FINAL AJW-2W12E APRIL 2022

FAA

Air Traffic Organization

Technical Specifications Refurbish OSW Elevator, Seattle ARTCC, Auburn, WA

Refurbish OSW Elevator April 2022 Seattle ARTCC, Auburn, WA

TABLE OF CONTENTS

SECTION SECTION TITLE

DIVISION 01 GENERAL REQUIREMENTS

01 10 00 SUMMARY

DIVISIONS 02 - 04 NOT USED

DIVISION 05 METALS

05 70 00 DECORATIVE METAL

DIVISIONS 06 - 13 NOT USED

DIVISION 14 CONVEYING EQUIPMENT

14 24 00 HYDRAULIC ELEVATORS

DIVISIONS 15 - 32 NOT USED

END OF DOCUMENT

SUMMARY 011000 - 1

SECTION 011000 - SUMMARY

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. General provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Project information.

2. Work covered by Contract Documents.

3. Contractor's use of site and premises.

4. Coordination with occupants.

5. Work restrictions.

6. Specification conventions.

7. Badging requirements.

8. Work plans.

1.3 PROJECT INFORMATION

A. Project Identification: Refurbish Operations Support Wing (OSW) Elevator.

1. Facility: Air Route Traffic Control Center (ARTCC).

2. Project Location: 3101 Auburn Way S, Auburn, WA 98092.

B. Owner: U.S. Department of Transportation, Federal Aviation Administration (FAA).

1. Owner's Representative: Contracting Officer.

1.4 WORK COVERED BY CONTRACT DOCUMENTS

A. The Work of Project is defined by the Contract Documents and includes, but is not limited to, the following:

1. Refurbish elevator to include new mechanical components; electrical components;

communications; and controls.

2. Existing car enclosures, car doors, and hoistway door panels to be retained.

B. Comply with NFPA 70 National Electrical Code and FAA-C-1217 Electrical Work, Interior.

SUMMARY 011000 - 2

1.5 CONTRACTOR'S USE OF SITE AND PREMISES

A. Limits on Use of Site: Limit use of Project site to Work in areas within the Contract limits indicated. Do not disturb portions of Project site beyond areas in which the Work is indicated.

1. Limits: Hoistway, elevator machine room, elevator landings, and connecting corridors.

2. Driveways, Walkways and Entrances: Keep driveways, loading dock, and entrances serving premises clear and available to Owner, Owner's employees, and emergency vehicles at all times. Do not use these areas for parking or for storage of materials.

a. Schedule deliveries to minimize use of driveways and entrances by construction operations.

b. Schedule deliveries to minimize space and time requirements for storage of materials and equipment on-site.

B. Condition of Existing Building: Maintain portions of existing building affected by construction operations in a weather tight condition throughout construction period. Repair damage caused by construction operations.

C. Condition of Existing Grounds: Maintain portions of existing grounds, landscaping, and hardscaping affected by construction operations throughout construction period. Repair damage caused by construction operations.

1.6 COORDINATION WITH OCCUPANTS

A. Full Owner Occupancy: Owner will occupy Project site and building(s) during entire construction period. Cooperate with Owner during construction operations to minimize conflicts and facilitate Owner usage. Perform the Work so as not to interfere with Owner's day-to-day operations. Maintain existing exits unless otherwise indicated.

1. Maintain access to existing walkways, corridors, and other adjacent occupied or used facilities. Do not close or obstruct walkways, corridors, or other occupied or used facilities without written permission from Owner.

2. Notify Owner not less than 7 days in advance of activities that will affect Owner's operations, unless otherwise indicated.

1.7 WORK RESTRICTIONS

A. Comply with restrictions on construction operations.

B. On-Site Work Hours: Limit work to between 6:00 a.m. to 4:30 p.m., Monday through Friday, unless otherwise indicated. Work hours may be modified to meet Project requirements if approved by Owner.

1. Holidays: On-site work is not permitted on holidays.

2. Moratoriums: On-site work is not permitted on the Friday before Thanksgiving through the Sunday after Thanksgiving and the Friday before Christmas through New Year’s Day.

SUMMARY 011000 - 3

C. Noise, Vibration, Dust, and Odors: Coordinate operations that may result in high levels of noise and vibration, dust, odors, or other disruption to Owner occupancy with Owner.

1. Notify Owner not less than 7 days in advance of proposed disruptive operations.

2. Limit work to between 1:00 am to 5:30 am.

D. Smoking and Controlled Substance Restrictions: Use of tobacco products, alcohol and other controlled substances on Project site is not permitted.

1. Tabaco products may only be used in designated areas.

E. Employee Identification: Owner will provide identification tags for Contractor personnel working on Project site. Require personnel to use identification tags at all times.

1. See Article for additional badging requirements.

F. Employee Screening: Comply with Owner's requirements for background screening of Contractor personnel working on Project site.

1. Maintain list of approved screened personnel with Owner's representative.

1.8 SPECIFICATION AND DRAWING CONVENTIONS

A. Specification Content: The Specifications use certain conventions for the style of language and the intended meaning of certain terms, words, and phrases when used in particular situations.

These conventions are as follows:

1. Imperative mood and streamlined language are generally used in the Specifications. The words "shall," "shall be," or "shall comply with," depending on the context, are implied where a colon (:) is used within a sentence or phrase.

2. Specification requirements are to be performed by Contractor unless specifically stated otherwise.

3. All “days” are calendar days unless otherwise indicated.

B. Division 01 General Requirements: Requirements of Sections in Division 01 apply to the Work of all Sections in the Specifications.

