About this file

This document is a set of drawings related to a federal contract opportunity for an FAA project to install a water treatment system and replace humidifiers at the Anchorage Air Route Traffic Control Center (ARTCC) in Anchorage, Alaska. The project includes demolishing the existing water treatment system in Mechanical Room 61, replacing 13 existing humidifiers, installing reverse osmosis treated water lines to new and existing humidifiers, and installing new electrical and control devices. The estimated cost of the project is between $500,000 and $750,000. The solicitation has no set-aside and is open to all businesses. Key dates include a site visit on November 12, 2024 and offers due by December 3, 2024.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OLD DAVIS HIGHWAY

A D

M

I N I S T R A T

I O N

N

OI

TAIVALAREDE

F

DE

PA

RT

MENT OF TRANSPORTATION

UN I T ED STAT ES OF AMER

I C

A

ANCHORAGE, ALASKA (ZAN)

AIR ROUTE TRAFFIC CONTROL CENTER (ARTCC)

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS, CONS.

CANADA

RUSSIA

ARCTIC OCEAN

ALASKA

PRUDHOE BAY

COLD BAY

BEAUFORT SEA

NOME

JUNEAU

ANCHORAGE

FAIRBANKS

GULF OF ALASKA

BERING SEA

CORDOVA

THIS

PROJECT

NOT TO SCALE

LOCATION MAP

PROJECT

LOCATION

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

ENROUT/FSS MANAGER CENTER-ANC

ANCHORAGE

ZAN-1303170-G001

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

COVER SHEET

za n-

0-g0

.d w g

ENROUTE/FSS

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

NOT TO SCALE

VICINITY MAP

DRAWING NO.

DRAWING INDEX

DESCRIPTION

ZAN-1303170-G001 COVER SHEET

ZAN-1303170-G002 DRAWING INDEX

ZAN-1303170-D001 BASEMENT FLOOR MECHANICAL DEMO PLAN

ZAN-1303170-D002 FIRST FLOOR MECHANICAL DEMO PLAN

ZAN-1303170-D003 SECOND FLOOR MECHANICAL DEMO PLAN

ZAN-1303170-D004 DEMO PLAN MECHANICAL ROOMS 64/AF LAB 63, B10, B02 AND 43

ZAN-1303170-D005 DEMO PLAN MECHANICAL ROOMS 245A, 245B AND F08

ZAN-1303170-D006 DEMO PLAN MECHANICAL ROOMS S20, S06 AND 61

ZAN-1303170-D007 MECHANICAL ROOM 61 DEMO PLAN (ELECTRICAL)

ZAN-1303170-M001 ABBREVIATIONS, SYMBOLS LEGEND AND MECHANICAL NOTES

ZAN-1303170-M002 EQUIPMENT SCHEDULES

ZAN-1303170-M003 BASEMENT FLOOR MECHANICAL NEW WORK PLAN

ZAN-1303170-M004 FIRST FLOOR MECHANICAL NEW WORK PLAN

ZAN-1303170-M005 SECOND FLOOR MECHANICAL NEW WORK PLAN

ZAN-1303170-M006 NEW WORK PLAN MECHANICAL ROOMS 64/AF LAB 63, B10, B02 AND 43

ZAN-1303170-M007 NEW WORK PLAN MECHANICAL ROOMS 245A, 245B, AND F08

ZAN-1303170-M008 NEW WORK PLAN MECHANICAL ROOMS S20, S06 AND 61

ZAN-1303170-M009 MECHANICAL DETAILS

ZAN-1303170-M010 CONCEPTUAL NEW WATER TREATMENT SYSTEM DIAGRAM

ZAN-1303170-E001 ELECTRICAL ABBREVIATION AND GENERAL NOTES

ZAN-1303170-E002 MECHANICAL ROOM 61 NEW WORK ELECTRICAL PLAN

ZAN-1303170-E003 MECHANICAL ROOM 61 EQUIPMENT SCHEDULE

ZAN-1303170-E004 MECHANICAL ROOM 61 PANEL SCHEDULES

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

IS

SU

ED

F

OR

ED

M

10/09/2024

STEVE SCHREFFLER

ENROUTE/FSS MANAGER CENTER-ANC

ANCHORAGE

ZAN-1303170-G002

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

DRAWING INDEX

za n-

0-g0

.d w g

ENROUTE/FSS

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

SEE MECH RM B02

ENLARGED PLAN

ON SHEET

ZAN-1303170-D004

SEE MECH RM B10

ENLARGED PLAN

ON SHEET

ZAN-1303170-D004

SEE LAN EQUIPMENT

RM 64/AF LAB 63

ENLARGED PLAN

ON SHEET

ZAN-1303170-D004

SEE MECH RM 43

ENLARGED PLAN

ON SHEET M401

ZAN-1303170-D004

SEE MECH RM 61

ENLARGED PLAN

ON SHEET ZAN-1303170-D006

COPPER PIPING FROM RO WATER

SYSTEM TO BE DEMOLISHED IN ITS ENTIRETY.

PEX PIPING TO REMAIN FOR REUSE

EXISTING 3/4" CW PIPING TO

REMAIN FOR REUSE.

LOCATED IN SPACE BELOW

FLOOR.

EXISTING 3/4" RO PEX PIPING

TO REMAIN FOR REUSE.

LOCATED IN SPACE BELOW

FLOOR.

EXISTING 3/4" PEX PIPING UP

TO FLOOR ABOVE TO REMAIN

FOR REUSE (TYP.)

EXISTING 3/4" PEX PIPING TO

REMAIN FOR REUSE (TYP.)

EXISTING 3/4" PEX PIPING TO

REMAIN FOR REUSE (TYP.)

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

ENROUTE/FSS MANAGER CENTER-ANC

ANCHORAGE

ZAN-1303170-D001

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

BASEMENT FLOOR MECHANICAL

DEMO PLAN

za n-

0-d0

.d w g

ENROUTE/FSS

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

SHEET NOTES:

1. EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE FROM RECORD

DRAWINGS AND NON-DESTRUCTIVE WALK-THROUGHS OF THE FACILITY.

ACTUAL SYSTEMS MAY VARY FROM THE INFORMATION INDICATED ON

THE DRAWINGS. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS,

LOCATIONS, AND SIZES BEFORE START OF WORK.

2. BUILDING COMPONENTS DAMAGED BY ASSOCIATION TO REMODEL

WORK THAT ARE TO REMAIN SHALL BE PATCHED AND REPAIRED TO

MATCH EXISTING. COORDINATE WITH ARCHITECTURAL.

3. PROTECT ALL MECHANICAL EQUIPMENT, CONTROL WIRING, PIPING, AND

DUCTWORK THAT IS TO REMAIN FROM DAMAGE DURING REMODEL..

4. DO NOT ROUTE ANY PIPING IN EXTERIOR WALLS UNLESS OTHERWISE

INDICATED.

5. PRESENT ALL REMOVED AND SALVAGED EQUIPMENT TO THE BUILDING

OWNER. IF NOT DESIRED TO BE KEPT BY THE OWNER, CONTRACTOR

SHALL HAUL OFF AND PROPERLY DISPOSE OF REMOVED EQUIPMENT.

SCALE: 3/32" = 1'-0"

BASEMENT FLOOR MECHANICAL DEMO PLAN

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

8' 0 8' 24'

SCALE: 3/32" = 1'-0"

16'

KEY PLAN

EXISTING 3/4" PEX PIPING THAT CONNECTS

WITH EXISTING IW PIPING TO REMAIN

EXISTING 3/4" PEX PIPING

TO REMAIN FOR REUSE (TYP.)

SEE MECH RM F08

ENLARGED PLAN

ON SHEET

ZAN-1303170-D005

REMOVE EXISTING CW PIPING

SERVING HUMIDIFIERS BACK TO

MAIN PIPING AND CAP IN

CONCEALED OCATION

EXISTING 3/4" COPPER UP TO

MECH RM 245 TO BE REMOVED IN

ITS ENTIRETY AS REQUIRED TO

REPLACE WITH PEX

EXISTING 3/4" PEX DN TO FLOOR

BELOW TO REMAIN FOR REUSE

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

ENROUTE/FSS MANAGER CENTER-ANC

ANCHORAGE

ZAN-1303170-D002

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

FIRST FLOOR MECHANICAL

DEMO PLAN

za n-

0-d0

.d w g

ENROUTE/FSS

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

SHEET NOTES:

1. EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE FROM RECORD

DRAWINGS AND NON-DESTRUCTIVE WALK-THROUGHS OF THE FACILITY.

ACTUAL SYSTEMS MAY VARY FROM THE INFORMATION INDICATED ON

THE DRAWINGS. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS,

LOCATIONS, AND SIZES BEFORE START OF WORK.

2. BUILDING COMPONENTS DAMAGED BY ASSOCIATION TO REMODEL WORK

THAT ARE TO REMAIN SHALL BE PATCHED AND REPAIRED TO MATCH

EXISTING. COORDINATE WITH ARCHITECTURAL.

3. PROTECT ALL MECHANICAL EQUIPMENT, CONTROL WIRING, PIPING, AND

DUCTWORK THAT IS TO REMAIN FROM DAMAGE DURING REMODEL..

4. DO NOT ROUTE ANY PIPING IN EXTERIOR WALLS UNLESS OTHERWISE

INDICATED.

5. PRESENT ALL REMOVED AND SALVAGED EQUIPMENT TO THE BUILDING

OWNER. IF NOT DESIRED TO BE KEPT BY THE OWNER, CONTRACTOR

SHALL HAUL OFF AND PROPERLY DISPOSE OF REMOVED EQUIPMENT.

