Attachment_2_Chiller_Cutsheet.pdf
PDF 1 MB Posted
- Attached to
- CHILLERS SERVICE AT LAKE MEAD NRA
- Solicitation number
- 140P8124Q0059
About this file
This document is a technical data sheet for two air-cooled scroll compressor chillers, model AGZ041E, that are part of the Lake Mead Interagency Center Chiller Replacement project. The data sheet provides detailed technical specifications for the chillers, including performance data, dimensions, weights, electrical requirements, and accessories. It also includes information on chiller placement and clearance requirements.
The related federal contract opportunity is a solicitation (140P8124Q0059) for routine quarterly and annual service of the chillers located at the Lake Mead National Recreation Area. The solicitation is being issued by the Department of the Interior, National Park Service, Pacific West Region. The document does not provide any additional details about the solicitation, such as response dates, award information, pricing terms, or set asides.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment_3_Contract_Price_Schedule.docx | DOCX document | |
| Sol_140P8124Q0059.pdf | ||
| Attachment_4_SCA_Wage_Determination.pdf | ||
| Attachment_1_Statement_of_Work.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Technical Data Sheet for C-1 & 2
Job Number: R75GEC Page Prepared Date: 6/23/2021 Job Name: Lake Mead Interagency Center
Chiller Replacement 4 of 17 www.DaikinApplied.com
Job Information Technical Data Sheet
Job Name Lake Mead Interagency Center Chiller Replacement
Date 6/23/2021
Submitted By Gavin Helm
Software Version 12.10
Unit Tag C-1 & 2
Unit Overview
Model Number
Max Capacity ton
Voltage Unit Starter Type
ASHRAE 90.1* LEED Enhanced Refrigerant Management Credit
AGZ041E 33.56 208 V / 60 Hz / 3 Ph Across the Line '07, '10, '13 & '16 Pass
Unit
Unit Type Platform Unit Revision
Air-Cooled Scroll Compressor Chiller Packaged 0A
Head Pressure Tubing
VFD w/o Line Reactors [Low Ambient] Replaceable Filter Dryer with Discharge & Liquid Valves, with
HGBP
Unit Controls Display
Electronic Expansion Valve On Controller only
Refrigerant Type Refrigerant Weight
R410A 46 lb (per unit)
Pump Controls
Dual Evaporator Pumps - Dual Control Output
Approval
ETL/cETL, AHRI & ASHRAE 90.1
Evaporator
Water Volume: 1.9 gal Connection Hand: Left Hand Connections
Connection Size: 2.5 in Insulation: Single Layer Insulation to Suction at each Compressor
Entering Fluid Temperature
Leaving Fluid Temperature
Fluid Type Fluid Flow
Fluid Flow Min / Max
Pressure Drop
Pressure Drop Min / Max
Fouling Factor
57.30 °F 45.00 °F Water 65.10 gpm
36.6/ 152.4 gpm
4.15 ft H₂O
1.10 / 15.2 ft H₂O
0.000100 °F.ft².h/Btu
Note: Evaporator Pressure Drop includes Factory Installed Strainer. Pressure drop without strainer is 3.3. Minimum flow is based on a Variable Flow Pumping System Type and applies to part load conditions only.
