Attachment_2_ANJO_140P5326Q0003_-_Homestead_Electric_Attachments_9-30-25.pdf

PDF 10 MB Posted

Attached to
ANJO-REPLACE ELECTRIC SUPPLY WIRE
Solicitation number
140P5326Q0012
Issued by

About this file

This is an attachments document for a federal contract involving replacement of underground electrical service at the Andrew Johnson National Historic Site located in Greeneville, Tennessee.

The project requires installation of new underground electrical infrastructure to replace existing aboveground service. Key technical requirements include: providing new underground conduits from an existing aboveground electrical box (located in a wooded area near the homestead) to the basement of the historic structure, chasing conduits into the basement at an approximate location to be identified by the Contracting Officer in the field, and installing new disconnect switches, transfer switches, distribution panels, and associated electrical components per the provided electrical drawings. The work must comply with Greenville Electric Authority (GEA) standards for underground electric service, including specific requirements for trench depth (minimum 3 feet), conduit sizing (2-1/2 inch or 3 inch primary conduits with 1 inch communication duct), warning tape installation, coupling support straps, expansion couplings, and elbow specifications. All electrical work must follow the 2002 National Electrical Code. The attachments include site maps with aerial and ground-level photographs marking the electrical box location and conduit chase alignment, detailed electrical as-built drawings showing the basement plan with new work, electrical legend and one-line diagrams, and GEA standard specifications for underground service requirements to structures and trench construction details. All facilities and conduit installation must be completed by GEA or approved contractors, with trench inspections required prior to backfill.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ATTACHMENTS

Replace Underground Electric

Andrew Johnson National Historic Site

Site Map

Approximate location where conduits must be chased into basement. Exact location to be identified by the Contracting Officer in the field.

Approximate location of existing aboveground electrical box

Location of Existing Electrical Box Approx. Alignment Where Conduits Must Be Chased Into Basement

Existing Aboveground Electrical Box

Existing Aboveground Electrical Box

Existing Main Disconnect Switch in Basement (shown on left)

Electric As Builts of Homestead Building - Includes Basement & One-Line Diagram

Greenville Electric Authority – Standard Underground Electric Service Requirements to a Structure

4 Feet Min.

6 Feet Max

3 Feet Min.

Ditch Depth

Expansion Coupling

Structure Wall

G E

A P

O

LE

Elbow

Strap Underneath Coupling

Strap (Alternate)

Strap

2-1/2" or 3" and 1"

STANDARD UNDERGROUND ELECTRIC

SERVICE REQUIREMENTS TO A STRUCTURE

100-200 AMP 120/240 Volt Single Phase

Greeneville Energy Authority 423-636-6200 www.mygea.net

NOTE: TO SCHEDULE A TRENCH INSPECTION,

CALL 423-636-6241.

SIDE WIRED/OFFSET

METER BASE

COMBINATION METER BASE

WITH DEDICATED CHASE FOR

UTILITY CONDUCTORS

*NOTE: NO LOAD

SIDE CONDUCTORS

ON LINE SIDE OF

METER BASE

**THE REQUIREMENTS OF THIS SPECIFICATION

ARE EFFECTIVE JANUARY 2, 2024 AND SUPERSEDE

ALL PREVIOUS PUBLICATIONS

8"

MAX DIST 215 FEET

NOTE: BEFORE GEA INSTALLS ANY FACILITIES ON PRIVATE PROPERTY, AN EASEMENT WILL NEED TO BE OBTAINED

A

B

C

C

C

D

E

G

B

B

*NOTE: 1 INCH COMMUNICATION DUCT NOT SHOWN IN ITS ENTIRETY FOR CLARITY

12"

Warning Tape

Warning Tape

F

Greenville Electric Authority – Trench Requirements