This document is a product catalog for Daikin's SmartSource® Compact Vertical Water Source Heat Pumps (Model GCV), providing comprehensive technical specifications for vertical water source heat pump units ranging from 1/2 to 6 tons. The catalog details multiple unit configurations, including standard PSC motor and optional electronically commutated (EC) motor versions, with unit sizes from 007 to 070.

The catalog extensively covers technical features including refrigeration circuit components, motor assemblies, control systems, filter options, and installation requirements. Key specifications include R-410A refrigerant, rotary or scroll compressors, optional communication modules (LonWorks and BACnet), various fan motor configurations, and multiple insulation and sound attenuation options. The document provides detailed performance data, electrical specifications, dimensional drawings, and engineering guide specifications, serving as a comprehensive technical reference for specifying and installing these water source heat pump systems in commercial and institutional applications.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Catalog 1116-12

SmartSource® Compact Vertical Water Source Heat Pumps Model GCV - Vertical Unit Sizes 007 – 070 (1/2 thru 6 tons)

Contents

Model Nomenclature AHRI Performance Data

Compact model GCV with PSC motor Compact model GCV with EC motor

Features and Options SmartSource® Compact Vertical Water Source Heat Pumps 6 Hot Gas Reheat Coil Hydronic Heat Waterside Economizer Designed-in Sound Reduction Sound Options Fan Motors Swing-Out Control Box Non-Fused Disconnect Switch (Option) High Efficiency Rotary or Scroll Compressor Freeze Fault Protection (Option) Water Pressure Differential Switch (Option) 2-Way Motorized Water Valve (Option) Water Connections Service Valve Connections Air-to-Refrigerant Coil Coax Coil Filters & Filter Racks LED Sight Glass Fan Speed Selector Switch

Controls MicroTech® III SmartSource Controller with LonWorks® Communication Module MicroTech III SmartSource Controller with BACnet® Communication Module

Accessories Hoses, Hose Kits and Shutoff Ball Valves for SmartSource Water Source Heat Pumps Supply and Return Hose Kits Shutoff Ball Valves with Memory Stop

Applications Standard Unit Typical Installation Unit With Hydronic Heat Coil Typical Installation Ductwork and Attenuation Piping Water System Quality Operating Limits

Performance Data Fan Performance - Standard PSC Motor Fan Performance - Optional Constant Torque Motor (Sizes 007–012) Fan Performance - Optional Constant Torque EC Motor (Sizes 015–070) Fan Performance - Optional Constant CFM EC Motor (Sizes 015–070) Fan Performance - Optional Constant CFM EC Motor (Sizes 015–070)

Electrical Data Unit With Standard PSC Motor Unit With Optional EC Constant Torque Motor Unit With Optional EC Constant CFM Motor

Physical Data Dimensional Data

Standard Model GCV Unit Dimensions – Right-Hand Standard Model GCV Unit Dimensions – Left-Hand Model GCV Unit With Waterside Economizer Dimensions 35

Thermostat and Sensor Information Model GCV Engineering Guide Specifications

©2023 Daikin Applied, Minneapolis, MN . All rights reserved throughout the world .This document contains the most current product information as of this printing . Daikin Applied Americas Inc . has the right to change the information, design, and construction of the product represented within the document without prior notice . For the most up-to-date product information, please go to www .DaikinApplied .com .

™® SmartSource, MicroTech, and Daikin Applied are trademarks or registered trademarks of Daikin Applied Americas Inc . The following are trademarks or registered trademarks of their respective companies: BACnet from American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc .; Echelon, LonWorks, LonMark, and LonTalk from Echelon Corporation; Modbus from Schneider Electric; and Windows from Microsoft Corporation . .

www .DaikinApplied .com 3 CAT 1116-12 • SmartSource Compact WSHP

Model Nomenclature

1 2-3 4 5-7 8 9 10-11 12 13 14 15 16-17 18 19 20 21 22 23-24 25 26

W GC V 007 E 1 LT S B C B HG 1 1 P F S 75 E D

Category Code Option Code Designation Description Product Category 1 W = Water Source Heat Pump Model Type 2-3 GC = Compact Configuration 4 V = Vertical Nominal Capacity 5-7 007 = 7,000 Btuh Nominal Cooling 009 = 9,000 Btuh Nominal Cooling 012 = 12,000 Btuh Nominal Cooling 015 = 15,000 Btuh Nominal Cooling 019 = 19,000 Btuh Nominal Cooling 024 = 24,000 Btuh Nominal Cooling 030 = 30,000 Btuh Nominal Cooling 042 = 42,000 Btuh Nominal Cooling 048 = 48,000 Btuh Nominal Cooling 060 = 60,000 Btuh Nominal Cooling 070 = 70,000 Btuh Nominal Cooling Voltage 8 A = 115/60/1 (007-015) E = 208-230/60/1 (007-070) F = 208-230/60/3 (024-070) J = 265/60/1 (007-036) K = 460/60/3 (024-070) L = 575/60/3 (048-070) Design Series (Vintage) 9 1 = Revision / Design Series 1 Return Air / Discharge Air 10-11 LT = Left-Hand Return / Top Discharge R = Right-Hand Return / Top Discharge Water Coil Type 12 C = Copper Inner Tube S = Cupro-Nickel Inner Tube G = Geothermal - Copper Inner Tube J = Geothermal - Cupro-Nickel Unit Control 13 B = MicroTech III SmartSource Unit Controller L = MicroTech III Unit Controller + Lon B = MicroTech III Unit Controller + BACnet Fan Motor 14 P = PSC C = ECM Constant CFM T = ECM Constant Torque Insulation (Compressor Side / Airside) 15 B = Standard (1/2" Fiberglass, Entire Unit) I = IAQ (Closed Cell Foam, Entire Unit) D = Dual Layer Fiberglass (Entire Unit) (sizes 007-019) F = Sound Blanket + Standard (1/2" Fiberglass)(sizes 024-070) G = Sound Blanket + IAQ (Closed Cell Foam) (sizes 024-070) H = Sound Blanket + Sound Package (1" Fiberglass / Dual Layer Fiberglass) (sizes 024-070) Options 16-17 WE = Waterside Economizer HG = Hot Gas Reheat HH = Hydronic Heat Filter & Racks 18 1 = Standard 1" Rail - 1" Throwaway Filter 2 = 2" Rack - 2" Filter (MERV 8) 4 = 4" Rack - 4" Filter (MERV 13) Piping Package 19 0 = None 1 = Isolation Valve (NO) 2 = Isolation Valve (NC) Electric Heat 20 0 = None P = Control for Electric Heat Single 24V Signal (Field Installed Duct Heater by Others) Additional Options 21 0 = None F = Freeze Fault Protection C = Pressure Differential Switch D = Freeze Fault Protection and Pressure Differential Switch Standard or Special 22 S = Standard X = Special Transformer 23-24 50 = 50VA Transformer 75 = 75VA Transformer Corrosion Protection 25 0 = None E = Corrosion Protection with Stainless Steel Drain Pan (Coated Air Coil Includes WSE and HGRH if applicable) Disconnect Switch 26 0 = None D = Disconnect Switch

