This is an attachments document for a federal contract involving replacement of underground electrical service at the Andrew Johnson National Historic Site located in Greeneville, Tennessee.
The project requires installation of new underground electrical infrastructure to replace existing aboveground service. Key technical requirements include: providing new underground conduits from an existing aboveground electrical box (located in a wooded area near the homestead) to the basement of the historic structure, chasing conduits into the basement at an approximate location to be identified by the Contracting Officer in the field, and installing new disconnect switches, transfer switches, distribution panels, and associated electrical components per the provided electrical drawings. The work must comply with Greenville Electric Authority (GEA) standards for underground electric service, including specific requirements for trench depth (minimum 3 feet), conduit sizing (2-1/2 inch or 3 inch primary conduits with 1 inch communication duct), warning tape installation, coupling support straps, expansion couplings, and elbow specifications. All electrical work must follow the 2002 National Electrical Code. The attachments include site maps with aerial and ground-level photographs marking the electrical box location and conduit chase alignment, detailed electrical as-built drawings showing the basement plan with new work, electrical legend and one-line diagrams, and GEA standard specifications for underground service requirements to structures and trench construction details. All facilities and conduit installation must be completed by GEA or approved contractors, with trench inspections required prior to backfill.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENTS
Replace Underground Electric
Andrew Johnson National Historic Site
Site Map
Approximate location where conduits must be chased into basement. Exact location to be identified by the Contracting Officer in the field.
Approximate location of existing aboveground electrical box
Location of Existing Electrical Box Approx. Alignment Where Conduits Must Be Chased Into Basement
Existing Aboveground Electrical Box
Existing Aboveground Electrical Box
Existing Main Disconnect Switch in Basement (shown on left)
Electric As Builts of Homestead Building - Includes Basement & One-Line Diagram
Greenville Electric Authority – Standard Underground Electric Service Requirements to a Structure
4 Feet Min.
6 Feet Max
3 Feet Min.
Ditch Depth
Expansion Coupling
Structure Wall
G E
A P
O
LE
Elbow
Strap Underneath Coupling
Strap (Alternate)
Strap
2-1/2" or 3" and 1"
STANDARD UNDERGROUND ELECTRIC
SERVICE REQUIREMENTS TO A STRUCTURE
100-200 AMP 120/240 Volt Single Phase
Greeneville Energy Authority 423-636-6200 www.mygea.net
NOTE: TO SCHEDULE A TRENCH INSPECTION,
CALL 423-636-6241.
SIDE WIRED/OFFSET
METER BASE
COMBINATION METER BASE
WITH DEDICATED CHASE FOR
UTILITY CONDUCTORS
*NOTE: NO LOAD
SIDE CONDUCTORS
ON LINE SIDE OF
METER BASE
**THE REQUIREMENTS OF THIS SPECIFICATION
ARE EFFECTIVE JANUARY 2, 2024 AND SUPERSEDE
ALL PREVIOUS PUBLICATIONS
8"
MAX DIST 215 FEET
NOTE: BEFORE GEA INSTALLS ANY FACILITIES ON PRIVATE PROPERTY, AN EASEMENT WILL NEED TO BE OBTAINED
A
B
C
C
C
D
E
G
B
B
*NOTE: 1 INCH COMMUNICATION DUCT NOT SHOWN IN ITS ENTIRETY FOR CLARITY
12"
Warning Tape
Warning Tape
F
Greenville Electric Authority – Trench Requirements