SCALE: 3/32" = 1'-0"

FIRST FLOOR MECHANICAL DEMO PLAN

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

NOT TO SCALE

KEY PLAN

8' 0 8' 24'

SCALE: 3/32" = 1'-0"

16'

SEE MECH RM S20

ON SHEET

ZAN-1303170-D006

SEE MECH RM 245

ENLARGED PLAN

ON SHEET

ZAN-1303170-D005

SEE MECH RM S06

ENLARGED PLAN ON

SHEET ZAN-1303170-D006

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

ENROUTE/FSS MANAGER CENTER-ANC

ANCHORAGE

ZAN-1303170-D003

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

SECOND FLOOR MECHANICAL

DEMO PLAN

za n-

0-d0

.d w g

ENROUTE/FSS

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

SHEET NOTES:

1. EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE FROM

RECORD DRAWINGS AND NON-DESTRUCTIVE WALK-THROUGHS OF

THE FACILITY. ACTUAL SYSTEMS MAY VARY FROM THE

INFORMATION INDICATED ON THE DRAWINGS. CONTRACTOR TO

FIELD VERIFY EXISTING CONDITIONS, LOCATIONS, AND SIZES

BEFORE START OF WORK.

2. BUILDING COMPONENTS DAMAGED BY ASSOCIATION TO REMODEL

WORK THAT ARE TO REMAIN SHALL BE PATCHED AND REPAIRED

TO MATCH EXISTING. COORDINATE WITH ARCHITECTURAL.

3. PROTECT ALL MECHANICAL EQUIPMENT, CONTROL WIRING,

PIPING, AND DUCTWORK THAT IS TO REMAIN FROM DAMAGE

DURING REMODEL..

4. DO NOT ROUTE ANY PIPING IN EXTERIOR WALLS UNLESS

OTHERWISE INDICATED.

5. PRESENT ALL REMOVED AND SALVAGED EQUIPMENT TO THE

BUILDING OWNER. IF NOT DESIRED TO BE KEPT BY THE OWNER,

CONTRACTOR SHALL HAUL OFF AND PROPERLY DISPOSE OF

REMOVED EQUIPMENT.

SCALE: 3/32" = 1'-0"

SECOND FLOOR MECHANICAL DEMO PLAN

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

NOT TO SCALE

KEY PLAN

8' 0 8' 24'

(E)AHU-101

(E)AHU-102

(E)HU-101

(E)HU-102

DEMOLISH CONDENSATE DRAIN PIPING

RUNNING FROM THE DISPERSION TUBES AND

HUMIDIFIERS TO THE FLOOR DRAIN (TYP.)

DEMOLISH STEAM PIPING RUNNING

FROM THE HUMIDIFIER UNIT TO THE

DISPERSION TUBES (TYP.)

PIPING AND

HUMIDIFIERS OFFSET

FOR CLARITY

(E)CRU-64

(E)CRU-63

EXISTING CRU UNITS TO

REMAIN FOR REUSE (TYP.2)

NOTE: PIPING SHOWN IS IN FLOOR SPACE BELOW

EXISTING 3/4" CW TO

REMAIN FOR RUSE

EXISTING FLOOR SINK TO

REMAIN FOR RUSE

EXISTING BACKFLOW PREVENTER

TO REMAIN FOR REUSE

EXISTING 3/4" PEX RO PIPING

TO REMAIN FOR REUSE (TYP.)

DEMO ALL EXISTING COPPER

PIPING AS REQUIRED TO REPLACE

WITH PEX AND STAINLESS STEEL

(E)HU-09

(E)HU-10

NOTE: NO WORK TO BE DONE IN

MECHANICAL ROOM 43. ALL EQUIPMENT

AND PIPING TO REMAIN. SHOWN FOR

REFERENCE PURPOSES ONLY.

EXISTING RO WATER PEX

PIPING TO REMAIN FOR

REUSE (TYP.)

(E) AHU-109

(E) AHU-110

(E)AHU-105

(E)AHU-104

(E)AHU-103

(E)HU-104

(E)HU-103

(E)HU-105

DEMOLISH CONDENSATE DRAIN PIPING

RUNNING FROM THE DISPERSION TUBE

TO THE FLOOR DRAIN (TYP.)

DEMOLISH STEAM PIPING RUNNING

FROM THE HUMIDIFIER UNIT TO THE

DISPERSION TUBES (TYP.)

EXISTING

INDUSTRIAL

WATER PIPING TO

REMAIN (TYP.)

DEMOLISH CONDENSATE PIPING

RUNNING FROM THE HUMIDIFIER UNIT

TO FLOOR DRAIN (TYP.)

EXISTING FLOOR

DRAIN TO REMAIN

FOR REUSE (TYP.)

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

ENROUTE/FSS MANAGER CENTER-ANC

ANCHORAGE

ZAN-1303170-D004

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

DEMO PLAN MECHANICAL ROOMS

64/AF, B10, B02 AND 43

za n-

0-d0

.d w g

ENROUTE/FSS

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

KEY NOTES:

REMOVE/DEMOLISH EXISTING HUMIDIFIER AND ASSOCIATED PIPING,

VALVES, FITTINGS, AND CONTROLS. CAP EXISTING IW PIPING AT WALL

PENETRATION.

REMOVE ALL COPPER PIPING DELIVERING RO WATER TO (E)CRU-63/64 AND

CONDENSATE PIPING ROUTED TO FLOOR SINK AS REQUIRED TO REPLACE

WITH PEX OR STAINLESS STEEL PIPING WHERE NECESSARY. COORDINATE

(E)CRU-63/64 DOWNTIME WITH RO SYSTEM UPGRADE AND FACILITY

PERSONAL.

EXISTING PEX PIPING TO RO SYSTEM TO REMAIN FOR RE-USE.

REMOVE/DEMOLISH EXISTING HUMIDIFIERS AND ASSOCIATED PIPING,

VALVES, FITTINGS, AND CONTROLS.

DISCONNECT AND REMOVE EXISTING STEAM AND CONDENSATE PIPING

FROM DISPERSION TUBES AS REQUIRED TO REPLACE WITH NEW.

DISPERSION TUBES TO REMAIN FOR REUSE.

DEMOLISH CW SUPPLY PIPING SERVING HUMIDIFIERS BACK TO MAIN

PIPING. CAP PIPING IN A CONCEALED LOCATION.

HUMIDIFIER AND ASSOCIATED PIPING TO REMAIN FOR REUSE.

SHEET NOTES:

1. EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE FROM RECORD

DRAWINGS AND NON-DESTRUCTIVE WALK-THROUGHS OF THE FACILITY.

ACTUAL SYSTEMS MAY VARY FROM THE INFORMATION INDICATED ON

THE DRAWINGS. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS,

LOCATIONS, AND SIZES BEFORE START OF WORK.

2. BUILDING COMPONENTS DAMAGED BY ASSOCIATION TO REMODEL WORK

THAT ARE TO REMAIN SHALL BE PATCHED AND REPAIRED TO MATCH

EXISTING. COORDINATE WITH ARCHITECTURAL.

3. PROTECT ALL MECHANICAL EQUIPMENT, CONTROL WIRING, PIPING, AND

DUCTWORK THAT IS TO REMAIN FROM DAMAGE DURING REMODEL..

4. DO NOT ROUTE ANY PIPING IN EXTERIOR WALLS UNLESS OTHERWISE

INDICATED.

5. PRESENT ALL REMOVED AND SALVAGED EQUIPMENT TO THE BUILDING

OWNER. IF NOT DESIRED TO BE KEPT BY THE OWNER, CONTRACTOR

SHALL HAUL OFF AND PROPERLY DISPOSE OF REMOVED EQUIPMENT.

6. EXISTING DISPERSION TUBES TO REMAIN IN PLACE FOR REUSE.

SCALE: 1/4" = 1'-0"

EQUIPMENT ROOM 64/AF LAB 63 DEMO PLAN

SCALE: 1/4" = 1'-0"

MECH RM B10 DEMO PLAN

SCALE: 1/4" = 1'-0"

MECH RM B02 DEMO PLAN

SCALE: 1/4" = 1'-0"

MECH ROOM 43 DEMO PLAN

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

4' 0 4' 8'

SCALE: 1/4" = 1'-0"

(E)AHU-204

(E)AHU-203

(E)HU-203

(E)HU-204

3/4" IW UP. REMOVE PIPING IN ITS ENTIRETY

TO FLOOR ABOVE. SEE SHEET ZAN-1303170-D006

FOR CONTINUATION.

REMOVE CW PIPING BACK

TO MAIN. CAP IN

CONCEALED LOCATION

3/4" CW

DEMOLISH CONDENSATE DRAIN PIPING

RUNNING FROM THE HUMIDIFIER TO THE FLOOR

DRAIN (TYP.)

DEMOLISH STEAM PIPING RUNNING

FROM THE HUMIDIFIER UNIT TO THE

DISPERSION TUBES (TYP.)

REMOVE BACKFLOW PREVENTER AND

ASSOCIATED PIPING AND APPURTENANCES

EXISTING FLOOR DRAIN TO

REMAIN FOR REUSE

DEMOLISH CONDENSATE

DRAIN PIPING RUNNING

FROM THE DISPERSION

TUBES TO THE FLOOR DRAIN

(TYP.)

(E)AHU-245A

(E)HU-245A

EXISTING COPPER PIPING SERVING

HUMIDIFIERS TO REMAIN TO SERVE

EXISTING TRAP PRIMERS

DEMOLISH CONDENSATE DRAIN

PIPING RUNNING FROM THE

CONDENSATE COOLER TO THE

FLOOR DRAIN (TYP.)