CAT 1116-12 • SmartSource Compact WSHP 4 www .DaikinApplied .com

AHRI Performance Data Compact model GCV with PSC motor Note: Rated in accordance with AHRI/ASHRAE/ISO Standard 13256-1.

Unit Size Motor Type CFM GPM

Water Loop (Boiler Tower) Ground Loop (Geothermal)

DimensionsCooling Heating Cooling Heating

Btu/hr EER Btu/hr COP Btu/hr EER Btu/hr COP

PSC

250 1 .8 6100 12 .8 7000 4 .5 6400 15 .1 4800 3 .3 19 .0W x 19 .0D x 24 .0H009 300 2 .3 8000 12 .2 9500 4 .3 8400 14 .8 6300 3 .2

012 400 3 .0 10900 12 .2 13600 4 .3 11600 14 .1 8900 3 .2

PSC

500 3 .5 13700 13 .8 16600 5 .1 14500 15 .6 10500 3 .4

21 .5W x 21 .5D x 32 .0H 019 600 4 .5 17300 13 .8 20300 4 .7 18300 15 .8 13000 3 .4

PSC

775 6 .0 24000 13 .4 25900 4 .4 25200 15 .5 17200 3 .2

21 .5W x 21 .5D x 39 .0H 030 1000 7 .1 28900 14 .0 33000 4 .4 30500 16 .0 21200 3 .3

PSC

1200 9 .1 36100 13 .0 42300 4 .3 37900 15 .0 27300 3 .3

21 .5W x 26 .0D x 44 .0H 042 1400 10 .0 40300 13 .7 45800 4 .6 42000 15 .7 29700 3 .3

PSC

1600 12 .0 47800 14 .2 58400 5 .0 49800 16 .3 38000 3 .6

24 .0W x 32 .5D x 46 .0H 060 2000 15 .0 58700 13 .2 74500 4 .6 61400 14 .8 49200 3 .3 070 PSC 2200 18 .0 66500 13 .5 79900 4 .6 69000 14 .9 53200 3 .3 26 .0W x 33 .25D x 54 .125H

Compact model GCV with EC motor Note: Rated in accordance with AHRI/ASHRAE/ISO Standard 13256-1.

Unit Size Motor Type CFM GPM

Water Loop (Boiler Tower) Ground Loop (Geothermal)

DimensionsCooling Heating Cooling Heating

Btu/hr EER Btu/hr COP Btu/hr EER Btu/hr COP

*ECM

250 1 .8 6200 13 .8 6900 4 .8 6500 16 .2 4700 3 .3 19 .0W x 19 .0D x 24 .0H009 300 2 .3 8100 13 .0 9200 4 .3 8400 14 .8 6100 3 .2

012 400 3 .0 10900 13 .2 13500 4 .6 11700 15 .1 8700 3 .4

ECM

500 3 .5 13900 14 .6 16400 5 .2 14700 16 .5 10300 3 .5

21 .5W x 21 .5D x 32 .0H 019 600 4 .5 17500 14 .3 20100 5 .0 18500 16 .7 12900 3 .5

ECM

775 6 .0 24200 13 .5 25700 4 .5 25400 15 .9 17100 3 .4

21 .5W x 21 .5D x 39 .0H 030 1000 7 .1 28900 14 .1 33000 4 .4 30500 16 .2 21200 3 .3

ECM

1200 9 .1 36500 13 .7 41900 4 .5 38300 15 .8 27000 3 .4

21 .5W x 26 .0D x 44 .0H 042 1400 10 .0 41000 14 .5 45000 4 .8 42700 16 .7 28900 3 .4

ECM

1600 12 .0 48200 14 .7 57400 5 .1 50100 16 .9 37000 3 .6

24 .0W x 32 .5D x 46 .0H 060 2000 15 .0 59300 13 .9 73100 4 .9 62000 15 .7 47800 3 .6 070 ECM 2200 18 .0 67500 14 .6 78900 4 .8 70000 16 .2 52200 3 .5 26 .0W x 33 .25D x 54 .125H

Legend: Btuh = British Thermal Units per Hour CFM = Airflow Rate, Cubic Feet per Minute COP = Coefficient of Performance EER = Energy Efficiency Ratio GPM = Gallons per Minute * = Constant torque EC motor only

Water Loop: 1. Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) EAT and 86°F (30°C) EWT.

2. Heating capacity is based on 68°F db, 59.0°F wb (20/15°C) EAT and 68°F (20°C) EWT.

3. All ratings based on 208V operation.

Ground Loop: 1. Cooling capacity is based on 80.6°F db, 66.2°F wb (27/19°C) EAT and 77°F (25°C) EWT.

2. Heating capacity is based on 68°F db, 59.0°F wb (20/15°C) EAT and 32°F (0°C) EWT.

3. All ratings based on 208V operation.

AHRI Performance Data www .DaikinApplied .com 5 CAT 1116-12 • SmartSource Compact WSHP

CAT 1116-12 • SmartSource Compact WSHP 6 www .DaikinApplied .com

Features and Options

Features and Options SmartSource® Compact Vertical Water Source Heat Pumps Daikin SmartSource Compact vertical water source heat pumps (WSHPs) lead the way in small-scale, service-able design that provides commercial building contractors and facility managers with a low-cost alternative to more expensive and larger WSHPs . Readily available in-stock, Compact units are ideal for new, existing, or replace-ment jobs where space is a premium and budgets are constrained. They can be configured for boiler tower or geothermal applications that are often found in schools, offices, lodging, condominiums, and retail facilities.

Although small in size, Compact units deliver big in performance capabilities . Specifying engineers will ap-preciate all the high-performing features and options we’ve built into the Compact; EC motors with adjustable air flow settings, dehumidification, and waterside econo-mizers that typically are found only in larger WSHPs, are now fully selectable and available in this smaller pack-aged unit, and at a lower cost .

