Attachment 1 - Statement of Work - Generator Maintenance.docx
DOCX document 31 KB Posted
- Solicitation number
- 36C25925Q0218
About this file
This is a Statement of Work for generator maintenance services at the VA Montana Healthcare System in Fort Harrison, MT. The SOW details maintenance requirements for six emergency generators: Onan Model DQKAA, John Deere Model 125, Detroit Diesel 400RE0ZDD, Kohler Model 500ROZD4, and two Onan Models (DQDAA-1407000 and DFEG).
The contractor must provide annual maintenance including 4-hour/2-hour load bank testing at 30% nameplate capacity, fluid analysis, and fuel quality testing. Required services include fuel system maintenance, lubrication system service, cooling system maintenance, and electrical system inspections. The contractor must use genuine OEM parts and meet VHA Directive 1028, NFPA 99, and NFPA 110 requirements. This is a Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside with NAICS code 335312 and a size standard of 1,250 employees. The base period is March 1, 2025 to February 28, 2026, with four one-year options. Quotes are due February 17, 2025 by 12:00 PM Mountain Time, with questions due by February 13, 2025.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25925Q0218 0001.docx | DOCX document | |
| Attachment 2 - 852.219-75 VA Notice of Limitations on Subcontracting.docx | DOCX document | |
| 36C25925Q0218.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA Montana Healthcare System 3687 Veterans Drive, P.O. Box 1500 Ft. Harrison, MT 59636-1500
Feb 05, 2025
PROJECT
Maintenance of six Emergency Generators at Montana VA Medical Center, Fort Harrison, MT.
SCOPE OF WORK
The purpose of this project is to perform all General Maintenance per the manufacturer’s guidelines on the following diesel engine emergency electric power generators:
1.7 MEG Onan Model DQKAA 1321166
| 1 |
| 0 |
| OIL SAMPLE |
| OIL SAMPLE |
| P1-OUTSIDE2 |
| 3 |
| 0 |
| FS19763 |
| PAC, FS |
| FLG |
| 1 |
| 0 |
| ANTIFREEZE PACKAGE |
| ANTIFREEZE PACKAGE |
| P1-OUTSIDE2 |
| 75 |
| 0 |
| 33377361 |
| VALVOLINE BULK GALLON |
| P1-OTHER |
| 3 |
| 0 |
| FF5782NN |
| FILTER,FUEL |
| FLG |
| 4 |
| 0 |
| LF9050 |
| PAC, LF |
| FLG |
| 1 |
| 0 |
| DIESEL FUEL PACKAGE |
| DIESEL FUEL PACKAGE |
| P1-OUTSIDE2 |
| 1 |
| 0 |
| BACTERIA |
| BACTERIA |
| P1-OUTSIDE2 |
171 John Deere Model 125 RE0 ZJG
| 1 |
| 0 |
| BACTERIA |
| BACTERIA |
| P1-OUTSIDE2 |
| 1 |
| 0 |
| DIESEL FUEL |
| DIESEL FUEL PACKAGE |
| P1-OUTSIDE2 |
PACKAGE LF16243
PAC, LFR
FLG
| 8 |
| 0 |
| 773780 |
| 1 GAL PREM BLUE 15W40 |
| P1- |
OIL SAMPLE
OIL SAMPLE
VALVOLINE P1-OUTSIDE2
| 1 |
| 0 |
| ANTIFREEZE |
| ANTIFREEZE PACKAGE |
| P1-OUTSIDE2 |
PACKAGE
FS19976
PAC, FS
FLG
158 Detroit Diesel 400RE0ZDD Model Series 60 14.0L
| 10 |
| 0 |
| 773780 |
| 1 GAL PREM BLUE 15W40 |
| P1- |
DIESEL FUEL
DIESEL FUEL PACKAGE
VALVOLINE P1-OUTSIDE2
PACKAGE LF3620
PAC, LF
FLG
| 1 |
| 0 |
| ANTIFREEZE |
| ANTIFREEZE PACKAGE |
| P1-OUTSIDE2 |
PACKAGE FF5207
PAC, FF
FLG
| 1 |
| 0 |
| BACTERIA |
| BACTERIA |
| P1-OUTSIDE2 |
| 1 |
| 0 |
| OIL SAMPLE |
| OIL SAMPLE |
| P1-OUTSIDE2 |
| 1 |
| 0 |
| FF5206 |
| PAC, FF |
| FLG |
144B Kohler Model 500ROZD4
| 16 |
| 0 |
| 773780 |
| 1 GAL PREM BLUE 15W40 |
| P1- |
FF5037
FF PKG
VALVOLINE FLG
| 1 |
| 0 |
| BACTERIA |
| BACTERIA |
| P1-OUTSIDE2 |
| 1 |
| 0 |
| ANTIFREEZE |
| ANTIFREEZE PACKAGE |
| P1-OUTSIDE2 |
PACKAGE FS20201
FUEL FILTE
FLG
| 1 |
| 0 |
| FF5036 |
| FF PKG |
| FLG |
| 1 |