PIPING DOWN THROUGH FLOOR TO

LEVEL BELOW TO REMAIN TO KEEP

SERVING EXISTING TRAP PRIMERS IN

MECHANICAL ROOM

(E)AHU-245B

(E)HU-245B

EXISTING COPPER PIPING

SERVING HUMIDIFIERS TO

REMAIN TO SERVE EXISTING

TRAP PRIMERS

DEMOLISH STEAM PIPING RUNNING

FROM THE HUMIDIFIER UNIT TO THE

DISPERSION TUBES (TYP.)

DEMOLISH CONDENSATE DRAIN

PIPING RUNNING FROM THE

CONDENSATE COOLER TO THE

FLOOR DRAIN (TYP.)

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

ENROUTE/FSS MANAGER CENTER-ANC

ANCHORAGE

ZAN-1303170-D005

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

DEMO PLAN MECHANICAL ROOMS

245A, 245B AND FO8

za n-

0-d0

.d w g

ENROUTE FSS

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

KEY NOTES:

REMOVE/DEMOLISH EXISTING HUMIDIFIERS AND ASSOCIATED

PIPING, VALVES, FITTINGS, AND CONTROLS IN THEIR ENTIRETY.

DISCONNECT AND REMOVE EXISTING STEAM AND CONDENSATE

PIPING FROM DISPERSION TUBES AS REQUIRED TO REPLACE

WITH NEW. DISPERSION TUBES TO REMAIN FOR REUSE.

SHEET NOTES:

1. EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE FROM RECORD

DRAWINGS AND NON-DESTRUCTIVE WALK-THROUGHS OF THE

FACILITY. ACTUAL SYSTEMS MAY VARY FROM THE INFORMATION

INDICATED ON THE DRAWINGS. CONTRACTOR TO FIELD VERIFY

EXISTING CONDITIONS, LOCATIONS, AND SIZES BEFORE START OF

WORK.

2. BUILDING COMPONENTS DAMAGED BY ASSOCIATION TO REMODEL

WORK THAT ARE TO REMAIN SHALL BE PATCHED AND REPAIRED TO

MATCH EXISTING. COORDINATE WITH ARCHITECTURAL.

3. PROTECT ALL MECHANICAL EQUIPMENT, CONTROL WIRING, PIPING,

AND DUCTWORK THAT IS TO REMAIN FROM DAMAGE DURING

REMODEL..

4. DO NOT ROUTE ANY PIPING IN EXTERIOR WALLS UNLESS

OTHERWISE INDICATED.

5. PRESENT ALL REMOVED AND SALVAGED EQUIPMENT TO THE

BUILDING OWNER. IF NOT DESIRED TO BE KEPT BY THE OWNER,

CONTRACTOR SHALL HAUL OFF AND PROPERLY DISPOSE OF

REMOVED EQUIPMENT.

6. EXISTING DISPERSION TUBES TO REMAIN IN PLACE FOR REUSE.

SCALE: 1/4" = 1'-0"

MECH RM 245A DEMO PLAN

SCALE: 1/4" = 1'-0"

MECH RM 245B DEMO PLAN

SCALE: 1/4" = 1'-0"

MECH RM F08 DEMO PLAN

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

4' 0 4' 8'

(E)AHU-302

(E)AHU-301 (E)HU-301

(E)HU-302

3/4" IW FROM BELOW. REMOVE PIPING IN ITS

ENTIRETY TO FLOOR BELOW. SEE SHEET

ZAN-1303170-D005 FOR CONTINUATION.

DEMOLISH STEAM PIPING RUNNING

FROM THE HUMIDIFIER UNIT TO THE

DISPERSION TUBES (TYP.)

DEMOLISH CONDENSATE

DRAIN PIPING RUNNING

FROM THE DISPERSION TUBE

TO THE FLOOR DRAIN (TYP.)

DEMOLISH CONDENSATE DRAIN

PIPING RUNNING FROM THE

DISPERSION TUBES AND

HUMIDIFIERS TO THE FLOOR

DRAIN (TYP.)

EXISTING FLOOR DRAIN TO

REMAIN FOR REUSE (TYP.)

(E)AHU-303

(E)HU-303

(E)AHU-304

(E)HU-304

3 3

DEMOLISH STEAM PIPING RUNNING

FROM THE HUMIDIFIER UNIT TO THE

DISPERSION TUBES (TYP.)

DEMOLISH CONDENSATE DRAIN

PIPING RUNNING FROM THE

HUMIDIFIER TO THE FLOOR

DRAIN (TYP.) EXISTING BACKFLOW

PREVENTER TO REMAIN

DEMOLISH CONDENSATE DRAIN

PIPING RUNNING FROM THE

DISPERSION TUBES TOT HE

FLOOR DRAIN (TYP.)

EXISTING

FLOOR DRAIN

TO REMAIN

FOR REUSE

(TYP.)

(E)RO SYSTEM 1

3/4" CW SUPPLY AND 3/4"PEX PIPING SERVING

RO SYSTEM TO REMAIN AN BE RECONNECTED

TO NEW SYSTEM.5

EXISTING FLOOR SINK TO REMAIN FOR REUSE.

ALL DRAINS FROM EXISTING RO SYSTEM TO BE

DEMOLISHED.

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

ENROUTE/FSS MANAGER CENTER-ANC

ANCHORAGE

ZAN-1303170-D006

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

DEMO PLAN MECHANICAL ROOMS

S20, S06, AND 61

za n-

0-d0

.d w g

ENROUTE/FSS

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

KEY NOTES:

DEMO EXISTING RO SYSTEM IN ITS ENTIRETY. INCLUDING BUT NOT

LIMITED TO PIPING, FITTINGS, FILTERS, PUMPS, AND STORAGE TANKS.

COORDINATE DEMOLITION WITH FACILITY SERVICES TO MINIMIZE

DOWNTIME AND IMPACT ON THE FACILITY.

DISCONNECT AND REMOVE EXISTING STEAM AND CONDENSATE PIPING

FROM DISPERSION TUBES AS REQUIRED TO REPLACE WITH NEW.

DISPERSION TUBE TO REMAIN FOR REUSE.

REMOVE/DEMOLISH EXISTING HUMIDIFIERS AND ASSOCIATED PIPING,

VALVES, FITTINGS, AND CONTROLS. HUMIDIFIER IS SERVED FROM

EXISTING CW LINES. DEMO AND CAP CW BRANCH PIPING SERVING

HUMIDIFIERS IN A CONCEALED LOCATION.

DEMOLISH COPPER PIPE SERVING EXISTING RO SYSTEM IN ITS

ENTIRETY AS REQUIRED TO REPLACE WITH PEX PIPING.

EXISTING 3/4"CW AND 3/4"RO PEX PIPING TO REMAIN TO BE

RECONNECTED AND REUSED WITH NEW SYSTEM. PIPE ROUTES

THROUGH WALL AND BENEATH FLOOR OF ADJACENT SPACES.

SHEET NOTES:

1. EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE FROM RECORD

DRAWINGS AND NON-DESTRUCTIVE WALK-THROUGHS OF THE

FACILITY. ACTUAL SYSTEMS MAY VARY FROM THE INFORMATION

INDICATED ON THE DRAWINGS. CONTRACTOR TO FIELD VERIFY

EXISTING CONDITIONS, LOCATIONS, AND SIZES BEFORE START OF

WORK.

2. BUILDING COMPONENTS DAMAGED BY ASSOCIATION TO REMODEL

WORK THAT ARE TO REMAIN SHALL BE PATCHED AND REPAIRED TO

MATCH EXISTING. COORDINATE WITH ARCHITECTURAL.

3. PROTECT ALL MECHANICAL EQUIPMENT, CONTROL WIRING, PIPING,

AND DUCTWORK THAT IS TO REMAIN FROM DAMAGE DURING

REMODEL..

4. DO NOT ROUTE ANY PIPING IN EXTERIOR WALLS UNLESS

OTHERWISE INDICATED.

5. PRESENT ALL REMOVED AND SALVAGED EQUIPMENT TO THE

BUILDING OWNER. IF NOT DESIRED TO BE KEPT BY THE OWNER,

CONTRACTOR SHALL HAUL OFF AND PROPERLY DISPOSE OF

REMOVED EQUIPMENT.

6. EXISTING DISPERSION TUBES TO REMAIN IN PLACE FOR REUSE.

SCALE: 1/4" = 1'-0"

MECH RM S20 DEMO PLAN

SCALE: 1/4" = 1'-0"

MECH RM S06 DEMO PLAN

SCALE: 1/4" = 1'-0"

MECH RM 61 DEMO PLAN

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

4' 0 4' 8'

(D) CONTROL POWER BOX

(D) CONTROLS 208VAC

HEATER CONTROLS

(D) EXIST WATER

PANEL 61B)

(ROUTED WITHIN WALL TO

(D) EXIST SOFTNER OUTLET

TYP.

TYP.