Condenser
Coil Fins: MicroChannel Guards: Condenser Coil Wire Grilles only
Design Ambient Air Temperature Altitude Fan Diameter Minimum Design Ambient Temperature
115.0 °F 2500 ft 30.0 in 20.0 °F
Image may not represent ordered unit
For Review
10/05/2021 8:32:07 AM
5 of 17 www.DaikinApplied.com
Unit Performance
Performance Points rated at User Defined DPLV Load Points
Unit Evaporator Condenser
Point # % Load Max
Capacity
% Load Request Capacity
Capacity ton
Input Power kW
IPLV.IP
* (EER)
Btu/W.h
% DPLV
Weighting
DPLV
Btu/W.h
Efficiency
(EER)
Btu/W.h
Fluid Flow gpm
Pressure Drop ft H₂O
Entering Fluid
°F
Leaving Fluid
°F
Ambient Air °F
Altitude ft
Max 100.0 33.56 53.94 17.80 7.466 65.30 3.30 57.30 45.00 115.0 2500
1 99.5 100.0 33.40 53.67 1 15.40 7.468 65.10 3.30 57.30 45.00 115.0 2500
2 74.6 75.0 25.05 25.86 42 11.63 65.10 3.30 54.20 45.00 92.5 2500
3 49.8 50.0 16.70 11.47 45 17.47 65.10 3.30 51.10 45.00 70.0 2500
4 24.9 This point is below the chiller minimum load without hot gas bypass (HGBP) but will run here with use of HGBP
Supplemental Performance Data for Unit Operation at AHRI Conditions
Performance Points at AHRI Standard Condition
Capacity Input Power Efficiency (EER) IPLV.IP* (EER)
38.12 ton 43.28 kW 10.57 Btu/W.h 17.80 Btu/W.h
Performance Points rated at AHRI
Unit Evaporator Condenser
Point # % Load Capacity ton
Input Power kW
Efficiency (EER) Btu/W.h
Fluid Flow gpm
Entering Fluid °F
Leaving Fluid °F
Ambient Air °F
Altitude ft
1 100 38.12 43.28 10.57 91.2 54.00 44.00 95.0 0.000
2 75 28.59 23.16 14.82 91.2 51.50 44.00 80.0 0.000
3 50 19.06 11.64 19.65 91.2 49.00 44.00 65.0 0.000
4 25 9.531 5.221 21.90 91.2 46.50 44.00 55.0 0.000
* IPLV reflects AHRI standard rating conditions with water and does not change with user defined conditions
Note: Evaporator Pressure Drop in this table does Not include strainer. For strainer pressure drop data see 'Evaporator' table on page 1.
Sound (with insulation)
Type of Sound Insulation: Low Noise (Sound Reduction Compressor Blankets)
Sound Pressure (at 30 feet)
63 Hz dB
125 Hz dB
250 Hz dB
500 Hz dB
1 kHz dB
2 kHz dB
4 kHz dB
8 kHz dB
Overall dBA
75% Load dBA
50% Load dBA
25% Load dBA
57 57 56 57 50 48 47 43 58 57 55 54
Sound Power
63 Hz dB
125 Hz dB
250 Hz dB
500 Hz dB
1 kHz dB
2 kHz dB
4 kHz dB
8 kHz dB
Overall dBA
75% Load dBA
50% Load dBA
25% Load dBA
84 84 83 84 77 75 74 70 85 84 82 81 Octave band is non 'A' weighted and overall readings are 'A' weighted. Sound data rated in accordance with AHRI Standard-370.
Physical
Unit
Length* Height Width* Shipping Weight* Operating Weight*
94 in 100 in 88 in 2948 lb 2964 lb
* Shipping and operating weights do not include the weights of any Options or Accessories. Contact Chiller Applications for additional information.
6 of 17 www.DaikinApplied.com
Electrical
Unit Electrical Data
Voltage Starter Type Fan Motor Quantity LRA Fan Motor (each) FLA Fan Motors (each)
208 V / 60 Hz / 3 Ph Across the Line 4 23 A 5.8 A
Power Connection Type: High Short Circuit Current Rating with Single Point Disconnect Switch and Circuit Protection Short Circuit Current Rating: 65 kA
Single Point Power Connection
Minimum Circuit Ampacity
(MCA):
182 A
Recommended Overcurrent Protection Size:
200 A
Maximum Overcurrent Protection Size(MOCP):
200 A
Lug Connection Size: (1) 4 - 300 MCM
Compressor Electrical Data
Compressor Type Compressor Quantity Starter Type
Scroll 4 Across the Line
Circuit #: 1 2
Compressor #: 1 3 2 4
Rated Load Amps (RLA): 34 A 34 A 34 A 34 A
Inrush Current: 240 A 240 A 240 A 240 A
Note: Power wiring connections to the chiller may be done with either copper or aluminum wiring. Wire should be sized per NEC and/or local codes. Wire sizing and wire count must fit in the power connection lug sizing listed above. Please contact your local sales office for more information.