| 0 |
| OIL SAMPLE |
| OIL SAMPLE |
| P1-OUTSIDE2 |
| 2 |
| 0 |
| LF3957 |
| PAC, LF |
| FLG |
| 1 |
| 0 |
| DIESEL FUEL PACKAGE |
| DIESEL FUEL PACKAGE |
| P1-OUTSIDE2 |
155 Onan Model DQDAA-1407000
| 1 |
| 0 |
| FF5580 |
| PAC, FF (S |
| FLG |
| 1 |
| 0 |
| FS19732 |
| PAC, FS |
| FLG |
| 1 |
| 0 |
| WF2071 |
| WF PKG |
| FLG |
| 1 |
| 0 |
| BACTERIA |
| BACTERIA |
| P1-OUTSIDE2 |
| 1 |
| 0 |
| LF9009 |
| PAC, LF |
| FLG |
| 9 |
| 0 |
| 773780 |
| 1 GAL PREM BLUE 15W40 |
| P1- |
ANTIFEEZE
ANTIFREEZE PACKAGE
VALVOLINE P1-OUTSIDE2
PACKAGE
DIESEL FUEL
DIESEL FUEL PACKAGE
P1-OUTSIDE2
PACKAGE
OIL SAMPLE
OIL SAMPLE
P1-OUTSIDE2
169 Onan Model DFEG
| 1 |
| 0 |
| BACTERIA |
| BACTERIA |
| P1-OUTSIDE2 |
| 1 |
| 0 |
| FS1040 |
| PAC, FS |
| FLG |
| 1 |
| 0 |
| OIL SAMPLE |
| OIL SAMPLE |
| P1-OUTSIDE2 |
| 1 |
| 0 |
| ANTIFREEZE |
| ANTIFREEZE PACKAGE |
| P1-OUTSIDE2 |
PACKAGE
| 25 |
| 0 |
| 773780 |
| 1 GAL PREM BLUE 15W40 |
| P1- |
VALVOLINE
| 1 |
| 0 |
| DIESEL FUEL |
| DIESEL FUEL PACKAGE |
| P1-OUTSIDE2 |
PACKAGE
| 1 |
| 0 |
| LF14000-NN |
| PAC,LF |
| FLG |
The contractor shall provide all necessary labor, materials, tools and specialized equipment necessary for the full performance of this contract.
a. Load Tests (Annually):
i. Perform a full load test at a predetermined percentage of the generator's capacity for a specified duration.
ii. Monitor all critical parameters during the load test.
b. Maintenance Procedures (Annually):
i. Fuel System Maintenance:
1. Regularly check fuel levels and quality.
2. Clean fuel filters and lines as per manufacturer recommendations.
ii. Lubrication System:
1. Change engine oil and filters according to schedule.
2. Inspect and lubricate all moving parts.
iii. Cooling System:
1. Check coolant levels and composition.
2. Clean cooling system components as needed.
3. Annual air filter replacement.
iv. Electrical System:
1. Inspect generator wiring and connections for damage or corrosion.
2. Test automatic transfer switch functionality.
Maintenance should include:
· 4-hour/2-hour load bank testing*
· Fluid analysis for oil, fuel and coolant.
· Fuel Quality testing for fuel tanks supplying the emergency generators
*test must meet The Joint Commission requirements to be under load of at least 30 percent of the nameplate load.
NOTE: The Joint Commission requires a 4-hour generator test under load (dynamic or static) that is at least 30 percent of the nameplate rating of the generator once every 36 months. All material & supplies should be genuine manufacturers OEM filters, fluids, gaskets, seals, etc. Testing, maintenance, and exercising of the generator, including all related components, must be executed to meet the requirements of VHA DIRECTIVE 1028, NFPA 99 and NFPA 110, whichever is more stringent.
DELIVERABLES:
The contractor will complete Maintenance and return to service.
Documentation and Reporting:
i. Detailed maintenance logs documenting all inspections, tests, and corrective actions taken.
ii. Reporting of any identified issues, including potential safety concerns, to facility management.
iii. Maintenance reports to be submitted to the facility after services are performed.
PRIVACY STATEMENT:
Information Security: The C&A requirements do not apply; a Security Accreditation Package is not required. Incidental exposure to protected health information may occur from accessing the work site. Staff will follow all Privacy & Security policies and procedures.
image1.jpeg