CONTROLS

(D) EXIST RO POWER

TYP. OF 3

(D) EXIST RO OUTLET

PANEL 61B

CONT ACROSS RM TO

(DEMO BY OTHERS)

EXIST VIKING PANEL

(SEE KEY NOTE 2)

EXISTING VIKING PANEL

(SEE KEY NOTE 2)

EXIST TRAP PRIMER

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/0

/2

:3

:0

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

z a n -1

-d

.d w g

8 234567

H

G

F

E

D

C

A

B

(E)RO SYSTEM

PANEL E61APANEL E61B

IS

S

U E

D F

O R

E D

M

INFRASTRUCTURE ENG CENTER-ANC

ANCHORAGE

ZAN-1303170-D007

ARTCC

INSTALL WATER TREATMENT SYSTEM

MECHANICAL ROOM 61

ELECTRICAL DEMO PLAN

z a n -1

-d

.d w g

INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N S

T R

U C

T

IO

N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PROJECT ENGINEER

1303170

AK

MECH RM 61 ELECTRICAL DEMO FLOOR PLAN

SCALE: 3/4" = 1'-0"D007

1' 0 1' 3'

SCALE: 3/4" = 1'-0"

2'

SHEET NOTES:

1. EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE FROM RECORD

DRAWINGS AND NON-DESTRUCTIVE WALK-THROUGHS OF THE FACILITY.

ACTUAL SYSTEMS MAY VARY FROM THE INFORMATION INDICATED ON THE

DRAWINGS. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS,

LOCATIONS, AND SIZES BEFORE START OF WORK.

2. BUILDING COMPONENTS DAMAGED BY ASSOCIATION TO REMODEL WORK THAT

ARE TO REMAIN SHALL BE PATCHED AND REPAIRED TO MATCH EXISTING.

COORDINATE WITH ARCHITECTURAL.

3. PROTECT ALL EXISTING EQUIPMENT, CONTROL AND POWER WIRING, PIPING,

AND DUCTWORK THAT IS TO REMAIN FROM DAMAGE DURING REMODEL.

4. DO NOT ROUTE ANY CONDUIT IN EXTERIOR WALLS UNLESS OTHERWISE

INDICATED.

5. PRESENT ALL REMOVED AND SALVAGED EQUIPMENT TO THE BUILDING

OWNER. IF NOT DESIRED TO BE KEPT BY THE OWNER, CONTRACTOR SHALL

HAUL OFF AND PROPERLY DISPOSE OF REMOVED EQUIPMENT.

6. MAINTAIN REQUIRED CLEARANCES FOR NEW AND EXISTING EQUIPMENT PER

NFPA 70 (NEC). COMPLY WITH FAA ORDER 1217F FOR ALL INDOOR ELECTRICAL

WORK.

7. COORDINATE OUTAGES WITH FAA. ONLY FAA PERSONAL MAY BE

ENERGIZE/RE-ENERGIZE CIRCUIT BREAKERS AND OPERATE VALVES. SEE

ZAN1303170-E004 FOR PANEL SCHEDULES.

NEW ROUTING.

SHUT OFF VIKING PANEL AND TRAP PRIMER CIRCUITS. SEE ZAN-1303170-E002 FOR

COORDINATE OUTAGE WITH FAA AND FIRE ALARM CONTRACTOR HONEYWELL TO

CONDUCTORS FOR POWER AND CONTROLS.

INCLUDING BUT NOT LIMITED TO OUTLETS, JUNCTION BOXES, CONDUIT AND

DEMO EXISTING ELECTRICAL EQUIPMENT FEEDING EXISTING RO SYSTEM,

KEY NOTES:

MECH RM 61 ELECTRICAL DEMO ELEVATION PLAN

NOT TO SCALED007

PANEL

EXISTING VIKING

PRIMER

EXIST TRAP

Jordan Batac COMMENT Text Box

JORDAN BATAC

Jordan Batac COMMENT Text Box

STEVEN SCHREFFLER

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

INFRASTRUCTURE ENG CENTER-ANC

ANCHORAGE

ZAN-1303170-M001

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

ABBREVIATIONS, SYMBOL LEGEND

MECHANICAL NOTES

za n-

0-m

1.

dw g

INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

ABBREVIATIONS

REDUCER

TEE DOWN

PIPE CONTINUATION

PIPE PENETRATION

PIPE UP

PIPE DOWN

FLOW DIRECTION

CHECK VALVE

ISOLATION VALVE

3-WAY CONTROL VALVE

SOLENOID VALVE

FLOW CONTROL VALVE

UNION

M

S

STRAINER

BALANCE VALVE

FLEXIBLE PIPING

AUTOMATIC AIR VENT

W/ ISOLATION

TEMPERATURE GAUGE

PRESSURE GAUGE

PIPING SYMBOLS

ANNOTATIONSGENERAL SYMBOLS

ROOM NAME/

NUMBER DESIGNATOR

MECH. RM.

EXISTING EQUIPMENT(E)CP-1

NEW EQUIPMENTCP-1

1.

FLUID FLOWTHERMOSTAT

HUMIDISTAT

SENSOR FLOOR DRAIN

FLOOR SINK

PIPING

OTHER HVAC SYMBOLS

NOTE SPECIFIC TO

LOCATION INDICATED

NOTE APPLIES TO

ENTIRE SHEET.

AAV AUTOMATIC AIR VENT

AFF ABOVE FINISH FLOOR

AG ABOVE GROUND

AHU AIR HANDLING UNIT

ARCH ARCHITECT OR ARCHITECTURAL

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS

BTU BRITISH THERMAL UNIT

BV BALANCING VALVE

CC COOLING COIL

CFM CUBIC FEET PER MINUTE

CLG CEILING

CO CLEANOUT

CU COPPER

CUH CABINET UNIT HEATER

CW COLD WATER

DB DRY BULB

ø DIAMETER OR PHASE

DEMO DEMOLISH

DN DOWN

DWG DRAWING

(E) EXISTING

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

EG ETHYLENE GLYCOL

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

FCO FLOOR CLEANOUT

F.D. FIRE DAMPER

FD FLOOR DRAIN

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY OR FUSIBLE OIL SAFETY

FSD FIRE SMOKE DAMPER

FTR FINNED TUBE RADIATION

G LOW PRESSURE GAS

GAL GALLONS

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

HB HOSE BIBB

HC HEATING COIL

HP HORSEPOWER

HR HOUR

HTG HEATING

HGR HEATING GLYCOL RETURN

HGS HEATING GLYCOL SUPPLY

HWC HOT WATER CIRCULATION

HWR HEATING WATER RETURN

HWS HEATING WATER SUPPLY

HW HOT WATER

HX HEAT EXCHANGER

IW IRRIGATION WATER

LAT LEAVING AIR TEMPERATURE

LF LINEAL FOOT

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH THOUSANDS BTU PER HOUR

MFR MANUFACTURER

MIN MINIMUM OR MINUTES

MUA MAKE UP AIR

NC NORMALLY CLOSED

N.I.C. NOT IN CONTRACT

NO NORMALLY OPEN

NPT NATIONAL PIPE THREAD

NSF NATIONAL SANITATION FOUNDATION

NTS NOT TO SCALE

OA OUTSIDE AIR

PG PROPYLENE GLYCOL

PH PHASE

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PEX RO WATER PIPING

INDUSTRIAL COLD WATER PIPING

STEAM PIPING

1. THE DRAWINGS AND SPECIFICATIONS INDICATE THE GENERAL DESIGN AND ARRANGEMENT OF PIPES, EQUIPMENT, SYSTEMS, ETC. INFORMATION SHOWN IS DIAGRAMMATIC AND DOES NOT NECESSARILY INDICATE EVERY REQUIRED OFFSET OR FITTING. MINOR DEVIATIONS FROM DRAWINGS MAY BE REQUIRED TO AVOID CONFLICTS WITH EXISTING

WORK OR TO PROVIDE BETTER ACCESSIBILITY TO EQUIPMENT.

2. THE CONTRACTOR WILL INSTALL ALL MECHANICAL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS.

3. STORE PIPES TO BE USED DURING INSTALLATION SUCH THAT THEY ARE PROTECTED FROM DUST, DEBRIS, AND

MOISTURE. KEEP PIPE ENDS SEALED UNTIL JUST BEFORE JOINING.

4. INSTALL EQUIPMENT SO THAT SERVICE AND ELECTRICAL CLEARANCES AS DEFINED BY MANUFACTURER ARE

MAINTAINED.

5. INSTALL ALL PIPING AND TUBING IN A NEAT, WELL ORGANIZED MANNER WITH SERVICES RUNNING PARALLEL WITH

PRIMARY LINES OF THE BUILDING CONSTRUCTION.

6. PRESSURE TEST NEW PLUMBING LINES IN ACCORDANCE WITH THE INTERNATIONAL PLUMBING CODE (IPC).

7. SLOPE ALL DRAIN TUBING 1/4" PER FOOT TOWARDS DRAIN OR SINK.

MECHANICAL NOTES

EXISTING WORK

DEMOLITION/NEW WORK

CONNECT TO EXISTING

RA RETURN AIR

RCP RADIANT CEILING PANEL

REQD REQUIRED

RL RAIN LEADER

RO REVERSE OSMOSIS

RPM REVOLUTION PER MINUTE

SA SUPPLY AIR

SD SMOKE DETECTOR

SL SOUNDLINING

SP STATIC PRESSURE

SSTL STAINLESS STEEL

T, TEMP TEMPERATURE

TAB TEST, ADJUST & BALANCE

TP TRAP PRIMER

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

UF UNDER FLOOR

UG UNDERGROUND

UH UNIT HEATER

US UNDERSLAB

V VENT OR VOLTS

VAC VOLTAGE ALTERNATING CURRENT

VAV VARIABLE AIR VOLUME

VTR VENT THRU ROOF

W WASTE

WB WET BULB

W/ WITH

WC WATER CLOSET

W.C. WATER COLUMN

WCO WALL CLEANOUT

WH WATER HEATER

WHA WATER HAMMER ARRESTOR

1.

