Attachment 2 Drawings.pdf

PDF 28 MB Posted

Attached to
REPAIR REPLACE OVERHEAD DOORS ASP BLDG'S 55294 & 55298 Federal contract opportunity
Solicitation number
FA500022Q0087
Issued by
Department of the Air Force Pacific Air Forces

View the file

Other files for this federal contract opportunity

Other files attached to REPAIR REPLACE OVERHEAD DOORS ASP BLDG'S 55294 & 55298, newest first.
File Type Posted
Attachment 1 Statement of Work- Updated 20220923.pdf PDF
Questions and Answers.pdf PDF
Solicitation Amendment FA500022Q00870002 SF 30.pdf PDF
Solicitation - FA500022Q0087.pdf PDF
Attachment 1 Statement of Work.pdf PDF
Solicitation Amendment FA500022Q00870001 SF 30.pdf PDF
Wage Determination.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MAP KEY

LOCATION DESCRIPTION

RICHARDSON VISITORS GATE

ARCTIC VALLEY GATE GLENN HWY SOUTHBOUND EXIT

ELMENDORF VISITORS GATE

654 6TH STREET: FIRE STATION 4

8517 20TH STREET: SECURITY FORCES

CLEAN FILL LANDFILL SITE

CONCRETE LANDFILL SITE

BUILDING 55294 AND 55298

JOINT BASE ELMENDORF-RICHARDSON

673RD CIVIL ENGINEER SQUADRON

KEY PLAN

NOT FOR CONSTRUCTION

A B C D E F G H I

SHEET

REFERENCE

NUMBER

AF PROJECT NUMBER:

AEC FILE NAME:

DRAWING SCALE:

PLOT SCALE:

SYMBOL DATE DESCRIPTION

REVISIONS

JOINT BASE ELMENDORF-RICHARDSON, AK

DESIGNED BY:

DRAWN BY:

CHECKED BY:

PROJ. ENG.

LOCATION

DRAWINGS

1:1

AF CONTRACT NUMBER:

INV. NUMBER:

DATE APPR

DATE:

DATE:

DATE:

DATE:

DRAWING NO:

U.S. AIR FORCE

02 JUN 2022

06/02/2022

06/02/2022

N

Repair Replace Overhead Doors ASP B55294, 55298

HJZH 22-1033

ANSI

D

AND

EXHIBIT

C-1

SCHEDULE OF DRAWINGS

SHEET NUMBER SHEET TITLE

C-1 COVER SHEET

C-2 LOCATION MAP

3-8 FACILITY EXHIBIT DRAWINGS

6-13 LPS EXHIBIT DRAWINGS

1. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS.

2. AT NO TIME WILL THE CONTRACTORS WORK, STORAGE OF MATERIALS, PARKING OF VEHICLES OR OTHER ACTIVITIES BE ALLOWED TO INTERFERE WITH THE WORK ACTIVITIES OF GOVERNMENT PERSONNEL OR TO DAMAGE GOVERNMENT OR PRIVATE PROPERTY.

3. THE CONTRACTOR SHALL AT ALL TIMES KEEP THE WORK AREA FREE FROM ACCUMULATION OF WASTE MATERIALS. DEBRIS SHALL BE REMOVED ON A DAILY

BASIS.

4. ALL WELDING AND / OR THE USE OF FLAME PRODUCING DEVICES SHALL BE CLEARED THROUGH THE FIRE DEPARTMENT.

5. ALL CONSTRUCTION PERMITS, FEES AND COORDINATION OF ANCILLARY ITEMS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

6. THE WORK OF THIS CONTRACT SHALL COMPLY WITH APPLICABLE FEDERAL, STATE AND LOCAL CODES OR STANDARDS, INCLUDING BUT NOT LIMITED TO:

ENVIRONMENTAL PROTECTION AGENCY, NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE, NATIONAL FIRE PROTECTION ASSOCIATION, OSHA

STANDARDS, FIRE CODES, INTERNATIONAL BUILDING CODE.

PROJECT NOTES:

COVER SHEET

PROJECT LOCATION

LOCATION 1

LOCATION 2

BLDG 55300

A B C D E F G H I

SHEET

REFERENCE

NUMBER

AF PROJECT NUMBER:

AEC FILE NAME:

DRAWING SCALE:

PLOT SCALE:

SYMBOL DATE DESCRIPTION

REVISIONS

JOINT BASE ELMENDORF-RICHARDSON, AK

DESIGNED BY:

DRAWN BY:

CHECKED BY:

PROJ. ENG.

LOCATION

DRAWINGS

1:1

AF CONTRACT NUMBER:

INV. NUMBER:

DATE APPR

DATE:

DATE:

DATE:

DATE:

DRAWING NO:

U.S. AIR FORCE

02 JUN 2022

06/02/2022

06/02/2022

N

Repair Replace Overhead Doors ASP B55294, 55298

HJZH 22-1033

ANSI

D

AND

EXHIBIT

AERIAL MAP

C-2

LADUE DR

BLDG 55294

BLDG 55298

EXHIBIT DRAWING

PRO

L P I TECTIONLI

G

HT

N ING

ITSNI

T U TE

MEM BER

Lowell Hart

CHECKED BY:

REVISED DATE:

SCALE:

SHEET:

DATE:

DRAWN BY:

DWG. NO.

EVALUATION:

AZ-2017-0220

JLH

20TH FEBRUARY 2017

AS SHOWN

ORIGINAL SIZE: 30" X 42"NO. DATE DESCRIPTION OF REVISION BY

Project Name and Location

Materials By:

Preferred Lightning Protection

2100 East First Street Maryville, MO 64468

Phone: 866-299-7406 or 660-562-2771

Fax: 660-582-2603 U.L. Listing E236181

L.P.I. Manufacturing Member

Design and Installation by:

CONDUCTOR BEND SHALL NOT FORM A SHARPER ANGLE THAN 90 DEGREES OR HAVE A RADIUS LESS THAN 8

INCHES.

ISOLATED METAL BODIES THAT SHOW NO CONDUCTANCE TO GROUND SHALL NOT REQUIRE BONDING. A

GROUNDED METAL BODY WITHIN THE SIX FOOT RULE SHALL BE BONDED TO THE SYSTEM.

AIR TERMINAL SHALL BE PLACED AT THE LOCATIONS INDICATED, NOT MORE THAN 2'-0" FROM THE ENDS OF RIDGES, OUTSIDE CORNERS, OR OUTSIDE EDGES OF MAIN ROOFS AND MUST EXTEND A MINIMUM OF 10"

ABOVE OBJECT TO BE PROTECTED.

MIDROOF AIR TERMINALS SHALL BE SPACED AT 50'-0" O.C. MAXIMUM SPACING.

JOB CONDITIONS MAY DICTATE VARIATIONS IN AIR TERMINAL, CONDUCTORS AND GROUND ROD LOCATIONS.

CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD PATH FREE FROM "U" AND "V" POCKETS. ANY

RISE IN HORIZONTAL CONDUCTOR SHALL NOT EXCEED 8 INCHES.

CABLE MAY RISE UPWARDS AT A RATE OF 3" OF RISE PER 1'-0" RUN MAXIMUM.

COPPER LIGHTNING PROTECTION MATERIALS SHALL NOT BE PLACED ON ALUMINUM, GALVANIZED STEEL, GALVALUME SURFACES OR ANY OTHER DISSIMILAR METAL SURFACES, PAINTED OR NOT, NOR SHALL

ALUMINUM MATERIALS BE PLACED ON COPPER SURFACES.

FOR THE SAKE OF CLARITY WE HAVE NOT CALLED OUT EACH INDIVIDUAL ITEM OF LIGHTNING PROTECTION MATERIALS ON THE ROOF PLAN. WE HAVE SHOWN TYPICAL DETAILS AND HAVE CALLED OUT EACH OF THESE

DETAILS ON THE ROOF PLAN, ONLY IN SCATTERED LOCATIONS.

ALL STRUCTURAL STEEL, REBAR, FRAMING & MISCELLANEOUS STEEL SHALL BE MADE ELECTRICALLY CONTINUOUS THROUGH CONSTRUCTION (NOT THE RESPONSIBILITY OF THE LIGHTNING PROTECTION

CONTRACTOR).

ELECTRIC, TELEPHONE AND ANTENNA SYSTEM GROUNDS SHALL BE CONNECTED WITH MAIN SIZE CONDUCTOR

TO ONE LIGHTNING PROTECTION GROUND OR METAL WATER PIPE.

A LIGHTNING ARRESTOR, PROTECTOR, OR ANTENNA-DISCHARGE UNIT MUST BE INSTALLED ON EACH ELECTRIC AND TELEPHONE SERVICE ENTRANCE AND RADIO AND TELEVISION ANTENNA LEAD IN. (TO BE PROVIDED BY

ELECTRICAL CONTRACTOR.)

ALL ADHESIVE FIXTURES SHALL BE SET WITH AN ADHESIVE COMPOUND COMPATIBLE WITH THE ROOFING

MATERIAL. ADHESIVES SHALL BE APPROVED IN ADVANCE BY THE ROOFING CONTRACTOR.

BOND ALL METAL PIPES SUCH AS WATER, GAS, FIRE, STORM, SEWER WHICH ENTER THE STRUCTURE TO THE

NEAREST DOWNLEAD, GROUND ROD OR COUNTERPOISE.

CABLE WILL BE FASTENED EVERY 3'-0" O.C. MAXIMUM SPACING.

PERIMETER AND RIDGE AIR TERMINALS 10" TO 23" WILL BE SPACED UP TO 20' MAXIMUM. AIR TERMINALS 24" AND

OVER WILL BE SPACED 25' MAXIMUM.

CONNECTIONS TO GROUND AND/OR COUNTERPOISE SHALL BE MADE AT A POINT NOT LESS THAN 1'-0" BELOW

GRADE, AND 2'-0" AWAY FROM FOUNDATION WALL.

LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED IN A NEAT, PROFESSIONAL MANNER.

ON EXTERIOR WALLS OF BLOCK OR BRICK, DOWNLEAD CABLES SHALL BE ANCHORED IN THE BLOCK OR BRICK, NOT IN MORTAR.

