Attachment 2 - Drawing_BBVC Roof Replacement.pdf

PDF 5 MB Posted

Attached to
Begich, Boggs Visitor Center Roof Replacement
Solicitation number
1240BH26Q0039
Issued by

About this file

Summary

This document is a set of design and construction drawings for a roof replacement project at the Begich, Boggs Visitor Center, located at Portage Lake Loop in Girdwood, Alaska 99587. The project is under the jurisdiction of the United States Department of Agriculture Forest Service, Alaska Region, Chugach National Forest, Glacier Ranger District.

The drawings detail the complete demolition and replacement of the existing roof system with a new 145 mil fleece-backed EPDM membrane assembly. Key project components include removal of all existing roofing materials (PVC, EPDM, and metal sections), replacement of roof drains with new cast iron/aluminum models meeting 30-year warranty requirements, installation of R-50 EPS/polyiso insulation with polyurethane adhesive between layers, and new aluminum coping with anchor clips. The project incorporates detailed specifications for membrane splices, terminations, pipe flashing, scupper flashing, and parapet details. A drain heating system is required to prevent ice formation at roof drains and overflows, consisting of self-regulating heat trace cable (6 watts per foot at 40 degrees F) connected to an adjustable controller with roof-mounted sensors. The system must connect to Panel B electrical infrastructure with multiple 120V, 20-amp circuits. The design includes provisions for reinstallation of existing equipment including a Starlink satellite, anemometer, FAA equipment, roof ladders, and heat trace cabling. The contractor must submit traffic control plans, coordinate with building operators on system adjustments, and complete field verification of all conditions prior to bidding. Design date is December 2025.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FOREST LOCATION MAP

PROJECT LOCATION MAP

TRAVEL DIRECTIONS:

SHEET OF

United States Department of Agriculture

Forest Service

BEGICH, BOGGS VISITOR CENTER

TRAVEL SOUTH FROM ANCHORAGE ON AK-1 (SEWARD HWY). TURN LEFT

ONTO PORTAGE GLACIER ROAD FOR 4.9 MILES. TURN RIGHT ONTO

PORTAGE LAKE LOOP, FOLLOWING SIGNS FOR THE BEGICH, BOGGS

VISITOR CENTER/PORTAGE GLACIER. VISITOR CENTER WILL BE ON YOUR

RIGHT. 60°47'4.74"N 148°50'28.87"W

ROOF REPLACEMENT

RECOMMENDED BY:

APPROVED:

CNF FOREST ENGINEER

GRD DISTRICT RANGER

DATE

DATE

CNF FOREST SUPERVISOR

DATE

DESIGN ENGINEER

/17

/25

:5 7 E

LI

JA

HU

DU

GG

ER

C :\U

SE

RS

\E

LI

JA

HU

DU

GG

ER

\B

OX

\R

C

NF

B

UI

LD

IN

GS

S

TR

UC

TU

RE

S\

B

LD

GS

&R

LT

DS

TR

UC

S\

FA

C_

PR

OJ

_F

IL

ES

\G

LA

CI

ER

_R D\

PO

RT

AG

E\

BB

VC

\B

BV

C_

RO

OF

\20

R

EP

LA

CE

ME

NT

P

RO

JE

CT

\D

RA

W

IN

GS

\B

BV

C

RO

OF

C

OV

ER

S

HE

ET

.D

W G;

ALASKA

PORTAGE VALLEY

(R10) ALASKA REGION

CHUGACH NATIONAL FOREST

GLACIER RANGER DISCTRICT

INDEX OF SHEETS

SHEET SHEET TITLE DATE

G-01 COVER SHEET DEC2025

C-01 EXISTING SITE PLAN DEC2025

AD-01 ROOF DEMOLITION PLAN DEC2025

AD-02 EXISTING ROOF PHOTOGRAPHS DEC2025

AD-03 EXISTING ROOF PHOTOGRAPHS DEC2025

A-01 NEW ROOF PLAN DEC2025

A-02 ELEVATIONS DEC2025

A-03 NEW ROOF DETAILS DEC2025

A-04 NEW ROOF DETAILS CONTINUED DEC2025

A-05 NEW ROOF DETAILS CONTINUED DEC2025

A-06 NEW ROOF DETAILS CONTINUED DEC2025

E-01 DRAIN HEATER PLAN DEC2025

Whittier

Girdwood

Project Location

Begich, Boggs Visitor Center

Portage Lake Loop

Girdwood, AK 99587

DATE

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

/17

/25

9:

E

LI

JA

HU

DU

GG

ER

C

:\U

SE

RS

\E

LI

JA

HU

DU

GG

ER

\B

OX

\R

C

NF

B

UI

LD

IN

GS

S

TR

UC

TU

RE

S\

B

LD

GS

&R

LT

DS

TR

UC

S\

FA

C_

PR

OJ

_F

IL

ES

\G

LA

CI

ER

_R

D\

PO

RT

AG

E\

BB

VC

\B

BV

C_

RO

OF

\20

R

EP

LA

CE

ME

NT

P

RO

JE

CT

\D

RA

W

IN

GS

\B

BV

C

RO

OF

.D W

G;

R10

ALASKA REGION

BEGICH, BOGGS

VISITOR CENTER

ROOF

REPLACEMENT

CHUGACH NF

GLACIER RANGER DISTRICT

EXISTING SITE PLAN

12/2025

E.DUGGER

E.DUGGER

G.BERG

C-01 2 12

POTENTIAL CONTRACTOR STAGING AREA. FINAL LOCATION

DEPENDS ON PROJECT TIMING AND ANTICIPATED VISITOR TRAFFIC.

NOTES:

1. FOR MORE DETAILED SITE CONDITIONS, INCLUDING CONTOURS, SEE THE EXHIBIT

DRAWINGS. ORIGINAL SITE PLANS FROM THE FACILITY CONSTRUCTION AND

CLASSROOM ADDITION HAVE DETAILED CIVIL INFORMATION.

