SPACED 25' MAXIMUM.
CONNECTIONS TO GROUND AND/OR COUNTERPOISE SHALL BE MADE AT A POINT NOT LESS THAN 1'-0" BELOW
GRADE, AND 2'-0" AWAY FROM FOUNDATION WALL.
LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED IN A NEAT, PROFESSIONAL MANNER.
ON EXTERIOR WALLS OF BLOCK OR BRICK, DOWNLEAD CABLES SHALL BE ANCHORED IN THE BLOCK OR BRICK, NOT IN MORTAR.
NOTE: ALL ROOF AREAS ILLUSTRATED ON THESE SUBMITTAL DRAWINGS WHICH HAVE NOT BEEN
PROVIDED WITH LIGHTNING PROTECTION COMPONENTS ARE PROTECTED FROM HIGHER ROOFS OR
STRUCTURES. THESE AREAS FALL WITHIN A "ZONE OF PROTECTION" AS ESTABLISHED BY THE
CURRENT EDITION OF THE STANDARD FOR PROTECTION AGAINST LIGHTNING "ANSI/NFPA 780" AND
THE INSTALLATION REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS AS PROVIDED BY
STANDARD 96A OF UNDERWRITERS' LABORATORIES.
NOTE: INSTALLING CONTRACTOR TO FIELD VERIFY ACTUAL TYPES, LOCATIONS, NUMBERS OF
ROOFTOP OBSTRUCTION LIGHTS, AREAWAY LIGHTS, AND ANY SIMILAR LIGHTING FIXTURES WHICH
MAY PROJECT ABOVE BUILDING ROOF EDGES OR PARAPET WALLS AND ALSO ALL MECHANICAL
EQUIPMENT SUCH AS EXHAUST FANS, FLUES, COOLING TOWERS, CHILLERS, CONDENSING UNITS, ROOFTOP AIR HANDLING UNITS, ETC. AND PROTECT BY CORRECT APPLICATION SHOWN IN DETAIL
"F" UNLESS ITEMS OF EQUIPMENT ARE UNDER ZONE OF PROTECTION BY ADJACENT HIGHER
PROTECTED ROOF LEVELS.
NOTE: THIS LIGHTNING PROTECTION LAYOUT DRAWING IS BASED UPON THE MOST CURRENT
CONTRACT DRAWINGS AND INFORMATION AVAILABLE. THE ACTUAL SYSTEM LAYOUT, CHOICE OF AIR
TERMINAL/CABLE MOUNTING AND ROUTING METHODS, THRU-ROOF AND DOWNLEAD/GROUNDING
LOCATIONS, BONDING REQUIREMENTS, ETC., MAY VARY ACCORDING TO THE FINAL DESIGN OF THE BUILDING. LIGHTNING PROTECTION INSTALLER MUST FIELD VERIFY THE ACTUAL CONDITIONS OF THE
BUILDING(S) TO DETERMINE THE PROTECTION LEVEL NEEDED AND MAKE ANY ADJUSTMENTS,
UPWARD OR DOWNWARD, AS REQUIRED FOR U.L. 96-96A COMPLIANCE AND CERTIFICATION.
NOTE: INSTALLING CONTRACTOR SHALL, PER GENERAL NOTE #2 AND DETAILS "G" AND "H", FIELD VERIFY ACTUAL TYPES AND LOCATIONS OF ROOF LOCATED METAL BODIES SUCH AS SUNSHADES, LADDERS, ROOF HATCHES, SMOKE HATCHES, SCUPPERS, ROOF DRAINS, CAMERAS, WINDOW
WASHING TIEBACKS, PHOTO CELLS, SOIL VENT PIPES, ETC., WHICH MAY REQUIRE BONDING. BOND IF WITHIN 6'-0" OF A LIGHTNING PROTECTION CONDUCTOR OR IF WITHIN 6'-0" OF AN ITEM WHICH HAS ALREADY BEEN BONDED BY THE 6' RULE. UTILIZE THE PROPER APPLICATION OF PLATE, CLAMP, LUG, ETC., TO THE SURFACE/SHAPE OF THE OBJECT TO BE BONDED.
NOTE: ALUMINUM LIGHTNING PROTECTION MATERIALS ARE REQUIRED TO BE UTILIZED ON ALL
BUILDING ROOF LEVELS FOR METALS COMPATIBILITY WITH GALVANIZED STEEL, GALVALUME AND
ALUMINUM SHEET METAL COPINGS, GRAVEL STOPS, ROOF AND WALL PANELS, FLASHINGS AND
EQUIPMENT HOUSINGS, ETC. THE ALUMINUM LIGHTNING PROTECTION MATERIALS AS BID AND
ILLUSTRATED ON THESE SHOP DRAWINGS ARE REQUIRED FOR UL 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATIONS AND TO MAINTAIN THE INTEGRITY OF ROOFING SHEET METAL MATERIALS
AGAINST DAMAGE AND POTENTIAL ROOF SYSTEM FAILURES.
LIGHTNING PROTECTION AND GROUNDING SYSTEM
Phone: 623.845.1094 Fax: 623.845.1093 Website: www.hart-assoc.com
HART & ASSOCIATES INC.
3803 NORTH 36TH AVENUE
PHOENIX, ARIZONA 85019
LP 200
NOTE: THE DESIGN & DETAILS SHOWN WILL MEET THE REQUIREMENTS OF
UNDERWRITERS LABORATORY STANDARD 96A, NATIONAL FIRE PROTECTION ASSOCIATION CODE 780
& THE LIGHTNING PROTECTION INSTITUTE STANDARD 175 FOR LIGHTNING PROTECTION SYSTEMS.
LHH
REPAIR AMMO AREA LIGHTNING PROTECTION
JBER, ALASKA
PROJECT NUMBER: HJZH161046
Master Installer # 1443
U.L. Listing E104704
EST. 1965
BUILDING NO. 55294
100' RADIUS ROLLING SPHERE
ELEVATION B
ELEVATION A
G
HT
N ING
ITSNI
T U TE
MEM BER
Lowell Hart
CHECKED BY:
REVISED DATE:
SCALE:
SHEET:
DATE:
DRAWN BY:
DWG. NO.
NOTES:
AZ-2017-0220
JLH
20TH FEBRUARY 2017
AS SHOWN
ORIGINAL SIZE: 30" X 42"NO. DATE DESCRIPTION OF REVISION BY
Project Name and Location
Materials By:
Preferred Lightning Protection
2100 East First Street Maryville, MO 64468
Phone: 866-299-7406 or 660-562-2771
Fax: 660-582-2603 U.L. Listing E236181
L.P.I. Manufacturing Member
Design and Installation by:
NOTE: THE DESIGN & DETAILS SHOWN WILL MEET THE REQUIREMENTS OF
UNDERWRITERS LABORATORY STANDARD 96A, NATIONAL FIRE PROTECTION ASSOCIATION CODE 780
& THE LIGHTNING PROTECTION INSTITUTE STANDARD 175 FOR LIGHTNING PROTECTION SYSTEMS.
CONDUCTOR BEND SHALL NOT FORM A SHARPER ANGLE THAN 90 DEGREES OR HAVE A RADIUS LESS THAN 8
INCHES.
ISOLATED METAL BODIES THAT SHOW NO CONDUCTANCE TO GROUND SHALL NOT REQUIRE BONDING. A
GROUNDED METAL BODY WITHIN THE SIX FOOT RULE SHALL BE BONDED TO THE SYSTEM.
AIR TERMINAL SHALL BE PLACED AT THE LOCATIONS INDICATED, NOT MORE THAN 2'-0" FROM THE ENDS OF RIDGES, OUTSIDE CORNERS, OR OUTSIDE EDGES OF MAIN ROOFS AND MUST EXTEND A MINIMUM OF 10"
ABOVE OBJECT TO BE PROTECTED.