With so many performance design features and options available for Compact WSHPs, building owners can ex-pect a quiet and more comfortable environment for occu-pants, in addition to a low first-installed cost, and efficient, cost-saving operation each year that lowers energy bills .

Big Features, Small Design, Perfect Fit

6 Sound options

5 4-position fan speed selector switch (option)

1 Non-fused disconnect (option)

2 Swing-out removable control box

3 LED status sight glass

4 Slide-out fan motor & housing

Easy access to terminal connections

Dual layer insulation Compressor blanket

1 Non-fused disconnect (option)

• Convenient power shut-off and lockout at the unit

2 Swing-out removable control box

• Designed for easy access to control terminal connections and easy service access

3 LED status sight glass

• The LED status sight glass allows an instant visual of unit operation for quick troubleshooting and advanced diagnosis

4 Slide-out fan motor & housing (sizes 015-048)

• The motor and fan housing assembly slide-out along rails for easy removal and service access

5 Smart ECM fan control with 4-position switch (option)

• Quiet and efficient motors are available on all sizes.

6 Sound options

• Reduces sound levels for quieter operation

7 Smart dehumidification

• Uses hot gas reheat, humidistat & smart airflow management for humidity control (see "Hot Gas Reheat Coil" on page 7)

Hot Gas Reheat Coil For improved indoor cli-mate control, Daikin Ap-plied offers accurate and cost effective dehumidifi-cation control using a hot gas reheat option known as smart dehumidifica-tion . Hot gas reheat with smart dehumidification is an excellent solution for applications where maintaining low humidity in a space is crucial .

With smart dehumidification, once the space temperature is satisfied, the humidistat signal diverts the high tempera-ture refrigerant gas to the reheat coil located downstream of the cooling coil . The conditioned and reheated air pre-vents over cooling of the space and maximizes moisture removal for improved indoor comfort . With the optional ECM fan system, the air flow is adjusted for optimal mois-ture removal, and helps keep sound levels at a minimum .

It is especially effective during low load conditions when proper control is critical .

Hydronic Heat The hydronic heat option helps to reduce energy consumption by using warm loop water temperatures to condition a space without energizing mechanical heating .

The unit includes a hydronic heating coil located down-stream of the unit evapora-tor coil . When entering water temperatures are between 90° to 120°F, a call for heating will divert the warm water to the hydronic coil .

An optional control sequence allows compressor heating operation when the loop water is below 90° F . In this se-quence, the control system will automatically switch from compressor heating to hydronic heating based on the loop temperature . With optional ECM smart fan controls sound levels can be reduced by adjusting air flow during hydronic heat operation .

Waterside Economizer The waterside econo-mizer option helps to reduce energy con-sumption by using cold loop water temperature to condition a space without energizing mechanical cooling .

Even in the coldest weather a space can experience a build-up of ambient heat from people, equipment, lighting and the sun .

Buildings benefit from the waterside economizer when loop temperatures are cool enough to provide air conditioning .

The waterside economizer includes a hydronic cooling coil located upstream of the unit's evaporator coil . When entering water temperatures are between 40° to 70°F, a call for 1st-stage cooling will divert the cold water to the economizer coil . A call for 2nd-stage cooling will allow simultaneous compressor operation whenever the loop temperature is below the changeover temperature .

Cabinet Configurations The SmartSource compact cabinet is fabricated from heavy gauge G-60 galvanized sheet metal .

Two cabinet configurations are available in either a left-hand or right-hand return air arrangement to provide the optimum return air location and service access .

Figure 1: Two vertical unit configurations

Right-hand, top dischargeLeft-hand, top discharge

R eturn Air

Control Box Control BoxWater Connections

R et ur n

Ai r

Water Connections

Unit Front Note: Unit left or right hand is determined by facing the piping connection (front) side of unit

What our customers are saying;

‟The service guys love the design of the GCV unit, serviceability overall is excellent .”

www .DaikinApplied .com 7 CAT 1116-12 • SmartSource Compact WSHP

CAT 1116-12 • SmartSource Compact WSHP 8 www .DaikinApplied .com

Designed-in Sound Reduction Provided as standard, the unit has a unique dual-level vibration isolation system . A heavy-gauge mounting plate is isolated from the cabinet base with a 1/2" thick dense foam pad to minimize vibration transfer . The compressor is then isolated from the mounting plate with isolation grommets . The compressor is located in a well-insulated compartment separated from the air stream to minimize sound transmission .

1/2" thick foam pad

Heavy-gauge mounting plate with dual isolation grommets

Vibration isolation grommets

Cabinet Insulation Dual density 1/2" fiberglass insulation is standard on all Vertical Compact units for improved thermal and acoustic performance . The insulation meets NFPA 90A requirements, air erosion and mold growth limits of UL- 181, fungal resistance test per ASTM-C1071 and ASTM G21, and meets zero level bacteria growth per ASTM G22. All insulation has a flame spread of less than 25 and a smoke developed classification of less than 50 per ASTM E-84 and UL 723 .

IAQ Insulation (Option) Optional insulation is available with closed-cell non fibrous insulation for Indoor Air Quality (IAQ).

Closed cell foam insulation

Sound Options Sound Package Available as a factory installed option, unit sizes 024-070 utilize sound attenuating compressor blankets combined with a dual layer of fiberglass insulation that is strategi-cally placed in the air handling compartment . Unit sizes 007-019 have a dual layer of fiberglass insulation that is strategically placed in both the air handling and com-pressor compartments .

Sound Options Sound attenuating compressor blankets for unit sizes 024-070 are available . They may be ordered on non sound package units as well .

Slide-Out Fan Motor & Housing Unit sizes 015-048 provide easy fan and motor removal by sliding the fan assembly in or out along mounting rails .

A large panel provides service access to the blower and motor . All blower/motor assemblies have a removable ori-fice ring on the housing to accommodate motor and blower removal without disconnecting the unit from the ductwork .

Motor and fan assembly removed by sliding out along mounting rails

Discharge & Return Fold Out Duct Collars The standard unit discharge and return air duct collars are perforated and easily fold out for duct connection . This de-sign helps to prevent damage during shipping and handling .