2. POTENTIAL CONTRACTOR STAGING AREA IDENTIFIED ON THIS DRAWING IS

PRELIMINARY AND MAY CHANGE TO OTHER PARKING AREAS AT THE CO'S

DISCRETION. IF WORK IS COMPLETED PRIOR TO THE VISITOR CENTER OPENING

FOR THE SEASON THEN CONTRACTOR AREAS WILL LIKELY BE MORE FLEXIBLE.

3. TRAFFIC CONTROLS AND SIGNAGE WILL BE THE RESPONSIBILITY OF THE

CONTRACTOR. SIGNAGE AND TRAFFIC CONTROL IS NOT LIMITED TO WHAT IS

SHOWN HERE - CONTRACTORS MUST BID FOR FLEXIBILITY IN QUANTITY AND

LOCATION OF CONTROLS/SIGNS. TRAFFIC CONTROL PLAN SHALL BE SUBMITTED

AS PART OF THE DEMOLITION & SAFETY PLAN DESCRIBED IN THE SOW,

PARAGRAPH 5.5.

4. EXACT PLACEMENT OF DUMPSTERS, HEAVY EQUIPMENT, AND MATERIAL

STORAGE WILL BE DETERMINED AT THE PRE-CONSTRUCTION MEETING.

PORTAGE GLACIER RD

EARLY WARNING SIGNAGE

BBVC FACILITY

POTENTIAL CONTRACTOR TRAFFIC

CONTROL. FINAL LOCATION DEPENDS ON

PROJECT TIMING AND ANTICIPATED

VISITOR TRAFFIC.

ONE-WAY ENTRY

NOT TO SCALE

EXISTING SITE PLAN

N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

AutoCAD SHX Text E

NIC

60 MIL FULLY

ADHERED PVC

(2) LAYERS OF 3.2"

ISO INSULATION

8 MIL POLY VB

7/16" EXPOSURE

1 OSB

" GYP BD

MECHANICALLY

FASTENED

CONCRETE

PAVERS

60 MIL EPDM

R-50 EPS

INSULATION

10 MIL POLY

V.R.

CONCRETE

DECK

METAL TRACK AT

PERIMETER IN SOME

LOCATIONS

LOOSE

LAID

FILTER

FABRIC

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

/17

/25

9:

E

LI

JA

HU

DU

GG

ER

C

:\U

SE

RS

\E

LI

JA

HU

DU

GG

ER

\B

OX

\R

C

NF

B

UI

LD

IN

GS

S

TR

UC

TU

RE

S\

B

LD

GS

&R

LT

DS

TR

UC

S\

FA

C_

PR

OJ

_F

IL

ES

\G

LA

CI

ER

_R

D\

PO

RT

AG

E\

BB

VC

\B

BV

C_

RO

OF

\20

R

EP

LA

CE

ME

NT

P

RO

JE

CT

\D

RA

W

IN

GS

\B

BV

C

RO

OF

.D W

G;

R10

ALASKA REGION

BEGICH, BOGGS

VISITOR CENTER

ROOF

REPLACEMENT

CHUGACH NF

GLACIER RANGER DISTRICT

ROOF DEMOLITION PLAN

12/2025

E.DUGGER

E.DUGGER

G.BERG

AD-01

3 12

NOTES:

1. FOR MORE DETAILED EXISTING ROOF CONDITIONS AND ASSEMBLIES SEE THE ATTACHED AS-BUILT DRAWINGS.

ROOFING DETAILS FROM 2004 FOR THE EPDM SECTION, AND DETAILS FROM THE PVC ADDITION ARE INCLUDED.

2. PHOTOGRAPHS ARE PROVIDED ON SHEETS AD-02/03 FOR ADDITIONAL REFERENCE.

3. FOR BLDG ELEVATIONS, SEE AS-BUILT DRAWINGS.

4. CONTRACTOR MUST FIELD VERIFY CONDITIONS, QUANTITIES, AND DIMENSIONS PRIOR TO BIDDING AND ORDERING

MATERIALS.

5. CONTRACTOR SHALL REMOVE ALL EXISTING ROOFING MATERIALS, FLASHING, TRIM, AND RELATED ITEMS IN THEIR

ENTIRETY AS DESCRIBED IN THE SOW AND PROJECT SPECIFICATIONS.

6. THE AIR CONDITIONING UNIT WILL BE REMOVED BY THE FOREST SERVICE PRIOR TO CONSTRUCTION.

ROOF DRAIN

SCUPPER

PIPE PENETRATION

STACK PENETRATION

HVAC HOOD

PVC ROOFING (DETAIL D1)

EPDM ROOFING (DETAIL D2)

METAL ROOFING

010 10 20 FT

NOT TO SCALE

EXISTING PVC ASSEMBLY

D1

NOT TO SCALE

EXISTING EPDM ASSEMBLY

D2

1" = 12'

ROOF DEMOLITION PLAN

N

P7

AD-03

P8

AD-03

STARLINK SATELLITE TO BE REMOVED

& REINSTALLED BY CONTRACTOR

P9

AD-03

P6

AD-03

P7

AD-03

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

/17

/25

9:

E

LI

JA

HU

DU

GG

ER

C

:\U

SE

RS

\E

LI

JA

HU

DU

GG

ER

\B

OX

\R

C

NF

B

UI

LD

IN

GS

S

TR

UC

TU

RE

S\

B

LD

GS

&R

LT

DS

TR

UC

S\

FA

C_

PR

OJ

_F

IL

ES

\G

LA

CI

ER

_R

D\

PO

RT

AG

E\

BB

VC

\B

BV

C_

RO

OF

\20

R

EP

LA

CE

ME

NT

P

RO

JE

CT

\D

RA

W

IN

GS

\B

BV

C

RO

OF

.D W

G;