MIDROOF AIR TERMINALS SHALL BE SPACED AT 50'-0" O.C. MAXIMUM SPACING.
JOB CONDITIONS MAY DICTATE VARIATIONS IN AIR TERMINAL, CONDUCTORS AND GROUND ROD LOCATIONS.
CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD PATH FREE FROM "U" AND "V" POCKETS. ANY
RISE IN HORIZONTAL CONDUCTOR SHALL NOT EXCEED 8 INCHES.
CABLE MAY RISE UPWARDS AT A RATE OF 3" OF RISE PER 1'-0" RUN MAXIMUM.
COPPER LIGHTNING PROTECTION MATERIALS SHALL NOT BE PLACED ON ALUMINUM, GALVANIZED STEEL, GALVALUME SURFACES OR ANY OTHER DISSIMILAR METAL SURFACES, PAINTED OR NOT, NOR SHALL
ALUMINUM MATERIALS BE PLACED ON COPPER SURFACES.
FOR THE SAKE OF CLARITY WE HAVE NOT CALLED OUT EACH INDIVIDUAL ITEM OF LIGHTNING PROTECTION MATERIALS ON THE ROOF PLAN. WE HAVE SHOWN TYPICAL DETAILS AND HAVE CALLED OUT EACH OF THESE
DETAILS ON THE ROOF PLAN, ONLY IN SCATTERED LOCATIONS.
ALL STRUCTURAL STEEL, REBAR, FRAMING & MISCELLANEOUS STEEL SHALL BE MADE ELECTRICALLY CONTINUOUS THROUGH CONSTRUCTION (NOT THE RESPONSIBILITY OF THE LIGHTNING PROTECTION
CONTRACTOR).
ELECTRIC, TELEPHONE AND ANTENNA SYSTEM GROUNDS SHALL BE CONNECTED WITH MAIN SIZE CONDUCTOR
TO ONE LIGHTNING PROTECTION GROUND OR METAL WATER PIPE.
A LIGHTNING ARRESTOR, PROTECTOR, OR ANTENNA-DISCHARGE UNIT MUST BE INSTALLED ON EACH ELECTRIC AND TELEPHONE SERVICE ENTRANCE AND RADIO AND TELEVISION ANTENNA LEAD IN. (TO BE PROVIDED BY
ELECTRICAL CONTRACTOR.)
ALL ADHESIVE FIXTURES SHALL BE SET WITH AN ADHESIVE COMPOUND COMPATIBLE WITH THE ROOFING
MATERIAL. ADHESIVES SHALL BE APPROVED IN ADVANCE BY THE ROOFING CONTRACTOR.
BOND ALL METAL PIPES SUCH AS WATER, GAS, FIRE, STORM, SEWER WHICH ENTER THE STRUCTURE TO THE
NEAREST DOWNLEAD, GROUND ROD OR COUNTERPOISE.
CABLE WILL BE FASTENED EVERY 3'-0" O.C. MAXIMUM SPACING.
PERIMETER AND RIDGE AIR TERMINALS 10" TO 23" WILL BE SPACED UP TO 20' MAXIMUM. AIR TERMINALS 24" AND
OVER WILL BE SPACED 25' MAXIMUM.
CONNECTIONS TO GROUND AND/OR COUNTERPOISE SHALL BE MADE AT A POINT NOT LESS THAN 1'-0" BELOW
GRADE, AND 2'-0" AWAY FROM FOUNDATION WALL.
LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED IN A NEAT, PROFESSIONAL MANNER.
ON EXTERIOR WALLS OF BLOCK OR BRICK, DOWNLEAD CABLES SHALL BE ANCHORED IN THE BLOCK OR BRICK, NOT IN MORTAR.
NOTE: ALL ROOF AREAS ILLUSTRATED ON THESE SUBMITTAL DRAWINGS WHICH HAVE NOT BEEN
PROVIDED WITH LIGHTNING PROTECTION COMPONENTS ARE PROTECTED FROM HIGHER ROOFS OR
STRUCTURES. THESE AREAS FALL WITHIN A "ZONE OF PROTECTION" AS ESTABLISHED BY THE
CURRENT EDITION OF THE STANDARD FOR PROTECTION AGAINST LIGHTNING "ANSI/NFPA 780" AND
THE INSTALLATION REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS AS PROVIDED BY
STANDARD 96A OF UNDERWRITERS' LABORATORIES.
NOTE: INSTALLING CONTRACTOR TO FIELD VERIFY ACTUAL TYPES, LOCATIONS, NUMBERS OF
ROOFTOP OBSTRUCTION LIGHTS, AREAWAY LIGHTS, AND ANY SIMILAR LIGHTING FIXTURES WHICH
MAY PROJECT ABOVE BUILDING ROOF EDGES OR PARAPET WALLS AND ALSO ALL MECHANICAL
EQUIPMENT SUCH AS EXHAUST FANS, FLUES, COOLING TOWERS, CHILLERS, CONDENSING UNITS, ROOFTOP AIR HANDLING UNITS, ETC. AND PROTECT BY CORRECT APPLICATION SHOWN IN DETAIL
"F" UNLESS ITEMS OF EQUIPMENT ARE UNDER ZONE OF PROTECTION BY ADJACENT HIGHER
PROTECTED ROOF LEVELS.
NOTE: THIS LIGHTNING PROTECTION LAYOUT DRAWING IS BASED UPON THE MOST CURRENT
CONTRACT DRAWINGS AND INFORMATION AVAILABLE. THE ACTUAL SYSTEM LAYOUT, CHOICE OF AIR
TERMINAL/CABLE MOUNTING AND ROUTING METHODS, THRU-ROOF AND DOWNLEAD/GROUNDING
LOCATIONS, BONDING REQUIREMENTS, ETC., MAY VARY ACCORDING TO THE FINAL DESIGN OF THE BUILDING. LIGHTNING PROTECTION INSTALLER MUST FIELD VERIFY THE ACTUAL CONDITIONS OF THE
BUILDING(S) TO DETERMINE THE PROTECTION LEVEL NEEDED AND MAKE ANY ADJUSTMENTS,
UPWARD OR DOWNWARD, AS REQUIRED FOR U.L. 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATION.
NOTE: INSTALLING CONTRACTOR SHALL, PER GENERAL NOTE #2 AND DETAILS "G" AND "H", FIELD VERIFY ACTUAL TYPES AND LOCATIONS OF ROOF LOCATED METAL BODIES SUCH AS SUNSHADES, LADDERS, ROOF HATCHES, SMOKE HATCHES, SCUPPERS, ROOF DRAINS, CAMERAS, WINDOW
WASHING TIEBACKS, PHOTO CELLS, SOIL VENT PIPES, ETC., WHICH MAY REQUIRE BONDING. BOND IF WITHIN 6'-0" OF A LIGHTNING PROTECTION CONDUCTOR OR IF WITHIN 6'-0" OF AN ITEM WHICH HAS ALREADY BEEN BONDED BY THE 6' RULE. UTILIZE THE PROPER APPLICATION OF PLATE, CLAMP, LUG, ETC., TO THE SURFACE/SHAPE OF THE OBJECT TO BE BONDED.