1.9 BADGING REQUIREMENTS

A. Application Procedures: Contract Clause 3.14-4 “Access to FAA Systems and Government- Issued Keys, Personal Identity Verification (PIV) Cards, and Vehicle Decals”.

1. Superintendent, foremen, and lead installers: Apply for PIV card to access facility and escort employees.

2. Workers: Apply for PIV card subject to Owner’s approval.

3. Allow 30 days for processing.

B. Pickup: Schedule appointment with the Owner’s security agent to receive PIV card at Project site.

SUMMARY 011000 - 4

1. Appointments Monday thru Wednesday only.

2. Pickup PIV card within 15 days of notification that the PIV card is available for pickup.

C. Visitors: Workers without PIV cards are considered visitors and will be issued a visitor badge daily. Home office personnel will not be badged but may visit Project site as visitor.

1.10 WORK PLANS

A. General: Prepare work plans for approval on any activity that could negatively affect Owner’s operations. Describe activity in detail, in a stepwise process, including daily and hourly schedules. Include mitigations for all credible risks.

B. Scheduling: Submit work plans to Owner for approval not less than 15 days before work begins.

PART 2 - PRODUCTS (Not Used)

PART 3 - EXECUTION (Not Used)

END OF SECTION 011000

DECORATIVE METALS 057000 - 1

SECTION 057000 - DECORATIVE METALS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Combination hall push-button stations.

1.3 COORDINATION

A. Coordinate installation of anchorages for decorative metal items. Furnish setting drawings, templates, and directions for installing anchorages, including sleeves, concrete inserts, anchor bolts, and items with integral anchors, that are to be embedded in concrete or masonry. Deliver such items to Project site in time for installation.

1.4 ACTION SUBMITTALS

A. Product Data: For each type of product, including finishing materials.

B. Shop Drawings: Show fabrication and installation details for decorative metal.

1. Include plans, elevations, component details, and attachment details.

2. Indicate materials and profiles of each decorative metal member, fittings, joinery, finishes, fasteners, anchorages, and accessory items.

C. Patterns, Models, or Plaster Castings: Made from proposed patterns for each design of custom casting required.

D. Samples for Initial Selection: For products involving selection of color, texture, or design.

E. Samples for Verification: For each type of exposed finish.

1. Sections of linear shapes.

2. Full-size Samples of castings and forgings.

DECORATIVE METALS 057000 - 2

1.5 INFORMATIONAL SUBMITTALS

A. Mill Certificates: Signed by manufacturers of stainless steel certifying that products furnished comply with requirements.

1.6 QUALITY ASSURANCE

A. Fabricator Qualifications: A firm experienced in producing decorative metal similar to that indicated for this Project and with a record of successful in-service performance, as well as sufficient production capacity to produce required units.

B. Installer Qualifications: Fabricator of products.

C. Organic-Coating Applicator Qualifications: A firm experienced in successfully applying organic coatings, of type indicated, to aluminum extrusions and employing competent control personnel to conduct continuing, effective quality-control program to ensure compliance with requirements.

D. Anodic Finisher Qualifications: A firm experienced in successfully applying anodic finishes of type indicated and employing competent control personnel to conduct continuing, effective quality-control program to ensure compliance with requirements.

E. Powder-Coating Applicator Qualifications: A firm experienced in successfully applying powder coatings of type indicated and employing competent control personnel to conduct continuing, effective quality-control program to ensure compliance with requirements..

1.7 DELIVERY, STORAGE, AND HANDLING

A. Store decorative metal in a well-ventilated area, away from uncured concrete and masonry, and protected from weather, moisture, soiling, abrasion, extreme temperatures, and humidity.

B. Deliver and store cast-metal products in wooden crates surrounded by enough packing material to ensure that products are not cracked or otherwise damaged.

1.8 FIELD CONDITIONS

A. Field Measurements: Verify actual locations of walls and other construction contiguous with decorative metal by field measurements before fabrication and indicate measurements on Shop Drawings.

PART 2 - PRODUCTS

2.1 DECORATIVE METAL FABRICATORS

A. Fabricator: Subject to compliance with requirements, provide products by the following

1. Otis Elevator

DECORATIVE METALS 057000 - 3

2.2 METALS, GENERAL

A. Metal Surfaces, General: Use materials with smooth, flat surfaces unless otherwise indicated.

Use materials without seam marks, roller marks, rolled trade names, stains, discolorations, or blemishes.

2.3 ALUMINUM

A. Fabricate products from alloy and temper recommended by aluminum producer and finisher for type of use and finish indicated, and with strength and durability properties for each aluminum form required not less than that of alloy and temper designated below.

B. Bars and Shapes: ASTM B221 (ASTM B221M), Alloy 6063-T5/T52.

C. Plate and Sheet: ASTM B209 (ASTM B209M), Alloy 6061-T6.

D. Forgings: ASTM B247 (ASTM B247M), Alloy 6061-T6.

E. Castings: ASTM B26/B26M, Alloy A356.0-T6.

2.4 COPPER AND COPPER ALLOYS

A. Fabricate products from alloys indicated and temper to suit application and forming methods but with strength and stiffness not less than H01 (quarter-hard) for plate, sheet, strip, and bars and H55 (light-drawn) for tube and pipe.

2.5 BRONZE

A. Extruded Shapes: ASTM B455, Alloy UNS C38500 (architectural bronze).

B. Plate, Sheet, Strip, and Bars: ASTM B36/B36M, Alloy UNS C28000 (muntz metal, 60 percent copper).

2.6 BRASS

A. Plate, Sheet, Strip, and Bars: ASTM B36/B36M, Alloy UNS C26000 (cartridge brass, 70 percent copper).

2.7 COPPER

A. Plate, Sheet, Strip, and Bars: ASTM B152/B152M, Alloy UNS C11000 (electrolytic tough pitch copper) or Alloy UNS C12200 (phosphorous deoxidized, high-residual phosphorous copper).

