Attachment 10 Bldg 157 identified asbestos and locations (1).pdf
PDF 414 KB Posted
- Solicitation number
- 12905B24Q0205
About this file
This document is an Asbestos Inspection Report for Building 157 at the National Animal Disease Center in Ames, Iowa. The report identifies the presence of asbestos-containing materials in the facility, including mud fittings, window caulk, and expansion caulk. The report provides detailed information on the locations and types of asbestos-containing materials found, and recommends that they be maintained in an intact and undamaged condition.
The related federal contract opportunity is a solicitation for a roof replacement project on Building 157 at the same facility. The solicitation requires all labor, materials, equipment, supplies, supervision, and transportation to repair the roof in accordance with the Statement of Work and other attachments. The estimated magnitude of the project is between $100,000 and $250,000, with a completion period of 180 days after notice to proceed. The applicable Department of Labor wage determination is provided, and bonds are required within 10 days of award.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
''Experienced. Professional. Solutions."
C. SUMMARY OF ASBESTOS CONTAINING BUILDING MATERIALS
Thermal System Insulation
P.O. Box 661 410 Main Street
Slater, IA 50244-0661 800-383-3400
Fax: 515-685-2236 www .AmesEnvironmental.com
Info@ AmesEnvirorunental.com
The mud fittings throughout were determined to contain asbestos. The mud fittings should be maintained in an intact and undamaged condition.
Nonfriable Miscellaneous Material The exterior window caulk on the exterior windows was determined to contain asbesto,~. The window caulk should be maintained in an intact and undamaged condition. The ex:pansiou canlk Qtl
J:he exterior wa11s was determined to contain asbest.Qs. The expansion caulk should be maintained in an intact and undamaged condition.
All matelials similar in appearance, color or texture to those determined to contain asbestos must be assumed to contain asbestos throughout this building. The location if described is where the sample(s) was collected during our inspection.
This document is not to be used as a guide to determine all of the amounts and locations of asbestos containing materials throughout the building.
81~ t 157
''Experienced. Professional. Solutions."
D. INSPECTION SUMMARY FOR BUILDING 157
Thermal System Insulation The suspect material in this category was mud fittings.
~ Mud Fittings ·
P.O. Box 661 410 Main Street
Slater, IA 50244-0661 800-383-3400
Fax: 515-685-2236 www .AmesEnvirorunental.com
Info@ AmesEnvironmental.com
~ The mud fittings throughout the facility were detennined to contain asbestos by analysis of sample numbers 11L092992A, B, and C. The mud fittings should be maintained in an ct and undama ed condition.
Friable Surfacing Material No suspect friable surfacing material was found during this inspection.
Ftiable Miscellaneous Material No suspect friable miscellaneous material was found during this inspection.
Nonfriable Miscellaneous Material The suspect materials in this category were window caulk, expansion caulk, and window glazing.
Window Caulk The exterior window caulk on the exterior windows was determined to contain asbestos by analysis of sample number 11L092994A. The window caulk should be maintained in an intact and undamaged condition . .-· ---------------------
The interior window caulk was determined to be non-asbestos by analysis of sample number 11L092991A.
Expansion Caulk ~ The expansion caulk on the exterior walls was determined to contain asbestos by analysis of sample number 11L092993A. The expansion caulk should be maintained in an intact and undamaged condition.
Window Glazing The window glazing was determined to be non-asbestos by analysis of sample number 11L092995A.
+ Suspect material was assumed to contain asbestos or found to contain asbestos from bull( sample collection and PLM analysis.
EMSL Analytical, Inc.
2001 East 52nd St., Indianapolis, IN 46205
Phone: (317) 803-2997 I - , ·· -·-· ·r . t:n
Attn: Kim Crosser Customer I D: AMES50 Ames Environmental, Inc. Customer PO:
410 Main St. Received: 1 0/03111 9:40 AM
P.O. Box 661 EMSLOrder: 161117882
Slater, lA 50244 Fax: (515) 685-2236 Phone: (515) 685-2299
EMSL Proj:
Project: NADC BLDG 157
Analysis Date: 10/512011
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using
Sample Description
11L092991A Interior window 161117882.()001 caulk
11L092992A mudflttin~s
161117882.()002
11L092992B ,.!!l!!dfittin~
16111788NX)(}3
11L092992C ,mud fiUlnas
181117882-0004
11L092993A ~nsionca.!!J.k 161117882-0005
11L092994A ~erllllMJilW.W 1611178824)006 caul!< jtnitiai report from 10/0512011 10:55:53
Analyst(s)
Craig Nixon (7}
Polarized Light Microscopy ~QD·A!!bgtQB
Appearance % Fibrous
Gray
Non-Fibrous Homogeneous
Gray 30% Min. WOO.
Fibrous Homogeneous
Gray 30% Min. WOO.
Fibrous Homogeneous
Gray 30% Min. WOO.
Fibrous Homogeneous
Brown/Gray Non-Fibrous Heterogeneous
Gray 8% Synthetic
Noo-Fibrous Homogeneous
Asbestos
% Non-Fibrous %Type
100% Non-fibrous (other) None Detected
68% Non-fibrous (other) 2% Amosite
68% Non-fibrous (other) 2% Amosite
700/o Non-fibrous (other) <1% Amosite
98% Noo·fibrous (other) :zetv Chrysotlle
90"A. Non-fibrous (other) 2% Chrysotile
Richard Hardilg, Laboratory Manager or other approved signatory
EMSL maintains liabiily limited to eo&l of anal)"lls. This report relates only to the samples reported and may not be reproduced, exrepl in full, without wriUen appro'4al by EIASL EMSL bears no rosponsibilily for sample colleclioo actMIIes or analytical mlllhod limitations. lnterprelation and use of tesl results are the ll>Silonsiblllly of the client. This mport must not be US<ld by the cllootlo claim product oortlficatlon, approval , or endorsement by NIII.AP, NIST or any agency of the federal government. Non-friable organicslly bound malerials present a problem matrix and therefore EMSL recommends grav!melric reduction prior to anal )"lis. Samples received In good condition unless otherwise noted. Esllmaled accuracy, precision and Ul1certalnty dala avallablo upon request.
8alllj)IOs a!UIIyzsd by EMSl Anal)'tical, he. Indianapolis. IN NVlAP Lab Code 200188.(1, AZ093!1 , CA 2575, CO AL-15132, TX 300262
Test Report PLM-7 .23.0 Printed: 1 0/5/2011 11 :06:25AM