NOTE: ALUMINUM LIGHTNING PROTECTION MATERIALS ARE REQUIRED TO BE UTILIZED ON ALL
BUILDING ROOF LEVELS FOR METALS COMPATIBILITY WITH GALVANIZED STEEL, GALVALUME AND
ALUMINUM SHEET METAL COPINGS, GRAVEL STOPS, ROOF AND WALL PANELS, FLASHINGS AND
EQUIPMENT HOUSINGS, ETC. THE ALUMINUM LIGHTNING PROTECTION MATERIALS AS BID AND
ILLUSTRATED ON THESE SHOP DRAWINGS ARE REQUIRED FOR UL 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATIONS AND TO MAINTAIN THE INTEGRITY OF ROOFING SHEET METAL MATERIALS
AGAINST DAMAGE AND POTENTIAL ROOF SYSTEM FAILURES.
DETAILS
HART & ASSOCIATES INC.
3803 NORTH 36TH AVENUE
PHOENIX,ARIZONA 85019
Phone: 623.845.1094 Fax: 623.845.1093 Website: www.hart-assoc.com
LP 300
REPAIR AMMO AREA LIGHTNING PROTECTION
JBER, ALASKA
PROJECT NUMBER: HJZH161046
LHH
Master Installer # 1443
U.L. Listing E104704
EST. 1965
NO. A325 TEE TYPE
CABLE CONNECTOR
NO. C309 CABLE CONNECTOR
NO. A320 BIMETALLIC CONNECTOR
NO. C50 COPPER CABLE
NO. C50 COPPER CABLE
NO. A50 ALUMINUM CABLE
NO. A327 CROSSRUN
CABLE CONNECTOR
NO. A50 ALUMINUM CABLE
NO. A50 ALUMINUM CABLE
NO. A309 CABLE CONNECTOR
NO. A50 ALUMINUM CABLE
NO. A50 ALUMINUM CABLE
NO. A50 ALUMINUM CABLE
NO. A50 ALUMINUM CABLE
R 8"
90°
BEND RADIUS DETAIL
NOTE:
NO BEND OF A CONDUCTOR SHALL FORM
AN INCLUDED ANGLE OF LESS THAN 90 DEGREES,
NOR SHALL IT HAVE A RADIUS
OF BEND LESS THAN 203mm (8").
4 TO 1 CONDUCTOR DETAIL
NOTE: CONDUCTOR SHALL INTERCONNECT ALL
AIR TERMINALS AND SHALL FORM A TWO-WAY
PATH FROM EACH AIR TERMINAL HORIZONTALLY,
DOWNWARD OR RISING AT A RATE NOT
EXCEEDING 3" PER FOOT (76.2mm) TO
CONNECTIONS WITH GROUND TERMINALS
FASTEN CABLE 3'-0" O.C.
MAX, WITH
APPROPRIATE CABLE
FASTENER.
1 2
NO. A5818ST ALUMINUM AIR TERMINAL (5/8" X 18")
NO. A250 ALUMINUM BASE SECURED
WITH FOUR NO. S725 STAINLESS
STEEL SELF-DRILLING SCREWS
NO. A404 ALUMINUM BONDING
CLAMP SECURED WITH TWO
NO. S725 STAINLESS STEEL
SELF-DRILLING SCREWS
NO. A55 ALUMINUM CABLE
TO PARALLEL SPLICER
NO. A210 TOP MOUNT EQUIPMENT BASE SECURED
WITH TWO NO. S725 STAINLESS STEEL
SELF-DRILLING SCREWS
NO. A55 ALUMINUM CABLE SECURED TO UNIT
WITH NO. A702 ALUMINUM LOOP AND NO. S725
STAINLESS STEEL SELF-DRILLING SCREWS
36" O.C. MAXIMUM SPACING
CONNECT TO ROOF CIRCUIT WITH
NO. A309 PARALLEL SPLICER
NO. A5818ST ALUMINUM AIR TERMINAL (5/8" X 18")
NOTE: AIR TERMINALS MUST BE WITHIN
TWO FEET (2') OF OUTSIDE CORNERS
NOTE: CABLE ROUTED AND CONNECTED
TO NEAREST ROOF CIRCUIT
NOTE: CABLE SHALL BE ROUTED AND CONNECTED TO
NEAREST ROOF CIRCUIT. LENGTH OF CABLE SHALL NOT
EXCEED EIGHT FEET (8') OR TWO CABLES WILL BE
REQUIRED FROM THE AIR TERMINAL TO THE ROOF CIRCUIT.
NO. A5818ST ALUMINUM AIR
TERMINAL (5/8" X 18”)
NO. A250 ALUMINUM BASE SECURED
WITH FOUR NO. S725 STAINLESS
STEEL SELF-DRILLING SCREWS
NO. A404 ALUMINUM BONDING CLAMP
SECURED WITH TWO NO. S725 STAINLESS
STEEL SELF-DRILLING SCREWS
NO. A55 ALUMINUM CABLE
TO PARALLEL SPLICER
NOTE: TOP OF UNIT MUST BE MORE THAN
400 SQUARE INCHES OR 1000 CUBIC INCHES
FOR THIS APPLICATION
NOTE: FIELD VERIFY CORRECT APPLICATION
WARNING NOTE
IT IS THE RESPONSIBILITY OF THE LIGHTNING PROTECTION
INSTALLER TO COORDINATE WITH THE MECHANICAL EQUIPMENT
CONTRACTOR AND FIELD VERIFY APPROVED LOCATIONS PRIOR
TO INSTALLATION OF LIGHTNING PROTECTION COMPONENT
FASTENERS FOR ANY DRILLING OR PUNCHING OF HOLES WHICH
MAY BE REQUIRED FOR THE INSTALLATION OF FASTENERS, SO
AS NOT TO DAMAGE INTERNAL PIPING SYSTEMS, WIRING
SYSTEMS OR THE OPERATION/FUNCTION OF THE EQUIPMENT.
NOTE: TOP OF UNIT MUST BE LESS THAN
400 SQUARE INCHES OR 1000 CUBIC INCHES
FOR THIS APPLICATION
NO. A5824ST ALUMINUM AIR
TERMINAL (5/8" X 24")
NO. A54 COPPER CABLE SECURED
WITH NO. A712 ADHESIVE CABLE
HOLDER AND APPROVED ADHESIVE
36" O.C. MAXIMUM SPACING
NO. A220 ADHESIVE BASE AND
SECURED WITH APPROVED ADHESIVE
Air terminals must be located within 2 feet of the roof edge
(where applicable)
TYPICAL HEADWALL AIR TERMINAL, BASE AND CABLE HOLDER A
NO. C56 - 19 COPPER CABLE
NO. C56 - 19 COPPER CABLE
NO. C56 - 19 COPPER CABLE
NO. C55 COPPER
LIGHTNING CONDUCTOR
TYPICAL EXPOSED HEADWALL DOWNLEAD TO GROUND AND COUNTERPOISEH
NO. C313 HEAV Y DUTY CAST STRAIGHT SPLICER
NOT AT EVERY DOWNLEAD
TYPICALAIR TERMINAL MAST AND CABLE HOLDER B
PART NO. C1224ST (1/2” X 24”) COPPER AIR TERMINAL SAFETY TIPPED
PART NO. SRDT15011 1.5” OD 11 GAUAGE
304 STAINLESS STEEL TUBING EXTENDING
4’ ABOVE HEADWALL OR REAR VENTILATOR.
PART NO. C24112 BRONZE SIDE MOUNT AIR TERMINAL BASE
V
G
HT
N ING
ITSNI
T U TE
MEM BER
Lowell Hart
CHECKED BY:
REVISED DATE:
SCALE:
SHEET:
DATE:
DRAWN BY:
DWG. NO.
