This document is a detailed Model Number Description guide for Trane Air-Cooled Scroll Chillers and Heat Pump Chillers. The guide provides a comprehensive breakdown of a 45-digit model number, with each digit representing specific unit characteristics such as unit type (Air-Cooled Scroll Chiller or Heat Pump Chiller), nominal tonnage (ranging from 80 to 230 tons), compressor type, voltage, manufacturing location, sound package, agency listing, refrigerant charge, communication options, and wireless connectivity. The specification allows for extensive customization across multiple technical parameters including electrical accessories, flow control, fan types, condenser fin options, heat recovery, and shipping configurations. Specifically relevant to the associated federal contract opportunity, this document provides technical specifications for a 230-ton, 460-volt chiller to be installed at the AFGSC Annex building 4565 at Barksdale Air Force Base.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 2 - Provisions and Clauses.pdf | ||
| Attachment 3 - Brand Name Class Justification.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AC-SVX004D-EN 7
Model Number Descriptions Unit Model Number Digit 1, 2, 3, 4 — Unit Model
ACSA = Air-Cooled Scroll Chiller ACXA = Air-Cooled Scroll Heat Pump Chiller
Digit 5, 6, 7 — Nominal Tonnage
080 = 80 Tons 100 = 100 Tons 120 = 120 Tons 140 = 140 Tons 160 = 160 Tons 180 = 180 Tons 200 = 200 Tons 215 = 215 Tons 230 = 230 Tons
Digit 8 — Compressor Type
2 = Scroll with Variable Volume Ratio 8 = Scroll with variable volume ratio and vapor injection
Digit 9 — Unit Voltage
A = 200V/60Hz/3 phase B = 230V/60Hz/3 phase C = 380V/60Hz/3 phase D = 400V/60Hz/3 phase E = 460V/60Hz/3 phase F = 575V/60Hz/3 phase
Digit 10 — Manufacturing Location
U = Trane Commercial Systems, Pueblo, CO USA
Digits 11, 12 — Design Sequence
** = Factory assigned
Digit 13 — Unit Sound Package
X = Standard Unit L = Superior R = Standard with Noise Reduction Request Q = Superior with Noise Reduction Request
Digit 14 — Agency Listing
E = ETL Listed/Certified to CSA/Conforms to UL C = No Agency Listing
Digit 15 — Pressure Vessel Code
X = Not Applicable C = CRN or Canada Equivalent U = ASME pressure vessel code
Digit 16 — Factory Charge
L = Refrigerant Charge R-454B M = Nitrogen Charge (R-454B Field Supplied)
Digit 17 — Auxiliary Items
X = No Auxiliary Items D = Condenser Drain Pan - HP Units Only G = Heating Water Side Reversing Valve and Drain Pans H = Heating Water Side Reversing Valve without Drain Pans
Digit 18 — Evaporator Application
N = Standard Cooling P = Low Temp Process Cooling F = Lower Temp Process Cooling C = Ice Making
Digit 19, 20 — Evaporator Type
B2 = Brazed Plate Heat Exchanger (Standard)
Digit 21 —Water Connection
X = Grooved Pipe A = Grooved Pipe + Flange Adapter
Digit 22 — Flow Switch Set Point
C = Flow Switch Setpoint 15 F = Flow Switch Setpoint 35 H = Flow Switch Setpoint 45 L = Flow Switch Setpoint 60
Digit 23 — Insulation
N = Standard 0.75 inch H = Evaporator-Only 1.25 inch humidity/low evap
Digit 24 — Unit Application
X = Standard Ambient L = Low Ambient H = High Ambient W = Wide Ambient
Digit 25 — Condenser Length
S = Standard
Digit 26 — Condenser Fin Options
M = Aluminum Microchannel C = CompleteCoat™ Microchannel R = Copper Round Tube, Aluminum Plate Fin K = Coated Copper Round Tube, Aluminum Plate Fin
Digit 27 — Fan Type
E = EC Condenser Fan Motors F = Fixed Speed Fans
Digit 28 — Compressor Starter
X = Across-the-Line Starter
Digit 29 — Incoming Unit Power Line Connection 1 = Single Point Unit Power Connection
Digit 30 — Power Line Connection Type
T = Terminal Block C = Circuit Breaker M = High Fault Rated Circuit Breaker with Energy Meter H = High Fault Rated Circuit Breaker
Digit 31 — Short Circuit Current Rating
A = Default Short Circuit Rating B = High Short Circuit Rating
Digit 32 — Electrical Accessories
X = None U = Under/Over Voltage Protection N = 20A - 115V Convenience Outlet B = Convenience Outlet and Under/Over Voltage Protection
Digit 33 — Remote Communications Options
X = None B = BACnet® Interface (MS/TP) p = BACnet Interface (IP) M = Modbus™ Interface L = LonTalk® Interface
Digit 34 — Hard Wire Communication
X = None A = Hard Wired Bundle — All
Digit 35 — Smart Flow Control
X = None T = Variable Primary Flow (Constant Delta T)
Digit 36 — Structural Options
A = Standard Unit Structure
Digit 37 — Appearance Options
X = No Appearance Options A = Architectural Louvered Panels
FA460825QC126
Attachment 1
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
1096040470C Highlight
8 AC-SVX004D-EN
Digit 38 — Unit Isolation
X = None 1 = Elastomeric Isolators
Digit 39 — Shipping Package
X = No Shipping Package F = Shipped with Fork Pocket T = Tarp Covering Full Unit
Digit 40 — Pump Package
X = No Pump Option 2 = Single Pump, High Pressure, Single VFD 4 = Dual Pump, High Pressure, Dual VFD
Digit 41 — Heat Recovery
X = No Heat Recovery P = Partial Heat Recovery
Digit 42 — Not Used
X = Selection1
Digit 43 — Special Requirement
0 = None S = Special Requirement F = Ship to Final Finisher
Digit 44 — Harmonic Filter
N = No Harmonic Filter
Digit 45 —Wireless Connectivity
X = None A = Wi-Fi B = LTE Modem C = Air-Fi D = Wi-Fi and LTE Modem E = Wi-Fi and Air-Fi F = LTE Modem and Air-Fi G = Wi-Fi, LTE Modem, and Air-Fi