Options
Basic Unit
Control Box Ambient: High Ambient with Exhaust Fans (125ºF maximum) Suction Shut-off Valve: Included
Evaporator Strainer: Factory Installed Evaporator Strainer – 175 PSI Pressure Rating
Control
Communication: BACnet MS/TP
Electrical
Unit Options: 115V Convenience Outlet Water Flow Indicator: Thermal Dispersion Type
Warranty
Unit Startup Domestic
Standard Warranty: 1st Year Entire Unit Parts only
Extended Compressor Warranty: Compressor Only; extended 4 years parts only (5 Years Total)
AHRI Certification
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org
Accessories
Optional
Part Number Description
332325101 RIS Isolator Kit; AGZ: Packaged, Microchannel,Al&Cu Fins, 030-071E (non-Seismic),25-65D,30-65C;
M'Chnl,75-101E (non-S'mc); Al Fin,70C/D;Remote,Al&Cu Fin,30-70E (non-S'mc); Pump Pkg, M'Chnl&Al Fin,30-65E (non-S'mic); Cu Fin,30-55E(non-S'mic)
331776661 Base Frame Grilles; AGZ: 030-071E (without Pump Package)
7 of 17 www.DaikinApplied.com
AGZ-E Close Spacing_Drawing for C-1 & 2
8 of 17 www.DaikinApplied.com
AGZ-E Cl ose S paci ng_Drawi ng for C -1 & 2
AGZ-E Close Spacing Performance 0A
The graphs below are based on individual cases and should not be combined with other scenarios
Case 1: Building or Wall on One Side of Unit
Assumes a solid height wall taller than unit. Refer to Case 4 for partial wall openings
Building or Wall on One Side of Unit
For models AGZ030-101E, maintain a 4 feet minimum from a wall of any height.
For models AGZ110-130E, maintain a 6 feet minimum from a wall of any height.
For models AGZ140-241E, maintain an 8 feet minimum from a wall of any height.
Case 2: Two Units, Side-by-Side
For models 030-180, there must be a minimum of 4 feet between two units placed side-by-side; however, performance may be affected at this distance. For models 191-241, the minimum is 6 feet as closing spacing may cause air recirculation and elevated condenser pressure.
Assuming the requirement of one side having at least 8 feet of service clearance is met, Case 2 figures show performance adjustments as the distance between two units increases.
Two Units, Side-by-Side
Case 2 - Full Load Capacity Reduction
Case 2 – Power Increase
Product Drawing Unit Tag: C-1 & 2
13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 12.10
Product: Air-Cooled Scroll Chiller Project Name:
Model: AGZ-E Sales Office: Norman Wright Mech. Equip.
Corp. Sales Engineer: Gavin Helm June 23, 2021 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-1.0” Dwg Units: in [mm] No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
9 of 17 www.DaikinApplied.com
Case 3: Three or More Units, Side-by-Side
For all models, there must be a minimum distance between any units placed side-by-side; however, performance may be affected at this distance. Minimum distances are: models 030 to 070 - 4 feet, models 075 to 101 - 5 feet, models 110 to 241 - 6 feet. The Case 3 charts below depict Case 3 performance adjustments as the distance between units increases. Data shown is for the middle unit with a unit on each side.
See Case 2 adjustment factors for the two outside units.
Three or More Units, Side-by-Side
Case 3 – Full Load Capacity Reduction
Case 3 – Power Increase
10 of 17 www.DaikinApplied.com
Case 4: Open Screening Walls
Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop. When possible, design these walls such that the combination of their open area and distance from the unit (see chart below) do not require performance adjustment. If the wall opening percentage is less than recommended for the distance to the unit, it should be considered as a solid wall. It is assumed that the wall height is equal to or less than the unit height when mounted on its base support. If the wall height is greater than the unit height, see Case 5: Pit Installation for performance adjustment factors. The distance from the sides of the unit to the side walls must be sufficient for service, such as opening control panel doors. For uneven wall spacing, the distance from the unit to each wall can be averaged providing no distance is less than 4 feet. Values are based on walls on all four sides.
Case 4 - Allowable Wall Open Area
Case 5: Pit Installation
Pit installations can cause operating problems resulting from air recirculation and restriction and require care that sufficient air clearance is provided, safety requirements are met and service access is provided. A solid wall surrounding a unit is substantially a pit and this data should be used. Derates are based on single chiller installation only.
Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit. The grating material and installation design must be strong enough to prevent such accidents, yet provide abundant open area to avoid recirculation problems. Have any pit installation reviewed by the Daikin Applied sales representative prior to installation to ensure it has sufficient air-flow characteristics and approved by the installation design engineer to avoid risk of accident.