DECORATIVE METALS 057000 - 4

2.8 STAINLESS STEEL

A. Plate, Sheet, and Strip: ASTM A240/A240M or ASTM A666, Type 304, Type 316, or Type 316L.

2.9 MISCELLANEOUS MATERIALS

A. Welding Rods and Bare Electrodes: Select according to AWS specifications for metal alloy welded.

1. For aluminum, provide type and alloy as recommended by producer of metal to be welded and as required for color match, strength, and compatibility in fabricated items.

B. Brazing Rods: For copper alloys, provide type and alloy as recommended by producer of metal to be brazed and as required for color match, strength, and compatibility in fabricated items.

C. Etching Cleaner for Galvanized Metal: Complying with MPI#25.

D. Galvanizing Repair Paint: High-zinc-dust-content paint complying with SSPC-Paint 20 and compatible with paints specified to be used over it.

E. Lacquer for Copper Alloys: Clear, acrylic lacquer specially developed for coating copper-alloy products.

2.10 FABRICATION, GENERAL

A. Assemble items in the shop to greatest extent possible to minimize field splicing and assembly.

1. Disassemble units only as necessary for shipping and handling limitations.

2. Clearly mark units for reassembly and coordinated installation.

3. Use connections that maintain structural value of joined pieces.

B. Make up wire-rope assemblies in the shop to field-measured dimensions with fittings machine swaged.

1. Minimize amount of turnbuckle take-up used for dimensional adjustment so maximum amount is available for tensioning wire ropes.

2. Tag wire-rope assemblies and fittings to identify installation locations and orientations for coordinated installation.

C. Form decorative metal to required shapes and sizes, true to line and level with true curves and accurate angles and surfaces. Finish exposed surfaces to smooth, sharp, well-defined lines and arris.

D. Form bent-metal corners to smallest radius possible without causing grain separation or otherwise impairing the Work.

E. Form simple and compound curves in bars, pipe, tubing, and extruded shapes by bending members in jigs to produce uniform curvature for each configuration required; maintain cross

DECORATIVE METALS 057000 - 5

section of member throughout entire bend without buckling, twisting, cracking, or otherwise deforming exposed surfaces.

F. Cut, drill, and punch metals cleanly and accurately. Remove burrs and ease edges to a radius of approximately 1/32 inch (1 mm) unless otherwise indicated. Remove sharp or rough areas on exposed surfaces.

G. Mill joints to a tight, hairline fit. Cope or miter corner joints. Fabricate connections that will be exposed to weather in a manner to exclude water.

H. Provide weep holes where water may accumulate. Locate weep holes in inconspicuous locations.

I. Provide necessary rebates, lugs, and brackets to assemble units and to attach to other work. Cut, reinforce, drill, and tap as needed to receive finish hardware, screws, and similar items unless otherwise indicated.

J. Provide castings that are sound and free of warp, cracks, blowholes, or other defects that impair strength or appearance. Grind, wire brush, sandblast, and buff castings to remove seams, gate marks, casting flash, and other casting marks.

2.11 FABRICATION OF DECORATIVE WINDOW SECURITY BARS

A. Fabricate decorative window grilles to designs indicated from steel bars and shapes of sizes and profiles indicated. Form steel bars by bending, forging, coping, mitering, and welding.

B. Welding: Interconnect grille members with full-length, full-penetration welds unless otherwise indicated. Use welding method that is appropriate for metal and finish indicated and that develops full strength of members joined. Finish exposed welds and surfaces smooth, flush, and blended to match adjoining surfaces.

C. Brackets, Fittings, and Anchors: Provide wall brackets, fittings, and anchors to connect decorative window grilles to other work unless otherwise indicated.

1. Furnish inserts and other anchorage devices to connect decorative window grilles to concrete and masonry work. Coordinate anchorage devices with supporting structure.

2. Fabricate anchorage devices that are capable of withstanding loads indicated.

2.12 FABRICATION OF COMBINATION HALL PUSH-BUTTON STATIONS

A. Fabricate units of stainless steel to comply with details indicated. Coordinate with elevator signal equipment to provide integrated, closely fitted assemblies.

1. Fabricate faceplates from 1/8-inch- (3.2-mm-) thick sheet with edges beveled at a 45-degree angle for one-half thickness of metal.

2. Provide units with rectangular, split-bowl trash receptacle, designed for recess mounting in nominal 4-inch (100-mm) wall depth. Fabricate recessed cabinets, top rings, and split bowls of same metal as face of units; fabricate removable receptacles of drawn

DECORATIVE METALS 057000 - 6

aluminum. Nominal dimensions of units are 10 by 10 by 3-1/2 inches (250 by 250 by 90

mm) in depth.

3. Provide units with emergency pictorial signs and text, complying with requirements of authorities having jurisdiction, indicating that in fire emergency, elevators should not be used and that stairways should be used instead. Engrave pictorial sign and text into front surface of faceplates to a depth of 1/16 inch (1.6 mm) with engraving painted red. Make signs 5 inches (125 mm) wide by 8 inches (200 mm) high.

4. Provide cutouts in faceplates of units for push buttons of elevator hall push-button station, card reader, and elevator key switches. Coordinate locations and sizes of cutouts so additional faceplate is not required and so faces of push buttons are flush with fronts of faceplates and key switches project beyond faceplate only by depth of bezels.

2.13 FINISHES, GENERAL

A. Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes.