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

CONDENSATE DRAIN PIPING

COMPUTER ROOM AIR CONDITIONING UNIT SCHEDULE (EXISTING, FOR INFORMATION ONLY)

TAG LOCATION

AREA

SERVED

OPERATIN

MODE

FAN COOLING DATA REHEAT DATA HUMIDIFIER FILTER ELECTRICAL DATA

# OF

WHEELS

CFM RPM

ESP

(IN.

W.G.)

TSP

(IN.

W.G.)

MOTOR

HP

CAPACITY AIR WATER

MIN.

ROWS

WPD

(FT.

W.G.)

MAX.

FACE

VEL.

(FPM)

CAP.

(MBH)

AIR WATER

MIN.

ROWS

WPD

(FT.

W.G.)

KW LBS/HR TYPE

MERV

RATING

V PH HZ

TOTAL

(MBH)

SENS.

(MBH)

EDB

(°F)

EWB

(°F)

LDB

(°F)

LWB

(°F)

EWT

(°F)

LWT

(°F)

GPM

EDB

(°F)

LDB

(°F)

EWT

(°F)

LWT

(°F)

GPM

(E)CRU-63 ROOM 63

ROOMS 62

& 63

NORMAL 1 3500 690 1.0 2.3 5.0 75.8 75.8 74.4 58.5 52.5 49.3 44.0 54.0 16.8 4 8.6 300 94.5 60 85.0 200 165 5.0 2 10.8 4.8 11.0 TYPE B MERV 7 460 3 60

EMERGENCY 1 5700 1125 1.0 2.8 5.0 112.8 112.8 74.0 58.5 55.2 50.6 44.0 54.0 25.4 4 18.6 500 94.5 60 75.0 200 165 5.0 2 10.8 4.8 11.0 TYPE B MERV 7 460 3 60

(E)CRU-64 ROOM 64

ROOMS 64

& 65

NORMAL 1 3500 690 1.0 2.3 5.0 75.8 75.8 74.4 58.5 52.5 49.3 44.0 54.0 16.8 4 8.6 300 94.5 60 85.0 200 165 5.0 2 10.8 4.8 11.0 TYPE B MERV 7 460 3 60

EMERGENCY 1 5700 1125 1.0 2.8 5.0 112.8 112.8 74.0 58.5 55.2 50.6 44.0 54.0 25.4 4 18.6 500 94.5 60 75.0 200 165 5.0 2 10.8 4.8 11.0 TYPE B MERV 7 460 3 60

HUMIDIFIER SCHEDULE

TAG LOCATION AHU SERVED AREA SERVED TYPE

MAXIMUM STEAM

CAPACITY

(LB/HR)

ELECTRICAL DATA

BASIS OF DESIGN

HUMIDIFIER

TO BE REPLACED

CURRENTLY

SERVED BY RO

SYSTEM

NOTES

TOTAL POWER

(KW)

V PH AMPS

MANUFACTURER MODEL

HU-101 ROOM B10 AHU-101 TECH/OPS ELECTRIC 91.2 32 480 3 38.5 DRISTEEM VLC-32-2 YES NO SEE NOTE 1

HU-102 ROOM B10 AHU-102 TECH/OPS ELECTRIC 91.2 32 480 3 38.5 DRISTEEM VLC-32-2 YES NO SEE NOTE 1

HU-103 ROOM B02 AHU-103 TECH/OPS ELECTRIC 119.7 42 480 3 50.5 DRISTEEM VLC-42-2 YES NO SEE NOTE 1

HU-104 ROOM B02 AHU-104 TECH/OPS ELECTRIC 119.7 42 480 3 50.5 DRISTEEM VLC-42-2 YES NO SEE NOTE 1

HU-105 ROOM B02 ANU-105 TECH/OPS ELECTRIC 119.7 42 480 3 50.5 DRISTEEM VLC-42-2 YES NO SEE NOTE 1

HU-203 ROOM F08 AHU-203 TECH/OPS ELECTRIC 91.2 32 480 3 38.5 DRISTEEM VLC-32-2 YES NO SEE NOTE 1

HU-204 ROOM F08 AHU-204 TECH/OPS ELECTRIC 91.2 32 480 3 38.5 DRISTEEM VLC-32-2 YES NO SEE NOTE 1

HU-301 ROOM S06 AHU-301 TECH/OPS ELECTRIC 71.3 25 480 3 30.1 DRISTEEM VLC-25-1 YES NO SEE NOTE 1

HU-302 ROOM S06 AHU-302 TECH/OPS ELECTRIC 71.3 25 480 3 30.1 DRISTEEM VLC-25-1 YES NO SEE NOTE 1

HU-303 ROOM S20 AHU-303 TECH/OPS ELECTRIC 91.2 32 480 3 38.5 DRISTEEM VLC-32-2 YES NO SEE NOTE 1

HU-304 ROOM S20 AHU-304 TECH/OPS ELECTRIC 91.2 32 480 3 38.5 DRISTEEM VLC-32-2 YES NO SEE NOTE 1

HU-245A ROOM 245 AHU-245A

BASEMENT &

FIRST FLOOR

ELECTRIC 63 21 480 3 25.3 DRISTEEM VM-21 YES YES SEE NOTES 1,2

HU-245B ROOM 245 AHU-245B

FIRST & SECOND

FLOOR

ELECTRIC 42 14 480 3 16.8 DRISTEEM VM-14 YES YES SEE NOTES 1,2

(E)HU-09 ROOM 43 AHU-09 BASEMENT VAV ELECTRIC 48 16 480 3 19.2 DRISTEEM VM-16 NO YES

EXISTING TO REMAIN FOR

REUSE

(E)HU-10 ROOM 43 AHU-10 FIRST FLOOR VAV ELECTRIC 48 16 480 3 19.2 DRISTEEM VM-16 NO YES

EXISTING TO REMAIN FOR

REUSE

1. PROVIDE HUMIDIFIER WITH 4 LEG STANDS AND HARDWARE, VAPOR-LOGIC CONTROLLER WITH BACNET CAPABILITIES, AND CONTROL CABINET TO BE MOUNTED ON FRONT OR WITHIN 50' OF HUMIDIFIER UNIT.

2. PROVIDE WITH DRANE-KOOLER WATER TEMPERING DEVICE. FOLLOW ALL MANUFACTURER PROVIDED INSTALLATION INSTRUCTIONS/REQUIREMENTS.

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

INFRASTRUCTURE ENG CENTER-ANC

ANCHORAGE

ZAN-1303170-M002

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

EQUIPMENT SCHEDULES

za n-

0-m

2.

dw g

INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

ORDER OF OPERATIONS/WORKFLOW

INSTALL TEMPORARY WATER LINES (HOSES OR PEX PIPING) CARRYING CITY WATER TO EXISTING HUMIDIFIERS

TO MAINTAIN HUMIDIFICATION DURING EXISTING RO SYSTEM DEMOLITION.

REMOVE AND REPLACE EXISTING WATER TREATMENT SYSTEM AND ANY EXISTING PIPING TO HUMIDIFIERS

THAT IS NOT TO REMAIN FOR REUSE.

START-UP WATER TREATMENT SYSTEM.

SWITCH TO TREATED WATER LINES AT EACH HUMIDIFIER. FINAL PERMANENT WATER LINES ARE TO ONLY CONTAIN TREATED WATER. COORDINATE WITH BUILDING PERSONNEL WHEN SWAPPING TO NEW WATER LINES AS AHU AND HUMIDIFIER OPERATION WILL NEED TO BE COORDINATED. ONLY ONE HUMIDIFIER PER SET OF REDUNDANT AHUS CAN BE SHUT DOWN AT A TIME. FULL VENTILATION AND HUMIDIFICATION OF THE BUILDING

MUST BE MAINTAINED AT ALL TIMES.

REPLACE EXISTING HUMIDIFIERS WHILE SWAPPING OVER TO NEW WATER LINES. SUCCESSFULLY OPERATE

NEW HUMIDIFIERS BEFORE CONTINUING TO REPLACE THE NEXT.

ANY EXISTING STAND-ALONE HUMIDIFIERS (WHERE NO REDUNDANT HUMIDIFIER/AHU IS PRESENT) SHALL BE INSTALLED LAST WHEN CONTRACTOR HAS THE WORKFLOW DIALED. THESE SHALL BE REPLACED ONE AT A

TIME AND SUCCESSFUL OPERATION VERIFIED BEFORE CONTINUING TO REPLACE THE NEXT.

AIR HANDLING UNIT SCHEDULE (EXISTING, FOR INFORMATION ONLY)

TAG LOCATION AREA SERVED

SUPPLY FAN DATA COOLING COIL DATA HEATING COIL ELECTRICAL DATA

SUPPLY

AIR

(CFM)

MINIMU

M OA

(CFM)

TSP

(IN.

W.G.)

ESP

(IN.

W.G.)

FAN

BHP

CAPACITY AIR WATER

ROWS

APD

(IN.

W.G.)

WPD

(FT.

W.G.)

CAP. AIR WATER

ROWS

APD

(IN.

W.G.)

WPD

(FT.

W.G.)

HP V PH

TOTAL

(MBH)

SENS.