R10

ALASKA REGION

BEGICH, BOGGS

VISITOR CENTER

ROOF

REPLACEMENT

CHUGACH NF

GLACIER RANGER DISTRICT

EXISTING ROOF PHOTOS

12/2025

E.DUGGER

E.DUGGER

G.BERG

AD-02

4 12

ALUMINUM TRACKS AROUND PERIMETER OF

THE EAST SECTION OF THE ROOF, TO BE

REMOVED WITH THE BALLASTS

ROOF DRAIN PITS TO BE REMOVED AND

REPLACED WITH DOME STYLE DRAINS

PVC SECTION OF ROOF - SEE DETAIL

D1 ON SHEET AD-01 FOR ASSEMBLY

NOT TO SCALE

EXISTING ROOF PANORAMIC

P1

NOT TO SCALE

PVC ROOF SECTION

P2

NOT TO SCALE

ROOF DRAIN

P3

NOT TO SCALE

ALUMINUM TRACKS

P4

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

/17

/25

9:

E

LI

JA

HU

DU

GG

ER

C

:\U

SE

RS

\E

LI

JA

HU

DU

GG

ER

\B

OX

\R

C

NF

B

UI

LD

IN

GS

S

TR

UC

TU

RE

S\

B

LD

GS

&R

LT

DS

TR

UC

S\

FA

C_

PR

OJ

_F

IL

ES

\G

LA

CI

ER

_R

D\

PO

RT

AG

E\

BB

VC

\B

BV

C_

RO

OF

\20

R

EP

LA

CE

ME

NT

P

RO

JE

CT

\D

RA

W

IN

GS

\B

BV

C

RO

OF

.D W

G;

R10

ALASKA REGION

BEGICH, BOGGS

VISITOR CENTER

ROOF

REPLACEMENT

CHUGACH NF

GLACIER RANGER DISTRICT

EXISTING ROOF PHOTOS

12/2025

E.DUGGER

E.DUGGER

G.BERG

AD-03

5 12

EXISTING ELECTRICAL

INFRASTRUCTURE CAN BE

RE-USED FOR NEW SNOW MELT

A/C UNIT AND STAND WILL BE

REMOVED BY THE GOV PRIOR TO

CONSTRUCTION STARTING

TWO ROOF LADDERS TO BE

REMOVED AND REINSTALLED BY

THE CONTRACTOR

NOT TO SCALE

HEAT TRACE CABLING & POWER

P5

NOT TO SCALE

AIR CONDITIONING UNIT

P6

NOT TO SCALE

ROOF LADDER

P7

NOT TO SCALE

FAA EQUIPMENT

P9

NOT TO SCALE

ANEMOMETER

P8

ANEMOMETER TO BE REMOVED

AND REINSTALLED AFTER

CONSTRUCTION BY CONTRACTOR

EQUIPMENT TO STAY IN PLACE FOR

CONSTRUCTION. IF REMOVAL IS

NEEDED, THE CONTRACTOR IS TO

COORDINATE WITH FAA.

AT LEAST (8) 120/240V 20A

CIRCUITS AVAILABLE FOR

UTILIZATION FOR NEW HEATERS

IN PANEL 'B'

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

/17

/25

9:

E

LI

JA

HU

DU

GG

ER

C

:\U

SE

RS

\E

LI

JA

HU

DU

GG

ER

\B

OX

\R

C

NF

B

UI

LD

IN

GS

S

TR

UC

TU

RE

S\

B

LD

GS

&R

LT

DS

TR

UC

S\

FA

C_

PR

OJ

_F

IL

ES

\G

LA

CI

ER

_R

D\

PO

RT

AG

E\

BB

VC

\B

BV

C_

RO

OF

\20

R

EP

LA

CE

ME

NT

P

RO

JE

CT

\D

RA

W

IN

GS

\B

BV

C

RO

OF

.D W

G;

R10

ALASKA REGION

BEGICH, BOGGS

VISITOR CENTER

ROOF

REPLACEMENT

CHUGACH NF

GLACIER RANGER DISTRICT

NEW ROOF PLAN

12/2025

E.DUGGER

E.DUGGER

G.BERG

A-01 6 12

ROOF DRAIN

SCUPPER

PIPE PENETRATION

STACK PENETRATION

VENT PENETRATION

METAL DECK ASSEMBLY (DETAIL B1, SHT A-03)

CONCRETE DECK ASSEMBLY (DETAIL B2, SHT A-03)

010 10 20 FT

NOTES:

1. CONTRACTOR MUST FIELD VERIFY CONDITIONS AND DIMENSIONS PRIOR TO BIDDING AND ORDERING MATERIALS.

2. REPLACE ALL ROOF DRAINS IN THE CONCRETE DECK ASSEMBLY AREA WITH NEW CAST IRON/ALUMINUM ONES AS SHOWN

ON B3, SHT A-03. DRAINS IN METAL DECK PORTION DO NOT NEED TO BE REPLACED.

3. REPLACE ALL BOOTS, FLASHING AND COPING THROUGHOUT WITH PRODUCTS THAT MEET THE MANUFACTURER'S

REQUIREMENTS FOR 30 YEAR ROOF WARRANTY AS WELL AS THE PROJECT SPECIFICATIONS.

4. CONTRACTOR MUST SUBMIT, FOR GOVERNMENT APPROVAL, DETAILS FOR ALL PENETRATIONS, CURBS, PARAPETS, AND

DRAINS IAW ROOFING MANUFACTURER'S REQUIREMENTS FOR 30 YEAR WARRANTY.