NOTE: ALL ROOF AREAS ILLUSTRATED ON THESE SUBMITTAL DRAWINGS WHICH HAVE NOT BEEN

PROVIDED WITH LIGHTNING PROTECTION COMPONENTS ARE PROTECTED FROM HIGHER ROOFS OR

STRUCTURES. THESE AREAS FALL WITHIN A "ZONE OF PROTECTION" AS ESTABLISHED BY THE

CURRENT EDITION OF THE STANDARD FOR PROTECTION AGAINST LIGHTNING "ANSI/NFPA 780" AND

THE INSTALLATION REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS AS PROVIDED BY

STANDARD 96A OF UNDERWRITERS' LABORATORIES.

NOTE: INSTALLING CONTRACTOR TO FIELD VERIFY ACTUAL TYPES, LOCATIONS, NUMBERS OF

ROOFTOP OBSTRUCTION LIGHTS, AREAWAY LIGHTS, AND ANY SIMILAR LIGHTING FIXTURES WHICH

MAY PROJECT ABOVE BUILDING ROOF EDGES OR PARAPET WALLS AND ALSO ALL MECHANICAL

EQUIPMENT SUCH AS EXHAUST FANS, FLUES, COOLING TOWERS, CHILLERS, CONDENSING UNITS, ROOFTOP AIR HANDLING UNITS, ETC. AND PROTECT BY CORRECT APPLICATION SHOWN IN DETAIL

"F" UNLESS ITEMS OF EQUIPMENT ARE UNDER ZONE OF PROTECTION BY ADJACENT HIGHER

PROTECTED ROOF LEVELS.

NOTE: THIS LIGHTNING PROTECTION LAYOUT DRAWING IS BASED UPON THE MOST CURRENT

CONTRACT DRAWINGS AND INFORMATION AVAILABLE. THE ACTUAL SYSTEM LAYOUT, CHOICE OF AIR

TERMINAL/CABLE MOUNTING AND ROUTING METHODS, THRU-ROOF AND DOWNLEAD/GROUNDING

LOCATIONS, BONDING REQUIREMENTS, ETC., MAY VARY ACCORDING TO THE FINAL DESIGN OF THE BUILDING. LIGHTNING PROTECTION INSTALLER MUST FIELD VERIFY THE ACTUAL CONDITIONS OF THE

BUILDING(S) TO DETERMINE THE PROTECTION LEVEL NEEDED AND MAKE ANY ADJUSTMENTS,

UPWARD OR DOWNWARD, AS REQUIRED FOR U.L. 96-96A COMPLIANCE AND CERTIFICATION.

NOTE: INSTALLING CONTRACTOR SHALL, PER GENERAL NOTE #2 AND DETAILS "G" AND "H", FIELD VERIFY ACTUAL TYPES AND LOCATIONS OF ROOF LOCATED METAL BODIES SUCH AS SUNSHADES, LADDERS, ROOF HATCHES, SMOKE HATCHES, SCUPPERS, ROOF DRAINS, CAMERAS, WINDOW

WASHING TIEBACKS, PHOTO CELLS, SOIL VENT PIPES, ETC., WHICH MAY REQUIRE BONDING. BOND IF WITHIN 6'-0" OF A LIGHTNING PROTECTION CONDUCTOR OR IF WITHIN 6'-0" OF AN ITEM WHICH HAS ALREADY BEEN BONDED BY THE 6' RULE. UTILIZE THE PROPER APPLICATION OF PLATE, CLAMP, LUG, ETC., TO THE SURFACE/SHAPE OF THE OBJECT TO BE BONDED.

NOTE: ALUMINUM LIGHTNING PROTECTION MATERIALS ARE REQUIRED TO BE UTILIZED ON ALL

BUILDING ROOF LEVELS FOR METALS COMPATIBILITY WITH GALVANIZED STEEL, GALVALUME AND

ALUMINUM SHEET METAL COPINGS, GRAVEL STOPS, ROOF AND WALL PANELS, FLASHINGS AND

EQUIPMENT HOUSINGS, ETC. THE ALUMINUM LIGHTNING PROTECTION MATERIALS AS BID AND

ILLUSTRATED ON THESE SHOP DRAWINGS ARE REQUIRED FOR UL 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATIONS AND TO MAINTAIN THE INTEGRITY OF ROOFING SHEET METAL MATERIALS

AGAINST DAMAGE AND POTENTIAL ROOF SYSTEM FAILURES.

LIGHTNING PROTECTION AND GROUNDING SYSTEM

Phone: 623.845.1094 Fax: 623.845.1093 Website: www.hart-assoc.com

HART & ASSOCIATES INC.

3803 NORTH 36TH AVENUE

PHOENIX, ARIZONA 85019

TEST WELL LOCATION

LP 100

NOTE: THE DESIGN & DETAILS SHOWN WILL MEET THE REQUIREMENTS OF

UNDERWRITERS LABORATORY STANDARD 96A, NATIONAL FIRE PROTECTION ASSOCIATION CODE 780

& THE LIGHTNING PROTECTION INSTITUTE STANDARD 175 FOR LIGHTNING PROTECTION SYSTEMS.

LHH

REPAIR AMMO AREA LIGHTNING PROTECTION

JBER, ALASKA

PROJECT NUMBER: HJZH161046

Master Installer # 1443

U.L. Listing E104704

EST. 1965

BUILDING NO. 55294

#A54 ALUMINUM LIGHTNING PROTECTION

CONDUCTOR

DOWNLEAD LOCATION 1” PVC CONDUIT

UL LISTED/RATED SCHEDULE 80

3/4” X 10’ COPPER CLAD GROUND ROD LOCATION

5/8” X 24” ALUMINUM AIR TERMINAL AND

ALUMINUM BASE

2/0 BARE COPPER GROUND RING/COUNTERPOISE

GROUNDING SYSTEM

LO

A

D

IN

G D

O

CK

LO

A

D

IN

G D

O

CK

LO

A

D

IN

G D

O

CK

65’-4” 10’-00”

’-8

LP300

TYP

V

LP300

TYP

A

LP300

TYP

H

LIGHTNING PROTECTION SYSTEM BASIS OF

DESIGN:

STANDARD: 2014 NFPA 780

STRIKING DISTANCE: 100'

GROUND RING: APPROX. 385’ of 2/0 BARE COPPER CLASS 2

NUMBER OF DOWN CONDUCTORS: 4

AIR TERMINALS: 1/2"X24" COPPER. 3 TOTAL

G

HT

N ING

ITSNI

T U TE

MEM BER

Lowell Hart

CHECKED BY:

REVISED DATE:

SCALE:

SHEET:

DATE:

DRAWN BY:

DWG. NO.

EVALUATION:

AZ-2017-0220

JLH

20TH FEBRUARY 2017

AS SHOWN

ORIGINAL SIZE: 30" X 42"NO. DATE DESCRIPTION OF REVISION BY

Project Name and Location

Materials By:

Preferred Lightning Protection

2100 East First Street Maryville, MO 64468

Phone: 866-299-7406 or 660-562-2771

Fax: 660-582-2603 U.L. Listing E236181

L.P.I. Manufacturing Member

Design and Installation by:

CONDUCTOR BEND SHALL NOT FORM A SHARPER ANGLE THAN 90 DEGREES OR HAVE A RADIUS LESS THAN 8

INCHES.

ISOLATED METAL BODIES THAT SHOW NO CONDUCTANCE TO GROUND SHALL NOT REQUIRE BONDING. A

GROUNDED METAL BODY WITHIN THE SIX FOOT RULE SHALL BE BONDED TO THE SYSTEM.

AIR TERMINAL SHALL BE PLACED AT THE LOCATIONS INDICATED, NOT MORE THAN 2'-0" FROM THE ENDS OF RIDGES, OUTSIDE CORNERS, OR OUTSIDE EDGES OF MAIN ROOFS AND MUST EXTEND A MINIMUM OF 10"

ABOVE OBJECT TO BE PROTECTED.

MIDROOF AIR TERMINALS SHALL BE SPACED AT 50'-0" O.C. MAXIMUM SPACING.

JOB CONDITIONS MAY DICTATE VARIATIONS IN AIR TERMINAL, CONDUCTORS AND GROUND ROD LOCATIONS.

CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD PATH FREE FROM "U" AND "V" POCKETS. ANY

RISE IN HORIZONTAL CONDUCTOR SHALL NOT EXCEED 8 INCHES.

CABLE MAY RISE UPWARDS AT A RATE OF 3" OF RISE PER 1'-0" RUN MAXIMUM.

COPPER LIGHTNING PROTECTION MATERIALS SHALL NOT BE PLACED ON ALUMINUM, GALVANIZED STEEL, GALVALUME SURFACES OR ANY OTHER DISSIMILAR METAL SURFACES, PAINTED OR NOT, NOR SHALL

ALUMINUM MATERIALS BE PLACED ON COPPER SURFACES.

FOR THE SAKE OF CLARITY WE HAVE NOT CALLED OUT EACH INDIVIDUAL ITEM OF LIGHTNING PROTECTION MATERIALS ON THE ROOF PLAN. WE HAVE SHOWN TYPICAL DETAILS AND HAVE CALLED OUT EACH OF THESE

DETAILS ON THE ROOF PLAN, ONLY IN SCATTERED LOCATIONS.

ALL STRUCTURAL STEEL, REBAR, FRAMING & MISCELLANEOUS STEEL SHALL BE MADE ELECTRICALLY CONTINUOUS THROUGH CONSTRUCTION (NOT THE RESPONSIBILITY OF THE LIGHTNING PROTECTION

CONTRACTOR).

ELECTRIC, TELEPHONE AND ANTENNA SYSTEM GROUNDS SHALL BE CONNECTED WITH MAIN SIZE CONDUCTOR

TO ONE LIGHTNING PROTECTION GROUND OR METAL WATER PIPE.

A LIGHTNING ARRESTOR, PROTECTOR, OR ANTENNA-DISCHARGE UNIT MUST BE INSTALLED ON EACH ELECTRIC AND TELEPHONE SERVICE ENTRANCE AND RADIO AND TELEVISION ANTENNA LEAD IN. (TO BE PROVIDED BY

ELECTRICAL CONTRACTOR.)

ALL ADHESIVE FIXTURES SHALL BE SET WITH AN ADHESIVE COMPOUND COMPATIBLE WITH THE ROOFING

MATERIAL. ADHESIVES SHALL BE APPROVED IN ADVANCE BY THE ROOFING CONTRACTOR.