EVALUATION:
AZ-2017-0220
JLH
20TH FEBRUARY 2017
AS SHOWN
ORIGINAL SIZE: 30" X 42"NO. DATE DESCRIPTION OF REVISION BY
Project Name and Location
Materials By:
Preferred Lightning Protection
2100 East First Street Maryville, MO 64468
Phone: 866-299-7406 or 660-562-2771
Fax: 660-582-2603 U.L. Listing E236181
L.P.I. Manufacturing Member
Design and Installation by:
CONDUCTOR BEND SHALL NOT FORM A SHARPER ANGLE THAN 90 DEGREES OR HAVE A RADIUS LESS THAN 8
INCHES.
ISOLATED METAL BODIES THAT SHOW NO CONDUCTANCE TO GROUND SHALL NOT REQUIRE BONDING. A
GROUNDED METAL BODY WITHIN THE SIX FOOT RULE SHALL BE BONDED TO THE SYSTEM.
AIR TERMINAL SHALL BE PLACED AT THE LOCATIONS INDICATED, NOT MORE THAN 2'-0" FROM THE ENDS OF RIDGES, OUTSIDE CORNERS, OR OUTSIDE EDGES OF MAIN ROOFS AND MUST EXTEND A MINIMUM OF 10"
ABOVE OBJECT TO BE PROTECTED.
MIDROOF AIR TERMINALS SHALL BE SPACED AT 50'-0" O.C. MAXIMUM SPACING.
JOB CONDITIONS MAY DICTATE VARIATIONS IN AIR TERMINAL, CONDUCTORS AND GROUND ROD LOCATIONS.
CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD PATH FREE FROM "U" AND "V" POCKETS. ANY
RISE IN HORIZONTAL CONDUCTOR SHALL NOT EXCEED 8 INCHES.
CABLE MAY RISE UPWARDS AT A RATE OF 3" OF RISE PER 1'-0" RUN MAXIMUM.
COPPER LIGHTNING PROTECTION MATERIALS SHALL NOT BE PLACED ON ALUMINUM, GALVANIZED STEEL, GALVALUME SURFACES OR ANY OTHER DISSIMILAR METAL SURFACES, PAINTED OR NOT, NOR SHALL
ALUMINUM MATERIALS BE PLACED ON COPPER SURFACES.
FOR THE SAKE OF CLARITY WE HAVE NOT CALLED OUT EACH INDIVIDUAL ITEM OF LIGHTNING PROTECTION MATERIALS ON THE ROOF PLAN. WE HAVE SHOWN TYPICAL DETAILS AND HAVE CALLED OUT EACH OF THESE
DETAILS ON THE ROOF PLAN, ONLY IN SCATTERED LOCATIONS.
ALL STRUCTURAL STEEL, REBAR, FRAMING & MISCELLANEOUS STEEL SHALL BE MADE ELECTRICALLY CONTINUOUS THROUGH CONSTRUCTION (NOT THE RESPONSIBILITY OF THE LIGHTNING PROTECTION
CONTRACTOR).
ELECTRIC, TELEPHONE AND ANTENNA SYSTEM GROUNDS SHALL BE CONNECTED WITH MAIN SIZE CONDUCTOR
TO ONE LIGHTNING PROTECTION GROUND OR METAL WATER PIPE.
A LIGHTNING ARRESTOR, PROTECTOR, OR ANTENNA-DISCHARGE UNIT MUST BE INSTALLED ON EACH ELECTRIC AND TELEPHONE SERVICE ENTRANCE AND RADIO AND TELEVISION ANTENNA LEAD IN. (TO BE PROVIDED BY
ELECTRICAL CONTRACTOR.)
ALL ADHESIVE FIXTURES SHALL BE SET WITH AN ADHESIVE COMPOUND COMPATIBLE WITH THE ROOFING
MATERIAL. ADHESIVES SHALL BE APPROVED IN ADVANCE BY THE ROOFING CONTRACTOR.
BOND ALL METAL PIPES SUCH AS WATER, GAS, FIRE, STORM, SEWER WHICH ENTER THE STRUCTURE TO THE
NEAREST DOWNLEAD, GROUND ROD OR COUNTERPOISE.
CABLE WILL BE FASTENED EVERY 3'-0" O.C. MAXIMUM SPACING.
PERIMETER AND RIDGE AIR TERMINALS 10" TO 23" WILL BE SPACED UP TO 20' MAXIMUM. AIR TERMINALS 24" AND
OVER WILL BE SPACED 25' MAXIMUM.
CONNECTIONS TO GROUND AND/OR COUNTERPOISE SHALL BE MADE AT A POINT NOT LESS THAN 1'-0" BELOW
GRADE, AND 2'-0" AWAY FROM FOUNDATION WALL.
LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED IN A NEAT, PROFESSIONAL MANNER.
ON EXTERIOR WALLS OF BLOCK OR BRICK, DOWNLEAD CABLES SHALL BE ANCHORED IN THE BLOCK OR BRICK, NOT IN MORTAR.
NOTE: ALL ROOF AREAS ILLUSTRATED ON THESE SUBMITTAL DRAWINGS WHICH HAVE NOT BEEN
PROVIDED WITH LIGHTNING PROTECTION COMPONENTS ARE PROTECTED FROM HIGHER ROOFS OR
STRUCTURES. THESE AREAS FALL WITHIN A "ZONE OF PROTECTION" AS ESTABLISHED BY THE
CURRENT EDITION OF THE STANDARD FOR PROTECTION AGAINST LIGHTNING "ANSI/NFPA 780" AND
THE INSTALLATION REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS AS PROVIDED BY
STANDARD 96A OF UNDERWRITERS' LABORATORIES.
NOTE: INSTALLING CONTRACTOR TO FIELD VERIFY ACTUAL TYPES, LOCATIONS, NUMBERS OF
ROOFTOP OBSTRUCTION LIGHTS, AREAWAY LIGHTS, AND ANY SIMILAR LIGHTING FIXTURES WHICH
MAY PROJECT ABOVE BUILDING ROOF EDGES OR PARAPET WALLS AND ALSO ALL MECHANICAL
EQUIPMENT SUCH AS EXHAUST FANS, FLUES, COOLING TOWERS, CHILLERS, CONDENSING UNITS, ROOFTOP AIR HANDLING UNITS, ETC. AND PROTECT BY CORRECT APPLICATION SHOWN IN DETAIL
"F" UNLESS ITEMS OF EQUIPMENT ARE UNDER ZONE OF PROTECTION BY ADJACENT HIGHER
PROTECTED ROOF LEVELS.
NOTE: THIS LIGHTNING PROTECTION LAYOUT DRAWING IS BASED UPON THE MOST CURRENT
CONTRACT DRAWINGS AND INFORMATION AVAILABLE. THE ACTUAL SYSTEM LAYOUT, CHOICE OF AIR
TERMINAL/CABLE MOUNTING AND ROUTING METHODS, THRU-ROOF AND DOWNLEAD/GROUNDING
LOCATIONS, BONDING REQUIREMENTS, ETC., MAY VARY ACCORDING TO THE FINAL DESIGN OF THE BUILDING. LIGHTNING PROTECTION INSTALLER MUST FIELD VERIFY THE ACTUAL CONDITIONS OF THE
BUILDING(S) TO DETERMINE THE PROTECTION LEVEL NEEDED AND MAKE ANY ADJUSTMENTS,
UPWARD OR DOWNWARD, AS REQUIRED FOR U.L. 96-96A COMPLIANCE AND CERTIFICATION.