1" = 10'

NEW ROOF PLAN

N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

SOUTH ELEVATION

SCALE: 1" = 10'

SCALE: 1" = 10'

NORTH ELEVATION

WEST ELEVATION - ADDITION

SCALE: 1" = 10'

EAST ELEVATION - ADDITION

SCALE: 1" = 10'

5 10

5 10

5 10

5 10

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

/17

/25

9:

E

LI

JA

HU

DU

GG

ER

C

:\U

SE

RS

\E

LI

JA

HU

DU

GG

ER

\B

OX

\R

C

NF

B

UI

LD

IN

GS

S

TR

UC

TU

RE

S\

B

LD

GS

&R

LT

DS

TR

UC

S\

FA

C_

PR

OJ

_F

IL

ES

\G

LA

CI

ER

_R

D\

PO

RT

AG

E\

BB

VC

\B

BV

C_

RO

OF

\20

R

EP

LA

CE

ME

NT

P

RO

JE

CT

\D

RA

W

IN

GS

\B

BV

C

RO

OF

.D W

G;

R10

ALASKA REGION

BEGICH, BOGGS

VISITOR CENTER

ROOF

REPLACEMENT

CHUGACH NF

GLACIER RANGER DISTRICT

ELEVATIONS

12/2025

E.DUGGER

E.DUGGER

G.BERG

A-02 7 12

NOTES:

1. REALIGN EXISTING SLOPED MEMBRANE TERMINATION AROUND THE CLASSROOM SECTION TO REMOVE CURVES AND

REPLACE WITH STRAIGHT LINES TO ENABLE PROPER REGLET/COUNTERFLASHING INSTALLATION.

2. REMOVE/GRIND MASONRY FLUTES TO ESTABLISH SMOOTH SURFACE FOR THE MEMBRANE.

3. EXACT MEMBRANE LINE TO BE DETERMINED IN THE FIELD WITH INPUT AND AGREEMENT FROM THE CONTRACTOR, MANUFACTURER, AND GOVERNMENT.

PROPOSED NEW MEMBRANE LINE

EXISTING MEMBRANE LINE

PROPOSED NEW MEMBRANE LINE

EXISTING MEMBRANE LINE

PROPOSED NEW MEMBRANE LINE

EXISTING MEMBRANE LINE

PROPOSED NEW MEMBRANE LINE

EXISTING MEMBRANE LINE

AutoCAD SHX Text C

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

METAL DECK

5/8" GYPSUM COVERBOARD

MECHANICALLY FASTENED PER

MANUFACTURER'S REQUIREMENTS

FOR ASCE-7 UPLIFT RATING

R-50 EPS/POLYISO INSULATION

POLYURETHANE ADHESIVE

B/W LAYERS

40 MIL SELF-ADHERING

RUBBERIZED ASPHALT

VAPOR BARRIER, WITH

PRIMER

5/8" COVERBOARD

POLYURETHANE

ADHESIVE

145 MIL FLEECE-BACKED

EPDM MEMBRANE

40 MIL SELF-ADHERING

RUBBERIZED ASPHALT VAPOR

BARRIER, WITH PRIMER

CONCRETE DECK

R-50 EPS/POLYISO INSULATION

POLYURETHANE ADHESIVE

B/W LAYERS

5/8" COVERBOARD

POLYURETHANE

ADHESIVE

145 MIL FLEECE-BACKED

EPDM MEMBRANE

COPING COVER, 12' LENGTHS, .050 ALUMINUM

12" WIDE 16 GA GALV.

ANCHOR CLIPS W/ FORMED

FRONT SUPPORT 2' OC

8" WIDE SPLICE PLATE W/

DUAL NON-CURING STRIPS

@ EA JOINT

INSIDE

FACE

OUTSIDE

FACE

ACTUAL WALL

WIDTH

NEW WOOD NAILER

NOTES:

1. INSIDE AND OUTSIDE FACE VALUES WILL VARY BASED ON LOCATION. OUTSIDE FACE MIN IS 3

", MAX 12". OUTSIDE FACE SHALL BE A MIN OF 8" WHEN OVERLAPPING AN ADJACENT

FINISHED SURFACE. INSIDE FACE MIN IS 2

", MAX 12".

2. COPING MUST BE .050 ALUMINUM (MIN.), FM 1-225 APPROVAL.

3. WOOD NAILER TO BE TREATED 2X, SECURED USING

" X 5" GALVANIZED ANCHOR BOLTS AT 2'

O.C. EXISTING NAILER CAN BE RE-USED IF THE GOVERNMENT, COPING MANUFACTURER,

AND CONTRACTOR AGREE THAT IT IS IN ACCEPTABLE CONDITION.

#10 X 1

" (38 MM)

STAINLESS STEEL FASTENERS

NOTES:

1. REMOVE EXISTING LEAD, FLASHING MATERIAL & ENSURE THE DRAIN RING IS COMPLETELY CLEAN DOWN TO BARE METAL.

2. FLEECE BACKING MUST BE REMOVED FROM THE MEMBRANE SO THAT WATER CUT OFF MASTIC IS IN DIRECT CONTACT.

3. THE HOLE IN THE MEMBRANE SHALL EXCEED THE DIAMETER OF THE DRAIN PIPE, BUT SHALL BE NO LESS THAN 1/2" FROM THE ATTACHMENT POINTS OF THE DRAIN

CLAMPING RING.

4. ALL BOLTS OR CLAMPS MUST BE IN PLACE TO PROVIDE CONSTANT COMPRESSION ON WATER CUT-OFF MASTIC.

5. FIELD SPLICES MUST BE LOCATED AT LEAST 6 INCHES OUTSIDE THE DRAIN SUMP.

6. ROOF DRAIN PIPING TO REMAIN IN PLACE (PRIMARILY 3") BUT NEW ROOF DRAINS MUST BE PROVIDED. SEE SPECIFICATIONS SECTION 077200 FOR REQUIREMENTS.