BOND ALL METAL PIPES SUCH AS WATER, GAS, FIRE, STORM, SEWER WHICH ENTER THE STRUCTURE TO THE

NEAREST DOWNLEAD, GROUND ROD OR COUNTERPOISE.

CABLE WILL BE FASTENED EVERY 3'-0" O.C. MAXIMUM SPACING.

PERIMETER AND RIDGE AIR TERMINALS 10" TO 23" WILL BE SPACED UP TO 20' MAXIMUM. AIR TERMINALS 24" AND

OVER WILL BE SPACED 25' MAXIMUM.

CONNECTIONS TO GROUND AND/OR COUNTERPOISE SHALL BE MADE AT A POINT NOT LESS THAN 1'-0" BELOW

GRADE, AND 2'-0" AWAY FROM FOUNDATION WALL.

LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED IN A NEAT, PROFESSIONAL MANNER.

ON EXTERIOR WALLS OF BLOCK OR BRICK, DOWNLEAD CABLES SHALL BE ANCHORED IN THE BLOCK OR BRICK, NOT IN MORTAR.

NOTE: ALL ROOF AREAS ILLUSTRATED ON THESE SUBMITTAL DRAWINGS WHICH HAVE NOT BEEN

PROVIDED WITH LIGHTNING PROTECTION COMPONENTS ARE PROTECTED FROM HIGHER ROOFS OR

STRUCTURES. THESE AREAS FALL WITHIN A "ZONE OF PROTECTION" AS ESTABLISHED BY THE

CURRENT EDITION OF THE STANDARD FOR PROTECTION AGAINST LIGHTNING "ANSI/NFPA 780" AND

THE INSTALLATION REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS AS PROVIDED BY

STANDARD 96A OF UNDERWRITERS' LABORATORIES.

NOTE: INSTALLING CONTRACTOR TO FIELD VERIFY ACTUAL TYPES, LOCATIONS, NUMBERS OF

ROOFTOP OBSTRUCTION LIGHTS, AREAWAY LIGHTS, AND ANY SIMILAR LIGHTING FIXTURES WHICH

MAY PROJECT ABOVE BUILDING ROOF EDGES OR PARAPET WALLS AND ALSO ALL MECHANICAL

EQUIPMENT SUCH AS EXHAUST FANS, FLUES, COOLING TOWERS, CHILLERS, CONDENSING UNITS, ROOFTOP AIR HANDLING UNITS, ETC. AND PROTECT BY CORRECT APPLICATION SHOWN IN DETAIL

"F" UNLESS ITEMS OF EQUIPMENT ARE UNDER ZONE OF PROTECTION BY ADJACENT HIGHER

PROTECTED ROOF LEVELS.

NOTE: THIS LIGHTNING PROTECTION LAYOUT DRAWING IS BASED UPON THE MOST CURRENT

CONTRACT DRAWINGS AND INFORMATION AVAILABLE. THE ACTUAL SYSTEM LAYOUT, CHOICE OF AIR

TERMINAL/CABLE MOUNTING AND ROUTING METHODS, THRU-ROOF AND DOWNLEAD/GROUNDING

LOCATIONS, BONDING REQUIREMENTS, ETC., MAY VARY ACCORDING TO THE FINAL DESIGN OF THE BUILDING. LIGHTNING PROTECTION INSTALLER MUST FIELD VERIFY THE ACTUAL CONDITIONS OF THE

BUILDING(S) TO DETERMINE THE PROTECTION LEVEL NEEDED AND MAKE ANY ADJUSTMENTS,

UPWARD OR DOWNWARD, AS REQUIRED FOR U.L. 96-96A COMPLIANCE AND CERTIFICATION.

NOTE: INSTALLING CONTRACTOR SHALL, PER GENERAL NOTE #2 AND DETAILS "G" AND "H", FIELD VERIFY ACTUAL TYPES AND LOCATIONS OF ROOF LOCATED METAL BODIES SUCH AS SUNSHADES, LADDERS, ROOF HATCHES, SMOKE HATCHES, SCUPPERS, ROOF DRAINS, CAMERAS, WINDOW

WASHING TIEBACKS, PHOTO CELLS, SOIL VENT PIPES, ETC., WHICH MAY REQUIRE BONDING. BOND IF WITHIN 6'-0" OF A LIGHTNING PROTECTION CONDUCTOR OR IF WITHIN 6'-0" OF AN ITEM WHICH HAS ALREADY BEEN BONDED BY THE 6' RULE. UTILIZE THE PROPER APPLICATION OF PLATE, CLAMP, LUG, ETC., TO THE SURFACE/SHAPE OF THE OBJECT TO BE BONDED.

NOTE: ALUMINUM LIGHTNING PROTECTION MATERIALS ARE REQUIRED TO BE UTILIZED ON ALL

BUILDING ROOF LEVELS FOR METALS COMPATIBILITY WITH GALVANIZED STEEL, GALVALUME AND

ALUMINUM SHEET METAL COPINGS, GRAVEL STOPS, ROOF AND WALL PANELS, FLASHINGS AND

EQUIPMENT HOUSINGS, ETC. THE ALUMINUM LIGHTNING PROTECTION MATERIALS AS BID AND

ILLUSTRATED ON THESE SHOP DRAWINGS ARE REQUIRED FOR UL 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATIONS AND TO MAINTAIN THE INTEGRITY OF ROOFING SHEET METAL MATERIALS

AGAINST DAMAGE AND POTENTIAL ROOF SYSTEM FAILURES.

LIGHTNING PROTECTION AND GROUNDING SYSTEM

Phone: 623.845.1094 Fax: 623.845.1093 Website: www.hart-assoc.com

HART & ASSOCIATES INC.

3803 NORTH 36TH AVENUE

PHOENIX, ARIZONA 85019

LP 200

NOTE: THE DESIGN & DETAILS SHOWN WILL MEET THE REQUIREMENTS OF

UNDERWRITERS LABORATORY STANDARD 96A, NATIONAL FIRE PROTECTION ASSOCIATION CODE 780

& THE LIGHTNING PROTECTION INSTITUTE STANDARD 175 FOR LIGHTNING PROTECTION SYSTEMS.

LHH

REPAIR AMMO AREA LIGHTNING PROTECTION

JBER, ALASKA

PROJECT NUMBER: HJZH161046

Master Installer # 1443

U.L. Listing E104704

EST. 1965

BUILDING NO. 55294

100' RADIUS ROLLING SPHERE

ELEVATION B

ELEVATION A

G

HT

N ING

ITSNI

T U TE

MEM BER

Lowell Hart

CHECKED BY:

REVISED DATE:

SCALE:

SHEET:

DATE:

DRAWN BY:

DWG. NO.

NOTES:

AZ-2017-0220

JLH

20TH FEBRUARY 2017

AS SHOWN

ORIGINAL SIZE: 30" X 42"NO. DATE DESCRIPTION OF REVISION BY

Project Name and Location

Materials By:

Preferred Lightning Protection

2100 East First Street Maryville, MO 64468

Phone: 866-299-7406 or 660-562-2771

Fax: 660-582-2603 U.L. Listing E236181

L.P.I. Manufacturing Member

Design and Installation by:

NOTE: THE DESIGN & DETAILS SHOWN WILL MEET THE REQUIREMENTS OF

UNDERWRITERS LABORATORY STANDARD 96A, NATIONAL FIRE PROTECTION ASSOCIATION CODE 780

& THE LIGHTNING PROTECTION INSTITUTE STANDARD 175 FOR LIGHTNING PROTECTION SYSTEMS.

CONDUCTOR BEND SHALL NOT FORM A SHARPER ANGLE THAN 90 DEGREES OR HAVE A RADIUS LESS THAN 8

INCHES.

ISOLATED METAL BODIES THAT SHOW NO CONDUCTANCE TO GROUND SHALL NOT REQUIRE BONDING. A

GROUNDED METAL BODY WITHIN THE SIX FOOT RULE SHALL BE BONDED TO THE SYSTEM.

AIR TERMINAL SHALL BE PLACED AT THE LOCATIONS INDICATED, NOT MORE THAN 2'-0" FROM THE ENDS OF RIDGES, OUTSIDE CORNERS, OR OUTSIDE EDGES OF MAIN ROOFS AND MUST EXTEND A MINIMUM OF 10"

ABOVE OBJECT TO BE PROTECTED.

MIDROOF AIR TERMINALS SHALL BE SPACED AT 50'-0" O.C. MAXIMUM SPACING.

JOB CONDITIONS MAY DICTATE VARIATIONS IN AIR TERMINAL, CONDUCTORS AND GROUND ROD LOCATIONS.

CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD PATH FREE FROM "U" AND "V" POCKETS. ANY

RISE IN HORIZONTAL CONDUCTOR SHALL NOT EXCEED 8 INCHES.

CABLE MAY RISE UPWARDS AT A RATE OF 3" OF RISE PER 1'-0" RUN MAXIMUM.

COPPER LIGHTNING PROTECTION MATERIALS SHALL NOT BE PLACED ON ALUMINUM, GALVANIZED STEEL, GALVALUME SURFACES OR ANY OTHER DISSIMILAR METAL SURFACES, PAINTED OR NOT, NOR SHALL

ALUMINUM MATERIALS BE PLACED ON COPPER SURFACES.

FOR THE SAKE OF CLARITY WE HAVE NOT CALLED OUT EACH INDIVIDUAL ITEM OF LIGHTNING PROTECTION MATERIALS ON THE ROOF PLAN. WE HAVE SHOWN TYPICAL DETAILS AND HAVE CALLED OUT EACH OF THESE

DETAILS ON THE ROOF PLAN, ONLY IN SCATTERED LOCATIONS.

ALL STRUCTURAL STEEL, REBAR, FRAMING & MISCELLANEOUS STEEL SHALL BE MADE ELECTRICALLY CONTINUOUS THROUGH CONSTRUCTION (NOT THE RESPONSIBILITY OF THE LIGHTNING PROTECTION

CONTRACTOR).

ELECTRIC, TELEPHONE AND ANTENNA SYSTEM GROUNDS SHALL BE CONNECTED WITH MAIN SIZE CONDUCTOR

TO ONE LIGHTNING PROTECTION GROUND OR METAL WATER PIPE.