NOTE: INSTALLING CONTRACTOR SHALL, PER GENERAL NOTE #2 AND DETAILS "G" AND "H", FIELD VERIFY ACTUAL TYPES AND LOCATIONS OF ROOF LOCATED METAL BODIES SUCH AS SUNSHADES, LADDERS, ROOF HATCHES, SMOKE HATCHES, SCUPPERS, ROOF DRAINS, CAMERAS, WINDOW
WASHING TIEBACKS, PHOTO CELLS, SOIL VENT PIPES, ETC., WHICH MAY REQUIRE BONDING. BOND IF WITHIN 6'-0" OF A LIGHTNING PROTECTION CONDUCTOR OR IF WITHIN 6'-0" OF AN ITEM WHICH HAS ALREADY BEEN BONDED BY THE 6' RULE. UTILIZE THE PROPER APPLICATION OF PLATE, CLAMP, LUG, ETC., TO THE SURFACE/SHAPE OF THE OBJECT TO BE BONDED.
NOTE: ALUMINUM LIGHTNING PROTECTION MATERIALS ARE REQUIRED TO BE UTILIZED ON ALL
BUILDING ROOF LEVELS FOR METALS COMPATIBILITY WITH GALVANIZED STEEL, GALVALUME AND
ALUMINUM SHEET METAL COPINGS, GRAVEL STOPS, ROOF AND WALL PANELS, FLASHINGS AND
EQUIPMENT HOUSINGS, ETC. THE ALUMINUM LIGHTNING PROTECTION MATERIALS AS BID AND
ILLUSTRATED ON THESE SHOP DRAWINGS ARE REQUIRED FOR UL 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATIONS AND TO MAINTAIN THE INTEGRITY OF ROOFING SHEET METAL MATERIALS
AGAINST DAMAGE AND POTENTIAL ROOF SYSTEM FAILURES.
LIGHTNING PROTECTION AND GROUNDING SYSTEM
Phone: 623.845.1094 Fax: 623.845.1093 Website: www.hart-assoc.com
HART & ASSOCIATES INC.
3803 NORTH 36TH AVENUE
PHOENIX, ARIZONA 85019
TEST WELL LOCATION
LP 100
NOTE: THE DESIGN & DETAILS SHOWN WILL MEET THE REQUIREMENTS OF
UNDERWRITERS LABORATORY STANDARD 96A, NATIONAL FIRE PROTECTION ASSOCIATION CODE 780
& THE LIGHTNING PROTECTION INSTITUTE STANDARD 175 FOR LIGHTNING PROTECTION SYSTEMS.
LHH
REPAIR AMMO AREA LIGHTNING PROTECTION
JBER, ALASKA
PROJECT NUMBER: HJZH161046
Master Installer # 1443
U.L. Listing E104704
EST. 1965
BUILDING NO. 55298
#A54 ALUMINUM LIGHTNING PROTECTION
CONDUCTOR
DOWNLEAD LOCATION 1” PVC CONDUIT
UL LISTED/RATED SCHEDULE 80
3/4” X 10’ COPPER CLAD GROUND ROD LOCATION
5/8” X 24” ALUMINUM AIR TERMINAL AND
ALUMINUM BASE
2/0 BARE COPPER GROUND RING/COUNTERPOISE
GROUNDING SYSTEM
LO
A
D
IN
G D
O
CK
LO
A
D
IN
G D
O
CK
LO
A
D
IN
G D
O
CK
65’-4” 10’-00”
’-8
LP300
TYP
V
LP300
TYP
A
LP300
TYP
H
LIGHTNING PROTECTION SYSTEM BASIS OF
DESIGN:
STANDARD: 2014 NFPA 780
STRIKING DISTANCE: 100'
GROUND RING: APPROX. 385’ of 2/0 BARE COPPER CLASS 2
NUMBER OF DOWN CONDUCTORS: 4
AIR TERMINALS: 1/2"X24" COPPER. 3 TOTAL
G
HT
N ING
ITSNI
T U TE
MEM BER
Lowell Hart
CHECKED BY:
REVISED DATE:
SCALE:
SHEET:
DATE:
DRAWN BY:
DWG. NO.
EVALUATION:
AZ-2017-0220
JLH
20TH FEBRUARY 2017
AS SHOWN
ORIGINAL SIZE: 30" X 42"NO. DATE DESCRIPTION OF REVISION BY
Project Name and Location
Materials By:
Preferred Lightning Protection
2100 East First Street Maryville, MO 64468
Phone: 866-299-7406 or 660-562-2771
Fax: 660-582-2603 U.L. Listing E236181
L.P.I. Manufacturing Member
Design and Installation by:
CONDUCTOR BEND SHALL NOT FORM A SHARPER ANGLE THAN 90 DEGREES OR HAVE A RADIUS LESS THAN 8
INCHES.
ISOLATED METAL BODIES THAT SHOW NO CONDUCTANCE TO GROUND SHALL NOT REQUIRE BONDING. A
GROUNDED METAL BODY WITHIN THE SIX FOOT RULE SHALL BE BONDED TO THE SYSTEM.
AIR TERMINAL SHALL BE PLACED AT THE LOCATIONS INDICATED, NOT MORE THAN 2'-0" FROM THE ENDS OF RIDGES, OUTSIDE CORNERS, OR OUTSIDE EDGES OF MAIN ROOFS AND MUST EXTEND A MINIMUM OF 10"
ABOVE OBJECT TO BE PROTECTED.
MIDROOF AIR TERMINALS SHALL BE SPACED AT 50'-0" O.C. MAXIMUM SPACING.
JOB CONDITIONS MAY DICTATE VARIATIONS IN AIR TERMINAL, CONDUCTORS AND GROUND ROD LOCATIONS.
CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD PATH FREE FROM "U" AND "V" POCKETS. ANY
RISE IN HORIZONTAL CONDUCTOR SHALL NOT EXCEED 8 INCHES.
CABLE MAY RISE UPWARDS AT A RATE OF 3" OF RISE PER 1'-0" RUN MAXIMUM.
COPPER LIGHTNING PROTECTION MATERIALS SHALL NOT BE PLACED ON ALUMINUM, GALVANIZED STEEL, GALVALUME SURFACES OR ANY OTHER DISSIMILAR METAL SURFACES, PAINTED OR NOT, NOR SHALL
ALUMINUM MATERIALS BE PLACED ON COPPER SURFACES.
FOR THE SAKE OF CLARITY WE HAVE NOT CALLED OUT EACH INDIVIDUAL ITEM OF LIGHTNING PROTECTION MATERIALS ON THE ROOF PLAN. WE HAVE SHOWN TYPICAL DETAILS AND HAVE CALLED OUT EACH OF THESE
DETAILS ON THE ROOF PLAN, ONLY IN SCATTERED LOCATIONS.
ALL STRUCTURAL STEEL, REBAR, FRAMING & MISCELLANEOUS STEEL SHALL BE MADE ELECTRICALLY CONTINUOUS THROUGH CONSTRUCTION (NOT THE RESPONSIBILITY OF THE LIGHTNING PROTECTION
CONTRACTOR).
ELECTRIC, TELEPHONE AND ANTENNA SYSTEM GROUNDS SHALL BE CONNECTED WITH MAIN SIZE CONDUCTOR
TO ONE LIGHTNING PROTECTION GROUND OR METAL WATER PIPE.
A LIGHTNING ARRESTOR, PROTECTOR, OR ANTENNA-DISCHARGE UNIT MUST BE INSTALLED ON EACH ELECTRIC AND TELEPHONE SERVICE ENTRANCE AND RADIO AND TELEVISION ANTENNA LEAD IN. (TO BE PROVIDED BY
ELECTRICAL CONTRACTOR.)
ALL ADHESIVE FIXTURES SHALL BE SET WITH AN ADHESIVE COMPOUND COMPATIBLE WITH THE ROOFING
MATERIAL. ADHESIVES SHALL BE APPROVED IN ADVANCE BY THE ROOFING CONTRACTOR.