DIMENSION

"X"

GREATER THAN

DIMENSION "X"

DRAIN PIPE

MIN. 1/2"

FLEECE-BACKED EPDM

SEE NOTE(S)

APPROVED SUBSTRATE

NEW ROOF DRAIN

ASSEMBLY PER

PROJECT

SPECIFICATIONS

WATER CUT-OFF

MASTIC

COMPLETELY REMOVE THE FLEECE

IN CLAMPING RING AREA

M

A

X

I M

U

M

A

L

L

O

W

D

S

O

P

E

R

T

I O

N

D

R

A

S

U

M

P

25%

14°

3:12

MAX.

APPROVED ADHESIVE

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

/17

/25

9:

E

LI

JA

HU

DU

GG

ER

C

:\U

SE

RS

\E

LI

JA

HU

DU

GG

ER

\B

OX

\R

C

NF

B

UI

LD

IN

GS

S

TR

UC

TU

RE

S\

B

LD

GS

&R

LT

DS

TR

UC

S\

FA

C_

PR

OJ

_F

IL

ES

\G

LA

CI

ER

_R

D\

PO

RT

AG

E\

BB

VC

\B

BV

C_

RO

OF

\20

R

EP

LA

CE

ME

NT

P

RO

JE

CT

\D

RA

W

IN

GS

\B

BV

C

RO

OF

.D W

G;

R10

ALASKA REGION

BEGICH, BOGGS

VISITOR CENTER

ROOF

REPLACEMENT

CHUGACH NF

GLACIER RANGER DISTRICT

NEW ROOF DETAILS

12/2025

E.DUGGER

E.DUGGER

G.BERG

A-03 8 12

NOT TO SCALE

NEW EPDM ASSEMBLY

B1

NOT TO SCALE

NEW EPDM ASSEMBLY

B2

NOT TO SCALE

NEW ROOF DRAIN

B3

NOT TO SCALE

NEW COPING

B4

AutoCAD SHX Text

XXXX XXX

AutoCAD SHX Text

XXXXXXXXXXXXX

AutoCAD SHX Text

XXXXXXXX

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

END LAP SPLICEMEMBRANE SPLICE

NOTES:

1. APPLY EPDM PRIMER TO MEMBRANE SURFACES PRIOR TO INSTALLING FLASHING AND/OR FACTORY APPLIED TAPE.

2. APPLY LAP SEALANT ALONG THE EDGE OF THE MEMBRANE SPLICE (UNDER THE 6"x6" T-JOINT COVER) COVERING THE EXPOSED SPLICE

TAPE 1/2" IN EACH DIRECTION FROM THE SPLICE INTERSECTION.

3. ALL EPDM SPLICE INTERSECTIONS MUST BE OVERLAID WITH TWO LAYERS OF EPDM FLASHING. THE BOTTOM LAYER SHALL BE 6"X6"

COVERED WITH A 12"X12" TOP LAYER. BOTH LAYERS SHALL BE CENTERED OVER THE SPLICE INTERSECTION AND SEALED WITH

CONTINUOUS LAP SEALANT, AS SHOWN.

M

A X

FLEECE-BACKED

EPDM

EPDM PRIMER

6" WIDE

FACTORY-APPLIED

TAPE

12" WIDE EPDM FLASHING

CENTERED OVER COVER

STRIP

6" WIDE CURED COVER STRIP

CENTERED OVER BUTTED END

LAPS

LAP SEALANT

6" AND 12" T-JOINT

DETAIL B6

F.A.T.

EPDM PRIMER

T-JOINT PER DETAIL B6

12" WIDE EPDM

FLASHING

LAP SEALANT

FIELD

SPLICE

6" WIDE CURED COVER STRIP CENTERED

OVER BUTTED END LAPS NOTES:

1. APPLY LAP SEALANT ALONG THE EDGES OF THE

MEMBRANE SPLICE COVERING THE EXPOSED SPLICE

TAPE 1/2" IN EACH DIRECTION FROM THE SPLICE

INTERSECTION.

2. APPLY LAP SEALANT AT CUT EDGES OF REINFORCED

MEMBRANE AND TAPE OVER LAPS.

RELEASE FILM

RELEASE FILM

POSITION MEMBRANE TO ALLOW AN APPROXIMATE 7"

OVERLAP. MARK THE BOTTOM SHEET WITH AN INDELIBLE

MARKER 1/2" FROM THE EDGE OF THE TOP SHEET AS SHOWN.

THE PRE-MARKED LINE ON THE MEMBRANE EDGE CAN ALSO BE

USED AS A GUIDE.

FOLD SHEETS BACK AS SHOWN. APPLY EPDM PRIMER TO THE

SPLICE AREA ON BOTH SURFACES AND ALLOW TO FLASH-OFF.

APPLY SPLICE TAPE WITH RELEASE FILM ALIGNED WITH

MARKED LINE.

SPLICE SHEET B TO SHEET A AND APPLY SECOND PIECE OF

SPLICE TAPE BETWEEN SHEET B AND C. TRIM RELEASE FILM

AS SHOWN.

SPLICE SHEET C TO SHEET A AND B, PRESS TOP SHEET ONTO

BOTTOM SHEET USING HAND PRESSURE TOWARDS THE OUTER

EDGE OF THE SPLICE AND ROLL THE SPLICE AREA WITH A 2"

WIDE STEEL ROLLER.

APPLY 6" T-JOINT COVER AND 12" T-JOINT COVER OR EPDM

FLASHING CENTERED OVER THE INTERSECTING POINT OF THE

LEADING EDGES OF THE FIELD SPLICE INTERSECTION AS

SHOWN.