(MBH)

EDB

(°F)

EWB

(°F)

LDB

(°F)

LWB

(°F)

EWT

(°F)

LWT

(°F)

GPM

TOTAL

(MBH)

EDB

(°F)

LDB

(°F)

EWT

(°F)

LWT

(°F)

GPM

AHU-101 ROOM B10 TECH/OPS 8900 875 --- 4.5 --- 238.0 --- 76.0 61.0 52.3 51.4 44.0 54.0 53 6 0.46 4.3 768.9 --- 92.2 200 180 79.9 2 0.05 4.1 10 460 3

AHU-102 ROOM B10 TECH/OPS 8900 875 --- 4.5 --- 238.0 --- 76.0 61.0 52.3 51.4 44.0 54.0 53 6 0.46 4.3 768.9 --- 92.2 200 180 79.9 2 0.05 4.1 10 460 3

AHU-103 ROOM B02 TECH/OPS 35000 --- --- 5.5 --- 1000.0 --- 76.0 61.0 56.1 53.3 44.0 54.0 200 8 0.68 10.8 --- --- --- --- --- --- --- --- --- 50 460 3

AHU-104 ROOM B02 TECH/OPS 35000 --- --- 5.5 --- 1000.0 --- 76.0 61.0 56.1 53.3 44.0 54.0 200 8 0.68 10.8 --- --- --- --- --- --- --- --- --- 50 460 3

AHU-105 ROOM B02 TECH/OPS 35000 --- --- 5.5 --- 1000.0 --- 76.0 61.0 56.1 53.3 44.0 54.0 200 8 0.68 10.8 --- --- --- --- --- --- --- --- --- 50 460 3

AHU-203 ROOM F08 TECH/OPS 8900 1140 --- 4.6 --- 288.0 --- 76.0 61.0 52.9 51.4 44.0 54.0 60 4 0.29 12.2 654.0 --- 78.7 200 180 66.0 2 0.05 4.1 10 460 3

AHU-204 ROOM F08 TECH/OPS 8900 1140 --- 4.6 --- 288.0 --- 76.0 61.0 52.9 51.4 44.0 54.0 60 4 0.29 12.2 654.0 --- 78.7 200 180 66.0 2 0.05 4.1 10 460 3

AHU-301 ROOM S06 TECH/OPS 15000 1140 --- 5.6 --- 463.0 --- 75.8 60.9 52.3 51.6 44.0 54.0 93 6 0.50 2.6 535.0 --- 78.0 200 180 54.0 2 0.05 4.1 20 460 3

AHU-302 ROOM S06 TECH/OPS 15000 1140 --- 5.6 --- 463.0 --- 75.8 60.9 52.3 51.6 44.0 54.0 93 6 0.50 2.6 535.0 --- 78.0 200 180 54.0 2 0.05 4.1 20 460 3

AHU-303 ROOM S20 TECH/OPS 9990 1500 --- 3.5 --- 156.0 --- 76.0 62.4 56.1 53.3 44.0 54.0 31.2 6 0.30 3.5 197.0 57.0 72.0 200 170 13.2 2 0.36 3.5 10 460 3

AHU-304 ROOM S20 TECH/OPS 9990 1500 --- 3.5 --- 156.0 --- 76.0 62.4 56.1 53.3 44.0 54.0 31.2 6 0.30 3.5 197.0 57.0 72.0 200 170 13.2 2 0.36 3.5 10 460 3

AHU-245

A

ROOM 245

BASEMENT &

FIRST FLOOR

4600 1470 4.4 3.0 --- 111.0 106.0 74.8 61.0 53.7 52.4 44.0 54.0 22.1 4 0.21 0.78 --- 24.3 62.4 200 180 11.6 1 0.09 0.80 7.5 460 3

AHU-245

B

ROOM 245

FIRST &

SECOND

FLOOR

4900 1100 4.6 3.0 --- 118.2 112.5 75.8 61.6 54.8 53.2 44.0 54.0 23.6 4 0.24 1.50 --- 26.5 68.3 200 180 10.0 1 0.09 0.21 10 460 3

AHU-09 ROOM 43

BASEMENT

VAV 5000 1500 4.88 2.00 5.97 110.9 101.4 73.9 61.2 54.0 52.8 44.0 54.0 22.2 4 0.56 6.90 53.9 37.5 50.0 180 160 29.8 1 0.10 0.90 7.5 460 3

AHU-10 ROOM 43

FIRST FLOOR

VAV 10000 2250 4.37 2.40 9.30 161.4 161.4 71.0 59.0 54.8 52.6 44.0 54.0 32.3 4 0.51 7.50 97.0 32.4 50.0 180 160 12.6 1 0.05 2.10 10 460 3

EXISTING 3/4"

PEX PIPING (TYP.)

SEE MECH RM 43

ENLARGED PLAN ON

SHEET ZAN-1303170-M006

SEE LAN EQUIPMENT

RM 64/AF LAB 63

ENLARGED PLAN

ON SHEET

ZAN-1303170-M006

SEE MECH RM B10

ENLARGED PLAN

ON SHEET

ZAN-1303170-M006

3/4" RO PEX

3/4" RO PEX PIPING

UP TO LEVEL ABOVE

3/4" RO PEX

SEE MECH RM 61

ENLARGED PLAN ON

SHEET ZAN-1303170-M008

3/4" RO PEX

CONNECT NEW

3/4"PEX PIPING

TO EXISITNG

ISOLATION

VALVE (TYP.)

3/4" RO PEX

SEE MECH RM B02

ENLARGED PLAN

ON SHEET

ZAN-1303170-M006

3/4" RO PEX

EXISTING 3/4" RO

PIPING BELOW FLOOR

EXISTING 3/4" CW

PIPING BELOW FLOOR

CORE DRILLING REQUIRED

FOR PIPE PENETRATION

THRU THIS WALL

USE EXISTING CABLE TRAY

PENETRATION TO ROUTE

PIPING THRU WALL

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

INFRASTRUCTURE ENG CENTER-ANC

ANCHORAGE

ZAN-1303170-M003

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM

BASEMENT FLOOR MECHANICAL

NEW WORK PLAN

za n-

0-m

3.

dw g

INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

SHEET NOTES:

1. EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE FROM RECORD

DRAWINGS AND NON-DESTRUCTIVE WALK-THROUGHS OF THE FACILITY.

ACTUAL SYSTEMS MAY VARY FROM THE INFORMATION INDICATED ON

THE DRAWINGS. CONTRACTOR TO FIELD VERIFY EXISTING

CONDITIONS, LOCATIONS, AND SIZES BEFORE START OF WORK.

2. BUILDING COMPONENTS DAMAGED BY ASSOCIATION TO REMODEL

WORK THAT ARE TO REMAIN SHALL BE PATCHED AND REPAIRED TO

MATCH EXISTING. COORDINATE WITH ARCHITECTURAL.

3. PROTECT ALL MECHANICAL EQUIPMENT, CONTROL WIRING, PIPING,

AND DUCTWORK THAT IS TO REMAIN FROM DAMAGE DURING REMODEL.

4. DO NOT ROUTE ANY PIPING IN EXTERIOR WALLS UNLESS OTHERWISE

INDICATED.

5. INSTALL ISOLATION VALVES AT ALL JUNCTIONS AND WHERE THE PIPING

CHANGES FLOOR LEVELS. INSTALL VALVED HOSE BIBS AT ALL LOW

POINTS SO SYSTEM CAN BE DRAINED. ENSURE ALL VALVES ARE

INSTALLED IN ACCESSIBLE LOCATIONS.

SCALE: 3/32" = 1'-0"

BASEMENT FLOOR MECHANICAL NEW WORK PLAN

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

8' 0 8' 24'

SCALE: 3/32" = 1'-0"

16'

KEY PLAN

CONNECT NEW

3/4" PEX PIPING

TO EXISTING

3/4"RO PEX PIPING

UP TO MECH RM 245

ISOLATION

VALVE (TYP.)

3/4" RO PEX

3/4" RO PEX

PIPING UP/DN

SEE MECH RM F08

ENLARGED PLAN

ON SHEET

ZAN-1303170-M007

EXISITNG 3/4"

RO PIPING

EXISTING 3/4"

RO PIPING DN

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

INFRASTRUCTURE ENG CENTER-ANC

ANCHORAGE

ZAN-1303170-M004

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

FIRST FLOOR MECHANICAL

NEW WORK PLAN

za n-

0-m

4.

dw g

INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

SHEET NOTES:

1. EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE FROM RECORD

DRAWINGS AND NON-DESTRUCTIVE WALK-THROUGHS OF THE

FACILITY. ACTUAL SYSTEMS MAY VARY FROM THE INFORMATION

INDICATED ON THE DRAWINGS. CONTRACTOR TO FIELD VERIFY

EXISTING CONDITIONS, LOCATIONS, AND SIZES BEFORE START OF

WORK.

2. BUILDING COMPONENTS DAMAGED BY ASSOCIATION TO REMODEL

WORK THAT ARE TO REMAIN SHALL BE PATCHED AND REPAIRED TO

MATCH EXISTING. COORDINATE WITH ARCHITECTURAL.

3. PROTECT ALL MECHANICAL EQUIPMENT, CONTROL WIRING, PIPING,

AND DUCTWORK THAT IS TO REMAIN FROM DAMAGE DURING

REMODEL.

4. DO NOT ROUTE ANY PIPING IN EXTERIOR WALLS UNLESS

OTHERWISE INDICATED.

5. INSTALL ISOLATION VALVES AT ALL JUNCTIONS AND WHERE THE PIPING

CHANGES FLOOR LEVELS. INSTALL VALVED HOSE BIBS AT ALL LOW

POINTS SO SYSTEM CAN BE DRAINED. ENSURE ALL VALVES ARE

INSTALLED IN ACCESSIBLE LOCATIONS.