BOND ALL METAL PIPES SUCH AS WATER, GAS, FIRE, STORM, SEWER WHICH ENTER THE STRUCTURE TO THE
NEAREST DOWNLEAD, GROUND ROD OR COUNTERPOISE.
CABLE WILL BE FASTENED EVERY 3'-0" O.C. MAXIMUM SPACING.
PERIMETER AND RIDGE AIR TERMINALS 10" TO 23" WILL BE SPACED UP TO 20' MAXIMUM. AIR TERMINALS 24" AND
OVER WILL BE SPACED 25' MAXIMUM.
CONNECTIONS TO GROUND AND/OR COUNTERPOISE SHALL BE MADE AT A POINT NOT LESS THAN 1'-0" BELOW
GRADE, AND 2'-0" AWAY FROM FOUNDATION WALL.
LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED IN A NEAT, PROFESSIONAL MANNER.
ON EXTERIOR WALLS OF BLOCK OR BRICK, DOWNLEAD CABLES SHALL BE ANCHORED IN THE BLOCK OR BRICK, NOT IN MORTAR.
NOTE: ALL ROOF AREAS ILLUSTRATED ON THESE SUBMITTAL DRAWINGS WHICH HAVE NOT BEEN
PROVIDED WITH LIGHTNING PROTECTION COMPONENTS ARE PROTECTED FROM HIGHER ROOFS OR
STRUCTURES. THESE AREAS FALL WITHIN A "ZONE OF PROTECTION" AS ESTABLISHED BY THE
CURRENT EDITION OF THE STANDARD FOR PROTECTION AGAINST LIGHTNING "ANSI/NFPA 780" AND
THE INSTALLATION REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS AS PROVIDED BY
STANDARD 96A OF UNDERWRITERS' LABORATORIES.
NOTE: INSTALLING CONTRACTOR TO FIELD VERIFY ACTUAL TYPES, LOCATIONS, NUMBERS OF
ROOFTOP OBSTRUCTION LIGHTS, AREAWAY LIGHTS, AND ANY SIMILAR LIGHTING FIXTURES WHICH
MAY PROJECT ABOVE BUILDING ROOF EDGES OR PARAPET WALLS AND ALSO ALL MECHANICAL
EQUIPMENT SUCH AS EXHAUST FANS, FLUES, COOLING TOWERS, CHILLERS, CONDENSING UNITS, ROOFTOP AIR HANDLING UNITS, ETC. AND PROTECT BY CORRECT APPLICATION SHOWN IN DETAIL
"F" UNLESS ITEMS OF EQUIPMENT ARE UNDER ZONE OF PROTECTION BY ADJACENT HIGHER
PROTECTED ROOF LEVELS.
NOTE: THIS LIGHTNING PROTECTION LAYOUT DRAWING IS BASED UPON THE MOST CURRENT
CONTRACT DRAWINGS AND INFORMATION AVAILABLE. THE ACTUAL SYSTEM LAYOUT, CHOICE OF AIR
TERMINAL/CABLE MOUNTING AND ROUTING METHODS, THRU-ROOF AND DOWNLEAD/GROUNDING
LOCATIONS, BONDING REQUIREMENTS, ETC., MAY VARY ACCORDING TO THE FINAL DESIGN OF THE BUILDING. LIGHTNING PROTECTION INSTALLER MUST FIELD VERIFY THE ACTUAL CONDITIONS OF THE
BUILDING(S) TO DETERMINE THE PROTECTION LEVEL NEEDED AND MAKE ANY ADJUSTMENTS,
UPWARD OR DOWNWARD, AS REQUIRED FOR U.L. 96-96A COMPLIANCE AND CERTIFICATION.
NOTE: INSTALLING CONTRACTOR SHALL, PER GENERAL NOTE #2 AND DETAILS "G" AND "H", FIELD VERIFY ACTUAL TYPES AND LOCATIONS OF ROOF LOCATED METAL BODIES SUCH AS SUNSHADES, LADDERS, ROOF HATCHES, SMOKE HATCHES, SCUPPERS, ROOF DRAINS, CAMERAS, WINDOW
WASHING TIEBACKS, PHOTO CELLS, SOIL VENT PIPES, ETC., WHICH MAY REQUIRE BONDING. BOND IF WITHIN 6'-0" OF A LIGHTNING PROTECTION CONDUCTOR OR IF WITHIN 6'-0" OF AN ITEM WHICH HAS ALREADY BEEN BONDED BY THE 6' RULE. UTILIZE THE PROPER APPLICATION OF PLATE, CLAMP, LUG, ETC., TO THE SURFACE/SHAPE OF THE OBJECT TO BE BONDED.
NOTE: ALUMINUM LIGHTNING PROTECTION MATERIALS ARE REQUIRED TO BE UTILIZED ON ALL
BUILDING ROOF LEVELS FOR METALS COMPATIBILITY WITH GALVANIZED STEEL, GALVALUME AND
ALUMINUM SHEET METAL COPINGS, GRAVEL STOPS, ROOF AND WALL PANELS, FLASHINGS AND
EQUIPMENT HOUSINGS, ETC. THE ALUMINUM LIGHTNING PROTECTION MATERIALS AS BID AND
ILLUSTRATED ON THESE SHOP DRAWINGS ARE REQUIRED FOR UL 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATIONS AND TO MAINTAIN THE INTEGRITY OF ROOFING SHEET METAL MATERIALS
AGAINST DAMAGE AND POTENTIAL ROOF SYSTEM FAILURES.
LIGHTNING PROTECTION AND GROUNDING SYSTEM
Phone: 623.845.1094 Fax: 623.845.1093 Website: www.hart-assoc.com
HART & ASSOCIATES INC.
3803 NORTH 36TH AVENUE
PHOENIX, ARIZONA 85019
LP 200
NOTE: THE DESIGN & DETAILS SHOWN WILL MEET THE REQUIREMENTS OF
UNDERWRITERS LABORATORY STANDARD 96A, NATIONAL FIRE PROTECTION ASSOCIATION CODE 780
& THE LIGHTNING PROTECTION INSTITUTE STANDARD 175 FOR LIGHTNING PROTECTION SYSTEMS.
LHH
REPAIR AMMO AREA LIGHTNING PROTECTION
JBER, ALASKA
PROJECT NUMBER: HJZH161046
Master Installer # 1443
U.L. Listing E104704
EST. 1965
BUILDING NO. 55298
100' RADIUS ROLLING SPHERE
ELEVATION B
ELEVATION A
G
HT
N ING
ITSNI
T U TE
MEM BER
Lowell Hart
CHECKED BY:
REVISED DATE:
SCALE:
SHEET:
DATE:
DRAWN BY:
DWG. NO.
NOTES:
AZ-2017-0220
JLH
20TH FEBRUARY 2017
AS SHOWN
ORIGINAL SIZE: 30" X 42"NO. DATE DESCRIPTION OF REVISION BY
Project Name and Location
Materials By:
Preferred Lightning Protection
2100 East First Street Maryville, MO 64468
Phone: 866-299-7406 or 660-562-2771
Fax: 660-582-2603 U.L. Listing E236181
L.P.I. Manufacturing Member
Design and Installation by:
NOTE: THE DESIGN & DETAILS SHOWN WILL MEET THE REQUIREMENTS OF
UNDERWRITERS LABORATORY STANDARD 96A, NATIONAL FIRE PROTECTION ASSOCIATION CODE 780
& THE LIGHTNING PROTECTION INSTITUTE STANDARD 175 FOR LIGHTNING PROTECTION SYSTEMS.
CONDUCTOR BEND SHALL NOT FORM A SHARPER ANGLE THAN 90 DEGREES OR HAVE A RADIUS LESS THAN 8
INCHES.