Duct collars folds out along perforations www .DaikinApplied .com 9 CAT 1116-12 • SmartSource Compact WSHP

Stainless Steel Drain Pan The condensate drain pan is constructed of corrosion-resistant stainless steel . It is tilted from two directions toward the drain end using tapered foam strips on its underside that also help minimize sound transmission between the pan and partition plate . The entire bottom of the drain pan is covered with 1/4" insulated foam that helps reduce sweating . The drain pan includes an electronic condensate overflow protec-tion sensor, more reliable than a mechanical float switch used with many competitor pans .

Foam leveling and isolation strips

Fan Motors Permanent Split Capacitor Motor (PSC)

All units are equipped standard with a 3-speed PSC motor .

The motors are permanently lubricated and include thermal overload protection for years of maintenance free service . The motor is factory wired to maximize performance and efficien-cy . The motor is isolated from the fan housing using rubber isolators to minimize vibration transmission . All blower/motor assemblies have a removable orifice ring on the housing to accommodate motor and blower removal without discon-necting the unit from the ductwork .

EC Constant Torque Fan Motor (Option)

Constant Torque EC Constant Torque EC Motor Sizes 007-012 Motor Sizes 015-070

The optional constant torque EC blower motor offers increased efficiencies. This motor is similar in function to a PSC, but will deliver airflow at higher external static pres-sures . These motors are available for all sizes 007 to 070 .

Size 007 through 012 include a field adjustable 4-position fan speed selector switch . Unit sizes 015 through 070 of-fer five selectable motor speed taps. This EC motor option is an excellent choice for retrofit projects. These motors do not require a neutral wire for 460/3 electrical .

EC Constant CFM Fan Motor (Option) For unit sizes 015 – 070, the high efficiency EC constant airflow motor option provides constant airflow and eco-nomical performance over a wide static pressure range .

This motor is an ideal option for high filtration applications, utilizing an optional MERV-13 air filter. One of the many benefits of the EC motor is a soft start/stop feature for quiet operation . The 4-speed fan selector switch allows for quick fan speed adjustment to optimize unit performance .

Swing-Out Control Box With the simple removal of one screw, the swing out control box can be swung open to allow access to all internal components, or completely removed to allow complete access to all electrical and refrigeration com-ponents . Terminal control connections have never been easier to accomplish through the cut out window in the top of the control box .

Non-Fused Disconnect Switch (Option) Compact units are available with an optional non-fused disconnect switch, located on the unit front corner post .

The disconnect switch is used to break power to the unit for ease of field service and is provided with a lockout/ tag out feature .

High Efficiency Rotary or Scroll Compressor Compressors are high efficiency rotary (sizes 007-019) and scroll (sizes 024-070) designed for heat pump duty . Mounted on a dual isolation system for reduced sound and vibration .

Horizontal Rotary Vertical Rotary Scroll

Freeze Fault Protection (Option) This factory installed option adds a leaving water tem-perature (LWT) sensor to disable compressor operation to protect against coil freeze-up .

Leaving water temperature sensor

Water Pressure Differential Switch (Option) The pressure differential switch monitors water pressure drop across the heat exchanger and will disable compressor operation if flow is not detected. Selectable as a factory installed option internal to the cabinet .

2-Way Motorized Water Valve (Option) The optional, factory-installed or field-installed 2-way valve is used in variable pumping applications when more than one unit is installed on a common loop . These valves are also used to conserve water when used for ground water applications .

Two-way motorized valve option

Table 1: Available motorized valves Type Sizes Connection

2 & 3-Way Motorized 1/2", 3/4", 1" Sweat

1/2", 3/4", 1" NPT

Water Connections The water and condensate connections are FPT fittings, securely mounted flush to the corner post to allow for connection to a flexible hose without the use of a back-up wrench for easy installation .

Service Valve Connections Two service valves are located inside the lower-front access panel – one on the low side and one on the high side of the refrigeration circuit . Easily accessible for routine service .

Supply

ReturnCoaxial Heat

Exchanger www .DaikinApplied .com 10 CAT 1116-12 • SmartSource Compact WSHP

CAT 1116-12 • SmartSource Compact WSHP 11 www .DaikinApplied .com

Air-to-Refrigerant Coil The air-to-refrigerant heat exchanger has copper tubes and aluminum fins. The fins are lanced and mechanically bonded to the tubes using finned edges on the inside which expand during assembly to enhance heat transfer capabilities . The coil is designed for optimal performance in both heating and cooling while maintaining the benefit of a compact size . The coils can be coated with an optional inorganic, silicon-based nano-ceramic coating . This coating has a 3,000 hour salt spray rating per ASTM B-117 .

Coax Coil The water-to-refrigerant heat exchanger is a coaxial coil with a convoluted copper inner tube and a steel outer tube .

The convoluted tube has increased heat transfer surface area per unit length for enhanced performance . The coil is rated for 500 psig on the water side and 600 psig on the refrigerant side . An optional a cupro-nickel inner tube is available for applications with lower water quality .

Filters & Filter Racks Units come standard with a 1" thick factory-installed disposable filter, mounted in a 2-sided filter rack. The filter rack has perforations that easily fold out to form a return air duct collar. The filter is easily removed from either side .

An optional 2" deep (4-sided, low leak) filter rack is avail-able as a factory-installed selectable option to accept a MERV 8 filter. An optional 4" deep (4-sided, low leak) filter rack accepts a MERV 13 filter. These optional (low leak) racks include gaskets between the filter rack and cabinet that maintain the leakage rate below 4 CFM per square foot of filter area at .5" ESP. The 4-sided filter rack includes a removable access door with thumb screws for easy filter access and changeout without the use of a tool.

Optional 2" or 4" Deep Four-Sided, Gasketed Filter Rack

Optional 2" or 4" MERV 8 or 13 Filter

Standard 1" Disposable Filter in a 2-Sided Filter Rack

Thumb Screws for Easy Removal of Filter Access Door

LED Sight Glass The LED status sight glass allows an instant visual of unit operation for quick troubleshooting and advanced-diagnosis without removing the access panel .

LED Sight Glass for Instant Visual of Unit Operation www .DaikinApplied .com 12 CAT 1116-12 • SmartSource Compact WSHP

Fan Speed Selector Switch Available on units with EC constant torque motor (sizes 007-012) and EC constant CFM motor (sizes 015-070) .

A 4-position fan speed selector switch located in the control box allows CFM settings to be field adjustable. Fan speed control optimizes unit fan speed based on thermostat/room sensor inputs . The fan speed switch allows for manually setting an optimal fan speed specific to the application requirements. Each position on the fan speed switch repre-sents settings 1-4 . See Table 2 below and Table 10 on page 25 for a complete list of fan speed selector switch settngs .