SCALE: 3/32" = 1'-0"

FIRST FLOOR MECHANICAL NEW WORK PLAN

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

NOT TO SCALE

KEY PLAN

8' 0 8' 24'

SEE MECH RM 245

ON SHEET

ZAN-1303170-M007

SEE MECH RM S06

ENLARGED PLAN

ON SHEET

ZAN-1303170-M0083/4" RO PEX

PIPING

DN TO LEVEL

BELOW

3/4" RO PEX

ISOLATION

VALVE (TYP.)

3/4" RO PEX

SEE MECH RM S20

ENLARGED PLAN

ON SHEET

ZAN-1303170-M008

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

INFRASTRUCTURE ENG CENTER-ANC

ANCHORAGE

ZAN-1303170-M005

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

SECOND FLOOR MECHANICAL

NEW WORK PLAN

za n-

0-m

5.

dw g

INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

SHEET NOTES:

1. EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE FROM RECORD

DRAWINGS AND NON-DESTRUCTIVE WALK-THROUGHS OF THE

FACILITY. ACTUAL SYSTEMS MAY VARY FROM THE INFORMATION

INDICATED ON THE DRAWINGS. CONTRACTOR TO FIELD VERIFY

EXISTING CONDITIONS, LOCATIONS, AND SIZES BEFORE START OF

WORK.

2. BUILDING COMPONENTS DAMAGED BY ASSOCIATION TO REMODEL

WORK THAT ARE TO REMAIN SHALL BE PATCHED AND REPAIRED TO

MATCH EXISTING. COORDINATE WITH ARCHITECTURAL.

3. PROTECT ALL MECHANICAL EQUIPMENT, CONTROL WIRING, PIPING,

AND DUCTWORK THAT IS TO REMAIN FROM DAMAGE DURING

REMODEL.

4. DO NOT ROUTE ANY PIPING IN EXTERIOR WALLS UNLESS

OTHERWISE INDICATED.

5. INSTALL ISOLATION VALVES AT ALL JUNCTIONS AND WHERE THE PIPING

CHANGES FLOOR LEVELS. INSTALL VALVED HOSE BIBS AT ALL LOW

POINTS SO SYSTEM CAN BE DRAINED. ENSURE ALL VALVES ARE

INSTALLED IN ACCESSIBLE LOCATIONS.

SCALE: 3/32" = 1'-0"

SECOND FLOOR MECHANICAL NEW WORK PLAN

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

NOT TO SCALE

KEY PLAN

8' 0 8' 24'

(E)AHU-101

(E)AHU-102

HU-101

HU-102

1 1

3/4"RO PEX

HUMIDIFIERS TO BE

STACKED. SHOWN

OFFSET FOR CLARITY

SEE ZAN-1303170-M003 FOR

PIPING CONTINUATION

NOTE: PIPING AND HUMIDIFIERS SHOWN OFFSET FOR

CLARITY. HUMIDIFIERS TO BE STACKED TO MATCH

ORIGINAL INSTALLATION CONFIGURATION AND PIPING IS

TO BE NEATLY ROUTED ALONGSIDE AHUs TO FLOOR DRAIN.

(E)CRU-64

(E)CRU-63

EXISTING CRU UNIT (TYP.2)

NOTE: PIPING SHOWN IS IN FLOOR SPACE BELOW

EXISTING 3/4" CW

EXISTING FLOOR SINK

EXISTING BACKFLOW PREVENTER

EXISTING 3/4" PEX RO PIPING

SEE ZAN-1303170-M003 FOR

PIPING CONTINUATION

(E)AHU-110

(E)HU-09

(E)HU-10

NOTE: NO WORK TO BE DONE IN

MECHANICAL ROOM 43. ALL EQUIPMENT

AND PIPING TO REMAIN. SHOWN FOR

REFERENCE PURPOSES ONLY.

EXISTING RO WATER PEX

PIPING (TYP.)

(E)AHU-109

SEE ZAN-1303170-M003 FOR

PIPING CONTINUATION

(E)AHU-105

(E)AHU-104

(E)AHU-103

HU-103

HU-104

3/4" RO PEX

HU-105

3/4" RO PEX

EXISTING

INDUSTRIAL WATER

PIPING (TYP.)

CAP PIPING (TYP.)

SEE ZAN-1303170-M003 FOR

PIPING CONTINUATION

1-1/4" D

1-1/4" D

1-1/4" D

2" STM

2" STM

2" STM

3/4" RO PEX

1-1/4" D

1-1/4" D

1-1/4" D

EXISTING BACKFLOW

PREVENTER

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

INFRASTRUCTURE ENG CENTER-ANC

ANCHORAGE

ZAN-1303170-M006

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

NEW WORK PLAN MECHANICAL ROOMS

64/AF LAB 63, B10, B02, AND 43

za n-

0-m

6.

dw g

INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

KEY NOTES:

SHEET NOTES:

1. EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE FROM

RECORD DRAWINGS AND NON-DESTRUCTIVE

WALK-THROUGHS OF THE FACILITY. ACTUAL SYSTEMS MAY

VARY FROM THE INFORMATION INDICATED ON THE

DRAWINGS. CONTRACTOR TO FIELD VERIFY EXISTING

CONDITIONS, LOCATIONS, AND SIZES BEFORE START OF

WORK.

2. BUILDING COMPONENTS DAMAGED BY ASSOCIATION TO

REMODEL WORK THAT ARE TO REMAIN SHALL BE PATCHED

AND REPAIRED TO MATCH EXISTING. COORDINATE WITH

ARCHITECTURAL.

3. PROTECT ALL MECHANICAL EQUIPMENT, CONTROL WIRING,

PIPING, AND DUCTWORK THAT IS TO REMAIN FROM DAMAGE

DURING REMODEL.

4. DO NOT ROUTE ANY PIPING IN EXTERIOR WALLS UNLESS

OTHERWISE INDICATED.

5. BRANCH PIPING TO HUMIDIFIERS TO MATCH UNITS

CONNECTION SIZE.

6. BRANCH PIPE ROUTING TO MATCH PREVIOUS ROUTING

WHEREVER POSSIBLE.

SCALE: 1/4" = 1'-0"

EQUIPMENT ROOM 64/ AF LAB 63 NEW WORK PLAN

SCALE: 1/4" = 1'-0"

MECH RM B10 NEW WORK PLAN

SCALE: 1/4" = 1'-0"

MECH RM B02 NEW WORK PLAN

SCALE: 1/4" = 1'-0"

MECH ROOM 43 NEW WORK PLAN

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

INSTALL HUMIDIFIER IN SAME LOCATION AS REMOVED

EXISTING UNIT. REFER TO MANUFACTURERS INSTALLATION

INSTRUCTIONS. SEE 4/ZAN-1303170-M009 FOR DETAIL.

ROUTE STEAM PIPING FROM ASSOCIATED HUMIDIFIER AND

CONNECT TO EXISTING DISPERSION TUBE. CONNECT AND

EXTEND CONDENSATE PIPING TO NEAREST DRAIN. ALL

STEAM AND CONDENSATE PIPING TO BE STAINLESS STEEL.

PROVIDE 1" MINIMUM AIR GAPS FOR ALL HUMIDIFIER

CONDENSATE PIPING. MATCH HUMIDIFIER

CONNECTION SIZE UP UNTIL AIR GAP, THEN UPSIZE TO

1-1/4" AS SHOWN IN THE ENLARGED PLANS.

CONNECT AND EXTEND PEX PIPING TO SERVE

EXISTING CRU-63/64. USE STAINLESS STEEL PIPING

WHEREVER PLASTIC PIPING CANNOT BE USED OR

WHERE PEX CANNOT BE CONNECTED TO CRU UNITS.

4' 0 4' 8'

SCALE: 1/4" = 1'-0"

5 REPLACE AND ROUTE DRAIN PIPING FROM

(E)CRU-63/64 TO EXISTING FLOOR SINK. PIPING TO BE

PEX AND TO MATCH UNIT CONNECTION SIZE. PROVIDE

WITH MINIMUM 1" AIR GAP AT FLOOR SINK.

6 PROVIDE 1" MINIMUM AIR GAP TO FLOOR DRAINS.

(E)AHU-204

(E)AHU-203

HU-203

HU-204

3/4" RO PEX

1-1/4" D

2" STM

1-1/4" D

2" STM

1-1/4" D

1-1/4" D

ISOLATION VALVE

(TYP.)

3/4" RO PEX

(E)AHU-245A

HU-245A

3/4" RO PEX

PIPING DN

1-1/4" D

1-1/4" D

2" STM

3/4" RO PEX

3/4" RO PEX

EXISTING COPPER PIPING SERVING

EXISTING TRAP PRIMERS

PIPING DOWN THROUGH FLOOR TO

LEVEL BELOW

(E)AHU-245B

HU-245B

1-1/4" D

3/4" RO PEX

1-1/4" D

2" STM

EXISTING FLOOR

DRAIN (TYP.)

EXISTING COPPER PIPING

SERVING HUMIDIFIERS TO

REMAIN TO SERVE EXISTING

TRAP PRIMERS

EXISTING COPPER PIPING SERVING

EXISTING TRAP PRIMERS

CAP PIPING

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

INFRASTRUCTURE ENG CENTER-ANC

ANCHORAGE

ZAN-1303170-M007

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

NEW WORK PLAN MECHANICAL ROOMS

245A, 245B AND F08

za n-

0-m

7.

dw g

INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

KEY NOTES:

INSTALL HUMIDIFIER IN SAME LOCATION AS REMOVED EXISTING

UNIT. REFER TO MANUFACTURERS INSTALLATION INSTRUCTIONS.

SEE 4/ZAN-1303170-M004 FOR DETAIL.