B. Protect mechanical finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.

2.14 STAINLESS STEEL FINISHES

A. Surface Preparation: Remove tool and die marks and stretch lines, or blend into finish.

B. Polished Finishes: Grind and polish surfaces to produce uniform finish, free of cross scratches.

1. Run grain of directional finishes with long dimension of each piece.

C. Stainless Steel Tubing Finishes:

1. 180-Grit Polished Finish: Uniform, directionally textured finish.

2. 320-Grit Polished Finish: Oil-ground, uniform, fine, directionally textured finish.

3. Polished and Buffed Finish: 320-grit finish followed by buffing to a high luster finish.

D. Stainless Steel Sheet and Plate Finishes:

1. Bright, Cold-Rolled, Unpolished Finish: ASTM A480/ASTM A480M, No. 2B.

2. Directional Satin Finish: ASTM A480/ASTM A480M, No. 4.

3. Dull Satin Finish: ASTM A480/ASTM A480M, No. 6.

4. High Luster Finish: ASTM A480/ASTM A480M, No. 7.

5. Mirror Finish: ASTM A480/ASTM A480M, No. 8.

E. When polishing is completed, passivate and rinse surfaces. Remove embedded foreign matter and leave surfaces chemically clean.

F. Sputter-Coated Finish: Titanium nitride coating deposited by magnetic sputter-coating process over indicated mechanical finish.

G. Colored, Oxide-Film Finish: Clear, oxide interference film produced by degreasing and then immersing in a mixture of chromic and sulfuric acids.

DECORATIVE METALS 057000 - 7

1. Product: Subject to compliance with requirements, provide INCO colored stainless steel finish as developed and licensed by International Nickel Co., Ltd.

2. Color: As selected by Architect from finisher's full range.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates and conditions, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of decorative metal.

B. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 INSTALLATION, GENERAL

A. Provide anchorage devices and fasteners where needed to secure decorative metal to in-place construction.

B. Perform cutting, drilling, and fitting required to install decorative metal. Set products accurately in location, alignment, and elevation, measured from established lines and levels. Provide temporary bracing or anchors in formwork for items to be built into concrete, masonry, or similar construction.

C. Fit exposed connections accurately together to form tight, hairline joints or, where indicated, uniform reveals and spaces for sealants and joint fillers. Where cutting, welding, and grinding are required for proper shop fitting and jointing of decorative metal, restore finishes to eliminate evidence of such corrective work.

D. Do not cut or abrade finishes that cannot be completely restored in the field. Return items with such finishes to the shop for required alterations, followed by complete refinishing, or provide new units as required.

E. Install concealed gaskets, joint fillers, insulation, and flashings as work progresses.

F. Restore protective coverings that have been damaged during shipment or installation. Remove protective coverings only when there is no possibility of damage from other work yet to be performed at same location.

1. Retain protective coverings intact; remove coverings simultaneously from similarly finished items to preclude nonuniform oxidation and discoloration.

G. Field Welding: Comply with applicable AWS specification for procedures of manual shielded metal arc welding and requirements for welding and for finishing welded connections in "Fabrication, General" Article. Weld connections that are not to be left as exposed joints but cannot be shop welded because of shipping size limitations.

H. Field Brazing: Comply with requirements for brazing and for finishing brazed connections in "Fabrication, General" Article. Braze connections that are not to be left as exposed joints but cannot be shop brazed because of shipping size limitations.

DECORATIVE METALS 057000 - 8

I. Control of Corrosion: Prevent galvanic action and other forms of corrosion by insulating metals and other materials from direct contact with incompatible materials.

1. Coat concealed surfaces of aluminum that will be in contact with grout, concrete, masonry, wood, or dissimilar metals, with a heavy coat of bituminous paint.

3.3 INSTALLATION OF COMBINATION HALL PUSH-BUTTON STATIONS

A. Coordinate installation of combination hall push-button stations with installation of related elevator signal equipment components. Secure units in place with faceplate overlapping surrounding wall finish and drawn into contact with surrounding wall finish at entire perimeter of faceplate.

3.4 CLEANING AND PROTECTION

A. Unless otherwise indicated, clean metals by washing thoroughly with clean water and soap, rinsing with clean water, and drying with soft cloths.

B. Clean copper alloys according to metal finisher's written instructions in a manner that leaves an undamaged and uniform finish matching approved Sample.

C. Touchup Painting: Immediately after erection, clean field welds, bolted connections, and abraded areas of shop paint and paint exposed areas with same material as used for shop painting to comply with SSPC-PA 1 for touching up shop-painted surfaces.

1. Apply by brush or spray to provide a minimum 2.0-mil (0.05-mm) dry film thickness.

D. Galvanized Surfaces: Clean field welds, bolted connections, and abraded areas and repair galvanizing to comply with ASTM A780/A780M.

E. Protect finishes of decorative metal from damage during construction period with temporary protective coverings approved by decorative metal fabricator. Remove protective covering at time of Substantial Completion.

F. Restore finishes damaged during installation and construction period so no evidence remains of correction work. Return items that cannot be refinished in the field to the shop; make required alterations and refinish entire unit, or provide new units.