Table 2: Single stage unit with constant CFM type EC motor - Fan speed selector switch settings example

Unit Size Setting

Maximum

ESP

(in . wg .)2

1Low CFM Heat

1High CFM Heat

1Low CFM Cool

1High CFM Cool

Fan Only Dehumidification Electric

Heat

Setting 4 (High)

1 .0

800 900 800 900 600 600 900

Setting 3 (Standard) 700 800 700 800 600 600 900

Setting 2 (Medium) 600 700 600 700 450 600 900

Setting 1 (Low) 600 600 600 600 450 600 900 Notes: 1 The unit is capable of high-low fan performance through the use of a 2-stage thermostat wired to specific terminals for High-Low CFM

2 Units are shipped at setting 3 (standard). Fan speed settings may be changed via the 4-position fan speed selector switch located inside the control box.

CAT 1116-12 • SmartSource Compact WSHP 13 www .DaikinApplied .com

Controls

Controls MicroTech® III Unit Controller The MicroTech III controller is a microprocessor-based controller and is provided on every SmartSource GCV unit .

The controller monitors the safety devices to protect the unit from unsafe operating conditions, controls the revers-ing valve, compressor and fan operation for efficient unit operation . This controller also protects against freezing of the water to refrigerant and air to refrigerant heat exchanger as well as condensate overflow.

Safety Controls included as standard:

• High pressure switch located in the refrigerant discharge line .

• Low pressure switch located in the refrigerant suction line for loss of refrigerant charge protection .

• Low suction temperature sensor located in the com-pressor suction line to protect against coil freeze-up .

• Condensate overflow protection sensor is factory mounted in the drain pan of the unit .

The controller is accessible within the electrical control box through the bottom-front access panel .

For additional information on the MicroTech III controller, see OM 1149 .

Each option features direct quick-connect wiring to all unit-controlled components for “clean” wiring inside the control box . Each control circuit board receives power from a 50 VA or optional 75 VA transformer . The main board can be wired for 24-volt AC output to the wall ther-mostat by using terminals R & C .

Built-in Diagnostics Status LED annunciator lights are located on the inte-rior of the unit, easily viewable through the sight glass to quickly check the operating status of the unit . The I/O Expansion Module has an independent LED annunciator to identify operational fault conditions .

By adding a communication module, LonWorks or BACnet, network Building Automation System (BAS) integration is possible .

Three control choices are offered with the MicroTech III SmartSource unit control system:

■ MicroTech III SmartSource unit controller (Standalone)

■ MicroTech III SmartSource unit controller with

LonWorks® communication module

■ MicroTech III SmartSource unit controller with BACnet® communication module

Controls Integration For protocol information including, integration points list for LonWorks and BACnet networks, Refer to ED 15103

MicroTech® III SmartSource Controller with LonWorks® Communication Module

Each Daikin water source heat pump can be equipped with a LonWorks communication module that is Lon- Mark 3.4 certified. The controller is microprocessor-based and is designed to communicate over a Lon- Works communications network . It can be factory or field-installed.

For installation details of the field-installed kit, "Micro- Tech III Water Source Heat Pump LonWorks Communi-cation Module", refer to IM 927 .

The unit controller is programmed and tested with all the logic required to monitor and control the unit . An optional wall sensor may be used with the communication mod-ule to provide limited local control of the Water Source Heat Pump . The unit controller monitors water and air temperatures and passes information to the communica-tion module . The module communicates with the BAS, to provide network control of the Water Source Heat Pump .

The MicroTech III SmartSource unit controller with com-munication module includes a factory installed leaving water temperature sensor, field installed discharge air and return air temperature sensor . A Daikin wall-mounted temperature sensor may be used in place of the factory provided return air temperature sensor .

http://salesportal.daikinapplied.com/bizlit/DocumentStorage/WaterSourceHeatPump/InstallationandOperationManuals/OM_1149-2_LR.pdf http://salesportal.daikinapplied.com/bizlit/DocumentStorage/Controls/ControlIntegration/ED15103-3.pdf http://salesportal.daikinapplied.com/bizlit/DocumentStorage/Controls/InstallationandOperationManuals/Daikin_IM_927-4_LR_MT_III_WSHP_Unit_Ctrlr_LonWorks_Comm_Mod_Manual.pdf

MicroTech III SmartSource Controller with BACnet® Communication Module

Daikin water source heat pumps are available with a BACnet MS/TP communication module that is designed to communicate over a BACnet MS/TP communications network to a building automation system (BAS) . It can be factory or field-installed.

For installation details of the field-installed kit, "Micro- Tech III Water Source Heat Pump LonWorks Communi-cation Module", refer to IM 928 .

The unit controller is programmed and tested with all the logic required to monitor and control the unit . An optional wall sensor may be used with the communication mod-ule to provide limited local control of the water source heat pump . The unit controller monitors water and air temperatures and passes information to the communica-tion module . The module communicates with the BAS, to provide network control of the water source heat pump .

The module makes operational data and commands available on a communications network using BACnet objects and properties:

■ The network cable is a shielded twisted-pair cable

■ Network communications run up to 76 .8 Kbps

■ DIP switches on the controller enable the MS/TP MAC address to be set in the range 0-127

■ Four green status LEDs on the communication module indicate communication activity on the MS/TP communi-cation network and with the unit controller

The MicroTech III SmartSource unit controller with com-munication module includes a factory installed leaving water temperature sensor, field installed discharge air and return air temperature sensor . A Daikin wall-mounted temperature sensor may be used in place of the factory provided return air temperature sensor .

Controls www .DaikinApplied .com 14 CAT 1116-12 • SmartSource Compact WSHP http://salesportal.daikinapplied.com/bizlit/DocumentStorage/Controls/InstallationandOperationManuals/Daikin_IM_928_LR_MT-III_WSHP_BACnet_Comm_Module_Manual.pdf

Accessories www .DaikinApplied .com 15 CAT 1116-12 • SmartSource Compact WSHP

Accessories Hoses, Hose Kits and Shutoff Ball Valves for SmartSource Water Source Heat Pumps Daikin offers a variety of flexible supply, return and condensate hoses and hose assemblies for connecting its water source heat pumps to a building's hard piping system . See catalog 1196-x for the complete hose and hose kit offering.