PROVIDE 1" MINIMUM AIR GAPS FOR ALL HUMIDIFIER

CONDENSATE PIPING. MATCH HUMIDIFIER CONNECTION SIZE UP

UNTIL AIR GAP, THEN UPSIZE TO 1-1/4" AS SHOWN IN THE

ENLARGED PLANS. ROUTE HUMIDIFIER CONDENSATE DRAIN PIPING

TO NEAREST FLOOR DRAIN.

ROUTE STEAM PIPING FROM ASSOCIATED HUMIDIFIER AND

CONNECT TO EXISTING DISPERSION TUBE. CONNECT AND EXTEND

CONDENSATE PIPING TO NEAREST DRAIN. PROVIDE 1" MINIMUM AIR

GAP TO FLOOR DRAIN.

RECONNECT EXISTING CW PIPING TO NEW 'DRANE KOOLER' WATER

TEMPERING DEVICE. CONNECT NEW CONDENSATE PIPING FROM

HUMIDIFIER AND DISPERSION TUBE. ROUTE DRAIN PIPING TO

NEAREST FLOOR DRAIN.

PROVIDE MINIMUM 1" AIR GAP TO FLOOR DRAIN.

SHEET NOTES:

1. EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE FROM RECORD

DRAWINGS AND NON-DESTRUCTIVE WALK-THROUGHS OF THE

FACILITY. ACTUAL SYSTEMS MAY VARY FROM THE INFORMATION

INDICATED ON THE DRAWINGS. CONTRACTOR TO FIELD VERIFY

EXISTING CONDITIONS, LOCATIONS, AND SIZES BEFORE START OF

WORK.

2. BUILDING COMPONENTS DAMAGED BY ASSOCIATION TO REMODEL

WORK THAT ARE TO REMAIN SHALL BE PATCHED AND REPAIRED TO

MATCH EXISTING. COORDINATE WITH ARCHITECTURAL.

3. PROTECT ALL MECHANICAL EQUIPMENT, CONTROL WIRING, PIPING,

AND DUCTWORK THAT IS TO REMAIN FROM DAMAGE DURING

REMODEL..

4. DO NOT ROUTE ANY PIPING IN EXTERIOR WALLS UNLESS

OTHERWISE INDICATED.

5. BRANCH PIPING TO HUMIDIFIERS TO MATCH UNITS CONNECTION

SIZE.

6. BRANCH PIPE ROUTING TO MATCH PREVIOUS ROUTING WHEREVER

POSSIBLE.

SCALE: 1/4" = 1'-0"

MECH RM 245A NEW WORK PLAN

SCALE: 1/4" = 1'-0"

MECH RM 245B NEW WORK PLAN

SCALE: 1/4" = 1'-0"

MECH RM F08 NEW WORK PLAN

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

4' 0 4' 8'

(E)AHU-302

(E)AHU-301

HU-301

HU-302

5 5

3/4" PEX RO

2" STM

1-1/4" D

2" STM

1-1/4" D

1-1/4" D

ISOLATION VALVE

(TYP.)

3/4" RO PEX

1-1/4" D

(E)AHU-303 (E)AHU-304

HU-303 HU-304

5 5

4 4

EXISTING INDUSTRIAL

WATER PIPING (TYP.)

3 3

3/4" RO PEX

CAP PIPING (TYP.)

EXISTING BACKFLOW

PREVENTER

1-1/4" D 1-1/4" D

2" STM 2" STM

3/4" RO PEX

1-1/4" D 1-1/4" D

SEE ZAN-1303170-M005 FOR

PIPING CONTINUATION

BRINE

TANK

SOFTENER

STORAGE

TANK

POST-UV FILTER

REVERSE OSMOSIS

AND PRE-RO FILTERS

3/4" RO PEX

44"

85"

EXISTING FLOOR SINK TO REMAIN FOR REUSE.

ALL DRAINS FROM EXISTING RO SYSTEM TO BE

DEMOLISHED. 6 2

SEE ZAN-1303170-M003 FOR

PIPING CONTINUATION

USE EXISTING WALL PENETRATION TO ROUTE

RO PIPING TO COORIDOR

ISOLATION VALVE (TYP.) 3/4" RO PEX

3/4" RO PEX

3/4" RO PEX

1" RO PEX

72"

9.5"

10"

74"

93"

RO SKID

ELEVATOR CLEARANCE

DIMENSIONS

85"

44"

NOTE: DIAGRAM SHOWS SKID ORIENTATION REQUIRED

IN ELEVATOR AT MAXIMUM ALLOWABLE DIMENSIONS.

RO SKID MANUFACTURER/CONTRACTOR TO VERIFY

PRODUCT WILL FIT IN ELEVATOR.

IS

SU

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

INFRASTRUCTURE ENG CENTER-ANC

ANCHORAGE

ZAN-1303170-M008

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

NEW WORK PLAN MECHANICAL ROOMS

S20, S06, AND 61

za n-

0-m

8.

dw g

INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

KEY NOTES:

CONNECT RO SKID TO EXISTING CW SUPPLY PIPING. REFER TO

CONCEPTUAL RO SKID P&ID ON SHEET ZAN-1303170-M10

ROUTE DRAIN PIPING FROM RO SKID TO EXISTING FLOOR SINK.

INSTALL HUMIDIFIER IN SAME LOCATION AS REMOVED EXISTING UNIT.

REFER TO MANUFACTURERS INSTALLATION INSTRUCTIONS. SEE

4/ZAN-1303170-M009 FOR DETAIL.

HUMIDIFIER CONDENSATE DRAIN PIPING TO BE ROUTED TO NEAREST

FLOOR DRAIN. PROVIDE WITH MINIMUM 1" AIR GAP TO FLOOR DRAIN.

ROUTE STEAM PIPING FROM ASSOCIATED HUMIDIFIER AND CONNECT

TO EXISTING DISPERSION TUBE. CONNECT AND EXTEND CONDENSATE

PIPING TO NEAREST DRAIN. PROVIDE WITH MINIMUM 1" AIR GAP TO

FLOOR DRAIN.

CONNECT EXISTING 3/4" RO PEX PIPING TO NEW PIPING FROM RO SKID.

CONNECT EXISTING 3/4" IW PIPING TO NEW RO SKID.

PROVIDE MINIMUM 1" AIR GAP TO FLOOR DRAIN FOR ALL CONDENSATE

PIPING.

SHEET NOTES:

1. EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE FROM RECORD

DRAWINGS AND NON-DESTRUCTIVE WALK-THROUGHS OF THE FACILITY.

ACTUAL SYSTEMS MAY VARY FROM THE INFORMATION INDICATED ON

THE DRAWINGS. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS,

LOCATIONS, AND SIZES BEFORE START OF WORK.

2. BUILDING COMPONENTS DAMAGED BY ASSOCIATION TO REMODEL

WORK THAT ARE TO REMAIN SHALL BE PATCHED AND REPAIRED TO

MATCH EXISTING. COORDINATE WITH ARCHITECTURAL.

3. PROTECT ALL MECHANICAL EQUIPMENT, CONTROL WIRING, PIPING, AND

DUCTWORK THAT IS TO REMAIN FROM DAMAGE DURING REMODEL..

4. DO NOT ROUTE ANY PIPING IN EXTERIOR WALLS UNLESS OTHERWISE

INDICATED.

5. BRANCH PIPING TO HUMIDIFIERS TO MATCH UNITS CONNECTION SIZE.

6. BRANCH PIPE ROUTING TO MATCH PREVIOUS ROUTING WHEREVER

POSSIBLE.

SCALE: 1/4" = 1'-0"

MECH RM S20 NEW WORK PLAN

SCALE: 1/4" = 1'-0"

MECH RM S06 NEW WORK PLAN

SCALE: 1/4" = 1'-0"

MECH RM 61 NEW WORK PLAN

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN REDLINE

DATE APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

$D

AT

E$ $T

IM

E$

$N

AM

E$

APPROVED

DATE

$F

IL

ES

8 234567

H

G

F

E

D

C

A

B

4' 0 4' 8'

SCALE: 1/4" = 1'-0"

SCALE: NOT TO SCALE

ELEVATOR DIMENSIONS

ED

F

O R

ED

M

10/09/2024

STEVE SCHREFFLER

INFRASTRUCTURE ENG CENTER-ANC

ANCHORAGE

ZAN-1303170-M009

PJB

PJB

ARTCC

INSTALL WATER TREATMENT SYSTEM & HUMIDIFIERS

MECHANICAL DETAILS

za n-

0-m

9.

dw g

INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

C O

N

ST

R U

C

TI

O N

ALASKA CENTER

DRAWING PRODUCED ON WSA ANCHORAGE CAD SYSTEM

PETER BREWER

PROJECT ENGINEER

1303170

AK

AIR HANDLING UNIT

EQUIPMENT PAD

UNION

H

EI

G H

T 2"

D

EE

PE

R

T H

AN

FA

N T

O

TA

L

ST

AT

IC

P R

ES

SU

R E

SE

E

AH

U

S C

H

ED

U

LEPITCH DOWN TO FLOOR

SINK (SEE FLOOR PLAN)

1 1/4" MINIMUM

DRAIN SIZE

2" STEAM HOSE WITH

CONNECTORS PROVIDED

WITH HUMIDIFIER (TYP.)

MANUAL INTERLOCKING

CIRCUIT BREAKER

L1 L2 L3

460 V, 3 PHASE

DRAIN

WATER INLET

MASTER HUMIDISTAT, INSTALL

IN SAME LOCATION AS EXISTING

REMOVED DURING DEMO

AHU DUCT

HI-LIMIT HUMIDISTAT

STEAM…