ISOLATED METAL BODIES THAT SHOW NO CONDUCTANCE TO GROUND SHALL NOT REQUIRE BONDING. A
GROUNDED METAL BODY WITHIN THE SIX FOOT RULE SHALL BE BONDED TO THE SYSTEM.
AIR TERMINAL SHALL BE PLACED AT THE LOCATIONS INDICATED, NOT MORE THAN 2'-0" FROM THE ENDS OF RIDGES, OUTSIDE CORNERS, OR OUTSIDE EDGES OF MAIN ROOFS AND MUST EXTEND A MINIMUM OF 10"
ABOVE OBJECT TO BE PROTECTED.
MIDROOF AIR TERMINALS SHALL BE SPACED AT 50'-0" O.C. MAXIMUM SPACING.
JOB CONDITIONS MAY DICTATE VARIATIONS IN AIR TERMINAL, CONDUCTORS AND GROUND ROD LOCATIONS.
CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD PATH FREE FROM "U" AND "V" POCKETS. ANY
RISE IN HORIZONTAL CONDUCTOR SHALL NOT EXCEED 8 INCHES.
CABLE MAY RISE UPWARDS AT A RATE OF 3" OF RISE PER 1'-0" RUN MAXIMUM.
COPPER LIGHTNING PROTECTION MATERIALS SHALL NOT BE PLACED ON ALUMINUM, GALVANIZED STEEL, GALVALUME SURFACES OR ANY OTHER DISSIMILAR METAL SURFACES, PAINTED OR NOT, NOR SHALL
ALUMINUM MATERIALS BE PLACED ON COPPER SURFACES.
FOR THE SAKE OF CLARITY WE HAVE NOT CALLED OUT EACH INDIVIDUAL ITEM OF LIGHTNING PROTECTION MATERIALS ON THE ROOF PLAN. WE HAVE SHOWN TYPICAL DETAILS AND HAVE CALLED OUT EACH OF THESE
DETAILS ON THE ROOF PLAN, ONLY IN SCATTERED LOCATIONS.
ALL STRUCTURAL STEEL, REBAR, FRAMING & MISCELLANEOUS STEEL SHALL BE MADE ELECTRICALLY CONTINUOUS THROUGH CONSTRUCTION (NOT THE RESPONSIBILITY OF THE LIGHTNING PROTECTION
CONTRACTOR).
ELECTRIC, TELEPHONE AND ANTENNA SYSTEM GROUNDS SHALL BE CONNECTED WITH MAIN SIZE CONDUCTOR
TO ONE LIGHTNING PROTECTION GROUND OR METAL WATER PIPE.
A LIGHTNING ARRESTOR, PROTECTOR, OR ANTENNA-DISCHARGE UNIT MUST BE INSTALLED ON EACH ELECTRIC AND TELEPHONE SERVICE ENTRANCE AND RADIO AND TELEVISION ANTENNA LEAD IN. (TO BE PROVIDED BY
ELECTRICAL CONTRACTOR.)
ALL ADHESIVE FIXTURES SHALL BE SET WITH AN ADHESIVE COMPOUND COMPATIBLE WITH THE ROOFING
MATERIAL. ADHESIVES SHALL BE APPROVED IN ADVANCE BY THE ROOFING CONTRACTOR.
BOND ALL METAL PIPES SUCH AS WATER, GAS, FIRE, STORM, SEWER WHICH ENTER THE STRUCTURE TO THE
NEAREST DOWNLEAD, GROUND ROD OR COUNTERPOISE.
CABLE WILL BE FASTENED EVERY 3'-0" O.C. MAXIMUM SPACING.
PERIMETER AND RIDGE AIR TERMINALS 10" TO 23" WILL BE SPACED UP TO 20' MAXIMUM. AIR TERMINALS 24" AND
OVER WILL BE SPACED 25' MAXIMUM.
CONNECTIONS TO GROUND AND/OR COUNTERPOISE SHALL BE MADE AT A POINT NOT LESS THAN 1'-0" BELOW
GRADE, AND 2'-0" AWAY FROM FOUNDATION WALL.
LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED IN A NEAT, PROFESSIONAL MANNER.
ON EXTERIOR WALLS OF BLOCK OR BRICK, DOWNLEAD CABLES SHALL BE ANCHORED IN THE BLOCK OR BRICK, NOT IN MORTAR.
NOTE: ALL ROOF AREAS ILLUSTRATED ON THESE SUBMITTAL DRAWINGS WHICH HAVE NOT BEEN
PROVIDED WITH LIGHTNING PROTECTION COMPONENTS ARE PROTECTED FROM HIGHER ROOFS OR
STRUCTURES. THESE AREAS FALL WITHIN A "ZONE OF PROTECTION" AS ESTABLISHED BY THE
CURRENT EDITION OF THE STANDARD FOR PROTECTION AGAINST LIGHTNING "ANSI/NFPA 780" AND
THE INSTALLATION REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS AS PROVIDED BY
STANDARD 96A OF UNDERWRITERS' LABORATORIES.
NOTE: INSTALLING CONTRACTOR TO FIELD VERIFY ACTUAL TYPES, LOCATIONS, NUMBERS OF
ROOFTOP OBSTRUCTION LIGHTS, AREAWAY LIGHTS, AND ANY SIMILAR LIGHTING FIXTURES WHICH
MAY PROJECT ABOVE BUILDING ROOF EDGES OR PARAPET WALLS AND ALSO ALL MECHANICAL
EQUIPMENT SUCH AS EXHAUST FANS, FLUES, COOLING TOWERS, CHILLERS, CONDENSING UNITS, ROOFTOP AIR HANDLING UNITS, ETC. AND PROTECT BY CORRECT APPLICATION SHOWN IN DETAIL
"F" UNLESS ITEMS OF EQUIPMENT ARE UNDER ZONE OF PROTECTION BY ADJACENT HIGHER
PROTECTED ROOF LEVELS.
NOTE: THIS LIGHTNING PROTECTION LAYOUT DRAWING IS BASED UPON THE MOST CURRENT
CONTRACT DRAWINGS AND INFORMATION AVAILABLE. THE ACTUAL SYSTEM LAYOUT, CHOICE OF AIR
TERMINAL/CABLE MOUNTING AND ROUTING METHODS, THRU-ROOF AND DOWNLEAD/GROUNDING
LOCATIONS, BONDING REQUIREMENTS, ETC., MAY VARY ACCORDING TO THE FINAL DESIGN OF THE BUILDING. LIGHTNING PROTECTION INSTALLER MUST FIELD VERIFY THE ACTUAL CONDITIONS OF THE
BUILDING(S) TO DETERMINE THE PROTECTION LEVEL NEEDED AND MAKE ANY ADJUSTMENTS,
UPWARD OR DOWNWARD, AS REQUIRED FOR U.L. 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATION.
NOTE: INSTALLING CONTRACTOR SHALL, PER GENERAL NOTE #2 AND DETAILS "G" AND "H", FIELD VERIFY ACTUAL TYPES AND LOCATIONS OF ROOF LOCATED METAL BODIES SUCH AS SUNSHADES, LADDERS, ROOF HATCHES, SMOKE HATCHES, SCUPPERS, ROOF DRAINS, CAMERAS, WINDOW
WASHING TIEBACKS, PHOTO CELLS, SOIL VENT PIPES, ETC., WHICH MAY REQUIRE BONDING. BOND IF WITHIN 6'-0" OF A LIGHTNING PROTECTION CONDUCTOR OR IF WITHIN 6'-0" OF AN ITEM WHICH HAS ALREADY BEEN BONDED BY THE 6' RULE. UTILIZE THE PROPER APPLICATION OF PLATE, CLAMP, LUG, ETC., TO THE SURFACE/SHAPE OF THE OBJECT TO BE BONDED.