Figure 2: Flexible, steel braided supply and return hoses

Supply and return hoses have a swivel fitting at one end to facilitate removal of the unit for replacement or service .

Standard supply and return fire-rated hoses have either a thermoplastic rubber or synthetic polymer core with a braided covering of stainless steel . Fittings are either plated steel or brass .

Table 3: Available fire rated supply and return hoses

Description Connection Size (O .D .) Length

Supply and Return Hoses

1/2" 24"

36"

3/4" 24"

36"

1" 24"

36"

Supply and Return Hose Kits Figure 3: Supply and return hoses

Supply hose - combination ball valve & strainer The supply valve body is a combination Y-strainer full port shut-off valve and union for use in HVAC systems.

Strainers are furnished with a 20 mesh stainless steel screen, hose end drain (blow down) valve for purging, one pressure/temperature port for commissioning, and one plugged bypass port. Three additional 1/4ʺ taps are plugged and available for accessories when specified.

A variety of pipe connections are available on both the fixed and union ends. Standard end connections are female pipe thread .

Shutoff Ball Valves with Memory Stop Constructed of brass and rated at 400 psig (2758 kPa) maximum working pressure . Valves have a built-in adjustable memory stop to eliminate rebalancing . Valves have FPT connections on both ends for connection to the water hose and to the field piping.

Figure 4: Shutoff ball valve with memory stop http://salesportal.daikinapplied.com/bizlit/DocumentStorage/WaterSourceHeatPump/Catalogs/CAT_1196-11_Hose_Kits_for_WSHPs_LR.pdf

CAT 1116-12 • SmartSource Compact WSHP 16 www .DaikinApplied .com

Applications

Applications Standard Unit Typical Installation Installation & Location SmartSource vertical water source heat pumps can be installed “free standing” in an equipment room; however, closet installations are more common for the small vertical type units . Generally, the unit is located in the corner of a closet with the non-ducted return air facing 90-degrees to the door and the major access panels facing the door as shown in Figure 5 . Alternatively, the unit can have a ducted return air with the opening facing the door and the major access panels facing 90-degrees to the door .

Locate a vertical unit to allow for easy removal of the fil-ter and access panels . Allow a minimum of 24" (610 mm) clearance on the front of the unit for service and mainte-nance access . Always be sure to leave at least one side of the filter rack unobstructed so that the service person-nel will be able to slide the filter out.

To reduce noise emissions, install a field-provided isola-tor pad beneath the entire base of the vertical unit . The pad should be equal to the overall foot-print size of the unit to provide sound dampening of the unit while in operation .

Figure 5: Typical closet installation - non-ducted application

1 . Discharge air 2 . Acoustic thermal duct lining - 10 feet 3 . Low voltage wiring to unit control box 4 . Line voltage disconnect 5 . Flexible duct collar 6 . Louvered closet door 7 . Condensate drain with trap 8 . Flexible, braided, stainless steel return hose with flow controller/ball valve with port 9 . Flexible, braided, stainless steel supply hose with Y-strainer/ball valve with port 10 . Access to unit control box 11 . LED annunciator lights sight glass to view unit operation status and faults 12 . Full vibration isolation pad between unit and floor 13 . Minimum distance between return air duct collar and wall for non-ducted return applications

• Size 007-012 – 5 inches

• Size 015-024 – 5 inches

• Size 030-036 – 6 inches

• Size 042-048 – 8 inches

• Size 060-070 – 10 inches Figure 6: Vertical unit wiring & piping locations

A- Condensate (right-hand unit shown) B- Water return C- Water supply D- Line voltage unit power (right-hand unit shown) E- Low voltage control Wiring (electric entrance) www .DaikinApplied .com 17 CAT 1116-12 • SmartSource Compact WSHP

Unit With Hydronic Heat Coil Typical Installation Installation & Location When installing the Compact unit with a hydronic heat section, the same location criteria described for the stan-dard unit application apply . Although hydronic unit piping requires single inlet, outlet and a "jumper" connection as shown in Figure 7 Figure 7: Typical closet installation - with hydronic heat, non-ducted application

Hydronic Heat Coil Section

1 . Discharge air 2 . Acoustic thermal duct lining - 10 feet 3 . Low voltage wiring to unit control box 4 . Line voltage disconnect 5 . Flexible duct collar 6 . Louvered closet door 7 . Condensate drain with trap 8 . Flexible, braided, stainless steel return hose with flow controller/ball valve with port 9 . Flexible, braided, stainless steel supply hose with Y-strainer/ball valve with port to hydronic section supply 10 . Access to unit control box 11 . LED annunciator lights sight glass to view unit operation status and faults

12 . Flexible, braided, stainless steel jumper from the hy-dronic return connection to the unit supply connection

13 . Full vibration isolation pad between unit and floor Figure 8: Hydronic heat unit wiring & piping locations

Hydronic Heat Coil Section

3-way motorized valve

A- Condensate (right-hand shown) E- Low voltage - control B- Water return F- Hydronic water return C- Water supply G- Hydronic water supply D- Line voltage - unit power

Note: Figure 8 and Figure 9 show a slab type hydronic coil, as on sizes 007 through 019. Unit sizes 024 through 070 hydronic coil is an "A" configuration type.

Figure 9: Piping schematic

Note: Two valves allow for cooling and heating, V1, 3-way motor-ized valve (factory installed) and V2 (factory or field-installed option) 2-way motorized valve (no water flow through the unit when there is no call for heating or cooling).

CAT 1116-12 • SmartSource Compact WSHP 18 www .DaikinApplied .com

Ductwork and Attenuation Vertical Unit All ductwork should conform to industry standards of good practice as described in ASHRAE Systems Guide .

The discharge duct system will normally consist of a flex-ible (boot) connector at the unit, a short run of acousti-cally insulated duct (approximately 10'), an 90-degree el-bow without vanes, and a trunk duct teeing into a branch circuit with discharge diffusers as illustrated in Figure 11 .

Return air ducts can be brought in through a wall grille and then to the unit . The return duct system will normally consist of a flexible connector at the unit and a trunk duct to the return air grille . With metal duct material, the return air duct should be internally lined with acoustic insulation for sound attenuation .