Models AGZ030-070E:
The Case 5 figures for models AGZ030-070E show adjustment factors for pit/wall heights of 4 feet, 5 feet, and 6 feet.
Case 5 - Full Load Capacity Reduction and Power Increase
(AGZ030E-070E)
Case 5- Pit Installation
KEY:
- - - - - - - - - - : Power Increase ______________: Capacity Reduction
11 of 17 www.DaikinApplied.com
Models AGZ075-130E:
The Case 5 figures for models AGZ075-130E show adjustment factors for pit/wall heights of 5 feet, 6 feet, and 8 feet.
Case 5 - Full Load Capacity Reduction and Power Increase (AGZ075-130E)
KEY:
- - - - - - - - - - : Power Increase ______________: Capacity Reduction
Models AGZ140-241E:
The Case 5 figures for models AGZ140-241E show adjustment factors for pit/wall heights of 6 feet, 8 feet, and 10 feet.
Case 5 - Full Load Capacity Reduction (AGZ140-180E)
Case 5 - Power Increase (AGZ140-211E)
Case 5 - Full Load Capacity Reduction (AGZ190-241E)
Case 5 - Power Increase (AGZ225-241E)
Jo b
N am e
Jo b
N u m b e r:
A G
Z0
-07
E_C n d G rl_w rp s_D raw in g fo r C -1
Lake M ead
In teragen cy C en te r
C h iller R ep lace m en t
R
EC
o f 1
P age re p are d D ate w w .D aikin A p p lied .co m
/2
/2
AGZ040 -070E_ CndGrl_wr ps_ Drawing for C-1 & 2
Product Drawing Unit Tag: C-1 & 2 Sales Office: Norman Wright Mech. Equip. Corp.
Product: Air-Cooled Scroll Chiller Project Name: Lake Mead Interagency Center Chiller Replacement
Sales Engineer: Gavin Helm Model: AGZ040-071E June 23, 2021 Ver/Rev: Sheet: 1 of 1 Scale: N/A Tolerance: N/A Dwg Units: N/A No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
00 AGZ-E Guards: Condenser Coil Wire Grilles, Front and Rear Wraps, Painted Base
Diagram Notes
Diagram simulates wrap, grille and louver options as selected only. Refrigeration components may vary depending on selected options.
N am e
Jo b
N u m b
Z0
E_P K
G _M
C C
_D raw in g fo r C -1
In teragen cy C en te r
C h iller R ep lace m en t
R o p are d D w .D aikin A p p lied
/2
AGZ041E_ PKG_MCC_Draw ing for C -1 & 2
Sales Engineer: Gavin Helm Model: AGZ041E June 23, 2021 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 1.0" Dwg Units: in [mm] No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
0A AGZ041E Packaged (Microchannel Condenser) Unit Dimensions
PACKAGE UNITS WITH MICROCHANNEL COILS
UNIT MODEL
CG LOCATION, IN (MM)
X Y Z
AGZ041E 39.8 (1011) 45.9 (1166) 38.4 (975)
AGZ046E 38.9 (988) 44.5 (1130) 41.2 (1047)
AGZ051E 39.1 (993) 44.9 (1141) 41.2 (1047)
AGZ056E 39.1 (993) 44.8 (1138) 41.2 (1047)
AGZ061E 39.2 (996) 44.6 (1133) 41.1 (1044)
AGZ066E 39.2 (996) 44.6 (1133) 41.1 (1044)
AGZ071E 36.8 (935) 41.8 (1062) 42.6 (1082)
NOTE
LIFTING WEIGHTS ARE BASED ON UNIT
SHIPPING WEIGHT. MOUNTING WEIGHTS
ARE BASED ON UNIT OPERATING WEIGHT
WITH EVAPORATOR WATER INCLUDED.
SHIPPING AND OPERATING WEIGHTS DO
NOT INCLUDE THE WEIGHTS OF ANY
OPTIONS OR ACCESSORIES.