A LIGHTNING ARRESTOR, PROTECTOR, OR ANTENNA-DISCHARGE UNIT MUST BE INSTALLED ON EACH ELECTRIC AND TELEPHONE SERVICE ENTRANCE AND RADIO AND TELEVISION ANTENNA LEAD IN. (TO BE PROVIDED BY

ELECTRICAL CONTRACTOR.)

ALL ADHESIVE FIXTURES SHALL BE SET WITH AN ADHESIVE COMPOUND COMPATIBLE WITH THE ROOFING

MATERIAL. ADHESIVES SHALL BE APPROVED IN ADVANCE BY THE ROOFING CONTRACTOR.

BOND ALL METAL PIPES SUCH AS WATER, GAS, FIRE, STORM, SEWER WHICH ENTER THE STRUCTURE TO THE

NEAREST DOWNLEAD, GROUND ROD OR COUNTERPOISE.

CABLE WILL BE FASTENED EVERY 3'-0" O.C. MAXIMUM SPACING.

PERIMETER AND RIDGE AIR TERMINALS 10" TO 23" WILL BE SPACED UP TO 20' MAXIMUM. AIR TERMINALS 24" AND

OVER WILL BE SPACED 25' MAXIMUM.

CONNECTIONS TO GROUND AND/OR COUNTERPOISE SHALL BE MADE AT A POINT NOT LESS THAN 1'-0" BELOW

GRADE, AND 2'-0" AWAY FROM FOUNDATION WALL.

LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED IN A NEAT, PROFESSIONAL MANNER.

ON EXTERIOR WALLS OF BLOCK OR BRICK, DOWNLEAD CABLES SHALL BE ANCHORED IN THE BLOCK OR BRICK, NOT IN MORTAR.

NOTE: ALL ROOF AREAS ILLUSTRATED ON THESE SUBMITTAL DRAWINGS WHICH HAVE NOT BEEN

PROVIDED WITH LIGHTNING PROTECTION COMPONENTS ARE PROTECTED FROM HIGHER ROOFS OR

STRUCTURES. THESE AREAS FALL WITHIN A "ZONE OF PROTECTION" AS ESTABLISHED BY THE

CURRENT EDITION OF THE STANDARD FOR PROTECTION AGAINST LIGHTNING "ANSI/NFPA 780" AND

THE INSTALLATION REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS AS PROVIDED BY

STANDARD 96A OF UNDERWRITERS' LABORATORIES.

NOTE: INSTALLING CONTRACTOR TO FIELD VERIFY ACTUAL TYPES, LOCATIONS, NUMBERS OF

ROOFTOP OBSTRUCTION LIGHTS, AREAWAY LIGHTS, AND ANY SIMILAR LIGHTING FIXTURES WHICH

MAY PROJECT ABOVE BUILDING ROOF EDGES OR PARAPET WALLS AND ALSO ALL MECHANICAL

EQUIPMENT SUCH AS EXHAUST FANS, FLUES, COOLING TOWERS, CHILLERS, CONDENSING UNITS, ROOFTOP AIR HANDLING UNITS, ETC. AND PROTECT BY CORRECT APPLICATION SHOWN IN DETAIL

"F" UNLESS ITEMS OF EQUIPMENT ARE UNDER ZONE OF PROTECTION BY ADJACENT HIGHER

PROTECTED ROOF LEVELS.

NOTE: THIS LIGHTNING PROTECTION LAYOUT DRAWING IS BASED UPON THE MOST CURRENT

CONTRACT DRAWINGS AND INFORMATION AVAILABLE. THE ACTUAL SYSTEM LAYOUT, CHOICE OF AIR

TERMINAL/CABLE MOUNTING AND ROUTING METHODS, THRU-ROOF AND DOWNLEAD/GROUNDING

LOCATIONS, BONDING REQUIREMENTS, ETC., MAY VARY ACCORDING TO THE FINAL DESIGN OF THE BUILDING. LIGHTNING PROTECTION INSTALLER MUST FIELD VERIFY THE ACTUAL CONDITIONS OF THE

BUILDING(S) TO DETERMINE THE PROTECTION LEVEL NEEDED AND MAKE ANY ADJUSTMENTS,

UPWARD OR DOWNWARD, AS REQUIRED FOR U.L. 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATION.

NOTE: INSTALLING CONTRACTOR SHALL, PER GENERAL NOTE #2 AND DETAILS "G" AND "H", FIELD VERIFY ACTUAL TYPES AND LOCATIONS OF ROOF LOCATED METAL BODIES SUCH AS SUNSHADES, LADDERS, ROOF HATCHES, SMOKE HATCHES, SCUPPERS, ROOF DRAINS, CAMERAS, WINDOW

WASHING TIEBACKS, PHOTO CELLS, SOIL VENT PIPES, ETC., WHICH MAY REQUIRE BONDING. BOND IF WITHIN 6'-0" OF A LIGHTNING PROTECTION CONDUCTOR OR IF WITHIN 6'-0" OF AN ITEM WHICH HAS ALREADY BEEN BONDED BY THE 6' RULE. UTILIZE THE PROPER APPLICATION OF PLATE, CLAMP, LUG, ETC., TO THE SURFACE/SHAPE OF THE OBJECT TO BE BONDED.

NOTE: ALUMINUM LIGHTNING PROTECTION MATERIALS ARE REQUIRED TO BE UTILIZED ON ALL

BUILDING ROOF LEVELS FOR METALS COMPATIBILITY WITH GALVANIZED STEEL, GALVALUME AND

ALUMINUM SHEET METAL COPINGS, GRAVEL STOPS, ROOF AND WALL PANELS, FLASHINGS AND

EQUIPMENT HOUSINGS, ETC. THE ALUMINUM LIGHTNING PROTECTION MATERIALS AS BID AND

ILLUSTRATED ON THESE SHOP DRAWINGS ARE REQUIRED FOR UL 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATIONS AND TO MAINTAIN THE INTEGRITY OF ROOFING SHEET METAL MATERIALS

AGAINST DAMAGE AND POTENTIAL ROOF SYSTEM FAILURES.

DETAILS

HART & ASSOCIATES INC.

3803 NORTH 36TH AVENUE

PHOENIX,ARIZONA 85019

Phone: 623.845.1094 Fax: 623.845.1093 Website: www.hart-assoc.com

LP 300

REPAIR AMMO AREA LIGHTNING PROTECTION

JBER, ALASKA

PROJECT NUMBER: HJZH161046

LHH

Master Installer # 1443

U.L. Listing E104704

EST. 1965

NO. A325 TEE TYPE

CABLE CONNECTOR

NO. C309 CABLE CONNECTOR

NO. A320 BIMETALLIC CONNECTOR

NO. C50 COPPER CABLE

NO. C50 COPPER CABLE

NO. A50 ALUMINUM CABLE

NO. A327 CROSSRUN

CABLE CONNECTOR

NO. A50 ALUMINUM CABLE

NO. A50 ALUMINUM CABLE

NO. A309 CABLE CONNECTOR

NO. A50 ALUMINUM CABLE

NO. A50 ALUMINUM CABLE

NO. A50 ALUMINUM CABLE

NO. A50 ALUMINUM CABLE

R 8"

90°

BEND RADIUS DETAIL

NOTE:

NO BEND OF A CONDUCTOR SHALL FORM

AN INCLUDED ANGLE OF LESS THAN 90 DEGREES,

NOR SHALL IT HAVE A RADIUS

OF BEND LESS THAN 203mm (8").

4 TO 1 CONDUCTOR DETAIL

NOTE: CONDUCTOR SHALL INTERCONNECT ALL

AIR TERMINALS AND SHALL FORM A TWO-WAY

PATH FROM EACH AIR TERMINAL HORIZONTALLY,

DOWNWARD OR RISING AT A RATE NOT

EXCEEDING 3" PER FOOT (76.2mm) TO

CONNECTIONS WITH GROUND TERMINALS

FASTEN CABLE 3'-0" O.C.

MAX, WITH

APPROPRIATE CABLE

FASTENER.

1 2

NO. A5818ST ALUMINUM AIR TERMINAL (5/8" X 18")

NO. A250 ALUMINUM BASE SECURED

WITH FOUR NO. S725 STAINLESS

STEEL SELF-DRILLING SCREWS

NO. A404 ALUMINUM BONDING

CLAMP SECURED WITH TWO

NO. S725 STAINLESS STEEL

SELF-DRILLING SCREWS

NO. A55 ALUMINUM CABLE

TO PARALLEL SPLICER

NO. A210 TOP MOUNT EQUIPMENT BASE SECURED

WITH TWO NO. S725 STAINLESS STEEL

SELF-DRILLING SCREWS

NO. A55 ALUMINUM CABLE SECURED TO UNIT

WITH NO. A702 ALUMINUM LOOP AND NO. S725

STAINLESS STEEL SELF-DRILLING SCREWS

36" O.C. MAXIMUM SPACING

CONNECT TO ROOF CIRCUIT WITH

NO. A309 PARALLEL SPLICER

NO. A5818ST ALUMINUM AIR TERMINAL (5/8" X 18")

NOTE: AIR TERMINALS MUST BE WITHIN

TWO FEET (2') OF OUTSIDE CORNERS

NOTE: CABLE ROUTED AND CONNECTED

TO NEAREST ROOF CIRCUIT

NOTE: CABLE SHALL BE ROUTED AND CONNECTED TO

NEAREST ROOF CIRCUIT. LENGTH OF CABLE SHALL NOT

EXCEED EIGHT FEET (8') OR TWO CABLES WILL BE

REQUIRED FROM THE AIR TERMINAL TO THE ROOF CIRCUIT.