END OF SECTION 057000

HYDRAULIC ELEVATORS 142400 - 1

SECTION 142400 - HYDRAULIC ELEVATORS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Scope of Work – Elevator refurbishment:

1. Scope of work includes the following equipment to be installed new in order to refurbish the current elevator installation:

a. Hydraulic pumping unit, including reservoir, valve, motor and pump

b. Machine room oil shut-off valve

c. Solid-state motor-starter

d. Operation and control system

e. Seismic operation rupture valve and retainer plate

f. Emergency service system

g. Hoistway access switches

h. Inspection run station

i. Communications equipment, including hands-free ADA cab phone

j. Car position indicator

k. Emergency lighting system

l. Hall button stations

m. Door rollers

n. Car door operators

o. Door clutch

p. Door protection

q. Hoistway limit switches

r. Traveling cables

2. The car guides shall be rebuilt.

3. All other equipment associated with the elevator is to be retained as is.

B. Section includes:

1. Hydraulic passenger elevators.

C. Related Requirements:

HYDRAULIC ELEVATORS 142400 - 2

1. Section 057000 "Decorative Metal" for combination hall push-button stations.

1.3 DEFINITIONS

A. Definitions in ASME A17.1/CSA B44 apply to work of this Section.

B. Service Elevator: A passenger elevator that is also used to carry freight.

1.4 ACTION SUBMITTALS

A. Product Data: Include capacities, sizes, performances, operations, safety features, finishes, and similar information. Include product data for car enclosures; hoistway entrances; and operation, control, and signal systems as necessary.

B. Shop Drawings:

1. Include plans, elevations, sections, and large-scale details indicating service at each landing; machine room layout; coordination with building structure; relationships with other construction; and locations of equipment.

2. Include large-scale layout of car-control station.

3. Indicate maximum dynamic and static loads imposed on building structure at points of support as well as maximum and average power demands.

C. Samples for Initial Selection: For finishes involving color selection.

1.5 INFORMATIONAL SUBMITTALS

A. Qualification Data: For Installer.

B. Seismic Qualification Certificates: For elevator equipment, accessories, and components, from manufacturer.

1. Basis for Certification: Indicate whether withstand certification is based on actual test of assembled components or on calculation.

2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions.

3. Detailed description of equipment anchorage devices on which the certification is based and their installation requirements.

C. Manufacturer Certificates: Signed by elevator manufacturer, certifying that hoistway, pit, and machine room layout and dimensions, as shown on Drawings, and electrical service including standby-power generator, as shown and specified, are adequate for elevator system being provided.

D. Sample Warranty: For special warranty.

HYDRAULIC ELEVATORS 142400 - 3

1.6 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For elevators to include in emergency, operation, and maintenance manuals.

1. Submit manufacturer's/installer's standard operation and maintenance manual, in accordance with ASME A17.1/CSA B44 including diagnostic and repair information available to manufacturer's and Installer's maintenance personnel.

B. Inspection and Acceptance Certificates and Operating Permits: As required by authorities having jurisdiction for normal, unrestricted elevator use.

C. Continuing Maintenance Proposal: Submit a continuing maintenance proposal from Installer to Owner, in the form of a standard one-year maintenance agreement, starting on date initial maintenance service is concluded. State services, obligations, conditions, and terms for agreement period and for future renewal options.

D. Continuing Maintenance Proposal: Submit a continuing maintenance proposal from Installer to Owner with terms, conditions, and obligations as set forth in, and in same form as, "Draft of Elevator Maintenance Agreement" at end of this Section, starting on date initial maintenance service is concluded.

1.7 QUALITY ASSURANCE

A. Installer Qualifications: Elevator manufacturer or an authorized representative who is trained and approved by manufacturer.

1.8 DELIVERY, STORAGE, AND HANDLING

A. Deliver, store, and handle materials, components and equipment in manufacturer's protective packaging. Store materials, components, and equipment off of ground, under cover, and in a dry location.

1.9 COORDINATION

A. Coordinate installation of sleeves, block outs, elevator equipment with integral anchors, and other items that are embedded in concrete or masonry for elevator equipment. Furnish templates, sleeves, elevator equipment with integral anchors, and installation instructions and deliver to Project site in time for installation.

B. Coordinate locations and dimensions of other work specified in other Sections that relates to hydraulic elevators, including pit ladders; sumps and floor drains in pits; entrance subsills;

electrical service; and electrical outlets, lights, and switches in hoistways, pits, and machine rooms.

HYDRAULIC ELEVATORS 142400 - 4

1.10 WARRANTY

A. Manufacturer's Special Warranty: Manufacturer agrees to repair, restore, or replace elevator work that fails in materials or workmanship within specified warranty period.

1. Failures include, but are not limited to, operation or control system failure, including excessive malfunctions; performances below specified ratings; excessive wear; unusual deterioration or aging of materials or finishes; unsafe conditions; need for excessive maintenance; abnormal noise or vibration; and similar unusual, unexpected, and unsatisfactory conditions.

2. Warranty Period: One (1) year from date of Substantial Completion.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Source Limitations: Obtain elevator equipment from single manufacturer.

1. Major elevator components, including pump-and-tank units, plunger-cylinder assemblies, controllers, signal fixtures, door operators, car frames, cars, and entrances, shall be manufactured by single manufacturer.

2.2 PERFORMANCE REQUIREMENTS

A. Regulatory Requirements: Comply with ASME A17.1/CSA B44.

B. Accessibility Requirements: Comply with Section 407 in the United States Access Board's ADA-ABA Accessibility Guidelines and with ICC A117.1.

C. Seismic Performance: Elevator system shall withstand the effects of earthquake motions determined according to ASCE/SEI 7 and shall comply with elevator seismic requirements in

ASME A17.1/CSA B44.

1. The term "withstand" means "the system will remain in place without separation of any parts when subjected to the seismic forces specified and the system will be fully operational after the seismic event."

2. Project Seismic Design Category: D

3. Elevator Component Importance Factor: 1.0.

4. Design earthquake spectral response acceleration short period (Sds) for Project is 0.832g.

5. Provide earthquake equipment required by ASME A17.1/CSA B44.

2.3 ELEVATORS

A. Elevator System, General: Manufacturer's standard elevator systems. Unless otherwise indicated, manufacturers' standard components shall be used, as included in standard elevator systems and as required for complete system.