Figure 10: Typical installation using ducted return

Flexible (Boot) Connector

Field Supplied Isolation Pad

Flexible (Boot) Connector

Duct piece from return air duct collar to boot Discharge Duct

Figure 11: Vertical unit duct example

Flexible (Boot) Connector

Acoustically Insulated Duct (approximately 10') 90-degree elbow

Trunk Duct

Trunk Duct Tee

Branch Duct

Branch Duct

Room Air Supply Diffuser

Room Air Supply Diffuser

Room Air Supply Diffuser www .DaikinApplied .com 19 CAT 1116-12 • SmartSource Compact WSHP

Piping The water source heat pump unit is typically connected to the supply / return piping using a “reverse return” pip-ing system which includes a flow control device so that flow requirements are met for each zone. A short, high pressure “flexible hose” is used to connect the unit to the building’s hard piping and acts as a sound attenuator for both the unit operating noise and hydronic pump-ing noise. One end of the hose has a swivel fitting to facilitate removal of the unit for replacement or service .

Include supply and return shutoff valves in the design to allow removal of a unit without the need to shut down the entire heat pump system . The return valve may be used for balancing and will typically have a “memory stop” so that it can be reopened to the proper position for the flow required. Fixed flow devices are commercially available and can be installed to eliminate the need for memory stop shut off valves. Include Pressure / Temperature ports to allow the service technician to measure water flow and unit operation.

Daikin has available optional hose kit combinations to better facilitate system flow balancing. These flexible hoses reduce vibration between the unit and the rigid piping system .

Polyolester Oil, commonly know as POE oil is a synthetic oil used in many refrigeration systems . POE oil, if ever in contact with PVC/CPVC will coat the inside wall of PVC/ CPVC pipe causing environmental stress fractures .

Although there is no PVC/CPVC piping in this product, please keep this in mind when selecting piping materials for your application, as system failure and property dam-age could result . For these reasons Daikin Applied does not recommend the use of PVC/CPVC water piping .

Figure 12: Reverse return piping system

CAT 1116-12 • SmartSource Compact WSHP 20 www .DaikinApplied .com

Water System Quality The cleaning, flushing and chemical treatment of a water source heat pump system is fundamental to efficient operation and the life expectancy of the system .

Potential system problems produced by the use of water fall into three general categories:

1 . Scale formation – Mineral deposits which result from the crystallization and precipitation of dissolved salts in the water . The deposits form an insulating barrier, reducing the heat transfer rate and impeding the circula-tion of fluids due to increased pressure drop.

2 . Corrosion – Decomposition of the metal caused by absorption of gases from the air . Corrosion may occur in any metal component of the system .

3 . Organic growths – Slime and algae which form under certain environmental conditions, and can reduce the heat transfer rate by forming an insulating coating or can promote corrosion by pitting .

The system water should be evaluated for degrees of impurity, with testing available from independent testing labs, health departments or state agencies .

Table 4 is a list of water characteristics, the potential im-purities and their results and the recommended treatment .

Avoiding Potential Problems As shown in Table 4, all water contains some degree of impurities which may affect the performance of a heat pump system . The use of a cupro-nickel coil can help avoid potential problems. Water flow rates should:

A . Be high enough that the temperature rise through the heat exchanger does not exceed 10° F when operating in the cooling mode .

B . Not exceed 4 GPM per nominal ton . Flow rates that have velocities of 10 feet per second or more may cause pipe erosion and heat exchanger failure .

Table 4: Water impurities, result & recommended water system application

Impurity Copper Coils Curpro-nickel Coils Result Application

Open Recirculating Closed Recirculating

Calcium & Magnesium Salts

(hardness)

Less than 350 ppm

350 ppm Sea Water Scaling

1. Bleed-off 2 . Surface active agents such as polyphosphates .

3 . Addition of acid .

4 . pH adjustment .

Other considerations:

▪ Adequate fouling factor

▪ Surface temperature

▪ Water temperature

▪ Clean system

No treatment required

Ironoxide Low levels only Moderate levels

Corrosion

1 . Corrosion inhibitors in high concentrations (200 to 500 ppm) .

2 . Corrosion inhibitors in low concentrations (20 to 80 ppm) .

3 . pH control .

4 . Proper materials of construction .

Corrosion inhibitors in high con-centrations .

Proper materials of construction .

pH 7 - 9 5 – 10

Hydrogen Sulfide Less than 10 ppm 10 – 50 ppm

CO2 Less than 50 ppm 50 – 75 ppm

Chloride Less than 300 ppm 300 – 600 ppm

Total Dissolved Solids

Less than 1000 ppm 1000 – 1500 ppm

Slime & Algae Slime and algae can form under certain environmental conditions

Reduced heat transfer due to forming of insulat-ing coating, or pitting due to corrosion

Chlorinated phenols .

Other biocides .

Chlorine by hypochlorites or by liquid chlorine No treatment required

Notes: 1. The tremendous variety in water quality around the country makes the recommendation of a single best method of treatment impossible. Consult a local water treatment specialist for specific treatment recommendations.

2. Cupro-Nickel is recommended if iron bacteria is present, suspended solids or dissolved oxygen levels are high.

3. If the concentration of these corrosives exceeds the maximum tabulated in the cupro-nickel column, then the potential for serious corrosion problems exists.

www .DaikinApplied .com 21 CAT 1116-12 • SmartSource Compact WSHP

Condensate Drain Vertical units have a 3/4-inch FPT condensate drain con-nection, flush to the unit. The field installed condensate piping must include a trap after the connection and be pitched away from the unit not less than 1/4" per foot .

A vent is required after the trap so that the condensate will drain away from the unit . The vent can also act as a clean out if the trap becomes clogged . To avoid having waste gases entering the building, the condensate drain should not be directly piped to a drain/waste/vent stack .

See local codes for the correct application of condensate piping to drains .

Improper trapping can lead to several problems . If the trap is too tall, negative pressure will prevent drainage, causing condensate backup . If the trap is too short the seal will be destroyed or nonexistent, producing the same effect as a non-trapped system.

Construct the trap of 7/8" clear plastic piping . The con-densate piping from the drain trap must be sloped to facilitate proper drainage . The clear plastic trap should be clamped and removable for cleaning . It may be nec-essary to manually fill the trap at system startup, or to run the unit for sufficient time to build a condensate seal.

The condensate trap and condensate piping drainage should be free of any foreign debris . Debris can prevent proper drainage and unit operation and result in conden-sate buildup .