NO. A5818ST ALUMINUM AIR

TERMINAL (5/8" X 18”)

NO. A250 ALUMINUM BASE SECURED

WITH FOUR NO. S725 STAINLESS

STEEL SELF-DRILLING SCREWS

NO. A404 ALUMINUM BONDING CLAMP

SECURED WITH TWO NO. S725 STAINLESS

STEEL SELF-DRILLING SCREWS

NO. A55 ALUMINUM CABLE

TO PARALLEL SPLICER

NOTE: TOP OF UNIT MUST BE MORE THAN

400 SQUARE INCHES OR 1000 CUBIC INCHES

FOR THIS APPLICATION

NOTE: FIELD VERIFY CORRECT APPLICATION

WARNING NOTE

IT IS THE RESPONSIBILITY OF THE LIGHTNING PROTECTION

INSTALLER TO COORDINATE WITH THE MECHANICAL EQUIPMENT

CONTRACTOR AND FIELD VERIFY APPROVED LOCATIONS PRIOR

TO INSTALLATION OF LIGHTNING PROTECTION COMPONENT

FASTENERS FOR ANY DRILLING OR PUNCHING OF HOLES WHICH

MAY BE REQUIRED FOR THE INSTALLATION OF FASTENERS, SO

AS NOT TO DAMAGE INTERNAL PIPING SYSTEMS, WIRING

SYSTEMS OR THE OPERATION/FUNCTION OF THE EQUIPMENT.

NOTE: TOP OF UNIT MUST BE LESS THAN

400 SQUARE INCHES OR 1000 CUBIC INCHES

FOR THIS APPLICATION

NO. A5824ST ALUMINUM AIR

TERMINAL (5/8" X 24")

NO. A54 COPPER CABLE SECURED

WITH NO. A712 ADHESIVE CABLE

HOLDER AND APPROVED ADHESIVE

36" O.C. MAXIMUM SPACING

NO. A220 ADHESIVE BASE AND

SECURED WITH APPROVED ADHESIVE

Air terminals must be located within 2 feet of the roof edge

(where applicable)

TYPICAL HEADWALL AIR TERMINAL, BASE AND CABLE HOLDER A

NO. C56 - 19 COPPER CABLE

NO. C56 - 19 COPPER CABLE

NO. C56 - 19 COPPER CABLE

NO. C55 COPPER

LIGHTNING CONDUCTOR

TYPICAL EXPOSED HEADWALL DOWNLEAD TO GROUND AND COUNTERPOISEH

NO. C313 HEAV Y DUTY CAST STRAIGHT SPLICER

NOT AT EVERY DOWNLEAD

TYPICALAIR TERMINAL MAST AND CABLE HOLDER B

PART NO. C1224ST (1/2” X 24”) COPPER AIR TERMINAL SAFETY TIPPED

PART NO. SRDT15011 1.5” OD 11 GAUAGE

304 STAINLESS STEEL TUBING EXTENDING

4’ ABOVE HEADWALL OR REAR VENTILATOR.

PART NO. C24112 BRONZE SIDE MOUNT AIR TERMINAL BASE

V

G

HT

N ING

ITSNI

T U TE

MEM BER

Lowell Hart

CHECKED BY:

REVISED DATE:

SCALE:

SHEET:

DATE:

DRAWN BY:

DWG. NO.

EVALUATION:

AZ-2017-0220

JLH

20TH FEBRUARY 2017

AS SHOWN

ORIGINAL SIZE: 30" X 42"NO. DATE DESCRIPTION OF REVISION BY

Project Name and Location

Materials By:

Preferred Lightning Protection

2100 East First Street Maryville, MO 64468

Phone: 866-299-7406 or 660-562-2771

Fax: 660-582-2603 U.L. Listing E236181

L.P.I. Manufacturing Member

Design and Installation by:

CONDUCTOR BEND SHALL NOT FORM A SHARPER ANGLE THAN 90 DEGREES OR HAVE A RADIUS LESS THAN 8

INCHES.

ISOLATED METAL BODIES THAT SHOW NO CONDUCTANCE TO GROUND SHALL NOT REQUIRE BONDING. A

GROUNDED METAL BODY WITHIN THE SIX FOOT RULE SHALL BE BONDED TO THE SYSTEM.

AIR TERMINAL SHALL BE PLACED AT THE LOCATIONS INDICATED, NOT MORE THAN 2'-0" FROM THE ENDS OF RIDGES, OUTSIDE CORNERS, OR OUTSIDE EDGES OF MAIN ROOFS AND MUST EXTEND A MINIMUM OF 10"

ABOVE OBJECT TO BE PROTECTED.

MIDROOF AIR TERMINALS SHALL BE SPACED AT 50'-0" O.C. MAXIMUM SPACING.

JOB CONDITIONS MAY DICTATE VARIATIONS IN AIR TERMINAL, CONDUCTORS AND GROUND ROD LOCATIONS.

CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD PATH FREE FROM "U" AND "V" POCKETS. ANY

RISE IN HORIZONTAL CONDUCTOR SHALL NOT EXCEED 8 INCHES.

CABLE MAY RISE UPWARDS AT A RATE OF 3" OF RISE PER 1'-0" RUN MAXIMUM.

COPPER LIGHTNING PROTECTION MATERIALS SHALL NOT BE PLACED ON ALUMINUM, GALVANIZED STEEL, GALVALUME SURFACES OR ANY OTHER DISSIMILAR METAL SURFACES, PAINTED OR NOT, NOR SHALL

ALUMINUM MATERIALS BE PLACED ON COPPER SURFACES.

FOR THE SAKE OF CLARITY WE HAVE NOT CALLED OUT EACH INDIVIDUAL ITEM OF LIGHTNING PROTECTION MATERIALS ON THE ROOF PLAN. WE HAVE SHOWN TYPICAL DETAILS AND HAVE CALLED OUT EACH OF THESE

DETAILS ON THE ROOF PLAN, ONLY IN SCATTERED LOCATIONS.

ALL STRUCTURAL STEEL, REBAR, FRAMING & MISCELLANEOUS STEEL SHALL BE MADE ELECTRICALLY CONTINUOUS THROUGH CONSTRUCTION (NOT THE RESPONSIBILITY OF THE LIGHTNING PROTECTION

CONTRACTOR).

ELECTRIC, TELEPHONE AND ANTENNA SYSTEM GROUNDS SHALL BE CONNECTED WITH MAIN SIZE CONDUCTOR

TO ONE LIGHTNING PROTECTION GROUND OR METAL WATER PIPE.

A LIGHTNING ARRESTOR, PROTECTOR, OR ANTENNA-DISCHARGE UNIT MUST BE INSTALLED ON EACH ELECTRIC AND TELEPHONE SERVICE ENTRANCE AND RADIO AND TELEVISION ANTENNA LEAD IN. (TO BE PROVIDED BY

ELECTRICAL CONTRACTOR.)

ALL ADHESIVE FIXTURES SHALL BE SET WITH AN ADHESIVE COMPOUND COMPATIBLE WITH THE ROOFING

MATERIAL. ADHESIVES SHALL BE APPROVED IN ADVANCE BY THE ROOFING CONTRACTOR.

BOND ALL METAL PIPES SUCH AS WATER, GAS, FIRE, STORM, SEWER WHICH ENTER THE STRUCTURE TO THE

NEAREST DOWNLEAD, GROUND ROD OR COUNTERPOISE.

CABLE WILL BE FASTENED EVERY 3'-0" O.C. MAXIMUM SPACING.

PERIMETER AND RIDGE AIR TERMINALS 10" TO 23" WILL BE SPACED UP TO 20' MAXIMUM. AIR TERMINALS 24" AND

OVER WILL BE SPACED 25' MAXIMUM.

CONNECTIONS TO GROUND AND/OR COUNTERPOISE SHALL BE MADE AT A POINT NOT LESS THAN 1'-0" BELOW

GRADE, AND 2'-0" AWAY FROM FOUNDATION WALL.

LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED IN A NEAT, PROFESSIONAL MANNER.

ON EXTERIOR WALLS OF BLOCK OR BRICK, DOWNLEAD CABLES SHALL BE ANCHORED IN THE BLOCK OR BRICK, NOT IN MORTAR.

NOTE: ALL ROOF AREAS ILLUSTRATED ON THESE SUBMITTAL DRAWINGS WHICH HAVE NOT BEEN

PROVIDED WITH LIGHTNING PROTECTION COMPONENTS ARE PROTECTED FROM HIGHER ROOFS OR

STRUCTURES. THESE AREAS FALL WITHIN A "ZONE OF PROTECTION" AS ESTABLISHED BY THE

CURRENT EDITION OF THE STANDARD FOR PROTECTION AGAINST LIGHTNING "ANSI/NFPA 780" AND

THE INSTALLATION REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS AS PROVIDED BY

STANDARD 96A OF UNDERWRITERS' LABORATORIES.

NOTE: INSTALLING CONTRACTOR TO FIELD VERIFY ACTUAL TYPES, LOCATIONS, NUMBERS OF

ROOFTOP OBSTRUCTION LIGHTS, AREAWAY LIGHTS, AND ANY SIMILAR LIGHTING FIXTURES WHICH

MAY PROJECT ABOVE BUILDING ROOF EDGES OR PARAPET WALLS AND ALSO ALL MECHANICAL

EQUIPMENT SUCH AS EXHAUST FANS, FLUES, COOLING TOWERS, CHILLERS, CONDENSING UNITS, ROOFTOP AIR HANDLING UNITS, ETC. AND PROTECT BY CORRECT APPLICATION SHOWN IN DETAIL

"F" UNLESS ITEMS OF EQUIPMENT ARE UNDER ZONE OF PROTECTION BY ADJACENT HIGHER

PROTECTED ROOF LEVELS.

NOTE: THIS LIGHTNING PROTECTION LAYOUT DRAWING IS BASED UPON THE MOST CURRENT

CONTRACT DRAWINGS AND INFORMATION AVAILABLE. THE ACTUAL SYSTEM LAYOUT, CHOICE OF AIR

TERMINAL/CABLE MOUNTING AND ROUTING METHODS, THRU-ROOF AND DOWNLEAD/GROUNDING

LOCATIONS, BONDING REQUIREMENTS, ETC., MAY VARY ACCORDING TO THE FINAL DESIGN OF THE BUILDING. LIGHTNING PROTECTION INSTALLER MUST FIELD VERIFY THE ACTUAL CONDITIONS OF THE

BUILDING(S) TO DETERMINE THE PROTECTION LEVEL NEEDED AND MAKE ANY ADJUSTMENTS,

UPWARD OR DOWNWARD, AS REQUIRED FOR U.L. 96-96A COMPLIANCE AND CERTIFICATION.