SPLICE TAPE

C

B

MEMBRANE

MEMBRANE

MEMBRANE

A

A

A

B

B

C

C

C

B

A

C

A

RELEASE FILM

B

MINIMUM

6" WIDE

SPLICE

SPLICE TAPE

SECOND LAYER

SPLICE TAPE

LAP SEALANT APPLIED

ALONG MEMBRANE EDGE

SPLICE TAPE

6" T-JOINT COVER

AND EPDM PRIMER

LAP SEALANT

BELOW THE 6"

T-JOINT COVER

12" T-JOINT COVER

AND EPDM PRIMER

LAP SEALANT

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

/17

/25

9:

E

LI

JA

HU

DU

GG

ER

C

:\U

SE

RS

\E

LI

JA

HU

DU

GG

ER

\B

OX

\R

C

NF

B

UI

LD

IN

GS

S

TR

UC

TU

RE

S\

B

LD

GS

&R

LT

DS

TR

UC

S\

FA

C_

PR

OJ

_F

IL

ES

\G

LA

CI

ER

_R

D\

PO

RT

AG

E\

BB

VC

\B

BV

C_

RO

OF

\20

R

EP

LA

CE

ME

NT

P

RO

JE

CT

\D

RA

W

IN

GS

\B

BV

C

RO

OF

.D W

G;

R10

ALASKA REGION

BEGICH, BOGGS

VISITOR CENTER

ROOF

REPLACEMENT

CHUGACH NF

GLACIER RANGER DISTRICT

NEW ROOF DETAILS

CONTINUED

12/2025

E.DUGGER

E.DUGGER

G.BERG

A-04 9 12

NOT TO SCALE

MEMBRANE SPLICES

B5

NOT TO SCALE

T-JOINT DETAIL

B6

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

USE 8A OR 8B

TERMINATION

NOTES:

1. MEMBRANE SPLICES SHALL INCORPORATE 6" WIDE SPLICE TAPE

W/ PRIMER.

2. 6" FIELD APPLIED TAPE MUST BE OUTSIDE PLATES.

3. 9" WIDE FLEECE-BACKED MEMBRANE INSTALLED WITH

FLEECE-BACKING SIDE FACING UP.

4. ADHESIVE BEADING IS SHOWN FOR ILLUSTRATIVE PURPOSES

ONLY - ACTUAL SPACING AND QUANTITY TO BE DETERMINED BY

MANUFACTURER TO OBTAIN REQUIRED WARRANTY.

5. ALL SPLICE INTERSECTIONS REFER TO SHEET A-04 DETAILS.

MANUFACTURER APPROVED

BONDING ADHESIVE

FASTENER & SEAM FASTENING

PLATE, MAX. 12" (30cm) O.C.

SEPARATE MEMBRANES

MANUFACTURER APPROVED

BONDING ADHESIVE

USE 8A OR 8B TERMINATION

FASTENER & SEAM FASTENING

PLATE, MAX. 12" (30cm) O.C.

CONTINUOUS MEMBRANES

MIN. 1/4"

MAX. 1/2"

NOTES:

1. APPLY ON HARD SMOOTH SURFACE ONLY; NOT FOR USE ON

EXPOSED WOOD.

2. DO NOT WRAP TERMINATION BAR AROUND CORNERS.

3. FLEECE-BACKING MUST BE REMOVED FROM THE MEMBRANE

SO THAT WATER CUT-OFF MASTIC IS IN DIRECT CONTACT.

4. DETAIL 8C MUST BE USED AT VERTICAL JOINTS IN PANEL

WALLS.

8B

8A

NOTES:

1. FOR COPING, REFER TO INSTALLATION

INSTRUCTIONS FROM THE

MANUFACTURER.

2. MEMBRANE MUST BE EXTENDED TO

CORNERS TO PROVIDE COMPLETE

COVERAGE OF THE TOP WALL SURFACE.

MECHANICAL TERMINATION WITH COUNTER FLASHING

SHEET METAL COPING

APPLICABLE BONDING ADHESIVE

WATER CUT-OFF MASTIC- MUST BE HELD UNDER

CONSTANT COMPRESSION.

8C

1"

MECHANICAL TERMINATION AT VERTICAL JOINTS

NOTES:

1. VERTICAL JOINTS IN THE PRE-CAST PANEL AS WELL AS ALL GAPS

AT THE JUNCTION OF THE TILT-UP PANEL AND ROOF DECK MUST

BE FULLY SEALED TO PREVENT AIR INFILTRATION.

2. APPLY ON HARD SMOOTH SURFACE ONLY.

METAL

COUNTER

FLASHING

SEALANT

0.5"

SEALANT

MANUFACTURER APPROVED POLYETHER

SEALANT

METAL COUNTER FLASHING

TERM BAR NAIL-IN

TERMINATION BAR

SEE SHEET A-02, DETAIL

B4 FOR COPING REQS

EXTEND MEMBRANE

BELOW JOINT

W

A

P

N

J

I

N

T

S

R

O

F

M

M

B

R

A

T

T

R

M

I

N

A

T

I

V

E

L

TERMINATION BAR

FLEECE-BACKED EPDM

SEE NOTE(S)

APPROVED ADHESIVE

WATER CUT-OFF MASTIC

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

/17

/25

9:

E

LI

JA

HU

DU

GG

ER

C

:\U

SE

RS

\E

LI

JA

HU

DU

GG

ER

\B

OX

\R

C

NF

B

UI

LD

IN

GS

S

TR

UC

TU

RE

S\

B

LD

GS

&R

LT

DS

TR

UC

S\

FA

C_

PR

OJ

_F

IL

ES

\G

LA

CI

ER

_R

D\

PO

RT

AG

E\

BB

VC

\B

BV

C_

RO

OF

\20

R

EP

LA

CE

ME

NT

P

RO

JE

CT

\D

RA

W

IN

GS

\B

BV

C

RO

OF

.D W

G;

R10

ALASKA REGION

BEGICH, BOGGS

VISITOR CENTER

ROOF

REPLACEMENT

CHUGACH NF

GLACIER RANGER DISTRICT

NEW ROOF DETAILS

CONTINUED

12/2025

E.DUGGER

E.DUGGER

G.BERG

A-05 10 12

NOT TO SCALE

PARAPET/CURB FLASHING

B7

NOT TO SCALE

MEMBRANE TERMINATIONS

B8

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

XXXXXX

AutoCAD SHX Text

XXX

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

NOTES:

1. WOOD NAILERS ARE INSTALLED ONLY AT SCUPPERS TO

SECURE METAL SLEEVE AND MUST EXTEND PAST THE WIDTH OF

METAL SLEEVE FLANGE.