HYDRAULIC ELEVATORS 142400 - 5

B. Elevator Description:

1. Group Number: Single elevator, not operating in a group

2. Emergency Elevator Number(s): N/A

3. Service Elevator Number(s): N/A

4. Type: Hydraulic

5. Under-the-car single in-ground cylinder.

6. Rated Load: 3500 lb (1589 kg)

7. Freight Loading Class for Service Elevators: N/A

8. Rated Speed: 100 fpm

9. Operation System: Single automatic operation

10. Auxiliary Operations:

a. Standby-power operation.

b. Standby-powered lowering.

c. Battery-powered lowering.

d. Automatic dispatching of loaded car.

e. Nuisance call cancel.

f. Loaded-car bypass.

g. Automatic operation of lights and ventilation fans.

11. Car Enclosures:

a. Existing elevator car enclosures to be retained

12. Hoistway Entrances:

a. Existing hoistway entrances to be retained

13. Hall Fixtures: Polished stainless steel, ASTM A480/A480M, No. 8 finish.

14. Additional Requirements:

a. Provide inspection certificate in each car, mounted under acrylic cover with frame made from polished stainless steel, ASTM A480/A480M, No. 8 finish.

b. Provide hooks for protective pads in all cars and one complete set(s) of full-height protective pads.

2.4 SYSTEMS AND COMPONENTS

A. Pump Units: Positive-displacement type with a maximum of 10 percent variation between no load and full load and with minimum pulsations.

1. Pump shall be submersible type with submersible squirrel-cage induction motor, and shall be suspended inside oil tank from vibration isolation mounts or shall be tank-top-mounted type with fan-cooled, squirrel-cage induction motor, and shall be mounted on oil tank with vibration isolation mounts and enclosed in prime-painted steel enclosure lined with 1-inch- (25-mm-) thick, glass-fiber insulation board.

2. Motor shall have solid-state starting.

HYDRAULIC ELEVATORS 142400 - 6

B. Hydraulic Silencers: System shall have hydraulic silencer containing pulsation-absorbing material in blowout-proof housing at pump unit.

C. Piping: Size, type, and weight of piping as recommended by elevator manufacturer, with flexible connectors to minimize sound and vibration transmissions from power unit.

1. Cylinder units shall be connected with dielectric couplings.

2. Casing for Underground Piping: Schedule 40 PVC pipe complying with ASTM D1785, joined with PVC fittings complying with ASTM D2466 and solvent cement complying with ASTM D2564.

D. Hydraulic Fluid: Nontoxic, biodegradable fire-resistant fluid, made from vegetable oil with antioxidant, anticorrosive, antifoaming, and metal-passivating additives, that is approved by elevator manufacturer for use with elevator equipment.

E. Inserts: Furnish required concrete and masonry inserts and similar anchorage devices for installing guide rails, machinery, and other components of elevator work. Device installation is specified in another Section.

F. Guides: Existing car guides to be retained.

2.5 OPERATION SYSTEMS

A. Provide manufacturer's standard microprocessor operation system as required to provide type of operation indicated.

B. Auxiliary Operations:

1. Single-Car Standby-Power Operation: On activation of standby power, car is returned to a designated floor and parked with doors open. Car can be manually put in service on standby power, either for return operation or for regular operation, by switches in control panel located at Elevator Machinery Room. Manual operation causes automatic operation to cease.

2. Single-Car Standby-Powered Lowering:

a. On activation of standby power, car is lowered to the lowest floor, opens its doors, and shuts down.

3. Single-Car Battery-Powered Lowering:

a. When power fails, car is lowered to the lowest floor, opens its doors, and shuts down. System includes rechargeable battery and automatic recharging system.

4. Automatic Dispatching of Loaded Car: When car load exceeds 80 percent of rated capacity, doors start closing.

5. Nuisance Call Cancel: When car calls exceed a preset number while car load is less than a predetermined weight, all car calls are canceled. Preset number of calls can be adjusted.

HYDRAULIC ELEVATORS 142400 - 7

6. Automatic Operation of Lights and Fan: When elevator is stopped and unoccupied with doors closed, lighting, ventilation fan, and cab displays are de-energized after 5 minutes and are re-energized before car doors open.

7. Keyswitch Operation: Push buttons are activated and deactivated by security keyswitches at car-control stations and hall push-button stations.

8. Car-to-Lobby Feature: Feature, activated by keyswitch at main lobby, which causes car to return immediately to lobby and open doors for inspection. On deactivation by keyswitch, calls registered before keyswitch activation are completed and normal operation is resumed.

2.6 DOOR-REOPENING DEVICES

A. Infrared Array: Provide door-reopening device with uniform array of 36 or more microprocessor-controlled, infrared light beams projecting across car entrance. Interruption of one or more light beams shall cause doors to stop and reopen.

B. Nudging Feature: After car doors are prevented from closing for predetermined adjustable time, through activating door-reopening device, a loud buzzer shall sound and doors shall begin to close at reduced kinetic energy.

2.7 CAR ENCLOSURES

A. Existing car enclosures, car doors, and hoistway door panels to be retained.

B. Car lighting and ventilation:

1. Light Fixture Efficiency: Not less than 35 lumens/W.

2. Ventilation Fan Efficiency: Not less than 3.0 cfm/W (1.4 L/s per W

2.8 HOISTWAY ENTRANCES

A. Existing Hoistway Entrance Assemblies to be retained.

2.9 SIGNAL EQUIPMENT

A. Provide hall-call and car-call buttons that light when activated and remain lit until call has been fulfilled. Provide buttons and lighted elements illuminated with LEDs.