NOTE: INSTALLING CONTRACTOR SHALL, PER GENERAL NOTE #2 AND DETAILS "G" AND "H", FIELD VERIFY ACTUAL TYPES AND LOCATIONS OF ROOF LOCATED METAL BODIES SUCH AS SUNSHADES, LADDERS, ROOF HATCHES, SMOKE HATCHES, SCUPPERS, ROOF DRAINS, CAMERAS, WINDOW

WASHING TIEBACKS, PHOTO CELLS, SOIL VENT PIPES, ETC., WHICH MAY REQUIRE BONDING. BOND IF WITHIN 6'-0" OF A LIGHTNING PROTECTION CONDUCTOR OR IF WITHIN 6'-0" OF AN ITEM WHICH HAS ALREADY BEEN BONDED BY THE 6' RULE. UTILIZE THE PROPER APPLICATION OF PLATE, CLAMP, LUG, ETC., TO THE SURFACE/SHAPE OF THE OBJECT TO BE BONDED.

NOTE: ALUMINUM LIGHTNING PROTECTION MATERIALS ARE REQUIRED TO BE UTILIZED ON ALL

BUILDING ROOF LEVELS FOR METALS COMPATIBILITY WITH GALVANIZED STEEL, GALVALUME AND

ALUMINUM SHEET METAL COPINGS, GRAVEL STOPS, ROOF AND WALL PANELS, FLASHINGS AND

EQUIPMENT HOUSINGS, ETC. THE ALUMINUM LIGHTNING PROTECTION MATERIALS AS BID AND

ILLUSTRATED ON THESE SHOP DRAWINGS ARE REQUIRED FOR UL 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATIONS AND TO MAINTAIN THE INTEGRITY OF ROOFING SHEET METAL MATERIALS

AGAINST DAMAGE AND POTENTIAL ROOF SYSTEM FAILURES.

LIGHTNING PROTECTION AND GROUNDING SYSTEM

Phone: 623.845.1094 Fax: 623.845.1093 Website: www.hart-assoc.com

HART & ASSOCIATES INC.

3803 NORTH 36TH AVENUE

PHOENIX, ARIZONA 85019

TEST WELL LOCATION

LP 100

NOTE: THE DESIGN & DETAILS SHOWN WILL MEET THE REQUIREMENTS OF

UNDERWRITERS LABORATORY STANDARD 96A, NATIONAL FIRE PROTECTION ASSOCIATION CODE 780

& THE LIGHTNING PROTECTION INSTITUTE STANDARD 175 FOR LIGHTNING PROTECTION SYSTEMS.

LHH

REPAIR AMMO AREA LIGHTNING PROTECTION

JBER, ALASKA

PROJECT NUMBER: HJZH161046

Master Installer # 1443

U.L. Listing E104704

EST. 1965

BUILDING NO. 55298

#A54 ALUMINUM LIGHTNING PROTECTION

CONDUCTOR

DOWNLEAD LOCATION 1” PVC CONDUIT

UL LISTED/RATED SCHEDULE 80

3/4” X 10’ COPPER CLAD GROUND ROD LOCATION

5/8” X 24” ALUMINUM AIR TERMINAL AND

ALUMINUM BASE

2/0 BARE COPPER GROUND RING/COUNTERPOISE

GROUNDING SYSTEM

LO

A

D

IN

G D

O

CK

LO

A

D

IN

G D

O

CK

LO

A

D

IN

G D

O

CK

65’-4” 10’-00”

’-8

LP300

TYP

V

LP300

TYP

A

LP300

TYP

H

LIGHTNING PROTECTION SYSTEM BASIS OF

DESIGN:

STANDARD: 2014 NFPA 780

STRIKING DISTANCE: 100'

GROUND RING: APPROX. 385’ of 2/0 BARE COPPER CLASS 2

NUMBER OF DOWN CONDUCTORS: 4

AIR TERMINALS: 1/2"X24" COPPER. 3 TOTAL

G

HT

N ING

ITSNI

T U TE

MEM BER

Lowell Hart

CHECKED BY:

REVISED DATE:

SCALE:

SHEET:

DATE:

DRAWN BY:

DWG. NO.

EVALUATION:

AZ-2017-0220

JLH

20TH FEBRUARY 2017

AS SHOWN

ORIGINAL SIZE: 30" X 42"NO. DATE DESCRIPTION OF REVISION BY

Project Name and Location

Materials By:

Preferred Lightning Protection

2100 East First Street Maryville, MO 64468

Phone: 866-299-7406 or 660-562-2771

Fax: 660-582-2603 U.L. Listing E236181

L.P.I. Manufacturing Member

Design and Installation by:

CONDUCTOR BEND SHALL NOT FORM A SHARPER ANGLE THAN 90 DEGREES OR HAVE A RADIUS LESS THAN 8

INCHES.

ISOLATED METAL BODIES THAT SHOW NO CONDUCTANCE TO GROUND SHALL NOT REQUIRE BONDING. A

GROUNDED METAL BODY WITHIN THE SIX FOOT RULE SHALL BE BONDED TO THE SYSTEM.

AIR TERMINAL SHALL BE PLACED AT THE LOCATIONS INDICATED, NOT MORE THAN 2'-0" FROM THE ENDS OF RIDGES, OUTSIDE CORNERS, OR OUTSIDE EDGES OF MAIN ROOFS AND MUST EXTEND A MINIMUM OF 10"

ABOVE OBJECT TO BE PROTECTED.

MIDROOF AIR TERMINALS SHALL BE SPACED AT 50'-0" O.C. MAXIMUM SPACING.

JOB CONDITIONS MAY DICTATE VARIATIONS IN AIR TERMINAL, CONDUCTORS AND GROUND ROD LOCATIONS.

CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD PATH FREE FROM "U" AND "V" POCKETS. ANY

RISE IN HORIZONTAL CONDUCTOR SHALL NOT EXCEED 8 INCHES.

CABLE MAY RISE UPWARDS AT A RATE OF 3" OF RISE PER 1'-0" RUN MAXIMUM.

COPPER LIGHTNING PROTECTION MATERIALS SHALL NOT BE PLACED ON ALUMINUM, GALVANIZED STEEL, GALVALUME SURFACES OR ANY OTHER DISSIMILAR METAL SURFACES, PAINTED OR NOT, NOR SHALL

ALUMINUM MATERIALS BE PLACED ON COPPER SURFACES.

FOR THE SAKE OF CLARITY WE HAVE NOT CALLED OUT EACH INDIVIDUAL ITEM OF LIGHTNING PROTECTION MATERIALS ON THE ROOF PLAN. WE HAVE SHOWN TYPICAL DETAILS AND HAVE CALLED OUT EACH OF THESE

DETAILS ON THE ROOF PLAN, ONLY IN SCATTERED LOCATIONS.

ALL STRUCTURAL STEEL, REBAR, FRAMING & MISCELLANEOUS STEEL SHALL BE MADE ELECTRICALLY CONTINUOUS THROUGH CONSTRUCTION (NOT THE RESPONSIBILITY OF THE LIGHTNING PROTECTION

CONTRACTOR).

ELECTRIC, TELEPHONE AND ANTENNA SYSTEM GROUNDS SHALL BE CONNECTED WITH MAIN SIZE CONDUCTOR

TO ONE LIGHTNING PROTECTION GROUND OR METAL WATER PIPE.

A LIGHTNING ARRESTOR, PROTECTOR, OR ANTENNA-DISCHARGE UNIT MUST BE INSTALLED ON EACH ELECTRIC AND TELEPHONE SERVICE ENTRANCE AND RADIO AND TELEVISION ANTENNA LEAD IN. (TO BE PROVIDED BY

ELECTRICAL CONTRACTOR.)

ALL ADHESIVE FIXTURES SHALL BE SET WITH AN ADHESIVE COMPOUND COMPATIBLE WITH THE ROOFING

MATERIAL. ADHESIVES SHALL BE APPROVED IN ADVANCE BY THE ROOFING CONTRACTOR.

BOND ALL METAL PIPES SUCH AS WATER, GAS, FIRE, STORM, SEWER WHICH ENTER THE STRUCTURE TO THE

NEAREST DOWNLEAD, GROUND ROD OR COUNTERPOISE.

CABLE WILL BE FASTENED EVERY 3'-0" O.C. MAXIMUM SPACING.

PERIMETER AND RIDGE AIR TERMINALS 10" TO 23" WILL BE SPACED UP TO 20' MAXIMUM. AIR TERMINALS 24" AND

OVER WILL BE SPACED 25' MAXIMUM.

CONNECTIONS TO GROUND AND/OR COUNTERPOISE SHALL BE MADE AT A POINT NOT LESS THAN 1'-0" BELOW

GRADE, AND 2'-0" AWAY FROM FOUNDATION WALL.

LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED IN A NEAT, PROFESSIONAL MANNER.

ON EXTERIOR WALLS OF BLOCK OR BRICK, DOWNLEAD CABLES SHALL BE ANCHORED IN THE BLOCK OR BRICK, NOT IN MORTAR.

NOTE: ALL ROOF AREAS ILLUSTRATED ON THESE SUBMITTAL DRAWINGS WHICH HAVE NOT BEEN

PROVIDED WITH LIGHTNING PROTECTION COMPONENTS ARE PROTECTED FROM HIGHER ROOFS OR

STRUCTURES. THESE AREAS FALL WITHIN A "ZONE OF PROTECTION" AS ESTABLISHED BY THE

CURRENT EDITION OF THE STANDARD FOR PROTECTION AGAINST LIGHTNING "ANSI/NFPA 780" AND

THE INSTALLATION REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS AS PROVIDED BY

STANDARD 96A OF UNDERWRITERS' LABORATORIES.

NOTE: INSTALLING CONTRACTOR TO FIELD VERIFY ACTUAL TYPES, LOCATIONS, NUMBERS OF

ROOFTOP OBSTRUCTION LIGHTS, AREAWAY LIGHTS, AND ANY SIMILAR LIGHTING FIXTURES WHICH

MAY PROJECT ABOVE BUILDING ROOF EDGES OR PARAPET WALLS AND ALSO ALL MECHANICAL

EQUIPMENT SUCH AS EXHAUST FANS, FLUES, COOLING TOWERS, CHILLERS, CONDENSING UNITS, ROOFTOP AIR HANDLING UNITS, ETC. AND PROTECT BY CORRECT APPLICATION SHOWN IN DETAIL

"F" UNLESS ITEMS OF EQUIPMENT ARE UNDER ZONE OF PROTECTION BY ADJACENT HIGHER

PROTECTED ROOF LEVELS.