Operating Limits Table 5: Air limits in °F (°C)

Air Limits Standard Range Units Geothermal Range Units

Cooling Heating Cooling Heating

Minimum Ambient Air1 50°F (10°C) 50°F (10°C) 40°F (4°C) 40°F (4°C)

Maximum Ambient Air2 100°F/77°F (38°C/25°C) 85°F (29°C) 100°F/77°F (38°C/25°C) 85°F (29°C)

Minimum Entering Air1 65°F/55°F (18°C/13°C) 50°F (10°C) 65°F/55°F (18°C/13°C) 50°F (10°C)

Common Design Entering Air 75°F/63°F (24°C/17°C) 70°F (21°C) 75°F/63°F (24°C/17°C) 70°F (21°C)

Maximum Entering Air2 85°F/71°F (29°C/22°C) 80°F (27°C) 85°F/71°F (29°C/22°C) 80°F (27°C)

Table 6: Fluid limits

Fluid Limits Standard Range Units Geothermal Range Units

Cooling Heating Cooling Heating

Minimum Entering Fluid 55°F (13°C)3 55°F (13°C) 30°F (-1°C) 20°F (-6°C)

Common Design Entering Fluid 85-90°F (29-32°C) 70°F (21°C) 90°F (32°C) 35-60°F (1 .5-16°C)

Maximum Entering Fluid 110°F (43°C) 90°F (32°C) 110°F (43°C) 90°F (32°C)

Minimum GPM/Ton 1 .5

Nominal GPM/Ton 3 .0

Maximum GPM/Ton 4 .0

Notes: 1 Maximum and minimum values may not be combined. If one value is at maximum or minimum, the other two conditions may not exceed the normal condition for standard units. Extended range units may combine any two maximum conditions, but not more than two, with all other conditions being normal conditions.

2 This is not a normal or continuous operating condition. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature.

3 Unit with waterside economizer option can operate in economizer cooling mode down to 40°F (4°C).

Performance Data Fan Performance - Standard PSC Motor Table 7: PSC motor CFM values (208V Operation)

Unit Size Setting Rated

Airflow External Static Pressure (in-H2O) [Dry Coil and STD Filter) (inches of water column)

.05 .10 .20 .30 .40 .45 .50 .60 .70 .80 .90 1 .0 1 .1 1 .2

High

394 388 374 350 313 291 266 215

Medium 331 329 321 302 267 244 220 Low 289 287 281 264 231 209 186

High

432 424 407 385 351 330 305 246

Medium 358 352 342 323 290 269 245

Low 317 312 300 278 245 224

High

432 424 407 385 351 330 305

Medium 358 352 342 323 290

Low 317 312 300

High

732 736 709 667 625 605 583 521 400

Medium 705 673 638 612 573 544 507 413

Low 611 599 575 543 498 468 433

High

732 736 709 667 625 605 583 521

Medium 705 673 638 612 573 544 507

Low 611 599 575 543 498 468 433

High

931 940 945 934 906 887 863 802 726 632

Medium 789 797 802 796 777 763 747 704 650 584

Low 695 706 717 714 696 682 664 618

High

1289 1270 1211 1147 1093 1069 1045 984 872

Medium 1194 1185 1140 1086 1037 1014 991 932 826

Low 1089 1079 1049 1016 980 960 936 869 755

High

1369 1359 1331 1292 1240 1209 1173 1088 980 843

Medium 1224 1221 1210 1187 1151 1126 1097 1023 924

Low 1078 1083 1084 1073 1049 1031 1009 949 859

High

1698 1695 1688 1679 1663 1652 1639 1602 1553 1490 1414 1327 1230 1126

Medium 1422 1421 1420 1419 1417 1414 1410 1396 1371 1331 1272 1187 1071

Low 1179 1191 1205 1211 1213 1212 1209 1201 1185 1154 1103 1021

High

1698 1695 1688 1679 1663 1652 1639 1602 1553 1490 1414 1327 1230 1126

Medium 1422 1421 1420 1419 1417 1414 1410 1396 1371 1331 1272 1187

Low 1179 1191 1205 1211 1213 1212 1209 1201 1185 1154

High

2265 2267 2252 2214 2156 2122 2084 2000 1909 1815 1721 1632 1551 1482

Medium 1962 1964 1957 1937 1905 1886 1864 1816 1761 1703 1642 1581 1521 1464

Low 1703 1702 1697 1687 1673 1664 1654 1629 1597 1559 1512 1458

High

2265 2267 2252 2214 2156 2122 2084 2000 1909 1815 1721

Medium 1962 1964 1957 1937 1905 1886 1864 1816 1761 1703

Low 1703 1702 1697 1687 Notes: 1. Speed adjustment is done at terminal strip on the motor. Refer to unit schematic.

2. Gray tinted areas, outside recommended operating range.

3. Refer to schematic supplied with the unit for wiring as supplied by the factory. Wire colors BK = hi, BL = med & RD = low.

CAT 1116-12 • SmartSource Compact WSHP 22 www .DaikinApplied .com

Fan Performance - Optional Constant Torque Motor (Sizes 007–012) Table 8: Constant torque motor CFM values

Unit Size Setting Function

External Static Pressure (in-H2O) [Dry Coil and STD Filter) (inches of water column) 0 .10 .15 .20 .25 .30 .35 .40 .45 .50 .55 .60 .65 .70

Setting 4

Stage 2

350 333 322 310 297 283 269 254 239 224

Setting 3 316 302 292 280 266 250 234 218

Setting 2 277 268 258 246 231 215

Setting 1 237 232 223 211

Setting 4

Stage 1

316 302 292 280 266 250 234 218

Setting 3 277 268 258 246 231 215

Setting 2 237 232 223 211

Setting 1 237 232 223 211

A Fan Only, Hydronic Heat and WSE

316 302 292 280 266 250 234 218 202 186 170 156 144 134

B 277 268 258 246 231 215 198 180 163 147 132 119 109 102

C 237 232 223 211 196 179 162 144 126 110 96 85 77 74

D* 173 173 166 155 141 126 109 92 76 62 50

Setting 4

Stage 2

398 377 367 356 344 333 321 308 295 282 268 253 238 222

Setting 3 367 348 337 326 313 300 287 272 258 243 229 214

Setting 2 331 316 305 293 279 264 249 233 217

Setting 1 292 281 271 259 244 228 212

Setting 4

Stage 1

367 348 337 326 313 300 287 272 258 243 229 214

Setting 3 331 316 305 293 279 264 249 233 217

Setting 2 292 281 271 259 244 228 212

Setting 1 292 281 271 259 244…