B. Car-Control Stations: Provide manufacturer's standard recessed or semirecessed car-control stations. Mount in return panel adjacent to car door unless otherwise indicated.

1. Mark buttons and switches for required use or function. Use both tactile symbols and Braille.

2. Provide "No Smoking" sign matching car-control station, either integral with car-control station or mounted adjacent to it, with text and graphics as required by authorities having jurisdiction.

HYDRAULIC ELEVATORS 142400 - 8

C. Emergency Communication System: Two-way voice communication system, with visible signal, which dials preprogrammed number of monitoring station and does not require handset use. System is contained in flush-mounted cabinet, with identification, instructions for use, and battery backup power supply.

D. Car Position Indicator: Provide illuminated, digital-type car position indicator, located above car door or above car-control station. Also, provide audible signal to indicate to passengers that car is either stopping at or passing each of the floors served. Include travel direction arrows if not provided in car-control station.

E. Hall Push-Button Stations: Provide one hall push-button station at each landing.

1. Provide manufacturer's standard wall-mounted units.

2. Equip units with buttons for calling elevator and for indicating applicable direction of travel.

3. Provide telephone jack in each unit for firefighters' two-way telephone communication service.

F. Hall Lanterns: Units with illuminated arrows; however, provide single arrow at terminal landings. Provide the following:

1. Manufacturer's standard wall-mounted units, for mounting above entrance frames.

G. Hall Annunciator: With each hall lantern, provide audible signals indicating car arrival and direction of travel. Signals sound once for up and twice for down.

1. At manufacturer's option, audible signals may be placed on cars.

H. Standby-Power Elevator Selector Switches: Provide switches, as required by ASME A17.1/CSA B44, where indicated. Adjacent to switches, provide illuminated signal that indicates when normal power supply has failed. For each elevator, provide illuminated signals that indicate when they are operational and when they are at the designated emergency return level with doors open.

I. Fire-Command-Center Annunciator Panel: Provide panel containing illuminated position indicators for each elevator, clearly labeled with elevator designation; include illuminated signal that indicates when elevator is operational and when it is at the designated emergency return level with doors open. Provide standby-power elevator selector switch(es), as required by ASME A17.1/CSA B44, adjacent to position indicators. Provide illuminated signal that indicates when normal power supply has failed.

J. Emergency Pictorial Signs: Fabricate from materials matching hall push-button stations, with text and graphics as required by authorities having jurisdiction, indicating that in case of fire, elevators are out of service and exits should be used instead. Provide one sign at each hall push-button station unless otherwise indicated.

2.10 FINISH MATERIALS

A. Cold-Rolled Steel Sheet: ASTM A1008/A1008M, commercial steel, Type B, exposed, matte finish.

HYDRAULIC ELEVATORS 142400 - 9

B. Hot-Rolled Steel Sheet: ASTM A1011/A1011M, commercial steel, Type B, pickled.

C. Stainless Steel Sheet: ASTM A240/A240M, Type 304.

D. Textured Stainless Steel Sheet: ASTM A240/A240M, Type 304, with embossed texture rolled into exposed surface.

E. Stainless Steel Bars: ASTM A276, Type 304.

F. Stainless Steel Tubing: ASTM A554, Grade MT 304.

G. Bronze Plate and Sheet: ASTM B36/B36M, Alloy UNS No. C28000 (muntz metal).

H. Bronze Extrusions: ASTM B455, Alloy UNS No. C38500 (architectural bronze).

I. Bronze Tubing: ASTM B135 (ASTM B135M), Alloy UNS No. C23000 (red brass, 85 percent copper).

J. Aluminum Extrusions: ASTM B221 (ASTM B221M), Alloy 6063.

K. Nickel Silver Extrusions: ASTM B151/B151M, Alloy UNS No. C74500 or No. C77600.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine elevator areas, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of the Work. Verify critical dimensions and examine supporting structure and other conditions under which elevator work is to be installed.

B. Prepare written report, endorsed by Installer, listing conditions detrimental to performance of the Work.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Excavation for Cylinder: Not required as existing cylinder will be retained.

B. Welded Construction: Provide welded connections for installing elevator work where bolted connections are not required for subsequent removal or for normal operation, adjustment, inspection, maintenance, and replacement of worn parts. Comply with AWS workmanship and welding operator qualification standards.

C. Sound Isolation: Mount rotating and vibrating equipment on vibration-isolating mounts to minimize vibration transmission to structure and structure-borne noise due to elevator system.

D. Install piping above the floor, where possible. Install underground piping in casing.

HYDRAULIC ELEVATORS 142400 - 10

E. Lubricate operating parts of systems as recommended by manufacturers.

F. Alignment: Coordinate installation of hoistway entrances with installation of elevator guide rails for accurate alignment of entrances with car. Where possible, delay installation of sills and frames until car is operable in shaft. Reduce clearances to minimum, safe, workable dimension at each landing.

G. Leveling Tolerance: 1/4 inch (6 mm), up or down, regardless of load and travel direction.

H. Set sills flush with finished floor surface at landing. Fill space under sill solidly with nonshrink, nonmetallic grout.

I. Locate hall signal equipment for elevators as follows unless otherwise indicated:

1. Retain existing hall lanterns.

3.3 FIELD QUALITY CONTROL

A. Acceptance Testing: On completion of elevator installation and before permitting elevator use (either temporary or permanent), perform acceptance tests as required and recommended by ASME A17.1/CSA B44 and by governing regulations and agencies.

B. Advise Owner, Architect, and authorities having jurisdiction in advance of dates and times that tests are to be performed on elevators.