2. INSTALL WALL FLASHING PRIOR TO SCUPPER INSTALLATION.

3. METAL SCUPPER BOX MUST HAVE CONTINUOUS FLANGES WITH

ROUNDED CORNERS. SOLDER ALL SCUPPER SEAMS

WATER-TIGHT.

4. WATER CUT-OFF MASTIC UNDER SCUPPER FLANGE MUST BE

UNDER CONSTANT COMPRESSION.

5. SCUPPER FLANGES MUST BE TOTALLY COVERED BY EPDM

FLASHING WITH MINIMUM 2" COVERAGE PAST NAIL HEADS.

6. TO REMOVE FINISHING OILS, SCRUB METAL FLANGE WITH

WEATHERED MEMBRANE CLEANER; ALLOW TO DRY PRIOR TO

APPLYING EPDM PRIMER.

7. APPLY EPDM PRIMER TO METAL FLANGE AND MEMBRANE

SURFACE PRIOR TO INSTALLING EPDM FLASHING.

B7

MIN. 6" EPDM FLASHING

EPDM

PRIMER

REFER TO APPLICABLE SMACNA (LATEST

EDITION) DETAILS

BONDING ADHESIVE

WATER CUT-OFF MASTIC

SEALANT

WATER CUT-OFF MASTIC

WOOD NAILER

LAP SEALANT

EPDM MEMBRANE

FLEECE-BACKED EPDM

SEE NOTE(S)

APPROVED ADHESIVE

NOTES:

1. REMOVE ALL LEAD AND OTHER FLASHING BEFORE INSTALLING FIELD FABRICATED PIPE SEAL.

2. TEMPERATURE OF PIPE MUST NOT EXCEED 180°F.

3. APPLY EPDM PRIMER TO SPLICE AREA.

4. PRE-MOLDED PIPE FLASHING MUST HAVE INTACT RIB AT THE TOP EDGE REGARDLESS OF PIPE DIAMETER.

5. DECK FLANGES OF THE PRE-MOLDED PIPE SEAL SHALL NOT BE OVERLAPPED, CUT OR APPLIED OVER ANY

ANGLE CHANGE.

6. WHEN A FIELD SPLICE INTERSECTS A PIPE SEAL, APPLY LAP SEALANT ALONG THE EDGE OF THE MEMBRANE

SPLICE COVERING THE EXPOSED SPLICE TAPE 2" IN EACH DIRECTION FROM THE SPLICE INTERSECTION &

OVERLAY WITH A 6"X6" T-JOINT COVER.

7. FIELD FABRICATED PIPE WRAPS MAY BE ACCEPTABLE IF APPROVED BY THE EPDM MANUFACTURER. SEE

INDIVIDUAL MANUFACTURER DETAILS FOR WARRANTED FIELD FABRICATION ASSEMBLY.

1/2" TO 6"

WATER CUT-OFF MASTIC

PRE-MOLDED PRESSURE-SENSITIVE PIPE

SEAL

STAINLESS STEEL CLAMPING RING

PRIMER

FLEECE-BACKED EPDM

APPROVED SUBSTRATE

APPROVED ADHESIVE

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

/17

/25

9:

E

LI

JA

HU

DU

GG

ER

C

:\U

SE

RS

\E

LI

JA

HU

DU

GG

ER

\B

OX

\R

C

NF

B

UI

LD

IN

GS

S

TR

UC

TU

RE

S\

B

LD

GS

&R

LT

DS

TR

UC

S\

FA

C_

PR

OJ

_F

IL

ES

\G

LA

CI

ER

_R

D\

PO

RT

AG

E\

BB

VC

\B

BV

C_

RO

OF

\20

R

EP

LA

CE

ME

NT

P

RO

JE

CT

\D

RA

W

IN

GS

\B

BV

C

RO

OF

.D W

G;

R10

ALASKA REGION

BEGICH, BOGGS

VISITOR CENTER

ROOF

REPLACEMENT

CHUGACH NF

GLACIER RANGER DISTRICT

NEW ROOF DETAILS

CONTINUED

12/2025

E.DUGGER

E.DUGGER

G.BERG

A-06 11 12

NOT TO SCALE

SCUPPER FLASHING

B9

NOT TO SCALE

PIPE FLASHING

B10

AutoCAD SHX Text

XXXXXX

AutoCAD SHX Text

XXXXXX

AutoCAD SHX Text

XXXXX

AutoCAD SHX Text

XXXXX

AutoCAD SHX Text

COLD PIPE

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

ALUMINUM

CHANNELS

ALUMINUM

CENTER RING

4"

HEAT TRACING CABLE

2'

EXTEND 2' INTO

CONDITIONED SPACE

CHANNELS SHOWN

W/ EXPOSED CABLING FOR

ILLUSTRATIVE PURPOSES

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

/17

/25

9:

E

LI

JA

HU

DU

GG

ER

C

:\U

SE

RS

\E

LI

JA

HU

DU

GG

ER

\B

OX

\R

C

NF

B

UI

LD

IN

GS

S

TR

UC

TU

RE

S\

B

LD

GS

&R

LT

DS

TR

UC

S\

FA

C_

PR

OJ

_F

IL

ES

\G

LA

CI

ER

_R

D\

PO

RT

AG

E\

BB

VC

\B

BV

C_

RO

OF

\20

R

EP

LA

CE

ME

NT

P

RO

JE

CT

\D

RA

W

IN

GS

\B

BV

C

RO

OF

.D W

G;