NOTE: THIS LIGHTNING PROTECTION LAYOUT DRAWING IS BASED UPON THE MOST CURRENT

CONTRACT DRAWINGS AND INFORMATION AVAILABLE. THE ACTUAL SYSTEM LAYOUT, CHOICE OF AIR

TERMINAL/CABLE MOUNTING AND ROUTING METHODS, THRU-ROOF AND DOWNLEAD/GROUNDING

LOCATIONS, BONDING REQUIREMENTS, ETC., MAY VARY ACCORDING TO THE FINAL DESIGN OF THE BUILDING. LIGHTNING PROTECTION INSTALLER MUST FIELD VERIFY THE ACTUAL CONDITIONS OF THE

BUILDING(S) TO DETERMINE THE PROTECTION LEVEL NEEDED AND MAKE ANY ADJUSTMENTS,

UPWARD OR DOWNWARD, AS REQUIRED FOR U.L. 96-96A COMPLIANCE AND CERTIFICATION.

NOTE: INSTALLING CONTRACTOR SHALL, PER GENERAL NOTE #2 AND DETAILS "G" AND "H", FIELD VERIFY ACTUAL TYPES AND LOCATIONS OF ROOF LOCATED METAL BODIES SUCH AS SUNSHADES, LADDERS, ROOF HATCHES, SMOKE HATCHES, SCUPPERS, ROOF DRAINS, CAMERAS, WINDOW

WASHING TIEBACKS, PHOTO CELLS, SOIL VENT PIPES, ETC., WHICH MAY REQUIRE BONDING. BOND IF WITHIN 6'-0" OF A LIGHTNING PROTECTION CONDUCTOR OR IF WITHIN 6'-0" OF AN ITEM WHICH HAS ALREADY BEEN BONDED BY THE 6' RULE. UTILIZE THE PROPER APPLICATION OF PLATE, CLAMP, LUG, ETC., TO THE SURFACE/SHAPE OF THE OBJECT TO BE BONDED.

NOTE: ALUMINUM LIGHTNING PROTECTION MATERIALS ARE REQUIRED TO BE UTILIZED ON ALL

BUILDING ROOF LEVELS FOR METALS COMPATIBILITY WITH GALVANIZED STEEL, GALVALUME AND

ALUMINUM SHEET METAL COPINGS, GRAVEL STOPS, ROOF AND WALL PANELS, FLASHINGS AND

EQUIPMENT HOUSINGS, ETC. THE ALUMINUM LIGHTNING PROTECTION MATERIALS AS BID AND

ILLUSTRATED ON THESE SHOP DRAWINGS ARE REQUIRED FOR UL 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATIONS AND TO MAINTAIN THE INTEGRITY OF ROOFING SHEET METAL MATERIALS

AGAINST DAMAGE AND POTENTIAL ROOF SYSTEM FAILURES.

LIGHTNING PROTECTION AND GROUNDING SYSTEM

Phone: 623.845.1094 Fax: 623.845.1093 Website: www.hart-assoc.com

HART & ASSOCIATES INC.

3803 NORTH 36TH AVENUE

PHOENIX, ARIZONA 85019

LP 200

NOTE: THE DESIGN & DETAILS SHOWN WILL MEET THE REQUIREMENTS OF

UNDERWRITERS LABORATORY STANDARD 96A, NATIONAL FIRE PROTECTION ASSOCIATION CODE 780

& THE LIGHTNING PROTECTION INSTITUTE STANDARD 175 FOR LIGHTNING PROTECTION SYSTEMS.

LHH

REPAIR AMMO AREA LIGHTNING PROTECTION

JBER, ALASKA

PROJECT NUMBER: HJZH161046

Master Installer # 1443

U.L. Listing E104704

EST. 1965

BUILDING NO. 55298

100' RADIUS ROLLING SPHERE

ELEVATION B

ELEVATION A

G

HT

N ING

ITSNI

T U TE

MEM BER

Lowell Hart

CHECKED BY:

REVISED DATE:

SCALE:

SHEET:

DATE:

DRAWN BY:

DWG. NO.

NOTES:

AZ-2017-0220

JLH

20TH FEBRUARY 2017

AS SHOWN

ORIGINAL SIZE: 30" X 42"NO. DATE DESCRIPTION OF REVISION BY

Project Name and Location

Materials By:

Preferred Lightning Protection

2100 East First Street Maryville, MO 64468

Phone: 866-299-7406 or 660-562-2771

Fax: 660-582-2603 U.L. Listing E236181

L.P.I. Manufacturing Member

Design and Installation by:

NOTE: THE DESIGN & DETAILS SHOWN WILL MEET THE REQUIREMENTS OF

UNDERWRITERS LABORATORY STANDARD 96A, NATIONAL FIRE PROTECTION ASSOCIATION CODE 780

& THE LIGHTNING PROTECTION INSTITUTE STANDARD 175 FOR LIGHTNING PROTECTION SYSTEMS.

CONDUCTOR BEND SHALL NOT FORM A SHARPER ANGLE THAN 90 DEGREES OR HAVE A RADIUS LESS THAN 8

INCHES.

ISOLATED METAL BODIES THAT SHOW NO CONDUCTANCE TO GROUND SHALL NOT REQUIRE BONDING. A

GROUNDED METAL BODY WITHIN THE SIX FOOT RULE SHALL BE BONDED TO THE SYSTEM.

AIR TERMINAL SHALL BE PLACED AT THE LOCATIONS INDICATED, NOT MORE THAN 2'-0" FROM THE ENDS OF RIDGES, OUTSIDE CORNERS, OR OUTSIDE EDGES OF MAIN ROOFS AND MUST EXTEND A MINIMUM OF 10"

ABOVE OBJECT TO BE PROTECTED.

MIDROOF AIR TERMINALS SHALL BE SPACED AT 50'-0" O.C. MAXIMUM SPACING.

JOB CONDITIONS MAY DICTATE VARIATIONS IN AIR TERMINAL, CONDUCTORS AND GROUND ROD LOCATIONS.

CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD PATH FREE FROM "U" AND "V" POCKETS. ANY

RISE IN HORIZONTAL CONDUCTOR SHALL NOT EXCEED 8 INCHES.

CABLE MAY RISE UPWARDS AT A RATE OF 3" OF RISE PER 1'-0" RUN MAXIMUM.

COPPER LIGHTNING PROTECTION MATERIALS SHALL NOT BE PLACED ON ALUMINUM, GALVANIZED STEEL, GALVALUME SURFACES OR ANY OTHER DISSIMILAR METAL SURFACES, PAINTED OR NOT, NOR SHALL

ALUMINUM MATERIALS BE PLACED ON COPPER SURFACES.

FOR THE SAKE OF CLARITY WE HAVE NOT CALLED OUT EACH INDIVIDUAL ITEM OF LIGHTNING PROTECTION MATERIALS ON THE ROOF PLAN. WE HAVE SHOWN TYPICAL DETAILS AND HAVE CALLED OUT EACH OF THESE

DETAILS ON THE ROOF PLAN, ONLY IN SCATTERED LOCATIONS.

ALL STRUCTURAL STEEL, REBAR, FRAMING & MISCELLANEOUS STEEL SHALL BE MADE ELECTRICALLY CONTINUOUS THROUGH CONSTRUCTION (NOT THE RESPONSIBILITY OF THE LIGHTNING PROTECTION

CONTRACTOR).

ELECTRIC, TELEPHONE AND ANTENNA SYSTEM GROUNDS SHALL BE CONNECTED WITH MAIN SIZE CONDUCTOR

TO ONE LIGHTNING PROTECTION GROUND OR METAL WATER PIPE.

A LIGHTNING ARRESTOR, PROTECTOR, OR ANTENNA-DISCHARGE UNIT MUST BE INSTALLED ON EACH ELECTRIC AND TELEPHONE SERVICE ENTRANCE AND RADIO AND TELEVISION ANTENNA LEAD IN. (TO BE PROVIDED BY

ELECTRICAL CONTRACTOR.)

ALL ADHESIVE FIXTURES SHALL BE SET WITH AN ADHESIVE COMPOUND COMPATIBLE WITH THE ROOFING

MATERIAL. ADHESIVES SHALL BE APPROVED IN ADVANCE BY THE ROOFING CONTRACTOR.

BOND ALL METAL PIPES SUCH AS WATER, GAS, FIRE, STORM, SEWER WHICH ENTER THE STRUCTURE TO THE

NEAREST DOWNLEAD, GROUND ROD OR COUNTERPOISE.

CABLE WILL BE FASTENED EVERY 3'-0" O.C. MAXIMUM SPACING.

PERIMETER AND RIDGE AIR TERMINALS 10" TO 23" WILL BE SPACED UP TO 20' MAXIMUM. AIR TERMINALS 24" AND

OVER WILL BE SPACED 25' MAXIMUM.

CONNECTIONS TO GROUND AND/OR COUNTERPOISE SHALL BE MADE AT A POINT NOT LESS THAN 1'-0" BELOW

GRADE, AND 2'-0" AWAY FROM FOUNDATION WALL.

LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED IN A NEAT, PROFESSIONAL MANNER.

ON EXTERIOR WALLS OF BLOCK OR BRICK, DOWNLEAD CABLES SHALL BE ANCHORED IN THE BLOCK OR BRICK, NOT IN MORTAR.

NOTE: ALL ROOF AREAS ILLUSTRATED ON THESE SUBMITTAL DRAWINGS WHICH HAVE NOT BEEN

PROVIDED WITH LIGHTNING PROTECTION COMPONENTS ARE PROTECTED FROM HIGHER ROOFS OR

STRUCTURES. THESE AREAS FALL WITHIN A "ZONE OF PROTECTION" AS ESTABLISHED BY THE

CURRENT EDITION OF THE STANDARD FOR PROTECTION AGAINST LIGHTNING "ANSI/NFPA 780" AND

THE INSTALLATION REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS AS PROVIDED BY

STANDARD 96A OF UNDERWRITERS' LABORATORIES.