PACKAGE UNITS WITH MICROCHANNEL COILS
UNIT
MODEL
SHIPPING WEIGHT OPERATING WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER LBS (KG) MOUNTING (OPERATING) WEIGHT LBS (KG)
LBS (KG) LBS (KG) L1 L2 L3 L4 M1 M2 M3 M4
AGZ041E 2948 (1337) 2964 (1345) 1067 (484) 881 (400) 548 (249) 453 (206) 1022 (464) 844 (383) 601 (273) 496 (225)
AGZ046E 3094 (1403) 3112 (1412) 1051 (477) 832 (377) 676 (307) 535 (243) 1021 (463) 809 (367) 715 (324) 567 (257)
AGZ051E 3093 (1403) 3114 (1413) 1049 (476) 837 (380) 671 (304) 536 (243) 1020 (463) 814 (369) 712 (323) 568 (258)
AGZ056E 3106 (1409) 3128 (1419) 1052 (477) 840 (381) 675 (306) 539 (245) 1023 (464) 817 (371) 716 (325) 572 (260)
AGZ061E 3130 (1420) 3155 (1431) 1059 (480) 851 (386) 676 (307) 543 (246) 1031 (468) 828 (376) 718 (326) 577 (262)
AGZ066E 3130 (1420) 3155 (1431) 1059 (480) 851 (386) 676 (307) 543 (246) 1031 (468) 828 (376) 718 (326) 577 (262)
AGZ071E 3472 (1575) 3497 (1586) 1180 (535) 847 (384) 842 (382) 604 (274) 1157 (525) 830 (377) 880 (399) 631 (286)
UNIT
MODEL
EVAP. DIMENSIONS IN (MM)
CONNECTION SIZE
(VICTAULIC)
A
(NO STRAINER)
B
(WITH STRAINER)
AGZ041E 23.5 (597) 2.3 (58) 2.5 (64)
AGZ046E 23.2 (589) 2.0 (51) 2.5 (64)
AGZ051E 22.2 (564) 1.0 (25) 2.5 (64)
AGZ056E 21.5 (546) 5.3 (135) 2.5 (64)
AGZ061E 20.5 (521) 4.3 (109) 2.5 (64)
AGZ066E 20.1 (511) 3.9 (99) 2.5 (64)
AGZ071E 19.1 (485) 2.9 (74) 2.5 (64)
N am e
Jo b
N u m b
ZE_C
learan ce _M
C C
D raw in g fo r C
-1 &
In teragen cy C en te r
C h iller R ep lace m en t
R o p are d D w .D aikin A p p lied
/2
AGZ-E Service Clearance
*NOTE: Additional clearance may be required for proper airflow. Please consult Close Spacing drawings and IOM for additional details.
AGZE_Cleara nce_MCC_Dra wing for C -1 & 2
Sales Engineer: Gavin Helm Model: AGZ-E June 23, 2021 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 1.0" Dwg Units: in [mm] No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
0B
FieldWiring_AGZE_SP_Drawing for C-1 & 2
15 of 17 www.DaikinApplied.com
FieldWiri ng_AGZE_S P_Drawi ng for C -1 & 2
Field Wiring Diagram Unit Tag: C-1 & 2
Product: Air-Cooled Scroll Project Name: Lake Mead Interagency Center Chiller Replacement Model: AGZ030-241E Single-Point Sales Office: Norman Wright Mech. Equip.
Corp. Sales Engineer: Gavin Helm June 23, 2021 Ver/Rev: Sheet 1 of 1 Scale: N/A Tolerance: N/A Dwg Units: N/A
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
AGZ030-241E Single-Point Connection Field Wiring Diagram
0D
N am e
Jo b
N u m b
Iso K it_ R
IS_33
_D raw in g fo r C
-1 &
In teragen cy C en te r
C h iller R ep lace m en t
R o p are d D w .D aikin A p p lied
/2
IsoKit_RIS_332 32510 1_Drawi ng for C -1 & 2
Accessory: Rubber-in-Shear (RIS) Isolator Kit Project Name: Lake Mead Interagency
Sales Engineer: Gavin Helm Kit Part Number: 332325101 June 23, 2021 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 1.0" Dwg Units: in [mm] No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
00 Rubber-in-Shear (RIS) Isolator Kit Dimensions and Placement
Mounting Location
M1 M2 M3 M4
Brown Brown Brown Brown
M3
M1
C o n tr o l P a n el
M4 M2