3.4 PROTECTION

A. Temporary Use: Comply with the following requirements for elevator used for construction purposes:

1. Provide car with temporary enclosure, either within finished car or in place of finished car, to protect finishes from damage.

2. Provide strippable protective film on entrance and car doors and frames.

3. Provide padded wood bumpers on entrance door frames covering jambs and frame faces.

4. Provide other protective coverings, barriers, devices, signs, and procedures as needed to protect elevator and elevator equipment.

5. Do not load elevators beyond their rated weight capacity.

6. Engage elevator Installer to provide full maintenance service. Include preventive maintenance, repair or replacement of worn or defective components, lubrication, cleanup, and adjustment as necessary for proper elevator operation at rated speed and capacity. Provide parts and supplies same as those used in the manufacture and installation of original equipment.

7. Engage elevator Installer to restore damaged work, if any, so no evidence remains of correction. Return items that cannot be refinished in the field to the shop, make required repairs and refinish entire unit, or provide new units as required.

HYDRAULIC ELEVATORS 142400 - 11

3.5 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to operate and maintain elevator(s).

B. Check operation of elevator with Owner's personnel present before date of Substantial Completion and again not more than one month before end of warranty period. Determine that operation systems and devices are functioning properly.

3.6 MAINTENANCE

A. Initial Maintenance Service: Beginning at Substantial Completion, maintenance service shall include 12 months' full maintenance by skilled employees of elevator Installer. Include monthly preventive maintenance, repair or replacement of worn or defective components, lubrication, cleaning, and adjusting as required for proper elevator operation. Parts and supplies shall be manufacturer's authorized replacement parts and supplies.

1. Perform maintenance during normal working hours.

2. Perform emergency callback service during normal working hours with response time of two hours or less.

END OF SECTION 142400

Cover Sheet
Table of Contents
011000 - Summary
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. General provisions of the Contract, including General and Supplementary Conditions, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Project information.
2. Work covered by Contract Documents.
3. Contractor's use of site and premises.
4. Coordination with occupants.
5. Work restrictions.
6. Specification conventions.
7. Badging requirements.
8. Work plans.
1.3 PROJECT INFORMATION
A. Project Identification: Refurbish Operations Support Wing (OSW) Elevator.
1. Facility: Air Route Traffic Control Center (ARTCC).
2. Project Location: 3101 Auburn Way S, Auburn, WA 98092.
B. Owner: U.S. Department of Transportation, Federal Aviation Administration (FAA).
1. Owner's Representative: Contracting Officer.
1.4 WORK COVERED BY CONTRACT DOCUMENTS
A. The Work of Project is defined by the Contract Documents and includes, but is not limited to, the following:
1. Refurbish elevator to include new mechanical components; electrical components; communications; and controls.
2. Existing car enclosures, car doors, and hoistway door panels to be retained.

B. Comply with NFPA 70 National Electrical Code and FAA-C-1217 Electrical Work, Interior.

1.5 CONTRACTOR'S USE OF SITE AND PREMISES
A. Limits on Use of Site: Limit use of Project site to Work in areas within the Contract limits indicated. Do not disturb portions of Project site beyond areas in which the Work is indicated.
1. Limits: Hoistway, elevator machine room, elevator landings, and connecting corridors.
2. Driveways, Walkways and Entrances: Keep driveways, loading dock, and entrances serving premises clear and available to Owner, Owner's employees, and emergency vehicles at all times. Do not use these areas for parking or for storage of materials.
a. Schedule deliveries to minimize use of driveways and entrances by construction operations.
b. Schedule deliveries to minimize space and time requirements for storage of materials and equipment on-site.
B. Condition of Existing Building: Maintain portions of existing building affected by construction operations in a weather tight condition throughout construction period. Repair damage caused by construction operations.
C. Condition of Existing Grounds: Maintain portions of existing grounds, landscaping, and hardscaping affected by construction operations throughout construction period. Repair damage caused by construction operations.
1.6 COORDINATION WITH OCCUPANTS
A. Full Owner Occupancy: Owner will occupy Project site and building(s) during entire construction period. Cooperate with Owner during construction operations to minimize conflicts and facilitate Owner usage. Perform the Work so as not to interfere wi...
1. Maintain access to existing walkways, corridors, and other adjacent occupied or used facilities. Do not close or obstruct walkways, corridors, or other occupied or used facilities without written permission from Owner.
2. Notify Owner not less than 7 days in advance of activities that will affect Owner's operations, unless otherwise indicated.
1.7 WORK RESTRICTIONS
A. Comply with restrictions on construction operations.
B. On-Site Work Hours: Limit work to between 6:00 a.m. to 4:30 p.m., Monday through Friday, unless otherwise indicated. Work hours may be modified to meet Project requirements if approved by Owner.
1. Holidays: On-site work is not permitted on holidays.
2. Moratoriums: On-site work is not permitted on the Friday before Thanksgiving through the Sunday after Thanksgiving and the Friday before Christmas through New Year’s Day.
C. Noise, Vibration, Dust, and Odors: Coordinate operations that may result in high levels of noise and vibration, dust, odors, or other disruption to Owner occupancy with Owner.
1. Notify Owner not less than 7 days in advance of proposed disruptive operations.
2. Limit work to between 1:00 am to 5:30 am.
D. Smoking and Controlled Substance Restrictions: Use of tobacco products, alcohol and other controlled substances on Project site is not permitted.
1. Tabaco products may only be used in designated areas.
E. Employee Identification: Owner will provide identification tags for Contractor personnel working on Project site. Require personnel to use identification tags at all times.
1. See Article for additional badging requirements.
F. Employee Screening: Comply with Owner's requirements for background screening of Contractor personnel working on Project site.