NOTE: INSTALLING CONTRACTOR TO FIELD VERIFY ACTUAL TYPES, LOCATIONS, NUMBERS OF

ROOFTOP OBSTRUCTION LIGHTS, AREAWAY LIGHTS, AND ANY SIMILAR LIGHTING FIXTURES WHICH

MAY PROJECT ABOVE BUILDING ROOF EDGES OR PARAPET WALLS AND ALSO ALL MECHANICAL

EQUIPMENT SUCH AS EXHAUST FANS, FLUES, COOLING TOWERS, CHILLERS, CONDENSING UNITS, ROOFTOP AIR HANDLING UNITS, ETC. AND PROTECT BY CORRECT APPLICATION SHOWN IN DETAIL

"F" UNLESS ITEMS OF EQUIPMENT ARE UNDER ZONE OF PROTECTION BY ADJACENT HIGHER

PROTECTED ROOF LEVELS.

NOTE: THIS LIGHTNING PROTECTION LAYOUT DRAWING IS BASED UPON THE MOST CURRENT

CONTRACT DRAWINGS AND INFORMATION AVAILABLE. THE ACTUAL SYSTEM LAYOUT, CHOICE OF AIR

TERMINAL/CABLE MOUNTING AND ROUTING METHODS, THRU-ROOF AND DOWNLEAD/GROUNDING

LOCATIONS, BONDING REQUIREMENTS, ETC., MAY VARY ACCORDING TO THE FINAL DESIGN OF THE BUILDING. LIGHTNING PROTECTION INSTALLER MUST FIELD VERIFY THE ACTUAL CONDITIONS OF THE

BUILDING(S) TO DETERMINE THE PROTECTION LEVEL NEEDED AND MAKE ANY ADJUSTMENTS,

UPWARD OR DOWNWARD, AS REQUIRED FOR U.L. 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATION.

NOTE: INSTALLING CONTRACTOR SHALL, PER GENERAL NOTE #2 AND DETAILS "G" AND "H", FIELD VERIFY ACTUAL TYPES AND LOCATIONS OF ROOF LOCATED METAL BODIES SUCH AS SUNSHADES, LADDERS, ROOF HATCHES, SMOKE HATCHES, SCUPPERS, ROOF DRAINS, CAMERAS, WINDOW

WASHING TIEBACKS, PHOTO CELLS, SOIL VENT PIPES, ETC., WHICH MAY REQUIRE BONDING. BOND IF WITHIN 6'-0" OF A LIGHTNING PROTECTION CONDUCTOR OR IF WITHIN 6'-0" OF AN ITEM WHICH HAS ALREADY BEEN BONDED BY THE 6' RULE. UTILIZE THE PROPER APPLICATION OF PLATE, CLAMP, LUG, ETC., TO THE SURFACE/SHAPE OF THE OBJECT TO BE BONDED.

NOTE: ALUMINUM LIGHTNING PROTECTION MATERIALS ARE REQUIRED TO BE UTILIZED ON ALL

BUILDING ROOF LEVELS FOR METALS COMPATIBILITY WITH GALVANIZED STEEL, GALVALUME AND

ALUMINUM SHEET METAL COPINGS, GRAVEL STOPS, ROOF AND WALL PANELS, FLASHINGS AND

EQUIPMENT HOUSINGS, ETC. THE ALUMINUM LIGHTNING PROTECTION MATERIALS AS BID AND

ILLUSTRATED ON THESE SHOP DRAWINGS ARE REQUIRED FOR UL 96-96A/NFPA 780 COMPLIANCE AND CERTIFICATIONS AND TO MAINTAIN THE INTEGRITY OF ROOFING SHEET METAL MATERIALS

AGAINST DAMAGE AND POTENTIAL ROOF SYSTEM FAILURES.

DETAILS

HART & ASSOCIATES INC.

3803 NORTH 36TH AVENUE

PHOENIX,ARIZONA 85019

Phone: 623.845.1094 Fax: 623.845.1093 Website: www.hart-assoc.com

LP 300

REPAIR AMMO AREA LIGHTNING PROTECTION

JBER, ALASKA

PROJECT NUMBER: HJZH161046

LHH

Master Installer # 1443

U.L. Listing E104704

EST. 1965

NO. A325 TEE TYPE

CABLE CONNECTOR

NO. C309 CABLE CONNECTOR

NO. A320 BIMETALLIC CONNECTOR

NO. C50 COPPER CABLE

NO. C50 COPPER CABLE

NO. A50 ALUMINUM CABLE

NO. A327 CROSSRUN

CABLE CONNECTOR

NO. A50 ALUMINUM CABLE

NO. A50 ALUMINUM CABLE

NO. A309 CABLE CONNECTOR

NO. A50 ALUMINUM CABLE

NO. A50 ALUMINUM CABLE

NO. A50 ALUMINUM CABLE

NO. A50 ALUMINUM CABLE

R 8"

90°

BEND RADIUS DETAIL

NOTE:

NO BEND OF A CONDUCTOR SHALL FORM

AN INCLUDED ANGLE OF LESS THAN 90 DEGREES,

NOR SHALL IT HAVE A RADIUS

OF BEND LESS THAN 203mm (8").

4 TO 1 CONDUCTOR DETAIL

NOTE: CONDUCTOR SHALL INTERCONNECT ALL

AIR TERMINALS AND SHALL FORM A TWO-WAY

PATH FROM EACH AIR TERMINAL HORIZONTALLY,

DOWNWARD OR RISING AT A RATE NOT

EXCEEDING 3" PER FOOT (76.2mm) TO

CONNECTIONS WITH GROUND TERMINALS

FASTEN CABLE 3'-0" O.C.

MAX, WITH

APPROPRIATE CABLE

FASTENER.

1 2

NO. A5818ST ALUMINUM AIR TERMINAL (5/8" X 18")

NO. A250 ALUMINUM BASE SECURED

WITH FOUR NO. S725 STAINLESS

STEEL SELF-DRILLING SCREWS

NO. A404 ALUMINUM BONDING

CLAMP SECURED WITH TWO

NO. S725 STAINLESS STEEL

SELF-DRILLING SCREWS

NO. A55 ALUMINUM CABLE

TO PARALLEL SPLICER

NO. A210 TOP MOUNT EQUIPMENT BASE SECURED

WITH TWO NO. S725 STAINLESS STEEL

SELF-DRILLING SCREWS

NO. A55 ALUMINUM CABLE SECURED TO UNIT

WITH NO. A702 ALUMINUM LOOP AND NO. S725

STAINLESS STEEL SELF-DRILLING SCREWS

36" O.C. MAXIMUM SPACING

CONNECT TO ROOF CIRCUIT WITH

NO. A309 PARALLEL SPLICER

NO. A5818ST ALUMINUM AIR TERMINAL (5/8" X 18")

NOTE: AIR TERMINALS MUST BE WITHIN

TWO FEET (2') OF OUTSIDE CORNERS

NOTE: CABLE ROUTED AND CONNECTED

TO NEAREST ROOF CIRCUIT

NOTE: CABLE SHALL BE ROUTED AND CONNECTED TO

NEAREST ROOF CIRCUIT. LENGTH OF CABLE SHALL NOT

EXCEED EIGHT FEET (8') OR TWO CABLES WILL BE

REQUIRED FROM THE AIR TERMINAL TO THE ROOF CIRCUIT.

NO. A5818ST ALUMINUM AIR

TERMINAL (5/8" X 18”)

NO. A250 ALUMINUM BASE SECURED

WITH FOUR NO. S725 STAINLESS

STEEL SELF-DRILLING SCREWS

NO. A404 ALUMINUM BONDING CLAMP

SECURED WITH TWO NO. S725 STAINLESS

STEEL SELF-DRILLING SCREWS

NO. A55 ALUMINUM CABLE

TO PARALLEL SPLICER

NOTE: TOP OF UNIT MUST BE MORE THAN

400 SQUARE INCHES OR 1000 CUBIC INCHES

FOR THIS APPLICATION

NOTE: FIELD VERIFY CORRECT APPLICATION

WARNING NOTE

IT IS THE RESPONSIBILITY OF THE LIGHTNING PROTECTION

INSTALLER TO COORDINATE WITH THE MECHANICAL EQUIPMENT

CONTRACTOR AND FIELD VERIFY APPROVED LOCATIONS PRIOR

TO INSTALLATION OF LIGHTNING PROTECTION COMPONENT

FASTENERS FOR ANY DRILLING OR PUNCHING OF HOLES WHICH

MAY BE REQUIRED FOR THE INSTALLATION OF FASTENERS, SO

AS NOT TO DAMAGE INTERNAL PIPING SYSTEMS, WIRING

SYSTEMS OR THE OPERATION/FUNCTION OF THE EQUIPMENT.

NOTE: TOP OF UNIT MUST BE LESS THAN

400 SQUARE INCHES OR 1000 CUBIC INCHES

FOR THIS APPLICATION

NO. A5824ST ALUMINUM AIR

TERMINAL (5/8" X 24")

NO. A54 COPPER CABLE SECURED

WITH NO. A712 ADHESIVE CABLE

HOLDER AND APPROVED ADHESIVE

36" O.C. MAXIMUM SPACING

NO. A220 ADHESIVE BASE AND

SECURED WITH APPROVED ADHESIVE

Air terminals must be located within 2 feet of the roof edge

(where applicable)

TYPICAL HEADWALL AIR TERMINAL, BASE AND CABLE HOLDER A

NO. C56 - 19 COPPER CABLE

NO. C56 - 19 COPPER CABLE

NO. C56 - 19 COPPER CABLE

NO. C55 COPPER

LIGHTNING CONDUCTOR

TYPICAL EXPOSED HEADWALL DOWNLEAD TO GROUND AND COUNTERPOISEH

NO. C313 HEAV Y DUTY CAST STRAIGHT SPLICER

NOT AT EVERY DOWNLEAD

TYPICALAIR TERMINAL MAST AND CABLE HOLDER B

PART NO. C1224ST (1/2” X 24”) COPPER AIR TERMINAL SAFETY TIPPED

PART NO. SRDT15011 1.5” OD 11 GAUAGE

304 STAINLESS STEEL TUBING EXTENDING

4’ ABOVE HEADWALL OR REAR VENTILATOR.

PART NO. C24112 BRONZE SIDE MOUNT AIR TERMINAL BASE

V