NOTE: ALUMINUM LIGHTNING PROTECTION MATERIALS ARE REQUIRED TO BE UTILIZED ON ALL
BUILDING ROOF LEVELS FOR METALS COMPATIBILITY WITH GALVANIZED STEEL, GALVALUME AND
ALUMINUM SHEET METAL COPINGS, GRAVEL STOPS, ROOF AND WALL PANELS, FLASHINGS AND
EQUIPMENT HOUSINGS, ETC. THE ALUMINUM LIGHTNING PROTECTION MATERIALS AS BID AND
ILLUSTRATED ON THESE SHOP DRAWINGS ARE REQUIRED FOR UL 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATIONS AND TO MAINTAIN THE INTEGRITY OF ROOFING SHEET METAL MATERIALS
AGAINST DAMAGE AND POTENTIAL ROOF SYSTEM FAILURES.
DETAILS
HART & ASSOCIATES INC.
3803 NORTH 36TH AVENUE
PHOENIX,ARIZONA 85019
Phone: 623.845.1094 Fax: 623.845.1093 Website: www.hart-assoc.com
LP 300
REPAIR AMMO AREA LIGHTNING PROTECTION
JBER, ALASKA
PROJECT NUMBER: HJZH161046
LHH
Master Installer # 1443
U.L. Listing E104704
EST. 1965
NO. A325 TEE TYPE
CABLE CONNECTOR
NO. C309 CABLE CONNECTOR
NO. A320 BIMETALLIC CONNECTOR
NO. C50 COPPER CABLE
NO. C50 COPPER CABLE
NO. A50 ALUMINUM CABLE
NO. A327 CROSSRUN
CABLE CONNECTOR
NO. A50 ALUMINUM CABLE
NO. A50 ALUMINUM CABLE
NO. A309 CABLE CONNECTOR
NO. A50 ALUMINUM CABLE
NO. A50 ALUMINUM CABLE
NO. A50 ALUMINUM CABLE
NO. A50 ALUMINUM CABLE
R 8"
90°
BEND RADIUS DETAIL
NOTE:
NO BEND OF A CONDUCTOR SHALL FORM
AN INCLUDED ANGLE OF LESS THAN 90 DEGREES,
NOR SHALL IT HAVE A RADIUS
OF BEND LESS THAN 203mm (8").
4 TO 1 CONDUCTOR DETAIL
NOTE: CONDUCTOR SHALL INTERCONNECT ALL
AIR TERMINALS AND SHALL FORM A TWO-WAY
PATH FROM EACH AIR TERMINAL HORIZONTALLY,
DOWNWARD OR RISING AT A RATE NOT
EXCEEDING 3" PER FOOT (76.2mm) TO
CONNECTIONS WITH GROUND TERMINALS
FASTEN CABLE 3'-0" O.C.
MAX, WITH
APPROPRIATE CABLE
FASTENER.
1 2
NO. A5818ST ALUMINUM AIR TERMINAL (5/8" X 18")
NO. A250 ALUMINUM BASE SECURED
WITH FOUR NO. S725 STAINLESS
STEEL SELF-DRILLING SCREWS
NO. A404 ALUMINUM BONDING
CLAMP SECURED WITH TWO
NO. S725 STAINLESS STEEL
SELF-DRILLING SCREWS
NO. A55 ALUMINUM CABLE
TO PARALLEL SPLICER
NO. A210 TOP MOUNT EQUIPMENT BASE SECURED
WITH TWO NO. S725 STAINLESS STEEL
SELF-DRILLING SCREWS
NO. A55 ALUMINUM CABLE SECURED TO UNIT
WITH NO. A702 ALUMINUM LOOP AND NO. S725
STAINLESS STEEL SELF-DRILLING SCREWS
36" O.C. MAXIMUM SPACING
CONNECT TO ROOF CIRCUIT WITH
NO. A309 PARALLEL SPLICER
NO. A5818ST ALUMINUM AIR TERMINAL (5/8" X 18")
NOTE: AIR TERMINALS MUST BE WITHIN
TWO FEET (2') OF OUTSIDE CORNERS
NOTE: CABLE ROUTED AND CONNECTED
TO NEAREST ROOF CIRCUIT
NOTE: CABLE SHALL BE ROUTED AND CONNECTED TO
NEAREST ROOF CIRCUIT. LENGTH OF CABLE SHALL NOT
EXCEED EIGHT FEET (8') OR TWO CABLES WILL BE
REQUIRED FROM THE AIR TERMINAL TO THE ROOF CIRCUIT.
NO. A5818ST ALUMINUM AIR
TERMINAL (5/8" X 18”)
NO. A250 ALUMINUM BASE SECURED
WITH FOUR NO. S725 STAINLESS
STEEL SELF-DRILLING SCREWS
NO. A404 ALUMINUM BONDING CLAMP
SECURED WITH TWO NO. S725 STAINLESS
STEEL SELF-DRILLING SCREWS
NO. A55 ALUMINUM CABLE
TO PARALLEL SPLICER
NOTE: TOP OF UNIT MUST BE MORE THAN
400 SQUARE INCHES OR 1000 CUBIC INCHES
FOR THIS APPLICATION
NOTE: FIELD VERIFY CORRECT APPLICATION
WARNING NOTE
IT IS THE RESPONSIBILITY OF THE LIGHTNING PROTECTION
INSTALLER TO COORDINATE WITH THE MECHANICAL EQUIPMENT
CONTRACTOR AND FIELD VERIFY APPROVED LOCATIONS PRIOR
TO INSTALLATION OF LIGHTNING PROTECTION COMPONENT
FASTENERS FOR ANY DRILLING OR PUNCHING OF HOLES WHICH
MAY BE REQUIRED FOR THE INSTALLATION OF FASTENERS, SO
AS NOT TO DAMAGE INTERNAL PIPING SYSTEMS, WIRING
SYSTEMS OR THE OPERATION/FUNCTION OF THE EQUIPMENT.
NOTE: TOP OF UNIT MUST BE LESS THAN
400 SQUARE INCHES OR 1000 CUBIC INCHES
FOR THIS APPLICATION
NO. A5824ST ALUMINUM AIR
TERMINAL (5/8" X 24")
NO. A54 COPPER CABLE SECURED
WITH NO. A712 ADHESIVE CABLE
HOLDER AND APPROVED ADHESIVE
36" O.C. MAXIMUM SPACING
NO. A220 ADHESIVE BASE AND
SECURED WITH APPROVED ADHESIVE
Air terminals must be located within 2 feet of the roof edge
(where applicable)
TYPICAL HEADWALL AIR TERMINAL, BASE AND CABLE HOLDER A
NO. C56 - 19 COPPER CABLE
NO. C56 - 19 COPPER CABLE
NO. C56 - 19 COPPER CABLE
NO. C55 COPPER
LIGHTNING CONDUCTOR
TYPICAL EXPOSED HEADWALL DOWNLEAD TO GROUND AND COUNTERPOISEH
NO. C313 HEAV Y DUTY CAST STRAIGHT SPLICER
NOT AT EVERY DOWNLEAD
TYPICALAIR TERMINAL MAST AND CABLE HOLDER B
PART NO. C1224ST (1/2” X 24”) COPPER AIR TERMINAL SAFETY TIPPED
PART NO. SRDT15011 1.5” OD 11 GAUAGE
304 STAINLESS STEEL TUBING EXTENDING
4’ ABOVE HEADWALL OR REAR VENTILATOR.
PART NO. C24112 BRONZE SIDE MOUNT AIR TERMINAL BASE
V