R10

ALASKA REGION

BEGICH, BOGGS

VISITOR CENTER

ROOF

REPLACEMENT

CHUGACH NF

GLACIER RANGER DISTRICT

DRAIN HEATER PLAN

12/2025

E.DUGGER

E.DUGGER

G.BERG

E-01 12 12

NOTES:

1. PROVIDE AN ICE MELT SYSTEM DESIGNED TO KEEP ROOF DRAINS AND ROOF OVERFLOWS FROM FREEZING. IT IS TO

AUTOMATICALLY OPERATE WHEN THE AIR TEMPERATURE AND MOISTURE IS WITHIN A TARGETED RANGE THAT IS TO BE

FULLY ADJUSTABLE BY BUILDING OPERATORS.

2. SYSTEM TO BE DESIGNED AND SUPPLIED AS AN INTEGRATED SYSTEM BY THE SELECTED MANUFACTURER IN

COORDINATION WITH A LICENSED ELECTRICIAN. PROVIDE COMPLETE SHOP DRAWINGS OF ALL COMPONENTS OF THE WORK

WITH LAYOUT DRAWINGS SHOWING LOCATIONS AND CONNECTIONS OF ALL COMPONENTS FOR A FULL AND COMPLETE

OPERATIONAL SYSTEM. DEMONSTRATE OPERATION OF SYSTEM UPON COMPLETION, MAKING SYSTEM ADJUSTMENTS AS

REQUIRED.

3. CONNECT 3-4 DRAIN HEATERS TO A SINGLE 120V, 20A WIRE CIRCUIT, HOME RUN TO PANEL B. EXACT NUMBER OF HEATERS

ON A CIRCUIT WILL DEPEND ON WATTAGE OF SYSTEM AND WILL BE DETERMINED BY A LICENSED ELECTRICIAN AND CABLE

MANUFACTURER TO PREVENT NUISANCE TRIPPING.

4. EXISTING HEAT TRACE CABLING IN THE DRAIN PIPES SHALL BE REMOVED WHERE HEATERS WILL BE INSTALLED. HEAT

TRACE IN THE DRAINS NOT RECEIVING NEW HEATERS SHALL REMAIN FUNCTIONAL AND NOT BE REMOVED.

5. SYSTEM TO CONSIST OF:

a. NECESSARY JUNCTION BOXES, WITH MINIMAL EQUIPMENT/HARDWARE ON THE ROOF DUE TO EXTREME WIND. BOXES

CONNECTED TO BLDG ELECTRICAL PANELS WITH 3- 10 AGW CONDUCTORS PLUS GROUND IN ¾” EMT. UTILIZE EXISTING

HEAT TRACE BOXES AND CONDUIT TO THE GREATEST EXTENT POSSIBLE.

b. HEAT TRACE CONTROLLER: PROVIDE ONE CONTROLLER TO ALLOW BUILDING OPERATORS TO SET DESIRED

TEMPERATURE AND MOISTURE SETTINGS. CONTROLLER TO INCLUDE OPENINGS FOR INPUT POWER, HEATER CABLE

OUTPUT AND SEPARATE OUTPUT FOR TEMPERATURE SENSOR. ALL HEATERS ARE TO BE CONTROLLED BY ONE CENTRAL

UNIT WITH 1-2 ROOF MOUNTED SENSORS.

c. HEAT TRACE CABLE: 120V MULTI SHIELDED HEATER CABLE, 6 WATT PER FOOT AT 40 DEGREES F. SELF REGULATING

HEATING CABLE. CONNECT TO HEAT TRACE CONTROLLER. RUN HEAT CABLE DOWN ROOF DRAIN APPROXIMATELY 24

INCHES.

d. DE-ICING ARRAY AT EACH ROOF DRAIN CONSISTING OF 6 SLIP FIT DE-ICING JIGS AND FRAME FOR ANCHORING HEAT

CABLE WITHOUT PENETRATING ROOF MEMBRANE. ARRAYS MUST BE ABLE TO WITHSTAND 145 MPH WIND SPEED.

015 15 30 FT

ROOF DRAIN

NEW ROOF DRAIN HEATER

NOT TO SCALE

ROOF DRAIN HEATER

E1

1" = 15'

HEATER LOCATIONS

N

PANEL 'B'

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

BBVC Roof Cover Sheet-PLOT
Sheets and Views
PLOT
OLE1
BBVC Roof-SITE
Sheets and Views
SITE
OLE1
BBVC Roof-Ex Roof
Sheets and Views
Ex Roof
OLE1
BBVC Roof-Photos
Sheets and Views
Photos
OLE1
BBVC Roof-Photos (2)
Sheets and Views
Photos (2)
OLE1
BBVC Roof-New Roof
Sheets and Views
New Roof
OLE1
BBVC Roof-Elevations
Sheets and Views
Elevations
OLE1
BBVC Roof-Details
Sheets and Views
Details
OLE1
BBVC Roof-Details (2)
Sheets and Views
Details (2)
OLE1
BBVC Roof-Details (3)
Sheets and Views
Details (3)
OLE1
BBVC Roof-Details (4)
Sheets and Views
Details (4)
OLE1
BBVC Roof-Heaters
Sheets and Views
Heaters
OLE1
Date1_af_date: 1/21/26
Date2_af_date: 3/2/26
Date3_af_date: 3/11/26
2026-01-21T07:45:24-0900
ELIJAHU DUGGER
2026-03-02T07:47:45-0900
GRIFFITH BERG
2026-03-11T15:52:01-0800
CHRISTOPHER STEWART
2026-03-23T22:30:34-0800
JENNIFER YOUNGBLOOD

Date8_af_date:

File details come from the government source that posted it. Updated .